2019 Oregon Structural Specialty Code Board review matrix Page 1 of 21 The following is a summary matrix showing the Building Codes Structures Board’s recommendation for the adoption of the 2019 Oregon Structural Specialty Code (OSSC). Source abbreviations IBC CH International Building Code (IBC) change OR A Existing Oregon amendment SAM Statewide Alternate Method Interp Statewide Code Interpretation Committee outcome markings * Denotes an item with a fiscal impact. The committee's estimated impact can be found in the description column. Section Subject and description of change Board outcomes Chapter 2 201, 202 Chapter 2 definitions include various existing amendments and new model code terms related to new model code provisions and referenced standards. The code review committee’s action on the provisions located in the body of the code will guide and dictate removal or modification of terms in Chapter 2, as applicable. Approved Chapter 3 302 Classification of outdoor areas. | IBC CH Approved IBC CH 304.2 Lockup facilities. | OR A: added provisions for lockup facilities defined in ORS 169.005(4). Retained OR A 306.3 Low-hazard factory industrial, Group F-2. | OR A: added wood barrel and bottled wine to Group F-2. Retained OR A 307.2.1 Storage of Class 1.4G Class C Common. Fireworks. | OR A: added section for temporary storage of Class C Common fireworks in permanent buildings. (14 OSSC 307.1.2) Retained OR A 308, 310 DHS Licensed facilities. | Public proposal no. OSSC-13 ~ Dan Purgiel Committee review: March 15, 2018 Committee requested more information from the proponent. March 29, 2018 Committee approved the proposal to update the existing amendments that align the OSSC with federal requirements for healthcare occupancies and DHS requirements. Board review: Aug. 1, 2018 Board affirmed the committee’s recommendation. Approved proposal 308.2 308.2.1 308.2.2 308.2.3 308.2.4 Institutional Group I-1. | OR A: modified section to exclude staff from the person count. (14 OSSC 308.3) Condition 1. | OR A: aligned to DHS and specified the facilities under Condition 1. (14 OSSC 308.3.1) Condition 2. | OR A: aligned to DHS and specified the facilities under Condition 2. (14 OSSC 308.3.2) Six to sixteen persons receiving custodial care. | OR A| Aligns with 18 IBC. (14 OSSC 308.3.3) ≤ Five persons receiving custodial care. | OR A: added reference to ORSC, App. T. (14 OSSC 308.3.4) Retained OR A Retained OR A Retained OR A Rescinded OR A Retained OR A 308.3.2 ≤ Five persons receiving medical care. | OR A: added reference to ORSC, App. T. (14 OSSC 308.4.1) Retained OR A 308.5.5 Family childcare homes. | OR A: added for those located in a private residence. (14 OSSC 308.6.5) Rescinded OR A 310.3 Residential Group R-2. | IBC CH | OR A: added for occupancies providing 21 or more housing units for low- income elderly. (14 OSSC 310.4) Approved IBC CH Retained OR A 310.4 Residential Group R-3. | IBC CH and OR A: added adult care facilities, child care facilities, adult foster homes and lodging houses. (14 OSSC 310.5) Approved IBC CH Rescinded OR A 310.4.2 Lodging houses. | IBC CH | added section in 2015 and modified the section in 2018. Committee review: March 29, 2018 Committee approved IBC CH, modified by deleting owner-occupiedto align with the ORSC number of occupants from 10 or fewer to 16 or fewer. Board review: Aug. 1, 2018 Board affirmed the committee’s recommendation. Final outcome: Approved the model code change and added a reference to ORSC, App. T. Approved IBC CH (modified) 310.5 310.5.1 310.5.2 Residential Group R-4. | OR A: modified for the addition of two sections. (14 OSSC 310.6) Condition 1. | OR A: added and specified the facilities under Condition 1. (14 OSSC 310.6.1) Condition 2. | OR A: added, align to DHS, and specified the facilities under Condition 2. (14 OSSC 310.6.2) Retained OR A Retained OR A Retained OR A

2019 Oregon Structural Specialty Code Board review matrix · 2019 Oregon Structural Specialty Code Board review matrix Page 3 of 14 No. Source Section Subject and description of change

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

2019 Oregon Structural Specialty Code Board review matrix

Page 1 of 21

The following is a summary matrix showing the Building Codes Structures Board’s recommendation for the adoption of the

2019 Oregon Structural Specialty Code (OSSC).

Source abbreviations

IBC CH – International Building Code (IBC) change

OR A – Existing Oregon amendment

SAM – Statewide Alternate Method

Interp – Statewide Code Interpretation

Committee outcome markings

* Denotes an item with a fiscal impact. The committee's estimated impact can be found in the description column.

Section Subject and description of change Board outcomes

Chapter 2

201, 202 Chapter 2 definitions include various existing amendments and new model code terms related to new model

code provisions and referenced standards. The code review committee’s action on the provisions located in the

body of the code will guide and dictate removal or modification of terms in Chapter 2, as applicable.

Approved

Chapter 3

302 Classification of outdoor areas. | IBC CH Approved IBC CH

304.2 Lockup facilities. | OR A: added provisions for lockup facilities defined in ORS 169.005(4). Retained OR A

306.3 Low-hazard factory industrial, Group F-2. | OR A: added wood barrel and bottled wine to Group F-2. Retained OR A

307.2.1 Storage of Class 1.4G Class C Common. Fireworks. | OR A: added section for temporary storage of Class C

Common fireworks in permanent buildings. (14 OSSC 307.1.2)

Retained OR A

308, 310 DHS Licensed facilities. | Public proposal no. OSSC-13 ~ Dan Purgiel

Committee review:

March 15, 2018 Committee requested more information from the proponent.

March 29, 2018 Committee approved the proposal to update the existing amendments that align the

OSSC with federal requirements for healthcare occupancies and DHS requirements.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved proposal

308.2

308.2.1

308.2.2

308.2.3

308.2.4

Institutional Group I-1. | OR A: modified section to exclude staff from the person count. (14 OSSC 308.3)

Condition 1. | OR A: aligned to DHS and specified the facilities under Condition 1. (14 OSSC 308.3.1)

Condition 2. | OR A: aligned to DHS and specified the facilities under Condition 2. (14 OSSC 308.3.2)

Six to sixteen persons receiving custodial care. | OR A| Aligns with 18 IBC. (14 OSSC 308.3.3)

≤ Five persons receiving custodial care. | OR A: added reference to ORSC, App. T. (14 OSSC 308.3.4)

Retained OR A

Retained OR A

Retained OR A

Rescinded OR A

Retained OR A

308.3.2 ≤ Five persons receiving medical care. | OR A: added reference to ORSC, App. T. (14 OSSC 308.4.1) Retained OR A

308.5.5 Family childcare homes. | OR A: added for those located in a private residence. (14 OSSC 308.6.5) Rescinded OR A

310.3 Residential Group R-2. | IBC CH | OR A: added for occupancies providing 21 or more housing units for low-

income elderly. (14 OSSC 310.4)

Approved IBC CH

Retained OR A

310.4 Residential Group R-3. | IBC CH and OR A: added adult care facilities, child care facilities, adult foster

homes and lodging houses. (14 OSSC 310.5)

Approved IBC CH

Rescinded OR A

310.4.2 Lodging houses. | IBC CH | added section in 2015 and modified the section in 2018.

Committee review:

March 29, 2018 Committee approved IBC CH, modified by deleting “owner-occupied” to align with

the ORSC number of occupants from 10 or fewer to 16 or fewer.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Final outcome: Approved the model code change and added a reference to ORSC, App. T.

Approved IBC CH

(modified)

310.5

310.5.1

310.5.2

Residential Group R-4. | OR A: modified for the addition of two sections. (14 OSSC 310.6)

Condition 1. | OR A: added and specified the facilities under Condition 1. (14 OSSC 310.6.1)

Condition 2. | OR A: added, align to DHS, and specified the facilities under Condition 2. (14 OSSC 310.6.2)

Retained OR A

Retained OR A

Retained OR A

2019 Oregon Structural Specialty Code Board review matrix

Page 2 of 21

Section Subject and description of change Board outcomes

311.1.1 Accessory storage spaces. | IBC CH | Public proposal no. OSSC-14 ~ Johnathan Balkema, OBOA

Committee review:

March 15, 2018 Committee agreed to forward the proposal for review.

March 29, 2018 Committee approved the IBC CH, modified by the proposal to make the provision

optional.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Feb. 6, 2019 Board reaffirmed the approval of the proposal.

Approved IBC CH

modified by the

Approved proposal

311.3 Low-hazard storage, Group S-2. | OR A: added wood barrels to Group S-2. Retained OR A

311.4 Mausoleums and Columbariums. Group S-3. | OR A: added Group S-3. Retained OR A

312.1 Classification of communication equipment structures. | IBC CH Approved IBC CH

312.1.1 Greenhouses. | IBC CH Approved IBC CH

Chapter 4

403.6.1 Fire service access elevator. | Public proposal no. OSSC-15 ~ Jesse Emory, GBD Architects

Committee review:

March 15, 2018 Committee requested more detailed fiscal analysis.

March 29, 2018 Committee disapproved the proposal.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Disapproved proposal

404.5 Smoke Control. | Exception. | IBC CH Approved IBC CH

404.6 Enclosure of atriums. | IBC CH Approved IBC CH

406 Motor Vehicle-Related Occupancies. | IBC CH Approved IBC CH

406.2.2 Clear Height. | IBC CH ~ *Fiscal impact: ≤ 5% increase. Approved IBC CH*

406.3.1 Classification. | IBC CH ~ *Fiscal impact: ≤ 5% increase. Approved IBC CH*

406.8 Repair Garages. | IBC CH ~ *Fiscal impact: ≤ 5% increase. Approved IBC CH*

407 Group I-2. | IBC CH Approved IBC CH

407.1 Group I-2 General. | IBC CH Approved IBC CH

407.2.5 Nursing Home Housing Units. | IBC CH Approved IBC CH

407.5 Maximum Smoke Compartment Size I-2. | IBC CH Approved IBC CH

408.2 Other occupancies Group I-3. | OR A: modified for security operations. Retained OR A

408.3.9 Cell tier exiting. | OR A: added cell tier exiting provisions. Retained OR A

408.9 Windowless buildings. | OR A: deleted. Retained OR A

408.11 Emergency ventilation. | OR A: added requirement for Group I-3 resident housing areas. Retained OR A

412.3.1

412.4.3

412.4.4

412.4.6

Exterior walls. (14 OSSC 412.4.1) | Public proposal no. OSSC-16 | Aron Faegre, OR Aviation Industries

Floor surface. (14 OSSC 412.3.3) | Public proposal no. OSSC-17 | Aron Faegre, OR Aviation Industries

Heating equip. (14 OSSC 412.3.4) | Public proposal no. OSSC-18 | Aron Faegre, OR Aviation Industries

Fire suppression. (14 OSSC 412.3.6) | Public proposal no. OSSC-19 | Aron Faegre, OR Aviation Industries

Committee review:

March 15, 2018 Committee requested more detailed fiscal analysis.

March 29, 2018 Committee disapproved the proposals.

Board review:

The BCSB reviewed this proposals separately and adopted temporary amendments for the 2014 OSSC.

Action outside of

Code review process

412.5 Aircraft Paint Hangars. | IBC CH ~ *Fiscal impact: Slight decrease Approved IBC CH*

412.5.6 Fire suppression. | OR A: added another exception. (14 OSSC 412.4.6) | Updated due to concurrent board

action.

Rescinded OR A

2019 Oregon Structural Specialty Code Board review matrix

Page 3 of 21

Section Subject and description of change Board outcomes

415.5 Emergency Alarms. | IBC CH Approved IBC CH

420 Groups I-1, R-1, R-2, R-3, and R-4. | IBC CH Approved IBC CH

420.6 Smoke barriers in Group I-1 Condition 2. | OR A | (14 OSSC 420.4 and 420.4.1) | Aligns with 18 IBC. Rescinded OR A

422.6 Electrical Systems in Ambulatory… | IBC CH Approved IBC CH

455 Piers and Wharves. | OR A: added section. (14 OSSC 424) Retained OR A

425 Hyperbaric facilities. | IBC CH Approved IBC CH

456 Mausoleums and Columbariums. | OR A: added sections. (14 OSSC 425) Retained OR A

426 Combustible Dusts, Grain Processing and Storage. | IBC CH Approved IBC CH

427 Medical Gas Systems. | IBC CH Approved IBC CH

428 Higher Education Laboratories. | IBC CH Approved IBC CH

New Earthquake relief shelter. | Public proposal no. OSSC-12 ~ Jeffrey Soulages, OSSPAC

Committee review:

March 15, 2018 Committee requested more detailed fiscal analysis.

March 29, 2018 Committee reviewed testimony and agreed to forward the proposal for review.

April 12, 2018 Committee approved the proposal.

Board review:

Nov. 7, 2018 Board received testimony in opposition and ultimately disapproved the proposal.

Disapproved proposal

Chapter 5

Table 504.3 Allowable building heights and areas. | OR A: added Group S-3. (14 OSSC Table 503) Retained OR A

503.1.4 Occupied roofs. | IBC CH Approved IBC CH

504 Building Height and Number of Stories. | IBC CH Approved IBC CH

504.2 Automatic sprinkler system increase. | OR A: added I-1 Condition 2 to the exception. | No longer necessary Rescinded OR A

505.2.3 Openness. | IBC CH Approved IBC CH

Table 506.2 Allowable Area Factor. | IBC CH Approved IBC CH

506.3 Automatic Sprinkler system increase. | OR A: limited I-3 occupancy allowance. | No longer necessary Rescinded OR A

507.1 Unlimited Area Building. | IBC CH Approved IBC CH

508.1 General. | OR A: added 4th exception per winery regulations. Retained OR A

Table 508.4 Required separation of occupancies. | Public proposal no. OSSC-21 ~ Jack Applegate, NCPA

Committee review:

March 15, 2018 Committee agreed to forward the proposal for review.

April 12, 2018 Committee approved the proposal to add values for the blanks in the Table.

Board review:

Aug. 1, 2018 Committee Board affirmed the committee’s recommendation.

Public proposal no. OSSC-20 | Johnathan Balkema, OBOA (Withdrawn by proponent)

Approved proposal

510.2 Horizontal Building Separation Allowance. | IBC CH Approved IBC CH

Chapter 6

2019 Oregon Structural Specialty Code Board review matrix

Page 4 of 21

Section Subject and description of change Board outcomes

Table 601 Fire-resistance rating requirements for building elements. |

OR A: added a footnote that prohibits the reduction from roofs supporting rooftop structures in Section 1509.

Public proposal no. OSSC-22 | Eric Bressman, Ankrom Moison Architects

Committee review:

April 26, 2018 Committee approved the proposal to add a footnote modified as follows:

“For the purpose of determining the fire-resistance rating of joints, penetrations, openings

and ducts in concrete floor and roof two-way slabs having direct connection to the

columns, the fire-resistance rating for associated secondary members shall be used. All

reinforcing steel and post-tensioning tendons shall have concrete coverage adequate to

provide the fire-resistance rating required for primary structural frame elements.”

[Also see Section 711.2.4] ~*Fiscal impact: Slight decrease.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Retained OR A

Approved proposal

602 Construction Classification. | IBC CH Approved IBC CH

Table 602 Fire-resistance rating requirements for exterior walls.... | OR A: added S-3 occupancies to Table. Retained OR A

602.4 Type IV. Construction classification. | IBC CH Approved IBC CH

602.4 SAM 15-01 | Cross-laminated timber provisions. Retained SAM

Chapter 7

706.2 SCI 06-03 | Sprinkler system installation in buildings with firewalls. Retained Interp

703.2.4 Supplemental Features. | IBC CH ~ *Fiscal impact: Slight decrease. Approved IBC CH*

Table 705.2 Minimum Distance of Projection. | IBC CH | OR A | Aligns with 18 IBC. Approved IBC CH

705.2.3 Combustible projections. | OR A: modified. Rescinded OR A

705.6 Structural Stability, Exterior Walls. | IBC CH Approved IBC CH

705.8.6 Vertical exposure. | OR A: added charging information for the vertical exposure opening protectives. Retained OR A

705.8.6.1 Vertical exposure for buildings on the same lot. | OR A: modified the points of measurements. Retained OR A

705.8.6.2 Vertical exposure for buildings on separate lots. | OR A: added provisions for those on separate lots. Retained OR A

Table 705.8 Maximum Area (Exterior) | Public proposal no. OSSC-23 ~ Jack Applegate, Northwest Code Professionals

Committee review:

March 15, 2018 Committee agreed to forward the proposal for review.

April 12, 2018 Committee disapproved the proposal.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Disapproved proposal

706.1.1 Party Walls Not … Fire Walls. | IBC CH | Public proposal no. OSSC-24 ~ Johnathan Balkema, OBOA

Committee review:

March 15, 2018 Committee agreed to forward the proposal for review.

April 12, 2018 Committee approved the proposal to disapprove the model code change by deleting

the second exception that would no longer require a fire wall at lot lines when the

building height and area comply with the code.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Disapproved IBC CH

Approved proposal

706.2 Structural Stability, Fire Walls. | IBC CH ~ *Fiscal impact: Slight decrease. Approved IBC CH*

708.4 Continuity of Fire Partitions. | IBC CH Approved IBC CH

709.5 Openings. | OR A: added Group I-1 Condition 2. | No longer necessary Rescinded OR A

2019 Oregon Structural Specialty Code Board review matrix

Page 5 of 21

Section Subject and description of change Board outcomes

711.2.4 Fire-resistance rating. | Public proposal no. OSSC-22 ~ Eric Bressman, Ankrom Moison Architects

Committee review:

March 15, 2018 Committee requested more detailed fiscal analysis.

March 29, 2018 Committee agreed to forward the proposal for review.

April 12, 2018 Committee discussed modifying the proposal and tabled the item for more info.

April 26, 2018 Committee approved the proposal to add an exception to see Table 601 for

“concrete floor or roof two-way assemblies having direct connection to the column.”

~ *Fiscal impact: Slight decrease.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved proposal*

714.5.2 Membrane Penetrations. | IBC CH ~ *Fiscal impact: Slight increase. Approved IBC CH*

Chapter 8

803.11 / 12 Flame Spread Testing of Laminates and Veneers. | IBC CH Approved IBC CH

Chapter 9

901.1 Scope. | OR A: modified. Retained OR A

901.1.2 Fire protection system shop drawings. | OR A: added section. Retained OR A

902.1.3 Environment. | Public proposal no. OSSC-26 ~ Johnathan Balkema, OBOA

Committee review:

March 15, 2018 Committee agreed to forward the proposal for review.

April 12, 2018 Committee approved the proposal to clarify that rooms being heated solely for

freeze protection are intended to be considered low-energy buildings, modified by

adding “and shall not be considered a conditioned space.”

Board review:

Nov. 7, 2018 Board affirmed the committee’s recommendation.

Approved proposal

(modified)

903 Automatic Sprinkler Systems. | IBC CH | Fiscal impact: ≤ $2.65 per square foot increase. Approved IBC CH*

903.2.1.6 Assembly occupancies on roofs. | IBC CH specific sprinkler requirements. Approved IBC CH

903.2.1.7 Multiple fire areas. | IBC CH Approved IBC CH

903.2.4.1 SCI 08-04 | Automatic sprinkler requirements in F-1 woodworking operations. Retained Interp

903.2.6 Group I. | OR A: deleted exception number 2. | No longer necessary. Rescinded OR A

903.2.7 Group M. | OR A: deleted item number 4 and added Section 903.2.7.2.

Committee review:

April 12, 2018 Committee approved the IBC language and rescinded the existing amendment. ~

*Fiscal impact: Less than or equal to $2.65 per square foot increase.

Board review:

Nov. 7, 2018 Board affirmed the committee’s recommendation.

Rescinded OR A*

903.2.8 Group R. | OR A: modified and added section. Rescinded OR A

903.2.8.4 Care facilities. | Deleted to align with the Chapter 3 changes. Deleted IBC language

903.2.8.5 Substantial Alterations of Group R2. | OR A: modified. Retained OR A

903.3.1.2.1 Balconies and Decks. | OR A | Public proposal no. OSSC-27 ~ Johnathan Balkema, OBOA

Committee review:

March 15, 2018 Committee agreed to forward the proposal for review.

April 12, 2018 Committee approved the proposal to retain the OR A that requires sprinkler

protection regardless if a deck or roof is above. ~ *Fiscal impact Slight increase.

Board review:

Nov. 7, 2018 Board affirmed the committee’s recommendation.

Approved proposal to

retain OR A*

2019 Oregon Structural Specialty Code Board review matrix

Page 6 of 21

Section Subject and description of change Board outcomes

904.13 Domestic cooking systems. | IBC CH requires protection on domestic cooking systems for R-2 dorms.

Committee review:

April 12, 2018 Committee approved the IBC CH, modified by adding “operated by a college or

university for student housing.”

Board review:

Nov. 7, 2018 Board affirmed the committee’s recommendation.

Approved IBC CH

(modified)

904.13.1.2 Protection from fire. | Public proposal no. OSSC-28 ~ Johnathan Balkema, OBOA

Committee review:

March 15, 2018 Committee requested more detailed fiscal analysis.

March 29, 2018 Committee agreed to forward the proposal for review.

April 12, 2018 Committee disapproved the proposal and approved the IBC language.

Board review:

Nov. 7, 2018 Board affirmed the committee’s recommendation.

Disapproved proposal

906 Portable fire extinguishers. | OR A: deleted entire section. Retained OR A

907.2.3 Group E, Emergency voice/alarm communication system. | OR A | IBC CH | Aligns with 18 IBC. Approved IBC CH

907.2.6 SCI 12-02 | Fire alarm design in health care facilities public vs. private mode. Retained Interp

907.2.9.3 Group R-2 college and university buildings. | IBC CH Approved IBC CH

907.2.10 Single- and multiple-station smoke alarms. | OR A: doesn't adopt Sect. 29.3.8 of NFPA 72. Retained OR A

907.5.2.3 Visible Alarms. | IBC CH expanded appliances in I-1, R-1, R-2. | OR A: modified R-2.

Committee review:

April 12, 2018 Committee approved the IBC CH and rescinded the OR A. ~ *Fiscal impact:

$280/unit

Board review:

Nov. 7, 2018 Board affirmed the committee’s recommendation.

Feb. 6, 2019 Board received testimony reversed the committee’s recommendation, disapproved

the IBC CH and retained the OR A.

Disapproved IBC CH

Retained OR A

909.21.1 Pressurization requirements. | IBC CH Approved IBC CH

910 Smoke and Heat Removal. | IBC CH Approved IBC CH

Load Performance. | Public proposal no. OSSC–30 ~ Herb Kroeger, Architectural Specialties

Committee review:

March 15, 2018 Committee requested a detailed fiscal analysis and more info about the proposal.

March 29, 2018 Committee requested a detailed fiscal analysis and more info about the proposal.

April 12, 2018 Committee requested a detailed fiscal analysis and more info about the proposal.

April 26, 2018 Committee disapproved the proposal.

Board review:

Nov. 7, 2018 Board affirmed the committee’s recommendation.

Disapproved proposal

915 Carbon Monoxide Detection. | IBC CH: moved, added Group E, and excluded Group I-3.

Committee review:

April 26, 2018 Committee tabled the item to gather more information.

May 17, 2018 Committee approved the IBC code changes.

Board review:

Nov. 7, 2018 Board affirmed the committee’s recommendation.

Feb. 6, 2019 Board received more testimony and approved the IBC change.

May 1, 2019 Topic returned to the board for additional discussion and revisited process,

including related public proposal.

Final outcome: The model code change was disapproved. The provisions will remain the same as in the

2014 OSSC.

Disapprove IBC CH

2019 Oregon Structural Specialty Code Board review matrix

Page 7 of 21

Section Subject and description of change Board outcomes

915.2.4 Groups A, B, and M. | Public proposal no. OSSC-29 ~ Mark Kohorst, NEMA

Committee review:

March 15, 2018 Committee requested more detailed fiscal analysis.

March 29, 2018 Committee agreed to forward the proposal for review.

April 12, 2018 Proponent requested that the proposal be discussed at the next committee meeting.

The committee tabled the item.

April 26, 2018 Committee requested to see the proposal language as a modification to the 18 IBC

for review. The committee tabled the item.

Testimony: Kenneth Ball, NEMA

May 17, 2018 Committee approved the proposal as modified and submitted by the proponent.

Board review:

Nov. 7, 2018 Board discussed the committee’s recommendation.

May 1, 2019 Proponent provided additional, extended testimony.

Feb. 6, 2019 Board received more testimony and ultimately disapproved the proposal.

Disapproved proposal

915.5 Carbon monoxide alarms. | OR A: doesn't adopt NFPA 720 section 9.4.2.2. (14 OSSC 908.7) Retained OR A

915.6 Group R. | OR A: separated out Group R provisions and added a Group R section. (14 OSSC 908.7.2)

Committee review:

April 12, 2018 Committee tabled the item.

April 26, 2018 Committee tabled the item.

May 17, 2018 Committee rescinded the existing amendments.

Board review:

Nov. 7, 2018 Board affirmed the committee’s recommendation.

Feb. 6, 2019 Board received more testimony, reversed the committee’s recommendation, and

retained the existing amendment.

Rescinded OR A

917 Mass Notification Systems. | IBC CH | Fiscal impact: Approx. $5,000 increase Approved IBC CH*

Chapter 10

1003.2 Ceiling height. | OR A: added hallways and corridors to exception. ~ Fiscal impact: Slight increase. Rescinded OR A *

1004.2 Cumulative Occupant Loads. | IBC CH Approved IBC CH

T. 1004.5 Maximum Floor Area Allowances per Occupant. | IBC CH Approved IBC CH

1006 Number of Exits and Exit Access Doorways. | IBC CH Approved IBC CH

1007 Exit and Exit Access. Doorway Configuration. | IBC CH |

Public proposal no. OSSC-31 | Heather Christenson, OBOA

Committee review:

March 15, 2018 Committee agreed to forward the proposal for review.

April 26, 2018 Committee disapproved the proposal and approved the IBC CH.

Board review:

Nov. 7, 2018 Board affirmed the committee’s recommendation.

Approved IBC CH

Disapproved proposal

1006.3 SCI 11-03 | Emergency power illumination in warehouse applications. Retained Interp

1008.1.2 Door Swing. | Public proposal no. OSSC-32 ~ Jesse Emory, GBD Architects

Committee review:

March 15, 2018 Committee agreed to forward the proposal for review.

April 26, 2018 Committee disapproved the proposal.

Board review:

Nov. 7, 2018 Board affirmed the committee’s recommendation.

Disapproved proposal

1010.1.4.4 Locking Arrangements in Educational Occupancies. | IBC CH Approved IBC CH

1010.1.9 Door operations. | IBC CH | Fiscal impact: Slight increase. Approved IBC CH*

1010.1.10 Panic and fire hardware. | OR A: modified. Retained OR A

2019 Oregon Structural Specialty Code Board review matrix

Page 8 of 21

Section Subject and description of change Board outcomes

1009.16 Stairways to roof. | Public proposal no. OSSC-33 ~ Eric Bressman, Ankrom Moisan Architects

(14 OSSC 1009.16)

Committee review:

March 15, 2018 Committee requested more detailed fiscal analysis.

March 29, 2018 Committee agreed to forward the proposal for review.

April 26, 2018 Committee approved the proposal as modified by removing the structural language

in the proposal and adopt the proposal to allow an alternating tread device, a ship

stair or ladder that is constructed of “noncombustible material” rather than “steel.”

Board review:

Nov. 7, 2018 Board affirmed the committee’s recommendation.

Approved proposal as

modified

1011.15 Ship Ladders, Ladders. Approved IBC CH

T. 1017.2 Exit Access Travel Distance. | OR A: added note D. Rescinded OR A

1017.2.2 Groups F-1 and S-1 increase. | IBC CH Approved IBC CH

1018.1 Construction. | OR A: modified – adds exception. (14 OSSC 1017.1.) Rescinded OR A

1018.3 Aisles in Groups B and M. | IBC CH Approved IBC CH

1023.3.1 Extension. | IBC CH ~ * Fiscal impact: Slight decrease. Approved IBC CH*

Chapter 11

1101.2.1 Alternate Methods. | OR A: added sections. Retained OR A

1103.1 SCI 95-04 | Accessibility requirements. - church baptisteries Retained OR A

1103.2.8 Areas in Places of Religious Worship. | IBC CH Approved IBC CH

1103.2.14 Access to Walk-In Coolers. | IBC CH Approved IBC CH

1103.2.16 Private membership clubs and churches. | OR A: added section. Retained OR A

1104.4 Multistory-Multilevel buildings and facilities. | OR A: modified. Retained OR A

1104.4 Multistory Buildings and Facilities. | IBC CH Approved IBC CH

1104.5 Elevators Required. | OR A: added section. Retained OR A

T. 1106.1 Accessible Parking Spaces. | OR A: added. Retained OR A

1106.5 Van Spaces. | OR A: added sentence. Retained OR A

1106.7 Parking spaces. | OR A: added section. Retained OR A

1106.8.2.1 Group I-2. | OR A: added section. Retained OR A

1107.3/4 Accessible Spaces and Routes. | IBC CH Approved IBC CH

1107.5 Group I-1. | OR A: modified and added language. (DHS Alignment) Retained OR A

1107.5.1.1 Accessible Units in ALFs. | IBC CH Approved IBC CH

1107.6.1.1 Group R – Accessible Units. | IBC CH Retained OR A

1107.6.4 Group R-4. | OR A: modified and added language. Retained OR A

1108.2 Assembly area seating. | OR A: modified. Retained OR A

1108.2.9 Dining and drinking areas. | OR A: deleted exception 2. Retained OR A

1108.2.9.1 Dining and drinking areas. | OR A: added language. Retained OR A

1109.2.1.2 Family or Assisted-Use Toilet Rooms. | IBC CH Approved IBC CH

2019 Oregon Structural Specialty Code Board review matrix

Page 9 of 21

Section Subject and description of change Board outcomes

Privacy. | Public proposal no. OSSC-35 ~ Jason Phelps

Committee review:

March 15, 2018 Committee requested more detailed fiscal analysis.

March 29, 2018 Committee agreed to forward the proposal for review.

April 26, 2018 Committee approved the proposal as modified by the following:

“Doors to single-user, an occupied indicator in accordance with Section 1010.1.9.6.”

And not include a change in Chapter 11. In Chapter 12 add to Section 1209.3.1:

"Single-Use Toilet and Bathing Rooms"

*Fiscal impact: $50 per door increase.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved IBC CH as

modified*

1109.2 Accessible Water Closet Compartments. | IBC CH Approved IBC CH

1109.2.3 Accessible Lavatories. | IBC CH Approved IBC CH

1109.15 Gaming Machines and Gaming Tables. | IBC CH Approved IBC CH

1110.4.13 Access to Children’s Play Areas. | IBC CH Approved IBC CH

1111 Clustered mailboxes. | OR A: added section.

Committee review:

June 12, 2018 Committee retained the existing amendment and requested clearer language

showing that the intent was for exterior use.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Retained OR A

Chapter 12

1204.1 Lighting, General. | IBC CH Approved IBC CH

93-94 | Moisture proofing in toilet rooms. Retained Interp

1210.4 Fixture clearances. | OR A: added section. Retained OR A

Chapter 14

1403.2.1 Exterior wall envelope drainage. | Public proposal no. OSSC-37 ~ Johnathan Balkema, OBOA

Committee review:

March 15, 2018 Committee requested more detailed fiscal analysis.

March 29, 2018 Committee agreed to forward the proposal for review.

June 12, 2018 Committee voted to disapproved the proposal.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Disapproved proposal

1402.5 Vertical and lateral flame propagation. | OR A: modified and added exceptions. Rescinded OR A

1404.3 Vapor retarders. | IBC CH Approved IBC CH

1404.3.1 Class III Vapor Retarders. | OR A: modified table and added notes. Retained OR A

1404.6.2 Seismic requirements. | OR A: added language. | (14 OSSC 1405.6.2)

Public proposal no. OSSC-38 ~ Tom Young, Northwest Concrete Masonry

Public proposal no. SEAO-2 ~ SEAO

Committee review:

March 15, 2018 Committee requested more detailed fiscal analysis for OSSC-38.

March 29, 2018 Committee agreed to forward the proposal for review.

June 12, 2018 Committee approved both proposals and rescinded the OR A.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Rescinded OR A

Approved proposal

Approved proposal

1404.10.3 Interior adhered masonry veneers. | OR A: added exception. Retained OR A

1405.4 SCI 94-04 | Acceptable window and door sealing methods. Retained Interp

2019 Oregon Structural Specialty Code Board review matrix

Page 10 of 21

Section Subject and description of change Board outcomes

1405.3 Vapor retarders. | OR A: modified and added exceptions. Retained OR A

1406 Metal Composite Materials MCM. | IBC CH Approved IBC CH

1406.3 SCI 07-03 | Stacked decks on buildings of types III, IV, and V construction. Retained Interp

1407.4.1 EIFS. | OR A: modified. Retained OR A

1408 SCI 08-01 | Use of exterior insulation and finish systems. Retained Interp

Chapter 15

1509.7.2 Structural Fire Resistance. | OR A: modified and deleted Sections 1509.7.3 and 7.4. Rescinded OR A

1510.3.1 Reroofing inspection. | OR A: added section. Retained OR A

1510.3.2 Final Inspection. | OR A: added section. Retained OR A

1512 Solar Photovoltaic. | OR A: deleted. Retained OR A

Chapter 16

1602.1 Notations. | OR A: modified “E” to include seismically induced lateral earth pressure and deleted “Fa” Flood

Load notation.

Note: Section 2.3.6 of ASCE 7-16 via ’18 IBC CH now specifically addresses, includes and clarifies this

requirement. Flood Load, Fa is specific to ASCE 7-16 requirements/load combinations.

Retained OR A

1603.1 General. | IBC CH | OR A: modified by deleting item #5, providing flood design data on CDs for

conventional light-frame construction located in flood hazard area.

Approved IBC CH

Retained OR A

1603.1.3 Roof Snow Load data. | IBC CH Approved IBC CH

1603.1.4 Wind design data. | IBC CH Approved IBC CH

1603.1.7 Flood design data. | OR A: deleted this section. Retained OR A

1603.1.8 Special loads. | IBC CH Approved IBC CH

1603.1.8.1 Photovoltaic panel systems. | IBC CH Approved IBC CH

1603.1.9 Roof rain load data. | IBC CH Approved IBC CH

1603.1.9 Systems and components requiring... | IBC CH Approved IBC CH

T. 1604.3 Deflection Limits. | IBC CH Approved IBC CH

1604.3 Serviceability. | IBC CH Approved IBC CH

1604.3.3 Steel. | IBC CH Approved IBC CH

1604.3.7 Framing supporting glass. | IBC CH Approved IBC CH

1604.4 Analysis. | OR A: modified and added language regarding rigid diaphragm determination. |

IBC CH | OR A is no longer necessary.

Rescinded OR A

Approved IBC CH

1604.5 Risk category. | IBC CH Disapproved IBC CH

1604.5 Risk category. | IBC CH Approved IBC CH

T. 1604.5 Risk category of buildings and other structures. | IBC CH Approved IBC CH

1604.5.1 Multiple Occupancies. | IBC CH Approved IBC CH

1604.9 Counteracting Structural Actions. | IBC CH Approved IBC CH

2019 Oregon Structural Specialty Code Board review matrix

Page 11 of 21

Section Subject and description of change Board outcomes

Wind and seismic detailing. | Public proposal no. SEAO-03 ~ SEAO

Committee review:

May 17, 2018 Committee approved the proposal.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved proposal

1604.10 Storm Shelters. | IBC CH: added a new section.

Committee review:

May 17, 2018 Approved the IBC CH.

Board review:

Nov. 7, 2018 Disapproved the IBC CH because it is not applicable in Oregon.

Disapproved proposal

1605.2.1 Other loads. | OR A: modified. | No longer necessary. Rescinded OR A

1605.3.1.2 Other loads. | OR A: modified. | No longer necessary. Rescinded OR A

1605.3.2.1 Other loads. | OR A: modified. Retained OR A

T. 1607.1 Minimum Live Loads. | IBC CH | OR A: modified | Public proposal no. SEAO-06 ~ SEAO

Committee review:

May 17, 2018 Committee approved the IBC code changes, approved the proposal, and retained

item #31 for storage loads and item #36 for exterior foot bridges from the existing

Oregon amendment. Fiscal impact: Slight increase for wood balconies.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved IBC CH*

Approved proposal

Retained OR A

1607.10.3 Elements supporting hoists for facade acces... | IBC CH Approved IBC CH

1607.10.4 Fall arrest and lifeline anchorages. | IBC CH Approved IBC CH

1607.13.3 Occupiable roofs. | IBC CH Approved IBC CH

1607.13.5 Interior walls and partitions. | IBC CH Approved IBC CH

1607.15 Fire walls. | IBC CH Approved IBC CH

1607.15.2 Photovoltaic panel systems. | IBC CH Approved IBC CH

306, 311 SAM 16-08 | Electronic snow load locator.

Use of the Oregon electronic snow load map as created by the SEAO as an alternate method to the snow load

provisions.

Rescinded SAM

1608.1 General. | OR A: modified. | Public proposal no. SEAO-10 ~ SEAO

Committee review:

May 17, 2018 Committee approved the proposal and rescinded the OR A.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Rescinded OR A

Approved proposal

1608.2 Ground Snow Loads. | OR A: modified | public proposal no. SEAO-09 ~ SEAO

Committee review:

May 17, 2018 Committee approved the proposal and rescinded the OR A.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Rescinded OR A

Approved proposal

1609 Wind Loads. | IBC CH | The IBC maps allow site-specific wind speeds to be determined from

https://hazards.atcouncil.org/ via Note 6 on Figures 1609.3 (1-4). Special wind regions identified on the maps

fall to local jurisdiction for design wind speed determination.

Disapproved IBC CH

1609 Figures A, B, C: Ultimate Wind Speed. | OR A: added Oregon specific figures on ultimate design wind

speed. – See item #45 below.

Retained OR A

2019 Oregon Structural Specialty Code Board review matrix

Page 12 of 21

Section Subject and description of change Board outcomes

1609.1.1 Determination of wind loads. | IBC CH | Public proposal no. SEAO-11 ~ SEAO

Committee review:

May 17, 2018 Tabled the item and requested more information.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved IBC CH

Approved proposal

1609.1.1 Wind Tunnel Test Adoption. | Public proposal no. SEAO-30 ~ SEAO

Committee review:

May 17, 2018 Committee approved the proposal as modified by removing exception #7 and

everything after.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved proposal as

modified

1610.1 Soil lateral loads. | OR A: added clarifying language when ascending backfill slope is present. Retained OR A

1612.1 Flood loads. | OR A: modified in alignment with ORS. Retained OR A

1612.3 Establishment of flood hazard areas. | OR A: modified. Retained OR A

1612.3.1 Design flood elevations. | OR A: deleted. Determination of impacts. | OR A: deleted. Retained OR A

1613.1 SAM 08-02 | Power actuated fasteners. Retained SAM

1613.1 SCI 10-01 | Construction requirements for suspended ceiling systems. Retained Interp

1613.1 Earthquake loads. - Scope. | IBC CH | Public proposal no. SEAO-04 ~ SEAO

Committee review:

May 17, 2018 Committee approved the IBC CH and the proposal.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved IBC CH

Approved proposal

1613.2.3 ASCE 7-16 Modifications. | Public proposal no. SEAO-40 ~ SEAO

Committee review:

May 17, 2018 Committee approved the proposal.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved proposal

1613.3 Ballasted Photovoltaic Panel Systems. | IBC CH Approved IBC CH

1613.3.5.1 Alternative seismic design category determination. | IBC CH Approved IBC CH

1613.3.1 Mapped acceleration parameters. | OR A: modified. Retained OR A

F.

1613.3.1(1)

Risk targeted maximum considered earthquake. | OR A: replaced. Retained OR A

F.

1613.3.1(2)

Risk targeted maximum considered earthquake. | OR A: replaced. Retained OR A

1613.4 Alternatives to ASCE 7. | IBC CH Approved IBC CH

1613.5.5 ASCE 7-16 modification. | Public proposal no. SEAO-12 ~ SEAO

Committee review:

May 17, 2018 Committee approved the proposal.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved proposal

2019 Oregon Structural Specialty Code Board review matrix

Page 13 of 21

Section Subject and description of change Board outcomes

1613.5 Modifications to ASCE 7-10. | OR A: added section.

Committee review:

May 17, 2018 Committee Retained OR A existing amendments in Sections 1613.5.4, 1613.5.5,

1613.5.6, 1613.5.7, 1613.5.8, 1613.5.9, 1613.5.10, and 1613.5.12.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Retained OR A

1613.5.1 ASCE 7 modification replaces. | Public proposal no. SEAO-13 ~ SEAO

Committee review:

May 17, 2018 Committee approved the proposal.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved proposal

1613.5.2 Clarification of component anchorage requirements. | Public proposal no. SEAO-14 ~ SEAO

Committee review:

May 17, 2018 Committee approved the proposal.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved proposal

1613.5.3 ASCE 7-10. | Public proposal no. OSSC-39 ~ Jon-Paul Cardin, American Iron and Steel Institute

Committee review:

March 15, 2018 Committee requested more detailed fiscal analysis.

March 29, 2018 Committee agreed to forward the proposal for review.

May 17, 2018 Committee approved the proposal.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved proposal

1613.5.3 ASCE 7 modification repeal. |

Public proposal no. OSSC-39 ~ Jon-Paul Cardin, American Iron and Steel Institute

Public proposal no. SEAO-15 ~ SEAO

Committee review:

May 17, 2018 Committee approved both of the proposals.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved proposal

1613.5.11 ASCE 7 modification repeal. | Public proposal no. SEAO-23 ~ SEAO

Committee review:

May 17, 2018 Committee approved the proposal.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved proposal

1613.5.13 ASCE 7 modification repeal. | Public proposal no. SEAO-25 ~ SEAO

Committee review:

May 17, 2018 Committee approved the proposal.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved proposal

1613.6 Earthquake recording instrumentation. | Public proposal no. SEAO-27 ~ SEAO (14 OSSC 1613.7)

Committee review:

May 17, 2018 Committee approved the proposal as modified to align with OAR 632-001-0012.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved modified

proposal

1613.6 Amendment to ASCE 7-05. | OR A: added section requiring suspended ceilings less than 1,000 sq. ft. in

SDC D-F have horizontal restraint to the structural system/framing.

Retained OR A

2019 Oregon Structural Specialty Code Board review matrix

Page 14 of 21

Section Subject and description of change Board outcomes

1613.7 Earthquake recording instruments. | OR A: added section.

Committee review:

May 17, 2018 Committee retained OR A the existing amendment as modified by item no. 71

(above).

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Retained OR A as

modified

1615

Tsunami Loads. | IBC CH: added a new section |Public proposal no. SEAO-05 ~ SEAO

Committee review:

May 17, 2018 Disapproved the IBC CH code change.

Board review:

Feb. 6, 2019 Board affirmed the committee’s recommendation to disapprove the IBC code

change and approved the division’s proposed changes to 1615.1 identifying the

buildings and structures required to be designed and constructed in accordance with

Chapter 6 of ASCE 7, where they are located in a DOGAMI-established tsunami

inundation zone.

Disapproved IBC CH

Disapproved proposal

New OR A

Chapter 17

1704.2.5.1 Fabricator approval. | IBC CH | OR A: added “by a nationally recognized accrediting authority.” Approved IBC CH

Retained OR A

1704.3 Statement of special instructions. | IBC CH Approved IBC CH

1704.5 Submittals to the Building Official. | IBC CH Approved IBC CH

1704.6.1 Structural observation. | IBC CH Approved IBC CH

1705.2 Steel construction. | IBC CH Disapproved IBC CH

1705.2 Steel construction. | OR A: modified. Maintain OR A. Retained OR A the Table. Retained OR A

1705.2.3 Open Web Steel Joists and Joist Girders. | IBC CH | Fiscal impact: Greater than 0.1% increase. Approved IBC CH*

1705.3 Required Special Inspections of Concrete Construction. | IBC CH Approved IBC CH

1705.5.2 Metal-plate-connected Wood Trusses. | IBC CH

SEE IBC Errata – This was withdrawn by proponent and subsequently changed back to model code but does

appear in first printing of 2018 iteration.

Approved Errata

1705.11 Special inspections for wind resistance. | IBC CH Approved IBC CH*

1705.12 Special Inspections for seismic resistance. | IBC CH | OR A | Public proposal no. SEAO-32 ~ SEAO

Committee review:

May 17, 2018 Approve the model code language, rescind the Oregon Amendment, disapprove the

proposal. ~ *Fiscal impact: 10% of the production 0.5% cost allocated to special

inspections.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved IBC CH*

Rescinded OR A

Disapproved proposal

1705.12.1 Structural steel. | Public proposal no. SEAO-33 ~ SEAO (14 OSSC 1705.11.1)

Committee review:

May 17, 2018 Approved as modified by adding only “In addition to the quality assurance

requirements contained in AISC 341, Chapter J, Section J5 Inspection Tasks., the

requirements of Section 1705.2 and Table 1705.2 of the Building Code shall

apply.”

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved proposal as

modified

2019 Oregon Structural Specialty Code Board review matrix

Page 15 of 21

Section Subject and description of change Board outcomes

1705.12.2

1705.12.3

1705.12.5

Structural wood. | Public proposal no. SEAO-34 ~ SEAO

Committee review:

May 17, 2018 Committee approved the proposal. ~ *Fiscal impact: Slight decrease.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved proposal*

1705.12.6 Plumbing, mechanical and electrical components. | IBC CH ~ *Fiscal impact: Less than or equal to 1%

increase of the special inspections cost.

Approved IBC CH*

1705.12.9 Cold-formed steel special bolted moment frames. | IBC CH Approved IBC CH

1705.13.2 Nonstructural components – Seismic qualification. | Public proposal no. SEAO-36 ~ SEAO

Committee review:

May 17, 2018 Committee approved the proposal.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved proposal

1705.13.3 Designated seismic systems. | Public proposal no. SEAO-37 ~ SEAO

Committee review:

May 17, 2018 Committee approved the proposal. ~ *Fiscal impact: Slight decrease.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved proposal*

1705.18 Radon Mitigation Inspections. | OR A: added section. Retained OR A

1705.18.1 Soil-Gas-Retarder Membrane. | OR A: added section. Retained OR A

1705.18.2 Sealing of construction joints, penetrations. | OR A: added section. Retained OR A

1708 Test safe load. | IBC CH Approved IBC CH

1708.2.2 Static Load Testing. | IBC CH Approved IBC CH

1709.5 Exterior Window and Door Assemblies. | IBC CH Approved IBC CH

1711 Material and Test Standards. | IBC CH Approved IBC CH

Chapter 18

1803.2 Investigations required. | OR A: added language.

Tsunami inundation zone. | OR A: added language. | Note: BCD moved to Chapter 16

Retained OR A

Retained OR A

1803.3.2 Seismic site hazard investigation. | OR A: added section. Retained OR A

1803.3.2.1 Design earthquake. | OR A: added section. Retained OR A

1803.5.6 Rock strata. | IBC CH Approved IBC CH

1803.5.7 Excavation near foundations. | IBC CH | Fiscal impact: $3,000 increase per report. Approved IBC CH*

1803.5.12 Seismic Design Categories D through F. | OR A: added language. Rescinded OR A

1803.5.13 Seismic Design Categories D through F. | Public proposal no. SEAO-38 ~ SEAO

Committee review:

May 17, 2018 Committee approved the proposal.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved proposal

1803.7 Seismic site hazard report. | OR A: added section. Retained OR A

1803.8 Seismic site hazard report review. | OR A: added section. Retained OR A

1803.9 Seismic site hazard report submittal. | OR A: added section. Retained OR A

1804.1 Excavation Near Foundations. | IBC CH Approved IBC CH

2019 Oregon Structural Specialty Code Board review matrix

Page 16 of 21

Section Subject and description of change Board outcomes

1804.2 Underpinning. | IBC CH Approved IBC CH

1804.2.1 Underpinning sequencing. | IBC CH | Fiscal impact: $100 increase. Approved IBC CH*

1804.4 Site Grading. | IBC CH Approved IBC CH

1804.8 Under-floor drainage. | OR A: added section. Retained OR A

1805.1.2.1 Flood Hazard Areas. | OR A: deleted. Retained OR A

1807.2 Retaining Walls. | IBC CH Approved IBC CH

1808.3.2 Surcharge. | IBC CH Approved IBC CH

1808.8.5.1 Grounding of foundation rebar. | OR A: added section. Retained OR A

1810.2.5 Group effects. | IBC CH Approved IBC CH

1810.3.2.3 Steel. | IBC CH Approved IBC CH

1810.3.3.1.6 Allowable uplift load of grouped deep foundation elements. | IBC CH Approved IBC CH

1810.3.5.3.2 Fully welded steel piles fabricated from plates. | IBC CH Approved IBC CH

1810.3.5.3.3 Structural steel sheet piling. | IBC CH Approved IBC CH

1810.3.8.3 Precast Prestressed Piles. | IBC CH Approved IBC CH

1811 Radon control methods public buildings. | OR A: added section. Retained OR A

1812 Radon control methods R-2 and R-3 occupancies. | OR A: added section. Retained OR A

Chapter 19

1901.2 Plain and reinforced concrete. | IBC CH Approved IBC CH

1901.3 Anchoring to concrete. | IBC CH Approved IBC CH

1901.4 Composite structural steel and concrete structures. | IBC CH Approved IBC CH

1904 Durability requirements. | IBC CH Approved IBC CH

1905 Modifications to ACI 318. | IBC CH Approved IBC CH

1909.1 SCI 2011-01 | Power actuated fasteners for suspended ceilings and concrete. Retained Interp

2100 Masonry. | IBC CH Approved IBC CH

2104.1 Construction. | Public proposal no. OSSC-40 ~ Tom Young, Northwest Concrete Masonry

Committee review:

March 15, 2018 Committee requested more detailed fiscal analysis.

March 29, 2018 Reviewed the submitted information and Committee agreed to forward the

proposal for review.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved proposal

2111 Masonry Fireplaces. | IBC CH Approved IBC CH

2113 Masonry Chimneys. | IBC CH Approved IBC CH

Chapter 22

2201.1 Scope. | IBC CH Approved IBC CH

2207.1 General. | IBC CH Approved IBC CH

2209.2 Cantilevered Steel Storage Racks. | IBC CH Approved IBC CH

2210.1.1.3 Composite slabs on steel decks. | IBC CH Approved IBC CH

2019 Oregon Structural Specialty Code Board review matrix

Page 17 of 21

Section Subject and description of change Board outcomes

2211 Cold-Formed Steel Light-Frame Construction. | IBC CH Approved IBC CH

Chapter 23

2300 Tall Wood Building Code | Public proposal no. OSSC-10 | Samir Mokashi, Code Unlimited, LLC

Committee review:

March 15, 2018 Committee agreed to forward the proposal for review.

April 12, 2018 Tabled the item.

April 26, 2018 Committee approved the proposal.

Testimony: Tien Peng, NRMCA

Testimony: James Bela, Oregon Earthquake Awareness

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved proposal as

modified

SAM 2009-01 | Western Juniper. Retained SAM

2303.1.4 Structural Glued Cross-Laminated Timber. | IBC CH: added a new subsection referring to ANSI/APA

PRG 320.

Committee review:

May 17, 2018 Approved IBC CH code as modified by adopting an amendment in Chapter 35

revising the edition of ANSI/APA PRG 320 to the 2018 edition.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Approved IBC CH as

modified

2303.1.13 Engineered Wood Rim Board. | IBC CH Approved IBC CH

2303.2.2 Fire-Retardant-Treated Wood. | IBC CH Approved IBC CH

2303.6 Nails and Staples. | IBC CH Approved IBC CH

2304.11 Heavy timber construction. | IBC CH Approved IBC CH

2304.12 Protection Against Decay and Termites. | IBC CH Approved IBC CH

T. 2304.10.1 Fastening Schedule. | IBC CH Approved IBC CH

2304.10.5.1 Fasteners and connectors in contact with PT or FRT wood. | IBC CH

Fiscal impact: Slight increase.

Approved IBC CH*

2304.10.6 Load Path. | IBC CH Approved IBC CH

2304.12.2.5 Supporting Members for Permeable Floors and Roofs. | IBC CH Approved IBC CH

2304.6 Exterior Wall Sheathing. | IBC CH Approved IBC CH

T. 2304.10.1 Fastening Schedule. | OR A: modified. Rescinded OR A

T. 2304.9.3.2 Fastening Schedule for Mechanically Laminated Decking. | IBC CH Approved IBC CH

2308 Conventional Light-Frame Construction. | IBC CH | OR A | Aligns with 18 IBC. Approved IBC CH

2308.3.1 Foundation plates or sills. | IBC CH Approved IBC CH

T. 2308.4.1.1 Headers and Girder Spans - Exterior Walls. | IBC CH Approved IBC CH

T. 2308.4.1.1 Headers and Girder Spans - Interior Walls. | IBC CH Approved IBC CH

2308.5.5.1 Openings in Exterior Bearing Walls. | IBC CH Approved IBC CH

2309 Wood Frame Construction Manual. | IBC CH Approved IBC CH

Chapter 26

2406.4.7 Safety Glazing Adjacent to Bottom Stair Landing. | IBC CH Approved IBC CH

2014-02 Safety Glazing Tub and Shower Enclosures. Retained OR A

2019 Oregon Structural Specialty Code Board review matrix

Page 18 of 21

Section Subject and description of change Board outcomes

2407.1 Structural Glass Baluster Panels. Materials. | IBC CH Approved IBC CH

SCI 1994-01 | Building within a building. Retained

2603.10.1 Exterior Walls. | OR A: deleted. Rescinded OR A

2603.13 Cladding Attachment over Foam Sheathing to Wood Framing. | IBC CH Approved IBC CH

Chapter 27

2702.1 Installation. | OR A: added exception. Rescinded OR A

2702.2.3 Emergency Responder Radio Coverage System. | IBC CH Approved IBC CH

2702.2.21 Group I-2. | OR A: added section. Rescinded OR A

2702.3 Critical Circuits. | IBC CH Approved IBC CH

Chapter 29

2901.1 Scope. | OR A: modified. Retained OR A

2902 Minimum Plumbing Facilities. | IBC CH

Committee review:

March 15, 2018 Approved the IBC CH code; use the 18 IBC Table and Retained OR A the drinking

fountain column, delete “other” column, and maintain the existing footnote

amendments.

Board review:

Nov. 7, 2019 Committee approved the proposal as modified.

Approved IBC CH as

modified

2902.1 Minimum number of fixtures. Table 2902.1 (See 2902) Rescinded OR A

2902.2 Separate facilities. | OR A: added exception. Retained OR A

2902.2 Separate facilities. | Public proposal no. OSSC-41 ~ Tom Schmidt, Hacker Architects

Committee review:

March 15, 2018 Committee agreed to forward the proposal for review.

March 29, 2018 Committee agreed to forward the proposal for review.

June 12, 2018 Committee approved the proposal as modified – add ‘shall be based on separate

facilities.’

Board review:

Nov. 7, 2018 Disapproved the proposal.

Disapproved proposal

2902.3 Public Toilet Facilities. | IBC CH Approved IBC CH

2902.3.3 Location of toilet facilities in occupancies other than malls. | OR A: added exception. Retained OR A

2902.5 Drinking fountain locations. | OR A: modified.

Committee review:

June 12, 2018 Committee adopted a new OR A deleting the section.

Board review:

Aug. 1, 2018 Board affirmed the committee’s recommendation.

Rescinded OR A

New OR A

2903 Alteration of existing group A, M &E Occupancies. | OR A: added section. Rescinded OR A

Chapter 30

3001.2 Emergency Elevator Communications Systems. | IBC CH ~*Fiscal impact: $5,000 increase per elevator.

(Note: Section is deleted due to authority.)

Approved IBC CH*

3001.2 Reference standards. | OR A: modified and added language. Retained OR A

3003.1.3 Two or more elevators. | OR A: modified. Retained OR A

3004 Elevator hoistway venting. | IBC CH Approved IBC CH

3004.1 Vents required. | OR A: modified to clarify the measurement. Rescinded OR A

2019 Oregon Structural Specialty Code Board review matrix

Page 19 of 21

Section Subject and description of change Board outcomes

3004.2 Location of vents. | OR A: added language. Rescinded OR A

3004.4 Plumbing and mechanical systems. | OR A: modified and deleted exception. Retained OR A

Rated Corridors. | Public proposal no. OSSC-42 ~ Justin Schmidt, Interior Tech Withdrawn by

proponent

Chapter 31

3111 Solar Energy Systems. | IBC CH: added a new section covering "solar energy systems."

Solar photovoltaic panels/modules. | OR A: added a section incorporating provisions from the now fully

integrated Solar Code regarding photovoltaic panels and modules.

Committee review:

June 12, 2018 Retained OR A the existing amendment, with necessary updates, and add a

requirement for “accessible ground level disconnect.”

Board review:

Nov. 7, 2018 Board affirmed the committee’s recommendation.

Final outcome: Accepted the IBC CH and retained the OR A. (Note Accessible ground level

disconnect provisions could not be added because it is regulated by the Oregon

Electrical Specialty Code.)

Retained OR A as

modified

3111.1.1 Wind tunnel testing for solar panels. | Public proposal no. SEAO-50 ~ SEAO

Committee review:

June 12, 2018 Committee approved the proposal.

Board review:

Nov. 7, 2018 Committee approved the proposal.

Final outcome: Added to the charging statement in Section 3111.1

Approved proposal

3113 Relocatable Buildings. | IBC CH: added a new section. Disapproved IBC CH

3314 Fire Watch during Construction. | IBC CH

Committee review:

June 12, 2018 Disapproved the IBC CH code language.

Board review:

Nov. 7, 2018 Board affirmed the committee’s recommendation.

Disapproved IBC CH

3400 Existing Structures. | IBC CH: deleted. This chapter has been removed completely.

Committee review:

June 12, 2018 Approved the IBC change and adopted the 18 IEBC where it doesn’t create

substantial increases in cost, incorporate the existing Oregon amendments and

Approved proposed amendments as discussed where it does not conflict with

statutory requirements.

Board review:

Nov. 7, 2018 Tabled for more information.

Feb. 6, 2019 Approved the draft Chapter 34 presented at the board meeting.

Approved IBC CH as

modified

IEBC 301.3 Alteration, addition or change of occupancy. | Public proposal no. SEAO-42 ~ SEAO

Committee review:

June 12, 2018 Disapproved the proposal.

Board review:

Feb. 6, 2019

Disapproved proposal

2019 Oregon Structural Specialty Code Board review matrix

Page 20 of 21

Section Subject and description of change Board outcomes

IEBC 303.3.2 Compliance alternatives. | Public proposal no. OSSC-45 ~Scott Caufield, Clackamas County

Committee review:

March 15, 2018 Committee agreed to forward the proposal for review.

June 12, 2018 Committee approved the proposal.

Board review:

Nov. 7, 2018 Tabled for more information.

Feb. 6, 2019 Board affirmed the committee’s recommendation.

Approved proposal

IEBC 302.5 New and replacement materials. | Public proposal no. SEAO-43 ~ SEAO

Committee review:

June 12, 2018 Committee approved the proposal.

Board review:

Nov. 7, 2018 Tabled for more information

Feb. 6, 2019 Board affirmed the committee’s recommendation.

Approved proposal

IEBC 302.7 Seismic loads for Change of Occupancy. | Public proposal no. SEAO-44 ~ SEAO

Committee review:

June 12, 2018 Committee approved the proposal. Vote: 5/3 and 1 abstain.

Fiscal impact: $20K increase per floor.

Board review:

Nov. 7, 2018 Tabled for more information.

Feb. 6, 2019 The board received more testimony about BCD’s statutory authority and

disapproved the proposal.

Disapproved proposal

IEBC 303.3.2 Removes Appendix A as optional compliance method. | Public proposal no. SEAO-45 ~ SEAO

Committee review:

June 12, 2018 Committee approved the proposal.

Board review:

Nov. 7, 2019 Tabled for more information.

Feb. 6, 2019 Board affirmed the committee’s recommendation.

Approved proposal

IEBC 401.2 Existing Building Repair. | Public proposal no. OSSC-44 ~ Scott Caufield, Clackamas County

Committee review:

March 15, 2018 Committee agreed to forward the proposal for review.

June 12, 2018 Committee approved the proposal as modified by adding “legally existing.”

Board review:

Nov. 7, 2018 Tabled for more information

Feb. 6, 2019 Board affirmed the committee’s recommendation.

Approved proposal as

modified

IEBC 405.2.1 Repairs for less than substantial structural damage. | Public proposal no. SEAO-46 ~ SEAO

Committee review:

June 12, 2018 Committee approved the proposal as modified by adding “structural.”

Board review:

Nov. 7, 2018 Tabled for more information.

Feb. 6, 2019 Board affirmed the committee’s recommendation.

Approved proposal as

modified

IEBC 506.4.3 Seismic loads and seismic force-resisting system. | Public proposal no. SEAO-47 ~ SEAO

Committee review:

June 12, 2018 Committee approved the proposal.

Board review:

Nov. 7, 2018 Tabled for more information.

Feb. 6, 2019 Board disapproved the proposal due to statutory conflict and unspecified fiscal

impact from the existing Chapter 34 allowances.

Approved proposal

2019 Oregon Structural Specialty Code Board review matrix

Page 21 of 21

Section Subject and description of change Board outcomes

14OSSC 3408 Compliance. | Public proposal no. OSSC-43 ~ Warren Jackson, Marion County

Committee review:

March 15, 2018 Committee agreed to forward the proposal for review.

June 12, 2018 Committee approved the proposal.

Board review:

Nov. 7, 2018 Tabled for more information.

Feb. 6, 2019 Board affirmed the committee’s recommendation.

Approved proposal

IEBC 706.3.1 Bracing for unreinforced masonry bearing wall parapets. | Public proposal no. SEAO-48 ~ SEAO

Committee review:

June 12, 2018 Committee approved the proposal.

Board review:

Nov. 7, 2018 Tabled for more information.

Feb. 6, 2019 Board affirmed the committee’s recommendation.

Approved proposal

IEBC 1006.3 Seismic loads. | Public proposal no. SEAO-49 ~ SEAO

Committee review:

June 12, 2018 Committee approved the proposal.

Board review:

Feb. 6, 2019 Board disapproved the proposal due to statutory conflict and unspecified fiscal

impact from the existing Chapter 34 allowances.

Disapproved proposal

App A Employee qualifications. | Not adopted by OR but can be adopted locally. Retained OR A

App B Board of Appeals. | Not adopted by OR Abut can be adopted locally. Retained OR A

App C Group U – Agricultural Buildings. | OR A: modified scope. Retained OR A

App D Fire Districts. | Not adopted by OR but can be adopted locally. Retained OR A

App E Supplementary accessibility requirements. | Not adopted by OR and cannot be adopted locally. Retained OR A

App F Rodent proofing. | Not adopted by OR but can be adopted locally. Retained OR A

App G Flood-resistant construction. | Not adopted by OR Abut can be adopted locally. Retained OR A

App H Signs. | Not adopted by OR but can be adopted locally. Retained OR A

App I Patio covers. | OR adds modified and new language. Retained OR A

App J Grading. | Not adopted by OR but can be adopted locally. Retained OR A

App K Administrative provisions. | Not adopted by OR and cannot be adopted locally. Retained OR A

App L Earthquake recording instrument. | Not adopted by OR and cannot be adopted locally. Retained OR A

App M Tsunami-generated flood hazard. | Not adopted by OR and cannot be adopted locally. Retained OR A

App N Guidelines for Replicable Buildings. | New appendix. Not adopted by OR. Disapproved IBC

CH

App O Tsumani loads. | Added during 2019 OSSC publishing due to legislation.

App P Tall wood buildings. | Added during 2019 OSSC publishing to incorporate the existing SAM