    Product Description Area Page

    Series Classification No.

    Incandescent

    AEV Incandescent Zone 1 5-2

    AEVA-EOLA Obstruction Marker Zone 1 5-6

    T100A Small Bulkhead Luminaire Zone 1 5-7

    Fluorescent

    eLLK92 Ceiling Mount Lighting Fixtures Zone 1 5-8

    eLLM92 Pole Mount Lighting Fixtures Zone 1 5-11

    eLL92 Emergency Lighting Fixtures Zone 1 5-13

    AEVF Exd Fluorescent Luminaires Zone 1and Zone 21&22 5-15

    NDFA Exn/DIP Heavy Duty Fluorescent Zone 2and Zone 21&22 5-16

    nLLK Exn/DIP Fluorescent Lighting Fixtures Zone 2and Zone 21&22 5-18

    H.I.D.

    AEVBH Large Bulkhead Luminaire Zone 1

    and Zone 21&22 5-20

    EVM Hazard Gard HID Lighting Fixtures Zone 1Integral Ballast Factory Sealed and Zone 21&22 5-21

    EVME Exde Hazard Gard HID Lighting Fixtures Zone 1Integral Ballast and Zone 21&22 5-26

    NVMV Champ HID Exn / DIP Zone 2Lighting Fixtures and Zone 21&22 5-34

    Floodlights

    NFMV Exn Floodlight Luminaire Zone 2and Zone 21&22 5-39

    Beacons

    FSFB301 Flashing Beacon Zone 1

    and Zone 21&22 5-42FRFB301 Rotating Beacon Zone 1

    and Zone 21&22 5-43

    5-1Crouse-Hinds

    May 2003 Copyright 2003 Cooper Industries, Inc

    Hazardous

    5Area

    Lighting

    Hazardous Area Lighting

  • 7/23/2019 4. Haz Area Lighting

    2/44

    5-2Crouse-Hinds

    Hazardous

    5Area

    Lighting

    May 2003 Copyright 2003 Cooper Industries, Inc

    AEV

    Incandescent

    Lighting Fixtures

    Application:AEV incandescent lighting fixtures are

    used:

    In locations which are hazardousdue to the presence of flammable

    vapours or gases and where

    dampness or corrosion are present

    In petroleum refineries, chemicaland petrochemical plants and other

    process industry facilities where

    similar hazards exist

    As pendant, ceiling, wall bracket orbulkhead fixtures indoors for general

    area or room lighting, or outdoors for

    "spot" lighting

    Features:

    Factory sealed - no external sealneeded

    Easy to assemble and relamp Shock absorbing receptacle

    Gasket seals out dirt and liquids

    Positive locking of globe holder Inner reflector eliminates upwardspill light

    Light weight, corrosion resistant,copper-free aluminium

    Standard Materials:

    Body and guard ........ Copper freealuminium

    Glass ..... configurated glass, heatand impact resistant

    Standard Finish: Body and guard ....................Greypolyurethane

    Size Ranges:

    20mm through 40mm hubs

    Capacity Ranges:

    100W to 300W incandescent 160Wself ballasted mercury vapour

    25W SL fluorescent lamp

    Options:

    Reflectors Exit Sign AEVX ........ SeeAccessories on page 5-4

    Temperature Classification to AS2480Incandescent Self-Ballasted Mercury SL FluorescentLamp Size T Rating Lamp Size T Rating Lamp Size T Rating100W T5 160W T4 18W T6150W T5 25W T6

    200W T5300W T4

    Compliances:

    AS2380 Electrical equipment forexplosive atmospheres - Flameproof

    enclosure

    AS1939 - Degrees of Protection IP66 Certificate of Compliance No. Ex 491

    Flameproof, Exd, IIC, IP66

    Zone 1

  • 7/23/2019 4. Haz Area Lighting

    3/44

    5-3Crouse-Hinds

    May 2003 Copyright 2003 Cooper Industries, Inc

    Hazardous

    5Area

    Lighting

    Max. Lamp Hub WallSize Style Size Pendant Ceiling Bracket Bulkhead

    With- 20mm AEVA211 AEVCX211 AEVBX211 AEVJ211150W Incandescent Guard 25mm AEVA221 AEVCX221 AEVBX221 AEVJ221

    SL 18W Fluorescent Without- 20mm AEVA210 AEVCX210 AEVBX210 AEVJX210Guard 25mm AEVA220 AEVCX220 AEVBX220 AEVJX220

    With - 20mm AEVA311 AEVCX311 AEVBX311 AEVJ311300W Incandescent Guard 25mm AEVA321 AEVCX321 AEVBX321 AEVJ321

    SL25W Fluorescent Without- 20mm AEVA310 AEVCX310 AEVBX310 AEVJ310

    160W S/B M/V Guard 25mm AEVA320 AEVCX320 AEVBX320 AEVJ320Notes:1: Ratings are for lamp base up mounting2: AEVBX and AEVJ fixtures take 30 angle reflectors only

    Dimensions:20mm 25mm

    Max. Lamp Size Type A B C D E F F150W AEVA 184 322 298Incandescent AEVCX 184 347 324 16 20SL18 Fluorescent AEVBX 184 390 368 318 16 20

    AEVJ 184 359 337 244 238

    300W AEVA 216 375 343Incandescent AEVCX 216 397 368 16 20SL25 Fluorescent AEVBX 216 441 413 333 16 20160W S/B M/V AEVJ 216 413 384 267 260Notes:1: Ratings are for lamp base up mounting2: When angle reflectors are used, dimension "b" should be changed as follows: add 70mm to AEVA, AEVBX and AEVCX fixtures.

    Add 76mm to AEVJ fixtures.3. Remove reflector for application with SL25W lamp

    Ordering Information:

  • 7/23/2019 4. Haz Area Lighting

    4/44

    5-4Crouse-Hinds

    Hazardous

    5Area

    Lighting

    May 2003 Copyright 2003 Cooper Industries, Inc

    Replacement Parts & Accessories

    Receptacles, Guards, Glass &Holder Assemblies

    Glass &Lamp Holder

    Fixture Receptacle Guards AssembliesSize Cat. No. Cat. No. Cat. No.

    100W-150W EV60 EV505 EV78

    200W-300W EV60 EV502 EV7202

    Exit Sign CoverCat. No. AEVXA3584

    Reflectors

    Material: Dome and 30 angle ... white fibreglass reinforcedpolyester (Krydon)

    High bay ... etched Alzak aluminium with natural finish

    Max. Lamp Size Style Diam. Cat. No.

    150W incandescent} Dome 300mm RD6318W fluorescent 30Angle 300mm RA63

    300W incandescent Dome 400mm RD72

    25W fluorescent } 30 Angle 400mm RA72250W S/B M/V High Bay 370mm EV2912

    Photometric Data

    Fixture with glass,

    30 angle reflectorwithout guard

    Lamp : 200W

    TotalLumens Eff%

    WithGuard 2090 55.0WithoutGuard 2481 65.3

    Measurements taken from A-A' plane

    High Bay

    Lamp Receptacles

    30 Angle Guards

    DomeGlass and holder assemblies

  • 7/23/2019 4. Haz Area Lighting

    5/44

    5-5Crouse-Hinds

    May 2003 Copyright 2003 Cooper Industries, Inc

    Hazardous

    5Area

    Lighting

    Photometric Data

    Fixture with glass andwith or without guard

    Lamp Data: 100W through 300WNote: All data provided is for 200W incandescent lamp.Use following candlepower / lumens multipliers for other lamp sizes: 100W 0.44; 150W 0.72; 300W 1.57

    Example: Zonallumens for 200Wlamp without guardfor 20-30 is 218.Zonal lumens for150W lamp for 20-

    30 is 218 x 0.72=157

    Example: Zonallumens for 200Wlamp without guardfor 20-30 is 366.Zonal lumens for

    150W lamp for 20-30 is 366 x 0.72=263

    Coefficient of UtilisationEffective Floor Cavity Reflectance 20%

    % Reflectance Room Cavity RatioEff.Ceil. Wall 1 2 3 4 5

    50 .706 .601 .521 .457 .40380 30 .659 .537 .451 .382 .330

    10 .618 .483 .395 .326 .275

    50 .671 .572 .497 .435 .38470 30 .629 .513 .432 .367 .316

    10 .590 .465 .380 .314 .265

    50 .605 .515 .449 .393 .34950 30 .571 .468 .395 .336 .291

    10 .541 .426 .351 .292 .247

    50 .545 .464 .404 .355 .31630 30 .519 .426 .361 .308 .266

    10 .494 .392 .324 .269 .229

    50 .491 .416 .363 .319 .28410 30 .469 .385 .327 .280 .244

    10 .449 .358 .296 .247 .210% Reflectance Room Cavity Ratio

    Eff.Ceil. Wall 6 7 8 9 1050 .362 .324 .291 .265 .234

    80 30 .290 .254 .224 .200 .17010 .238 .207 .177 .155 .129

    50 .345 .310 .279 .254 .22370 30 .278 .244 .216 .192 .165

    10 .228 .199 .171 .151. .126

    50 .313 .282 .254 .232 .20550 30 .256 .224 .200 .178 .153

    10 .214 .185 .160 .141 .117

    50 .284 .255 .232 .212 .18730 30 .236 .208 .183 .164 .140

    10 .198 .171 .149 .131 .107

    50 .257 .233 .210 .192 .17010 30 .215 .191 .168 .151 .128

    10 .183 .158 .138 .121 .099

    Coefficient of UtilisationEffective Floor Cavity Reflectance 20%

    % Reflectance Room Cavity RatioEff.Ceil. Wall 1 2 3 4 5

    50 .700 .618 .547 .485 .43280 30 .672 .576 .497 .428 .373

    10 .648 .540 .457 .385 .330

    50 .685 .606 .538 .476 .42370 30 .659 .566 .490 .424 .369

    10 .636 .535 .453 .382 .328

    50 .655 .583 .519 .459 .41050 30 .635 .550 .478 .414 .362

    10 .617 .520 .445 .378 .325

    50 .629 .561 .501 .444 .39730 30 .613 .534 .466 .405 .254

    10 .597 .509 .437 .373 .321

    50 .607 .541 .484 .430 .38510 30 .593 .518 .455 .395 .348

    10 .580 .498 .430 .367 .317% Reflectance Room Cavity Ratio

    Eff.Ceil. Wall 6 7 8 9 1050 .389 .350 .316 .289 .252

    80 30 .331 .294 .261 .234 .19710 .290 .255 .221 .196 .162

    50 .383 .345 .312 .285 .24870 30 .328 .328 .259 .232 .197

    10 .287 .252 .220 .196 .162

    50 .370 .335 .302 .277 .24250 30 .322 .284 .254 .228 .194

    10 .285 .250 .219 .195 .161

    50 .360 .324 .294 .270 .23530 30 .316 .281 .249 .224 .191

    10 .283 .247 .217 .193 .159

    50 .349 .317 .286 .262 .23010 30 .310 .277 .246 .221 .188

    10 .279 .245 .216 .191 .158

    Fixture with glass, domereflector and with or without guard

  • 7/23/2019 4. Haz Area Lighting

    6/44

    5-6Crouse-Hinds

    Hazardous

    5Area

    Lighting

    May 2003 Copyright 2003 Cooper Industries, Inc

    AEV-EOLA

    Obstruction Marker

    Application:AEV incandescent lighting fixtures are

    used:

    To aid aircraft navigation inhazardous locations

    To mark towers and processcolumns in petroleum refineries or

    chemical process plants

    To indicate the presence of drilling

    rigs or other industrial facilities

    Features:

    Easy to assemble and re-lamp Lightweight, corrosion resistant,copper free aluminium

    Red fresnel prismatic lens ensureshigh visibility and avoids glare (other

    colours also available upon request)

    Available in single or double units,pipe or base mount versions

    1 x M20 entry (other entries

    available upon request)

    Standard Materials:

    Body and guard - Copper freealuminium

    External Lens - Configurated glass,heat treated and impact resistant

    Internal Lens - Coloured glass withfresnel configuration

    Standard Finish:

    Body and guard - Greypolyurethane

    Size Ranges: 150W (max) 240/250VIncandescent

    Compliances:

    AS2380 Electrical equipment forexplosive atmospheres - Flameproof

    enclosure

    AS1939 - Degrees of ProtectionIP66

    Certificate of Compliance No.Ex 491

    Flameproof, Exd, IIC, IP66

    Zone 1

    TypeOrder

    Code

    Entry

    Size

    Incandescent

    Lamp

    Lamp

    Holder

    Single Unit

    Pipe MountAEVA-EOLA1* 1 x M20 150W Max E27

    Double Unit

    Pipe MountAEVA-EOLA2* 1 x M20 150W Max E27

    Single

    Base MountAEVCX-EOLA1* 4 x M20 150W Max E27

    Ordering Information

    Dimensions:

  • 7/23/2019 4. Haz Area Lighting

    7/44

    5-7Crouse-Hinds

    May 2003 Copyright 2003 Cooper Industries, Inc

    T100A Small

    Bulkhead

    Luminaire

    Application:

    For use in hazardous areas wherespace is limited and local lighting is

    required

    In areas where low mounting heightrequires a fixture with a low profile

    For wall mounting in confinedspaces such as inspection pits

    For mounting in pre-cast recesses

    Features:

    Cast aluminium body with flatimpact resistant glass, cast guard and

    mounting feet

    The lamp housing is separate fromthe terminal housing which allows

    direct connection to circuit wiring

    without the use of high temperature

    cable.The terminal housing is

    accessible by means of an inspection

    cover

    Internal LPF control gear forfluorescent and HID lamps

    Three 25mm entries, 1 on eachside and 1 in the end

    Reduced maintenance costs whenused with long life HID light sources

    Standard Materials:

    Body and guard........ Copper freealuminium

    Lens...Heat resistant borrosilicateglass

    Standard Finish:

    Natural

    Compliances:

    AS2380 Electrical equipment forexplosive atmospheres - Flameproof

    enclosure

    AS1939 - Degrees of ProtectionIP66

    Certificate of Compliance No.Ex618

    Electrical Rating:

    Incandescent .....................100W

    Mercury vapour ................... 50W High pressure sodium ......... 35W Fluorescent (SL type lamp) ..18W Fluorescent (PL) type lamp) . 9W All types .................... 240V/50Hz

    Ordering Information:Lamp Size & Type Cat. No. Temperature Rating

    100W Incandescent T100A T3

    18W SL type fluorescent T18-SL T6

    9W PL type fluorescent T09-PL T6

    Dimensions:

    Flameproof, Exd, IIB, IP66

    Zone 1

    Hazardous

    5Area

    Lighting

  • 7/23/2019 4. Haz Area Lighting

    8/44

    5-8Crouse-Hinds

    Hazardous

    5Area

    Lighting

    May 2003 Copyright 2003 Cooper Industries, Inc

    Compliances:

    EN50014, EN50019, EN50018,Electrical apparatus for potentially

    explosive atmospheres, General

    Requirements, Increased Safety e,

    Flameproof Enclosure d

    EN60529 Specification for degreesof protection provided by enclosures

    (IP Code) IP66

    PTB ATEX 96 2144 SAA Aus Ex 3558X

    Ordering Information:Type Lamps Rated Power Temp. Catalogue

    Current Factor Class No.

    eLLK92018/18 2 x 18W 0.18A 0.95 T4 1 2265 875 111eLLK92036 1 x 36W 0.18A 0.95 T4 1 2263 875 103

    eLLK92036/36 2 x 36W 0.34A 0.95 T4 1 2266 875 111

    eLLK92058 1 x 58W 0.27A 0.95 T4 1 2264 875 111

    eLLK92058/58 2 x 58W 0.53A 0.95 T4 1 2267 875 111

    Bi Pin Fluorescent Lamp

    eLLK92 Series

    Fluorescent

    Lighting Fixtures

    Application:

    Suitable for use in areas wherehazardous liquids, gases or vapours

    are present during normal operation

    Suitable for arduous conditions orextreme environments

    Ideal for walkways, bridges,tunnels, security lighting, roadways

    and process plants where reliable

    lighting is required for safe operation

    Low profile for use in areas wherevery low mounting heights or other

    space restrictions exist

    Features:

    Incorporates CEAG designedelectronic ballasts which are suitable

    for use with bi-pin (to IEC 81)

    fluorescent lamps

    Electronic ballast provides highluminous efficiency, lower energy

    consumption and longer service life

    of the lamps

    Central locking system operatedby standard SW13 hex socket key

    enables fixture to be opened from

    single point on fixture housing

    Diffuser fastened by 10, 20 and 24latch points respectively on 18W,

    36W, and 58W fixtures

    Diffuser hinges from either sideand is also designed to act as a

    convenient lamp support when open

    to simplify lamp replacement

    Automatic disconnect switchensures the isolation of all exposedcomponents when the fixture is

    opened

    Lamp operation on twin lampfixtures is independent so that failure

    of one does not affect the other

    Large internal terminal compartmentwith twist locking knob on the cover

    enables ready wiring access

    Supplied as standard with 2 x M20metal entries at each end, complete

    with through wiring facility

    Wide voltage range

    Standard Materials:

    Housing .... Glass-mat reinforcedpolyester

    Diffuser ........... Polycarbonate

    Electrical Ratings:

    Operating VoltageAC 110 to 254 V 10% 47 - 63HZ

    DC 110 to 230 V 10%

    Lamp configurations2 x 18W, 1 x 36W, 2 x 36W,

    1 x 58W, 2 x 58W

    Bi-pin 26mm diameter

    Terminals ...... L1, L2, L3, L, N, PE6mm2 maximum, 1 wire per terminal

    Ambient Temperature Range .....-25 C to +50 C

    Options:

    Alternate entry sizes available,consult factory for details

    Increased Safety, Exde, IIC, IP66

    Zone 1

  • 7/23/2019 4. Haz Area Lighting

    9/44

    5-9Crouse-Hinds

    May 2003 Copyright 2003 Cooper Industries, Inc

    Hazardous

    5Area

    Lighting

    eLLK92058 & eLLK92058/58

    Dimensions:

    eLLk92018/18

    Mounting Accessories:

    Eye bolt A2Cat No. 2 2480 002 000

    Hex Screw S4Cat No. 2 2480 054 000

    Ceiling Mount D2Cat No. 2 2480 102 000

    Note: Supplied as sets of two

    eLLK92036 & eLLK92036/36

    Pipe Clamp

    Type Pipe Diameter Height H Cat No:

    R12 38-42mm 85mm 2 2480 462 000

    R22 47-50mm 95mm 2 2480 472 000

    R32 58-62mm 105mm 2 2480 482 000

    Dimensions

    & Mounting Accessories

  • 7/23/2019 4. Haz Area Lighting

    10/44

    5-10Crouse-Hinds

    Hazardous

    5Area

    Lighting

    May 2003 Copyright 2003 Cooper Industries, Inc

    Rated luminous flux of lamps 2 x 18 W = 2,700 ImLight efficiency in operation:2 x 18 W = 78%Illumination data acc. to LiTG B 30

    1 x 36 W Fixture

    Rated luminous flux of lamps 1 x 36 W = 3,350 lmLight efficiency in operation:1 x 36 W = 86%Illumination data acc. to LiTG B 30

    Rated luminous flux of lamps 2 x 36 W = 6,700 lmLight efficiency in operation:2 x 36 W = 78%Illumination data acc. to LiTG B 30

    2 x 36 W Fixture

    1 x 58 W Fixture

    Rated luminous flux of lamps 1 x 58 W = 5,200 lm

    Light efficiency in operation:1 x 58 W = 81%Illumination data acc. to LiTG B 30

    Rated luminous flux of lamps 2 x 58 W = 10,400 lm

    Light efficiency in operation:2 x 58 W = 72%Illumination data acc. to LiTG B 30

    2 x 58 W Fixture

    Photometric Data

    2 x 18 W Fixture

  • 7/23/2019 4. Haz Area Lighting

    11/44

    5-11Crouse-Hinds

    May 2003 Copyright 2003 Cooper Industries, Inc

    Hazardous

    5Area

    Lighting

    Ordering Information:Type Lamps Rated Power Temp. Catalogue

    Current Factor Class No.

    eLLM92018/18 2 x 18W 0.18A 0.95 T4 1 2268 875 101

    eLLM92036/36 2 x 36W 0.34A 0.95 T4 1 2269 875 101

    eLLM92 Series

    Fluorescent Pole

    Lighting Fixtures

    Application:

    Suitable for use in areas wherehazardous liquids, gases or vapours

    are present during normal operation

    Suitable for arduous conditions orextreme environments

    Ideal for walkways, bridges,security lighting, roadways and

    process plants where reliable

    lighting is required for safe operation

    To provide overhead lighting frompole end mount position

    Features:

    Incorporates CEAG designedelectronic ballasts which are suitable

    for use with bi-pin (to IEC 81)

    fluorescent lamps

    Electronic ballast provides highluminous efficiency, lower energy

    consumption and longer service life

    of the lamps

    Integral pole mounting sleeverecessed into housing for 44mmpipe (1 1/4 nominal bore)

    Large terminal compartmentreadily accessible and located

    beneath pole mount

    Central locking system operatedby standard SW13 hex socket key

    enables fixture to be opened from

    one point on housing

    Diffuser fastened by 10, 20 and 24latch points respectively on 18W,

    36W and 58W fixtures

    Diffuser hinges from either sideand is also designed to act as aconvenient lamp support when open

    to simply lamp replacement

    Automatic disconnect switchensures the isolation of all exposed

    components when the fixture is

    opened

    Lamp operation on twin lampfixtures is independent so that failure

    of one does not affect the other

    Supplied with 25mm cable glandfor 8-17mm cable

    Wide voltage rangeStandard Materials:

    Housing ....Glass-mat reinforcedpolyester

    Diffuser .......... Polycarbonate

    Electrical Ratings:

    Operating VoltageAC 110 to 254 V 10% 47 - 63HZ

    DC 110 to 230 V 10%

    Lamp configurations........2 x 18W, 2 x 36W

    Bi-pin 26mm diameter

    Terminals ...... L1, N, PE, 2 x 6mm21 wire per terminal

    Ambient Temperature Range .....-25 C to +50 C

    Options:

    Accessory kit for single endedthrough wiring comprising adaptor

    with 2 x M25 cable glands...........

    .................Cat No. 2 2218 602 000

    Bi Pin Fluorescent Lamp

    Compliances:

    EN50014, EN50019, EN50018,Electrical apparatus for potentially

    explosive atmospheres, General

    Requirements, Increased Safety e,

    Flameproof Enclosure d

    EN60529 Specification for degrees

    of protection provided by enclosures

    (IP Code) IP66

    PTB96 ATEX 2144 SAA Aus Ex 3558X

    Increased Safety, Exde, IIC, IP66/67

    Zone 1

  • 7/23/2019 4. Haz Area Lighting

    12/44

    5-12Crouse-Hinds

    Hazardous

    5Area

    Lighting

    May 2003 Copyright 2003 Cooper Industries, Inc

    2 x 18 W Fixture

    Rated luminous flux of lamps 2 x 18 W = 2,700 Im

    Light efficiency in operation:2 x 18 W = 6,700 ImIllumination data acc. to LiTG B 30

    Rated luminous flux of lamps 2 x 36 W = 6,700 lm

    Light efficiency in operation:2 x 36 W = 78%Illumination data acc. to LiTG B 30

    2 x 36 W Fixture

    Dimensions & Photometric Data

    Photometric Data:

    eLLM Pole Mount

    Dimensions:

    Wall Mount Bracket W26Cat No. 2 2485 027 000

    Mounting Accessories:

    Standard Through wiringoption

    Internal View ofTerminal Compartment

  • 7/23/2019 4. Haz Area Lighting

    13/44

    5-13Crouse-Hinds

    May 2003 Copyright 2003 Cooper Industries, Inc

    Standard Materials: Housing .... Glass-mat reinforcedpolyester

    Diffuser ......... Polycarbonate

    Electrical Ratings: Operating VoltageAC 220 to 254 V 10% 47 - 63HZ

    Lamp configurations2 x 18W, 2 x 36WBi-pin 26mm diameter

    Terminals ...... L1, L2, L3, L, N, PE6mm2 maximum, 1 wire per terminal Ambient Temperature Range .....

    -5 C to +50 C

    Emergency operation single lampfor 1.5 hour or 3 hour, set by internalwire terminal link

    eLLK92036/36NiB

    Emergency

    Lighting Fixtures

    Bi Pin Fluorescent Lamp

    Application: Suitable for use in areas wherehazardous liquids, gases or vapoursare present during normal operation

    Suitable for arduous conditions orextreme environments

    In applications where lighting mustbe maintained under emergencyconditions to ensure safe evacuationof personnel

    Ideal for walkways, bridges, tunnels,roadways and process plants where

    reliable lighting is required for safeoperation

    Features: Incorporates CEAG designedelectronic ballasts which are suitablefor use with bi-pin (to IEC 81)fluorescent lamps

    Electronic ballast provides highluminous efficiency, lower energyconsumption and longer service life ofthe lamps

    Intelligent microelectronic controllermonitors battery charge cycleeliminating overcharge and ni-clad

    memory effect, extending battery life Battery charge level indicated bygreen LED display

    Indicates when an operatingduration test is necessary at six monthintervals as required by safetyregulations

    Indication provided after durationtest if a malfunction is apparent

    Battery set can be safely replacedwithin hazardous environment

    Emergency operation can be set for1.5 or 3 hour duration

    Central locking system operated bystandard SW13 hex socket key

    enables fixture to be opened from onepoint of housing

    Diffuser fastened by 10 and 20 latchpoints respectively on 18W and 36Wfixtures

    Diffuser hinges from either side andis also designed to act as aconvenient lamp support when opento simplify lamp replacement

    Automatic disconnect switchensures the isolation of all exposedcomponents when the fixture isopened

    Lamp configuration on twin lampfixtures is dependent so that failure of

    one does not affect the other Incorporates inhibit function set byinternal wire terminal link to disableemergency operation for when poweris intentionally removed. Link can alsobe wired as external switch, for up to10 fixtures per switch

    Ordering Information:Ceiling Mounted Emergency Fittings

    Type Lamps Rated Power Temp. Catalogue

    Current Factor Class No.eLLK92018/18NiB 2 x 18W 0.23A 0.95 ind T4 1 2260 879 111eLLK92036/36NiB 2 x 36W 0.4A 0.95 ind T4 1 2261 879 111

    Pole Mounted Emergency FittingType Lamps Rated Power Temp. Catalogue

    Current Factor Class No.eLLM92018/18NiB 2 x 18W 0.23A 0.95 ind T4 1 2273 879 101

    Compliances: EN50014, EN50019, EN50018, EN50028,EN50020 Electrical apparatus forpotentially explosive atmospheres,General Requirements, IncreasedSafety e, Flameproof Enclosure d,Encapsulation m, Intrinsic Safety i

    EN60529 Specification for degreesof protection provided by enclosures(IP Code) IP66

    PTB96 ATEX2144

    SAA AUS Ex 3558X

    Increased Safety, Exdem ib, IIC, IP66

    Zone 1

    Hazardous

    5Area

    Lighting

  • 7/23/2019 4. Haz Area Lighting

    14/44

    5-14Crouse-Hinds

    Hazardous

    5Area

    Lighting

    May 2003 Copyright 2003 Cooper Industries, Inc

    Features, Dimensions

    & Photometric Data

    eLLk92018/18 Ni Ceiling Mount - Emergency

    eLLK92036/36 Ni Ceiling Mount - Emergency

    eLLM92018/18 Ni Pole Mount - Emergency

    Dimensions:

    Photometric Data:

    Emergency Operation:Apply the following luminous flux factors when determiningperformance under emergency single lamp operation:

    18 W = approx. 1.5 h 90% / 3.0 h 45%36 W = approx. 1.5 h 45% / 3.0 h 25%Rated luminous flux of lamps:1 x 18 W = 1,350 Im1 x 36 W = 3,350 lm

    Charge status indicatedby green LED display

    Microelectronic controllermonitors charge cycle,eliminating over charge and

    Ni-cad memory effect

    Flashing red LED indicateswhen an operating durationtest is necessary at sixmonth intervals as requiredby safety regulations

    Battery set is replaceablewithin hazardous area

    Red LED continues to

    flash after duration test ifa malfunction is apparent

    Battery temperature ismonitored during chargecycleOperation:

    Status of the battery charge cycle is indicated by aseries of five green Light Emitting Diodes (LED), eachof which represents 20% of battery capacity.The levelof charge attained is indicated by the leading greenLED which flashes.The charge cycle is complete whenall five green LEDs are on.

    Emergency operation commences on mains failureor when the main supply is switched off. Duringemergency operation the remaining battery capacity isindicated by the number of LEDs which are on.

    The red LED begins flashing after six months fromthe last successful emergency duration test, or whenduring battery discharge a defective power supply or

    fluorescent lamp is detected.The red LED will continueto flash until a successful duration test is completed.

    Mounting Accessories: Refer to pages 5-9 and 5-12

  • 7/23/2019 4. Haz Area Lighting

    15/44

    5-15Crouse-Hinds

    May 2003 Copyright 2003 Cooper Industries, Inc

    AEVF Series

    Explosionproof

    FluorescentLighting Fixture

    Application:AEVF Luminaires are used to illuminateareas where hazardous liquids, fumes

    or gases are present. Areas such as:

    Spray Booths Drum Filling Areas Process Plants Combustible dusts present

    Features: Luminaire has been designed toutilise the latest technology of compact

    fluorescent lamps

    Cast aluminium body with screwthreaded construction

    Integral control gear in fullyaccessible compartment

    Stainless steel guard and reflector Mounting feet facilitate mounting oneither wall or ceiling

    Ease of installation Reduced initial cost

    Reduced maintenance cost

    Can be supplied with specialEmergency Exit sign

    Can be supplied with externalEmergency Battery Pack for 2 hoursstandby lighting

    Standard Materials:

    Body ......... copper free aluminium Stainless steel guard and reflector

    Standard Finish:

    Grey polyurethane

    Electrical Rating: 240V 50Hz Twin and single lamps PL18, PL24,PL36. 18, 24 and 36W respectively

    Compliances:

    AS2380 Electrical equipment forexplosive atmospheres - Flameproof

    enclosure

    AS2236 Electrical equipment forexplosive atmospheres - Dust excluding

    Ignition proof

    AS1939 Degrees of Protection IP66 Certificate of Compliance No. Ex933X

    Options:

    Emergency Exit Sign ........... NCE Emergency Lighting Battery Pack....................................................NC

    Pole Mount ..............................PM

    Utilisation factors: UF (F) SHR NOM = 1.75Roomreflectance Room Index

    C W F .60 .75 .801.00 1.251.50 2.002.50 3.00 4.00 5.00.70 .50 .20 .22 N/A .24 .26 .29 .31 .35 .37 .38 .40 .42

    .30 .19 N/A .21 .23 .26 .28 .32 .34 .36 .38 .40

    .10 .14 N/A .17 .20 .23 .26 .29 .32 .34 .36 .38.50 .50 .20 .14 N/A .23 .25 .28 .30 .33 .35 .36 .38 .39

    .30 .18 N/A .20 .22 .25 .27 .30 .32 .34 .36 .38

    .10 .15 N/A .17 .19 .22 .25 .28 .30 .32 .35 .36.30 .50 .20 .20 N/A .22 .24 .26 .28 .31 .32 .34 .36 .37

    .30 .15 N/A .18 .21 .24 .26 .29 .31 .32 .34 .35

    .10 .13 N/A .16 .19 .22 .24 .27 .29 .31 .33 .34.00 .00 .00 .13 N/A .16 .17 .20 .22 .25 .26 .28 .30 .31Rating: Photometrically tested without ceiling board.Multiply values by service corrections factors.Calculated in accordance with CIBS Technical Memorandum No. 5 1980.

    Ordering Information:Cat. No. No. & Size of Lamps Entries Temp Rating

    AEVF118 1 x 18W 2 x 25mm T5AEVF136 1 x 36W 2 x 25mm T5AEVF218 2 x 18W 2 x 25mm T5AEVF236 2 x 36W 2 x 25mm T5

    Dimensions: (mm)

    Flameproof, Exd, IIB, IP66

    Zone 1

    Combustible DustZone 21 & 22

    Hazardous

    5Area

    Lighting

  • 7/23/2019 4. Haz Area Lighting

    16/44

    5-16Crouse-Hinds

    Hazardous

    5Area

    Lighting

    May 2003 Copyright 2003 Cooper Industries, Inc

    Application: For use in locations where aconcentration of flammable gases orvapours may occur as the result ofan abnormal situation

    Suitable for DIP locations such asgrain handling facilities or otherareas where hazardous dusts fibres& flyings are present and may

    become suspended in theatmosphere or settle on equipmentor ledges

    Ideal for walkways, bridges,tunnels, security lighting, roadwaysand process plants where reliablelighting is required for safe operation

    For arduous conditions or extremeenvironments

    Low profile for use in areas wherevery low mounting heights or otherspace restrictions make installationdifficult

    Features: Three different mountingarrangements available:Ceiling mountPipe mountHanger mount

    Corrosion resistant FRP housingmakes it ideal for installations inareas where corrosive and / or wetconditions exist during normal plantoperation

    Noryl clips secure prismaticdiffuser to the body to ensurereliable sealing while still allowing

    ease of relamping and maintenance A reliable seal between body anddiffuser is provided by a closed cellnon aging rubber gasket

    Prismatic Diffuser eliminates glarewithout diminishing the amount ofilluminance

    Reflector / gear tray is suspendedon hangers for ease of installationand maintenance

    Standard Materials: Body ......... Grey FRP (Fibreglassreinforced polyester)

    Prismatic Diffuser .......... Mouldedpolycarbonate Gasket ........... Polyurethane foam Quick Release Clips .......... Noryl Cable entry ........................Brass

    Standard Finishes: Body .....................................Grey Prismatic Diffuser ................ Clear

    Options:(Refer to ordering information)

    Through wiring ...... Terminal block

    at each end of the fixture internallywired (4mm2) to facilitate ease ofconnection

    Hanger Mounting ...... Eye Boltsallow for suspension of the fixture byeither chain or steel cable

    Pipe Mounting ..Brackets to allowsuspension from a pipe stanchion orwall bracket

    Emergency Lighting Pack .....integral power pack to give 2 hoursstandby lighting in the event of apower supply failure

    Non standard voltages

    Stainless Steel quick-release clips Other entries available uponrequest

    Electrical Ratings: 240 V, 50 Hz standard. Othervoltages and frequencies on request

    18W, and 36W Temperature rating....

    Exn - T3, DIP - T5

    Compliances: Australian Standard 2238 ElectricalEquipment for explosiveatmospheres ............. Non-sparkingapparatus.Type of Protection n.Certificate of Compliance Ex1153x

    Australian Standard 2236 ElectricalEquipment for explosiveatmospheres ........... Dust-excludingignitionproof enclosure. Certificate ofCompliance Ex1149DIP

    Australian Standard 1939 Degreesof Protection of electrical equipmentIP66

    Robustdiffuser clips

    Brass entry

    NDFA

    Heavy Duty

    FluorescentLighting Fixtures

    Non-Sparking, Exn, IIC, IP66/67

    Zone 2

    Combustible DustZone 21 & 22

  • 7/23/2019 4. Haz Area Lighting

    17/44

    5-17Crouse-Hinds

    May 2003 Copyright 2003 Cooper Industries, Inc

    Hazardous

    5Area

    Lighting

    Ordering Information

    Mounting Accessories :Lighting fixtures supplied completewith ceiling mount brackets. Order pipeclamps and eye bolts separately ifrequired. Two required per fixture.

    Eye boltCat No. EBM6SS

    Ceiling Mount Bracket

    Pipe Clamp

    Pipe Diameter Height H Cat No:

    38-42mm 85mm UN8-43

    47-50mm 95mm UN8-51

    58-62mm 105mm UN8-63

    Dimensions:

    Lamp A BSize mm mm18W 660 55036W 1275 800

    Photometric Data:

    C0 C90 cd/klm

    Typical luminous flux of lamps1 x 18 W = 1,350 Im, 2 x 18 W = 2,700 Im1 x 36 W = 3,350 lm, 2 x 36 W = 6,700 lm

    N D F A 1M 236 8 D M N S EProduct Identifier -

    NDFA

    Entry Size1M- M202M- M251N - 1/2" NPT2N - 3/4" NPT

    Wattage118 - 1x18218 - 2x18

    136 - 1x36236 - 2x6

    Cable Entries0 - No through entryT - Through entriesS - Single through entries

    (2 entries on one side)D - Double through entries

    (2 entries on one side)

    Types of EntryP - PlasticM - Metal

    Securing Clips0 - Plastic

    S - Stainless SteelExit Sign

    0 - NoneE - Exit Sign

    Voltage &Frequency

    1 - 110V / 60Hz2 - 120V / 60Hz3 - 220V / 50Hz4 - 220V / 60Hz5 - 230V / 50Hz6 - 240V / 50Hz8 - ElectronicBallast - 220-245V /

    47-63Hz

    Emergency0 - StandardN - Emergency

  • 7/23/2019 4. Haz Area Lighting

    18/44

    5-18Crouse-Hinds

    Hazardous

    5Area

    Lighting

    May 2003 Copyright 2003 Cooper Industries, Inc

    Application: For use in locations where aconcentration of flammable gases orvapours may occur as the result ofan abnormal situation

    Suitable for DIP locations such asgrain handling facilities or otherareas where hazardous dusts fibres& flyings are present and may

    become suspended in theatmosphere or settle on equipmentor ledges

    Ideal for walkways, bridges,tunnels, security lighting, roadwaysand process plants where reliablelighting is required for safe operation

    For arduous conditions or extremeenvironments

    Low profile for use in areas wherevery low mounting heights or otherspace restrictions make installationdifficult

    Features: Electronic ballast provides highluminous efficiency, lower energyconsumption and longer service lifeof the lamps

    Emergency operation can be setfor 2 hour duration

    Central locking system operatedby standard SW13 hex socket keyenables fixture to be opened fromone point of housing

    Diffuser fastened by 10 and 20latch points respectively on 18Wand 36W fixtures

    Diffuser hinges from either sideand is also designed to act as aconvenient lamp support when opento simplify lamp replacement

    Standard Materials: Body ......... Grey FRP (Fibreglassreinforced polyester)

    Diffuser .... Mouldedpolycarbonate

    Gasket ........... Polyurethane foam Cable entry ........................Brass

    Standard Finishes: Body .....................................Grey

    Prismatic Diffuser ................ Clear

    Options:(Refer to ordering information)

    Through wiring ...... Terminal blockat each end of the fixture internallywired (4mm2) to facilitate ease ofconnection

    Hanger Mounting ...... Eye Boltsallow for suspension of the fixture byeither chain or steel cable

    Pipe Mounting ..Brackets to allowsuspension from a pipe stanchion orwall bracket

    Emergency Lighting Pack .....integral power pack to give 2 hoursstandby lighting in the event of apower supply failure

    Other entries available uponrequest

    Electrical Ratings: 240 V, 50 Hz standard. Othervoltages and frequencies on request

    18W, and 36W Temperature rating.

    - Exn - T4

    Compliances: Australian Standard 2238 ElectricalEquipment for explosive atmospheres............. Non-sparking apparatus.Type of Protection n.

    Certificate of Compliance- Aus Ex 3723- PTB 98 ATEX 2208 (excluding Emergency Luminaires)

    Australian Standard 1939 Degreesof Protection of electrical equipmentIP66

    nLLK

    Heavy Duty

    FluorescentLighting Fixtures

    Non-Sparking, Exn, IIC, IP66/67

    Zone 2

    Combustible DustZone 21 & 22

  • 7/23/2019 4. Haz Area Lighting

    19/44

    5-19Crouse-Hinds

    May 2003 Copyright 2003 Cooper Industries, Inc

    Hazardous

    5Area

    Lighting

    Standard Fixtures

    nLLK98018/18 2 x 18W T4 Electronic 13465218021nLLK98036 1 x 36W T4 Electronic 13465136021

    nLLK98036/36 2 x 36W T4 Electronic 13465236021nLLK98058 1 x 58W T4 Electronic 13465158021nLLK98058/58 2 x 58W T4 Electronic 13465258021

    Emergency Fixtures

    nLLK98018/18N 2 x 18W T4 Electronic nLLK1M2188DMN00nLLK98036N 1 x 36W T4 Electronic nLLK1M1368DMN00nLLK98036/36N 2 x 36W T4 Electronic nLLK1M2368DMN00

    Type. Lamps Temp Classat 400C

    Circuit

    Accessories

    Type Catalogue No.

    Galvanised Eyebolt A2 2 2480 002 000Stainless Steel Ceiling Bracket D92 2 2480 092 000

    Pipe Clamps 43mm UN8-43SPPipe Clamps 51mm UN8-51P

    Options

    Type Catalogue No.

    Diffuser c/w EXIT Sign Add E to Cat. No.

    Dimensions

    Ordering Information

    Ordering Information

    & Dimensions

    CatalogueNo.

  • 7/23/2019 4. Haz Area Lighting

    20/44

    5-20Crouse-Hinds

    Hazardous

    5Area

    Lighting

    May 2003 Copyright 2003 Cooper Industries, Inc

    Ordering Information:Cat. No. Lamp Lamp Entry Temperature

    Size Type Size RatingAEVBH 22201 200W Incandescent 25mm T3AEVBH 42051 50W HPS 25mm T4AEVBH 42071 70W HPS 25mm T4AEVBH 42101 100W HPS 25mm T4AEVBH 42151 150W HPS 25mm T3

    AEVBH 52021 2 x 11W PL Fluorescent 25mm T6AEVBH 82051 50W Mercury Vapour 25mm T3AEVBH 82081 80W Mercury Vapour 25mm T3AEVBH 82101 100W Mercury Vapour 25mm T3AEVBH 82121 125W Mercury Vapour 25mm T3AEVBH 82171 175W Mercury Vapour 25mm T3AEVBH 92171 175W Metal Halide 25mm T3

    AEVBH

    Large Bulkhead

    Luminaire

    Application: The AEVBH bulkhead luminaire issuitable for use with HID, fluorescentand incandescent light sources inZone 1 and Zone 21 & 22 hazardouslocations

    Ideal for areas with low headroom ormounting height where it allows theuse of energy efficient HID lightsources

    For wall mounting in inspection pitsand similar wall mounting applicationwhere the adjustable reflector allowsthe light to be directed

    Features: Low profile (180mm) enables it to bemounted in tight spots

    Adjustable reflector allows directionof light in specific directions

    Available with a variety of lightsources including energy efficientHPS

    Reduced maintenance costs whenused with long-life HID light sources

    Standard Materials: Body and dome cover ................................... Copper free aluminium

    Diffuser ............................................ Heat and impact resistant glass

    Guard ........... Stainless steel wire Reflector .............. Stainless steel

    Standard Finish: Grey polyurethane

    Electrical Rating: 240V 50Hz

    200W incandescent 175W mercury vapour 150W high pressure sodium 2 x 11W fluorescent 175W metal halide

    Option: Pipe mounting............ Add suffix J Corro free powder polyester finish.....................Information on request

    Compliances: AS2380 - Electrical equipment forexplosive atmospheres - Flameproof

    enclosure AS2236 - Electrical equipment forexplosive atmospheres - Dustexcluding ignition proof

    AS1939 - Degrees of ProtectionIP66

    Certificate of Compliance No. Ex647

    Dimensions:

    Flameproof, Exd, IIC, IP66

    Zone 1

    Combustible DustZone 21 & 22

  • 7/23/2019 4. Haz Area Lighting

    21/44

    5-21Crouse-Hinds

    May 2003 Copyright 2003 Cooper Industries, Inc

    EVM Hazard Gard

    H.I.D. Lighting Fixtures

    Integral BallastFactory SealedApplication:EVM Hazard Gard lighting fixturesare used in

    Hazardous areas, both indoorsand outdoors where long lamp lifeand low maintenance costs aredesired

    Heavy process industries havingenvironments where flammable orexplosive vapours or gases, or

    where combustible dusts arepresent

    Features: Fixture is factory wired; power isfed through "wireless" connectionblock which serves as a mechanicalseal between entry and ballastcompartment. The result is fast,easy installation with improvedreliability and safety, enabling costeffective installation andmaintenance

    Dome and angle reflectors madeof Krydon - will not rust, corrode,

    dent, chip or peel High bay Alzak aluminumreflectors are available for mountingheights above 6m.

    Uniform attractive appearance inall wattages and mounting styles

    Configurated glass reduces glareimproving light distribution

    Certified for operation in elevatedambient temperatures of up to 50

    oC

    Wide range of light sources tomeet specific lighting needs - 80,100, 125, 175, 250 & 400W mercuryvapour (MV); 175, 250 & 400Wmetal halide (MH); 70, 100, 150,

    250W, 400W high pressure sodium(HPS)

    Four mounting types to suit alllighting layout ... pendant, ceiling,wall bracket, and stanchion

    Integral ballasts ... separateballasts are not required

    Lowest installed cost

    Standard Materials: Mounting modules, cover, ballasthousing, guard, globe ring - copperfree aluminium

    Glass ................. Heat and impactresistant, configurated glass

    Lamp socket .......... porcelain withstainless steel screw shell Reflectors ... dome and angle .......fibreglass reinforced polyester(Krydon); High Bay, Alzakaluminium

    External Hardware stainless steel

    Standard Finishes:

    Copper free aluminium ........ Grey

    polyurethane

    Krydon .................... natural white Alzak ............... natural aluminium

    Options(Refer to ordering Information)

    For Group IIC applications Fuse .......... To protect ballast andcapacitors against line surges

    May be ordered with or withoutguard

    Instant restrike ballast - enables ahot HPS lamp to immediatelyrestrike after momentary loss of arc

    due to voltage fluctuation or powerloss. Available for use with 50-150WLX HPS only

    Flameproof, Exd, IIB or IIC, IP66

    Zone 1

    Combustible DustZone 21 & 22

    Electrical Ratings: 240 VAC 50Hz 70 to 400 Watts Alternate operating voltagesavailable, see ordering information

    Entry Sizes: 20, 25mm hubs on ceiling, pendantand wall mounted, 1 1/4BSP on Stanchion Mount

    Alternate entries available, seeordering information

    Compliances: AS2380 Electrical equipment forexplosive atmospheres - Flameproofenclosure

    AS2236 - Electrical equipment forexplosive atmospheres. Dust

    excluding ignition proof AS1939 - Degrees of ProtectionIP66

    Certificate of Compliance No. Ex434

    Hazardous

    5Area

    Lighting

  • 7/23/2019 4. Haz Area Lighting

    22/44

    5-22Crouse-Hinds

    Hazardous

    5Area

    Lighting

    May 2003 Copyright 2003 Cooper Industries, Inc

    E V M A H 1 M 40 B 6 0 0 0 0

    Product IdentifierEVMA- Pendant MountEVMB- Wall Mount

    EVMC- Ceiling MountEVMJ - Stanchion Mount

    Lamp TypeS - HPSH - MVM - MH

    Entry Size1 - 20mm / 1/2"

    2 - 25mm / 3/4"3 - 32mm / 1"4 - 1 1/4 "

    Entry ThreadM - MetricN - 25mm / 3/4"B - BPS

    Wattage07 - 70W08 - 80W10 - 100W12 - 125W

    15 - 150W17 - 175W25 - 250W40 - 400W

    Voltage& Frequency

    2 - 120V/60Hz3 - 220V/50Hz4 - 220V/60Hz5 - 230V/50Hz

    6 - 240V/50Hz

    Special OptionsO - StandardS - Fuse

    Special Options0 - Standard1 - Special

    Instant Restrike0 - NoneI - IR

    Options0 - Standard1 - Offshore Paint

    Gas GroupB - Group IIBC - Group IIC

    Ordering Information

  • 7/23/2019 4. Haz Area Lighting

    23/44

    5-23Crouse-Hinds

    May 2003 Copyright 2003 Cooper Industries, Inc

    Hazardous

    5Area

    Lighting

    Pendant Wall Bracket Ceiling StanchionEntry With Guard With Guard WIth Guard With Guard

    Watts Size Cat.No. Cat.No. Cat.No. Cat.No.

    Mercury Vapour - High Power Factor

    80 20mm EVMA81M08B60000 EVMB81M08B60000 EVMC81M08B6000025mm EVMA82M08B60000 EVMB82M08B60000 EVMC82M08B600001 1/4" BSP EVMJ84B08B60000

    100 20mm EVMA82M10B60000 EVMB81M10B60000 EVMC81M10B6000025mm EVMA82M10B60000 EVMB82M10B60000 EVMC82M10B600001 1/4" BSP EVMJ84B10B60000

    125 20mm EVMA81M12B60000 EVMB81M12B60000 EVMC81M12B6000025mm EVMA82M12B60000 EVMB82M12B60000 EVMC82M12B600001 1/4" BSP EVMJ84B12B60000

    175 20mm EVMA81M17B60000 EVMB81M17B60000 EVMC81M17B6000025mm EVMA82M017B6000 EVMB82M17B60000 EVMC82M17B600001 1/4" BSP EVMJ84B17B60000

    250 20mm EVMA81M25B60000 EVMB81M25B60000 EVMC81M25B6000025mm EVMA82M25B60000 EVMB82M25B60000 EVMC82M25B600001 1/4" BSP EVMJ84B25B60000

    400 20mm EVMA81M40B60000 EVMB81M40B60000 EVMC81M40B6000025mm EVMA82M40B60000 EVMB82M40B60000 EVMC82M40B600001 1/4" BSP EVMJ84B40B60000

    High Pressure Sodium - High Power Factor

    70 20mm EVMA41M07B60000 EVMB41M07B60000 EVMC41M07B6000025mm EVMA42M07B60000 EVMB42M07B60000 EVMC42M07B600001 1/4" BSP EVMJ44B07B60000

    100 20mm EVMA41M10B60000 EVMB41M10B60000 EVMC41M10B6000025mm EVMA42M10B60000 EVMB42M10B60000 EVMC42M10B600001 1/4" BSP EVMJ44B10B60000

    150 20mm EVMA41M15B60000 EVMB41M15B60000 EVMC41M15B6000025mm EVMA42M15B60000 EVMB42M15B60000 EVMC42M15B600001 1/4" BSP EVMJ44B15B60000

    250 20mm EVMA41M25B60000 EVMB41M25B60000 EVMC41M25B6000025mm EVMA42M25B60000 EVMB42M25B60000 EVMC42M25B600001 1/4" BSP EVMJ44B25B60000

    400 20mm EVMA41M40B60000 EVMB41M40B60000 EVMC41M40B60000

    25mm EVMA42M40B60000 EVMB42M40B60000 EVMC42M40B600001 1/4" BSP EVMJ44B40B60000

    Metal Halide - High Power Factor Ballast

    175 20mm EVMA91M17B60000 EVMB91M17B60000 EVMC91M17B6000025mm EVMA92M17B60000 EVMB92M17B60000 EVMC92M17B600001 1/4" BSP EVMJ94B17B60000

    250 20mm EVMA91M25B60000 EVMB91M25B60000 EVMC91M25B6000025mm EVMA92M25B60000 EVMB92M25B60000 EVMC92M25B600001 1/4" BSP EVMJ94B25B60000

    400 20mm EVMA91M40B60000 EVMB91M40B60000 EVMC91M40B6000025mm EVMA92M40B60000 EVMB92M40B60000 EVMC92M40B600001 1/4" BSP EVMJ94B40B60000

    Fixtures are supplied as standard suitable for 240/50 hz operation.For other voltages please specify required voltage. Ceiling and bracket mounts have 4 hubs;3 are plugged

    Ordering Information

  • 7/23/2019 4. Haz Area Lighting

    24/44

    5-24Crouse-Hinds

    Hazardous

    5Area

    Lighting

    May 2003 Copyright 2003 Cooper Industries, Inc

    30 Angle ReflectorCat.No. RA739

    Dome ReflectorCat.No. RD739

    LampReceptacleCat. No. EV62All sizes

    Glass AssemblyWatts Cat. No.Up to 175 EV7302250/400 EV7404

    Ceiling MountEntry Cat. No.20mm EV1625mm EV26

    GuardWatts Cat. No.Up to 175 EV503250/400 EV5140

    Wall MountEntry Cat. No.20mm EV16 + EV8725mm EV26 + EV87

    Pendant MountEntry Cat. No.20mm EVMP225mm EVMP3

    Stanchion MountEntry Cat. No.1 1/4" BSP EVMJ4

    Temperature Classification:

    40oc AmbientPower Mercury High Pressure MetalRating (W) Vapour (MV) Sodium (HPS) Halide (MH)70 - T6 -80 T6 - -

    100 T4 T4 -125 T4 - -150 - T4 -175 T3 - T4250 T3 T3 T3400 T3 T3 T3

    50oc AmbientPower Mercury High Pressure MetalRating (W) Vapour (MV) Sodium (HPS) Halide (MH)70 - T6 -80 T6 - -100 T4 T4 -125 T4 - -150 - T4 -175 T3 - T4250 T3 T3 T3400 T3 T3 T3

    High Bay ReflectorCat.No. EV3912

    Accessories

  • 7/23/2019 4. Haz Area Lighting

    25/44

    5-25Crouse-Hinds

    May 2003 Copyright 2003 Cooper Industries, Inc

    Hazardous

    5Area

    Lighting

    80, 100, 125, 175, MV70, 100, 150W HPS 250W & 400W

    175 MH MV, HPS, MH All

    Type A B C D E

    EVMA 553 610 499 564 618

    EVMBX 635 693 581 646 697

    EVMCX 553 610 499 564 618

    EVMJ 543 594 573

    Accessories

    Pendant Mount

    Ceiling Mount

    Wall Mount

    Stanchion Mount

  • 7/23/2019 4. Haz Area Lighting

    26/44

    5-26Crouse-Hinds

    Hazardous

    5Area

    Lighting

    May 2003 Copyright 2003 Cooper Industries, Inc

    EVME Hazard Gard

    H.I.D. Lighting Fixtures

    Integral Ballast

    Application:EVME Hazard Gard lighting fixturesare used in

    Hazardous areas, both indoorsand outdoors where long lamp lifeand low maintenance costs are

    desired

    Heavy process industryenvironments where flammable or

    explosive vapours or gases, orcombustible dusts are present

    Features:

    Indirect cable entry into aseparate Exe termination enclosure

    ensures ease of installation

    Dome and angle reflectors madeof Krydon - will not rust, corrode,

    dent, chip or peel

    High bay Alzak aluminiumreflectors are available for mountingheights above 6m

    Uniform attractive appearance in

    all wattages and mounting styles

    Configurated glass reduces glareimproving light distribution

    Certified for operation in elevatedambient temperatures of up to 50

    oC

    Wide range of light sources tomeet specific lighting needs - 80,

    100, 125, 175, 250 & 400W mercury

    vapour (MV); 175, 250 & 400Wmetal halide (MH); 70, 100, 150,

    250W, 400W high pressure sodium(HPS)

    Standard ceiling mount luminaires

    can be adapted for wall, pendant orstanchion mount by using brackets

    (order brackets seperatetly)

    Integral ballasts ... separateballasts are not required

    Lowest installed cost

    Standard Materials:

    Mounting modules, cover, ballasthousing, guard, globe ring - copper

    free aluminium

    Glass ................. Heat and impactresistant, configurated glass

    Lamp socket .......... porcelain with

    stainless steel screw shell

    Reflectors ... dome and angle .......fibreglass reinforced polyester

    (Krydon); High Bay, Alzak

    aluminium

    External Hardware stainless steel

    Standard Finishes:

    Copper free aluminium ........ Greypolyurethane

    Krydon .................... natural white Alzak ............... natural aluminium

    Options(Refer to ordering Information)

    For Group IIC applications Fuse .......... To protect ballast andcapacitors against line surges

    Instant restrike ballast - enables ahot HPS lamp to immediately

    restrike after momentary loss of arcdue to voltage fluctuation or power

    loss. Available for use with 50-150W

    LX HPS only

    Alternate entries available -please consult factory

    Electrical Ratings:

    240 VAC 50Hz 70 to 400 Watts Alternate operating voltagesavailable, see ordering information

    Entry Sizes:

    20, 25mm hubs on ceiling, pendantand wall mounted, 1 1/4

    BSP on Stanchion Mount

    Alternate entries available, seeordering information

    Compliances:

    EN50014EN50018EN50019

    EN60529

    EN60598

    AS/NZS: 60079.0.2000AS/NZS: 60079.1.2000AS/NZS: 60079.7.2002

    Certificate of Compliance No.PTB ATEX1056

    Aus EX Pending

    Ambient Temperature-50

    0

    to 550

    C

    Flameproof, Exde, IIB or IIC, IP66

    Zone 1

    Combustible DustZone 21 & 22

  • 7/23/2019 4. Haz Area Lighting

    27/44

    5-27Crouse-Hinds

    May 2003 Copyright 2003 Cooper Industries, Inc

    Hazardous

    5Area

    Lighting

    E V M E H 1 M 40 B 6 0 0 0 0

    Ordering Information

    Product Identifiers

    Lamp TypeS - HPSH - MVM - MH

    Entry Size1 - 20mm / 1/2"

    2 - 25mm / 3/4"3 - 32mm / 1"4 - 1 1/4 "

    Entry ThreadM - MetricN - 25mm / 3/4"B - BPS

    Wattage07 - 70W08 - 80W10 - 100W12 - 125W

    15 - 150W17 - 175W25 - 250W40 - 400W

    Voltage& Frequency

    2 - 120V/60Hz3 - 220V/50Hz4 - 220V/60Hz5 - 230V/50Hz

    6 - 240V/50Hz

    Special OptionsO - StandardS - Fuse

    Special Options0 - Standard1 - Special

    Instant Restrike0 - NoneI - IR

    Options0 - Standard1 - Offshore Paint

    Gas GroupB - Group IIBC - Group IIC

  • 7/23/2019 4. Haz Area Lighting

    28/44

    5-28Crouse-Hinds

    Hazardous

    5Area

    Lighting

    May 2003 Copyright 2003 Cooper Industries, Inc

    Ordering Information

    Mercury Vapour (M/V)

    Wattage T Rating Cat No.

    80W T6 EVMEH1M08B60000100W T5 EVMEH1M10B60000125W T4 EVMEH1M12B60000175W T4 EVMEH1M17B60000250W T3 EVMEH1M25B60000400W T3 EVMEH1M40B60000

    High Pressure Sodium (HPS)

    Wattage T Rating Cat No.

    70W T6 EVMES1M07B60000100W T4 EVMES1M10B60000150W T4 EVMES1M15B60000250W T3 EVMES1M25B60000400W T3 EVMES1M40B60000

    High Metal Halide (MH)

    Wattage T Rating Cat No.

    70W T6 EVMEM1M07B60000100W T4 EVMEM1M10B60000150W T4 EVMEM1M15B60000175W T4 EVMEM1M17B60000250W T3 EVMEM1M25B60000400W T3 EVMEM1M40B60000

    * Please refer to table for other possible configurations

    Mounting Brackets (order seperately)Pendant Mount Cat No.

    M20 EVMEPM1M25 EVMEPM21/2" NPT Clearance Hole EVMEPN13/4" NPT Clearance Hole EVMEPN2

    Wall Mount Cat No.

    M20 Thread EVMEWM1M25 Thread EVMEWM2

    Stanchion Mount Cat No.

    2" Slipfitter Pipe EVMEJ1 1/4" BSP Thread EVMEJB41 1/2" NPT Thread EVMEJN5

  • 7/23/2019 4. Haz Area Lighting

    29/44

    5-29Crouse-Hinds

    May 2003 Copyright 2003 Cooper Industries, Inc

    Hazardous

    5Area

    Lighting

    Accessories

    Stanchion BracketCat No. EVMEJ

    Wall BracketCat No. EVMEW

    30 Angle ReflectorCat.No. RA739

    Dome ReflectorCat.No. RD739

    High Bay ReflectorCat.No. EV3912

    Glass AssemblyWatts Cat. No.

    Up to 175 EV7302250/400 EV7404

    GuardWatts Cat. No.Up to 175 EV503250/400 EV5140

    Lamp HolderWatts Cat. No.

    Up to 125 EVMVS62600-SA150 to 400 EVMVS12850-SA

    Pendant BracketCat No. EVMEP

  • 7/23/2019 4. Haz Area Lighting

    30/44

    5-30Crouse-Hinds

    Hazardous

    5Area

    Lighting

    May 2003 Copyright 2003 Cooper Industries, Inc

    Dimensions

    Pendant Mount

    Ceiling Mount

    Wall Mount

    Stanchion Mount

  • 7/23/2019 4. Haz Area Lighting

    31/44

    5-31Crouse-Hinds

    May 2003 Copyright 2003 Cooper Industries, Inc

    Fixture With Globe, Dome Reflectorand Without Guard

    NOTE: Photometric data was developed using a 100 wattdiffuse mercury vapour lamp (4200 lumens). For otherdiffuse lamps, use the following conversion factors(multipliers): 175W MV - 2.05; 70W MH - 1.33;100W MH - 1.85; 175W MH - 3.3.Multipliers are for use with candela curve only.Luminaire Spacing ratio is 1.30.

    Coefficient of UtilisationEffective Floor Cavity Reflectance 20%

    % Reflectance Room Cavity RatioEff.Ceil. Wall 1 2 3 4 5

    50 .694 .584 .503 .439 .38680 30 .644 .516 .428 .361 .31110 .600 .459 .369 .302 .253

    50 .660 .556 .479 .418 .36870 30 .615 .493 .410 .347 .297

    10 .572 .441 .355 .291 .244

    50 .596 .501 .432 .377 .33450 30 .559 .450 .375 .317 .274

    10 .526 .405 .328 .270 .227

    50 .538 .451 .389 .339 .30230 30 .509 .410 .342 .290 .250

    10 .481 .373 .302 .249 .210

    50 .485 .405 .349 .305 .27110 30 .461 .371 .310 .263 .223

    10 .439 .341 .277 .228 .1930 0 .410 .313 .251 .204 .171

    % Reflectance Room Cavity RatioEff.Ceil. Wall 6 7 8 9 10

    50 .347 .312 .282 .259 .23080 30 .273 .241 .214 .192 .166

    10 .220 .192 .165 .147 .125

    50 .331 .298 .270 .248 .22070 30 .262 .231 .206 .185 .162

    10 .211 .184 .160 .143 .121

    50 .300 .272 .246 .227 .20350 30 .241 .212 .190 .172 .150

    10 .197 .171 .149 .134 .113

    50 .272 .245 .225 .207 .18530 30 .222 .196 .175 .158 .138

    10 .183 .158 .139 .124 .105

    50 .246 .224 .203 .188 .16910 30 .202 .180 .160 .146 .127

    10 .168 .147 .129 .115 .096

    0 0 .148 .128 .111 .099 .082

    NOTE: Photometric data was developed using a 100 wattdiffuse mercury vapour lamp (4200 lumens). For otherdiffuse lamps, use the following conversion factors(multipliers): 175W MV - 2.05; 70W MH - 1.33;100W MH - 1.85; 175W MH - 3.3.Multipliers are for use with candela curve only.Luminaire spacing ratio is 1.25.

    Lamp: 100W mercury vapour - (MV)Total bare lamp lumens: 4200

    Coefficient of UtilisationEffective Floor Cavity Reflectance 20%

    % Reflectance Room Cavity RatioEff.Ceil. Wall 1 2 3 4 5

    50 .715 .637 .570 .509 .45880 30 .688 .596 .521 .455 .401

    10 .655 .562 .483 .413 .359

    50 .699 .624 .560 .500 .44870 30 .675 .586 .514 .450 .396

    10 .652 .556 .478 .410 .356

    50 .668 .598 .539 .481 .43450 30 .648 .568 .500 .438 .388

    10 .631 .540 .468 .404 .353

    50 .640 .576 .519 .465 .42030 30 .624 .550 .487 .428 .379

    10 .609 .527 .459 .398 .348

    50 .615 .554 .502 .450 .40710 30 .602 .553 .474 .418 .372

    10 .589 .514 .450 .391 .3430 0 .575 .500 .436 .377 .329

    % Reflectance Room Cavity RatioEff.Ceil. Wall 6 7 8 9 10

    50 .414 .375 .340 .313 .27580 30 .358 .319 .286 .259 .222

    10 .318 .282 .247 .222 .187

    50 .407 .369 .335 .308 .27170 30 .354 .315 .283 .256 .222

    10 .315 .278 .246 .221 .187

    50 .394 .358 .325 .229 .26450 30 .347 .309 .278 .252 .217

    10 .312 .275 .244 .219 .185

    50 .383 .346 .316 .292 .25730 30 .340 .304 .273 .248 .214

    10 .308 .272 .242 .217 .183

    50 .371 .338 .307 .284 .25110 30 .333 .299 .268 .244 .210

    10 .304 .269 .240 .215 .181

    0 0 .292 .257 .227 .204 .170

    Lamp: 100W mercury vapour - (MV)Total bare lamp lumens: 4200

    Fixture With Globeand Without Guard

    Hazardous

    5Area

    Lighting

  • 7/23/2019 4. Haz Area Lighting

    32/44

    5-32Crouse-Hinds

    Hazardous

    5Area

    Lighting

    May 2003 Copyright 2003 Cooper Industries, Inc

    Isolux Chart: Fixture With Globe and300 Angle Reflector, Without Guard

    Illumination in footcandles on work plane 3m below lightcentre. Multiply by factor shown to convert to other

    mounting heightsHeight (m) Factor Height (m) Factor

    1.8 2.78 2.7 1.232.1 2.04 3.3 0.832.4 1.56 3.7 0.70

    Fixture With Globeand Without Guard

    Lamp: 150W high pressure sodium (HPS)

    Total bare lamp lumens: 16,000

    Coefficient of UtilisationEffective Floor Cavity Reflectance 20%

    % Reflectance Room Cavity RatioEff.Ceil. Wall 1 2 3 4 5

    50 .695 .579 .494 .410 .38280 30 .644 .509 .417 .326 .305

    10 .599 .450 .356 .262 .246

    50 .659 .549 .469 .387 .36370 30 .613 .484 .397 .311 .291

    10 .570 .431 .341 .251 .236

    50 .592 .491 .419 .344 .23750 30 .555 .439 .360 .279 .265

    10 .522 .393 .312 .229 .218

    50 .531 .438 .373 .304 .29230 30 .502 .396 .325 .250 .240

    10 .474 .358 .284 .207 .200

    50 .476 .390 .331 .267 .26010 30 .451 .355 .291 .222 .217

    10 .429 .325 .257 .184 .1810 0 .399 .295 .230 .159 .159

    % Reflectance Room Cavity RatioEff.Ceil. Wall 6 7 8 9 10

    50 .342 .306 .278 .265 .23380 30 .266 .234 .209 .198 .168

    10 .212 .184 .160 .153 .127

    50 .324 .292 .265 .253 .22270 30 .254 .223 .201 .191 .163

    10 .202 .176 .155 .149 .123

    50 .292 .263 .240 .231 .20350 30 .232 .203 .184 .177 .150

    10 .187 .162 .143 .139 .114

    50 .262 .236 .218 .210 .18530 30 .211 .186 .167 .162 .138

    10 .172 .148 .132 .129 .105

    50 .234 .213 .195 .191 .16710 30 .190 .169 .152 .149 .125

    10 .156 .135 .121 .118 .096

    0 0 0 .135 .116 .103 .081

    NOTE: Photometric data was developed using a 150 wattclear high pressure sodium lamp (16,000 lumens). Forother clear lamps, use the following conversion factors(multipliers): 50W HPS - .25; 70W HPS - .40;100W HPS - .59.Multipliers are for use with candela curve only.Luminaire spacing ratio is 0.80.

    Lamp: 100W diffuse mercury vapour (MV)

    Total bare lamp lumens: 4,200

    NOTE: Photometric data was developed using a 100 wattdiffuse mercury vapour lamp (4200 lumens). For otherdiffuse lamps, use the following conversion factors(multipliers): 175W MV - 2.05; 70W MH - 1.33;100W MH - 1.85; 175W MH - 3.3.

  • 7/23/2019 4. Haz Area Lighting

    33/44

    5-33Crouse-Hinds

    May 2003 Copyright 2003 Cooper Industries, Inc

    Hazardous

    5Area

    Lighting

    Lamp: 150W high pressure sodium - (HPS)Total bare lamp lumens: 16,000

    Fixture With Globe, Hi-Bay Reflectorand Without Guard

    Fixture With Globe, Dome Reflectorand Without Guard

    Coefficient of UtilisationEffective Floor Cavity Reflectance 20%

    % Reflectance Room Cavity RatioEff.Ceil. Wall 1 2 3 4 5

    50 .716 .637 .568 .507 .45580 30 .689 .596 .519 .452 .39810 .666 .561 .480 .410 .355

    50 .700 .624 .559 .498 .44670 30 .675 .585 .512 .447 .393

    10 .653 .555 .476 .407 .353

    50 .668 .598 .538 .479 .43250 30 .648 .567 .498 .435 .385

    10 .631 .539 .466 .400 .349

    50 .640 .575 .518 .463 .41730 30 .625 .549 .485 .425 .376

    10 .610 .526 .457 .394 .344

    50 .615 .554 .500 .447 .40410 30 .602 .532 .472 .415 .369

    10 .590 .513 .448 .388 .3390 0 .575 .498 .434 .373 .326

    % Reflectance Room Cavity RatioEff.Ceil. Wall 6 7 8 9 10

    50 .413 .373 .339 .312 .27580 30 .355 .318 .285 .258 .222

    10 .316 .280 .246 .221 .187

    50 .405 .368 .334 .308 .27170 30 .352 .314 .283 .256 .222

    10 .312 .277 .245 .221 .187

    50 .392 .356 .324 .299 .26450 30 .345 .307 .277 .252 .217

    10 .309 .274 .243 .219 .185

    50 .380 .345 .316 .291 .257

    30 30 .338 .303 .272 .247 .21410 .306 .270 .241 .217 .183

    50 .369 .337 .307 .283 .25110 30 .331 .298 .267 .244 .210

    10 .301 .267 .238 .215 .181

    0 0 .292 .257 .227 .204 .170

    NOTE: Photometric data was developed using a 150 wattclear high pressure sodium lamp (16000 lumens). For otherclear lamps, use the following conversion factors(multipliers): 50W HPS - .25; 70W HPS - .40;100W HPS - .59.Multipliers are for use with candela curve only.Luminaire spacing ratio is 1.00.

    Coefficient of UtilisationEffective Floor Cavity Reflectance 20%

    % Reflectance Room Cavity RatioEff.Ceil. Wall 1 2 3 4 5

    50 .688 .618 .573 .531 .49480 30 .651 .592 .542 .495 .455

    10 .636 .569 .517 .468 .427

    50 .655 .608 .566 .525 .48770 30 .639 .583 .536 .491 .452

    10 .525 .564 .513 .464 .425

    50 .629 .587 .550 .511 .47650 30 .616 .568 .525 .482 .446

    10 .606 .550 .505 .459 .422

    50 .606 .569 .535 .498 .46630 30 .597 .554 .514 .474 .438

    10 .588 .539 .497 .454 .418

    50 .586 .533 .522 .487 .45710 30 .578 .539 .504 .466 .433

    10 .570 .528 .489 .449 .4130 0 .560 .517 .479 .439 .404

    % Reflectance Room Cavity RatioEff.Ceil. Wall 6 7 8 9 10

    50 .460 .427 .396 .369 .32880 30 .420 .388 .358 .330 .288

    10 .394 .361 .330 .303 .262

    50 .455 .423 .392 .366 .32570 30 .418 .385 .356 .328 .288

    10 .391 .359 .329 .303 .262

    50 .444 .414 .385 .360 .32050 30 .412 .380 .352 .325 .285

    10 .388 .357 .328 .301 .261

    50 .436 .406 .379 .354 .315

    30 30 .407 .377 .348 .322 .28210 .385 .354 .326 .300 .259

    50 .428 .400 .373 .348 .31110 30 .402 .373 .345 .319 .280

    10 .382 .352 .324 .298 .258

    0 .373 .343 .315 .290 .249

    NOTE: Photometric data was developed using a 150 wattclear high pressure sodium lamp (16000 lumens). Forother clear lamps, use the following conversion factors(multipliers): 50W HPS - .25; 70W HPS - .40;100W HPS - .59.Multipliers are for use with candela curve only.Luminaire spacing ratio is 1.00.

    Lamp: 150Whigh pressure sodium - (HPS)

    Total bare lamp lumens: 16,000

  • 7/23/2019 4. Haz Area Lighting

    34/44

    5-34Crouse-Hinds

    Hazardous

    5Area

    Lighting

    May 2003 Copyright 2003 Cooper Industries, Inc

    Electrical Rating:

    240V 50Hz 70 to 400W P.F. 0.9

    Compliances: AS2380 Electrical equipment forexplosive atmospheres - Non-Sparking Equipment, & DustExcluding Ignition Proof

    AS 1939 ...Degrees of protectionIP66

    EN50021:1999 Certificate of Compliance No.

    - Ex426

    - PTB00 ATEX 2215

    Dimensions: See Pages 6-8 to 6-9

    Photometric Data: See Pages 6-10 to 6-13

    Accessories: See Page 5-38

    NVMV Champ

    HID Lighting Fixtures

    Integral Ballast

    Application: Used in locations where aconcentration of hazardous gasesliquids or vapours may occur forshort periods of time at infrequentintervals

    Used in hazardous locations wherecombustible dusts, fibres or flyingsmay be present

    Used where maintenance access

    is difficult and extended periodsbetween relamping is required

    Ideal for processing plants, wasteand sewage treatment facilitiessecurity lighting, roadways, garages& other heavy industrial applications

    Used where space is limited andhigh levels of lighting are required

    Features:All Units:

    Several mounting arrangements:PendantCeiling for flush to surface mountingWall bracket-through feedStanchion - 25 angle

    Integral long-life ballast Choice of light source - mercuryvapour (MV), high pressure sodium(HPS) or metal halide

    Operating ambient temperaturebetween minus 45C and 55

    Attractive gray polyurethane paintfinish

    Configured glass and prismaticrefractors reduce glare and improvelight distribution

    Recessed hubs Restricted breathing design givesimproved T Rating allowing use ofhigher lumen output fixtures

    Special Exn terminals to ensurepositive connection to circuit wiring

    Standard Materials: Ballast housings and mountings -copper free aluminium(less than 0.4 of 1%)

    Guards - copper free aluminium orstainless steel wire

    Exterior hardware - stainless steel Globes - configurated glass

    Reflectors - dome or angle whiteKrydon fibreglass - reinforcedpolyester material

    Reflector lens assy - Alzakaluminium reflector, tempered glasslens

    Ceiling mount with dome reflector

    Non-Sparking, ExnR, IIC, IP66

    Zone 2

    Combustible DustZone 21 & 22

    Standard Finishes:

    Aluminium ballast housings,

    mountings and aluminium guards............ grey polyurethane paint

    Stainless steel wire guards............................ natural

    Reflectors .......................... natural

    Options:(Refer to ordering information)

    Corro-free powder polyestercoating, information available onrequest

    Quartz auxiliary lamp to providelight during the period required forHID lamps to restrike followingresumption of power after a powerfailure - Large body fixtures only

    Instant restrike ballast - enables ahot HPS lamp to immediately restrikeafter a momentary loss of arc due tovoltage fluctuation or power outage. Ithas no effect on the warm-up periodof cold lamps. Available for use with50-150W HPS LX only

    Large body for improved T Ratingon 250 Watt fixtures

    For application subject to extremethermal shock, Tuff-skin coated G34and G251 glasses are available

    Non-standard supply voltage andfrequency, consult factory Fuse - to protect against abnormalline conditions and provide additionalcircuit protection

    Other entries available upon request

  • 7/23/2019 4. Haz Area Lighting

    35/44

    5-35Crouse-Hinds

    May 2003 Copyright 2003 Cooper Industries, Inc

    Ordering Information

    NVMV S 1 M C 40 6 P I 0 0

    Product GroupNVMV- Champ

    Lamp TypeS - HPSH - MVM - MH

    Entry Size1 - 20mm / 1/2"

    2 - 25mm / 3/4"3 - 32mm / 1"4 - 1 1/4"5 - 1 1/2"

    Entry ThreadM - MetricN - NPTB - BSP

    Mounting

    C - CeilingW - WallJ - Stanchion

    Voltage& Frequency

    2 - 120V / 60Hz3 - 220V / 50Hz4 - 220V / 60Hz5 - 230V / 50Hz

    6 - 240V / 50Hz

    Special Options0 - StandardS - Fuse

    Guard0 - Without GuardP - GuardR - RD4A

    Instant Restrike0 - None / Small BodyI - IRL - Large Body

    Options0 - Standard1 - Offshore PaintR - Red Body

    Wattage07 - 70W08 - 80W10 - 100W12 - 125W15 - 150W17 - 175W25 - 250W40 - 400W

    Hazardous

    5Area

    Lighting

  • 7/23/2019 4. Haz Area Lighting

    36/44

    5-36Crouse-Hinds

    Hazardous

    5Area

    Lighting

    May 2003 Copyright 2003 Cooper Industries, Inc

    Ordering Information

    Mercury Vapour (M/V) 240V/50Hz*High power factor reactor ballast (.9)

    Entry Lamp With Glass and Guard With Reflector Lens Assy.Size Watts Cat. No. Cat. No.

    Ceiling/Pendant Mount20mm 80 NVMVH1MC086P000 -25mm 80 NVMVH2MC086P000 -20mm 100 NVMVH1MC106P000 -25mm 100 NVMVH2MC106P000 -20mm 125 NVMVH1MC126P000 -25mm 125 NVMVH2MC126P000 -20mm 175 NVMVH1MC176P00025mm 175 NVMVH2MC176P00020mm 250 NVMVH1MC256P000 NVMVH1MC256RL0025mm 250 NVMVH2MC256P000 NVMVH2MC256RL0020mm 400 NVMVH1MC406PL00 NVMVH1MC406RL0025mm 400 NVMVH2MC406PL00 NVMVH2MC406RL00

    Wall Mount20mm 80 NVMVH1MW086P000 -25mm 80 NVMVH2MW086P000 -20mm 100 NVMVH1MW106P000 -25mm 100 NVMVH2MW106P000 -20mm 125 NVMVH1MW126P000 -25mm 125 NVMVH2MW126P000 -20mm 175 NVMVH1MW176P000 -25mm 175 NVMVH1MW176P000 -20mm 250 NVMVH1MW256P000 NVMVH1MW256RL0025mm 250 NVMVH2MW256P000 NVMVH2MW256RL0020mm 400 NVMVH1MW406PL00 NVMVH1MW406RL0025mm 400 NVMVH2MW406PL00 NVMVH2MW406RL00

    Stanchion Mount1 1/4" BSP 80 NVMVH4BJ086P000 -1 1/4" BSP 100 NVMVH4BJ106P000 -1 1/4" BSP 125 NVMVH4BJ126P000 -1 1/4" BSP 175 NVMVH4BJ176P000 -1 1/4" BSP 250 NVMVH4BJ256P000 -1 1/4" BSP 400 NVMVH4BJ406PL00 -

    Large body ceiling mount withRD4A reflector lens assembly

  • 7/23/2019 4. Haz Area Lighting

    37/44

    5-37Crouse-Hinds

    May 2003 Copyright 2003 Cooper Industries, Inc

    Hazardous

    5Area

    Lighting

    Ordering Information

    High Pressure Sodium (HPS) 240V/50Hz*High power factor reactor ballast (.9) with solid state ignitor

    With Glass With ReflectorEntry Lamp And Guard & Lens Assy.Size Watts Cat. No. Cat. No.Ceiling / Pendant Mount20mm 70 NVMVS1MC076P000 -25mm 70 NVMVS2MC076P000 -20mm 100 NVMVS1MC106P000 -25mm 100 NVMVS1MC106P000 -20mm 150 NVMVS1MC156P000 -25mm 150 NVMVS2MC156P000 -20mm 250 NVMVS1MC256P000 NVMVS1MC256RL00

    25mm 250 NHMVS2MC256P000 NVMVS2MC256RL0020mm 400 NVMVS1MC406PL00 NVMVS1MC406RL0025mm 400 NVMVS2MC406PL00 NVMVS2MC406RL00Wall Mount20mm 70 NVMVS1MW076P000 -25mm 70 NVMVS2MW076P000 -20mm 100 NVMVS1MW106P000 -25mm 100 NVMVS2MW106P000 -20mm 150 NVMVS1MW156P000 -25mm 150 NVMVS2MW156P000 -20mm 250 NVMVS1MW256P000 NVMVS1MW256RL0025mm 250 NVMVS2MW256P000 NVMVS2MW256RL0020mm 400 NVMVS1MW406PL00 NVMVS1MW406RL0025mm 400 NVMVS2MW406PL00 NVMVS2MW406RL00

    Stanchion Mount1 1/4" BSP 70 NVMVS4BJ076P000 -1 1/4" BSP 100 NVMVS4BJ106P000 -1 1/4" BSP 150 NVMVS4BJ156P000 -1 1/4" BSP 250 NVMVS4BJ256P000 NVMVS4BJ256RL001 1/4" BSP 400 NVMVS4BJ406PL00 NVMVS4BJ406RL00

    Metal Halide (MH)High power factor reactor ballast (.9) with solid state ignitor

    Ceiling / Pendant Mount20mm 175 NVMVM1MC176P000 -

    25mm 175 NVMVM2MC176P000 -20mm 250 NVMVM2MC256P000 NVMVM1MC256RL0025mm 250 NVMVM2MC256P000 NVMVM1MC256RL0020mm 400 NVMVM2MC406PL00 NVMVM1MC406RL0025mm 400 NVMVM2MC406PL00 NVMVM1MC406RL00Wall Mount20mm 175 NVMVM1MW176P000 -25mm 175 NVMVM1MW176P000 -20mm 250 NVMVM1MW256P000 NVMVM1MW256RL0025mm 250 NVMVM1MW256P000 NVMVM1MW256RL0020mm 400 NVMVM1MW406PL00 NVMVM1MW406RL0025mm 400 NVMVM1MW406PL00 NVMVM1MW406RL00Stanchion Mount1 1/4" BSP 175 NVMVM4BJ176P000 -

    1 1/4" BSP 250 NVMVM4BJ176P000 NVMVM4BJ256RL001 1/4" BSP 400 NVMVM4BJ176PL00 NVMVM4BJ406RL00

    Please refer to page 5-30 for other configurations

  • 7/23/2019 4. Haz Area Lighting

    38/44

    5-38Crouse-Hinds

    Hazardous

    5Area

    Lighting

    May 2003 Copyright 2003 Cooper Industries, Inc

    Accessories

    GLASSES

    ConfiguredLamp Fixture GlassSize Cat. No. Type70-250W G34 Heat

    (No Guard) Resistant

    G251 Heat(With Guard) Resistant

    400W G303 HeatResistant

    REFLECTORSLampSize Cat. No. Type

    70-250W RD70 DomeRA70 30 Angle

    400W RD739 Dome(Large Body) RA739 30 Angle

    REFLECTOR/LENSLampSize Cat. No.400W RD4A

    GUARDSLamp Suits Glass Guard.Size Cat No. Cat No.70-250W G251 P22250W (Large Body) G303 P33400W G303 P33

    Temperature Classification:

    Power Mercury High Pressure Metal

    Rating (W) Vapour (MV) Sodium (HPS) Halide (MH)G34 G303 G251 G34 G303 G251 G34 G303 G251

    70 - - T5 T5 - -

    80 T4 T4 - - - -

    100 T4 T4 T4 T3 - -

    125 T4 T3 - - - -

    150 - - T4 T3 - -

    175 (small body) T3 T3 - - T3 T3

    175 (large body) T4

    250 (small body) T3 T2 T3 T2 T3 T2

    250 (large body) T3 T3 T3

    400 T2 T3 T2

    400 (using sealed T3 T4 T3

    reflector/glass RD4A)

    Note: Light fixtures up to 250W use small body.

    400W fixtures use large body

    250W can be supplied in large body to give improved T rating - Please refer to table o

  • 7/23/2019 4. Haz Area Lighting

    39/44

    5-39Crouse-Hinds

    May 2003 Copyright 2003 Cooper Industries, Inc

    Hazardous

    5Area

    Lighting

    NFMV

    Industrial

    FloodlightLuminaires

    Application:NFMV floodlights are suitable for use in:

    Outdoor locations such as thosefound in process plants,manufacturing plants, loading andstorage areas, petrochemical, wasteror sewerage treatment plants

    Features: Enclosed and gasketed forwet locations Choice of HID light sourcesincluding HPS; 70, 100, 150,250, & 400 MV; 175, 250 &400 MH;175, 250 & 400

    Versatile yoke mountingbracket simplifies installation

    Slipfitter adaptoravailable for 2 pole topmounting

    Door frame is hingedand has captivefastening screws forease of relamping

    Silicone rubbergaskets are standard,ensuring long life andreliable environmentalsealing even underadverse conditions

    Die cast aluminiumexterior components areepoxy powder coated forsuperior corrosion resistance

    Corrosion resistant stainlesssteel external hardware

    Standard Materials: Housing and door frame............................die cast aluminium

    Lens ... tempered heat and impactresistant glass Gasket .............. extruded silicone Exterior hardware .......... stainlesssteel

    Standard Finishes: Grey epoxy powder coated

    Electrical Rating: 240 50Hz 70 to 400 watts Other voltages and frequenciesavailable on request

    Compliances: AS2380.9 Exn AS 2236... 1994 DIP EN50021 Certificate of Compliance No.

    - Aus Ex 3562- PTB 00 Atex 2214

    Ordering Information:Cat No.

    Mercury Vapour

    NFMVH1MY4060000 T3 400W MV

    NFMVH1MY2560000 T3 250W MV

    NFMVH1MY1760000 T4 175W MV

    High Pressure Sodium

    NFMVS1MY4060000 T3 400W HPS

    NFMVS1MY2560000 T4 250W HPS

    NFMVS1MY1560000 T5 150W HPS

    NFMVS1MY1060000 T5 100W HPS

    NFMVS1MY0760000 T6 70W HPS

    Metal Halide

    NFMVM1MY4060000 T3 400W MH

    NFMVM1MY2560000 T4 250W MH

    NFMVM1MY1760000 T4 175W MH

    Mounting Accessory

    Slipfitter

    SFA6 - M20

    SFA6 / 2M - M25

    NFMV showing SFA6

    slipfitter adaptor and gland

    (order separately)

    Non-Sparking, Exn R, IIC, IP66

    Zone 2

    Combustible DustZone 21 & 22

  • 7/23/2019 4. Haz Area Lighting

    40/44

    5-40Crouse-Hinds

    Hazardous

    5Area

    Lighting

    May 2003 Copyright 2003 Cooper Industries, Inc

    NFMV S 1 M Y 40 6 0 0 0 0

    Product GroupNFMV - Floodlight

    Lamp TypeS - HPSH - MVM - MH

    Entry Size1 - 20mm / 1/2"2 - 25mm / 3/4"

    3 - 32mm / 1"4 - 1 1/4"5 - 1 1/2"

    Entry ThreadM - MetricN - NPTB - BSP

    Mounting

    C - CeilingW - WallJ - Stanchion

    Voltage& Frequency

    1 - 110V / 60Hz2 - 120V / 60Hz3 - 220V / 50Hz4 - 220V / 60Hz

    5 - 230V / 50Hz6 - 240V / 50Hz7 - 227V / 60Hz

    Special Options0 - StandardS - Fused

    0 - NFMV

    Instant Restrike0 - NoneI - IR

    Options0 - Standard1 - Offshore PaintR - Red Body

    Wattage07 - 70W08 - 80W10 - 100W12 - 125W15 - 150W17 - 175W25 - 250W40 - 400W

    Ordering Information

  • 7/23/2019 4. Haz Area Lighting

    41/44

    5-41Crouse-Hinds

    May 2003 Copyright 2003 Cooper Industries, Inc

    Hazardous

    5Area

    Lighting

    Dimensions (mm)

    Lamp: 400W high pressure sodium (HPS)Total bare lamp lumens:50,000

    For 150 watt HPS, multiply lux by 0.32. For 250 watthigh pressure sodium, multiply lux values by 0.6

    Lamp: 400W metal halide (M / H)Total bare lamp lumens: 34,000

    For 250 watt clear metal halide,multiply lux values by 0.6

    175

    530

    45065

    390

    120

    2Holes15

    20mm Entry

    430

    660

    MountingDe

    tails

    Isolux Values at Various Mounting Heights(Lux values for both charts)

    MountingHeight A B C D E

    5m 86.0 43.0 21.52 8.61 4.30

    6m 18.42 24.75 11.84 5.38 2.47

    7m 31.20 15.06 7.53 3.23 1.51

    9m 21.52 10.76 5.38 2.15 1.08

    11m 16.14 7.53 4.30 1.61 0.75

    12m 11.84 6.46 3.23 1.18 0.65

    RatioofD

    istanceto

    Mountin

    gHeight

    Ratio of Distance to Mounting Feet Ratio of Distance to Mounting Feet

    Fixtures located at 00, 00

    Aiming angle at 450

    Fixture aiming angle 300 past verticalthrough 600 before vertical

    00 = 2.9 300 = 2.5 450 = 2.5

    EPA Data - Aiming Angle

    10

    Photometric Data

    & Dimensions

    RatioofD

    istanceto

    Mountin

    gHeight

  • 7/23/2019 4. Haz Area Lighting

    42/44

    5-42Crouse-Hinds

    Hazardous

    5Area

    Lighting

    May 2003 Copyright 2003 Cooper Industries, Inc

    Application:The FSFB flashing beacon can beused as:

    as an obstruction marker as a visual alarm signal in areas which may be hazardousdue to the presence of flammableliquids, gases or vapours,and dusts

    Features: Solid state beacon means no movingparts to wear out or fail Flametight threaded joints O-ring gaskets for weatherproofing Lightweight, copper free aluminiumprincipal parts

    Easy to assemble

    Standard Materials: Body ..... Copper free cast aluminium Dome ................. Heat and impactresistant glass

    Beacon ......Solid state strobe light

    Standard Finish:

    Grey polyurethaneOptions: Cast aluminium guard.........................Cat. No.EV505

    Special paint or protective finishes.............................. specify

    Other colours: Clear, Green, Blue,Amber. Add C, G, B or A to Cat. No.when ordering

    Pendant entry ..... specify size &thread form

    Compliances:

    AS2480 Electrical equipment forexplosive atmospheres - Flameproofenclosure

    AS2236 - Electrical equipment forexplosive atmospheres. Dust excludingIgnition - proof

    AS1939 - Degrees of ProtectionIP65

    Certificate of Compliance No. Ex491

    Ordering Information: FSFB201 / Voltage / ColourExample FSFB20124R = 24 Volt red

    Technical Data:

    Supply 24V DC240V AC

    Flash Rate 60 FPM Light Output 2.25 Joules per flash Conduit Entries 2 x 20mm

    (1 Plugged)

    FSFB 301

    Flashing

    Beacon

    Dimensions:

    Flameproof, Exd, IIC, IP66

    Zone 1

    Combustible DustZone 21 & 22

  • 7/23/2019 4. Haz Area Lighting

    43/44

    5-43Crouse-Hinds

    May 2003 Copyright 2003 Cooper Industries, Inc

    Hazardous

    5Area

    Lighting

    Application:The FRFB rotating beacon can beused as:

    as an obstruction marker as a visual alarm signal in areas which may be hazardousdue to the presence of flammableliquids, gases or vapours, and dusts

    Features: Flametight threaded joints O-ring gaskets for weatherproofing Lightweight, copper free aluminiumprincipal parts

    Easy to assemble

    Standard Materials: Body .. Copper free cast aluminium Dome ................. Heat and impactresistant glass - red

    Beacon ..........................Lamp size70 W quartz Halogen / 24V DC55W quartz Halogen / 12V DC25W incandescent / 240V ACAdd 12, 24 or 240 to Cat. No. when

    orderingStandard Finish: Grey polyurethane

    Options: Cast aluminium guard.........................Cat. No. EV505

    Special paint or protective finishes.............................. specify

    Other dome colours: Clear, Green,Blue, Amber. Add C, G, B or A to Cat.No. when ordering

    Pendant entry ..... specify size &thread form

    Compliances: AS2480 - Electrical equipment forexplosive atmospheres - Flameproofenclosure

    AS2236 - Electrical equipment forexplosive atmospheres. Dust excludingIgnition - proof AS1939 - Degrees of Protection IP65 Certificate of Compliance No. Ex491

    Technical Data: Supply 12/24V DC

    240V 50HZ AC

    Flash Rate 150 RPM Conduit Entries 2 x 20mm(1 Plugged)

    Ordering Information: FRFB301 / Voltage / ColourExample FRFB30124R = 24 Volt red

    FRFB 301

    Rotating

    Beacon

    Dimensions:

    Flameproof, Exd, IIC, IP66

    Zone 1

    Combustible DustZone 21 & 22

  • 7/23/2019 4. Haz Area Lighting

    44/44

    5-44Crouse-Hinds

    Hazardous

    5Area

    Lighting