37
Manual WS.500 v4 2Wire Energy Monitor 1 2WIRE WS.500 ENGLISH MANUAL 1. Overview 2. Bus structure 3. Startup 4. Network settings 5. Mail settings 6. Upgrading 7. Energy prices 8. Login password 9. Programming modules 10. Logic alarm via email 11. Layout 12. EPC level 13. Control 14. Graphs 15. Sub totals 16. Logging to ftp server 17. Data transfer via HTTP 18. Quick start 19. Troubleshooting

2WIRE WS.500 ENGLISH MANUAL WS500 has two bus systems on board: a 2wire bus according to the 2‐WIRE protocol, and a 3‐ or 4

Embed Size (px)

Citation preview

Manual WS.500 v4                  2‐Wire Energy Monitor  

1  

2‐WIRE WS.500 ENGLISH MANUAL  

1. Overview 2. Bus structure 3. Startup 4. Network settings 5. Mail settings 

6. Upgrading 7. Energy prices 8. Login ‐ password 9. Programming modules 

10. Logic alarm via email 

11. Layout 

12. EPC level 

13. Control 

14. Graphs 

15. Sub totals 

16. Logging to ftp server 

17. Data transfer via HTTP 

18. Quick start 

19. Troubleshooting 

  

Manual WS.500 v4                  2‐Wire Energy Monitor  

2  

1. OVERVIEW  

The 2‐WIRE Web WS.500 offers a lot of opportunities to make logging and visualization of data 

possible. What type of data, there may be all kinds: 

Measurement of electrical loads: voltage, current, power, reactive power, power factor, 

consumption. 

Thermostat values:  pre‐set (heating, cooling, ventilation), set point, room temperature, fan 

speed. 

Air sensor values: temperature, humidity, CO2, VOC. 

Counting impulses from energy meters such as gas, electricity and water meter. 

Measuring energy consumption on devices with fix power on a time basis. (Ex. water heater, 

heating oil burners, lights ...) 

Alerts to mailbox when crossing power consumption, temperature control 

 

On the web pages to view all log values of the modules in graphs, per hour, per day or per year, 

together with the costs of that year. 

 

Also subtotals are calculated, which can be imported into different formats. 

 

Features WS.500: 

DIN rail module (2 modules wide) 

Power supply: 15V / 1A 

Bus connection: 2‐WIRE (up to 500mA) and MODBUS (up to 32 modules.) 

Ethernet connectivity with integrated transformers 

Network processor 10 / 100Mbit / sec 

Real Time Clock with backup battery, daily put in sync with NTP server 

Flash Memory 8Mb 

4Gb SD card (backup configuration data and logs 3 years) 

Upgrading via FTP server 2‐WIRE 

64 log channels, each up to five readings (32bits) and 2 consumption values (import‐

export) 

Communication every minute to the connected modules for reading the measurements 

Logging every minute to SD of five measurements per channel, and every 5 mins 2 

consumption values 

Energy consumption cost calculation (estimate NOT FOR CLEARANCE !!) 

EPC level calculation (kWh / m2) 

Web HTML: 4 + 1 user administrator can simultaneously use the server. 

set login, password and language (NL‐FR‐EN‐DU) per user. 

IP address fix or dynamically via DHCP server 

Domain name instead of IP address via DNS server 

Full configuration of all modules, create groups for layout 

Manual WS.500 v4                  2‐Wire Energy Monitor  

3  

FTP client: Setting rhythm for logging data to remote FTP server separately adjustable for 

real‐time measurement (interval per minute to 60 minutes) and for consumption 

measurements (interval by 5min until 24h). The format is CSV delimited '|', but can also 

be the AMR format MMR (BE: EANDIS). Each file has a unique name and can be 

incorporated into your own remote database. 

HTTP request: Via an instruction request all readings and consumptions per channel from 

a selected time and a certain period of time (1 day to 31 days). The format is also JSON 

and can be split easily (ex. Excel). 

Online control or request statuses ex. relay outputs, thermostat can also be controlled 

via an HTTP request. 

2. BUS STRUCTURE  

The WS500 has two bus systems on board: a 2wire bus according to the 2‐WIRE protocol, and a 

3‐ or 4 wire bus according to the RS485 MODBUS standard  

PC.080: 2‐wire: BUSTERMINAL 1 (GND) and BUSTERMINAL 4 (VDD)  

EMM630 ‐ ACQ.CO2 – TFC.01: BUSTERMINAL 2(A) and BUSTERMINAL 3 (B) 

EMM120‐EMM220: BUSTERMINAL 1(GND), BUSTERMINAL 2(A) and BUSTERMINAL 3 (B)  

EC.441: BUSTERMINAL 1(GND), BUSTERMINAL 2(A), BUSTERMINAL 3(B) and 

BUSTERMINAL 4(VDD)   

Between the terminals A‐B there must be placed the provided resistors (120 ohms) at both ends of 

the bus!! Recommended is EIB bus cable (4 core) 

More information: please consult documentation modules! 

3. START UP  Connect the included power supply (15V) to the WS500 supply terminals at the top. (Polarity is not 

important) 

Connect the network cable at the bottom, the WS.500 must be connected to the Internet via switch 

or (wireless) router. 

Bus connection to the energy modules: EC.441 ‐ PC.080 ‐ EMMxxx etc. 

Turn on the power: at the top of the WS.500, all LEDs should light up. After a few seconds LED L2 

should turn off, followed by LED L3 and L4 LED. Afterwards led L3 will flash every 2 seconds(heart‐

beat) 

 

 

 

 

L1

S1 S2

L2 L3 L4

 

POWER 

15V 

Manual WS.500 v4                  2‐Wire Energy Monitor  

4  

 

 

Down where the network cable is plugged in, there should light a green LED, and frequently an 

orange LED. Then the network is OK. 

If EC.441 or PC.080 modules are connected, the power led of these modules should light up.  

4. NETWORK SETTINGS By default, the WS500 is configured to "DHCP" which means that at the first boot thee webserver 

gets automatically assigned an IP address by your router. To find out the address, there are programs 

that show the IP address. You can also download a server‐scanner on the 2‐WIRE website: 

ServerScanner: 

Start the program and press the green button 

so the data appears.  

(Sometimes there are more efforts needed) 

Now browse to the IP address by typing it in in the 

address field and add always the port number! 

The default setting is for the port is  "8080" For example, 

type thus: 192.168.0.220:8080 

Note the colon between address and port number! 

 

There should appear the following login screen. If this is not the case, check 

the connections again from the web server. 

Login with username and password: "adminIP' and password' 2015 ' 

With this login you can change any IP settings, but not change any password 

(this should be done with login 'admin2‐WIRE) 

 

Manual WS.500 v4                  2‐Wire Energy Monitor  

5  

 

HARD RESET to a fixed IP address When there are problems with DHCP (ex. your router has no IP address), and the Server Scanner still cannot find a Web server, despite a decent network connection, you can decide to go to a "default" fixed IP address: 

Procedure: Power off the WS500, wait 5 seconds, push button 2 and hold, turn on power, and continue to press until the LED starts to flash. Keep on pushing for another 3 seconds and then release. After about 5 seconds all LEDs are off and the WS500 is now at a fixed IP address. Now you need to "browse" to the default IP address: 192.168.0.123:8080 

Note: This address is not always reachable for the network where your PC or laptop is connected to. When you are in a different range, you need to change the network settings of your PC! Further explanations can be found in "TROUBLESHOOTING" 

 

Once logged in:  

Click on 'Configuration', then appear the following menus: 

 

 

 

 

 

 

 

 

 

Manual WS.500 v4                  2‐Wire Energy Monitor  

6  

Starting with 'SETTINGS'. We start with checking the network settings. This is as said standard DHCP. 

Do you want to fix the address, or assign a different address or port number, check out "DHCP" and 

fill in your address and port number. 

Example: 

192.168.0.123 and the port number 

8080.  

Note that if you change this address, 

you should write down exactly what is 

the new address and port number! 

After sending you have no longer 

communication and you have to start 

the browser with the new IP address 

and port number. 

  

 

Press ‘SEND CONFIG’ 

 

 

 

 

After a second confirmation ( in RED) you have to enter in the toolbar of your browser the new 

address and port number. If you have communication, the new setting is successful. 

  

Now we have to browse to 192.168.0.123:8080 and then the address successfully setting. 

 

DHCP: automatically assign an IP address via a DHCP server " 

Check the 'DHCP' and press' SEND CONFIG. 

 

Manual WS.500 v4                  2‐Wire Energy Monitor  

7  

After a short time, a new IP address is assigned to your Web server. (In this example 192.168.0.164: 

8080)

 

Make a note of this new address and press the button to confirm.

 

As from now there is no communication on your old IP address. Type in the toolbar, the newly 

assigned address to recover connection. 

Go back to "SETUP" ‐> "SETTINGS" 

There has to be Internet available on your web server, otherwise there are no visible graphics, and 

you cannot send logs to a remote FTP server. 

"GATEWAY": Normally this is the first 3 digits of your IP address, and the last number '1'. (Ex, your IP 

address is 192.168.0.123, then the GATEWAY 192.168.0.1) 

If you do not fill in this properly, there is no internet possible on your web server. 

 

'SUBNET MASK': default is set to 255.255.255.0 

This should only be changed if the Web server is connected to an extensive (sometimes industrial) 

network. These settings you will then get notified by your IT technicians. 

"DNS SERVER": automatically filled in when you checked on ‘DHCP’. This usually works when you 

type in the same IP address as your gateway. (Eg 192.168.0.1) 

LOGS TO FTP‐SERVER: It is also possible that you want to send the log data to a remote FTP server. For this we have to work 

with an IP address, either with a 'domain'. The port number is always "21" (eg 78.22.222.111:21)) 

 

 

 

 

 

Manual WS.500 v4                  2‐Wire Energy Monitor  

8  

 

IP FTP logserver: Enter the IP address of your FTP log server (port 21 fix) 

Do you own a domain name, check the box on ‘IP FTP‐LogServer’  

Domain Name: enter the domain name (ex. ‘www.mydomain.com’) 

 

In "SEND FTP CONFIG", if entered a valid domain name, the found IP address will be filled in 

automatically (eg 195.130.132.100:21) 

Login Name – Pass – Dir Name: In the FTP server, we need (for security reasons) also set a user 

password, and optionally a directory where the data is stored. 

Multiple web servers can indeed log their data to a single FTP server and then it is desirable that each 

logger is assigned a folder for their data. 

Of course, the chosen login name, password, and the folder name must also be the same as in the 

FTP server. If the FTP server is assigned a folder for each user, the "Dir Name" should remain blank. 

 

The length of the login is up to 32 characters (contiguous without special characters!) 

The length of the password up to 22 characters, and the directory maximum 32 characters  

 

RT log : RT stands for Realtime. This is only data from connected modules and shows the actual  

recorded values. In function of the type of module: electrical measurements (voltage‐current‐

power‐reactive power ‐ PF), temperature, CO2, humidity, pulse counters ... 

Interval adjustable between 1‐15minuten or 'NO'. 

Manual WS.500 v4                  2‐Wire Energy Monitor  

9  

RT Daylog interval: Once per day, the webserver can send at a chosen time, the complete data 

from the previous day, with an interval that can be chosen between 1 and 60minutes. 

Send Daylog: time of day to transmit all RT‐logs. 

 

 

ConsumptionLog: direct forwarding consume to the FTP server at a specified interval. 

Day Log Interval: One can also send daily at a chosen time the complete data from the previous 

day, with an interval that can be selected between 5 minutes and 24 hours. 

Send Daylog: time of day to transmit all consumption logs. 

Location Name: All logs are named "Location Name" and get a date stamp. The same “location 

name” will also be send with the mails from 'Alerts'. See later 

 

5. MAIL SETTINGS "Alerts for exceeding limits on consumption and temperatures should be set up in the configuration 

of the modules . If you have an account with a provider, you can fill in the outgoing mail server 

address (eg. Uit.telenet.be) and your email address (sender address). 

The alerts can be sent to up to two addresses. (Mail Address1 and 2) 

 

6. UPGRADING:  The next compartment is used for upgrading the server and the 2‐WIRE modules. The condition for 

this function is of course that the webserver is  connected to the Internet. 

At 2‐WIRE we have a server where are the necessary upgrade files can be downloaded from. To 

check whether upgrading is needed, one can press the button "FIRMWARE VERSIONS" 

When the connection with the 2‐WIRE Upgrade Server succeeds, you can see the different firmware 

versions available. (Sometimes a second attempt be possible if the server 'occupied'.) 

Manual WS.500 v4                  2‐Wire Energy Monitor  

10  

 

 

 

 

 

 

 

 

"UPG VERSION” means the versions on the 2‐WIRE Upgrade Server. 

'INSTALLED VERSION " is the firmware on board the modules in your system. 

When UPG version has a higher number than the Installed Version, is to upgrade the 

components. 

'STYLE SCRIPT " includes the CSS style (= look of the web page), and JavaScript, which is 

used to display all the' buttons' function and add the necessary logic.  

Upgrading the server deserves more attention! During upload, we see a progress'balk. This is done in 

three phases: the first phase is upload the script, the second step is to upload the firmware for the 

server, the third phase is to install this firmware. When the progress bar is finished, automatically the 

webpage is refreshed and you need to log in again. 

 

 

 

 

 

 

 

 

 

 

 

 

When your 2‐WIRE system has modules such as PC.080 or EC.441 there may be an upgrade needed: 

If the UPGversion exceeds the Installed Version, you must press the "DOWNLOAD" button. After 

some time, there will be green checkmarks beside the available module versions. 

(A red cross does not mean available (v255.255.255.255), or failed transfer) 

Manual WS.500 v4                  2‐Wire Energy Monitor  

11  

The modules are thus not upgraded yet! This should be done in menu 'Modules' ‘MODULES’  

 

At the bottom there are 4 buttons: These serve as a backup of your configuration and logs to SD: 

SAVE CONFIG: save configuration to SD (this happens automatically every night at 3 am) 

SAVE LOGS: Keep all energy logs to SD (happens automatically every night at 3 am) 

LOAD CONFIG: This button can be used if you want to reset the configuration to the last, 

last saved copy. (For example, you delete a module, or channels incorrectly filled in). 

Keep in mind that if you made a backup yet, this is dated the same day, at 3am! 

With this we do not need to re‐enter all data. The password = 'admin2‐WIRE. 

Note: The setting of IP address, login and passwords are NOT stored on the SD! 

LOAD LOGS: USE ONLY at replacement of the server, same as above! 

(The energy logs are thus put back to the last backup (at night at 3am)  

 

 

Manual WS.500 v4                  2‐Wire Energy Monitor  

12  

7. ENERGY PRICES As already mentioned, we can (approximate) calculate the daily energy consumption and there is a 

price tag attached to them. When we know what the cost is for gas, water electricity, we can 

complete this table below. There are two pricelevels for electricity (day ‐ and night consumption). 

Everything must be filled in cents, so DO NOT DECIMAL!! 

 

 

 

 

 

 

"SEND" because the values are entered. 

NB. Tariff changes you can always change, every day is calculated what your consumption costs was 

the inspired fare, and so is stored in the database. Enter your other values in afterwards, this will 

have no effect on the previous calculations. 

8. LOGIN 

The last section in the SETTINGS tops, and is certainly not unimportant: 

login ‐ password 

LOGIN: The WS.500 can simultaneously work with 4 users. Each user can choose a login name (up to 16 characters), a password (always four digits) and a language version. 

 Only logged in as administrator, with password "admin 2‐WIRE ' , you can make changes here! 

 

 

 

 

 

When we start up the first time we see:  "USERS": 0 

The administrator is not counted in the 4 users, the administrator usually serves only to modify the 

configuration so that other users can not make changes. (So do not sprinkle around the admin login 

name and password ...) The login name admin2‐WIRE " or ’adminIP’ can never be changed, but you 

can change the password (2015). 

Manual WS.500 v4                  2‐Wire Energy Monitor  

13  

Change password of the administrator:  

Type in the filed "LOGIN OLD 'and' PASS OLD ' the current login name (admin2‐WIRE) and password. 

Type in "LOGIN NEW 'back' admin2‐WIRE" and "PASS NEW 'your new password (4 digits) 

 

Press 'SENDPASS' to send the new data. 

 

The same applies to newly created users:  

Enter to “LOGIN OLD”  'loginold' and “PASS OLD”  1234 

At “LOGIN NEW” now the user name (up to 16 characters) and “PASS NEW” password (4 digits) 

The 'TIMEOUT' serves to set the expiry time of your login. When there are actions with the web 

server this time is restarted every time. If there are no further actions, and the expiration time has 

passed, it should be re‐signed. 

Adjustable between 1 and 255u. 0 means 30 days’ expiry time. 

The language version is a user adjustable and serves for the fixed texts on your web server. 

Not all texts have been translated. Some are difficult to translate and are usually displayed in English. 

Press 'SENDPASS' to confirm. 

When sending the login we always return to the boot menu. We now need to login again to confirm 

who you are. 

Example: 

 

 

Manual WS.500 v4                  2‐Wire Energy Monitor  

14  

To remove a user is doing it the other way: 

 

At “LOGIN OLD” comes his username, his password at “OLD PASS”. 

At “LOGIN NEW” coming now 'loginold' and “PASS NEW “1234 

Press 'SENDPASS' to confirm. 

 

NB. From v6.3 can also retrieve the login and password on the next field "USERS" to enter a number 

between 1 (user1) and 5 (admin). The data from each user are displayed. 

9. MODULE PARAMETERS 

Choose the menu 'Modules' Left we see a number of text boxes, and a few notes: 

'NEW': entering new Serial 

'CHANGE': change the module name (not channel name!) or serial number 

'DELETE': Delete selected module 

"CANCEL": undo changes if it had not been sent. 

'SEND': Forward module to Web server 

"DOWNLOAD": back load the previous configuration of the selected 

module, provided that the changes had not yet been sent. 

"UPGRADE": only active if modules are with 2‐WIRE protocol 

To start, we must first complete a "serial number" at the place where we see "Serial No.". The serial number always consists of two figures, one uppercase letter, and returned five digits. These have a meaning: 

A = Air quality meter = AQM.CO2 

C = Counter module PC.080 

D = Dimmer Module (not yet available) 

E = Energy meter = EMM.120 ... 630 series 

T = Temperature  = TFC.01 

M = Modbus energy counter EC.441  

P = expansie (dummy)module voor EC.441 slimme meter Poort  

Serial numbers: 

These modules have a fixed serial number assigned by 2‐WIRE and this number 

is printed on the module: PC.080, EC.441. 

Other modules such EMM.120 ... 630 do not have SerialNr but only a Modbus addresses (range 1‐

247). Still there can only be worked with SerialNrs in programming. 

Manual WS.500 v4                  2‐Wire Energy Monitor  

15  

Therefore, we will create fictive serial numbers. Most modules require only one channel, except for 

the more complex modules such as EMM.630, it has 3 channels required (= 3 phases) 

Each serial number: 

The first two digits of the serial number will be: 

'01' for single phase meters, thermometers, CO2 

'03' for three‐phase meters 

The meaning of the letter‐character has already been discussed. 

The next five digits dialing yourself, but make sure that the serial number "unique" continues! 

Examples of the series EMMxxx energy Modbus meters: 

Single‐phase (import only): EMM120 ‐ EMM220: 01E00001 ... .01E99999 

Single‐phase (import + export): EMM220: 02E00001 … 02E99999 

Three‐phase: EMM630 ‐ EMM630CT: 03E00001 ... 03E99999 

Thermostat TFC.01: 01T00001 ... 01T99999 

AirQuality AQM.CO2: 01A00001 ... .01A99999 

The limit on the number of log channels is 64, and the limit of the number of modules is 32. 

The first serial number we will enter in the “SerialNr” field. In the field “Module Name "you can enter 

a name that refers to the module. (Eg distribution thermostat garage ...) If we press 'NEW' will be 

placed typed the serial number in the "list box”. 

On the right you will see a module with a number of channels in our serial 

 (Eg. 01A00001 = 1 Chanel. ) 

 

MODE: (meter, thermostat, air conditioning ....) Is selected automatically 

UNIT: is automatically filled with "kWh ° C ppm ..." 

CH: stands for "CHANNEL" (channel), and is also automatically generated by the Web 

server. Channel no, later it will serve to make the link between log channel and 

(Modbus) address. (see further). 

Manual WS.500 v4                  2‐Wire Energy Monitor  

16  

ADDR: Each channel must have a unique address in the range 1‐247. So no channel 

can have the same address. Start from number 1 and so on, so that each 

measurement input has a unique address. The simplest is to 'ADDR' to complete the 

same value as the channel number 'CH'. When we have no serial modules (series 

EMMxxxx) we have to program these addresses on these modules via the existing 

display on the EMM module itself. (How to change the address on the MODBUS 

module is described in the manual of the module itself.) 

SUBADD: for PC080 modules and EC441: see manual of these modules. 

For the EMMxxxx series: 

Serial 01Exxxx: sub add = 0 

Serial 02Exxxx: both channels SAME ADDRESS, sub add 0‐1 

Serial 03Exxxx: all three channels SAME ADDRESS, sub add = 0, ‐ 1 – 2 

PARA3: PARA6: specifically explained in the manual of the module EC441 or PC080. 

For EMMxxx should be completed nothing. 

Log type: This is for those who want to send the log data to a remote FTP server (see 

Section 9).. You can check which log types you want. 

NB. The log types are dependent on the type of module, and will always be logged to SD every 

minute, even if nothing is checked! 

An overview on ‘MODE’  ‘LOGTYPE‘ and  ‘UNIT’: 

TYPE  MODULE  MEANING  MODE  LOGTYPE  UNIT 

A   AQM.CO2  CO2 measure  AirQ  roomtp  °C 

     RH  % 

     CO2  ppm 

            VOC  0‐3 

E  EMM.120/220  electr.power  Teller  Voltage  V 

     Current  mA 

     Power  W/Var 

     power factor  ‐‐ 

     Consumption import  kWh+ 

            Consumption export  kWh‐ 

C‐M  EC.441  Counter module  Teller  Voltage  V 

     Current  mA 

   PC.080    Power  W 

            Consumption  kWh 

T  TFC.01  thermostat  Temp  roomtp  °C 

     setpoint  °C 

     regime  0‐2 

            fan speed  0‐3 

    

We assume that the EMM modules are on the display assigned a unique MODBUS address. Note 

down these addresses and the group or circuit with which this module is connected. Give it a name 

(eg lighting above, sockets living room, stove, etc ..) 

Manual WS.500 v4                  2‐Wire Energy Monitor  

17  

If the Modbus module is connected to the RS485 bus, and there is power to the module, you can 

press 'SEND'. In "Module OK" you know that communication, the address and the power supply is in 

order. If not, check power, address and bus connection (A and B do not confuse?) 

(The address can be checked on the module via the display on the EMM120‐220‐630, see instructions 

for the module) 

Note: You can enter or modify only one module at a time. Do you want to continue with new 

modules, you must first press "SEND" button when it was changed to red light. 

If you want to change an existing module, do not type in the SerialNr but select it from the "list box. 

A change, if not yet sent can also be cancelled (“CANCEL”) or return to the previous setting by 

pressing the "

 

 

DOWNLOAD". 

When all modules have been introduced and the communication was fine, a brief explanation in case 

changes should be made. 

A module that you want to change can be done by selecting the serial number in the 'list box: 

THEREFORE, DO NOT retype the serial number! 

Now you can only make changes in this module. (The other modules are 'locked' to prevent that you 

can change anything in the wrong module.) 

After changing a text or number, you should always confirm with 'ENTER': Click any other cell, so you 

stand outside the cell in which you have made changes. Now, again the "SEND" button will light red. 

If any changes are made, click "SEND". 

 If you forget to give a name to the module, which serves as a 'helping hand', select this serial 

number in the 'list box and press' CHANGE'. 

Manual WS.500 v4                  2‐Wire Energy Monitor  

18  

The text on the button will change to "CONFIRM." 

In the box where 'Module Name' is stated, you can 

now put in your text. (Vb 'EMM630') 

 

Now press 'Confirm' and you get this name (later) 

in addition to the serial number of the module. 

Note. The name will be visible only if you leave and 

return from the 'Modules' menu. 

It is better to give in a module name directly at the 

creation of the SerialNrs. 

 

 

CHANGE SERIAL NUMBER  

If you have an existing module which you like to replace by the same type (eg EC441, SN 08M00001) 

and you want to keep the existing logs, you can change the serial number on the condition that the 

first three digits are the same. (Eg new module has serial 08M00015) 

Select the serial number from the old module in the 

'list box and press' CHANGE'. The text on the button 

will change to "CONFIRM." In the box where the old 

"Serial No." state, you can now change the last 5 

digits to the new serial no. 

Press 'CONFIRM'. A second screen appears for 

confirmation again. then press 'SEND'. 

If the module is connected correctly, the answer is 

"Module OK" will be. In case the module is not yet 

connected the answer will be 'Module NOK. 

 

NB. If you still want to start with new logs, and delete all previous logs of this module, you must first 

delete the old module (DELETE), and then completely recreate the new module. 

10. ALERTS The web server WS500 has a function ALERTS. These are warning messages that are out as an email 

when a consumer has exceeded a certain condition. We must clearly state that this function does not 

replace an official alarm system!!! 

What are the possibilities:  

Indication of the status of an input connected to a window‐door contact, motion sensor, 

current or voltage sensor. 

Warning when power exceeds a limit. 

Manual WS.500 v4                  2‐Wire Energy Monitor  

19  

 Warning when the daily consumption exceeds a limit. 

Monitoring temperatures if upper or lower limit is reached. 

 

The WS500 can be filled up with to 2 email addresses, which receive these messages. 

For the programming the PC.080 we have to complete a number of parameters according to the 

mode. 

At the parameter‐field 'ALERT' (= ALARM) we determine the logic that is to be followed: 

The maximum number of characters is 5, the first character contains the logic, and the other 

characters must be digits from 0 up to 9999. Exceptions are temperatures with lower and upper limit 

where we will place a letter between two values (see below) 

In function of the chosen MODE we use letters that determine the "logic":  

Input contacts:  A followed by an on‐delay 0‐9999 sec 

Power limit:   p (power) for capacity up to 9999 W 

Power limit:   P for larger capacity up to 9999 kW 

daily consumption limit:   c (consumption) for consumption up to 9999 Wh 

daily consumption limit:   C for large consumption up to 9999 kWh 

Temperature:   see below in Table temperatures 

The possibilities per Type explained in a table below: 

1. STATUS TRACKING: The alert function is activated by the letter 'A' for input contacts. 

FUNCTION:  MODE  PARA3  ALERT  PARA6 

Track status of the connected input 

Alway’s bi‐stable 

Type contact:  

Delay ON  

Delay OFF  

Pushbutton with  ‘toggle’ function (PB)  

Bi‐stable  0   Ex. A10 (10 sec delay) 

Ex. 120 (120 sec delay) 

Contact normal open (NO) 

Bi‐stable  1   Ex. A0  (no delay) 

VEx. 5 (5 sec delay) 

Contact normal closed (NC) 

Bi‐stable  2  Ex. A500 (500 sec delay) 

Ex. 0 (no delay) 

 

Example email with warning: 

 

 

 

2. POWER LIMIT: The alert function is activated by entering the letter "p" or "P" (power) in the 

alert field. 

Manual WS.500 v4                  2‐Wire Energy Monitor  

20  

When the power of the connected meters exceeds longer than one hour the limit, an email is sent 

with the data set limit and measured value. 

At midnight, the measurement is restarted for a new evaluation. 

FUNCTION:  MODE  ALERT 

Warning high power  Always counter 

Power Limit (W of kW) 

Power up to max 9999 W (Resolution 1 W) 

Counter  Ex. p1000 (Border 1000 W) 

Power up to max 9999 kW  (Resolution 1 kW) 

Counter   Ex. P10  (Border 10 kW) 

Example of a received mail: 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3. DAILY CONSUMPTION LIMIT: the alert function is activated by the letter "c" or "C" 

(consumption). If the daily consumption of connected meters goes above this limit during the 

day, an email is sent with the data set limit and measured value. 

At midnight, the measurement is restarted. This results in maximum 1 message per day.  

FUNCTION:  MODE  ALERT 

Warning 1 day consumption  Counter  Consumption limit(max 9999 Wh) 

Consumption up to max 9999 Wh (resolution 1 Wh) 

Counter  Ex. c1500 (limit 1500 Wh) 

Consumption up to max 9999 kWh  (resolution 1 kWh) 

Counter   Vb. C30  (limit 30 kWh) 

 

Manual WS.500 v4                  2‐Wire Energy Monitor  

21  

Example warning day consumption goes above a limit of 15 kWh: 

 

 

 

 

 

 

 4. TEMPERATURE LIMIT: 

Temperatures can be very important, and in some applications you want to follow this closely. 

Examples fridge‐freezer monitoring, risk of frost, over‐temperature boiler ... 

Therefore, it is also here to introduce a (limited) logic for measuring values of ‐15 ° C to + 85 ° C 

Note. All limits can only be full integers, so half a degree is not possible! 

There is a fixed delay of 30 minutes before an alert is possible. 

If there has been an alert, we can set the waiting time before there will be a new alert possible. In 

'PARA6' will be placed this time. The waiting period must be at least 30 minutes, and can go up to 

1440 minutes (= 24 hours). 0 means only 1x per day alert. 

The options are: 

Alert when the temperature drops below the set value 

Alert when the temperature is HIGHER than the set value 

Alert when the temperature falls below the minimum limit OR HIGHER than the maximum 

limit. 

Keep in mind that negative temperatures are possible, and ‐15 ° C lower than ‐5 ° C ... 

Lowercase letters mean BELOW, uppercase means EXCEED 

When a sensor is 'linked' to a different sensor (see page 4), a distinction needs to be made which 

sensor we mean, because you cannot set an alert function on the input of the connected sensor 

(slave).  

Where we have '255' filled in 'ADDR' there cannot be made an alert function. Therefore, we use two 

types: "T" (t) is the main sensor and the associated sensor is 'O' (o) (outdoor). 

The following table makes it more clear: 

FUNCTION:  MODE  ALERT 

Temperature control  Thermo  t or T = sensor1 (master)  o or O = sensor2 (slave) 

Temperature LOWER than limit SENSOR 1 (master) 

Thermo  Ex. t‐5 (temp LOWER than ‐5°C) Ex. t23 (temp LOWER than +23°C)  

Manual WS.500 v4                  2‐Wire Energy Monitor  

22  

Temperature LOWER than limit SENSOR 2 (slave) 

Thermo  Ex. o‐10 (temp LOWER than ‐10°C) Ex. o23 (temp LOWER than +23°C)  

Temperature HIGHER than limit SENSOR 1 (master) 

Thermo  Ex. T‐5 (temp HIGHER than ‐5°C) Ex. T23 (temp HIGHER than +23°C)  

Temperature HIGHER than limit SENSOR 2 (slave) 

Thermo  Ex. O‐10 (temp HIGHER than ‐10°C) Ex. O23 (temp HIGHER than +23°C)  

Now there is a third possibility: compare BELOW OR ABOVE 

Now we have to set in 2 limits, and it must also be possible to set in both negative and positive 

temperatures. Only a maximum of five characters are possible. Therefore, we are going to put the 

type BETWEEN the two values. The minus sign is NOT used, but is represented by a letter. Please 

note: the first value is always the limit for LESS THAN, and the 2nd is the limit for EXCEED. This means 

that the first value must always be smaller than the 2nd value! 

We therefore only three combinations: 

limit negative 1st, 2nd negative (n or N) 

1st limit negative, 2 positive (m or M) 

1st limit positive, 2nd positive (p or P) 

 

The combination of the 1st and the 2nd positive limit value can never, because then the first value 

would be greater than the 2nd negative, and this is not possible. 

Following letters are used for these three possibilities, both for sensor1 and sensor2: 

FUNCTION:  MODE  ALERT 

Temperature control With lower – and upper limit 

Thermo  Capital letters  = sensor1 (master)  Minor letters = sensor2 (slave) 

Limit1 negative  Limit2 negative SENSOR 1 (master) 

Thermo  Ex. 10N2 (temp LOWER than ‐10°C OR temp HIGHER than ‐2°C)  

Limit1 negative  Limit2 positive SENSOR 1 (master) 

Thermo  Ex. 10M25 (temp LOWER than ‐10°C OR temp HIGHER than +25°C)  

Limit1 positive  Limit2 positive SENSOR 1 (master) 

Thermo  Ex. 10P25 (temp LOWER than +10°C OR temp HIGHER than +25°C)  

The same can be done if we have an associated sensor (sensor2) 

All letters must now be used lowercase. 

FUNCTION:  MODE  ALERT 

Limit1 negative  Limit2 negative SENSOR 2 (slave) 

Thermo  Ex. 10n2 (temp LOWER than ‐10°C OR temp HIGHER than ‐2°C)  

Limit1 negative  Limit2 positive SENSOR 2 (slave) 

Thermo  Ex. 10m25 (temp LOWER than ‐10°C OR temp HIGHER than +25°C)  

Manual WS.500 v4                  2‐Wire Energy Monitor  

23  

Limit1 positive  Limit2 positive SENSOR 2 (slave) 

Thermo  Ex. 10p25 (temp LOWER than +10°C OR temp HIGHER than +25°C)  

An example of the warning: 

 

 

 

 

 

 

A few more tips to make good use of these 'alerts': 

To set up the limits of power monitoring or day consumption, you can look in the respective charts 

during the week, and take the peak values.  

Also look to the average on a weekly or monthly graph, and make your own conclusion: could I 

achieve the same comfort with less energy? In what period are these tops in consumption? Too 

many "sleep power" by devices in standby mode? Perhaps now you can see who is responsible for 

the big waste. A little warning by your email alert tells you that there is (excessive?) too much 

consumption, according to your configurations. Do you get constant alerts, adjust the limits, because 

it may not start to work disturbing. 

Good luck with this 'ALERTS'. This could be the start of your first 'savings' ...  

11.LAYOUT  Go to the menu CHANNELS. We now see the channel names in the same rank as those we have 

created in our modules, but maybe this is not the order you like you see in the dashboard. It is also 

interesting to 'group' the consumers. 

 

Left there is a text field 'Group Name'. Furthermore, there are a number of buttons with the 

following functions:  

'NEW': Naming a group eg heating, lighting, ventilation, automatic head ... 

"CHANGE": edit a group name 

Manual WS.500 v4                  2‐Wire Energy Monitor  

24  

'Delete': Remove group 

"SORT" Order To determine the channels for the visualization 

'DESCRIPTION': divide the channels into groups 

"CANCEL": failure to implement the change 

"SEND": forwarding groups to the web server 

"DOWNLOAD": return showing previous configuration, provided that the changes were not 

sent!  

 

We must always begin with the completion of group names: Go to the field where "Group Name" is 

stated and then enter a new group name in there. Press 'NEW' 

The name will now appear in the "list box, press 'SEND' will turn red to 

indicate that a change is happening, but we also get alert with the 

message" RESET GROUPS? ", Press" Cancel " 

So we will continue until all the groups have been given a name (max 8). 

 

 

 

 

 

 

 

 

 

Now we can sort the channels if the order is not desired, press 'SORT'  

Click on the channel text field that you want to move. This name is now coloured red. Then click on 

the number field where you want the clicked channel to go to. The desired channel will now appear 

in place and it is coloured yellow. 

These two steps we repeat until all names in the desired order. 

Manual WS.500 v4                  2‐Wire Energy Monitor  

25  

Here is an example:

 

Now we have to divide the channels in the categories: 

Press 'DESCRIPTION' and confirm the question "RESET GROUPS" ‐> OK 

Now click on each time to the last channel of each group. 

Each group is now coloured .... made mistake? No problem, you can always re‐order or delete / or 

add new groups. 

When everything is in order, then click "SEND". 

example: 

 

Manual WS.500 v4                  2‐Wire Energy Monitor  

26  

12. MAIN CHANNELS AND ENERGY VALUE EPC Below the channels there are some specific channels that we can use for the overview of electricity 

and heating consumption, water consumption and calculate the EPC level.  

example: 

 

 

 

 

 

 

 

 

 

 

 

 

When you have an overall measure of your electricity consumption (can also be a 'smart meters' 

value), then enter the log‐channel number at the ELECTRA Ph1 field. This channel number will be 

found in the table above (LOG_xx ). Do you have a three‐phase system, then you must enter the 3 

channel numbers. 

Ex. LOG_8 ‐ 9 and 10, the total measurements of phase 1‐phase 2 and stage 3 

For the heating this can be gas or petroleum or electricity. If you measure these consumers on the 

Web server, then also enter these channels. (The gas meter can also be linked via the smart meter 

through the serial P1 connection at the EC.441)  

Is there a pulse contact provided for the water meter (via EC.441 or PC.080), please fill out this 

channel also. 

And if you have solar panels and an energy meter (EMMxxx) connected to it, you can enter up to 

three channels (for three‐phase meters) 

Finally, we make an (approximate) calculation of the EPC level (energy efficiency value of the 

building): This is a value in kWh / m2, which is in function of heat consumption and the area of the 

house. The lower the number, the better your home is insulated. 

The total consumption of heating is divided by the heated surfaces in the home. The unit is KWh / 

m2. At the installation time we do not have logging values for the whole year the webserver then 

makes an estimation of the missing time periods as a function of the heating period has already been 

measured. 

Manual WS.500 v4                  2‐Wire Energy Monitor  

27  

If you have an additional heating system such as a stove, or when your regular use additional electric 

heating loads, you need to "EXTRA HEATING 'Enter the estimated annual energy consumption: Ex. 

Wood produce about  4 kWh / kg 

Do you have a temperature sensor connected via the module EC441 or 

PC080, and you want to display this temperature on the login screen, you 

can enter this channel at 'OUTDOOR_TP' 

 

13. BEDIENING Go to 'EXIT'. The page will reload and you can see the following: 

On the left are the group names, and 

some menus for visualization of the 

logs. On the right we see the 

channels in the order as we have 

ordered them. 

Clicking on a group on the left, closes 

any other open groups and opens 

the requested group. 

Clicking on a group on the right 

opens or closes the group.  

When there are active and 

connected loads, every minute a 

measurement is taken. 

However, the page will be as you 

see them now, the new measured 

values shall not show. 

Do you want to keep them 

constantly in mind, you can click 

‘refresh the page’ in your browser. Or press ‘AUTO REFRESH ', and every minute you will now see the 

newly measured values. 

Each channel now shows the main value’s: consumption, daily consumption, annual consumption. 

(Or temperature...CO2 ...) 

Note. When a 'graph' is displayed, there is no 'refresh' possible that channel! 

The thermostat TFC01 you can do all the settings on your dashboard: 

There are three "regimes": "HEAT = heating, 'CLIMATE' = cooling (if there is one), and 'fan' = 

ventilate. When the heating system is working with fans, there are three speeds that can be selected, 

or "AUTO" = automatic speed adjustment recorded against the temperature difference.  

Manual WS.500 v4                  2‐Wire Energy Monitor  

28  

 

 

 

 

At the right is the "set points to its left the" room temperature. " By pressing one of them (room 

temperature) you can increase or decrease the set point by half a degree. 

Below these temperatures, a red beam (= heat) or a blue beam (= air conditioning on) appears to 

indicate present status. 

 ODERAT           

 

In the AQM.CO2 module we see the room temperature, humidity, CO2 content, and an indication of the air quality (VOC): VERY GOOD ‐ GOOD ‐ MODERATE – POOR 

14. GRAPHS  CONTROL: Clicking on the name of a consumer in chart shows the daily consumption of that 

consumer. To 'hover' over the chart we see a tooltip with the measurements in time. 

 

Manual WS.500 v4                  2‐Wire Energy Monitor  

29  

 By clicking again on the name the month graph will be displayed 

On the right there are two arrows <<< || >>> With these we can go back up to 7 days at the daily 

schedule, or up to 12 months at the monthly statement. Click once more closes the chart. 

Note. Opening a graphs for the first time may take several seconds (according to the speed of your 

browser and laptop / tablet). The next time this will go considerably faster because the graphics are 

buffered. 

Clicking 'DAY' shows all channels simultaneously see their readings per hour. 

Manual WS.500 v4                  2‐Wire Energy Monitor  

30  

 

Clicking 'MONTH' shows all channels simultaneously see with readings per day. 

If you have connected temperature sensors, you can see in this chart the minimum and maximum 

temperature of the day. 

Clicking 'YEAR' shows all channels simultaneously with their readings per month. Just above the top 

of the chart shows the consumption and estimated cost per month and the year totals.

 

Manual WS.500 v4                  2‐Wire Energy Monitor  

31  

Click on ‘OVERVIEW' shows in a table an overview of electricity consumption, heating consumption 

(gas or oil), water and possibly yield of solar panels. An EPC (energy level) levels approximate 

calculation is computed if the parameters are entered as explained in Chapter 11 (LAYOUT) 

The "TOP 10 CONSUMERS 'gives an overview (in euros) of the most expensive energy consumers. 

Below is a table reading a monthly consumption and projected energy costs. For comparison, you can 

see the consumption of last year (if your system has been in service for over a year) The outputs are 

sorted according to the largest costs.

 

Manual WS.500 v4                  2‐Wire Energy Monitor  

32  

When you have filled in a canal at 'total electricity (see Chapter 12), then there's now see an extra channel:' VARIA ', this is the difference between the total measurement, and these measurements. 

15. EXPORTING SUBTOTALS 

It can be useful if you want to calculate consume over a given period, and there is even an (approximate) cost calculation. 

To do this click on the menu on the left to "SUBTOTALS”. The following image now emerges. 

 

 

 

Click the field next to "START DATE" and you will now see a calendar. Select the start date for the 

period. Right on this calendar you can select the starting hour (per quarter).  

 

Do the same for the end date (END DATE) 

(Standard it is set to the current time) 

Then click on the button "CALCULATE". 

 

 

The screen will now show all the subtotals of the log channels. (Log channels CO2 or temperature are 

not included in this table, only "consumers") 

The waiting time for the calculation can vary in function of the period and the number of channels. 

(Eg. Period 9 months, with 20 channels can last about 8 seconds) 

An example:

 

Manual WS.500 v4                  2‐Wire Energy Monitor  

33  

The table name first, then the consumption of the starting time (START VALUE), the consumption of 

the end time (EndValue), the difference between the two (DIFF), the unit (UNITS) and the 

(approximate) cost (COST) . This price was calculated according to the values entered in the 

"SETTINGS". 

In the 'Search' you can type part of a name and then these names are only shown which occur in the 

keyword. 

On top of the table, there are now several "buttons": this we can export the displayed table with the 

filename = 'Subtotals ENERGY jaar_maand‐day‐hour‐minute, "and the extension:EXCEL: ‘.xlsx’ 

JSON: ‘.json’  

CSV: ‘.csv’ 

PDF: ‘.pdf’ 

With the button “PRINT”‐ we can directly print out this table. 

NB. Exports choices 'EXCEL' 'json' are not supported on many tablets (especially IPAD) 

(Full support under Microsoft Windows) 

16. LOGGING TOWARDS FTP‐SERVER Do you have your own FTP server? Or do you have one available through your service provider? Then 

you can get more out of the 2‐WIRE Web server! 

LOGGING: 

LOG TYPES: The logs are in CSV format and separator is a “;”. The decimal separator is a “,”. There 

are four types of logs available: 

RT log: Real Time logs of measured values: voltage, current, power W (), power (VA), Power 

Factor (PF), m3, m3 of gas, litres of fuel, temperature, CO2, ... 

The interval can be set from 1 minute to 15 minutes. (NO is inactive) When active, the values 

of all log‐modules are redirected to the log server following the interval. 

You can specify which measurements are to be logged in the setting of each individual log‐

channel by a checkbox! (This occurs in the configuration of the modules) 

 

File Name: LOCATION NAME + Log type + DATE + TIME + .csv 

      (Ex. Nieuwstraat18Aalst_RTLOG28082015_013003.csv) 

 

RT Daylog (AMR): the webserver can also send all collected Real‐Time day‐logs once per 

day. The interval of the measurements can be set here, from 1 minute to 60 minutes. In CSV 

format we see all log channels with their associated measurements (as indicated in the 

RTlog‐checkbox) 

The CSV file has been prepared using the "AMR" format (see EANDIS) 

Note: A file containing 32 log‐channels, each measuring about 5 types (V‐A‐W‐VA‐PF) with an 

Manual WS.500 v4                  2‐Wire Energy Monitor  

34  

interval of one minute takes approximately 1MB in size. 

The point in time when the file is transmitted is set per hour. 

The logging is starting from midnight to midnight. 

 

File Name: LOCATION NAME +  log type + DATE + TIME + .csv 

 (Ex. Nieuwstraat18Dendermonde_AMR_28082015_0001.csv) 

Consumption log: The values can also be logged with intervals of 5 minutes to 60 

minutes and will be forwarded directly to the log server. Here one can see the consumption, 

split apart according to day and night rate. (if present) 

If solar panels may also be displayed separately. 

 

File Name: LOCATION NAME + Log type + DATE + TIME + .csv 

    (Ex. Nieuwstraat18Dendermonde_PAYLOG28082015_013003.csv) 

Consumption Daylog (MMR): identically as in the RT Daylog, but only consumption, 

with an adjustable interval of 5 to 60 minutes, or 1 total log of 24h. 

The CSV file has been prepared using the "MMR" format (see EANDIS) 

The point in time when the file is transmitted is set per hour. 

The logging is starting from midnight to midnight. 

File Name: LOCATION NAME + Log type + DATE + TIME + .csv 

  (Ex. Nieuwstraat18Dendermonde_MMR_28082015_013003.csv) 

LOCATION NAME: This information is the file name, and also featured in the header of the file. 

EANnr: can be invoice number, location number ... 

17. DATA TRANSMISSION VIA HTTP 

Log data retrieval is also available with a very simple HTTP request. Enter a statement in the 'Toolbar' from your browser and the 2‐WIRE Web server will answer with a mass of log data. When you can capture this data and process it in your database, you can create your own graphs, statistics or warnings at over‐consumption .... 

The data has the 'JSON' format. The following commands are possible: 

Retrieve current (real‐time) measurements (5logtypes) of all log‐channels 

Retrieve historical (real‐time) measurements of the previous period (up to 3 years back) 

Retrieve consumption‐by‐the‐hour Calling back hourly (up to 3 years back) 

Daily consumption and daily energy cost (up to 1 years back) 

Interested? Check our website and ask for the HTTP instruction‐set at www. 2‐WIRE.be 

18. QUICK START A shortened repeat of all the steps: 

5. Make the necessary connections of power, bus, LAN network. 

Manual WS.500 v4                  2‐Wire Energy Monitor  

35  

6. Retrieve the IP address and port number of your webserver via the “IP Server Scanner” 

software. 

7. Surf to the address and port number (default 8080) 

8. Login with 'adminIP' or ‘admin2‐WIRE’ and password '2015' 

9. Change to fix IP address: go back to menu "SETTINGS" (see Chapter 4) 

10. Add new: go to menu "SETTINGS" old login = 'loginold' old pass = '1234' 

11. Check energy prices: go to menu "SETTINGS", below, cost 

12. Add new Modules: go to menu 'Modules' type serial number, assign names, parameters, fill 

according to the type of module (see leaflet in this section) and send. 

13. Create Channels: to menu CHANNELS ", first create groups (minimum 1), then sort channels, 

divide the groups over the channels. 

14. Main sources: if there are total measurements for menu CHANNELS 'type of channel 

numbers for electricity, gas, water, heating oil. 

15. Export of energy: if total measurements are for export (solar panels), to menu CHANNELS ", 

typing in the channel number (s). 

16. EPC‐level calculation: determine the heating source (s), to menu "CHANNELS", typing of this 

log‐channel number (s) and estimated surface area of the heated rooms. 

17. Go to 'EXIT' and test all channels. (Attention: logging appears only after the first hour!) 

18. PROBLEM SOLUTIONS REFRESH PAGE: When you are on the website of your webserver, and the buttons give no reaction, 

then you're probably lost the 'connection'. This may be because your login time has expired, or your 

PC / tablet was turned off. If so, then go to the 'tool bar of your browser and refresh the page. 

Usually you will have to log in again and then everything will work normally again. 

When there are problems such as the message "page not found" or the 'hourglass' continues to run, 

then there may be a network problem. Try to reload the page. If this is not successful, check whether 

there is Internet connection by visiting a known website. 

SEARCH IP‐ADRES: If you are unable to log in, and there's decent network connection, then you may 

be using the wrong IP address. To determine this, we need an IP address scanner. This program can 

be downloaded via the 2‐WIRE website. (IP Server Scanner). This program will make a 'broadcast' on 

your local network to search for your Web server. When the server scanner has connection, you will 

be able to read all settings. There may be assigned a different IP address. (DHCP ...) and this is the 

way to find out. 

NETWORK PROBLEM: If you cannot reach your web page even after checking with the Server 

Scanner, please check the network cable: At the bottom of the web server where the network 

connector is plugged in, there are two LEDs: green must still lit, the orange LED off and then light up 

briefly. 

When the orange LED never lights up, the network is not connected to your network. 

On top of the WS500 close to the power connector there should light up a green LED, if so then the 

power is okay. Right above there are two push‐buttons, with two associated LEDs. Both LEDs must be 

off, and every 2 seconds the left side LED should light up briefly (heart beat). 

Manual WS.500 v4                  2‐Wire Energy Monitor  

36  

If there remains a continuous LED lights up, then something has gone wrong with the network. Turn 

the power to the webserver and wait for 5 seconds, and turn back the power. The LED should light 

up a 3 seconds and go out afterwards. 

DHCP: When there are problems with DHCP (ex. your router has no IP address), and the Server 

Scanner still cannot find a Web server, despite a decent network connection, you can decide to move 

to a 'default' address: 

Procedure: Power off the WS500, wait 5 seconds, push button 2 and hold, turn on power, and 

continue to press until the LED starts to flash and keep on pressing another 3 seconds before release. 

After about 5 seconds, all LEDs are off and the WS500 is at a fixed address. Now you need to 

"browse" to the default IP address: 192.168.0.123:8080 

Note: This address is not always suitable for the network where your PC or laptop is connected. 

When you are in a different range, you must change the settings of your PC! 

CHANGE IP‐ADRES: You can also change the IP address with the Server Scanner. 

After the program has found your web server, you can manually change the current IP address with 

this program. Type the address and port number, along with other data such SUBNET, GATEWAY, 

DNS. 

FAULTY JAVASCRIPT/STYLE: If you discover errors on the website, or there is no key that still reacts, 

even after 'refresh page, then there may slipped an error when loading the script / style. You can 

then manually re‐download the javascript by pressing the 2‐Wire Server button 1  (left, shortest at 

the power connector) and keep pressing until the left LED lits continuously. Then release the key. 

Now the LED 15 to 20 seconds should stay on and then go out again. If this is OK, then you do the 

right button (press 2) just the same: keep pressing until the flashing stops and both LEDs light up 

continuously, then release the key. 

Now the LEDs must also be 15 to 20 seconds on and then the right LED starts quickly flashing. 

Afterwards the LED will burn continuously 3 seconds and then go out. Everything fine !!! 

When these things happen as described, then try again "refresh page and sign in. 

CLEAR COMPLETE DATABASE, RESET IP and PASSWORD:  

Key 1 (shortest to power connector) 

Procedure: Power off the WS500, wait 5 seconds, press button 1 and hold, turn on power, and 

continue to press until the LED starts flashing, keep pushing another 3seconds until the LED stops 

blinking and then release. 

The delete process may take about 60 seconds, and the WS500 is ready when the LED goes out. 

IFORGOT IP‐ADRES or FORGOT PASSWORD: 

Key 2 (far right away from the connector) 

Procedure: Power off the WS500, wait 5 seconds, push button 2 and hold, turn on power, and 

continue to press until the LED starts to flash. Stay on pushing another 3 seconds until the LED stops 

blinking and then release. 

Manual WS.500 v4                  2‐Wire Energy Monitor  

37  

The delete process can take about 3 seconds, and the WS500 is ready when the LED goes out. 

Now you need to "browse" to the default IP address: 192.168.0.123:8080 and login, password as 

described in Part 8 

In summary: 

Pressing buttons during the running: 

Key 1: Upgrading Javascript and CSS. 

Key 2: Upgrading firmware Webserver WS500 

Pressing keys during startup POWER: 

Key 1: Delete entire database, IP address, reset, login and password 

Key 2: reset the IP address and password. 

 

2‐WIRE 2015