Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
Automatic Fire Alarm Association
2021 Webinar SeriesFire Protection and Elevators
Presented by: Ray Grill, P.E., FSFPE
Automatic Fire Alarm Association
Automatic Fire Alarm Association
Agenda• Elevator types• Fire protection requirements for elevators• When are Fire Service Access Elevators (FSAEs)
required? • FSAE requirements and features
tsapps.nist.gov/publications/get_pdf.cfm?pub_id+100971
Automatic Fire Alarm Association
Types of Elevators• Hydraulic
• Holed• Holeless
• Traction• Conventional with machine room• Machine room less (MRL)
• Limited-use/Limited-application• Hydraulic or Traction (Limited rise – Max 25ft.)
Automatic Fire Alarm Association
Drivers for Requirements• Building and Fire Codes• NFPA 72 – National Fire Alarm and Signaling Code• NFPA 13 – Standard for the Installation of Sprinkler
Systems• ASME A17.1 – Safety Code for Elevators and
Escalators • Local amendments
Automatic Fire Alarm Association
Sprinklers and Fire Alarm Devices• If the hoistway is sprinklered;
• Smoke detection at top required for recall
• Heat detection within 24 inches of each sprinkler required for power shunt trip or waterflow with zero delay can provide shunt trip activation
Automatic Fire Alarm Association
When are Sprinklers required - NFPA 13? • 2013 & 2016 Edition- 8.15.5 - Exceptions• 2019 Edition-9.3.6 - Exceptions• Bottom of the pit for hydraulic elevators
(within 2 ft of the bottom of the pit)• Machine rooms, Control Spaces in fully
sprinklered buildings. (Except for FSAE’s)• Combustible hoistways• MRL Hoistways (Except for FSAE’s)
• At top only unless combustible suspension system (check local criteria)
NFPA 13-2013 edition
Automatic Fire Alarm Association
When are Sprinklers required - NFPA 13?• If combustible suspension used (polyurethane
coated or elastomeric coated belts) (MRLs) sprinklers are required at top and bottom of shaft (8.15.5.7.1 – 2013)
• If the suspension means provides not less than a FT-1 rating per UL 62, Flexible Cords and Cables, and UL 1581, Reference Standard for Electrical Wires, Cables and Flexible Cords, sprinklers are not required (8.15.5.7.2 – 2013)
Automatic Fire Alarm Association
Machine-Room-Less Designs• Some jurisdictions require sprinklers in
hoistways of MRL’s regardless of the suspension system if the building is required to be fully sprinklered.
• Hoistway is considered a machinery space
Automatic Fire Alarm Association
NFPA 72 Requirements for Elevator Hoistways and Machine Rooms
• Smoke detector located within 21 feet from the centerline of the elevator in the elevator lobby (21.3.5)
• Other detection devices can be used in hoistways and machine rooms when ambient conditions do not permit smoke detectors (21.3.9)
• Heat detectors used for power shut down must be located within 24 inches of each sprinkler (21.4.2)
• Smoke detectors shall not be installed in un-sprinklered hoistways except to activate smoke relief (2013) or Phase I emergency recall (2016) (21.3.6)
Automatic Fire Alarm Association
Detection in the Pit?Prior to 2019 NFPA 72
Automatic Fire Alarm Association
Detection in the Pit? 2019 NFPA 72
Automatic Fire Alarm Association
ASME A17.1 Requirement – Elevator Inspection
Automatic Fire Alarm Association
IBC Requirements for FSAE’s• Occupied floor more than 120 feet
above FD Vehicle Access.
• 2018 IBC – Doesn’t require FSAE’s to serve levels below FD Vehicle access level.
Automatic Fire Alarm Association
IBC Requirements for FSAE’s• Cannot be sprinklered (Typically requires
separation from non-FSAEs in hoistway and machinery/control spaces)
• Hoistways illuminated 1 foot-candle during emergency activation (3007.5)
• Lobby’s shall have a fire resistance rating ≥1 hour with doors ≥ 3/4 hour rating (3007.6.2)
• FSAE symbol shall be installed on each side of the hoistway doorframe (3007.6.5)
Automatic Fire Alarm Association
NFPA 72 Requirements for Monitoring FSAE
17
2013 Edition 2016 Edition
Automatic Fire Alarm Association
NFPA 72 Requirements for Monitoring FSAE
2019 Edition
18
Automatic Fire Alarm Association
Hydraulic Elevator
19
Using Waterflow Switch for Shunt trip
Automatic Fire Alarm Association
Traction with Machine Room
20
Using Waterflow Switch for Shunt trip
Automatic Fire Alarm Association
Limited-use/Limited-application Elevators
• Typically installed to provided to meet accessibility requirements of the building code.
• Can travel a maximum of 25 feet.
• Maximum weight limit of 1400 lbs.
• Speed limited to 30 ft/min.
21
Automatic Fire Alarm Association
Code Path for addressing a Hydraulic LULA Elevator
• NFPA 13 – 2013• Since it is hydraulic, Sprinklers required in the pit.
22
Automatic Fire Alarm Association
Code Path for addressing a Hydraulic LULA Elevator
• NFPA 72-2013• Since sprinklers are
required, fire detection required in pit.
• Detector activation causes Phase I recall functions.
• Phase II not required for LULA Elevators.
23