Performance Analysis 230 Ton York Chiller Nashville, TN ® Energy Performance Solutions 21011 Hegar Road Hockley, Texas 77447 713-931-2735 www.energyps.com

230 Ton York Chiller - energyps.com

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 230 Ton York Chiller - energyps.com

Performance Analysis230 Ton York Chiller

Nashville, TN

®

Evaporcool Solutions, LLC5100 Wilfong Road, Memphis, TN 38134

Phone: 901 -382 -7809 Fax: 901 -382 -7819E -mail: [email protected]

Energy Performance Solutions21011 Hegar Road

Hockley, Texas 77447713-931-2735

www.energyps.com

Page 2: 230 Ton York Chiller - energyps.com

® ®

PERFORMANCE ANALYSIS

Step 1: Baseline TestingThe performance of the test unit was recorded from 5/25/10 until 6/15/10.

Step 2: Installation of Evaporcool SystemThe Evaporcool System was installed on the test unit on 7/27/10.

Step 3: Comparison TestingThe performance of the test unit was recorded from 7/28/10 until 8/26/10.

The energy consumption of an Air-Cooled Chiller was recorded with and without the Evaporcool System at a facility located in Nashville, TN.

Page 3: 230 Ton York Chiller - energyps.com

The test unit was a York (YCAS Model)

230 Ton High Efficiency R-22 Air-Cooled Chiller.

PERFORMANCE ANALYSIS

Nashville, TN

Page 4: 230 Ton York Chiller - energyps.com

EVAPORCOOL SYSTEM

Page 5: 230 Ton York Chiller - energyps.com

Definition: COOLING DEGREE DAY (“CDD”)

A unit used to relate the day's temperature to the energy demands of air conditioning. One cooling degree day occurs for each degree the daily mean temperature is above 65 Fahrenheit.

Examples:

Day 1 Day 2 Day 3Min 60 70 75Max 80 90 105Mean 70 80 90

- 65 - 65 - 65

CDD 5 15 25

To accurately determine savings, days with similar weather must be compared to one another. The industry standard metric is the Cooling Degree Day.

RESULTS

Page 6: 230 Ton York Chiller - energyps.com

RESULTSBelow are the average energy consumption readings for

the Test Unit during the baseline test.

1500.00

2000.00

2500.00

3000.00

3500.00

4000.00

4500.00

5000.00

0 5 10 15 20 25

Without Evaporcool

Aver

age

kW

h

CDD

Page 7: 230 Ton York Chiller - energyps.com

RESULTSWith the Evaporcool System, the energy consumption

was lower at all CDD’s.

1500.00

2000.00

2500.00

3000.00

3500.00

4000.00

4500.00

5000.00

0 5 10 15 20 25

Without Evaporcool

With Evaporcool

CDD

Aver

age

kW

h

Page 8: 230 Ton York Chiller - energyps.com

RESULTS

CDD 11 12 13 14 17 19 20 21

Before (kWh) 3798.9 3777.6 4194.7 4221.7 4372.9 4603.0 4372.9 4355.4

Before Date 26-May-10 27-May-10 2-Jun-10 1-Jun-10 11-Jun-10 14-Jun-10 12-Jun-10 13-Jun-10

After (kWh)

2369.5 2546.2 2689.7 2611.0 2855.9 3002.8 3314.2 3299.0

After Date 26-Aug-10 24-Aug-10 18-Aug-10 23-Aug-10 17-Aug-10 30-Jul-10 28-Jul-10 29-Jul-10

Savings (kWh)

1429.5 1231.4 1505.0 1610.8 1517.0 1600.2 1058.6 1056.5

Savings (%) 37.6% 32.6% 35.9% 38.2% 34.7% 34.8% 24.2% 24.3%

Below is a comparison of individual days with identical CDD’s.

Page 9: 230 Ton York Chiller - energyps.com

HOURLY RESULTSBelow is an hourly comparison of days with similar weather.

kWh

0.00

50.00

100.00

150.00

200.00

250.00

With Evaporcool (8/23/10)

Without Evaporcool (6/1/10)

Page 10: 230 Ton York Chiller - energyps.com

OVERALL RESULTS

• Baseline Equipment Performance– Average Daily Energy Consumption 4,014.67 kWh– Average Daily High Temperature 89.0 degrees (f)

• Equipment Performance – with Evaporcool®

– Average Daily Energy Consumption 2,830.05 kWh– Average Daily High Temperature 93.3 degrees (f)

Page 11: 230 Ton York Chiller - energyps.com

OVERALL RESULTS

• Baseline Equipment Performance– Average Daily Energy Consumption 4,014.67 kWh– Average Daily High Temperature 89.0 degrees (f)

• Equipment Performance – with Evaporcool®

– Average Daily Energy Consumption 2,830.05 kWh– Average Daily High Temperature 93.3 degrees (f)

Note that the average high temperature was much warmer during the period with the Evaporcool System installed.

Page 12: 230 Ton York Chiller - energyps.com

OVERALL RESULTS

• Baseline Equipment Performance– Average Daily Energy Consumption 4,014.67 kWh– Average Daily High Temperature 89.0 degrees (f)

• Equipment Performance – with Evaporcool®

– Average Daily Energy Consumption 2,830.05 kWh– Average Daily High Temperature 93.3 degrees (f)

• Energy Savings– Average Daily Energy Savings 1,184.62 kWh– Savings as Percentage of Consumption 29.5%

Page 13: 230 Ton York Chiller - energyps.com

Additional Savings

Additional �nancial bene�ts include:

1. Peak Demand Reduction;

2. Maintenance Savings;

3. Reduced Equipment Failure;

4. Increased Equipment Life;

5. Available Tax Benefits; or

6. Potential for Utility Rebates.

The previous case study only demonstrate savings from kWh reduction… but the Evaporcool System provides many additional bene�ts…