Upload
harsh-tanwar
View
222
Download
0
Embed Size (px)
Citation preview
8/6/2019 33 kV yard
1/31
33 kV yard
Components of the 33kV yard
1. Generator Transformer(GT)2. Unit Auxiliary Transformer(UAT)3. Station Transformer(ST)4. Potential Transformer5. Lightening Arrestor(LA)6. Isolator7. Current Transformer8.
Circuit Breaker9. Capacitor Bank
8/6/2019 33 kV yard
2/31
Generator Transformer (GT)
The generator transformer is the first essential component for energy transmission,
allowing energy supplied by the generator to be transferred to the network at the
required voltage.
This is a type of Power Transformer where the LV winding is connected to the
generator through the bus duct and HV winding to the transmission system.
Generator Transformer is designed to withstand over voltage caused by sudden
load throws off from the generator. It is built as a single or three phase unit and
located in power stations.
8/6/2019 33 kV yard
3/31
BHARAT HEAVY ELECTRICALS LIMITED
FOR 85/59.5/42.5 MVA, 10.5/33.5 KV, 3 phase, 50 Hz
OFAF/ONAF/ONAN cooled power transformer
2 x 67.5 MW
8/6/2019 33 kV yard
4/31
TECHNICAL DATASHEET
Item Unit Particulars
Name of Manufacturer BHEL Jhansi
Reference Standards IS 2026
Service OutdoorInstallation Outdoor
Rated No Load Voltage
HV Winding KV 33.5
LV Winding KV 10.5
Type of Cooling
(ONAN/ONAF/OFAF/OFWF)
OFAF/ONAF/ONAN
Rated Power under site conditions corresponding
to various methods of cooling.
ONAN MVA 42.5
ONAF MVA 59.5
OFAF MVA 85.0
No. of Phases 3
Rated Frequency Hz 50
Winding Connections
HV windings Star
LV windings delta
VectorGroup Reference Ynd11
Type of Tap Changer
On Load / off circuit Off circuit
On HV/MV/LV winding ON HV for HV
variation
Total range of tapping +/- % +/-5%
Size of tapping step % 2.5% step
Impulse voltage withstand level
8/6/2019 33 kV yard
5/31
HV winding KVp 170
LV winding KVp 75
Power frequency withstand voltage for one minute
HV winding KV(rms) 70
LV winding KV(rms) 28
No Load Losses at rated frequency
90% rated voltage KW 28.71 23.92
100% rated voltage KW 34.5 29.71
110% rated voltage(58 KW approx.)
KW 40.71 37.00
Load losses at normal ratio rated current and 75deg.C
KW 281.96 276.93
Tolerance on losses +a) No Load Lossesb) Load Lossesc) Total Losses
% Nil on Guaranteedlosses
Guaranteed Max. Temp. Rise of
Oil by thermometer Deg.C 50
Winding by resistance fora) ONANb) ONAFc) OFAF
Deg.C 55
5555
Efficiency at 75 deg.C and unity power factor for
100% full load % 99.63 99.64
75%full load % 99.70 99.71
50%full load % 99.75 99.77
Voltage Regulation at Full Load at 75 deg.C
Unity power factor % 1.21 1.23
0.8 power factor (lagging) % 8.79 8.90
8/6/2019 33 kV yard
6/31
Terminals of Tertiary winding brought out tobushing
Yes/No NA
Type of magnetic circuit Core/Shell Core
Type of core joints Mitred
Type of Windings
H.V. Helical
L.V. Helical
Type of insulation
H.V. winding Kraft + Press Board
L.V. winding + Transformer Oil
Core to adjacent windings Press Board + OilBetween Windings Press Board + Tr. Oil
Bushings
HV Bushings
Rated Voltage KV 36
Rated Current A 2000
1.2/50/ U/S impulse withstand1 minute power frequency
KVp(rms)
170
LV Bushings
Rated Voltage KV 24
Rated Current A 5500
1.2/50/ S impulse withstand
1 minute power frequency
Maximum Flux Density
At Rated Voltage Wb/mxm 1.58
At 110% rated voltage Wb/mxm 1.74
Maximum current density
H.V. A/cmxcm 350 to 400
L.V. A/cmxcm 350 to 400
Magnetizing current at rated voltage and 0.17 0.21
8/6/2019 33 kV yard
7/31
8/6/2019 33 kV yard
8/31
Unit Auxiliary Transformers (UAT)
The Unit Auxiliary Transformer is the Power Transformer that provides power tothe auxiliary equipment of a power generating station during its normal operation.
This transformer is connected directly to the generator out-put by a tap-off of the
isolated phase bus duct and thus becomes cheapest source of power to the
generating station.
It is generally a three-winding transformer i.e. one primary and two separate
secondary windings. Primary winding of UAT is equal to the main generator
voltage rating. The secondary windings can have same or different voltages i.e.
generally 11KV and or 6.9KV as per plant layout.
8/6/2019 33 kV yard
9/31
BHARAT HEAVY ELECTRICALS LIMITED
FOR 9 MVA , 10.5/6.8 KV , 3 phase, 50 Hz
ONAN cooled power transformer
8/6/2019 33 kV yard
10/31
TECHNICAL DATASHEET
Item Unit Particulars
Name of Manufacturer BHEL Jhansi
Reference Standards IS 2026
Service OutdoorInstallation Outdoor
Type of Transformer
Three/two windings/auto Two winding
No. of Transformers 2
Rated No Load Voltage
HV Winding KV 10.5
LV Winding KV 6.8
Type of Cooling(ONAN/ONAF/OFAF/OFWF)
ONAN
Rated Power under site conditions correspondingto various methods of cooling.
ONAN MVA 9.0
ONAF MVA -
OFAF MVA -
No. of Phases 3
Rated Frequency Hz 50
Winding Connections
HV windings Delta
LV windings Star
VectorGroup Reference Dyn1
Type of Tap Changer
On Load / off circuit Off circuit
On HV/MV/LV winding ON HV for HVvariation
Total range of tapping +/- % +/-5%
Size of tapping step % 2.5% step
8/6/2019 33 kV yard
11/31
Impulse voltage withstand level
HV winding KVp 75
LV winding KVp 60
Power frequency withstand voltage for one minuteHV winding KV(rms) 28
LV winding KV(rms) 20
No Load Losses at rated frequency
90% rated voltage KW 05.77 05.97
100% rated voltage KW 07.03 07.50
110% rated voltage(58 KW approx.)
KW 09.77 10.46
Load losses at normal ratio rated current and 75
deg.C
KW 38.88 42.8
Tolerance on losses +
d) No Load Lossese) Load Losses
) Total Losses
% Nil on Guaranteedlosses
Guaranteed Max. Temp. Rise of
Oil by thermometer Deg.C 50
Winding by resistance for
d) ONANe) ONAFf) OFAF
Deg.C
55-
-
Efficiency at 75 deg.C and unity power factor for
100% full load % 99.49 99.44
75%full load % 99.57 99.53
50%full load % 99.63 99.60
Voltage Regulation at Full Load at 75 deg.C
8/6/2019 33 kV yard
12/31
Unity power factor % 0.71 0.72
0.8 power factor (lagging) % 5.00 4.76
Terminals of Tertiary winding brought out to
bushing
Yes/No NA
Type of magnetic circuit Core/Shell Core
Type of core joints Mitred
Type of Windings
H.V. Disc
L.V. Helical
Type of insulation
H.V. winding Kraft Parer + PressBoard
L.V. winding + Transformer OilCore to adjacent windings Press Board + Tr. Oil
Between Windings Press Board + Tr. Oil
Bushings
HV Bushings
Rated Voltage KV 17.5
Rated Current A 1000
1.2/50/ U/S impulse withstand1 minute power frequency
KVpKV(rms)
9545
LV Bushings
Rated Voltage KV 7
Rated Current A 2000
1.2/50/ S impulse withstand
1 minute power frequency
KVp
KV(rms)
60
20
Maximum Flux Density
At Rated Voltage Wb/mxm 1.55
At 110% rated voltage Wb/mxm 1.71
Maximum current density
H.V. A/cmxcm 350 to 400
L.V. A/cmxcm 350 to 400
8/6/2019 33 kV yard
13/31
Magnetizing current at rated voltage and
frequency (% of full load current )
0.3 0.41
(less than 1%)
Cooling Fans NA
d)
Typee) Quantityf) Rating
--
-
Cooling Oil Pump NA
d) Type No. -e) Quantity No. -
f) Rating KW -
Approximate Weight ofCore & Winding Kg 14000
Tank Fittings & Coolers Kg 8630
Oil Kg 5470
Total Weight without oil Kg 22630
Untanking Weight Kg 14000
List of test which may be carried out at extra costquoted elsewhere 1) Impulse test2)Temperature rise
test3)Acoustic noise level
4)3rd
harmoniccontent in no load
current
8/6/2019 33 kV yard
14/31
Station Transformer (ST)
Station transformer forms one of the essential components of the power station. It
is used for provides power to some of the equipments of the power plant in normal
functioning mode. Unlike UAT, it draws power form the grid.
ST forms important part when station is not operational. In that case, all power
supplied to the equipments of station by ST.
8/6/2019 33 kV yard
15/31
BHARAT HEAVY ELECTRICALS LIMITED
FOR 15/10.5 MVA, 32/7 KV, 3 phase, 50 Hz
ONAF/ONAN cooled power transformer
With on load tap changer
8/6/2019 33 kV yard
16/31
TECHNICAL DATASHEET
S.No. Item Unit Particulars
01 Name of Manufacturer BHEL Jhansi
02 Reference Standards IS 2026
03 Service Outdoor04 Installation Outdoor
Rated No Load Voltage
HV Winding KV 32
MV Winding KV 7
LV Winding KV 7
Type of Cooling
(ONAN/ONAF/OFAF/OFWF)
ONAF/ONAN
Rated Power under site conditions correspondingto various methods of cooling.
ONAN MVA 10.5
ONAF MVA 15.0
OFAF MVA -
No. of Phases 3
Rated Frequency Hz 50
Winding Connections
HV windings Star
MV windings Star
LV windings Delta closed with only
one terminal broughtoutside
VectorGroup Reference YYnod11
Type of Tap Changer
On Load / off circuit On load
On HV/MV/LV winding ON HV for HV
variation
Total range of tapping +/- % +/-10.0
8/6/2019 33 kV yard
17/31
Size of tapping step % 1.25% step
Impulse voltage withstand level
HV winding KVp 170
MV winding KVp 60LV winding KVp 60
Power frequency withstand voltage for one minute
HV winding KV(rms) 70
MV winding KV(rms) 20
LV winding KV(rms) 20
No Load Losses at rated frequency
90% rated voltage KW 8.21 8.92
100% rated voltage KW 9.90 11.00
110% rated voltage(58 KW approx.)
KW 12.57 13.83
Load losses at normal ratio rated current and 75deg.C
KW 70.82 76.00
Tolerance on losses +
g) No Load Lossesh) Load Lossesi) Total Losses
% Nil on Guaranteedlosses
Guaranteed Max. Temp. Rise of
Oil by thermometer Deg.C 50
Winding by resistance forg) ONANh) ONAFi) OFAF
Deg.C55
55-
Efficiency at 75 deg.C and unity power factor for
100% full load % 99.46 99.41
75%full load % 99.56 99.52
50%full load % 99.63 99.60
8/6/2019 33 kV yard
18/31
Voltage Regulation at Full Load at 75 deg.C
Unity power factor % 0.85 0.90
0.8 power factor (lagging) % 5.84 5.88
Terminals of Tertiary winding brought out to
bushing
Yes/No Only one terminal
brought out
Type of magnetic circuit Core/Shell Core
Type of core joints Mitred
Type of Windings
H.V. Disc
M.V. Helical
L.V. Spiral
Type of insulation
H.V. winding Kraft + Press Board
M.V. winding + Transformer Oil
L.V. winding Press Board + Oil
Core to adjacent windings SRBP cylinder + Tr.
Oil
Between Windings Press Board + Tr. Oil
Bushings
HV Bushings
Rated Voltage KV 36
Rated Current A 630
1.2/50/ U/S impulse withstand1 minute power frequency
KVpKV(rms)
170840
MV Bushings
Rated Voltage KV 7
Rated Current A 20001.2/50/ S impulse withstand1 minute power frequency
KVpKV(rms)
6020
LV Bushings
8/6/2019 33 kV yard
19/31
Rated Voltage KV 17.5
Rated Current A 1000
1.2/50/ S impulse withstand
1 minute power frequency
KVp
KV(rms)
95
45
Maximum Flux Density
At Rated Voltage Wb/mxm 1.52
At 110% rated voltage Wb/mxm 1.67
Maximum current density
H.V. A/cmxcm 350 to 400
L.V. A/cmxcm 350 to 400
M.V. A/cmxcm 350 to 400
Magnetizing current at rated voltage andfrequency (% of full load current )
0.35 0.42(less than 1%)
Cooling Fans
g) Typeh) Quantityi) Rating
Outdoor
6 (4 running & 2stand by)
0.085 KW
Cooling Oil Pump
g) Type No. -h) Quantity No. -
i) Rating KW -
Approximate Weight of
Core & Winding Kg 20000
Tank Fittings & Coolers Kg 12720
Oil Kg 8280
Total Weight without oil Kg 32720
Untanking Weight Kg 20000
8/6/2019 33 kV yard
20/31
DESCRIPTIONOF
TRANFORMER(GT,UAT,ST)
General
The transformer is oil immersed with a rating of 9 MVA under ONAN conditions respectively.
The transformer is provided with tank mounted radiators and associated control equipment. It is
also equipped with off circuit load tap switch on HV winding.
Transformer
Core
The magnetic circuit is a three limbed core type construction, each limb being mitered with top
and bottom yokes. The laminations are made of high grade non-ageing cold rolled grain oriented
silicon alloy steel. The insulation of lamination is of carlite coating.
The yokes bolts, End frame, clamp plates and core are insulated from each other to withstand a
test pressure of 2 KV rms 50 Hz for one minute.
Windings
The windings are arranged in concentric formation with LV winding next to the core, then HVand HV tapping winding.
Conservator
As the temperature of the transformer oil increases or decreases there is a corresponding rise and
fall in the oil volume. To account for this an expansion vessel (conservator) is connected to the
transformer tank. It has the capacity between the maximum and the minimum oil level equal to
7.5% of the total oil in the transformer (tank + cooling system)
The conservator is filled to level appropriate to the filling temperature and in the remaining
portion is Air Cell which I connected to atmosphere through a breather. If the volume of the oil
in the transformer increases the conservator breathes out air and if the volume of oil in the
8/6/2019 33 kV yard
21/31
8/6/2019 33 kV yard
22/31
PressureReliefValve
In the case of severe fault in the transformer, the internal pressure may build up to a very high
level, which may result in an explosion of the tank. To avoid such a contingency a pressure relief
valve is fitted at the transformer top cover. It is a spring loaded and has contacts for tripping the
transformer.
Oil Transformer Indicator
Oil Transformer Indicator is a distance thermometer operating on the principle of liquid
expansion (mercury in steel capillary). It provides a local indication of the top oil temperature at
the Marshalling kiosk. The bulb is enclosed in a pocket and the pocket is fixed on the
transformer at the hot test oil region. The pocket has to be filled with the transformer oil. The oil
temperature indicator is provided with a maximum pointer and two mercury switches; one for
alarm and other for trip.
Switches are suitable for 250 volt AC or DC. The mercury switches are adjustable to make
contact between 50deg.C and 120deg.C.
The temperature for alarm and trip contact setting shall be as under:
i) Alarm = 85 deg.Cii) Trip = 90 deg.C(At an ambient temperature of 45 deg.C)
Winding TemperatureIndicator
This indicator operating on the principle of liquid expansion provides local indication at the
marshalling box of hot spot temperature of winding. The winding hot spot to top oil temperature
differential is simulated by means o heater coil fitted around the operating below. A current
proportional to the load current is fed to the heater coil from a current transformer, fitted on the
2U phase of LV winding.
The bulb of the WTI fitted at the top cover senses top oil temperature. Thus winding temperatureindicators temperature reading are proportional to load current plus top oil temperature.
The indicator is fitted with maximum pointer and four mercury switches. One is used for alarm
and 2nd
is used for trip and other two switches are as spare. All the switches are adjustable on
their individual scales over the entire working range of the instrument and are suitable for 250
volts AC or DC.
8/6/2019 33 kV yard
23/31
The temperature for the alarm and the trip contact setting shall be as followed:
i) Alarm = 90 deg.Cii)
Trip = 100 deg.C(Ambient temperature considered for the above settings 45 deg.C)
Earthing Arrangement
i) Core to end frame earthingii)
Tank to Tank cover earthing
iii) Earthing of the Tank
Marshalling Kiosk
The M.Kiosk is a weather proof steel housing which is suitable for ground mounting. The kiosk
is provided with a metal clad heater along with thermostat switch for the prevention of
condensation.
Gas and OilRelay
(Buchholz Relay)
A protective device on transformers
Company: ATVUS
It keeps round the clock vigilance on transformers and indicates the faults with help of two
floats, upper and lower
i) Giving alarm signal for minorii) Isolating the transformer from the main supply in the event of heavy faults inside the
transformer or fail of level below the mounting height of the relay.
8/6/2019 33 kV yard
24/31
It is connected in the pipe connection between the transformer and the expansion vessel so that
normally it is usually connected to an external alarm circuit.
Dehydrating
Breather
A dehydrating breather is used to dry the air that enters a transformer as the volume of the
transformer oil decreases because of a fall in the temperature.
Air entering the breather is first drawn through an oil seal and passes upwards through the silica
gel crystals to the connecting pipe at the top. During the upward passage of air, any moisture
present is absorbed by the dry silica gel.
The oil seal ensures that the gel absorbs moisture only when the transformer is breathing.
MaintenanceInspect the breather every 3 months more frequently if found by experience to be necessary.
When the crystal is first installed, the crystals have a blue tint, and after a period of operation the
colour of the tinted crystals gradually changes to pink; this is the indication that the silica gel is
becoming saturated and losing its absorbent properties. When there is preponderance of pink
crystals the gel should be changed or reactivated.
Silica gel may be reactivated by heating in a shallow pan at a temperature of 150deg.C to
200deg.C for two or three hours when the crystals should have regained their original blue tint.
8/6/2019 33 kV yard
25/31
Voltage Transformer
Voltage transformers (VT) or potential transformers (PT) are another type of instrumenttransformer, used for metering and protection in high-voltage circuits.
They are designed to present negligible load to the supply being measured and to have a precise
voltage ratio to accurately step down high voltages so that metering and protective relay
equipment can be operated at a lower potential.
Typically the secondary of a voltage transformer is rated for 69 V or 120 V at rated primary
voltage, to match the input ratings of protective relays.
Specification oftransformer
1. Standards IS 3156
2. High system voltage K.V. 36
3. Frequency Hz 50
4. Oil Ltrs/kg 16
5. Insulation level KV
KVp
70 170
6. RVF/times Sec 1.2/1.57. Total weight Kg 90
8/6/2019 33 kV yard
26/31
Lightening Arrester (LA)
A lightning arrester is a device used on electrical power systems to protect the insulation on thesystem from the damaging effect of lightning. Metal oxide varistors (MOVs) have been used for
power system protection since the mid 1970s. The typical lightning arrester also known as surge
arrester has a high voltage terminal and a ground terminal. When a lightning surge or switching
surge travels down the power system to the arrester, the current from the surge is diverted around
the protected insulation in most cases to earth.
Specification ofLightening Arrestors
Zinc Oxide Lightening Arrestor
1. Rating KV 30
2. Frequency Hz 50
3. C.O.V KV 25
4. P.R. Class A,40KV
5. N.DC KA 106. Model MWL
8/6/2019 33 kV yard
27/31
8/6/2019 33 kV yard
28/31
Circuit Breaker
A circuit breaker is an automatically operated electrical switch designed to protect an electrical
circuit from damage caused by overload or short circuit. Its basic function is to detect a fault
condition and, by interrupting continuity, to immediately discontinue electrical flow. Unlike a
fuse, which operates once and then has to be replaced, a circuit breaker can be reset (either
manually or automatically) to resume normal operation. Circuit breakers are made in varying
sizes, from small devices that protect an individual household appliance up to large switchgear
designed to protect high voltage circuits feeding an entire city.
SF6 circuit breaker is used in the station. In this type of breaker the arc in chamber is
extinguished by sulfur hexafluoride gas.
(All above Circuit breaker are medium-voltage circuit breakers rated between 1 and 72 kV.
These are also operated by current sensing protective relays operated through currenttransformers)
Circuit Breakers may be connected into the circuit by bolted connections to bus bars or wires,
especially in outdoor switchyards.
Specification ofCircuit Breaker
y Type: Gas Circuit Breaker,SF61. Type 70-SFM-32 A
2. Rated Lightening Impulse withstand voltage KVp 350
3. Rated short circuit breaking current KA 31.5
4. Rated operated pressure Kg/cmxcm.g 15 (at 20 deg.C)
5. First pole to clear factor 1.5
6. Rated duration of short circuit current Sec 3
7. Gas Weight Kg 6
8. Rated voltage KV 72.5
9. Frequency Hz 50
10. Rated normal current A 2000
11. Rated closing voltage V(DC) 220
12. Rated opening voltage V(DC) 220
13. Total weight of the gas Kg 1650
8/6/2019 33 kV yard
29/31
Current Transformer
A curren
t transf
ormer (CT) is used for measurement of electric currents.
Use:
y When current in a circuit is too high to directly apply to measuring instruments, a currenttransformer produces a reduced current accurately proportional to the current in the
circuit, which can be conveniently connected to measuring and recording instruments.
y It also isolates the measuring instruments from what may be very high voltage in themonitored circuit.
Safety precautions
Care must be taken that the secondary of a current transformer is not disconnected from its load
while current is flowing in the primary, as the transformer secondary will attempt to continuedriving current across the effectively infinite impedance. This will produce a high voltage across
the open secondary (into the range of several kilovolts in some cases), which may cause arcing.The high voltage produced will compromise operator and equipment safety and permanently
affect the accuracy of the transformer.
Specification ofTransformer
1. Standard IS 2705
2. Insulation Level K.V. K.V.p 75/170
3. S.T. Current K.A./sec 31.5/3
4. Frequency Hz 50
5. Rated primary current A 2000
6. System voltage KV 33
7. Electrical specification number 6306162
8. Serial number 2216368
8/6/2019 33 kV yard
30/31
Aluminum Conductor SteelReinforced(or
ACSR)
Aluminum Conductor Steel Reinforced (or ACSR) cable is a specific type of high-capacity,
high-strength stranded cable typically used in overhead power lines. The outer strands arealuminum, chosen for its excellent conductivity, low weight and low cost. The center strand is of
steel for the strength required to support the weight without stretching the aluminum due to itsductility. This gives the cable an overall high tensile strength.
ACSR cables are available in several specific sizes, with multiple center steel wires andcorrespondingly larger quantities of aluminum conductors. For example, an ACSR cable with 72
aluminum conductors that requires a core of 7 steel conductors will be called 72/7 ACSR
cable.
[1]
The higher resistance of the steel core is of no consequence to the transmission of electricity
since it is located far below the skin depth where essentially no AC current flows.
8/6/2019 33 kV yard
31/31
Capacitor Bank
A capacitor bank is a grouping of several identical capacitors interconnected in parallel or in
series with one another. These groups of capacitors are typically used to correct or counteract
undesirable characteristics, such as power factor lag or phase shifts inherent in alternating current
(AC) electrical power supplies. Capacitor banks may also be used in direct current (DC) power
supplies to increase stored energy and improve the ripple current capacity of the power supply.
The use of a capacitor bank in the power supply system effectively cancels out or counteracts
these phase shift issues, making the power supply far more efficient and cost effective. The
installation of a capacitor bank is also one of the cheapest methods of correcting power lag
problems and maintaining a power factor capacitor bank is simple and cost effective. One thingthat should always be kept in mind when working with any capacitor or capacitor bank is the fact
that the stored energy, if incorrectly discharged, can cause serious burns or electric shocks. The
incorrect handling or disposal of capacitors may also lead to explosions, so care should always
be exercised when dealing with capacitors of any sort.