    Installation Instructions

    Accessory Compressor Protection Control SystemPart No. 30GB900131

    50 and 60 Hz

    GENERAL

    Check Package Contents (Table 1) for shippingdamage. If damage is found or any part(s) is missing, file aclaim with the shipper immediately.

    Table 1 Package Contents

    LEGEND

    CPCS Compressor Protection Control System

    INSTALLATION

    Units without Current Sensing Board1. Cut off all quick-connect terminals from wires connected

    to compressor control relays, being careful not to cut offwire markers.

    2. Remove and discard the 2 control relays (see Fig. 1).

    3. Using screws provided, position the 2 compressor protec-tion control system (CPCS) boards (see Fig. 2) over thepredrilled holes in the area where the control relays wereremoved.

    4. Strip back1/2 in. the wires cut in Step 1. Crimp the 1/4-inquick-connects provided to the wires.

    5. Route the compressor power wires through the toroids asshown in Fig. 3, and connect toroids to terminals 23 and24 on the appropriate compressor protection boards.

    6. Reconnect the compressor power wires to the circuibreakers and connect the wires to the CPCS boards. SeeFig. 4 for equivalent CPCS connections to the former CR(control relay) connections. Be sure to connect the appro-priate toroid for the proper compressor.

    7. Restore power to the unit.

    ITEM DESCRIPTION QTY PART NO.

    1 CPCS Assembly 2 HN65KZ0272 Toroid 2 HT08DZ0253 Sheet Metal Screw; 4 AL56AU128

    4No. 6B-20 x 3/4-in. long1/4-in. Quick-Connect

    20 HY69DS057

    ELECTRIC SHOCK HAZARD

    To avoid the possibility of electrical shock,open all disconnects before installing orservicing this equipment.

    30GTN,GTR,GUN,GUR040-070Compressor Protection Control System

    (CPCS)50/60 Hz

    Fig. 2 Compressor Protection Control System (CPCS)

    CPCS-A1070 50HZ

    ONLY

    CPCS-B1070 50HZ

    ONLY

    CR-A1 CR-B1

    LEGEND

    Fig. 1 CPCS Installation

    CPCS Compressor Protection Control SystemCR Control Relay

  • 8/3/2019 30gtn-8si

    2/42

    LEGEND

    CB Circuit Breaker NC Normally ClosedCOM Common NO Normally OpenCPCS Compressor Protection SN Toroid

    Control System TB Terminal Block

    NOTE: Power wires from terminal block TB1 to circuit breakersCB-A1 and CB-B1 must be routed through the appropriate toroids.CPCS-A1 is for compressor no. A1; CPCS-B1 is for compressorno. B1.

    Fig. 3 Compressor Power Routing

  • 8/3/2019 30gtn-8si

    3/43

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    11

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    J9

    MAIN BASE

    BOARD

    PNK

    CPCS-A2

    VIO

    GRA

    RED

    S2 S1

    S2 S1

    CPCS-B1

    3 1

    S2 S1

    3 1

    CR-B1CPCS-A1

    CR-A1

    070 50HZONLY

    RED

    RED

    3 S1 S2

    R1 C

    23 24

    TOROID

    COM NC

    NO

    8

    9

    7

    C1 C2

    (FAULT CURRENT)

    STANDARD: 040-060 50HZ

    040-070 60HZ

    040-070 60HZ

    CR CPCS

    1

    STANDARD: 070 50HZACCESSORY: 040-060 50HZ

    LOGIC

    A1/B1

    CR

    040-070 60HZ

    LEGEND

    COM Common

    CPCS Compressor Protection Control SystemCR Control RelayNC Normally ClosedNO Normally Open

    CPCS CONTROL WIRING

    Fig. 4 Equivalent Connections Control Relay and Compressor Protection Board Module(Units without Current Sensing Board)

    CPCS CONTROL CONNECTIONS

    CPCS FEEDBACK CONNECTIONS

  • 8/3/2019 30gtn-8si

    4/4

    Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

    PC 903 Catalog No. 533-089 Printed in U.S.A. Form 30GTN-8SI Pg 4 704 4-99 Replaces: NewBook 2

    Tab 5c

    Copyright 1999 Carrier Corporation

    Units With Current Sensing Board

    NOTE: Units with starting serial number 0204F were pro-duced with factory-installed current sensing board.

    1. Cut off all quick-connect terminals from wires connectedto compressor control relays, being careful not to cut offwire markers.

    2. Remove and discard the 2 control relays (see Fig. 1).

    3. Using screws provided, position the 2 compressor protec-tion control system (CPCS) boards (see Fig. 2) over thepredrilled holes in the area where the control relays were

    removed.4. Strip back1/2-in. the wires cut in Step 1. Crimp the 1/4-in.

    quick-connects provided to the wires. Four extra quickconnects will remain.

    5. Route the compressor power wires through the toroids asshown in Fig. 3, and connect toroids to terminals 23 and24 on the appropriate compressor protection boards.

    6. Reconnect the compressor wires to the circuit breakersand connect wires to the CPCS boards. See Fig. 5 forequivalent connections to the former CR (control relay)connections. Be sure to connect the appropriate toroid forthe proper compressor. The feedback portion of theCPCS must not be connected to the main base board J9terminal strip because the current sensing board providesthe feedback.

    7. Restore power to the unit.

    TESTINGTo check the compressor protection boards for proper oper-

    ation, during Test mode check COMP, CCA1, and CCB1 asdescribed in the Controls and Troubleshooting Guide.

    R1 C

    23 24

    TOROID

    COM NC

    NO

    8

    9

    7

    C1 C2

    (FAULT CURRENT)

    STANDARD: 040-060 50HZ

    040-070 60HZ

    040-070 60HZ

    STANDARD: 070 50HZACCESSORY: 040-060 50HZ

    LOGIC

    A1/B1

    CR

    CR CPCS

    040-070 60HZ

    LEGEND

    COM CommonCPCS Compressor Protection Control SystemCR Control RelayNC Normally ClosedNO Normally Open

    CPCS CONTROL WIRING

    Fig. 5 Equivalent Connections Control Relay and Compressor Protection Board Module(Units with Current Sensing Board)

    CPCS CONTROL CONNECTIONS