  • Nozzles must be mounted so that they are pointing down

    Nozzle Positions and Heights

    FM-200 GX20 -Nozzle to be 0.3m from wall (50mm)

    3MNovec 1230 -Nozzle to be 0.15m from wall (50mm)

    Maximum nozzle height:4.87m

    FM-200 GX20 - Nozzle orifices 0.15m below

    ceiling (50mm)3MNovec 1230 -

    Nozzle orifices 100mm356mm below ceiling

  • Nozzle Positions FM-200 & 3MNovec 1230

    Nozzles to Obstacles:FM200 >1.2mNovec > 1.8m separation

    Minimum nozzle separation: 3.3m

    180nozzles back-to-back:Minimum separation0.3 0.6m

    180nozzle in middle 1/3 of wall

  • Design Distribution Piping

    Fully Engineered Designs

    Tee splits; permitted type and orientation

    Kidde Hydraulic Flow Calculation Software provides detailed printable report

    Allows for unbalanced apportioning of agent and protects more then 1 compartment.

    NOTE: It is recommended that floor and ceiling voids are protected unless they are completely sealedfrom the main risk.

  • Pipe Rules Permitted Vertical Splits

  • 3. Pipe Rules Unacceptable Vertical Splits

  • Not Acceptable Acceptable Flow splits at tees are sensitive

    to gravity: No vertical side-tee splits No vertical bull-tee splits No vertical nozzle drops

    Chemical Suppressants: Acceptable Tee- Splits

    No vertical nozzle drops

    10 x pipe diameter for Novec 15 x pipe diameter for FM-200

  • 100%30-70% 70-90%

    FM-200 Division of Flow

    30-70%

    FM-200 10-30%100%

    Bull Tees: Both outlets must be in the horizontal plane. The inlet may approach in a horizontal or vertically up or down direction Side Tees: Outlets in the Horizontal Plane only Tee splits going to separate hazards from a common supply line must be spaced a minimum of 15 x nominal pipe diameter apart

    FM-200

  • 100%25-75% 65-90%

    3MNovec 1230 Division of Flow

    25-75%

    100% 10-35%

    Bull Tees: Both outlets must be in the horizontal plane. The inlet may approach in a horizontal or vertically up or down direction Side Tees: Outlets in the Horizontal Plane only Tee splits going to separate hazards from a common supply line must be spaced a minimum of 10 x nominal pipe diameter apart

    3MNovec 1230