35” CONDENSING GAS FURNACES Vent and Combustion Air System Design & Installation 1 Add Distributor Art and Text Here

35” CONDENSING GAS FURNACES Vent and Combustion Air System Design & Installation

Embed Size (px)

DESCRIPTION

35” CONDENSING GAS FURNACES Vent and Combustion Air System Design & Installation. Add Distributor Art and Text Here. Vent and Combustion Air Design and Installation Contents. Section 1: New 35” Condensing Furnace Design Section 2: National and International Codes - PowerPoint PPT Presentation

Citation preview

Page 1: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

35” CONDENSING GAS FURNACES

Vent and Combustion Air System Design & Installation

1

Add Distributor Art and Text Here

Page 2: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

2

Section 1: New 35” Condensing Furnace Design

Section 2: National and International Codes

Section 3: Vent and Combustion Air System Design Rules

Section 4: Common Vent Installation Problems

Vent and Combustion Air Design and InstallationContents

Page 3: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

3

Section 1

35” Condensing Furnace Design

Vent and Combustion Air Design and Installation

Page 4: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

Liquid

VaporVapor

Liquid

Vent and Combustion Air Design and InstallationFlue Gas Water Vapor Comparison

4

Legacy 92% New 92% New 98%

Lower flue gas temps More liquid water in vent

Vent

Drain

Furnace Water Vapor

Vapor

Liquid

Flue Gas Temp

low

high

Liquid passed out furnace drain

Total water vapor passed into vent

Page 5: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

Vent and Combustion Air Design and InstallationVent Liquid Water Load Comparison

5

Legacy 92% New 92% New 98%

More liquid water in vent Vent slope is important

Vent Liquid Water Load

VaporVapor

Vapor

Inducer Airflow

Inducer Airflow

Inducer Airflow

Liquid passed out furnace drain

LiquidLiquid

LiquidTotal water vapor passed into vent

Page 6: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

Vent and Combustion Air Design and InstallationPressure Switch Operation: Single and 2-Stage

6

LPS (Low Pressure Switch)Measures: collector box pressure

Purpose: Prevent furnace from running with a partially or fully blocked heat exchanger, trap or condensate drain

Low Pressure Switch is used to prevent carbon monoxide from entering a living space.

Heat Exchanger

Pressure Switch

Collector BoxTrap

Page 7: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

Vent and Combustion Air Design and InstallationPressure Switch Operation: Single and 2-Stage

7

HPS (High Pressure Switch)Measures: inducer housing pressure

Purpose: Prevent furnace from running with a partially or fully blocked vent

High Pressure Switches is used to prevent carbon monoxide from entering a living space.

Pressure Switch

Inducer Housing

Page 8: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

Vent and Combustion Air Design and InstallationPressure Switch Operation: Single and 2-Stage

8

Status Code 3 (Single & 2-

stage models)

LPS (Low Pressure Switch)Measures: collector box pressure

Purpose: Prevent furnace from running with a partially or fully blocked heat exchanger, trap or condensate drain

HPS (High Pressure Switch)Measures: inducer housing pressure

Purpose: Prevent furnace from running with a partially or fully blocked vent

Pressure switches are used to prevent carbon monoxide from entering a living space.

Pressure switches are not for “furnace proving”.

Page 9: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

9

Section 2

National and International Codes

Vent and Combustion Air Design and Installation

Page 10: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

10

National Standard Plumbing Code 2009International Plumbing Code 2012

Vent and Combustion Air Design and InstallationPlumbing Codes and Furnace Vent Systems

NSPC plumbing definition excludes piping for ‘environmental control’.IPC plumbing definition excludes fuel gas appliance exhaust or combustion air.

NSPC vent definitions do not refer to fuel gas appliance exhaust.IPC vent definitions do not include fuel gas appliance exhaust or combustion air.

The National and International Plumbing Codes do not apply to gas furnace vent systems.

Page 11: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

Vent and Combustion Air Design and Installation Fuel Gas Codes and Furnace Vent Systems

11

NFGC and IGFC refer to manufacturer’s Installation Instructions for vent design, sizing and installation.

IFGC refers to manufacturer’s Installation Instructions for vent support, combustion and ventilation air requirements

Vent and combustion air termination location is specified in NFGC.

Make-up and combustion air is specified in IFGC.

Refer to National and International Fuel Gas Codes and manufacturer’s Installation Instructions for vent, combustion air, ventilation and make-up air design and installation.

11

NATIONAL FUEL GAS CODE 2012 ANSI Z223.1, NFPA 54

INTERNATIONAL FUEL GAS CODE 2012**IFGC applies to residential gas furnaces in 1 or 2 family dwellings and townhouses.

Page 12: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

12

Section 3

Vent and Combustion Air System Design Rules

Vent and Combustion Air Design and Installation

Page 13: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

Unit Size 80,000 100,000 Pipe Dia. (in) 1 ½ 2 2 ½ 3 4 2 2 ½ 3 4

Model Family

Single Stage 92% & 95%, Two Stage

Modulating Single Stage 92% & 95%, Two Stage

Modulating All Single Stage 92% & 95%, Two Stage

Modulating All

Alt

itu

de

(fee

t)

0-2000 15 25 50 95 130 175 200 20 35 80 175 200 2001-3000

10

20 45 65

125 165 185 15

30 75

165 185 3001-4000 115 155 175

155 175

4001-4500

15

40 110 150 165

10

70 170 4501-5000 145 160

65 150 165

5001-6000 35 55 100 135 150 25 140 155 6001-7000

N/A 30 50 90

125 140 20

60 135 145 7001-8000 120 125

N/A 55 125 135

8001-9000 10

25 45 80 110 115 50 115 125 9001-10000 20 40 75 100 105 15 45 100 115

Vent and Combustion Air Design and InstallationVent Design Rules

13

Do not exceed the maximum equivalent vent length in the Installation Instructions.

Affect on Operation: Vent system pressure drop is too high. Burners starved of combustion air resulting in incomplete combustion.

Maximum Equivalent Vent Length (Example)

Page 14: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

Unit Size 80,000 100,000 Pipe Dia. (in) 1 ½ 2 2 ½ 3 4 2 2 ½ 3 4

Model Family

Single Stage 92% & 95%, Two Stage

Modulating Single Stage 92% & 95%, Two Stage

Modulating All Single Stage 92% & 95%, Two Stage

Modulating All

Alt

itu

de

(fee

t)

0-2000 15 25 50 95 130 175 200 20 35 80 175 200 2001-3000

10

20 45 65

125 165 185 15

30 75

165 185 3001-4000 115 155 175

155 175

4001-4500

15

40 110 150 165

10

70 170 4501-5000 145 160

65 150 165

5001-6000 35 55 100 135 150 25 140 155 6001-7000

N/A 30 50 90

125 140 20

60 135 145 7001-8000 120 125

N/A 55 125 135

8001-9000 10

25 45 80 110 115 50 115 125 9001-10000 20 40 75 100 105 15 45 100 115

Vent and Combustion Air Design and InstallationVent Design Rules

14

Use the smallest practical vent diameter listed in the Installation Instructions.

Affect on Operation: Vent system pressure drop is too low. Too much combustion air causes an unstable flame.

Maximum Equivalent Vent Length (Example)

Page 15: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

Vent and Combustion Air Design and InstallationVent Design Rules

15

Affect on Operation: Vent or combustion air termination becomes partially or fully blocked by snow or ice. Burners starved of combustion air resulting in incomplete combustion.

Locate vent and combustion air terminations above the anticipated snow line.

Page 16: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

Space combustion air and vent terminations away from another fuel gas appliance vent termination, dryer vent and plumbing stack by the distance stated in the National or International Fuel Gas Code

Vent and Combustion Air Design and InstallationVent Design Rules

16

Affect on Operation: Vent or combustion air termination becomes partially or fully blocked by ice. Burners starved of combustion air resulting in incomplete combustion.

Affect on Operation: Flue gas is pulled into combustion air termination. Burners starved of oxygen resulting in incomplete combustion.

Page 17: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

Vent and Combustion Air Design and InstallationVent Design Rules

17

Locate vent and combustion air termination is in a space that is protected from prevailing winds.

Affect on Operation: Inducer is unable to overcome wind pressure.

Page 18: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

Vent and Combustion Air Design and InstallationVent Design Rules

18

Do not locate vent and combustion air terminations on an inside corner as described in the Installation Instructions.

Affect on Operation: Combustion products are pulled into combustion air termination. Burners are starved of oxygen resulting in incomplete combustion.

Page 19: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

19

Section 4

Vent Installation Problems

Vent and Combustion Air Design and Installation

Page 20: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

Vent and Combustion Air Design and InstallationCommon Vent System Installation Problems

20

Affect on Operation: Liquid water collects at elbows or horizontal sections causing partial blockage and water slugs create pressure waves.

Pipe slope is less than ¼” per foot toward furnace.

Page 21: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

Vent and Combustion Air Design and InstallationCommon Vent System Installation Problems

21

Too much space between pipe support resulting in sags.

Affect on Operation: Liquid water collects in the low section of vent pipe, which causes partial blockage and pressure changes.

Page 22: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

Vent and Combustion Air Design and InstallationCommon Vent System Installation Problems

22

Horizontal sections less than 4 feet must have a minimum ¼” per foot slope to the furnace.

Affect on Operation: Liquid water collects in horizontal section causing partial blockage and water slugs create pressure waves.

Page 23: 35” CONDENSING GAS FURNACES Vent and Combustion Air System  Design & Installation

Vent and Combustion Air Design and InstallationResults of Poor Vent System Design and Installation

23

Pressure Switch Opens

Loss of Flame Sense

No Heat

Customer Dissatisfaction