358prospektventilc3a1tory en Web

  • Upload
    hqt1989

  • View
    224

  • Download
    0

Embed Size (px)

Citation preview

  • 8/4/2019 358prospektventilc3a1tory en Web

    1/8

    Fans of ZVVZ a.s.

    Fans and Megtec Division

    Fansforyou

  • 8/4/2019 358prospektventilc3a1tory en Web

    2/8

    Fans & Megtec Division

    Fans ProtcentreThe ZVVZ a.s. manuacturing program includes an extensive range o axial and radial

    ans which are used in all spheres o human activities. In a sense, they are make

    the heart o air-conditioning technology. Perhaps, all air-handling acilities consist

    o ans they are the mainspring o airow and pressure necessary or combustion,

    they exhaust ue gas, transport ingredients, aerate loose materials

    Fans carrying the ZVVZ a.s. label can be ound in signicant buildings in the Czech

    and Slovak Republics, but also in Europe, Asia, Arica and even in America.

    Currently we manuacture axial ans with the impeller diameter ranging rom 500 mm

    up to 10,400 mm and radial ans ranging rom diameter 400 mm up to 2,500 mm.

    At customers request, we can supply ans with a special surace nish, made in

    stainless steel, seismically resistant ans, etc.

    Fans & Megtec DivisionFans ProtCenter is involved in the production and supplies o small and big ans including spare parts and service. We ocus on

    supplies or power stations, heating plant and other industrial operations. We also supply ans or ventilation o tunnels, mines

    and underground railways.

    Megtec ProtCenter is or a large part engaged in collaboration and cooperation production with the American company

    MEGTEC in the area o thermal combustion and driers or printing industry. We also ocus on standard mechanical engineering

    production.

    Production and supplier programMains areas o supplies and types o ansApplications or power stations and heating plants, air

    blasting into the combustion chambers o steam boilers,

    power stations, heating plants, or exhaustion o fue gas

    and or other industrial operations.

    Axial overpressure ans with the impeller vanes adjustment

    during operation APJB, APJC, APH (airow up to 800 m3.s-1).

    Axial equipressure ans with ARK, ARM (ARF, ARG) regulation

    device (airow rate up to 650 m3.s-1).

    Radial middle-pressure RSM ans (airow rate up to 160 m3.s-1).Radial high-pressure RVM ans (airow rate up to 150 m3.s-1).

    Radial middle-pressure RSB ans (airow rate up to 50 m3.s-1).

    Ventilation o road and railway tunnelsAxial overpressure ans (also ully reversible) or longitudinal

    ventilation APW (volume ow rate up to 90 m3.s-1).

    Axial overpressure APH ans (ow rate up to 880 m3.s-1).

    Axial overpressure APB ans (ow rate up to 105 m3.s-1).

    Axial overpressure APJ ans (ow rate up to 250 m3.s-1).

    General ventilation and transport o air

    All types o dimensions o the standard ofer can be used.

    Applications or cooling towers, micro-towers,

    condensers

    Axial overpressure APL ans (ow rate up to 1,000 m3.s-1).

    Axial overpressure APMA ans (ow rate up to 215 m3.s-1).

    Axial overpressure APMB ans (ow rate up to 58 m3.s-1).

    Axial overpressure APF ans (ow rate up to 105 m3.s-1).

    Special applicationsUnderground (subways) ventilation APC reversible (volume

    ow rate up to 81m3.s-1).Mines ventilation APH ully reversible, ARK, ARM (volume ow

    rate up to 600 m3.s-1).

    Fans or explosive environment operations.

    Fans or operation in nuclear power plants.

    Other production and servicesManuacture and supplies o an spare parts.

    Comprehensive service o ans.

    Fan service and repairs.

    Measuring o an air technical parameters

    Commissioning o ans

    Alignment o an couplings.Rotary machines diagnostics.

    Rotary machines dynamic balancing.

    1

  • 8/4/2019 358prospektventilc3a1tory en Web

    3/8

    Axial Fans

    Fans designed or ventilation and transport o air

    AXIAL OVERPRESSURE APB FANS

    APB type ans are axial overpressure horizontal ans made in

    diameters 1,120, 1,400, 1,800 and 2,240 mm.

    volume ow rate 7 up to 100 m3.s-1

    total pressure 180 up to 1,480 Pa

    temperature o transported air -20 to +40C

    diameters 1,120, 1,400, 1,800 mm (diameter 2,240 mm is designed

    or road tunnel ventilation)

    AXIAL OVERPRESSURE APH FANS

    APH type ans are designed or air-conditioning, drying, cooling and

    industrial ventilation. Diameters over 1,800 mm are designed mostly

    or traversal ventilation o road tunnels.

    volume ow rate 6 up to 880 m3.s-1

    total pressure 24 up to 5,450 Pa

    temperature o transported air -20 up to +40C

    diameters 1,000 up to 4,000 mm

    AXIAL OVERPRESSURE APJB (APJC) FANS

    Axial overpressure single-stage APJB (two-stage APJC) ans aremade in standard diameters 2,000, 2,240, 2,500, 2,800, 3,150,

    3,550 and 4,000 mm or in other sizes, depending on customers

    needs. Adjustment o air-handling parameters is made by

    adjusting the impeller blades angle during an operation. The

    an is o horizontal type. These ans are mainly used or blasting

    o air into boiler combustion chambers and exhaustion o ue

    gases. They can be also used in other operations, provided

    they meet the working conditions.

    volume ow rate 45 up to 800 m3.s-1

    total pressure 1,000 up to 19,000 Pa

    temperature o transported air up to +200C (peak

    temperature up to +320 C)diameters 2,000 up to 4,000 mm

    AXIAL EQUIPRESSURE ARK AND ARM FANS

    Axial equipressure ans ARK and ARM with diameters 710to 4,000 mm are designed or power plants and industrial

    operations. They are mainly used in boilers or air blasting into

    combustion chamber and exhausting o ue gases. They can

    also be used in other plants or air or hot gases transport.

    total ow rate 2.5 up to 600 m3.s-1

    total ow rate 250 up to 9,100 Pa

    temperature o transported air up to +250C

    diameters 710 up to 4,000 mm

    Fans designed or blasting o air into combustion chambers o heating plants steam boilers, power stations,exhausting o fue gases and or other industrial operations (cement making plants, lime works, mines,etc.).

    2

  • 8/4/2019 358prospektventilc3a1tory en Web

    4/8

    Axial Fans

    AXIAL OVERPRESSURE APW FANS

    Axial ow overpressure ans APW are mainly used or ventilation

    o road and railway tunnels they have been designed or. They

    can be applied in other operations when the appropriate

    environment and parameters are met. These ans are designed

    as horizontal ans with output control by means o the impeller

    blade angle at standstill. The are designed as one-way ans or

    ully reversible.

    main direction volume ow rate 4.8 up to 52.9 m3.s-1

    secondary direction volume ow rate 4.2 up to 44.9 m3.s-1

    static main direction draught 140 up to 2,734 N

    static secondary direction draught 106 up to 1,971 N

    temperature o transported air -30 up to +40C, at relative

    humidity up to 95%diameters 500 up to 1,250 mm

    Temperature resistance:

    AXIAL OVERPRESSURE APB FANSThe APB ans are axial overpressure horizontal ans made in

    diameters 1,120, 1,400, 1,800 and 2,240 mm.

    volume ow rate 35 up to 106 m3.s-1

    total pressure 290 up to 1,000 Pa

    temperature o transported air -20 up to +40C

    during 2 hours up to + 250C

    diameter 2,240 mm

    AXIAL OVERPRESSURE APJ FANS

    The APJ ans are the axial-ow overpressure horizontal ans,

    driven by an electric motor through the V- belt drive. They are

    manuactured in diameters 1,400 and 1,800 mm. The diameter

    2,800 mm is designed or ventilation o road tunnels. They are

    used or air conditioning, ventilation in the industry and or

    orced circulation in drying, cooling and other plants, where

    power regulation while the an operation is required.

    volume ow rate 65 up to 250 m3.s-1

    total pressure 350 up to 2,200 Pa

    temperature o transported air -20 up to +40C

    during 2 hours up to + 250C

    diameter 2,800 mm

    AXIAL OVERPRESSURE APH FANS

    They are designed or air-conditioning, drying and cooling

    plants and industrial ventilation. Diameters over 1,800 mm are

    intended mainly or cross passage road tunnel ventilation.

    volume ow rate 6 up to 808 m3.s-1

    total pressure 240 up to 5,450 Pa

    temperature o transported air -20 up to +40C

    diameters 1,800 up to 3,150 mm

    Fans designed or ventilation o road and railway tunnels

    AXIAL OVERPRESSURE APL FANS

    Axial overpressure ans type APL with diameters 6,000, 8,000

    and 10,400 mm are used exclusively or cooling towers with

    orced draught. These ans are produced as vertical.

    volume ow rate 170 up to 850 m3.s-1

    total pressure 57 up to 220 Pa

    temperature o transported air up to +40C at relative

    humidity up to 100 %

    diameters 6,000, 8,000, 10,400 mm

    AXIAL OVERPRESSURE APMA FANS

    The APMA ventilator ans are axial overpressure vertical ans

    with diameter 4,500 mm. They are used exclusively or cooling

    towers with orced draught.

    volume ow rate 52 up to 215 m3.s-1

    total pressure 30 up to 220 Pa

    temperature o transported air 15 up to +40C at relative

    humidity up to 100 %

    diameter 4,500 mm

    Ventilators or cooling towers with orced draught

    3

    Temperature resistance

    class

    Temperature

    [C]

    Functional time

    [minutes]

    F 300 as per CSN EN 12101-3 300 minimum 60

    F 400 as per CSN EN 12101-3 400 minimum 120

    250C / 120 min. 250 minimum 120

  • 8/4/2019 358prospektventilc3a1tory en Web

    5/8

    Fans designed or ventilation o the undergrounds

    AXIAL OVERPRESSURE APC FANS REVERSIBLE

    The ans are used or the ventilation o the underground and

    everywhere where reversing o the direction o ow is required

    and the regulation during operation in both directions o ow.

    The ans are designed or mounting on the oundation in the

    horizontal position.

    volume ow rate in the main direction 7 up to 81 m3.s-1

    volume ow rate in the secondary direction 13 up to 58 m3.s-1

    total pressure 100 up to 990 Pa

    temperature o transported air -20 up to +40 C

    diameters 1,400 and 1,800 mm (possibility o variable pitch o

    the impeller blades during an operation)

    Fans or air-conditioning,

    cooling plants, industrial ventilation etc.

    AXIAL OVERPRESSURE APJ FANS

    The APJ ventilator ans are the axial overpressure horizontal ans,

    driven by an electric motor through the V- belt drive. They are

    manuactured in diameters 1,400 and 1,800 mm. They are used or

    air conditioning, industrial ventilation and or orced circulation

    in drying, cooling and other plants where power regulation while

    the an operation is required. They can be equipped by a an

    operation monitor enabling monitoring o parameters important

    or trouble-ree operation.volume ow rate 12 up to 92 m3.s-1

    total pressure 200 up to 1,300 Pa

    temperature o transported air -20 up to +60C

    diameters 1,400 and 1,800 mm

    Fans or engines cooling

    AXIAL OVERPRESSURE APV FANS

    The APV ans are the axial overpressure vertical ans with

    diameter 1,120 mm, with suction rom below. They are used or

    engines cooling and in all applications, where their parameters

    are suitable.

    volume ow rate 4 up to 20 m3.s-1

    total pressure 70 up to 700 Pa

    temperature o transported air -20 up to +85C

    diameter 1,120 mm

    Fans designed or air coolers and condensers

    AXIAL OVERPRESSURE APF FANS

    The ans are used or the ventilation o the underground and

    everywhere, where reversing o the direction o ow is required

    and the regulation during operation in both directions o ow. The

    an is designed or mounting on the oundation in the horizontal

    position.

    volume ow rate 7.5 up to 105 m3.s-1

    total pressure 55 up to 310 Pa

    temperature o transported air -30 up to +40C

    diameters 1,800; 2,240; 2,800; 3,550 mm (diameters 2,240 and

    3,550 mm are also or very low temperatures)

    AXIAL OVERPRESSURE APZC FANS

    Axial ow pressure ans APZC with diameters 500 and 630 mm are

    used or air-conditioning, industrial ventilation, in rerigerating

    plants or shops where their parameters comply with requirements

    o customer.

    The ans are designed to be connected to the ducts with the

    anges in horizontal or vertical position.

    volume ow rate 0.7 up to 6.5 m3.s-1total pressure 30 up to 450 Pa

    temperature o transported air -30 up to +60C

    diameters 500 and 630 mm

    Fans or mini-towers and coolers

    AXIAL OVERPRESSURE APMB FAN

    The APMB ans with diameters 1,600 and 2,400 mm are the over-

    pressure axial ans. They can be used in horizontal and vertical

    position.

    volume ow rate 4.5 up to 58 m3

    .s-1

    total pressure 10 up to 215 Pa

    temperature o transported air -5 up to +45C at relative humi-

    dity 100%

    diameters 1,600 and 2,400 mm

    4

  • 8/4/2019 358prospektventilc3a1tory en Web

    6/8

    Radial Fans

    RADIAL HIGH-PRESSURE RVM FANS

    The radial high-pressure ans RVM with diameters 400 to 2,500 mm

    with one-side or both-side suction are used as industrial ans in power

    plants, heating plants, cement works, lime works, stone quarries, l-

    tering plants and at every other plant, where they conorm with their

    technical parameters and workmanship.

    volume ow rate 0.35 up to 180 m3.s-1

    total pressure 700 up to 15,000 Pa

    temperature o transported air -20 up to +400C

    diameters 400 up to 1,250 mm directly or with coupling

    diameters 1,600 up to 2,500 mm with coupling

    - suction in axis- with a suction chamber

    - double-sided suction

    RADIAL HIGH-PRESSURE RVF FANS

    Radial high-pressure one-side suction ans RVF with diameters 355 up

    to 560 mm are used or exhausting o transported air at lters or other

    applications.

    RADIAL MIDDLE-PRESSURE RSB FANS

    Radial middle-pressure ans RSB with diameters 400 up to 1,250 mm

    are designed or blasting o air into combustion chambers o heating

    plants steam boilers, power stations, exhausting o ue gases and orother industrial operations (cement works, lime works, metallurgical

    works, etc.).

    volume ow rate 0.3 up to 40 m3.s-1

    total pressure 400 up to 20,000 Pa

    temperature o transported air -20 up to +400C

    standard type has diameters 400 up to 1,250 mm directly with

    coupling or in larger diameters according to customers request

    RADIAL MIDDLE-PRESSURE RSM FANS

    The medium-pressure one-way suction radial ow ans RSM with dia-

    meters 800 to 2,500 are used or small and medium boiler houses.

    volume ow rate 2 up to 70 m3.s-1

    total pressure 300 up to 4,500 Pa

    temperature o transported air -20 up to +250C

    diameters 800 up to 2,000 mm

    Fans designed or separating plants o industrial vacuum

    cleaners.

    RADIAL HIGH-PRESSURE RVG FANS

    Fans o RVG type are centriugal high-pressure one-side-suction eight-

    stage horizontal ans with motor drive via exible coupling.volume rate o ow 1,500 m3.s-1

    total pressure 29,500 Pa

    temperature o transported gaseous uid rom - 15 to + 40 C

    diameter 560 mm

    Fans designed or blasting o air into combustion chambers o heating plants steam boilers, power stations,

    exhausting o fue gases and other industrial operations (cement works, lime works, mines etc.).

    5

  • 8/4/2019 358prospektventilc3a1tory en Web

    7/8

    Fans designed or wind tunnels and climatic tunnels

    ZVVZ a.s. supplies ans or wind and climatic tunnels. It is possible to supply

    both main ans and auxiliary and service ans or these types o tunnels. The

    ans comply with the strictest requirements demanded or such equipment

    and the ans can operate in climatic, acoustic or energy tunnels. Rotating

    an components are made o steel or aluminium, or can be delivered made

    o composite materials, which complies with extreme requirements needed

    or acceleration or deceleration o the transported air. In developing

    these products, ZVVZ a.s. cooperates with oremost R&D institutes, which

    makes it possible or our company to ofer products based on the latest

    knowledge and to give to our customers advantages to be one step ahead

    o competitors.

    Measuring o air technical parameters in ans is divided into testlaboratory measurements or tests during operation. ZVVZ can

    make problem-ree normative measurements using standard

    digital manometers and the collected data are subsequently

    processed semi-automatically.

    Aerodynamic tests always run in three stages, on a 600 mm

    diameter testing line:

    1. measuring o aerodynamic class characteristics

    2. probing o ow patterns in selected operating points

    3. measuring o perormance areas o the whole eld

    Measurement o aerodynamic characteristics usually

    includes measuring o the ollowing parameters:volume ow rate

    barometric pressure measured by barometer in test laboratory

    temperature o test laboratory by thermocouplestatic pressure on inlet orice

    our static pressures in the box in the suction plane

    total temperature in the suction plane in the middle o airow

    duct

    22 static pressures in the housing in the discharge plane

    total temperature in the discharge plane in the middle o

    airow duct

    dynamometer torque

    Functional test o ansvibration measurement

    strength test o impellers, blades (shredder)requency analysis

    noise analysis

    Methods o measuring o air technical parameters, equipment and instrumentation

    Shredder (strength test of impeller blades) Test line diagram Vibration measurement

    6

  • 8/4/2019 358prospektventilc3a1tory en Web

    8/8