    Generic Guidelines

    Environmental Protection

    Eltek Valere DC Power Supply Systems

    Outdoor Enclosures

  • 8/10/2019 2038879 Environmantal Guidelines for Instalation of EV Power Systems 1v1

    2/8

    2 Generic GuidelinesEnvironmental Protection 2038879, Issue 1.1, 2009-03

    Information in this document is subject to change without notice and does not represent a commitment onthe part of Eltek Valere.

    No part of this document may be reproduced or transmitted in any form or by any means electronic ormechanical, including photocopying and recording for any purpose without the explicit written permissionof Eltek Valere.

    Copyright : Eltek Valere, 2009

    NS-EN ISO 14001 Certified

    Certificate No:11276-2007-AE-NOR-NA

    NS-EN ISO 9001 Certified

    Certificate No:4072-2007-AQ-NOR-NA

    2038879 Issue 1.1, 2009 Mars

    Published 2009-03-26

    clha/mafe

  • 8/10/2019 2038879 Environmantal Guidelines for Instalation of EV Power Systems 1v1

    3/8

    Generic GuidelinesEnvironmental Protection 2038879, Issue 1.1, 2009-03 3

    Table of Contents

    1. Int roduct ion ............................................................................................ 4

    2.

    Cabinet and Environmental Considerations ....................................... 4

    Open Loop (Fan/Filter) Cooling .................................................................................... 4

    Standard Filter Class F5 (Mat or Pleated Type) ............................................................. 4Membrane Filter (Gore Pleated Type) ............................................................................ 4

    Closed Loop (HEX or Air-Conditioner) Cooling ............................................................ 5

    Heat Exchanger (HEX) ................................................................................................... 5

    Air-Conditioner (ACU) ..................................................................................................... 5

    Enclosure Material Selection Table .............................................................................. 5

    3. Follow Installation and Commissioning Guides ................................. 6

    4.

    Adding Equipment to the Enclosure On Site ...................................... 6

    5. Follow Maintenance Guide .................................................................... 7

  • 8/10/2019 2038879 Environmantal Guidelines for Instalation of EV Power Systems 1v1

    4/8

    4 Generic GuidelinesEnvironmental Protection 2038879, Issue 1.1, 2009-03

    1. Introduction

    This document describes the environmental guidelines required for an Eltek Valere enclosure. The intentionof this guide is to ensure that Eltek Valere cabinets installed outdoors or in other exposed area are installed,

    operated and maintained as required, in order to meet the applicable warranty terms for the product.

    2. Cabinet and Environmental ConsiderationsAll Eltek Valere outdoor enclosures are design and verified to meet some mandatory environmental criteria

    including:

    Dust and water: EN 60950 IP 55 or IP54

    Storage: EN 300 019-1-1 class 1.3Transport: EN 300 019-1-2 class 2.3

    Operation: EN 300 019-1-4 class 4.1E.

    However this does not mean that all cabinets can be used in any location without additional consideration of

    the local environment on site. During site planning a few additional basic criteria must be considered. Please

    note that MTBF/ lifetime of electronics also depends heavily on the temperature in the enclosure, this has to

    be considered when selecting cooling option.

    .

    Open Loop (Fan/Filter) Cool ingOpen loop cooling systems (fan/filter) are using the ambient air to cool the equipment inside the cabinet.This solution will require maintenance as the filter media will get clogged and will have to be changed on

    site. See maintenance section for more details. Note that temperature inside the cabinet will be higher than

    ambient temperature (positive delta-t) when using this cooling option.

    Standard Filter Class F5 (Mat or Pleated Type)

    Recommended used on sites with:

    Normal air pollution

    Location 1500 meters or more from sea side

    Not recommended used on sites with:

    Moderate or high air pollution

    Location closer than 1500 meters from sea side costal areas

    Membrane Filter (Gore Pleated Type)Can be an alternative on sites with:

    Normal or moderate air pollution

    Location closer than 1500 meters from sea side costal areas

    Not recommended used on sites with:High air pollution

  • 8/10/2019 2038879 Environmantal Guidelines for Instalation of EV Power Systems 1v1

    5/8

    Generic GuidelinesEnvironmental Protection 2038879, Issue 1.1, 2009-03 5

    Closed Loop (HEX or Air-Conditioner) Cool ingClosed loop cooling systems are not using the ambient air to cool the equipment inside the cabinet; it is only

    circulating the internal air. The cooling of the air inside the enclosure can be done by using either ambient air

    in a sealed channel (HEX) or active components (ACU). This will hence protect the equipment inside the

    cabinet from a corrosive and humid environment.Note that temperature inside the cabinet will be higher than ambient temperature (positive delta-t) when

    using HEX cooling option, ACU can provide a lower cabinet temperature than ambient temperature

    (negative delta-t)

    Heat Exchanger (HEX)Recommended used on locations with:

    Normal tohigh air pollution

    Location closer than 1500 meters from sea side costal areas

    High humidity

    Moderate ambient temperature

    Not recommended used on sites with:

    High ambient temperature

    Air-Conditioner (ACU)Recommended used on locations with:

    Normal tohigh air pollution

    Location closer than 1500 meters from sea side costal areas

    High humidity

    Applications where the cabinet temperature is required to be below ambient temperature (negative delta-T)

    Enclosure Material Selection Table

    Enclosure material specification: Recommended used:

    Painted uncoated (black) steel Indoors or other protected area

    Painted alu-zinc or galvanized coated steel Outdoors or in other exposed area

    Painted aluminium Outdoors or in other exposed area

    Note:

    Small traces of rust might be visible on the cutting edges of non painted parts made of alu-zinc or pre-

    galvanized steel. This is a normal mechanical cutting/punching process phenomenon and will not limit the

    product lifetime.

  • 8/10/2019 2038879 Environmantal Guidelines for Instalation of EV Power Systems 1v1

    6/8

    6 Generic GuidelinesEnvironmental Protection 2038879, Issue 1.1, 2009-03

    3. Follow Installation and Commissioning Guides

    All Eltek Valere cabinets are electrically tested and visual inspected to secure delivery of a high qualityproduct.

    To secure a high quality product also after installation and commissioning all cabinets are delivered with a

    user manual (printed and/or electronically on a CD).

    It is the customers responsibility that all people working on installation and commissioning have the

    necessary technical knowhow and follow all details in the manual. If the manual is missing please contact

    your local Eltek Valere company.

    In addition to follow the details in the installation and commissioning guides please read and follow the

    generic installation guidelines for lightning and surge protection ref. Eltek Valere document number

    2024623

    4. Adding Equipment to the Enclosure On Site

    Some Eltek Valere enclosures might be delivered with additional internal space which can be used for

    customer equipment. It will be the customers responsibility that this equipment is designed for the overall

    cabinet environmental specifications before integration. Below are a few basic points for general

    consideration:

    Corrosion protection of the equipment (salt, humidity, air pollution) Temperature range of the equipment

    Cooling design of equipment (airflow path, and available space for airflow)

    Mechanical design of equipment (mounting, shock and vibration, zone 4)

    Make sure you know the max cooling capacity of the cabinet. Do not add more heat load into thecabinet than max capacity.

    Please do not limit your total evaluation to the above points, use them only as a rough guide.

  • 8/10/2019 2038879 Environmantal Guidelines for Instalation of EV Power Systems 1v1

    7/8

    Generic GuidelinesEnvironmental Protection 2038879, Issue 1.1, 2009-03 7

    5. Follow Maintenance Guide

    To ensure that the expected design lifetime of the enclosure are met and to be within the warranty terms of

    the product the owner of the enclosure must adapt and follow a complete maintenance scheme. This scheme

    has to be tailored to match the local site and cabinet solution. Eltek Valere recommends general cabinet

    maintenance minimum ones a year.Note: ones a year is not applicable for filter maintenance (see separate

    section below)

    All Eltek Valere cabinets are delivered with a user manual (printed and/or electronically on a CD).

    It is the customers responsibility that all people involved in making the maintenance scheme or doing site

    maintenance has the necessary technical knowhow and follows the recommendation in the manual. Please

    note that the points in the manual have to be tailored by the customer to match the local site condition. If the

    manual is missing please contact your local Eltek Valere company.

    Below are a few basic points for general consideration. Please do not limit your total evaluation to the below

    points.

    Cabinet:

    Check that no physical damage has been applied to the exterior of the cabinet (dents or scratches)

    Use touch-up paint to repair any scratches on painted surfaces of the cabinet

    Check that the door gasket has no visible damage

    Check that cabinet cable entry points (bottom and/or top) is sealed

    Check that the fixing bolts of the cabinet is tighten

    Give the hinges of the door a droplet of oil or grease

    Check for abnormal traces of dust or water inside the enclosure

    Filter Maintenance (when applicable):

    Implementation of an air filter preventive maintenance program is one of the most important factors to

    protect installed equipment, keep operational cost down and to keep the equipment up running!

    Make sure to adapt the filter change interval to the local conditions

    It is recommended to inspect frequently in the first period after installation in order to understandand adapt to local conditions

    Use only original filters provided by Eltek Valere or in accordance with technical specification

    supplied by Eltek Valere Use of non-original filters might partly or completely void the warranty provided by Eltek Valere

    See the manual or contact your local Eltek Valere company for further details.

    Other maintenance:

    Remove any leaves or other items that might block the external airflow (in/out)

    Check that the fans are running without any abnormal noise