LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216 Phone: 510-352-9600 1-800-982-4587 Fax: 510-352-6707
www.lvscontrols.com
Project:
Model No.:
Comments:
APPLICATION
FEATURESMOUNTING
LED COMPATIBLE
UL®UL924 LISTEDC US YEAR
WARRANTY
In the past, emergency lights were kept on 24 hours a day to meet life safety codes. Now, you can use a UL 924 listed Emergency Power Control, Model EPC-2-D-FM, to convert normal light fixtures into approved emergency lights. The EPC-2-D-FM saves energy and money while ensuring compli-ance with both life safety and energy codes.
During normal operation, the same dimmer, occu-pancy sensor, dimming panel, or lighting control can switch and dim normal and emergency fixtures on and off simultaneously.
During a utility power interruption, the EPC-2-D-FM automatically bypasses the normal lighting controls, turning the emergency lights ON at full brightness, regardless of dimmer position.
The EPC-2-D-FM is fixture mounted.
Unique, Patented Automatic Diagnostic
Fire Alarm, Remote Test & 0-10V Dimming Option
When the room switch is turned off, the EPC-2-D-FM will run a 2.5 self-test routine, veri-fying that the emergency power source was available and that the EPC-2-D-FM, ballast, and lamp(s) are all functioning correctly. This feature eliminates the need for time-consuming and costly manual monthly testing and is approved for this purpose. This also allows the unit to be installed in remote or inaccessible locations, because the unit does not rely on access to its manual test switch.
Utility & Emergency Power Indicator LED’sSlim, profile allows mounting in most ballast channels.
Isolated 0-10V relay contact ensures full bright-ness during utility power interruption, regardless of dimmer model.
EPC-2-D-FMEmergency Power ControlFor 0-10V & DALI Dimmable Loads
0-10 V Dimmer Compatible
Fire Alarm Tie-In/Overridewww.lvscontrols.com/assets/UL924FAI.pdf
Red Fire Alarm Jumper (see
additional resources)
SPECIFICATIONS
SINGLE LINE DRAWING
WIRING DIAGRAM
ORDERING INFORMATION ADDITIONAL RESOURCES
EPC-2-D-FM Installation SheetFAQ SheetAlternative Wiring SheetTerms & Conditions/Warranty Information
20181215_LVUNV2
LVS, Inc. 2555 Nicholson Street, San Leandro, CA 94577-4216 Phone: 510-352-9600 1-800-982-4587 Fax: 510-352-6707
www.lvscontrols.com
DESIGNATEDEMERGENCY
LIGHT
REGULAR ROOM LIGHTS
EPC-2-DCONTROL
UL 1008Transfer SwitchOr Equivalent
NormalUtility Power
Emergency Power Source
Neutral Not Shown
EPC-2-DCONTROL
NORMALPANEL
Normal Utility Power
EMERGENCYPANEL
$
EPC-2-D
ZONECONTROLLER
Photo-cell D
EMERGENCY HOT
#3 WHITE
NORMAL PANEL
20A
#2 RED
#1 BLACK
*
Relay Panel, Power Pack, Sensor, or other (optional)*
Normal Light (optional)
EMERGENCY PANEL OR INVERTER
20ANORMAL HOT
NORMAL NEUTRALEMERGENCY NEUTRAL#4 WHITE/BLUE
#5 YELLOW
#6 BLUE
Emergency Light
Note: Emergency Light is also called N/E Light or Normal/Emergency
Light by many specifiers
VioletOrange
EMPOWER
TEST
UTILITYPOWER
Note: N/C low voltage yellow wire not shown, cap for 0-10V applications, see installation instructions for details
MODEL NO.SENSING INPUTLED LOAD RATINGBALLAST LOAD RATINGINCANDESCENT LOADWARRANTY
EPC-2-D-FM120V - 277V3A (120-277V)5A (120-277V)360W (120V) / 600W (277V)5 Year Replacement Warranty
ELECTRICAL
MOUNTINGRATINGSHIPPING WEIGHT / COLORTEMPERATURE
BODY SIZE
Fixture Mount, Panel MountUL94-5VA, Damp Location Rated
-40ºF - 140ºF (-40ºC - 60ºC)
MECHANICAL
8 oz. / Black
125mmx25.4mmx30mm (L x H x W)