    WarrantyDefects occurring within 3 years from delivery date shall beremedied free of charge at our plant (carriage and insurancepaid by sender).Sensors, fittings, and accessories: 1 year.

    Subject to change without notice.

    KnickElekt ronische MessgerteGmbH & Co. KG

    P.O. Box 37 04 15D-14134 Berlin

    Phone: +49 (0)30 - 801 91 - 0Fax: +49 (0)30 - 801 91 - 200Internet: http://[email protected]

    3

    Safet y inf ormat ion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6Trademarks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

    EC Declaration of Conformity . . . . . . . . . . . . . . . . . . . . . . .7

    Overview o f Strat os e 2402 CondI . . . . . . . . . . . . . . . . . . .9Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

    Package contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10Mounting plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11Pipe mounting, panel mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Information on installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14Terminal assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

    Installat ion and connection . . . . . . . . . . . . . . . . . . . . . . .14Preparing the shield connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16Typical wiring SE 655 / SE 656 sensor . . . . . . . . . . . . . . . . . . . . . . . . . . .17Typical wiring SE 652 sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18Typical wiring SE 654 sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

    Sensors from other manufacturers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19Protective wiring of relay outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20

    User int erface and display . . . . . . . . . . . . . . . . . . . . . . . .22Operation: Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24

    Safety f eat ures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Sensocheck, Sensoface sensor monitoring . . . . . . . . . . . . . . . . . . . . . . . .25GainCheck device self test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Automatic device self-test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Hold mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26External activation of Hold mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27

    Configu rat ion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28Menu structure of configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29

    Overview of configuration steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30Output 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32Output 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48Temperature compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54Alarm settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56Limit function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62Controlling a rinsing probe or signaling parameter set 2 . . . . . . . . . . . .64

    Contents

  • 8/9/2019 2402 condi

    3/65

    4 Stratos e 2402 CondI

    Selecting paramet er set 1/2 . . . . . . . . . . . . . . . . . . . . . . .66Manually or automatically via Control . . . . . . . . . . . . . . . . . . . . . . . . . .66External switchover of parameter sets . . . . . . . . . . . . . . . . . . . . . . . . . . .67Default settings of parameter sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69Parameter set, individual settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70

    Calibrat ion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72

    Calibration by input of cell factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74Calibration with calibration solution . . . . . . . . . . . . . . . . . . . . . . . . . . . .76Product calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78Zero calibration in air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80Zero calibration with calibration solution . . . . . . . . . . . . . . . . . . . . . . . . .82Adjusting temp probe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .84

    Diagnostics functions . . . . . . . . . . . . . . . . . . . . . . . . . . . .85Display of output currents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85Display of calibration data (Cal Info) . . . . . . . . . . . . . . . . . . . . . . . . . . . .85Sensor monitor for validation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85Display of last error message (Error Info) . . . . . . . . . . . . . . . . . . . . . . . . .85Specify current at output 1 (current source 1) . . . . . . . . . . . . . . . . . . . . .86Specify current at output 2 (current source 2) . . . . . . . . . . . . . . . . . . . . .86

    Relay test (manual test of contacts) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86Controller test (manual specification of controller output) . . . . . . . . . . . .87

    Cont roller functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86PID controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88Pulse length / pulse frequency control ler . . . . . . . . . . . . . . . . . . . . . . . .90

    Error m essages (error codes) . . . . . . . . . . . . . . . . . . . . . .92Operat ing sta tes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .94Sensoface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .99

    Product line and accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .99Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100

    Explosion protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .106Warnings and notes to ensure safe operating . . . . . . . . . . . . . . . . . . . .107Control Drawing CSA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108Calibration solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .112Concentration measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .114Concentration curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .115

    Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120

    5

    Safety informat ion

    Be sure to read and observe the following instruc-tions!

    The device has been designed in accordance with the state ofthe art and complying with the applicable safety regulations.When operating the device, certain conditions may neverthe-less lead to danger for the operator or damage to the device.

    Caution!Commissioning may only be carried out by trained experts.Whenever it is likely that protection has been impaired, thedevice shall be made inoperative and secured against unintend-

    ed operation.

    The protection is likely to be impaired if, for example: the device shows visible damage the device fails to perform the intended measurements after prolonged storage at temperatures above 70 C after severe transport stresses

    Before recommissioning the device, a professional routine testin accordance with EN 61010-1 must be performed. This test

    should be carried out by the manufacturer.

    Caution!Before commissioning it must be proved that the device maybe connected with other equipment.

  • 8/9/2019 2402 condi

    4/65

  • 8/9/2019 2402 condi

    5/65

    8 Stratos e 2402 CondI 9

    Overview of Stratos e 2402 CondI

    1

    2

    3

    4

    5

    C

    D

    E

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    CondIinput

    Hold

    input

    Control

    input

    Output 1

    Output 2

    Alarm

    Clean

    PSet2

    Power

    receive hi

    receive lo

    drain

    send lo

    send hi

    shield

    RTD

    RTD

    hold

    hold/control

    control

    + output 1

    - output 1/2

    + output 2

    relay 1

    relay 1/2

    relay 2

    alarm

    alarm

    clean

    PSet2

    power

    power

    R1

    R2

    Tempinput

    cleanPset2

  • 8/9/2019 2402 condi

    6/65

    10 Stratos e 2402 CondI

    Package contentsCheck the shipment for transport damage and completeness.The package should contain: Front unit of Stratos Lower case

    Bag containing small parts Instruction manual Specific test report

    Assembly

    11

    10

    9

    8

    7 6 5 4

    1

    2

    3

    6 Sealing inserts (1 piece)

    7 Rubber reducer (1 piece)8 Cable glands (3 pieces)9 Filler plugs (3 pieces)10 Hexagon nuts (5 pieces)11 Sealing plugs (2 pieces),

    for sealing in case of wall mounting

    1 Jumper (2 piece)

    2 Washer (1 piece), for conduitmounting: place washer betweenenclosure and nut

    3 Cable ties (3 pieces)4 Hinge pin (1 piece), insertable from

    either side5 Enclosure screws (4 pieces)

    Fig.: Assembling the enclosure

    11

    M ounting plan

    144

    144

    15

    42

    84

    8032

    21

    43

    105

    27

    72

    6,

    2

    1 2

    3

    4

    1 Cable gland (3 pieces)2 Breakthroughs for cable gland

    or conduit 1/2 , 21.5 mm (2 breakthroughs)Conduits not included!

    3 Breakthroughs for pipe mounting(4 breakthroughs)

    4 Breakthroughs for wall mounting(2 breakthroughs)

    Fig.: Mounting plan

  • 8/9/2019 2402 condi

    7/65

    12 Stratos e 2402 CondI

    40 60132

    1

    2

    3

    4

    5

    Fig.: ZU 0274 pipe-mount kit

    1 ZU 0276 protective hood (if required)2 Hose clamps with worm gear drive to DIN 3017 (2 pieces)3 Pipe-mount plate (1 piece)4 For vertical or horizontal posts or pipes5 Self-tapping screws (4 pieces)

    1

    132165

    173

    1

    Fig.: ZU 0276 protective hood for wall and pipe mounting

    Pipe mount ing, panel mounting

    13

    1

    2

    3

    45

    max. 25

    78 27

    1...22

    1 Screws (4 pieces)2 Gasket (1 piece)3 Panel4 Span pieces (4 pieces)5 Threaded sleeves (4 pieces)

    Fig.: ZU 0275 panel-mount kit

  • 8/9/2019 2402 condi

    8/65

  • 8/9/2019 2402 condi

    9/65

  • 8/9/2019 2402 condi

    10/65

    18 Stratos e 2402 CondI

    Typical w iringSE 652 sensor

    receivehi

    receivelo

    drain

    shield

    RTD

    15

    wt

    16

    bk(rcv)

    14

    bk

    12

    bu

    11

    rd

    sendlo

    sendhi

    2402 CondI

    Caution!Place jumper across terminals 3 and 4!

    RTD

    17

    bk

    13

    bn(snd)

    jumper!

    19

    Typical w iringSE 654 X sensor

    receivehi

    receivelo

    drain

    shield

    RTD

    r

    d

    t

    ransparent

    t

    ransparent

    w

    t

    b

    n

    b

    u

    sendlo

    sendhi

    2402 CondI

    Sensors of ot her m anufacturers:For special applications (chemical resistance, type of mounting), youcan also connect sensors from other manufacturers.Permissible ranges for the Stratos e 2402 CondI as well as terminalassignments and factory settings for these sensors are available onrequest.

    RTD

    b

    k

    coaxwt

    coaxbk

  • 8/9/2019 2402 condi

    11/65

    20 Stratos e 2402 CondI

    Protective w iring of switching contactsRelay contacts are subjected to electrical erosion. Especiallywith inductive and capacitive loads, the service life of the con-tacts will be reduced. For suppression of sparks and arcing,components such as RC combinations, nonlinear resistors,

    series resistors and diodes should be used.

    1

    23

    1 2

    3

    Typical AC applicationswit h inductive load

    1 Load2 RC combination, e.g. RIFA PMR209

    Typical RC combinationsfor 230 V AC:Capacitor 0.1F/ 630V,Resistor 100 Ohms / 1 W

    3 Contact

    Protective wiring of switching outputs

    21

    A: DC application with inductive load

    B: AC/DC applications with capacitive loadC: Connection of incandescent lamps

    A1 Inductive loadA2 Free-wheeling diode, e.g. 1N4007

    (Observe polarity)A3 ContactB1 Capacitive loadB2 Resistor, e.g. 8 Ohms/1 W at 24 V / 0.3 AB3 Contact

    C1 Incandescent lamp, max 60 W / 230 V, 30 W / 115 VC3 Contact

    Warning!Make sure that the maximum ratings of the relaycontacts are not exceeded even during switching!

    Typical protective w iring m easures

  • 8/9/2019 2402 condi

    12/65

  • 8/9/2019 2402 condi

    13/65

    24 Stratos e 2402 CondI

    Operation: Keypad

    Start, end calibration

    Start, end configuration

    Select digit position

    (selected position flashes)Edit digit

    Calibration:Continue in program sequence

    Configuration: Confirm entries,next configuration step

    Measuring mode: Display output current

    Cal Info: Display of cell factor and zero point

    Error Info: Display of last error message

    Start GainCheck device self-test+

    25

    Sensocheck, Sensoface sensor m onitoringSensocheck cont inuously monitors the sensor and its wiring.Sensocheck can be switched of f (Configuration, Pg 57).

    Sensoface provides information on the conductivitysensor condition. The primary coil and its wirings arecontinuously monitored for short circuits, the secondarycoil and its wirings are checked for open circuits.The three Sensoface indicators inform of the sensorcondition.

    GainCheck device self testA display test is carried out, the software version is displayed andthe memory and measured value transfer are checked.

    Start GainCheck device self-test:

    Automatic device self-testThe automatic device self-test checks the memory and meas-ured-value transfer. It runs automatically in the background atfixed intervals.

    +

    Safet y funct ions

  • 8/9/2019 2402 condi

    14/65

  • 8/9/2019 2402 condi

    15/65

    28 Stratos e 2402 CondI

    The configuration parameters arechecked during the input. In thecase of an incorrect input Err isdisplayed for approx. 3 s. Theincorrect parameters cannot bestored. Input must be repeated.

    ConfigurationIn the Configuration mode you set the device parameters. The Stratos canstore two different parameter sets and switch between them. Sensor dataand Clean/Pset2 output are edited in parameter set 1 only. They are validfor both parameter sets.

    Press conf.

    Enter mode code 1200 :

    Edit parameter set 1 with and, confirm/proceed with enter.

    Enter mode code 1288 :Edit parameter set 2 with and

    , confirm/proceed with enter.

    The output current is frozen(at its last value or at a preset fixedvalue, depending on the configura-tion), limit and alarm contacts are

    inactive. The controller is in the con-figured state, Sensoface is off, modeindicator Configuration is on.

    Configuring

    Hold

    Input errors

    End End with conf. The measured valueand Hold are displayed alternately,

    enter flashes. Press enter to end the

    Hold mode. The measured value is dis-

    played. The output current remains

    frozen for another 20 s (HOLD icon

    on, hourglass flashes).

    HOLD icon

    During config-

    uration theStratos remainsin the Holdmode.

    Parameter set 1

    Parameter set 2Configure: 88 appears inthe display.

    29

    Menu group Code DisplaySelect menu group

    M enu structure of configuration

    The configuration steps are assigned to dif ferent menu groups.With the arrow keys you can jump between the individual menugroups.Each menu group contains menu items for setting the parameters.

    Pressing enter opens a menu item. The values are edited using thearrow keys. Pressing enter confirms/stores the settings.Return to measurement: Press conf .

    Select menu item

    Output 1 o1.

    Output 2 o2.

    Temperature

    compensationtc.

    Alarm

    settingsAL.

    Relay / Controller rL.

    CLEAN contact /Signaling param-

    eter set 2Cn.

    Previousmenu

    group:

    Menu item 1

    Menu item 2

    Menu item ...

  • 8/9/2019 2402 condi

    16/65

    30 Stratos e 2402 CondI

    Overview of configuration steps

    Selection / Default

    SE652/SE654/SE655/SE656/other

    xx.xxx c

    8 kHz / 16 kHz

    mS/cm, S/m, Conc, SAL

    NaCl, HCl, NaOH, H2SO4, HNO3

    (Code 01 ... 10, see Pg 114)

    Select current range 0-20 mA / 4-20 mA

    Characteristic (not for Conc, SAL) Linear LIN / Logarithmic LOG

    Time constant of output filter xxxx SEC

    out2 Output 2

    o2. Select temperature unit C / F

    Select current range 0-20 mA / 4-20 mA

    Enter current beginning xxx.x

    Enter current end xxx.x

    Time constant of output filter xxxx SEC

    ON / OFF

    Signal behavior during HOLD Last / Fix

    xxx.x mA

    22 mA signal for error messages ON / OFF

    MenuCode

    out1 Output 1

    o1. Sensor selection *

    Enter transfer ratio

    Select measured variable

    Select solution (Conc)

    Signal behavior during HOLD Last / Fix

    Enter fixed value xxx.x mA

    xxx.xx

    Entry of cell factor

    Meas. frequency selection

    Select temperature probe Pt100/Pt1000/NTC100

    LIN: xxxx mSEnter current beginning

    Enter current end

    LOG: Enter current beginning

    Enter current end

    xxxx mS

    in decades: 0.001 ... 1000

    in decades: 0.001 ... 1000

    other * :

    Enter fixed valueFix:

    Fix:

    22 mA signal in the case of temp error

    31

    tc Temperat ure compensation

    tc. Temperature compensation selection OFF / Lin / nLF

    xx.xx %/K

    MenuCode Selection / Default

    ALrt Alarm settings

    AL.Select Sensocheck ON / OFF

    Enter alarm delay xxxx s

    LED in HOLD mode ON / OFF

    rLAY

    rL. Select limit function / controller LiMIT / CtROL

    Select contact function Lo / HiL1.

    Select contact response N/O / N/C

    Enter switching point xxxx

    Enter hysteresis xxxx

    Enter delay xxxx SEC

    Select contact function Lo / HiL2.

    Enter controller setpoint xxxxCt.

    Enter neutral zone xxxx

    (P) Controller gain KP xxxx %

    (I) Reset time TR xxxx SEC

    (D) Rate time TD xxxx SEC

    PLC: Pulse length xxxx SECPFC: Pulse frequency xxxx /min

    Select HOLD behavior Y Last / Y Off

    rinse / PSEt 2

    Rinsing interval xxx.x hrinse

    Rinse duration xxxx SEC

    Contact response N/O / N/C

    Select contact response N/O / N/C

    Enter switching point xxxx

    Enter hysteresis xxxx

    Enter delay xxxx SEC

    Relay 1/2: Limit values, controller

    (Select Cleaning/Signal/Parameter set)*

    Contact CLEAN / PSet2Cln

    Cn.

    * These parameters are only edited in parameter set 1.They are valid for both parameter sets.

    Pulse length/frequency controller PLC / PFC

    Lin: Input of temp. coefficient

    C fi ti

  • 8/9/2019 2402 condi

    17/65

    32 Stratos e 2402 CondI

    ConfigurationOutput 1Select sensor

    Sensor selection

    Select measured variable

    Select 0-20 / 4-20 mA

    End:Press conf, then enter

    Code

    Output 1 o1.

    DisplayMenu group Select menu item

    Enter current beginning

    Enter current end

    Set output filter

    22 mA in the case of error

    Hold mode

    Characteristic: LIN / LOG

    Select solution (Conc)

    33

    Note: Characters represented in gray are flashing and can be edited.

    Code Display Action Choices

    o1. Select configurat ion(Press conf .)

    The Stratos is in HOLD mode(HOLD icon is on).

    Select sensor * : Select witharrow key. Proceed with enter.

    Note:

    After each sensor selection thenominal cell factor of the sensoris stored.To adjust the cell factor to thedevice, calibrate the sensorafterwards!

    SE 655(SE 652SE 654SE 655SE 656other)

    For parameter set 1:

    Enter mode code 1200(Select position using arrow

    key and edit number using .When the display reads 1200 ,press enter to confirm.)

    For parameter set 2:Enter mode code 1288

    (Select position using arrow

    key and edit number using .When the display reads 1288 ,

    press enter to confirm.)

    After correct input a welcometext (CONF) isdisplayed forapprox. 3 s

    After correct input a welcometext ( CONF) is displayed forapprox. 3 s

    * These parameters are only edited in parameter set 1.They are valid for both parameter sets.

    C

  • 8/9/2019 2402 condi

    18/65

    34 Stratos e 2402 CondI

    ConfigurationOutput 1Select sensor and temperature probe

    Sensor selection

    Select solution (Conc)

    Select 0-20 / 4-20 mA

    End:Pressconf, then enter

    Code

    Output 1 o1.

    DisplayMenu group Select menu i tem

    Enter current beginning

    Enter current end

    Set output filter

    22 mA in the case of error

    Hold mode

    Characteristic: LIN / LOG

    Select measured variable

    35

    Code Display Action Choices

    o1.

    Select measuring frequency

    Select with arrow key

    8 KHZ(8 KHZ16 KHZ)

    100Pt(100Pt1000Pt100NTC)

    Proceed with enter

    Select temperature probe

    Select with arrow keyProceed with enter

    Note: Characters represented in gray are flashing and can be edited.

    With other selected the sensorparameters are entered separate-ly:

    Enter cell factor:(Select position using arrow

    key and edit number using .)Proceed with enter

    Enter transfer ratioProceed with enter.

    NoteWhen other is called up oncemore, the last sensor parame-ters are displayed and can beedited.

    C fi ti

  • 8/9/2019 2402 condi

    19/65

    36 Stratos e 2402 CondI

    ConfigurationOutput 1Select m easured variable

    End:Pressconf, then enter

    Code

    Output 1 o1.

    DisplayMenu group Select menu item

    Sensor selection

    Select measured variable

    Select 0-20 / 4-20 mA

    Enter current beginning

    Enter current end

    Set output filter

    22 mA in the case of error

    Hold mode

    Characteristic: LIN / LOG

    Select solution (Conc)

    37

    Code Display Action Choices

    o1. Select measured variable:

    Select with arrow keyProceed with enter

    Conductivity: 0.000 ... 9.999 mS/cm 00.00 ... 99.99 mS/cm 000.0 ... 999.9 mS/cm 0000 ... 1999 mS/cm 0.000 ... 9.999 S/m 00.00 ... 99.99 S/m

    Salinity (SAL): 0.0 ... 45

    Concentration (Conc) 00.00 ... 99.99 % by wt

    000.0 mS(0.000 mS00.00 mS000.0 mS

    0000 mS0.000 S/m00.00 S/m00.00 SAL00.00 %(Conc))

    Note: Characters represented in gray are flashing and can be edited.

    C fi ti

  • 8/9/2019 2402 condi

    20/65

    38 Stratos e 2402 CondI

    ConfigurationOutput 1Concentration measurement: Select process solution

    Sensor selection

    Select measured variable

    Select 0-20 / 4-20 mA

    Enter current beginning

    Enter current end

    Set output filter

    22 mA in the case of error

    Hold mode

    End:Pressconf, then enter

    Code

    Output 1 o1.

    DisplayMenu group Select menu item

    Characteristic: LIN / LOG

    Select solution (Conc)

    39

    Code Display Action Choices

    o1. Only with 00.00 % CoNCyou can select the process solution:

    Select with arrow key

    -01- NaCl (0 ... 26 % by wt)

    -02- HCl (0 ...18 % by wt)

    -03- NaOH (0 ... 14 % by wt)

    -04- H2SO4 (0 ... 30 % by wt)

    -05- HNO3 (0 ... 30 % by wt)

    -06- H2SO4 (92 - 99 % by wt)

    -07- HCl (22 - 29 % by wt)

    -08- HNO3 (35 -36 % by wt)

    -09- H2SO4 (32 - 84 % by wt)

    -10- NaOH (18 ... 50 % by wt)Proceed with enter

    -01-SOL

    (-01-SOL-02-SOL-03-SOL

    -04-SOL-05-SOL-06-SOL-07-SOL-08-SOL-09-SOL-10-SOL)

    Concentration curves / rangessee Pg 114 and the following

    The concentration curves of many sub-stances show a maximum. This means that

    if the substance concentration continues toincrease and the temperature remains con-stant, the conductivity will drop. Therefore,a one-to-one correlation of values is onlypossible in defined ranges.These partial ranges must be selected asmeasurement ranges in the configuration.

    Example:Measurement ranges forsulphuric acid

    Configuration

  • 8/9/2019 2402 condi

    21/65

    40 Stratos e 2402 CondI

    ConfigurationOutput 1Output current range. LIN/LOG curveLIN curve: Current beginning / end

    End:Pressconf, then enter

    Code

    Output 1 o1.

    DisplayMenu group Select menu item

    Sensor selection

    Select measured variable

    Select 0-20 / 4-20 mA

    Enter current beginning

    Enter current end

    Set output filter22 mA in the case of error

    Hold mode

    Characteristic: LIN / LOG

    Select solution (Conc)

    41

    Code

    LIN(LIN / LOG)

    Display Action Choices

    o1.

    Select output characteristicSelect with keyProceed with enter(Step omitted for % (Conc) and SAL))

    000.0 mS(xxx.x mS)

    100.0 mS(xxx.x mS)

    Conductivity

    [mS/cm]

    204

    200

    0

    Assignment of measured values:Current beginning and current end

    [mS/cm]

    204

    200

    100[mA]

    Example 1: Range 0...200 mS/cm Example 2: Range 100...200 mS/cmAdvantage: Higher resolution in range ofinterest

    [mA]

    Output current

    Conductivity

    4-20 mA(0 - 20 mA4 - 20 mA)

    Set output current range

    Select with keyProceed with enter

    With LIN selected: Enter current beginning

    Enter lower end of scale

    Select with key,

    edit number with key,proceed with enter

    Enter current endEnter upper end of scaleProceed with enter

    Output current

    Configuration

  • 8/9/2019 2402 condi

    22/65

    42 Stratos e 2402 CondI

    ConfigurationOutput 1Output current range. LOG curveCurrent beginning / end

    End:Pressconf, then enter

    Code

    Output 1 o1.

    DisplayMenu group Select menu item

    Sensor selection

    Select measured variable

    Select 0-20 / 4-20 mA

    Enter current beginning

    Enter current end

    Set output filter22 mA in the case of error

    Hold mode

    Characteristic: LOG

    Select solution (Conc)

    43

    Code Display Action Choices

    o1. With LOG selected: Enter current beginning

    Enter lower end of scale

    Select with key,

    edit number with key,proceed with enter key.

    0.1 mS(0.001 mS0.01 mS1.0 mS

    10 mS100 mS1000 mS)

    100 mS(0.001 mS0.01 mS1.0 mS10 mS100 mS1000 mS)

    Enter current endEnter upper end of scale

    Select with key,edit number with key.

    Proceed with enter

    Example: Measurement range over 3 decades

    Selection: 0-20/4-20mA Current beginning: 4 mA Current end: 20 mA

    Characteristic: LOG 4 mA 0.1 mS/cm

    20 mA 100 mS/cm

    [mA]

    100

    4.0

    Output current

    Y

    X

    Conductivity[mS/cm]

    20.09.3 14.7

    1

    10

    0.1

    Configuration

  • 8/9/2019 2402 condi

    23/65

    Stratos e 2402 CondI44

    ConfigurationOutput 1Time constant of output filter

    End:Pressconf, then enter

    Code

    Output 1 o1.

    DisplayMenu group Select menu i tem

    Sensor selection

    Select measured variable

    Select 0-20 / 4-20 mA

    Enter current beginning

    Enter current end

    Set output filt er

    22 mA in the case of error

    Hold mode

    Characteristic: LIN / LOG

    Select solution (Conc)

    45

    0 s

    0 ... 120 s

    Code Display Action Choices

    o1. Time constant of output filterDefault setting: 0 s (inactive).To specify a time constant:

    Select with key,

    edit number with key,proceed with enter key.

    Time constant of output filter (attenuation)To smoothen the current output, a low-pass fil ter withadjustable filter time constant can be switched on. When thereis a jump at the input (100 %), the output level is 63 % afterthe time constant has been reached.

    The time constant can be set from 0 to 120 s.If the time constant is set to 0 s, the current output follows theinput.Note:The filter only acts on the current output, not on the display, thelimit values, or the controller!

    Leitfhigkeit

    Time constant 0 to 120 s

    Conductivity

    Configuration

  • 8/9/2019 2402 condi

    24/65

    Stratos e 2402 CondI46

    ConfigurationOutput 1Output current during Error and HOLD.

    End:Pressconf, then enter

    Code

    Output 1 o1.

    DisplayMenu group Select menu item

    Sensor selection

    Select measured variable

    Select 0-20 / 4-20 mA

    Enter current beginning

    Enter current end

    Set output filter

    22 mA in the case of error

    Hold mode

    Characteristic: LIN / LOG

    Select solution (Conc)

    47

    OFF

    (OFFON)

    Code Display Action Choices

    o1. 22 mA signal for error messageSelect with keyProceed with enter

    LAST(LASTFIX)

    Only with FIX selected:

    Enter current which is to flow atthe output during HOLD

    Select position with key,

    edit number with key,proceed with enter key.

    021.0 mA(00.0 ...

    21.0 mA

    Output signal f or HOLD:

    Output current[mA]

    Output signal HOLDSetting FIX = 21.0 mA

    HOLD active

    21

    4

    Output signal HOLDSetting LAST

    HOLD active

    Output signal during HOLDLAST: During HOLD the lastmeasured value is maintained atthe outputFIX: During HOLD a value (to beentered) is maintained at theoutput

    Select with key.Proceed with enter

    Configuration

  • 8/9/2019 2402 condi

    25/65

    Stratos e 2402 CondI48

    ConfigurationOutput 2Temperature unit and output current.

    Select C/F

    Select 0-20 / 4-20 mA

    Enter current beginning

    Enter current end

    Set output filter

    22 mA for temp error

    Hold mode

    End:Pressconf, then enter

    Code DisplayMenu group Select menu i tem

    Output 2 o2.

    49

    C(CF)

    Code Display Action Choices

    o2. Specify temperature unitSelect with keyProceed with enter

    4-20 mA(4 - 20 mA0 - 20 mA)

    Set output current rangeSelect with keyProceed with enter

    Current beginning: Enter lowerend of scale.

    Select with , edit number with

    , proceed with enter.

    000 .0 C(xxx.x C)

    Current end: Enter upper end ofscale.

    Select with , edit number with

    , proceed with enter.

    100 .0 C(xxx.x C)

    Output current

    Process temperature

    204

    100

    0

    Process temperature: Current beginning and current end

    Process temperature

    204

    70

    50[mA]

    Example 1: Range 0 to 100 C Example 2: Range 50 to 70 C.Advantage: Higher resolution inrange of interest[C]

    [C]

    [mA]

    Output current

    Configuration

  • 8/9/2019 2402 condi

    26/65

    Stratos e 2402 CondI50

    Co gu at oOutput 2Time constant of output filter.

    End:Pressconf, then enter

    Output 2 o2.

    Code DisplayMenu group Select menu item

    Select C/F

    Select 0-20 / 4-20 mA

    Enter current beginning

    Enter current end

    Set output filt er

    22 mA for temp error

    Hold mode

    51

    0 s

    (0 - 120 s)

    Code Display Action Choices

    o2. Time constant of output filterDefault setting: 0 s (inactive).To specify a time constant:

    Select with key,

    edit number with key,proceed with enter key.

    Time constant of output filter (attenuation)To smoothen the current output 2, a low-pass filter withadjustable filter time constant can be switched on. When thereis a jump at the input (100 %), the output level is 63 % afterthe time constant has been reached.

    The time constant can be set from 0 to 120 s.If the time constant is set to 0 s (default), the current outputfollows the input.Note:The filter only acts on the current output, not on the display!

    Leitfhigkeit

    Time constant 0 to 120 s

    Conductivity

    Configuration

  • 8/9/2019 2402 condi

    27/65

    Stratos e 2402 CondI52

    gOutput 2Temperature error. Output current during HOLD.

    End:Pressconf, then enter

    Output 2 o2.

    Code DisplayMenu group Select menu item

    Select C/F

    Select 0-20 / 4-20 mA

    Enter current beginning

    Enter current end

    Set output filter

    22 mA for temp error

    Hold mode

    53

    OFF(ON)

    Code Display Action Choices

    o2. 22 mA signal for error messageSelect with arrow keyProceed with enter

    Output signal during HOLDLAST: During HOLD the lastmeasured value is maintained atthe outputFIX: During HOLD a value (to beentered) is maintained at theoutput

    Select with arrow key.Proceed with enter

    LAST(FIX)

    Only with FIX selected:Enter current which is to flow atthe output during HOLD

    Select position with key,

    edit number with key,proceed with enter key.

    21.0 mA(00.0 ...

    21.0 mA

    Output signal during HOLD:

    Output current[mA]

    Output signal HOLDSetting FIX = 21.0 mA

    HOLD active

    21

    4

    Output signal HOLDSetting LAST

    HOLD acti ve

    Configuration

  • 8/9/2019 2402 condi

    28/65

    Stratos e 2402 CondI54

    gTemperature compensationSelect temperature compensation

    Selecttemperature compensation

    End:Pressconf, then enter

    Temperature

    compensationtc.

    Code DisplayMenu group Select menu item

    55

    OFF

    (OFFLINnLF)

    Code Display Action Choices

    tc.

    Only with manual temp detec-tion selected (MAN)Enter temperature.Select position with arrow keyand edit number with key.Proceed with enter

    Only with linear temperaturecompensation (LIN) selected:Enter temperature coefficient.

    Select position with key,edit number with key,proceed with enter key.

    02.00%/K(xx.xx%/K)

    Temperature compensationselection (not for SAL, CONC)

    OFF: Temperature compensa-tion switched off

    Select with key,proceed with enterLIN:Linear temperature compensa-tion with entry of temperaturecoefficient and reference tem-peratureNLF:Temperature compensation fornatural waters toEN 27888

    Configuration

  • 8/9/2019 2402 condi

    29/65

    Stratos e 2402 CondI56

    Alarm sett ings

    Select Sensocheck

    Delay

    LED in HOLD mode

    Code DisplayMenu group Select menu i tem

    Alarm

    settingsAL.

    End:Pressconf, then enter

    15

    16

    Alarm Alarm contact

    The alarm contact is closed during normal operation(N/C). It opens in the case of alarm or power outage.As a result, a failure message is provided even in thecase of line breakage (fail-safe behavior). For contact rat-ings, see Specifications.

    Error messages can also be signaled by a 22 mA outputcurrent ( see Pg 47,

    The operating behavior of the alarm contact is shown onPg 94.

    The alarm delay acts on the LED, the 22 mA signaland the alarm contact.

    53, 92).

    57

    Code Display Action Choices

    OFF(ON / OFF)

    AL. Select Sensocheck(Continuous monitoring ofsensor properties)

    Select with , proceed with

    enter

    Alarm delay

    Select with , edit number

    with , proceed with enter.

    0010 s

    (xxxx s)

    LED in HOLD modeSelect with , proceed withenter

    OFF(ON / OFF)

    Configurat ion Alarm HOLD

    ON on flashes

    OFF f lashes of f

    LED state:

    Configuration

  • 8/9/2019 2402 condi

    30/65

    Stratos e 2402 CondI58

    Limit functionRelay 1

    Contact function

    Contact response

    Enter swit ching point

    Enter hysteresis

    Delay

    Relay 2 menu group

    Controller menu group

    L1.

    L2.

    Ct.

    Relay / Controller rL.

    Code DisplayMenu group Select menu i tem

    End:Pressconf, then enter

    59

    LiMIT(LiMitCtROL)

    Code Display Action Choices

    rL. Use of relays: Limit function (LiMIT) Controller (CtROL)

    Select with .

    Proceed with enterNote:Selecting CtROL leads toController menu group Ct.

    Lo(Lo/Hi)

    Limit 1 function , see Pg 61.

    Select with .Proceed with enter

    Limit 1 contact responseN/O: normally open contact

    N/C: normally closed contactSelect with .Proceed with enter

    N/O(NON/C)

    Limit 1 switching point

    Select with , edit number

    with , proceed with enter.

    000.0 mS(xxxx)

    Limit 1 hysteresis

    Select with , edit number

    with , proceed with enter.

    001.0 mS(xxxx)

    Limit 1 delayThe contact is activated withdelay (deactivated withoutdelay)

    Select with , edit number

    with , proceed with enter.

    0010 s(0 ...9999 s)

    L1.

    Configuration

  • 8/9/2019 2402 condi

    31/65

    Stratos e 2402 CondI60

    Limit functionRelay 2

    Relay 1 menu group

    Contact function

    Contact response

    Enter switching point

    Enter hysteresis

    Delay

    Controller menu group

    L1.

    L2.

    Ct.

    Relay / Controller rL.

    Code DisplayMenu group Select menu i tem

    End:Pressconf, then enter

    61

    Code Display Action Choices

    L2. Hi(Lo/Hi)

    Select Limit 2, see Fig. below.

    Select with .Proceed with enter

    Limit 2 contact responseN/O: normally open contactN/C: normally closed contact

    Select with .Proceed with enter

    N/O(N/ON/C)

    Limit 2 switching point

    Select with , edit number with

    , proceed with enter.

    100.0 mS(xx.xx mS)

    Limit 2 hysteresis

    Select with , edit number with, proceed with enter.

    001.0 mS(xx.xx mS)

    Limit 2 delayThe contact is activated withdelay (deactivated withoutdelay)

    Select with , edit number with, proceed with enter.

    0010 s(0 ...9999 s)

    Limit Lo

    Hysteresis+

    Switchingpoint

    Contact

    0

    1

    Signal

    Limit Hi

    Hysteresis-

    Signal

    Switchingpoint

    Contact

    0

    1

    ConfigurationC t ll (f d i ti P 88 d th f ll i )

  • 8/9/2019 2402 condi

    32/65

    Stratos e 2402 CondI62

    Controller (for description see Pg 88 and the follow ing)Setpoint. Neutral zone.

    Relay 1 menu group

    Relay 2 menu group

    Controller setpoint

    Enter neutral zone

    (P) Controller gain

    (I) Reset time TR

    (D) Rate time TD

    Pulse length/Pulse frequency

    PLC: Pulse length

    PFC: Pulse frequency

    HOLD behavior

    L1.

    L2.

    Ct.

    Relay / Controller rL.

    Code DisplayMenu group Select menu item

    End:Pressconf, then enter

    63

    001.0 mS

    (xxx.x mS)

    050.0 mS(xxx.x mS)

    Setpoint

    Select with , edit number with, proceed with enter.

    Neutral zone (dead band)

    Select with , edit number with, proceed with enter.

    Controller: P action

    Select with , edit number with

    , proceed with enter.

    Code Display Action Choices

    Ct.

    0100 %(xxxx %)

    Controller: I action (reset time)

    Select with , edit number with

    , proceed with enter.

    0000 s(xxxx s)

    Controller: D action (rate time)Select with , edit number with

    , proceed with enter.

    0000 s(xxxx s)

    Pulse length /Pulse frequency

    Select with .Proceed with enter

    PLCPLC/(PFC)

    PLC: Pulse length

    Select with , edit number with, proceed with enter.

    0010 s(xxxx s)

    PFC: Pulse frequencySelect with , edit number with

    , proceed with enter.

    0060 /min(xxxx /min)

    Behavior during HOLD

    Select with .Proceed with enter.

    Y Last(YOff/Y Last)

    KonfigurationControlling a rinsing probe or

  • 8/9/2019 2402 condi

    33/65

    64

    Controlling a rinsing probe orsignaling parameter set 2

    Select CLEAN/ PSEt2

    Rinsing int erval

    Rinse duration

    Cont act response

    Contact:CLEAN / PSEt2

    Cln

    Code DisplayMenu group Select menu item

    Code Display Action (Rinsing probe) Choices

    Cn. Control* of : Rinsing probe (rinse) Signaling parameter set 1/2

    Select with .Proceed with enter

    000.0 h(xxx.x h)

    Rinsing interval*

    Select with , edit number

    with , proceed with enter.

    Rinse duration*

    Select with , edit numberwith , proceed with enter.

    0060 s(xxxx s)

    Contact response*N/O: normally open contactN/C: normally closed contact

    Select with .Proceed with enter

    N/O(N/ON/C)

    rinse

    rinse

    (rinse / PSEt2)For PSEt2,

    see next page

    * These parameters are only edited in parameter set 1.They are valid for both parameter sets. 65

    Signaling parameter set 2

    17

    18

    CleanPSet2

    Process control system(PCS)

    Parameter set 1 selected

    Parameter set 2 selected

    Power supply

    Stratos e 2402

    Power supply:AC< 250 V / < 3 A / < 750 VADC< 30 V / < 3 A / < 90 W

    17

    18

    Clean

    e.g. rinse cleaning

    Power supply

    Controlling a rinsing probeThe Clean contact can be used to connect a simple rinsing probe.Rinse duration and rinsing interval are defined during configuration.Contact response can be set as N/O, N/C.

    Depending on the selected parameter set, the relay

    is active or inactive. The signal can be used forsuperordinated process control systems.Parameter set 2 is indicated by 88 in the upperleft corner of the display.

    Select ing paramet er set (1/2)M anually or via a signal at the Control input

  • 8/9/2019 2402 condi

    34/65

    Stratos e 2402 CondI66

    M anually or via a signal at the Control input

    Display Action Choices

    Select: Parameter set 1 (MAN) Parameter set 2 (MAN) Automatic switchover via

    Control input (Ctr-EXT)

    Select with , proceed with enter

    Select parameter setPress conf , enter code 7654

    Select with , edit number with ,proceed with enter.

    Wrong settings change the measure-ment properties!If an invalid code is entered, theStratos returns to measuring mode.

    With -1- or -2- selected:Since the complete device configurationis changed in one step, there is a secu-rity prompt (No/Yes).

    Note:

    When pressing enter directly, theselection is not stored.

    Activation of parameter set 2 is indi-cated by 88 in the upper left cornerof the display.

    After correct input a welcome

    text (CONF) isdisplayed forapprox. 3 s

    -1-(-1- MAN-2-MANCtr-EXT)

    Ctr-EXT:

    see nextpage

    67

    With Control input Ctr-EXT selected:You can switch between the parame-ter sets by applying an external signalto the Control input:

    Display Action Choices

    External sw itchover of parameter sets

    The parameter set can be selected from outside by sending asignal to the Control input (e.g. from the process control sys-tem). To do so, the Control input is set to Ctr-EXT during config-uration.

    Note:

    Parameter set 2 is indicated by 88 in the upper left corner of t hedisplay.

    7

    8

    Control

    input

    0 ... 2 V AC/DC Parameter set 1 selected

    10 ... 30 V AC/DC Parameter set 2 selected

    Stratos e 2402 Process control system (PCS)

    Power supply12...24 V AC/DC

  • 8/9/2019 2402 condi

    35/65

    68 Stratos e 2402 CondI 69

    Two complete parameter sets are stored in the EEPROM.As delivered, the two sets are identical but can be edited.Note:

    Fill in your configuration data on the following pages.

    Code. Parameter Default set t ing

    o1. Sensor selection * SE655o1. Process variable 000.0 mSo1. Conc solut ion -01-o1. 0/4-20 mA 4-20 mAo1. Characteristic LINo1. Current start (LIN) 000.0 mSo1. Current end (LIN) 100.0 mS

    o1. Current start (LOG) 0.1 mSo1. Current end (LOG) 100 mSo1. Filter time 0 so1. 22mA signal OFFo1. Hold behavior Lasto1. Fix current 021.0 mAo2. Unit C / F Co2. 0/4...20mA 4-20 mAo2. Current start 000.0 Co2. Current end 100.0 Co2. Filter time 0 so2. 22mA signal OFFo2. Hold behavior Last

    o2. Fix current 021.0 mAtc. Temp compensation OFFtc. Temp coefficient 02.00%/K

    Code. Parameter Default set t ing

    AL. Sensocheck OFFAL. Alarm delay 0010 sAL. LED Hold OFFrL. Relay function LimitL1. Contact function LoL1. Contact response N/OL1. Switching point 000.0 mS

    L1. Hysteresis 001.0 mSL1. Delay 0010 sL2. Contact function HiL2. Contact response N/OL2. Switching point 100.0 mSL2. Hysteresis 001.0 mSL2. Delay 0010 sCt. Setpoint 050.0 mSCt. Neutral zone 001.0 mSCt. Paction 0100 %Ct. I action 0000 sCt. D action 0000 sCt. PLC/PFC controller PLC

    Ct. Pulse length 0010 sCt. Pulse frequency 0060 /minCt. Hold behavior LastCn. Rinse/Pset2 * rinseCn. Rinsing interval * 000.0 hCn. Rinse duration * 0060 sCn. Contact response* N/O

    Default settings of parameter sets

    * These parameters are only edited in parameter set 1.They are valid for both parameter sets.

    Parameter set - user settings

  • 8/9/2019 2402 condi

    36/65

    Stratos e 2402 CondI70

    Code. Parameter Sett ing

    P1 (conf 1200) P2 (conf 1288)

    o1. Sensor selection ____________ *

    o1. Process variable ____________ ____________

    o1. Solut ion (Conc) ____________ ____________

    o1. 0/4-20 mA ____________ ____________

    o1. Characteristic (LIN/LOG) ____________ ____________

    o1. Current start ____________ ____________

    o1. Current end ____________ ____________

    o1. Filter time ____________ ____________

    o1. 22mA signal ____________ ____________

    o1. Hold behavior ____________ ____________

    o1. Fix current ____________ ____________

    o2. Unit C / F ____________ ____________

    o2. 0/4...20mA ____________ ____________

    o2. Current start ____________ ____________

    o2. Current end ____________ ____________

    o2. Filter time ____________ ____________

    o2. 22mA signal ____________ ____________

    o2. Hold behavior ____________ ____________

    o2. Fix current ____________ ____________

    tc. Temp compensation ____________ ____________

    tc. Temp coefficient ____________ ____________AL. Sensocheck ____________ ____________

    AL. Alarm delay ____________ ____________

    AL. LED Hold ____________ ____________

    71

    Code. Parameter Sett ingP1 (conf 1200) P2 (conf 1288)

    rL. Relay funct ion ____________ ____________

    L1. Contact function ____________ ____________

    L1. Contact response ____________ ____________

    L1. Switching point ____________ ____________

    L1. Hysteresis ____________ ____________

    L1. Delay ____________ ____________

    L2. Contact function ____________ ____________

    L2. Contact response ____________ ____________

    L2. Switching point ____________ ____________

    L2. Hysteresis ____________ ____________

    L2. Delay ____________ ____________

    Ct. Setpoint ____________ ____________

    Ct. Neutral zone ____________ ____________

    Ct. P action ____________ ____________

    Ct. I action ____________ ____________

    Ct. D action ____________ ____________

    Ct. PLC/PFC controller ____________ ____________

    Ct. Pulse length ____________ ____________

    Ct. Pulse frequency ____________ ____________

    Ct. Hold behavior ____________ ____________

    Cn. Rinse/ PSet2 ____________ *Cn. Rinsing interval ____________ *

    Cn. Rinse duration ____________ *

    Cn. Contact response ____________ *

    * These parameters are only edited in parameter set 1.They are valid for both parameter sets.

    CalibrationCalibration adjusts the device to the sensor

  • 8/9/2019 2402 condi

    37/65

    Stratos e 2402 CondI72

    Calibration adjusts the device to the sensor.

    Activate with cal

    Enter mode code: Entry of cell factor 1100 With calibration solution 0110 Product calibration 1105 Zero point 1001

    Temp probe adjustment 1015Select with , edit number with ,proceed with enter.(End with cal + enter.)

    Output current is frozen (last valueor preset fixed value, depending onconfiguration), limit and alarm con-tacts are inactive. The controller isin the configured state, Sensofaceis off, Calibration mode indicatoris on.

    Activate

    Hold

    Input errors The calibration parameters arechecked during the input. In thecase of an incorrect input Err isdisplayed for approx. 3 s. Theincorrect parameters cannot bestored. Input must be repeated.

    End End with cal.

    The measured value and Hold aredisplayed alternately, enter flashes.Pressenter to end the Hold mode.The measured value is displayed.The output current remains frozenfor another 20 s (HOLD icon on, hourglass flashes).

    HOLD icon

    During calibra-tion the Stratosremains in the

    Hold mode forreasons of safe-

    ty.

    73

    Informat ion on calibrationCalibration can be performed by: Entry of cell factor Determining the cell factor with a known calibration

    solution taking account of the temperature Product calibration

    Zero calibration in air or with calibration solution Temperature probe adjustment

    Note:If measurements are taken in containers withA < 110 mm, be sure to choose the samedistance and the same container material(metal/plastic) for calibration.

    Caution All calibration procedures must be performed by trained per-

    sonnel. Incorrectly set parameters may go unnot iced, butchange the measuring properties.

    When another sensor is used, its sensor data (cell factor,transfer ratio, measuring frequency, t emperature probe) must

    be entered in the configuration menu before calibration. Each time a new sensor is connected, the Stratos must becalibrated.

    Calibration by input of cell factor

  • 8/9/2019 2402 condi

    38/65

    74 Stratos e 2402 CondI

    Display Action Remark

    Enter cell factor:Select with , edit number

    with , proceed with enter.Conductivity and temperatureare alternately displayedduring the input(lower display).Confirm entry with enter.

    Press cal key.Enter code 1100

    Select with , edit number

    with , proceed with enter.

    Ready for calibration

    Dismount and clean sensor

    If an invalid code isentered, the Stratosreturns to measur-ing mode.

    The entered cell factor andzero point are displayed.Confirm with enter.

    Display (3 s)Stratos in Holdmode, measuredvalue frozen.

    Sensoface inactive.

    Input of cell factor with simultaneous display of conductivity andtemperature (without temperature compensation)

    75

    Display Act ion Remark

    Conductivity and temperatureare displayed.

    The measured value is shown

    in the main display alternatelywith Hold ; enter flashes.End with enter.Press enter to end calibra-tion.

    After end of cali-bration, the out-puts remain inHold mode for

    approx. 20 sec.

    Calibration w ith calibration solution

  • 8/9/2019 2402 condi

    39/65

    Stratos e 2402 CondI76

    Display Action Remark

    Press cal key.Enter code 0110.

    Select with , edit number

    with , proceed with enter.

    Ready for calibration

    Dismount and clean sensor

    If an invalid code isentered, the Stratosreturns to measur-ing mode.

    Display (3 s)Stratos in Holdmode, measuredvalue frozen.

    Sensoface inactive.

    Be sure to use known calibration solutions and the respective tempera-ture-corrected conductivity values (see Calibration solutions Pg 112).During the calibration procedure the temperature should be kept con-stant.

    Immerse sensor in calibrationsolution.Enter the temperature-corrected conductivity valueof the calibration solution:

    Select with , edit numberwith , proceed with enter.

    Cell factor and temperatureare alternately displayed in thelower display.Confirm entry with enter.

    When there hasnot been an entryfor 6 sec, thelower display alter-nately shows the

    conductivity andtemperature value.

    77

    Display Act ion Remark

    The determined cell factor andzero point are displayed.Confirm cell factor with

    enter.

    Conductivity and temperatureare displayed.The measured value is shownin the main display alternatelywith Hold ; enter flashes.End with enter.Press enter to end calibra-tion.

    After end of cali-bration, the out-puts remain inHold mode forapprox. 20 sec.

    Product calibrat ionCalibration by sampling

  • 8/9/2019 2402 condi

    40/65

    78 Stratos e 2402 CondI

    The measurement process is only interrupted briefly. Duringproduct calibration the sensor remains in the process.Calibration is without TC correction!

    Procedure: During sampling the currently measured value isstored in the Stratos. The Stratos immediately returns to meas-uring mode. The calibration mode indicator flashes andreminds you that calibration has not been terminated. Thesample is measured in the lab or directly on the site using aportable meter. The measured sample value is then entered inthe Stratos. The new cell factor is calculated from these twovalues.If the sample is invalid, you can take over the value stored dur-ing sampling. In that case the old calibration values are stored.Afterwards, you can start a new product calibration.

    Display Action Remark

    Product calibration step 1:Press cal key.Enter code 1105.

    (Select position with key,edit number with key,proceed with enter key. )

    Take sample and store value.Proceed with enter

    If an invalid code isentered, the Stratosreturns to measur-ing mode.

    Now the samplecan be measuredin the lab.

    Display(approx. 3 sec)

    79

    Display Act ion Remark

    Measuring mode:

    From the flashing CAL modeindicator you see that samplecalibration has not been ter-minated.

    Product calibration step 2:When the sample value hasbeen determined, call up theproduct calibration once more(cal, code 1105).

    Display(approx. 3 sec)

    Enter sample value. The newcell factor is calculated.

    Confirm with enter.

    While the samplevalue is deter-mined, the Stratosis in measuring

    mode.

    The new cell factor and zeropoint are displayed.Confirm with enter.

    The measured value is shown

    in the main display alternatelywith Hold ; enter flashes.End with enter.

    After end of cali-

    bration, the out-puts remain inHold mode forapprox. 20 sec.

    New calibration:Press cal.

    Zero calibration in air

  • 8/9/2019 2402 condi

    41/65

    80 Stratos e 2402 CondI

    Display Action Remark

    When there has notbeen an entry for6 sec, the lower

    display alternatelyshows the conduc-tivity and tempera-ture value.

    Press cal key,enter code 1001

    Select position with key,

    edit number with key,

    proceed with enter key.

    Modify the zero point untilzero is displayed as conductiv-ity value in the lower display.

    Select with .

    Edit number with .

    If required, change the sign ofthe zero point.

    Press enter to confirm thezero point.

    Stratos is in theHold mode.If an invalid code isentered, Stratos

    returns to measur-ing mode.

    Ready for calibration

    Dismount and clean sensor.(Sensor must be dry!)

    Display (3 s)

    81

    Display Action Remark

    The cell factor and zero pointare displayed.Press enter to confirm thecalibration data.

    Conductivity and temperatureare displayed.

    Place sensor in process.

    End calibration with

    enter.

    After end of calibra-tion, the outputsremain in Holdmode for approx.

    20 sec.

    Zero calibration with calibration solution

    Calibration solution w ith low conductivity

  • 8/9/2019 2402 condi

    42/65

    82 Stratos e 2402 CondI

    Display Action Remark

    When there has not

    been an entry for6 sec, the lowerdisplay alternatelyshows the conduc-tivity and tempera-ture value.

    Calibration solution w ith low conductivity

    Press cal key,enter code 1001

    Select position with key,

    edit number with key,proceed with enter key.

    Immerse sensor in calibration

    solution.Modify the value until thelower display shows the con-ductivity value of the calibra-tion solution.Press enter to confirm cali-bration

    Stratos is in theHold mode.If an invalid code isentered, Stratosreturns to measur-ing mode.

    Ready for calibration

    Dismount and clean sensor

    Display (3 s)

    The cell factor and zero pointare displayed.

    Press enter to confirm thecalibration data.

    83

    Display Act ion Remark

    Conductivity and temperatureare displayed.Remove the sensor from the

    calibration solution and cleanit.Place sensor in process.

    The measured value is shownin the main display alternatelywith Hold ; enter flashes.End with enter.End calibration with

    enter.

    After end of calibra-tion, the outputsremain in Holdmode for approx.20 sec.

    Temperature probe adjustm ent Diagnostics functions

  • 8/9/2019 2402 condi

    43/65

    Stratos e 2402 CondI84

    Display Action Remark

    Measure the temperature ofthe process medium using anexternal thermometer. Entermeasured temperature value:

    Select with , edit number

    with , proceed with enter.End adjustment with enter.HOLD will be deactivatedafter 20 sec.

    Activate calibration(Press cal,enter 1015)

    Select position with key,

    edit number with key,proceed with enter key.

    Ready for calibration

    Wrong settingschange the meas-urement properties!If an invalid code is

    entered, the Stratosreturns to measur-ing mode.

    Default:Current value ofsecondary display.

    Display (approx. 3 sec)Stratos is in the Holdmode.

    Display Remark

    Measurement

    In the measuring mode the main display shows theconfigured process variable (conductivity [mS/cm,S/m] or resistivity [Mcm] or concentration [% bywt] or salinity [SAL]) and the lower display the tem-perature. During calibration you can return to meas-uring mode by pressing the cal key, during configu-ration by pressing conf .

    85

    Display of output currentsPress enter while in measuring mode.The current at output 1 is shown in the main dis-play, the current at output 2 in the secondary dis-

    play.After 5 sec the Stratos returns to measuring mode.

    Display Remark

    Sensor monitor for validationof sensor and complete measured-value processing.Loop a defined sensing resistor (e.g. R = 100 )

    through the sensor as shown in the figure.Press the conf key and enter code 2222.The sensor monitor displays the directly measuredresistance and the temperature.If t here is a signif icant dif ference between resistorvalue and display, the sensor and its transmissionbehavior should be checked.Press enter to return to measurement.Note:The Stratos does not automatically go to Holdmode.

    Display of last error message(Error Inf o)Press conf while in measuring mode and confirmcode 0000. The last error message is displayed forapprox. 20 sec. After that the message will bedeleted. (immediate return to measurement atpressing enter).

    Display of calibration data (Cal Info)Press cal while in measuring mode and confirmcode 0000. The current cell constant is shown inthe main display. After 20 sec the Stratos returns tomeasuring mode (immediate return at pressing

    enter).

    Diagnostics functionsThese functions are used for testing the connected peripherals.

  • 8/9/2019 2402 condi

    44/65

    Stratos e 2402 CondI86

    Relay t est ( manual test of contacts) Pressconf , enter code 5557The relays are frozen. This state is indicated in thedisplay. The 4 digits in the display correspond to the4 relays (as on terminal plate):1st digit: R1

    2nd digit: R23rd digit: AL4th digit: CLNFunction test using arrow keys see left column.When exiting the function (enter), the relays are setcorresponding to the measured value.

    Select arelay

    Specify current for output 1(current source 1) Pressconf , enter code 5555The current indicated in the main display for output1 can be edited.

    Select with key, edit number with key,proceed with enter key.The actually measured current is shown in the sec-ondary display. The Stratos is in Hold mode.Press enter to return to measurement(Hold remains active for another 20 sec).

    Display Action / Remarks

    Specify current at output 2(current source 2) Pressconf , enter code 5556The current indicated in the main display for output2 can be edited.

    Select with key, edit number with key, proceedwith enter. The actually measured current is shownin the secondary display. The Stratos is in Hold mode.Press enter to return to measurement.

    Test 0/1

    Return tomeasurement

    87

    The arrows indi-cate which relay(valve) is active:

    Controllercharacteristic

    +100 %

    -100 %

    Relay 2 active(Meas. value >setpoint)

    Relay 1 active(Meas. value 45 Sensor connection or cable defective

    Errors DisplayProblem

    Possib le causes

    ERR 01 Measuredvalue

    flashes

    xxx

    Unsuitable sensor Conductance range > 3000 mS

    ERR 02 Measuredvalueflashes

    xxx

    System errorConfiguration or calibration datadefective; completely reconfigureand recalibrate the device.Memory error in device program

    ERR 98 ConFflashes

    xxx x

    Factory sett ingsEEPROM or RAM defectiveThis error message only occurs inthe case of a complete defect.The Stratos must be repaired andrecalibrated at the factory.

    ERR 99 FAILflashes

    xxx x

    Temperat ure probeOpen or short circuitTemperature range exceeded

    ERR 03 xxx x

    93

    Sensocheck: Primary coil

    Secondary coil

    Alarmc

    ontac

    RedLED

    Out1(22mA

    Out2(22mA

    Current output 1Current below 0 (3.8) mA

    ErrorsSymbol(flashes)

    Problem

    Possib le causes

    ERR 11 xxx

    Current output 1Current above 20.5 mA

    ERR 12 xxx

    Current output 1Current span too small / too large

    ERR 13 xxx

    Current output 2Current below 0 (3.8) mA

    ERR 21 xxx

    Current output 2Current above 20.5 mA

    ERR 22 xxx

    Current output 2Current span too small / too largeERR 23xxx

    ERR 33xxx

    ERR 34Sensoface activesee Pg 97

    Temperature outsideconversion tables(TC, conc, SAL)

    Sensoface activesee Pg 97

    Operating stat es

    t

  • 8/9/2019 2402 condi

    48/65

    Stratos e 2402 CondI

    Conf par set 2(conf) 1288

    Parameter set 1/2(conf) 7654

    94

    Alarmc

    ontact

    Cleaning

    contact

    LED

    TimeoutOperating

    state

    Measurement

    Rel.1/2

    Controller

    Rel.1/2

    Limitvalue

    Out2

    Out1

    Cal Info(cal) 0000

    20 s

    Error Info(conf) 0000

    20 s

    Calibration(cal) 1100

    Temp adjustment(cal) 1015

    Zero point(cal) 1001

    Calibration(cal) 0110

    Conf par set 1

    (conf) 1200

    Product cal 1(cal) 1105

    Product cal 2(cal) 1105

    20

    min

    20min

    20min

    95

    Sensor monitor(conf) 2222

    Current source 1(conf) 5555

    Current source 2(conf) 5556

    Relay test(conf) 5557

    Manual controller(conf) 5559

    Cleaningfunction

    HOLD input

    Alarmc

    ontact

    Cleaning

    contact

    LED

    TimeoutOperating

    state

    Rel.1/2

    Controller

    Rel.1/2

    Limitvalue

    Out2

    Out1

    Explanation: active

    as configured (Last/Fix or Last/Off)

    20min

    20min

    20min

    20min

    20min

    Sensoface

    The little smiley in the display (Sensoface) alerts to sensor

  • 8/9/2019 2402 condi

    49/65

    Stratos e 2402 CondI96

    SensocheckContinuously monitors the primary coil and its lines for shortcircuits and the secondary coil and its lines for open circuits.Critical values make the Sensoface sad and the correspondingicon flashes:

    The Sensocheck message is also output as error message Err 33.The alarm contact is active, the red LED is lighted, output cur-rent 1 is set to 22 mA (when configured correspondingly).Sensocheck can be switched off during configuration (thenSensoface is also disabled). Exception: After a calibration aSmiley is always displayed for confirmation.

    The little smiley in the display (Sensoface) alerts to sensorproblems (defective sensor, defective cable).The conditions for a friendly, neutral, or sad Sensoface aresummarized in the following chart. Additional icons refer tothe error cause.

    NoteThe worsening of a Sensoface criterion leads to the devaluationof the Sensoface indicator (Smiley becomes sad ). To reset theSensoface indicator, the defect must be remedied and theStratos be calibrated.

    97

    StatusDisplay Problem

    Sensor defect Short circuit in primary coilOpen circuit in secondary coil(see also Error messagesErr 33 and Err 34, Page 93).

    Temperature outside range for TC,conc, SAL

    Temperatureerror

    Appendix

    Product line and accessories

  • 8/9/2019 2402 condi

    50/65

    98 Stratos e 2402 CondI 99

    Product line and accessories

    Devices Order No.

    Strat os e 2402 CondI 2402 CondI

    M ountin g accessories

    Pipe-mount kit ZU 0274Panel-mount kit ZU 0275Protective hood ZU 0276

    SensorsSE 655 electrodeless conductivity sensor SE 655SE 656 electrodeless conductivity sensor SE 656

    For more information concerning our sensors and fittings product line pleaserefer to our Sensors, Fitt ings, Accessories catalog:Download at http://www.knick.deor request catalog:Phone: +49 (0)30 - 801 91 - 290Fax: +49 (0)30 - 801 91 - 200Mail: [email protected]

    Note:For special applications (chemical resistance, type of mounting), youcan also connect sensors from other manufacturers.Permissible ranges for the Stratos e 2402 CondI as well as terminalassignments and factory settings for these sensors are available onrequest.

    Conductivity input Input for electrodeless conductivity sensors:

    Specifications

    Sensor standardizati on

  • 8/9/2019 2402 condi

    51/65

    Stratos e 2402 CondI100

    y p p ySE 652, SE 654 X, SE 655, SE 656

    Display ranges Conductivity 0.000 ... 1999 mS/cm

    Concentration 0.00 ... 100.0 % by wt

    Salinity 0.0 ... 45 (0 ... 35 C)

    Measurement ranges Conductivi ty 0.000 . .. 9.999 mS/cm00.00 ... 99.99 mS/cm000.0 ... 999.9 mS/cm0000 ... 1999 mS/cm0.000 ... 9.999 S/m00.00 ... 99.99 S/m

    Concentration 00.00 ... 99.99 % by wt

    Salinity 0.0 ... 45 (0 ... 35 C)

    Response time (T90) Approx. 2/sec

    Measurement error1,2,3)

    < 1% meas.val. + 0.005 mS

    Temperat ure compensation*

    (Reference temp 25 C) (OFF) Without(Lin) Linear characteristic 00.00 ... 19.99 % /K(NLF) Natural waters to EN 27888 (0 ... 35C)

    Concentration determinationOperating modes: * )

    -01- NaCl 0 ... 26 % by wt (0 ... 60 C)-02- HCl 0 ... 18 % by wt (-20 ... 50 C)-03- NaOH 0 ... 14 % by wt (0 ... 100 C)-04- H2SO4 0 ... 30 % by wt (-17 ... 110 C)

    -05- HNO3 0 ... 30 % by wt (-20 ... 50 C)

    -06- H2SO4 92 ... 99 % by wt (-17 ... 115 C)-07- HCl 22 .. 39 % by wt (-20 ... 50 C)-08- HNO3 35 ... 96 % by wt (-20 ... 50 C)

    -09- H2SO4 32 ... 84 % by wt (-17 ... 115 C)

    -10- NaOH 18 ... 50 % by wt (0 ... 100 C)

    See graphs in the Appendix Pg 115 and follow ing

    101

    Operating modes Entry of cell factor with simultaneous displayof conductivity and temperature

    Input of onductivity of calibration solution withsimultaneous display of cell factor andtemperature

    Product calibration

    Zero point adjustment

    Temperature probe adjustment

    Adm. cell factor 00.100 ... 19.999

    Adm. t ransfer rat io 01.00 ... 199.99

    Adm. zero point deviation 0.5 mS/cm

    Sensor monitoring Monitoring of primary and wiringSensocheck for short circuit

    Monitoring of secondary and wiringfor open circuit

    Sensoface Provides information on the sensor condition(evaluation of zero point, Sensocheck)

    Sensor monitor Sensor monitor for validation of sensor andcomplete measured-value processing(Display: resistance / temperature)

    Temperat ure input * Pt100 / Pt1000 / NTC 100 kOhms2-wire connection, adjustable

    Ranges Pt100 / Pt1000: -20 .. +200 C(-4 ... +392 F)

    NTC100 kOhms -20 ... +130 C

    (-4 ... +266 F)Resolution 0.1 C / 1 F

    Measurement error1,2,3)

    0.5 K(

  • 8/9/2019 2402 condi

    52/65

    Stratos e 2402 CondI102

    Function Switches device to HOLD mode

    Switching voltage 0 ... 2 V (AC/DC) Hold inact ive10 ... 30 V (AC/DC) Hold active

    CONTROL input Galv. separated (OPTO coupler)Function Switch-over to second parameter set

    Switching voltage 0 ... 2 V (AC/DC) Parameter set 1

    10 ... 30 V (AC/DC) Parameter set 2

    Output 1 0/4 to 20 mA, max. 10 V, floating(galv. connected to output 2)

    Measured variable * Conductivity, concentration or salinity

    Characteristic Linear or logarithmic

    Overrange* 22 mA in the case of error messages

    Output filter * (attenuation) Low-pass, filter time constant 0 ... 120 s

    Measurement error 1) < 0.3 % current value + 0.05 mA

    Start /end of scale As desired within range

    Min. span LIN: 5 % of selected rangeLOG: 1 decade

    Output 2 0/4 ... 20 mA, max. 10 V, floating(galv. connected to output 1)

    Process variable Temperature

    Overrange * 22 mA in the case of temp error messages

    Output filter * Low-pass, filt er time constant 0 ... 120 s

    Meas. error 1) < 0.3 % current value + 0.05 mA

    Start/end of scale * -20 to +200 C / -4 ... +392 F

    Adm. span 20 ... 320 K (36 to 608 F)

    Alarm contact Relay contact, float ing

    Contact rat ings AC< 250 V / < 3 A / < 750 VADC< 30 V / < 3 A / < 90 W

    Contact response N/C (fail-safe type)Alarm delay 0000 ... 0600 s

    103

    (see PID process controller)

    Contacts R1, R2 floating but inter-connected

    Contact ratings * AC< 250 V / < 3 A / < 750 VADC< 30 V / < 3 A / < 90 W

    Contact response * N/O or N/C

    Delay * 0000 ... 9999 s

    Switching points

    *

    As desired within rangeHysteresis * 0 ... 50 % full scale

    PID process controller Output via relay contacts R1, R2(see limit values)

    Setpoint * As desired within range

    Neutral zone * As desired within range

    Proport ional action * Controller gain KC: 0010 ... 9999 %

    Integral action* Reset time TR: 0000 ... 9999 s

    (0000 s = no integral action)

    Derivative action * Rate time TD: 0000 ... 9999 s

    (0000 s = no derivative action)

    Controller type * Pulse length or pulse frequency controller

    Pulse period * 0001 ... 0600 s, min. ON time 0.5 s(pulse length controller)

    Max. pulse frequency * 0001 ... 0180 min-1

    (pulse f requency controller)

    Cleaning function / Parameter set 2 *

    Clean / PSet2 Relay contact, floating,for controlling a rinsing probe orsignaling that 2nd parameter set is active

    Contact ratings AC< 250 V / < 3 A / < 750 VADC< 30 V / < 3 A / < 90 W

    Contact response N/O when signaling parameter set 2N/O or N/C when used as cleaning contact *

    Rinsing interval * 000.0 ... 999.9 h(000.0 h = cleaning function switched off)

    Rinse duration * 0000 ... 1999 s

    Specifications

    Display LC display, 7-segment with icons Protection against Protective separation of all extra-low-voltage circuits againstelectrical shock mains by double insulation as per EN 61010 1

  • 8/9/2019 2402 condi

    53/65

    Stratos e 2402 CondI104

    Main display Character height 17 mm, unit symbols 10 mm

    Secondary display Character height 10 mm, unit symbols 7 mm

    Sensoface 3 status indicators (friendly, neutral, sad Sensoface)

    Mode indicators 5 status bars meas , cal, alarm , cleaning ,

    config

    18 further icons for configuration and messages

    Alarm indication Red LED in case of alarm or HOLD, user defined

    Keypad 5 keys: [cal] [conf] [ ] [ ] [enter]

    Service f unctions

    Current source Current specifiable for output 1 and 2 (00.00 to 22.00mA)

    Manual controller Controller output entered directly (start of control process)

    Device self-test Automatic memory test (RAM, FLASH, EEPROM)

    Display test Display of all segment s

    Last Error Display of last error occurred

    Sensor monitor Display of direct sensor signal (resistance/temperature)

    Relay test Manual cont rol of the four switching contacts

    Parameter sets * Two selectable parameter sets for differentprocess phasesSwitchover via CONTROL input or manuallySignaling via relay contact PSet2

    Data retention Parameters and calibration data > 10 years (EEPROM)

    105

    electrical shock mains by double insulation as per EN 61010-1

    Pow er supply 24 (-15%) to 230 V AC/DC (+10%); approx. 5 VA, 2.5 WAC: 45 to 65 Hz; Overvoltage category II, Class II

    Nominal operating conditionsAmbient temperature -20 to +55 CTransport/Storage temp -20 to +70 C

    Relative humidity 10 to 95 % not condensingPower supply 24 (-15%) to 230 V AC/DC (+10%)Frequency for AC 45 to 65 Hz

    EMC EN 61326Emitted interference Class B (residential environment)

    Class A for mains supply > 60 V DCImmunity tointerference Industrial environment

    Explosion prot ectionFM: NI Class I Div 2 Group A, B, C & D, T4 Ta = 55 C; Type 2

    NI Class I Zone 2 Group IIC, T4 Ta = 55C; Type 2

    CSA: Class I Div 2 Groups A, B, C and D, T4Ex nA IIC T4

    Enclosure molded enclosure made of PBT (polybutylene terephtalate)Color Bluish gray RAL 7031Assembly Wall mounting

    Pipe mounting: dia 40 to 60 mm, 30 to 45 mm Panel mounting, cutout to DIN 43 700

    Sealed against panelDimensions H 144 mm, B 144 mm, T 105 mmIngress protection IP 65 / NEMA 4XCable glands 3 breakthroughs for cable glands M20x1.5

    2 breakthroughs for NPT 1/2 orRigid Metallic Conduit

    Weight Approx. 1 kg

    * ) User-defined1) To IEC 746 Part 1, at nominal operati ng condit ions2) 1 count3) Plus sensor error

    Explosion protectionWarnings and notesto ensure safe operation

  • 8/9/2019 2402 condi

    54/65

    106 Stratos 2402 CondI 107

    Warning: Do not disconnect equipment unless power hasbeen switched off.

    Warning: Clean only with antistatic moistened cloth.Warning: Substitution of components may impair suitability

    for hazardous locations. The equipment shall be installed and protected from mechanical

    impact and ultraviolet (UV) sources. Clean only with a moistened antistatic cloth as potential

    electrostatic hazard may exist. Service equipment only withconductive clothing, footwear and personal grounding devicesto prevent electrostatic accumulation.

    Internal grounding provisions shall be provided for field wiring.Bonding between conduit shall be provided during installation,and all exposed non-current carrying metallic parts shall bebonded and grounded.

    Installation in a Class I, Division 2 or Class I, Zone 2 hazardous

    location shall be in accordance with the Canadian ElectricalCode (CEC Part 1) Section 18 Division 2 wiring methods.

    The equipment shall have a switch or circuit breaker in thebuilding installation (that is in close proximity to the equipment)that is marked as the disconnect switch.

    The enclosure Type 2 is only for indoor use. The mains supply voltage fluctuations should not exceed

    -15/+10 percent of the nominal supply voltage. Do not use the equipment in a manner not specified in this

    documentation.

    Caution: Use supply wires suitable for 30 C above ambientand rated at least 250 V.

    Caution: Use signal wires suitable for at least 250 V.

    SPECIAL INSTRUCTIONS FOR FIELD REPRESENTATIVESNone

  • 8/9/2019 2402 condi

    55/65

    108 Stratos 2402 CondI 109

  • 8/9/2019 2402 condi

    56/65

    110 Stratos 2402 CondI 111

    Calibration solutions

    Potassium chloride solutions (conductivity in mS/cm) Sodium chloride solutions (conductivity in mS/cm)

  • 8/9/2019 2402 condi

    57/65

    Stratos 2402 CondI112

    Tempera ture Concentration

    [C] 0.01 mol/l 0.1 mol/l 1 mol/l

    0510

    151617181920212223242526

    27282930313233343536

    0.7760.8961.020

    1.1471.1731.1991.2251.2511.2781.3051.3321.3591.3861.4131.441

    1.4681.4961.5241.5521.5811.6091.6381.6671.696

    7.158.229.33

    10.4810.7210.9511.1911.4311.6711.9112.1512.3912.6412.8813.13

    13.3713.6213.8714.1214.3714.6214.8815.1315.3915.64

    65.4174.1483.19

    92.5294.4196.3198.22100.14102.07104.00105.94107.89109.84111.80113.77

    115.74

    Data source: K. H. Hellwege (Editor), H. Landolt, R. Brnstein: Zahlenwerte undFunktionen ..., volume 2, part. volume 6

    113

    012

    3456789

    1011121314151617

    181920212223242526272829303132

    33343536

    134.5138.6142.7

    146.9151.2155.5159.9164.3168.8173.4177.9182.6187.2191.9196.7201.5206.3211.2

    216.1221.0226.0231.0236.1241.1246.2251.3256.5261.6266.9272.1277.4282.7288.0

    293.3298.7304.1309.5

    5.7865.9656.145

    6.3276.5106.6956.8817.0687.2577.4477.6387.8318.0258.2218.4188.6178.8169.018

    9.2219.4259.6319.838

    10.04710.25810.46910.68310.89811.11411.33211.55211.77311.99512.220

    12.44512.67312.90213.132

    0.6310.6510.671

    0.6920.7120.7330.7540.7750.7960.8180.8390.8610.8830.9050.9270.9500.9720.995

    1.0181.0411.0641.0871.1111.1351.1591.1831.2071.2321.2561.2811.3061.3311.357

    1.3821.4081.4341.460

    Temperat ure Concentrat ion

    [C] 0.01 mol/l * 0.1 mol/l * saturated **

    * Data source: Test solutions calculated according to DIN IEC 746-3* * Data source: K. H. Hellwege (Editor), H. Landolt, R. Brnstein:

    Zahlenwerte und Funktionen ..., volume 2, part. volume 6

  • 8/9/2019 2402 condi

    58/65

    -02- Hydrochloric acid solution HCl-07-

    -03- Sodium hydroxide solution NaOH-10-

  • 8/9/2019 2402 condi

    59/65

    Stratos e 2402 CondI116

    Conductivity in dependence on substance concentration and processtemperature for hydrochloric acid (HCl)Source: Haase/Sauermann/Dcker; Z. phys. Chem. New Edition, Vol. 47(1965)

    07

    -02- -07-

    Concentrat ion measurement not possible in this range.c [% by wt]

    117

    Conductivity in dependence on substance concentration andprocess temperature for sodium hydroxide solution (NaOH)

    -10-

    Concentration measurement not possible in this range.

    -03-

    c [% by wt]

    -10-

    -04- Sulfuric acid H2SO4-06-

    -05- Nitric acid HNO308

  • 8/9/2019 2402 condi

    60/65

    118 Stratos e 2402 CondI

    Conductivity in dependence on substance concentration and processtemperature for sulfuric acid (H2SO4)

    Source: Darling; Journal of Chemical and Engineering Data;Vol. 9 No. 3, July 1964

    -06--09-

    -04- -09- -06-

    Concentration measurement not possible in this range.

    c [% by wt]

    119

    Conductivity in dependence on substance concentration and processtemperature for nitric acid (HN03)

    Source: Haase/Sauermann/Dcker; Z. phys. Chem. New Edition, Vol. 46(1965)

    -08-

    -05- -08-

    Concentration measurement not possible in this range. c [% by wt]

    22 mA signal for error message . . . . . . . . . . . . . . . . . 47, 53Alarm settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

    Index

    Use of relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59Configuration: Output 1 . . . . . . . . . . . . . . . . . . . . . . . . . . 32

  • 8/9/2019 2402 condi

    61/65

    gAlarm contact . . . . . . . . . . . . . . . . . . . . . . . . . . .56, 102Alarm delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57Error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .92Operating states . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .94

    Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    Cal Info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

    Calibration by input of cell factor . . . . . . . . . . . . . . . . .74Calibration with calibration solution . . . . . . . . . . . . . . .76Product calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . .78Temperature probe adjustment . . . . . . . . . . . . . . . . . . .84Zero calibration in air . . . . . . . . . . . . . . . . . . . . . . . . . .80Zero calibration with calibration solution . . . . . . . . . . .82

    Calibration solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112Concentration curves . . . . . . . . . . . . . . . . . . . . . . . . . . . 115

    Hydrochloric acid solut ion . . . . . . . . . . . . . . . . . . . . .116Nitric acid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .119Sodium chloride solut ion . . . . . . . . . . . . . . . . . . . . . .115Sodium hydroxide solut ion . . . . . . . . . . . . . . . . . . . . .117Sulfuric acid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .118

    Concentration measurement . . . . . . . . . . . . . . . . . . . . . . 114Concentration curves . . . . . . . . . . . . . . . . . . . . . . . . .115Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38Ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39, 114

    Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Configuration steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Configuration: Alarm settings . . . . . . . . . . . . . . . . . . . . . . 56Configuration: Controller . . . . . . . . . . . . . . . . . . . . . . . . . 62Configuration: Limit function . . . . . . . . . . . . . . . . . . . . . . 58

    Sett ings for relay 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . .59Sett ings for relay 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . .61

    120 Stratos e 2402 CondI

    g pConcentration measurement . . . . . . . . . . . . . . . . . . . .38LIN curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40LOG curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . .36Output current during Error . . . . . . . . . . . . . . . . . . . . .46

    Output current range . . . . . . . . . . . . . . . . . . . . . . .40, 42Output signal during HOLD . . . . . . . . . . . . . . . . . . . . .47Select sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32Select t emp probe . . . . . . . . . . . . . . . . . . . . . . . . . . . .34Time constant of output filter . . . . . . . . . . . . . . . . . . .44

    Configuration: Output 2 . . . . . . . . . . . . . . . . . . . . . . . . . . 48Output current during HOLD . . . . . . . . . . . . . . . . . . . .52Output current range . . . . . . . . . . . . . . . . . . . . . . . . . .49Temperature error . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52Temperature unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48

    Time constant of output filter . . . . . . . . . . . . . . . . . . .50Configuration: Output Clean/PSEt2 . . . . . . . . . . . . . . . . . . 64Control of rinsing probe . . . . . . . . . . . . . . . . . . . . . . . .64Signaling parameter set 2 . . . . . . . . . . . . . . . . . . . . . . .64

    Configuration: Temperature compensation . . . . . . . . . . . . 54Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    Rinsing probe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65Special cable for SE 655 / SE 656 sensors . . . . . . . . . . .16Typical wirings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18

    Controller characteristic . . . . . . . . . . . . . . . . . . . . . . . . . . 88Controller configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 62Controller equations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89Controller test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87Controller types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88Controlling a rinsing probe . . . . . . . . . . . . . . . . . . . . . . . . 65CSA Certif icate of Compliance . . . . . . . . . . . . . . . . . . . . 106

    121

    Current source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86Diagnostics functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85

    Switchover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66User settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70

  • 8/9/2019 2402 condi

    62/65

    Controller test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .87Display of calibration data . . . . . . . . . . . . . . . . . . . . . .85Display of last error message . . . . . . . . . . . . . . . . . . . .85Display of output currents . . . . . . . . . . . . . . . . . . . . . .85Relay test (manual test of contacts) . . . . . . . . . . . . . . .86

    Sensor monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85Specify current for output 1/2 . . . . . . . . . . . . . . . . . . .86

    Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Division 2 wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15EC Declaration of Conformity . . . . . . . . . . . . . . . . . . . . . . . 7Err . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Error Info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85Error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92Hold mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

    External activation . . . . . . . . . . . . . . . . . . . . . . . . . . . .27

    LED in HOLD mode . . . . . . . . . . . . . . . . . . . . . . . . . . .57Output signal for HOLD . . . . . . . . . . . . . . . . . . . . .47, 53Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Limit function (LiMIT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Mount ing plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Operating states . . . . . . . . . . . . . . . . . . . . . . . .