Eternity Technologies vented lead-acid batteries for the standby power market. Eternity Technologies OPzS batteries have optimised design resulting in a low maintenance, reliable energy storage solution for critical and unstable conditions.
4 OPzS-ET 200(2V 225Ah @ 10hr)
Nominal Voltage 2VNumber of cells 1Design Life 20 years
Nominal Capacity 20°C (68°F)10 hour rate (22.5A, 1.8V) 225Ah5 hour rate (41A, 1.75V) 205Ah1 hour rate (127A, 1.6V) 127Ah
Internal ResistanceFully Charged Battery 20°C (68°F) 0.89mOhm
ElectrolyteNominal S.G at 20°C = 1.240kg/l
Operating Temperature Range -20°C to +55°C
Maximum Discharge Current 20°C (68°F) 373A
Charge Methods: Constant Voltage Charge 20°C (68°F)Cycle use 2.40V (time limited) Maximum charging current 90AStandby use 2.25V ± 1% Temperature compensation -3.0mV/°C/Cell Terminal torque 23Nm
Performance characteristics
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
324.9
300.7
271.3
237.6
199.8
174.5
157.7
140.9
114.6
Cells (V) 30 m
280.7
261.8
240.8
215.5
182.9
160.9
146.1
131.4
109.3
199.8
191.4
180.8
166.1
147.2
132.5
124.1
112.5
96.7
15 m 2 h
127.2
124.1
120.9
114.6
106.2
99.6
94.9
88.6
79.1
81.3
80.3
79.1
77.3
73.5
69.8
67.4
63.5
57.8
1 h 5 h
63.0
62.5
61.6
60.0
57.4
54.7
52.8
49.9
45.7
42.0
42.2
41.7
41.1
39.5
37.9
36.7
35
32.7
3 h 10 h
28.3
28.3
28.3
28.1
26.9
26.3
25.9
24.9
23.7
23.4
23.4
23.4
23.2
22.5
22.0
21.7
20.7
19.2
8 h
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
533.1
505.7
467.9
421.6
363.8
321.7
293.3
262.9
217.6
Cells (V) 30 m
465.8
444.7
418.5
383.8
333.3
297.5
273.4
247.1
208.2
340.7
331.2
319.6
299.6
269.2
247.1
231.3
213.4
185.0
15 m 2 h
223.9
221.8
217.6
210.3
197.7
186.1
178.7
168.2
152.5
148.2
148.2
146.1
144.0
137.7
132.5
128.3
122.0
111.4
1 h 5 h
117.8
116.7
115.7
113.6
108.3
104.2
101.0
96.2
88.8
80.0
80.0
79.5
78.5
76.0
73.1
71.1
68.3
64.0
3 h 10 h
54.5
54.5
54.5
54.3
52.3
51.2
50.5
48.9
46.6
45.3
45.3
45.3
45.0
43.8
43.0
42.4
40.6
38.0
8 h
Discharge Constant Power (Watts at 20°C)
Discharge Constant Current (Amperes at 20°C)
ET/DATAOPZSSTANDBY 200V3
High energy density
Robust tubular positive electrode design, compliant with DIN 40736
Minimal maintenance due to low antimony alloy and large electrolyte volume
Operating temperature -20°C to +55°C
EUROBAT design life: Long Life > 12 years
Fully recyclable with low CO2 footprint
Features
Telecommunications/ Mobile Phone Stations
Traffic Systems
UPS Systems
Emergency Lighting
Electrical Switching
Applications
Part of our Network Power range
Length 103 mmWidth 206 mmHeight (H1) 355 mmTotal height (H2) 368 mmDry weight 12.9 kgFilled weight 17.7 kg
Dimensions and weight
W
L
H1 H2
Compliant with IEC60896-11
Eternity Technologies vented lead-acid batteries for the standby power market. Eternity Technologies OPzS batteries have optimised design resulting in a low maintenance, reliable energy storage solution for critical and unstable conditions.
5 OPzS-ET 250(2V 280Ah @ 10hr)
High energy density
Robust tubular positive electrode design, compliant with DIN 40736
Minimal maintenance due to low antimony alloy and large electrolyte volume
Operating temperature -20°C to +55°C
EUROBAT design life: Long Life > 12 years
Fully recyclable with low CO2 footprint
FeaturesNominal Voltage 2VNumber of cells 1Design Life 20 years
Nominal Capacity 20°C (68°F)10 hour rate (28A, 1.8V) 280Ah5 hour rate (51A, 1.75V) 255Ah1 hour rate (156A, 1.6V) 156Ah
Internal ResistanceFully Charged Battery 20°C (68°F) 0.74mOhm
ElectrolyteNominal S.G at 20°C = 1.240kg/l
Operating Temperature Range -20°C to +55°C
Maximum Discharge Current 20°C (68°F) 459A
Charge Methods: Constant Voltage Charge 20°C (68°F)Cycle use 2.40V (time limited) Maximum charging current 112AStandby use 2.25V ± 1% Temperature compensation -3.0mV/°C/Cell Terminal torque 23Nm Telecommunications/ Mobile Phone Stations
Traffic Systems
UPS Systems
Emergency Lighting
Electrical Switching
Applications
Performance characteristics
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
398.3
367.7
330.7
289.5
243.0
212.4
191.2
170.1
138.4
Cells (V) 30 m
343.4
320.2
293.7
263.1
222.9
195.5
177.5
159.5
132.1
245.1
234.6
221.9
203.9
179.6
162.7
151.1
137.4
118.3
15 m 2 h
156.4
153.2
149.0
141.6
131.0
122.6
116.2
108.8
96.9
101.1
100.0
98.3
95.9
91.2
86.5
83.5
78.7
71.6
1 h 5 h
77.6
76.9
75.9
74.0
70.7
67.3
65.0
61.5
56.3
52.0
52.2
51.7
50.8
48.9
46.8
45.3
43.4
40.5
3 h 10 h
35.0
35.0
35.0
34.8
33.4
32.5
32.0
30.9
29.3
29.2
29.2
29.2
28.8
28.0
27.4
26.9
25.7
23.9
8 h
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
653.0
617.1
570.6
512.5
441.7
389.9
356.1
319.1
263.1
Cells (V) 30 m
569.5
543.1
510.3
467.0
405.7
361.4
330.7
300.1
252.5
417.4
405.7
390.9
366.6
328.6
301.1
283.2
259.9
226.1
15 m 2 h
276.8
273.7
268.4
258.9
242.0
229.3
219.8
206.0
186.0
184.9
183.8
181.7
179.6
171.2
163.8
158.5
151.1
138.4
1 h 5 h
144.8
143.7
142.6
139.5
134.2
127.8
124.7
118.3
109.9
99.1
99.1
98.4
97.3
94.1
90.4
88.0
84.5
79.4
3 h 10 h
67.4
67.4
67.4
67.1
64.7
63.4
62.4
60.5
57.7
56.3
56.3
56.3
56.0
54.5
53.5
52.7
50.5
47.2
8 h
Discharge Constant Power (Watts at 20°C)
Discharge Constant Current (Amperes at 20°C)
Part of our Network Power range
Length 124 mmWidth 206 mmHeight (H1) 355 mmTotal height (H2) 368 mmDry weight 15.5 kgFilled weight 21.3 kg
Dimensions and weight
W
L
H1 H2
Compliant with IEC60896-11
ET/DATAOPZSSTANDBY 250V3
Eternity Technologies vented lead-acid batteries for the standby power market. Eternity Technologies OPzS batteries have optimised design resulting in a low maintenance, reliable energy storage solution for critical and unstable conditions.
5 OPzS-ET 350(2V 400Ah @ 10hr)
High energy density
Robust tubular positive electrode design, compliant with DIN 40736
Minimal maintenance due to low antimony alloy and large electrolyte volume
Operating temperature -20°C to +55°C
EUROBAT design life: Long Life > 12 years
Fully recyclable with low CO2 footprint
FeaturesNominal Voltage 2VNumber of cells 1Design Life 20 years
Nominal Capacity 20°C (68°F)10 hour rate (40A, 1.8V) 400Ah5 hour rate (72A, 1.75V) 358Ah1 hour rate (228A, 1.6V) 228Ah
Internal ResistanceFully Charged Battery 20°C (68°F) 0.67mOhm
ElectrolyteNominal S.G at 20°C = 1.240kg/l
Operating Temperature Range -20°C to +55°C
Maximum Discharge Current 20°C (68°F) 542A
Charge Methods: Constant Voltage Charge 20°C (68°F)Cycle use 2.40V (time limited) Maximum charging current 160AStandby use 2.25V ± 1% Temperature compensation -3.0mV/°C/Cell Terminal torque 23Nm Telecommunications/ Mobile Phone Stations
Traffic Systems
UPS Systems
Emergency Lighting
Electrical Switching
Applications
Performance characteristics
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
490.5
438.9
387.4
332.6
277.9
244.2
222.1
196.8
160.0
Cells (V) 30 m
440.0
398.9
356.8
311.6
264.2
232.6
212.6
189.5
154.7
335.8
312.6
288.4
260.0
227.4
204.2
187.4
168.4
140.0
15 m 2 h
228.4
222.1
212.6
200.0
181.1
166.3
155.8
142.1
121.1
146.3
144.2
141.1
135.8
126.3
118.9
112.6
105.1
92.9
1 h 5 h
110.5
108.4
105.3
102.4
98.0
92.5
88.8
84.0
76.8
72.8
73.6
73.2
71.6
68.4
65.8
64.0
60.8
56.0
3 h 10 h
49.6
49.6
49.6
49.6
48.0
46.8
46.0
43.9
40.8
42.0
42.0
42.0
41.2
40.0
39.1
38.4
36.6
34.0
8 h
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
803.2
737.9
667.4
589.5
504.2
449.5
412.6
369.5
305.3
Cells (V) 30 m
729.5
676.8
618.9
554.7
481.1
429.5
395.8
355.8
295.8
571.6
541.1
508.4
468.4
417.9
377.9
351.6
318.9
268.4
15 m 2 h
403.2
396.8
384.2
365.3
335.8
310.5
293.7
269.5
233.7
267.4
266.3
261.1
252.6
237.9
224.2
214.7
201.1
180.0
1 h 5 h
205.3
202.1
197.9
192.6
185.3
175.8
170.5
162.1
149.5
140.0
140.0
138.9
136.8
131.6
127.4
124.2
118.9
109.5
3 h 10 h
96.7
96.7
96.7
95.9
93.2
91.2
89.9
86.1
80.5
81.3
81.3
81.3
79.9
77.8
76.2
75.3
72.0
67.3
8 h
Discharge Constant Power (Watts at 20°C)
Discharge Constant Current (Amperes at 20°C)
Part of our Network Power range
Length 124 mmWidth 206 mmHeight (H1) 471 mmTotal height (H2) 484 mmDry weight 20.0 kgFilled weight 27.4 kg
Dimensions and weight
W
L
H1 H2
Compliant with IEC60896-11
ET/DATAOPZSSTANDBY 350V3
Eternity Technologies vented lead-acid batteries for the standby power market. Eternity Technologies OPzS batteries have optimised design resulting in a low maintenance, reliable energy storage solution for critical and unstable conditions.
6 OPzS-ET 300(2V 335Ah @ 10hr)
High energy density
Robust tubular positive electrode design, compliant with DIN 40736
Minimal maintenance due to low antimony alloy and large electrolyte volume
Operating temperature -20°C to +55°C
EUROBAT design life: Long Life > 12 years
Fully recyclable with low CO2 footprint
FeaturesNominal Voltage 2VNumber of cells 1Design Life 20 years
Nominal Capacity 20°C (68°F)10 hour rate (33.5A, 1.8V) 335Ah5 hour rate (60.5A, 1.75V) 302.5Ah1 hour rate (187A, 1.6V) 187Ah
Internal ResistanceFully Charged Battery 20°C (68°F) 0.63mOhm
ElectrolyteNominal S.G at 20°C = 1.240kg/l
Operating Temperature Range -20°C to +55°C
Maximum Discharge Current 20°C (68°F) 539A
Charge Methods: Constant Voltage Charge 20°C (68°F)Cycle use 2.40V (time limited) Maximum charging current 134AStandby use 2.25V ± 1% Temperature compensation -3.0mV/°C/Cell Terminal torque 23Nm Telecommunications/ Mobile Phone Stations
Traffic Systems
UPS Systems
Emergency Lighting
Electrical Switching
Applications
Performance characteristics
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
468.6
431.5
388.0
338.2
284.1
244.9
222.6
197.2
160.1
Cells (V) 30 m
403.9
376.3
344.5
307.4
259.7
227.9
206.7
185.5
153.7
288.4
276.7
261.9
239.6
211.0
190.8
177.0
161.1
137.8
15 m 2 h
186.6
181.3
176.0
167.5
154.8
144.2
137.8
128.3
114.5
120.9
119.8
117.7
114.5
109.2
103.2
99.3
93.7
85.2
1 h 5 h
91.8
91.2
89.9
87.6
83.8
79.7
77.0
72.8
66.7
61.8
62.1
61.5
60.5
58.2
55.7
54.0
51.6
48.1
3 h 10 h
41.7
41.7
41.7
41.3
39.6
38.7
38.1
36.8
34.8
34.9
34.9
34.9
34.6
33.5
32.8
32.2
30.7
28.6
8 h
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
767.5
725.1
668.9
599.0
515.2
454.8
414.5
371.0
305.3
Cells (V) 30 m
670.0
637.1
597.9
547.0
473.9
420.9
385.9
348.8
293.7
491.9
479.2
461.2
431.5
386.9
354.1
331.8
305.3
265.0
15 m 2 h
328.6
324.4
318.0
306.4
286.2
270.3
258.7
243.8
219.4
221.6
220.5
217.3
214.1
204.6
195.1
188.7
179.2
165.4
1 h 5 h
170.7
170.7
168.6
165.4
159.0
151.6
147.4
139.9
129.3
117.7
117.7
116.6
115.6
112.4
108.1
104.7
100.6
94.5
3 h 10 h
80.3
80.3
80.3
79.8
77.0
75.5
74.4
72.1
68.7
67.4
67.4
67.4
66.9
65.2
63.9
63.1
60.4
56.5
8 h
Discharge Constant Power (Watts at 20°C)
Discharge Constant Current (Amperes at 20°C)
Part of our Network Power range
Length 145 mmWidth 206 mmHeight (H1) 355 mmTotal height (H2) 368 mmDry weight 18.3 kgFilled weight 25.2 kg
Dimensions and weight
W
L
H1 H2
Compliant with IEC60896-11
ET/DATAOPZSSTANDBY 300V3
Eternity Technologies vented lead-acid batteries for the standby power market. Eternity Technologies OPzS batteries have optimised design resulting in a low maintenance, reliable energy storage solution for critical and unstable conditions.
6 OPzS-ET 420(2V 480Ah @ 10hr)
High energy density
Robust tubular positive electrode design, compliant with DIN 40736
Minimal maintenance due to low antimony alloy and large electrolyte volume
Operating temperature -20°C to +55°C
EUROBAT design life: Long Life > 12 years
Fully recyclable with low CO2 footprint
FeaturesNominal Voltage 2VNumber of cells 1Design Life 20 years
Nominal Capacity 20°C (68°F)10 hour rate (48A, 1.8V) 480Ah5 hour rate (86A, 1.75V) 429.5Ah1 hour rate (267A, 1.6V) 267Ah
Internal ResistanceFully Charged Battery 20°C (68°F) 0.57mOhm
ElectrolyteNominal S.G at 20°C = 1.240kg/l
Operating Temperature Range -20°C to +55°C
Maximum Discharge Current 20°C (68°F) 625A
Charge Methods: Constant Voltage Charge 20°C (68°F)Cycle use 2.40V (time limited) Maximum charging current 192AStandby use 2.25V ± 1% Temperature compensation -3.0mV/°C/Cell Terminal torque 23Nm Telecommunications/ Mobile Phone Stations
Traffic Systems
UPS Systems
Emergency Lighting
Electrical Switching
Applications
Performance characteristics
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
565.5
506.4
446.2
384.0
319.6
279.6
253.2
225.8
184.6
Cells (V) 30 m
507.4
461.0
411.4
359.7
304.9
269.0
244.7
218.4
178.3
390.3
365.0
336.5
303.8
265.8
237.4
218.4
196.2
163.5
15 m 2 h
266.9
259.5
247.9
233.1
211.0
193.1
181.5
165.6
141.4
174.1
170.9
166.7
160.4
149.8
140.3
134.0
124.5
110.8
1 h 5 h
131.9
129.8
126.6
122.4
117.1
110.8
106.5
100.9
92.2
87.3
88.3
87.9
85.9
82.1
78.9
76.8
73.0
67.2
3 h 10 h
61.0
61.0
61.0
59.5
57.6
56.1
55.2
52.7
48.9
50.4
50.4
50.4
49.5
48.0
46.8
46.1
44.0
40.8
8 h
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
927.3
851.3
770.1
679.4
580.2
514.8
471.6
424.1
352.4
Cells (V) 30 m
840.8
780.7
714.2
640.4
554.9
495.8
456.8
410.4
340.7
665.7
630.9
592.9
545.4
486.3
441.0
410.4
371.3
312.3
15 m 2 h
469.5
462.1
448.4
426.2
391.4
361.8
341.8
314.4
272.2
318.6
315.4
310.2
300.7
282.7
265.8
255.3
238.4
213.1
1 h 5 h
245.8
242.6
237.4
232.1
222.6
212.0
203.6
194.1
179.3
167.7
167.7
167.7
164.6
158.2
153.0
148.7
142.4
131.9
3 h 10 h
117.1
117.1
117.1
115.0
111.8
109.7
107.6
103.4
96.6
97.5
97.5
97.5
95.9
93.4
91.5
90.3
86.4
80.7
8 h
Discharge Constant Power (Watts at 20°C)
Discharge Constant Current (Amperes at 20°C)
Part of our Network Power range
Length 145 mmWidth 206 mmHeight (H1) 471 mmTotal height (H2) 484 mmDry weight 23.4 kgFilled weight 33.3 kg
Dimensions and weight
W
L
H1 H2
Compliant with IEC60896-11
ET/DATAOPZSSTANDBY 420V4
Eternity Technologies vented lead-acid batteries for the standby power market. Eternity Technologies OPzS batteries have optimised design resulting in a low maintenance, reliable energy storage solution for critical and unstable conditions.
6 OPzS-ET 600(2V 690Ah @ 10hr)
High energy density
Robust tubular positive electrode design, compliant with DIN 40736
Minimal maintenance due to low antimony alloy and large electrolyte volume
Operating temperature -20°C to +55°C
EUROBAT design life: Long Life > 12 years
Fully recyclable with low CO2 footprint
FeaturesNominal Voltage 2VNumber of cells 1Design Life 20 years
Nominal Capacity 20°C (68°F)10 hour rate (69A, 1.8V) 690Ah5 hour rate (118A, 1.75V) 588.5Ah1 hour rate (394A, 1.6V) 394Ah
Internal ResistanceFully Charged Battery 20°C (68°F) 0.47mOhm
ElectrolyteNominal S.G at 20°C = 1.240kg/l
Operating Temperature Range -20°C to +55°C
Maximum Discharge Current 20°C (68°F) 734A
Charge Methods: Constant Voltage Charge 20°C (68°F)Cycle use 2.40V (time limited) Maximum charging current 276AStandby use 2.25V ± 1% Temperature compensation -3.0mV/°C/Cell Terminal torque 23Nm Telecommunications/ Mobile Phone Stations
Traffic Systems
UPS Systems
Emergency Lighting
Electrical Switching
Applications
Performance characteristics
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
682.9
613.9
542.9
468.8
393.7
346.0
313.5
281.1
231.4
Cells (V) 30 m
654.5
584.5
514.5
443.4
373.4
329.8
300.4
270.9
226.3
535.8
489.1
439.4
386.6
329.8
293.3
268.9
242.5
204.0
15 m 2 h
393.7
369.4
342.0
310.5
275.0
248.6
231.4
210.0
177.6
255.7
246.6
236.4
223.2
205.0
189.8
179.6
165.4
143.1
1 h 5 h
181.6
179.6
175.5
169.5
158.3
149.2
142.1
132.9
118.7
120.8
120.8
119.7
117.7
113.6
108.6
104.5
99.9
92.4
3 h 10 h
87.7
87.7
85.5
84.2
81.4
78.9
77.3
74.0
69.0
72.5
72.5
71.7
71.0
69.0
67.4
66.3
63.2
58.7
8 h
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
1121.3
1029.9
936.6
830.0
713.3
636.2
583.5
526.6
440.4
Cells (V) 30 m
1085.7
990.4
891.9
788.4
679.9
608.8
561.1
509.4
432.3
913.2
846.3
775.2
695.1
604.8
543.9
504.3
458.6
389.6
15 m 2 h
694.1
657.5
616.9
568.2
510.4
465.8
436.3
397.8
340.9
468.8
455.6
437.3
416.0
385.6
359.2
340.9
315.6
278.0
1 h 5 h
337.9
336.9
329.8
318.6
300.4
284.1
271.9
255.7
230.3
229.3
229.3
227.3
224.3
218.2
209.0
204.0
194.8
181.6
3 h 10 h
168.4
168.4
164.4
162.4
158.3
154.2
151.2
145.1
136.0
140.0
140.0
139.0
138.0
133.9
131.9
129.9
123.8
115.7
8 h
Discharge Constant Power (Watts at 20°C)
Discharge Constant Current (Amperes at 20°C)
Part of our Network Power range
Length 145 mmWidth 206 mmHeight (H1) 647 mmTotal height (H2) 660 mmDry weight 32.1 kgFilled weight 41.1 kg
Dimensions and weight
W
L
H1 H2
Compliant with IEC60896-11
ET/DATAOPZSSTANDBY 600V3
Eternity Technologies vented lead-acid batteries for the standby power market. Eternity Technologies OPzS batteries have optimised design resulting in a low maintenance, reliable energy storage solution for critical and unstable conditions.
7 OPzS-ET 490(2V 560Ah @ 10hr)
High energy density
Robust tubular positive electrode design, compliant with DIN 40736
Minimal maintenance due to low antimony alloy and large electrolyte volume
Operating temperature -20°C to +55°C
EUROBAT design life: Long Life > 12 years
Fully recyclable with low CO2 footprint
FeaturesNominal Voltage 2VNumber of cells 1Design Life 20 years
Nominal Capacity 20°C (68°F)10 hour rate (56A, 1.8V) 560Ah5 hour rate (100A, 1.75V) 501.5Ah1 hour rate (304A, 1.6V) 304Ah
Internal ResistanceFully Charged Battery 20°C (68°F) 0.5mOhm
ElectrolyteNominal S.G at 20°C = 1.240kg/l
Operating Temperature Range -20°C to +55°C
Maximum Discharge Current 20°C (68°F) 714A
Charge Methods: Constant Voltage Charge 20°C (68°F)Cycle use 2.40V (time limited) Maximum charging current 224AStandby use 2.25V ± 1% Temperature compensation -3.0mV/°C/Cell Terminal torque 23Nm Telecommunications/ Mobile Phone Stations
Traffic Systems
UPS Systems
Emergency Lighting
Electrical Switching
Applications
Performance characteristics
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
646.6
579.0
510.3
439.5
365.6
320.2
289.5
258.9
211.3
Cells (V) 30 m
580.1
527.2
471.2
412.1
348.7
307.5
280.0
249.4
203.9
446.9
417.4
384.6
346.6
303.2
271.5
250.4
225.1
187.0
15 m 2 h
304.3
295.8
284.2
266.3
242.0
220.8
207.1
189.1
161.7
200.8
197.6
193.4
186.0
173.3
162.7
155.3
143.7
127.8
1 h 5 h
154.3
151.1
147.9
143.7
137.4
130.0
124.7
117.3
107.8
102.0
103.0
102.5
100.3
95.7
92.0
89.6
85.2
78.4
3 h 10 h
71.1
71.1
71.1
69.4
67.2
65.5
64.5
61.5
57.2
58.9
58.9
58.9
57.7
56.0
54.6
53.8
51.2
47.7
8 h
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
1061.9
973.1
880.2
776.6
663.5
588.5
538.9
483.9
402.6
Cells (V) 30 m
961.5
892.8
816.8
732.2
635.0
566.3
522.0
469.1
389.9
760.8
721.7
677.3
623.4
555.8
504.0
469.1
423.7
357.1
15 m 2 h
537.8
528.3
512.5
487.1
448.0
414.2
390.9
359.2
311.7
367.7
364.5
358.2
346.6
326.5
307.5
294.8
275.8
247.2
1 h 5 h
287.4
283.2
277.9
270.5
259.9
247.2
237.7
226.1
209.2
195.5
195.5
195.5
191.2
183.8
177.5
174.3
165.9
154.3
3 h 10 h
137.4
137.4
137.4
134.2
130.0
127.8
125.7
120.5
113.1
114.1
114.1
114.1
112.0
108.8
106.7
105.3
100.8
94.1
8 h
Discharge Constant Power (Watts at 20°C)
Discharge Constant Current (Amperes at 20°C)
Part of our Network Power range
Length 166 mmWidth 206 mmHeight (H1) 471 mmTotal height (H2) 484 mmDry weight 26.7 kgFilled weight 36.9 kg
Dimensions and weight
W
L
H1 H2
Compliant with IEC60896-11
ET/DATAOPZSSTANDBY 490V3
Eternity Technologies vented lead-acid batteries for the standby power market. Eternity Technologies OPzS batteries have optimised design resulting in a low maintenance, reliable energy storage solution for critical and unstable conditions.
7 OPzS-ET 700(2V 805Ah @ 10hr)
High energy density
Robust tubular positive electrode design, compliant with DIN 40736
Minimal maintenance due to low antimony alloy and large electrolyte volume
Operating temperature -20°C to +55°C
EUROBAT design life: Long Life > 12 years
Fully recyclable with low CO2 footprint
FeaturesNominal Voltage 2VNumber of cells 1Design Life 20 years
Nominal Capacity 20°C (68°F)10 hour rate (80.5A, 1.8V) 805Ah5 hour rate (138.9A, 1.75V) 694Ah1 hour rate (463.6A, 1.6V) 463.6Ah
Internal ResistanceFully Charged Battery 20°C (68°F) 0.35mOhm
ElectrolyteNominal S.G at 20°C = 1.240kg/l
Operating Temperature Range -20°C to +55°C
Maximum Discharge Current 20°C (68°F) 942A
Charge Methods: Constant Voltage Charge 20°C (68°F)Cycle use 2.40V (time limited) Maximum charging current 322AStandby use 2.25V ± 1% Temperature compensation -3.0mV/°C/Cell Terminal torque 23Nm Telecommunications/ Mobile Phone Stations
Traffic Systems
UPS Systems
Emergency Lighting
Electrical Switching
Applications
Performance characteristics
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
877.5
787.3
694.4
598.9
498.9
436.1
394.5
350.4
284.8
Cells (V) 30 m
811.2
729.0
644.0
557.3
467.1
410.5
373.3
334.4
275.1
652.0
595.4
536.1
472.4
404.3
360.1
330.0
298.1
249.5
15 m 2 h
463.6
444.1
416.7
380.4
334.4
302.6
281.3
256.6
219.4
302.6
296.4
284.8
268.0
245.0
225.6
213.2
196.4
171.6
1 h 5 h
219.4
215.9
209.7
199.9
186.6
176.1
169.0
157.5
140.6
143.3
143.3
141.6
138.9
134.5
128.3
124.7
118.6
109.7
3 h 10 h
102.6
102.6
100.9
99.1
95.6
92.9
91.1
86.8
80.5
84.6
84.6
83.7
82.1
80.5
78.6
77.4
73.8
68.5
8 h
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
1437.5
1322.5
1198.7
1061.6
906.8
803.3
733.3
657.3
543.1
Cells (V) 30 m
1344.6
1234.0
1119.0
990.8
850.2
758.1
696.2
628.1
525.4
1110.2
1030.6
946.6
849.2
740.4
667.0
618.4
561.8
477.7
15 m 2 h
818.3
791.7
752.9
695.3
619.2
565.3
529.9
487.5
422.9
553.8
545.8
529.0
500.7
460.0
427.3
406.0
376.0
331.7
1 h 5 h
407.8
403.4
392.8
376.0
353.9
336.2
323.8
303.5
274.2
271.6
271.6
269.9
266.3
258.3
248.6
242.4
230.9
215.0
3 h 10 h
196.4
196.4
193.7
191.1
185.8
181.4
177.8
169.8
159.3
163.6
163.6
161.9
159.3
156.5
153.0
151.3
145.1
135.4
8 h
Discharge Constant Power (Watts at 20°C)
Discharge Constant Current (Amperes at 20°C)
Part of our Network Power range
Length 145 mmWidth 206 mmHeight (H1) 647 mmTotal height (H2) 660 mmDry weight 43.0 kgFilled weight 57.0 kg
Dimensions and weight
W
L
H1 H2
Compliant with IEC60896-11
ET/DATAOPZSSTANDBY 700V2
Eternity Technologies vented lead-acid batteries for the standby power market. Eternity Technologies OPzS batteries have optimised design resulting in a low maintenance, reliable energy storage solution for critical and unstable conditions.
8 OPzS-ET 800(2V 920Ah @ 10hr)
High energy density
Robust tubular positive electrode design, compliant with DIN 40736
Minimal maintenance due to low antimony alloy and large electrolyte volume
Operating temperature -20°C to +55°C
EUROBAT design life: Long Life > 12 years
Fully recyclable with low CO2 footprint
FeaturesNominal Voltage 2VNumber of cells 1Design Life 20 years
Nominal Capacity 20°C (68°F)10 hour rate (92A, 1.8V) 920Ah5 hour rate (159A, 1.75V) 793.5Ah1 hour rate (530A, 1.6V) 530Ah
Internal ResistanceFully Charged Battery 20°C (68°F) 0.33mOhm
ElectrolyteNominal S.G at 20°C = 1.240kg/l
Operating Temperature Range -20°C to +55°C
Maximum Discharge Current 20°C (68°F) 1077A
Charge Methods: Constant Voltage Charge 20°C (68°F)Cycle use 2.40V (time limited) Maximum charging current 368AStandby use 2.25V ± 1% Temperature compensation -3.0mV/°C/Cell Terminal torque 23Nm Telecommunications/ Mobile Phone Stations
Traffic Systems
UPS Systems
Emergency Lighting
Electrical Switching
Applications
Performance characteristics
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
1002.9
899.8
793.6
684.4
570.2
498.4
450.9
400.4
325.5
Cells (V) 30 m
927.1
833.1
736.0
636.9
533.8
469.1
426.6
382.2
314.4
745.1
680.4
612.7
539.9
462.0
411.5
377.1
340.7
285.1
15 m 2 h
529.8
507.5
476.2
434.7
382.2
345.8
321.5
293.2
250.7
345.8
338.7
325.5
306.3
280.0
257.8
243.6
224.4
196.1
1 h 5 h
250.7
246.7
239.6
228.5
213.3
201.2
193.1
180.0
160.7
163.8
163.8
161.8
158.7
153.7
146.6
142.5
135.5
125.4
3 h 10 h
117.3
117.3
115.3
113.2
109.2
106.2
104.1
99.2
92.0
96.7
96.7
95.6
93.8
92.0
89.8
88.4
84.3
78.3
8 h
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
1642.9
1511.4
1369.9
1213.2
1036.3
918.0
838.1
751.2
620.7
Cells (V) 30 m
1536.7
1410.3
1278.9
1132.3
971.6
866.4
795.6
717.8
600.5
1268.8
1177.8
1081.8
970.5
846.2
762.3
706.7
642.0
545.9
15 m 2 h
935.2
904.8
860.4
794.6
707.7
646.0
605.6
557.1
483.3
632.9
623.8
604.6
572.2
525.7
488.3
464.0
429.7
379.1
1 h 5 h
466.1
461.0
448.9
429.7
404.4
384.2
370.0
346.8
313.4
310.4
310.4
308.4
304.3
295.2
284.1
277.0
263.9
245.7
3 h 10 h
224.4
224.4
221.4
218.4
212.3
207.3
203.2
194.1
182.0
187.0
187.0
185.0
182.0
178.9
174.9
172.9
165.8
154.7
8 h
Discharge Constant Power (Watts at 20°C)
Discharge Constant Current (Amperes at 20°C)
Part of our Network Power range
Length 210 mmWidth 191 mmHeight (H1) 647 mmTotal height (H2) 660 mmDry weight 45.0 kgFilled weight 60.4 kg
Dimensions and weight
Compliant with IEC60896-11
ET/DATAOPZSSTANDBY 800V3
W
L
H1 H2
Eternity Technologies vented lead-acid batteries for the standby power market. Eternity Technologies OPzS batteries have optimised design resulting in a low maintenance, reliable energy storage solution for critical and unstable conditions.
9 OPzS-ET 900(2V 1035Ah @ 10hr)
High energy density
Robust tubular positive electrode design, compliant with DIN 40736
Minimal maintenance due to low antimony alloy and large electrolyte volume
Operating temperature -20°C to +55°C
EUROBAT design life: Long Life > 12 years
Fully recyclable with low CO2 footprint
FeaturesNominal Voltage 2VNumber of cells 1Design Life 20 years
Nominal Capacity 20°C (68°F)10 hour rate (104A, 1.8V) 1035Ah5 hour rate (183A, 1.75V) 915Ah1 hour rate (590A, 1.6V) 590Ah
Internal ResistanceFully Charged Battery 20°C (68°F) 0.29mOhm
ElectrolyteNominal S.G at 20°C = 1.240kg/l
Operating Temperature Range -20°C to +55°C
Maximum Discharge Current 20°C (68°F) 1099A
Charge Methods: Constant Voltage Charge 20°C (68°F)Cycle use 2.40V (time limited) Maximum charging current 414AStandby use 2.25V ± 1% Temperature compensation -3.0mV/°C/Cell Terminal torque 23Nm Telecommunications/ Mobile Phone Stations
Traffic Systems
UPS Systems
Emergency Lighting
Electrical Switching
Applications
Performance characteristics
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
1024
922
816
704
590
518
471
422
347
Cells (V) 30 m
982
876
771
666
560
495
451
406
339
805
734
660
579
495
440
403
364
305
15 m 2 h
590
554
512
466
413
373
347
314
266
384
370
354
335
308
284
269
248
215
1 h 5 h
272
270
264
254
238
223
213
199
178
181
181
179
183
170
162
157
150
139
3 h 10 h
131
131
128
126
122
119
116
111
104
109
109
107
107
104
101
100
94
88
8 h
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
1681
1549
1405
1247
1069
956
876
789
660
Cells (V) 30 m
1624
1484
1337
1182
1020
914
842
763
647
1371
1269
1163
1043
907
816
755
687
585
15 m 2 h
1043
986
925
854
767
699
654
597
512
703
683
656
624
578
538
511
474
416
1 h 5 h
507
505
496
478
451
425
408
384
346
344
344
341
337
326
314
305
292
272
3 h 10 h
252
252
247
244
237
230
227
218
204
210
210
209
207
201
197
195
187
174
8 h
Discharge Constant Power (Watts at 20°C)
Discharge Constant Current (Amperes at 20°C)
Part of our Network Power range
Length 210 mmWidth 233 mmHeight (H1) 647 mmTotal height (H2) 660 mmDry weight 52.5 kgFilled weight 71.5 kg
Dimensions and weight
Compliant with IEC60896-11
ET/DATAOPZSSTANDBY 900V2
W
L
H1 H2
Eternity Technologies vented lead-acid batteries for the standby power market. Eternity Technologies OPzS batteries have optimised design resulting in a low maintenance, reliable energy storage solution for critical and unstable conditions.
10 OPzS-ET 1000(2V 1150Ah @ 10hr)
High energy density
Robust tubular positive electrode design, compliant with DIN 40736
Minimal maintenance due to low antimony alloy and large electrolyte volume
Operating temperature -20°C to +55°C
EUROBAT design life: Long Life > 12 years
Fully recyclable with low CO2 footprint
FeaturesNominal Voltage 2VNumber of cells 1Design Life 20 years
Nominal Capacity 20°C (68°F)10 hour rate (115A, 1.8V) 1150Ah5 hour rate (198A, 1.75V) 988.5Ah1 hour rate (659A, 1.6V) 659Ah
Internal ResistanceFully Charged Battery 20°C (68°F) 0.27mOhm
ElectrolyteNominal S.G at 20°C = 1.240kg/l
Operating Temperature Range -20°C to +55°C
Maximum Discharge Current 20°C (68°F) 1281A
Charge Methods: Constant Voltage Charge 20°C (68°F)Cycle use 2.40V (time limited) Maximum charging current 460AStandby use 2.25V ± 1% Temperature compensation -3.0mV/°C/Cell Terminal torque 23Nm Telecommunications/ Mobile Phone Stations
Traffic Systems
UPS Systems
Emergency Lighting
Electrical Switching
Applications
Performance characteristics
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
1195.4
1074.3
949.3
819.1
683.9
600.2
543.7
484.2
396.4
Cells (V) 30 m
1124.8
1007.8
888.7
767.7
644.6
567.9
517.5
465.0
385.4
912.9
833.2
749.5
659.7
563.9
501.4
460.0
415.6
348.0
15 m 2 h
658.7
625.4
582.1
530.6
468.1
423.7
393.4
358.1
304.6
429.7
417.6
400.5
377.3
346.0
319.8
301.6
278.4
242.1
1 h 5 h
307.7
304.6
296.6
283.5
265.3
250.2
239.1
222.9
199.7
202.8
202.8
200.7
197.7
190.7
181.6
176.5
168.5
155.4
3 h 10 h
146.3
146.3
143.2
141.2
136.2
132.1
129.1
124.1
115.0
121.1
121.1
120.0
118.0
115.0
112.0
110.0
104.9
97.8
8 h
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
1962.1
1805.7
1634.2
1447.6
1240.8
1104.6
1008.8
906.9
754.6
Cells (V) 30 m
1866.2
1709.9
1543.4
1366.9
1175.2
1049.1
964.4
872.6
735.4
1553.5
1442.5
1321.5
1185.3
1034.0
930.1
861.5
783.8
665.8
15 m 2 h
1160.1
1114.7
1054.2
970.4
867.5
791.9
741.4
679.9
587.1
786.8
769.7
742.5
704.1
649.6
604.3
574.0
531.6
468.1
1 h 5 h
573.0
568.9
555.8
534.6
503.4
476.1
458.0
429.7
388.4
385.4
385.4
382.3
377.3
366.2
352.1
342.0
326.8
304.6
3 h 10 h
280.4
280.4
275.4
272.4
264.3
257.2
253.2
242.1
227.0
233.0
233.0
231.0
229.0
223.9
218.9
215.9
206.8
193.7
8 h
Discharge Constant Power (Watts at 20°C)
Discharge Constant Current (Amperes at 20°C)
Part of our Network Power range
Length 210 mmWidth 233 mmHeight (H1) 647 mmTotal height (H2) 660 mmDry weight 54.5 kgFilled weight 73.6 kg
Dimensions and weight
Compliant with IEC60896-11
ET/DATAOPZSSTANDBY 1000V3
W
L
H1 H2
Eternity Technologies vented lead-acid batteries for the standby power market. Eternity Technologies OPzS batteries have optimised design resulting in a low maintenance, reliable energy storage solution for critical and unstable conditions.
11 OPzS-ET 1100(2V 1265Ah @ 10hr)
High energy density
Robust tubular positive electrode design, compliant with DIN 40736
Minimal maintenance due to low antimony alloy and large electrolyte volume
Operating temperature -20°C to +55°C
EUROBAT design life: Long Life > 12 years
Fully recyclable with low CO2 footprint
FeaturesNominal Voltage 2VNumber of cells 1Design Life 20 years
Nominal Capacity 20°C (68°F)10 hour rate (126.5A, 1.8V) 1265Ah5 hour rate (223.7A, 1.75V) 1118.3Ah1 hour rate (721.1A, 1.6V) 721.1Ah
Internal ResistanceFully Charged Battery 20°C (68°F) 0.23mOhm
ElectrolyteNominal S.G at 20°C = 1.240kg/l
Operating Temperature Range -20°C to +55°C
Maximum Discharge Current 20°C (68°F) 1344A
Charge Methods: Constant Voltage Charge 20°C (68°F)Cycle use 2.40V (time limited) Maximum charging current 506 AStandby use 2.25V ± 1% Temperature compensation -3.0mV/°C/Cell Terminal torque 23Nm Telecommunications/ Mobile Phone Stations
Traffic Systems
UPS Systems
Emergency Lighting
Electrical Switching
Applications
Performance characteristics
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
1251.2
1126.5
997.2
860.6
721.1
633.4
575.2
515.3
423.9
Cells (V) 30 m
1200.4
1071.1
941.8
813.5
684.2
604.8
551.3
496.7
414.6
983.4
896.6
806.1
708.2
604.8
538.4
493.1
445.0
373.0
15 m 2 h
721.1
676.9
626.0
569.7
505.1
456.1
423.9
384.1
325.1
469.1
452.5
433.0
409.0
375.8
347.1
328.7
302.9
263.2
1 h 5 h
332.4
330.6
322.2
310.3
290.9
272.4
260.4
243.7
217.9
221.7
221.7
218.8
223.4
207.7
198.6
192.0
182.8
169.9
3 h 10 h
160.7
160.7
156.9
154.2
149.6
144.9
141.3
135.8
126.5
133.0
133.0
131.1
130.2
126.5
123.8
121.9
115.4
107.1
8 h
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
2054.4
1892.9
1717.5
1523.5
1306.5
1168.0
1071.1
964.9
807.0
Cells (V) 30 m
1985.2
1814.4
1634.3
1445.0
1246.6
1117.2
1029.5
932.6
791.4
1675.9
1551.3
1421.9
1274.3
1108.1
997.2
923.4
840.2
714.6
15 m 2 h
1274.3
1205.0
1131.1
1043.4
937.2
854.2
799.6
729.5
626.0
859.7
834.7
802.4
762.7
706.4
657.4
625.1
579.0
508.8
1 h 5 h
619.6
617.7
605.7
584.5
551.3
519.8
498.6
469.1
422.9
420.1
420.1
416.4
411.9
398.9
382.2
373.0
356.4
332.4
3 h 10 h
308.4
308.4
302.0
298.3
289.9
281.6
277.0
265.9
249.3
256.7
256.7
254.8
253.0
245.6
241.0
238.2
228.1
212.4
8 h
Discharge Constant Power (Watts at 20°C)
Discharge Constant Current (Amperes at 20°C)
Part of our Network Power range
Length 210 mmWidth 275 mmHeight (H1) 647 mmTotal height (H2) 660 mmDry weight 59.0 kgFilled weight 83.5 kg
Dimensions and weight
Compliant with IEC60896-11
ET/DATAOPZSSTANDBY 1100V1
W
L
H1 H2
Eternity Technologies vented lead-acid batteries for the standby power market. Eternity Technologies OPzS batteries have optimised design resulting in a low maintenance, reliable energy storage solution for critical and unstable conditions.
12 OPzS-ET 1200(2V 1380Ah @ 10hr)
High energy density
Robust tubular positive electrode design, compliant with DIN 40736
Minimal maintenance due to low antimony alloy and large electrolyte volume
Operating temperature -20°C to +55°C
EUROBAT design life: Long Life > 12 years
Fully recyclable with low CO2 footprint
FeaturesNominal Voltage 2VNumber of cells 1Design Life 20 years
Nominal Capacity 20°C (68°F)10 hour rate (138A, 1.8V) 1380Ah5 hour rate (235A, 1.75V) 1173.5Ah1 hour rate (787A, 1.6V) 787Ah
Internal ResistanceFully Charged Battery 20°C (68°F) 0.23mOhm
ElectrolyteNominal S.G at 20°C = 1.240kg/l
Operating Temperature Range -20°C to +55°C
Maximum Discharge Current 20°C (68°F) 1466A
Charge Methods: Constant Voltage Charge 20°C (68°F)Cycle use 2.40V (time limited) Maximum charging current 552AStandby use 2.25V ± 1% Temperature compensation -3.0mV/°C/Cell Terminal torque 23Nm Telecommunications/ Mobile Phone Stations
Traffic Systems
UPS Systems
Emergency Lighting
Electrical Switching
Applications
Performance characteristics
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
1364.9
1228.9
1087.9
938.8
786.7
691.0
627.5
562.1
462.4
Cells (V) 30 m
1309.5
1168.5
1027.4
887.4
746.4
659.8
601.4
541.9
452.3
1072.8
978.1
879.4
772.6
659.8
587.3
537.9
485.5
406.9
15 m 2 h
786.7
738.4
682.9
621.5
551.0
497.6
462.4
419.0
354.6
511.7
493.6
472.4
446.2
410.0
378.7
358.6
330.4
287.1
1 h 5 h
362.6
360.6
351.5
338.5
317.3
297.2
284.1
265.9
237.7
241.8
241.8
238.7
243.7
226.6
216.6
209.5
199.4
185.3
3 h 10 h
175.3
175.3
171.2
168.2
163.2
158.1
154.1
148.1
138.0
145.1
145.1
143.0
142.0
138.0
135.0
133.0
125.9
116.8
8 h
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
2241.2
2065.0
1873.6
1662.0
1425.3
1274.2
1168.5
1052.6
880.4
Cells (V) 30 m
2165.7
1979.3
1782.9
1576.4
1359.9
1218.8
1123.1
1017.4
863.3
1828.2
1692.3
1551.2
1390.1
1208.8
1087.9
1007.3
916.6
779.6
15 m 2 h
1390.1
1314.5
1233.9
1138.2
1022.4
931.8
872.3
795.8
682.9
937.8
910.6
875.3
832.0
770.6
717.2
681.9
631.6
555.0
1 h 5 h
675.9
673.9
660.8
637.6
601.4
567.1
543.9
511.7
461.3
458.3
458.3
454.3
449.3
435.2
418.0
406.9
388.8
362.6
3 h 10 h
336.4
336.4
329.4
325.4
316.3
307.2
302.2
290.1
272.0
280.0
280.0
278.0
276.0
267.9
262.9
259.9
248.8
231.7
8 h
Discharge Constant Power (Watts at 20°C)
Discharge Constant Current (Amperes at 20°C)
Part of our Network Power range
Length 210 mmWidth 275 mmHeight (H1) 647 mmTotal height (H2) 660 mmDry weight 63.8 kgFilled weight 86.7 kg
Dimensions and weight
Compliant with IEC60896-11
ET/DATAOPZSSTANDBY 1200V3
W
L
H1 H2
Eternity Technologies vented lead-acid batteries for the standby power market. Eternity Technologies OPzS batteries have optimised design resulting in a low maintenance, reliable energy storage solution for critical and unstable conditions.
12 OPzS-ET 1500(2V 1650Ah @ 10hr)
High energy density
Robust tubular positive electrode design, compliant with DIN 40736
Minimal maintenance due to low antimony alloy and large electrolyte volume
Operating temperature -20°C to +55°C
EUROBAT design life: Long Life > 12 years
Fully recyclable with low CO2 footprint
FeaturesNominal Voltage 2VNumber of cells 1Design Life 20 years
Nominal Capacity 20°C (68°F)10 hour rate (165A, 1.8V) 1650Ah5 hour rate (292A, 1.75V) 1460Ah1 hour rate (906A, 1.6V) 906Ah
Internal ResistanceFully Charged Battery 20°C (68°F) 0.23mOhm
ElectrolyteNominal S.G at 20°C = 1.240kg/l
Operating Temperature Range -20°C to +55°C
Maximum Discharge Current 20°C (68°F) 1470A
Charge Methods: Constant Voltage Charge 20°C (68°F)Cycle use 2.40V (time limited) Maximum charging current 660AStandby use 2.25V ± 1% Temperature compensation -3.0mV/°C/Cell Terminal torque 23Nm Telecommunications/ Mobile Phone Stations
Traffic Systems
UPS Systems
Emergency Lighting
Electrical Switching
Applications
Performance characteristics
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
1426.8
1261.8
1091.9
924.0
754.1
648.4
578.5
505.7
396.0
Cells (V) 30 m
1354.0
1203.5
1053.1
895.9
733.8
632.8
565.9
496.0
390.2
1155.0
1038.5
922.1
799.8
669.7
584.3
528.0
464.9
370.8
15 m 2 h
905.6
827.9
745.4
656.1
561.0
497.9
455.2
406.7
332.9
623.1
594.0
556.1
508.6
448.4
405.7
376.6
341.6
288.3
1 h 5 h
462.0
448.4
429.0
400.9
363.0
332.9
313.5
288.3
249.4
327.1
320.3
308.6
292.1
268.9
250.4
238.8
223.2
200.9
3 h 10 h
217.4
216.4
212.6
205.8
195.1
185.4
178.6
167.9
151.4
178.6
178.6
176.6
172.8
165.0
157.2
151.4
143.6
132.0
8 h
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
2319.7
2106.2
1873.2
1625.7
1358.8
1184.1
1072.5
945.4
752.2
Cells (V) 30 m
2222.6
2023.7
1810.1
1582.1
1329.7
1159.9
1048.2
927.9
741.5
1946.0
1781.0
1611.2
1426.8
1222.9
1077.4
980.3
813.4
706.6
15 m 2 h
1543.2
1431.6
1310.3
1174.4
1028.8
921.1
849.3
764.8
635.7
1087.1
1048.2
994.9
923.0
828.9
755.1
706.6
645.4
553.2
1 h 5 h
828.9
807.5
779.4
738.6
678.4
628.0
594.0
549.4
481.4
600.8
592.1
572.6
548.4
509.6
476.6
457.1
430.0
391.1
3 h 10 h
407.6
406.7
401.8
391.1
373.7
357.2
345.5
326.1
297.0
339.7
339.7
337.8
331.0
318.4
304.8
295.1
281.5
260.1
8 h
Discharge Constant Power (Watts at 20°C)
Discharge Constant Current (Amperes at 20°C)
Part of our Network Power range
Length 210 mmWidth 275 mmHeight (H1) 797 mmTotal height (H2) 810 mmDry weight 77.1 kgFilled weight 105.6 kg
Dimensions and weight
Compliant with IEC60896-11
ET/DATAOPZSSTANDBY 1500V3
W
L
H1 H2
Eternity Technologies vented lead-acid batteries for the standby power market. Eternity Technologies OPzS batteries have optimised design resulting in a low maintenance, reliable energy storage solution for critical and unstable conditions.
14 OPzS-ET 1750(2V 1925Ah @ 10hr)
High energy density
Robust tubular positive electrode design, compliant with DIN 40736
Minimal maintenance due to low antimony alloy and large electrolyte volume
Operating temperature -20°C to +55°C
EUROBAT design life: Long Life > 12 years
Fully recyclable with low CO2 footprint
FeaturesNominal Voltage 2VNumber of cells 1Design Life 20 years
Nominal Capacity 20°C (68°F)10 hour rate (192.5A, 1.8V) 1925Ah5 hour rate (340A, 1.75V) 1701Ah1 hour rate (1103A, 1.6V) 1103Ah
Internal ResistanceFully Charged Battery 20°C (68°F) 0.20mOhm
ElectrolyteNominal S.G at 20°C = 1.240kg/l
Operating Temperature Range -20°C to +55°C
Maximum Discharge Current 20°C (68°F) 1869A
Charge Methods: Constant Voltage Charge 20°C (68°F)Cycle use 2.40V (time limited) Maximum charging current 770AStandby use 2.25V ± 1% Temperature compensation -3.0mV/°C/Cell Terminal torque 23Nm Telecommunications/ Mobile Phone Stations
Traffic Systems
UPS Systems
Emergency Lighting
Electrical Switching
Applications
Performance characteristics
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
1818
1604
1390
1176
963
826
737
643
504
Cells (V) 30 m
1707
1519
1330
1129
924
799
714
625
493
1437
1292
1151
997
833
727
657
578
462
15 m 2 h
1104
1010
907
798
683
606
554
495
406
739
705
660
603
532
481
447
405
343
1 h 5 h
539
524
501
468
424
388
365
335
291
381
373
360
341
314
293
279
261
234
3 h 10 h
254
252
248
240
227
216
208
196
177
208
208
206
201
193
183
177
168
154
8 h
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
2956
2678
2387
2070
1737
1514
1365
1202
958
Cells (V) 30 m
2798
2550
2289
1993
1673
1467
1326
1168
937
2421
2216
2006
1780
1523
1343
1223
1014
881
15 m 2 h
1882
1745
1591
1429
1249
1121
1035
928
774
1292
1245
1176
1095
984
894
838
765
659
1 h 5 h
967
945
911
864
792
732
692
637
561
699
689
678
639
595
557
534
502
456
3 h 10 h
477
475
469
457
434
415
402
381
347
395
395
394
385
371
355
346
329
304
8 h
Discharge Constant Power (Watts at 20°C)
Discharge Constant Current (Amperes at 20°C)
Part of our Network Power range
Length 214 mmWidth 399 mmHeight (H1) 772 mmTotal height (H2) 785 mmDry weight 93.5 kgFilled weight 133.5 kg
Dimensions and weight
Compliant with IEC60896-11
ET/DATAOPZSSTANDBY 1750V3
W
L
H1 H2
Eternity Technologies vented lead-acid batteries for the standby power market. Eternity Technologies OPzS batteries have optimised design resulting in a low maintenance, reliable energy storage solution for critical and unstable conditions.
15 OPzS-ET 1875(2V 2062.5Ah @ 10hr)
High energy density
Robust tubular positive electrode design, compliant with DIN 40736
Minimal maintenance due to low antimony alloy and large electrolyte volume
Operating temperature -20°C to +55°C
EUROBAT design life: Long Life > 12 years
Fully recyclable with low CO2 footprint
FeaturesNominal Voltage 2VNumber of cells 1Design Life 20 years
Nominal Capacity 20°C (68°F)10 hour rate (206.3A, 1.8V) 2062.5Ah5 hour rate (364.9A, 1.75V) 1823.4Ah1 hour rate (1182.5A, 1.6V) 1182.5Ah
Internal ResistanceFully Charged Battery 20°C (68°F) 0.17mOhm
ElectrolyteNominal S.G at 20°C = 1.240kg/l
Operating Temperature Range -20°C to +55°C
Maximum Discharge Current 20°C (68°F) 2002.5A
Charge Methods: Constant Voltage Charge 20°C (68°F)Cycle use 2.40V (time limited) Maximum charging current 825 AStandby use 2.25V ± 1% Temperature compensation -3.0mV/°C/Cell Terminal torque 23Nm Telecommunications/ Mobile Phone Stations
Traffic Systems
UPS Systems
Emergency Lighting
Electrical Switching
Applications
Performance characteristics
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
Cells (V) 30 m
1828.8
1627.1
1425.4
1210.0
990.0
856.1
765.4
670.1
528.0
1540.0
1384.1
1232.9
1067.9
892.9
779.2
704.0
619.7
495.0
15 m 2 h
1182.5
1081.7
971.6
855.3
731.5
649.0
594.0
529.9
434.5
792.0
755.3
706.8
646.2
570.2
515.2
478.5
433.6
367.6
1 h 5 h
577.5
561.0
536.3
501.4
453.8
416.2
391.4
359.3
311.6
407.9
399.7
385.9
364.9
336.4
313.5
298.9
279.6
251.2
3 h 10 h
272.3
270.4
265.9
257.6
242.9
231.0
222.8
209.9
189.8
222.8
222.8
220.9
215.4
206.3
196.1
189.8
179.6
165.0
8 h
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
3167.1
2869.1
2557.5
2218.3
1860.8
1622.5
1462.1
1287.9
1026.7
Cells (V) 30 m
2997.5
2731.7
2452.1
2135.8
1792.1
1572.1
1420.9
1251.3
1003.8
2594.2
2374.1
2149.6
1906.7
1631.6
1439.2
1310.8
1086.3
944.2
15 m 2 h
2016.7
1870.0
1705.0
1530.8
1338.4
1200.8
1109.2
994.6
829.6
1384.1
1333.8
1260.4
1173.4
1054.1
957.9
898.3
819.5
705.8
1 h 5 h
1035.8
1012.9
976.2
925.9
848.8
784.7
741.6
682.9
601.3
748.9
737.9
726.0
684.8
637.1
596.7
572.0
538.1
488.6
3 h 10 h
510.6
508.8
502.3
489.5
464.7
444.6
430.9
407.9
372.2
423.5
423.5
421.7
412.5
397.9
380.4
370.3
352.0
325.4
8 h
Discharge Constant Power (Watts at 20°C)
Discharge Constant Current (Amperes at 20°C)
Part of our Network Power range
Length 214 mmWidth 399 mmHeight (H1) 772 mmTotal height (H2) 785 mmDry weight 97.5 kgFilled weight 142.5 kg
Dimensions and weight
Compliant with IEC60896-11
ET/DATAOPZSSTANDBY 1875V2
1947.9
1718.7
1489.6
1260.4
1031.3
885.5
789.3
689.3
539.9
W
L
H1 H2
Eternity Technologies vented lead-acid batteries for the standby power market. Eternity Technologies OPzS batteries have optimised design resulting in a low maintenance, reliable energy storage solution for critical and unstable conditions.
16 OPzS-ET 2000(2V 2200Ah @ 10hr)
High energy density
Robust tubular positive electrode design, compliant with DIN 40736
Minimal maintenance due to low antimony alloy and large electrolyte volume
Operating temperature -20°C to +55°C
EUROBAT design life: Long Life > 12 years
Fully recyclable with low CO2 footprint
FeaturesNominal Voltage 2VNumber of cells 1Design Life 20 years
Nominal Capacity 20°C (68°F)10 hour rate (220A, 1.8V) 2200Ah5 hour rate (389A, 1.75V) 1945Ah1 hour rate (1261A, 1.6V) 1261Ah
Internal ResistanceFully Charged Battery 20°C (68°F) 0.17mOhm
ElectrolyteNominal S.G at 20°C = 1.240kg/l
Operating Temperature Range -20°C to +55°C
Maximum Discharge Current 20°C (68°F) 2136A
Charge Methods: Constant Voltage Charge 20°C (68°F)Cycle use 2.40V (time limited) Maximum charging current 880AStandby use 2.25V ± 1% Temperature compensation -3.0mV/°C/Cell Terminal torque 23Nm Telecommunications/ Mobile Phone Stations
Traffic Systems
UPS Systems
Emergency Lighting
Electrical Switching
Applications
Performance characteristics
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
2077.8
1833.3
1588.9
1344.4
1100.0
944.5
841.9
735.3
575.9
Cells (V) 30 m
1950.7
1735.6
1520.4
1290.7
1056.0
913.2
816.4
714.8
563.2
1642.7
1476.4
1315.1
1139.1
952.4
831.1
750.9
661.0
528.0
15 m 2 h
1261.3
1153.8
1036.4
912.3
780.3
692.3
633.6
565.2
463.5
844.8
805.7
753.9
689.3
608.2
549.5
510.4
462.5
392.1
1 h 5 h
616.0
598.4
572.0
534.8
484.0
443.9
417.5
383.3
332.4
435.1
426.3
411.6
389.2
358.8
334.4
318.8
298.2
267.9
3 h 10 h
290.4
288.4
283.6
274.8
259.1
246.4
237.6
223.9
202.4
237.6
237.6
235.6
229.8
220.0
209.2
202.4
191.6
176.0
8 h
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
3378.2
3060.4
2728.0
2366.2
1984.9
1730.7
1559.6
1373.8
1095.1
Cells (V) 30 m
3197.3
2913.8
2615.6
2278.2
1911.6
1676.9
1515.6
1334.7
1070.7
2767.1
2532.4
2292.9
2033.8
1740.4
1535.1
1398.2
1158.7
1007.1
15 m 2 h
2151.1
1994.7
1818.7
1632.9
1427.6
1280.9
1183.1
1060.9
884.9
1476.4
1422.7
1344.4
1251.6
1124.4
1021.8
958.2
874.1
752.9
1 h 5 h
1104.9
1080.4
1041.3
987.6
905.4
837.0
791.0
728.4
641.4
798.8
787.1
774.4
730.4
679.6
636.5
610.1
574.0
521.2
3 h 10 h
544.6
542.7
535.8
522.1
495.7
474.2
459.6
435.1
397.0
451.7
451.7
449.8
440.0
424.4
405.8
395.0
375.5
347.1
8 h
Discharge Constant Power (Watts at 20°C)
Discharge Constant Current (Amperes at 20°C)
Part of our Network Power range
Length 214 mmWidth 399 mmHeight (H1) 772 mmTotal height (H2) 785 mmDry weight 103.8 kgFilled weight 146.2 kg
Dimensions and weight
Compliant with IEC60896-11
ET/DATAOPZSSTANDBY 2000V4
W
L
H1 H2
Eternity Technologies vented lead-acid batteries for the standby power market. Eternity Technologies OPzS batteries have optimised design resulting in a low maintenance, reliable energy storage solution for critical and unstable conditions.
18 OPzS-ET 2250(2V 2475Ah @ 10hr)
High energy density
Robust tubular positive electrode design, compliant with DIN 40736
Minimal maintenance due to low antimony alloy and large electrolyte volume
Operating temperature -20°C to +55°C
EUROBAT design life: Long Life > 12 years
Fully recyclable with low CO2 footprint
FeaturesNominal Voltage 2VNumber of cells 1Design Life 20 years
Nominal Capacity 20°C (68°F)10 hour rate (247.5A, 1.8V) 2475Ah5 hour rate (438.5A, 1.75V) 2191.5Ah1 hour rate (1414A, 1.6V) 1414Ah
Internal ResistanceFully Charged Battery 20°C (68°F) 0.15mOhm
ElectrolyteNominal S.G at 20°C = 1.240kg/l
Operating Temperature Range -20°C to +55°C
Maximum Discharge Current 20°C (68°F) 2408A
Charge Methods: Constant Voltage Charge 20°C (68°F)Cycle use 2.40V (time limited) Maximum charging current 990AStandby use 2.25V ± 1% Temperature compensation -3.0mV/°C/Cell Terminal torque 23Nm Telecommunications/ Mobile Phone Stations
Traffic Systems
UPS Systems
Emergency Lighting
Electrical Switching
Applications
Performance characteristics
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
2338
2064
1786
1512
1215
1061
946
827
647
Cells (V) 30 m
2197
1958
1706
1454
1189
1030
919
804
633
1847
1666
1476
1282
1070
937
845
689
594
15 m 2 h
1414
1295
1167
1030
878
779
712
636
527
955
906
849
775
685
619
574
521
440
1 h 5 h
693
674
644
601
545
500
470
431
374
490
480
463
438
403
377
359
336
302
3 h 10 h
327
324
319
309
292
277
267
251
228
267
267
265
259
248
236
228
216
198
8 h
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
3801
3447
3063
2661
2192
1940
1750
1547
1229
Cells (V) 30 m
3602
3288
2935
2568
2152
1892
1706
1503
1202
3111
2859
2577
2289
1953
1728
1573
1207
1131
15 m 2 h
2413
2241
2046
1843
1604
1441
1330
1198
1008
1666
1600
1516
1405
1264
1154
1078
986
845
1 h 5 h
1242
1215
1171
1109
1017
942
893
822
721
902
888
860
823
764
718
687
646
588
3 h 10 h
613
610
603
588
559
533
516
488
447
507
507
507
496
477
458
445
423
390
8 h
Discharge Constant Power (Watts at 20°C)
Discharge Constant Current (Amperes at 20°C)
Part of our Network Power range
Length 212 mmWidth 487 mmHeight (H1) 772 mmTotal height (H2) 785 mmDry weight 119 kgFilled weight 165 kg
Dimensions and weight
Compliant with IEC60896-11
ET/DATAOPZSSTANDBY 2250V2
W
L
H1 H2
Eternity Technologies vented lead-acid batteries for the standby power market. Eternity Technologies OPzS batteries have optimised design resulting in a low maintenance, reliable energy storage solution for critical and unstable conditions.
18 OPzS-ET 2400(2V 2400Ah @ 10hr)
High energy density
Robust tubular positive electrode design, compliant with DIN 40736
Minimal maintenance due to low antimony alloy and large electrolyte volume
Operating temperature -20°C to +55°C
EUROBAT design life: Long Life > 12 years
Fully recyclable with low CO2 footprint
FeaturesNominal Voltage 2VNumber of cells 1Design Life 20 years
Nominal Capacity 20°C (68°F)10 hour rate (240A, 1.8V) 2400Ah5 hour rate (425A, 1.75V) 2125Ah1 hour rate (1371A, 1.6V) 1371Ah
Internal ResistanceFully Charged Battery 20°C (68°F) 0.15mOhm
ElectrolyteNominal S.G at 20°C = 1.240kg/l
Operating Temperature Range -20°C to +55°C
Maximum Discharge Current 20°C (68°F) 2335A
Charge Methods: Constant Voltage Charge 20°C (68°F)Cycle use 2.40V (time limited) Maximum charging current 960AStandby use 2.25V ± 1% Temperature compensation -3.0mV/°C/Cell Terminal torque 23Nm Telecommunications/ Mobile Phone Stations
Traffic Systems
UPS Systems
Emergency Lighting
Electrical Switching
Applications
Performance characteristics
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
2267
2001
1731
1466
1179
1029
917
802
627
Cells (V) 30 m
2130
1899
1654
1410
1153
999
891
780
614
1791
1616
1431
1243
1037
909
819
668
576
15 m 2 h
1371
1256
1131
999
851
755
691
617
511
926
879
823
752
664
600
556
505
427
1 h 5 h
672
653
624
583
528
485
456
418
363
475
465
449
425
391
365
348
326
293
3 h 10 h
317
315
309
300
283
268
259
243
221
259
259
257
251
240
229
221
209
192
8 h
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
3686
3343
2970
2580
2126
1881
1697
1500
1191
Cells (V) 30 m
3493
3189
2846
2490
2087
1834
1654
1457
1166
3017
2773
2499
2220
1894
1676
1526
1170
1097
15 m 2 h
2340
2173
1984
1787
1556
1397
1290
1161
977
1616
1551
1470
1363
1226
1119
1046
956
819
1 h 5 h
1204
1179
1136
1076
986
914
866
797
699
874
861
834
798
741
696
666
627
570
3 h 10 h
595
591
585
570
542
517
501
473
434
492
492
491
481
463
444
431
410
378
8 h
Discharge Constant Power (Watts at 20°C)
Discharge Constant Current (Amperes at 20°C)
Part of our Network Power range
Length 212 mmWidth 487 mmHeight (H1) 772 mmTotal height (H2) 785 mmDry weight 119 kgFilled weight 165 kg
Dimensions and weight
Compliant with IEC60896-11
ET/DATAOPZSSTANDBY 2400V2
W
L
H1 H2
Eternity Technologies vented lead-acid batteries for the standby power market. Eternity Technologies OPzS batteries have optimised design resulting in a low maintenance, reliable energy storage solution for critical and unstable conditions.
19 OPzS-ET 2375(2V 2610Ah @ 10hr)
High energy density
Robust tubular positive electrode design, compliant with DIN 40736
Minimal maintenance due to low antimony alloy and large electrolyte volume
Operating temperature -20°C to +55°C
EUROBAT design life: Long Life > 12 years
Fully recyclable with low CO2 footprint
FeaturesNominal Voltage 2VNumber of cells 1Design Life 20 years
Nominal Capacity 20°C (68°F)10 hour rate (261A, 1.8V) 2610Ah5 hour rate (462A, 1.75V) 2310Ah1 hour rate (1498A, 1.6V) 1498Ah
Internal ResistanceFully Charged Battery 20°C (68°F) 0.15mOhm
ElectrolyteNominal S.G at 20°C = 1.240kg/l
Operating Temperature Range -20°C to +55°C
Maximum Discharge Current 20°C (68°F) 2534A
Charge Methods: Constant Voltage Charge 20°C (68°F)Cycle use 2.40V (time limited) Maximum charging current 880AStandby use 2.25V ± 1% Temperature compensation -3.0mV/°C/Cell Terminal torque 23Nm Telecommunications/ Mobile Phone Stations
Traffic Systems
UPS Systems
Emergency Lighting
Electrical Switching
Applications
Performance characteristics
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
2467
2177
1887
1596
1306
1122
1000
873
684
Cells (V) 30 m
2316
2061
1805
1533
1254
1084
969
849
669
1951
1753
1562
1353
1131
987
892
785
627
15 m 2 h
1498
1370
1231
1083
927
822
752
671
550
1003
957
895
819
722
653
606
549
466
1 h 5 h
732
711
679
635
575
527
496
455
395
517
506
489
462
426
397
379
354
318
3 h 10 h
345
342
337
326
308
293
282
266
240
282
282
280
273
261
248
240
228
209
8 h
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
4012
3634
3240
2810
2357
2055
1852
1631
1300
Cells (V) 30 m
3797
3460
3106
2705
2270
1991
1800
1585
1271
3286
3007
2723
2415
2067
1823
1660
1376
1196
15 m 2 h
2554
2369
2160
1939
1695
1521
1405
1260
1051
1753
1689
1596
1486
1335
1213
1138
1038
894
1 h 5 h
1312
1283
1237
1173
1075
994
939
865
762
949
935
920
867
807
756
724
682
619
3 h 10 h
647
644
636
620
589
563
546
517
471
536
536
534
523
504
482
469
446
412
8 h
Discharge Constant Power (Watts at 20°C)
Discharge Constant Current (Amperes at 20°C)
Part of our Network Power range
Length 212 mmWidth 487 mmHeight (H1) 772 mmTotal height (H2) 785 mmDry weight 122.0 kgFilled weight 172.0kg
Dimensions and weight
Compliant with IEC60896-11
ET/DATAOPZSSTANDBY 2375V2
W
L
H1 H2
Eternity Technologies vented lead-acid batteries for the standby power market. Eternity Technologies OPzS batteries have optimised design resulting in a low maintenance, reliable energy storage solution for critical and unstable conditions.
20 OPzS-ET 2500(2V 2750Ah @ 10hr)
High energy density
Robust tubular positive electrode design, compliant with DIN 40736
Minimal maintenance due to low antimony alloy and large electrolyte volume
Operating temperature -20°C to +55°C
EUROBAT design life: Long Life > 12 years
Fully recyclable with low CO2 footprint
FeaturesNominal Voltage 2VNumber of cells 1Design Life 20 years
Nominal Capacity 20°C (68°F)10 hour rate (275A, 1.8V) 2750Ah5 hour rate (487A, 1.75V) 2435Ah1 hour rate (1571A, 1.6V) 1571Ah
Internal ResistanceFully Charged Battery 20°C (68°F) 0.13mOhm
ElectrolyteNominal S.G at 20°C = 1.240kg/l
Operating Temperature Range -20°C to +55°C
Maximum Discharge Current 20°C (68°F) 2676A
Charge Methods: Constant Voltage Charge 20°C (68°F)Cycle use 2.40V (time limited) Maximum charging current 1100AStandby use 2.25V ± 1% Temperature compensation -3.0mV/°C/Cell Terminal torque 23Nm Telecommunications/ Mobile Phone Stations
Traffic Systems
UPS Systems
Emergency Lighting
Electrical Switching
Applications
Performance characteristics
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
2597.8
2293.3
1983.9
1679.5
1350.4
1178.6
1050.9
919.3
718.9
Cells (V) 30 m
2440.6
2175.4
1895.5
1615.6
1321.0
1144.2
1021.4
893.8
703.2
2052.7
1851.3
1640.2
1424.1
1188.4
1041.1
938.9
765.1
660.0
15 m 2 h
1571.4
1438.8
1296.4
1144.2
975.3
865.3
791.6
707.1
585.4
1060.7
1006.7
942.9
861.3
761.2
687.5
637.4
578.5
489.1
1 h 5 h
770.0
748.4
715.0
667.9
605.0
555.9
522.5
479.3
415.4
544.1
533.3
514.6
487.1
447.9
418.4
398.8
373.2
335.9
3 h 10 h
363.4
360.4
354.6
343.8
324.1
307.4
296.6
278.9
253.4
296.6
296.6
294.6
287.8
275.0
262.2
253.4
239.6
220.0
8 h
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
4223.2
3830.4
3403.1
2956.3
2435.7
2155.8
1944.6
1718.8
1365.2
Cells (V) 30 m
4002.2
3653.6
3260.7
2853.1
2391.5
2101.8
1895.5
1669.6
1335.7
3457.1
3177.2
2862.9
2543.8
2170.5
1920.1
1748.2
1340.6
1257.1
15 m 2 h
2681.3
2489.7
2273.7
2047.8
1782.6
1600.9
1478.1
1330.8
1119.6
1851.3
1777.7
1684.4
1561.6
1404.5
1281.7
1198.2
1095.1
938.9
1 h 5 h
1379.9
1350.4
1301.3
1232.6
1129.5
1047.0
992.0
913.4
801.4
1001.8
987.1
955.6
914.4
848.6
797.5
763.1
717.9
653.1
3 h 10 h
681.6
677.7
669.8
653.1
620.7
592.2
573.6
542.1
497.0
563.8
563.8
562.8
551.0
530.4
508.8
494.0
469.5
433.1
8 h
Discharge Constant Power (Watts at 20°C)
Discharge Constant Current (Amperes at 20°C)
Part of our Network Power range
Length 212 mmWidth 487 mmHeight (H1) 772 mmTotal height (H2) 785 mmDry weight 127.5 kgFilled weight 178.8 kg
Dimensions and weight
Compliant with IEC60896-11
ET/DATAOPZSSTANDBY 2500V3
W
L
H1 H2
Eternity Technologies vented lead-acid batteries for the standby power market. Eternity Technologies OPzS batteries have optimised design resulting in a low maintenance, reliable energy storage solution for critical and unstable conditions.
22 OPzS-ET 2750(2V 3025Ah @ 10hr)
High energy density
Robust tubular positive electrode design, compliant with DIN 40736
Minimal maintenance due to low antimony alloy and large electrolyte volume
Operating temperature -20°C to +55°C
EUROBAT design life: Long Life > 12 years
Fully recyclable with low CO2 footprint
FeaturesNominal Voltage 2VNumber of cells 1Design Life 20 years
Nominal Capacity 20°C (68°F)10 hour rate (303A, 1.8V) 3025Ah5 hour rate (535A, 1.75V) 2825Ah1 hour rate (1729A, 1.6V) 1729Ah
Internal ResistanceFully Charged Battery 20°C (68°F) 0.11mOhm
ElectrolyteNominal S.G at 20°C = 1.240kg/l
Operating Temperature Range -20°C to +55°C
Maximum Discharge Current 20°C (68°F) 2944A
Charge Methods: Constant Voltage Charge 20°C (68°F)Cycle use 2.40V (time limited) Maximum charging current 1210AStandby use 2.25V ± 1% Temperature compensation -3.0mV/°C/Cell Terminal torque 23Nm Telecommunications/ Mobile Phone Stations
Traffic Systems
UPS Systems
Emergency Lighting
Electrical Switching
Applications
Performance characteristics
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
2858.6
2515.8
2183.0
1845.3
1507.5
1295.7
1159.6
1013.4
791.5
Cells (V) 30 m
2682.2
2389.8
2087.3
1779.7
1457.0
1255.4
1124.3
984.1
773.4
2258.7
2031.8
1799.9
1562.9
1310.8
1144.5
1033.5
910.5
726.0
15 m 2 h
1729.3
1583.1
1426.8
1255.4
1073.9
951.9
871.2
777.4
637.3
1164.6
1109.2
1033.5
947.8
836.9
756.3
700.8
636.3
538.5
1 h 5 h
847.0
821.8
786.5
735.1
665.5
611.1
574.8
527.4
456.8
599.0
586.9
565.7
535.4
493.1
460.8
438.6
410.4
369.1
3 h 10 h
399.3
396.3
390.2
378.1
357.0
338.8
326.7
307.5
278.3
326.7
326.7
323.7
315.6
302.5
288.4
278.3
264.2
242.0
8 h
10 m
1.60
1.65
1.70
1.75
1.80
1.83
1.85
1.87
1.90
4643.4
4199.7
3746.0
3246.8
2722.5
2369.6
2147.8
1895.7
1502.4
Cells (V) 30 m
4396.3
4013.2
3589.7
3141.0
2636.8
2304.0
2087.3
1840.2
1467.1
3806.5
3483.8
3141.0
2788.0
2389.8
2112.5
1920.9
1593.2
1381.4
15 m 2 h
2949.4
2737.6
2505.7
2248.6
1966.3
1759.5
1623.4
1462.1
1215.0
2031.8
1956.2
1845.3
1719.2
1547.8
1406.6
1315.9
1205.0
1033.5
1 h 5 h
1522.6
1482.3
1426.8
1356.2
1245.3
1149.5
1089.0
1004.3
881.3
1099.1
1084.0
1048.7
1005.3
934.7
878.3
839.9
789.5
717.9
3 h 10 h
748.2
745.2
737.1
717.9
683.7
652.4
632.2
597.9
545.5
621.1
621.1
618.1
604.0
583.8
559.6
542.5
518.3
476.9
8 h
Discharge Constant Power (Watts at 20°C)
Discharge Constant Current (Amperes at 20°C)
Part of our Network Power range
Length 212 mmWidth 575 mmHeight (H1) 772 mmTotal height (H2) 785 mmDry weight 138.4 kgFilled weight