269_Leido

Embed Size (px)

Citation preview

  • 8/12/2019 269_Leido

    1/5

    A study on relay setting for AT feeding system protection

    using PSCAD/EMTDC

    Hosung Jung, Moonseob Han, Changmu Lee, Joorak Kim

    Korea Railroad Research Institute

    360-1, Woulam-Dong, Uiwang-City, Kyeonggi-Do, Korea

    Abstract

    This paper presents simulation technique for relay setting of AT feeding system protection. To prove if relay setting

    value is proper, AT feeding system and various locomotives are modeled using PSCAD/EMTDC. Operation and fault

    data have been extracted by simulating various load operation and fault situations. Using these data, setting values of

    distance relay and !I fault selection device for protection of AT feeding circuit could be verified. And due to the inrush

    current of unloading transformer and increase of temporary maximum load current, the possibility of protection relays

    malfunction is shown.

    Keywords: PSCAD/EMTDC, AT Feeding System, Locomotive, Distance Relay, !I Fault Selection Device

    1 INTRODUCTION

    Electrification of railway was rapidly spread with the

    opening of KTX(Korea Train Express) in Korea.

    Electric railway system supplies power to rolling stocks

    by converting three phase ac power supplied bypower supply company to two single phase ac power of

    which phase difference is 90"using scott transformer.

    And electric locomotive has been developed from the

    thyristor phase controlled locomotive to PWM(Pulse

    Width Modulation) controlled locomotive.

    Since any fault in these electric railway systems may

    cause damages on rolling stork and ground facilities as

    well as interruption of railway operation and damages

    on life or properties, it requires a more reliable

    protection method. For the protection of AT feeding

    system, distance relay using impedance magnitude

    measured at substation and !I fault selection device

    using current increment value in fixed time are installed

    for main and backup protection relay[1], [2].

    However protection relay is hard to detect fault and

    cause malfunction in the normal operation condition

    because of increase of train operation frequency,

    competition of traction load and regeneration load, and

    operation of different type of locomotive in the same

    section. To prevent it, protection relay setting value

    should be corrected by analyzing load and fault

    characteristics of the AT feeding system generally[3].

    Therefore, this paper modeled AT feeding system and

    locomotives using PSCAD/EMTDC, power system

    analysis program, to prove the suitable setting value.

    Various operation and fault conditions have been

    simulated and the load operation characteristics and

    fault are analyzed.In conclusion, we can see the reliable trip of relay to the

    various faults and the possibility of protection relays

    malfunction due to the inrush current of unloading

    transformer and increase of temporary maximum load

    current.

    2 Protection System for AT Feeding Circuit

    For the protection of feeding circuit in AT feeding

    system, distance relay(44F) and ! I fault selection

    device(50F) are applied in dual mode. The main

    protection, distance relay calculates impedance using

    voltage and current measured at substation and detects a

    fault in case the calculated value converges into a range

    of fault impedance. In general, distance relay is setted

    to protect up to 120% of line impedance between

    substation(SS) and sectioning post(SP) in order to

    eliminate any unprotected arear. The secondary

    protection, ! I fault selection device compares the

    current increment value by notches of load current(1I )

    and fault current(2I ) to detect a fault such as

    expression (1).

    21 III

  • 8/12/2019 269_Leido

    2/5

    Figure 1 shows the protection region of distance relay

    and ! fault selection technique.

    Figure 1. Protection System for AT Feeding Circuit

    Distance relay and ! I fault selection device may

    malfunction due to the inrush current of AT and rolling

    stocks transformer during unloading or increase of the

    maximum load current in case of sudden load increase.To prevent it, the trip of relay is blocked by a certain

    amount of low order harmonics using the feature that

    low order harmonics in fault current is relatively not

    more than that of load current.

    3 AT Feeding System Modeling Using PSCAD/EMTDC

    3.1 AT Feeding System

    AT feeding system generally consists of electric power

    company, transmission line, electric railway substation,

    sectioning post/subsectioning post and feeding circuit.

    This paper modeled it by each component usingPSCAD/EMTDC such as figure 2[4], [5].

    Figure 2. Modeling of AT feeding system

    First, it receives three phase 154kV from electric power

    company through transmission line, and converts three

    phase 154kV into two single phase 55kV using scott

    transformer at railway substation and then converts the

    55kV to 27.5kV using AT transformer for supply to the

    rolling stocks. Autotransformer of SP and SSP has been

    modeled to supply 27.5kV to upper/lower lines. Andfeeding circuit is modeled by 10 port network divided

    into upper/lower catenary line group, upper/lower

    feeder line group and rail group. To verify the accuracy

    degree of modeling, the magnitude of fault current at

    each point and line impedance magnitude of short

    circuit between rail and catenary are compared in

    manual calculation and simulation results. Table 1 and

    figure 3 illustrate the result of comparison[6].

    Table 1. Comparison of fault Current by Manual

    Calculation and Simulation

    Unit : [kA]

    Fault point and typeManual

    CalculationSimulation

    3 phase short 39.13 39.08Substation of

    power

    company 1 line ground 37.20 37.12

    3 phase short 12.63 12.63End of

    transmissionline 1 line earth f 9.47 9.61

    2nd of Scott

    Transformershort fault 2.31 2.42

    2nd of AT

    TransformerShort fault 10.71 10.79

    0 2 4 6 8 10 12 14 16 18 20

    2

    4

    6

    8

    10

    12

    14

    16

    Comparison of the Line Impedance

    Impedance[Ohm]

    Calculation Value

    Simulation Value

    Figure 3. Comparison of Line Impedance by Manual

    Calculation and Simulation

    It is reasonable that AT feeding system modeling isaccurate, considering the values of calculation and

    simulation. It is also shown that the short-circuit

    impedance between rail and catenary is not linear but

    slightly curved due to the boost of autotransformer of

    SP and SSP. And there is a little difference between

    calculation and simulation, it is assuming that it is

    calculated in the single line condition and

    autotransformer is not considered.

    3.2 Locomotive Modeling

    Due to the development of power electronicstechnology, locomotive has been developed from

  • 8/12/2019 269_Leido

    3/5

    resistance control to thyristor phase control and up to

    PWM control method. So locomotive with different

    controls are inevitably operated in a same section and

    the protection relay should be set considering the load

    characteristics.

    To model locomotive using PSCAD/EMTDC, the speedis divided into 10 levels from start to the maximum

    speed and the effective/reactive power by speeds is

    converted into impedance. Meanwhile, harmonics,

    which occurs when locomotives are operated, is

    expressed with the maximum values of each order as its

    constant current source and modeled accordingly.

    Thyristor phase controlled locomotive, using ac power

    supplied from catenary and a rectifier combining

    semi-bridge type thyristor and diode, controls thyristor

    phase, changes speed and alternates its traction force by

    field-weakening control. The currently operated

    thyristor phase controlled locomotives is EL 8000electric locomotive and KTX. The power factor at the

    maximum traction is about 0.7~0.8 and the harmonics

    seems to be relatively huge generally.

    Figure 4 illustrates the load region by modeling

    thyristor phase controlled and simulating them in

    various operation conditions. It shows that power factor

    is better than that of thyristor phase controlled

    locomotives, because it was compensated the power

    factor using power factor compensation device in

    locomotive.

    0 100 200 300 4000

    100

    200

    300

    400

    44F

    X[Ohm]

    Load

    Thyristor Phase Control Vehicle

    Figure 4. Load area of thyristor phase controlled

    locomotive

    PWM controlled locomotives convert electric power

    from feeder voltage of single phase ac power and 60Hz

    frequency to dc constant voltage while ac voltage

    generated from voltage transformer is structured as

    pulse voltage, converting pulse width to ac voltage. The

    currently operated PWM controlled locomotives are EL

    8100 locomotives and High Speed Railroad(HSR-350),G7 trains. Since the voltage and current wave are

    almost closed to sine wave, it is controlled that power

    factor is to be 1 regardless of sizes of feeder voltage

    and traction motors. And unlike other controlled

    locomotives, it contains a little low order harmonics.

    Figure 5 illustrates the load area by modeling PWM

    controlled locomotives and simulating them in various

    operation conditions, showing that in traction, thepower factor is maintained 1.

    0 100 200 300 400

    0

    100

    200

    300

    44F

    X[Ohm]

    Load

    PWM Control Vehicle

    Figure 5. Load area of PWM controlled locomotive

    Harmonic components, which are generated when

    locomotive is operated, have an influence on the

    fundamental wave, making it difficult to detect faults

    while they are used to the factor of low order harmonics

    in order to prevent maloperation of distance relay and

    I fault selection device. Since the generation of

    harmonics is, however, different depending on vehicles,

    it is required to analyze the generation by control types.

    1 5 9 13 17 21 25 29 33 37 41 45 490

    5

    10

    15

    20

    25

    30

    35

    40

    Maximum H arnomic Current

    Harm

    onicCurrent[A]

    Harnomic Degree

    Thyristor Phase Control

    PWM C ontrol

    Figure 6. Comparison of Harmonic Current by Control Types

    Figure 6 illustrates the comparison of harmonic currents,

    which occur from thyristor phase controlled locomotive

    and PWM controlled locomotive respectively. In

    general, PWM controlled locomotives THD is within

    5% while thyristor phase controlled locomotive is about

    15%.

  • 8/12/2019 269_Leido

    4/5

    4 Relay Setting and Impedance Convergence Characteristics

    4.1 Relay Setting for Feeding Circuit Protection

    To verify setting values of distance relay and !I fault

    selection device, the following feeding system has been

    modeled. In the modeling, the full length of line is up to

    50km considering extension feeding, and the lineimpedance is 0.159+j0.695(0.73 77.15 ") !/km. In

    addition, for the maximum load condition, it is

    simulated with the maximum load current of 945A

    (based on 55kV) because up to 3 locomotives could be

    operated to each direction in the same section.

    ( ) Distance Protective Relaying Scheme

    R = 0.159 !/km # 50 km # 120 % = 9.54 !

    X = 0.695 !/km # 50 km # 120 % = 41.7!

    () !I fault selection device (in maximum operation)

    )2/(/0 hLFF kIIVZ += = 55000 / (945/2 + 945 * 0.5) = 58.2 !

    Figure 7 illustrates the protection region according to

    setting values of protection relay drawn on impedance

    map. Distance relay could protect up to 120% of the

    line impedance from a substation to its neighboring

    substation, considering extension feeding while ! I

    fault selection device could protect up to maximum

    load current.

    0 10 20 30 40 50 60

    0

    10

    20

    30

    40

    50

    60

    R [Ohm]

    44F

    Line Impedance

    50F

    X

    [Ohm]

    Protection Region

    77.15

    Figure 7. Protection Region of Protection Relay

    4.2 Impedance Convergence Characteristics

    To analyze the convergence characteristics of fault

    impedance in case of any condition, the short fault

    between catenary and rail and short fault between

    catenary and feeder have been simulated. Figure 8

    illustrates the simulated short fault between catenary

    and rail at the maximum load operation and shows theimpedance convergence for faults, which occurred at

    10%, 30%, 50%, 70% and 90% from a substation.

    0 10 20 30 40 50 60

    0

    10

    20

    30

    40

    50

    60

    R [Ohm]

    10%

    30%

    50%

    70% 90%

    44F

    Line Impedance

    50F

    X[Ohm]

    Catenary-Rail Short Fault

    Figure 8. Fault Impedance Convergence

    (Catenary-Rail Short Fault)

    Figure 9 shows the simulated short-circuit between

    catenary and feeder at the maximum load operation and

    illustrate impedance convergence for faults, which have

    occurred at 10%, 30%, 50%, 70% and 90% from a

    substation.

    0 10 20 30 40 50 60

    0

    10

    20

    30

    40

    50

    60

    R [Ohm]

    10%

    30%

    50%

    70%

    90%

    44F

    Line Impedance

    50F

    X[Ohm]

    Catenary-Feeder Short Fault

    Figure 9. Fault Impedance Convergence(Short Fault of Catenary-Feeder)

    As seen in the above results, it is verified that the

    setting values of distance relay could be used to detect

    faults regardless of type or distance of faults.

    Figure 10 shows the characteristics of changes in

    impedance due to inrush current of unloading

    transformer or sudden load increase. It can be expected

    that a relay may maloperation as impedance temporarily

    converges into protection region due to sudden load

    increase or inrush current. Therefore, low orderharmonic restriction is essential to prevent a relays

    maloperation.

  • 8/12/2019 269_Leido

    5/5

    0 10 20 30 40 50 60

    0

    10

    20

    30

    40

    50

    60

    R [Ohm]

    Maximum Load Curren

    Inrush Current

    44F

    Line Impedance

    50F

    X[Ohm]

    Maloperatoin Condition

    Figure 10. Load Impedance Convergence

    (maloperation condition)

    5 CONCLUSION

    This paper presents simulation technique for relay

    setting of AT feeding system protection. To prove if

    relay setting value is proper, AT feeding system and

    thyristor phase controlled and PWM controlled

    locomotives are modeled using PSCAD/EMTDC.

    Operation and fault data have been extracted by

    simulating various load operation and fault situations.

    Using these data, setting values of distance relay and

    I fault selection device for protection of AT feeding

    circuit could be verified. And due to the inrush currentof unloading transformer and increase of temporary

    maximum load current, the possibility of protection

    relays malfunction is shown.

    It is required in further studies that AT feeding system

    and locomotives considered moving load characteristics

    are modeled in detail.

    REFERENCES

    [1] Gao Shibin, He Weijun, Chen Xiaochuan, Study

    on Microprocessor-Based Adaptive Protective Relay

    for Heavy Duty Electric Traction System,

    Developments in Power System Protection Conference

    Publication No. 434, pp319-322, 1997

    [2] Tevfik Sezi, Frank E. Menter, Protection Scheme

    for a New AC Railway Traction Power System, IEEE

    Transmission and Distribution Conference vol 1,

    pp388-393, 1999

    [3] Hosung Jung, A Study on Protection system to the

    Load Characteristics on the AC Feeder System,

    Proceeding of the KIEE Summer Annual Conference

    2004, No. B, pp 1370-1372, 2004

    [4] Hanmin Lee, Kwanghae Oh, Fault Analysis of AC

    Electric Railway System Mode by EMTDC, Trans.

    KIEE vol. 52A, no. 9, pp 1-7, 2003.

    [5] PSCAD/EMTDC Users mannual.

    [6] Korea Railroad Research Institute, A Study on the

    Overhead Contact-line Constant and Optimal Strategy

    of Protection Circuit in the Electrical Railway

    Substation, Korea Railroad, 1998

    Biographies

    Hosung Jung

    1998 Master Degree in Sungkyunkwan

    Univ. 1998-2002 Ph.D in

    Sungkyunkwan Univ. 2002-Present

    Researcher in KRRI (Korea Railroad

    Research Institute) E-mail

    [email protected]

    Moonseob Han

    1989 Master Degree in Inha Univ.

    1989-1995 Researcher in ADD

    (Agency for Defense Development)

    1995-Present Senior Researcher in

    KRRI (Korea Railroad Research

    Institute) E-mail [email protected]

    Changmu Lee

    1994 Master Degree in Hanyang Univ.

    1994-1997 Researcher in Korea

    Institute of Industrial Technology

    1997-Present Senior Researcher in

    KRRI (Korea Railroad Research

    Institute) E-mail [email protected]

    Joorak Kim

    1999 Master Degree in Hongik Univ.

    1999-2000 Researcher in Hongik Univ.

    2000-Present Researcher in KRRI

    (Korea Railroad Research Institute)

    E-mail [email protected]