81

2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub
Page 2: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

2018 International Building Code • Very few consequential changes. • Definitions added or amended for clarification purposes: Sleeping Unit-Single unit providing rooms or spaces for one or more persons that includes permanent provisions for sleeping and can include provisions for living, eating and either sanitation or kitchen facilities but not both. Such rooms or spaces that are also part of a dwelling unit are not sleeping units. Repair Garage-A building, structure or portion thereof used for servicing or repairing motor vehicles. (Replicated from the IFC) Greenhouse-A structure or thermally isolated area of a building that maintains a specialized sunlit environment used for and essential to the cultivation, protection or maintenance of plants.

Page 3: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

GREENHOUSES

• In a greenhouse, the environment is such that it is maintained exclusively for, and essential to, the aggressive propagation of plants used by commercial growers for plant production. (Exempt from building thermal envelope requirements per IECC C402.1.1)

• It is acceptable for other activities to be conducted in a greenhouse, such as retail sales, educational research, conservation, education and assembly use. The occupancy class of a greenhouse will be determined accordingly.

• Greenhouses not classified as another occupancy shall be classified as Use Group U.

Page 4: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

302.1 Classification of Occupied Roofs

• Although the City of Columbia already interpreted the code this way it has been clarified that occupied roofs are to be assigned one or more occupancy classifications in a manner consistent with the classification of uses inside the building, based upon the fire and life safety hazards posed by the rooftop activities.

• For example, where a rooftop contains a restaurant having an area/occupant load for 50 or more persons, the occupied roof would be classified as an A-2 occupancy in order to address those hazards associated with such an assembly use.

Page 5: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

311.2 Classification of Self-Service Storage Facilities

Again, the City of Columbia already interpreted the code this way but it has been clarified that self-service storage facilities, due to the reasonable expectation it will contain a considerable amount of combustible materials, shall be classified as a Group S-1 moderate-hazard storage.

Page 6: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

311.1.1 CLASSIFICATION OF ACCESSORY STORAGE SPACES

• Regardless of size, storage rooms and storage spaces that are accessory to other uses are to be classified as part of the occupancy to which they are accessory.

• The key point is the hazard level that storage brings to the building. It is assumed that accessory storage uses pose little additional hazard above the occupancies which they serve.

• Where storage activities pose a significantly higher hazard than the other uses in the building, they will not be considered accessory.

Page 7: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

503.1.4 Allowable Height and Area of Occupied Roofs

• A roof level or portion thereof shall be permitted to be used as an occupied roof provided the occupancy of the roof is an occupancy permitted by Table 504.4 for the story immediately below the roof. The area of the occupied roof shall not be included in the building area as regulated by Section 506. (Any elements that enclose the occupied roof area are limited to a maximum height of 4 feet above the roof’s surface.)

Exceptions: 1. The occupancy located on an occupied rood shall not be limited to the occupancies allowed on the story immediately below the roof where the building is equipped throughout with an automatic sprinkler system and occupant notification is provided in the area of the occupied roof. 2. Assembly occupancies shall be permitted on roofs of open parking garages of Type 1 or Type 2 construction.

Page 8: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

Table 705.2 Extent of Projections

• The minimum required clearance between the edge of a projection and the line used to determine the fire separation distance has been significantly decreased.

Page 9: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

1004.8 Occupant Load Calculation for Business Use

• The method of calculating occupant load in business areas has been revised, which will typically result in reduced design occupant loads. However, higher design occupant loads can now be assigned to concentrated business areas such as telephone call centers and similar uses.

• The occupant load factor for business areas changes from 100 sf to 150 sf.

• For concentrated business use areas the occupant load factor changes to 50 sf.

Page 10: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

1603.1 Construction Documents

• Construction document requirements for environmental and special loads have been updated for rain, snow and wind forces and their components.

• The roof slope factor, Cs, has been added to the required list of snow load data and factors.

• Rain load data is added to the list of design loads required on construction documents.

• Special loads, such as loads of machinery or equipment, shall be specified by their descriptions and locations.

Page 11: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

1604.3.7 Deflection of Glass Framing • 1604.3.7 Framing supporting glass. The deflection of framing members supporting glass subjected to 0.6 times the “component and cladding” wind loads shall not exceed either of the following: • 1. 1/175 of the length of span of the framing member, for framing members

having a length not more than 13 feet 6 inches (4115 mm). • 2. 1/240 of the length of span of the framing member + 1/4 inch (6.4 mm),

for framing members having a length greater than 13 feet 6 inches (4115 mm).

• The limits do not allow a reduction to this design load for deflection analysis as was previously permitted in footnote f in the 2015 IBC Table 1604.3.

Page 12: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

Table 1607.1 Deck Live Load

• Table 1607.1 is now consistent with the provisions in the 2010 and 2016 editions of ASCE 7 for minimum uniformly distributed live loads on decks and balconies by increasing the deck live load to one and one-half times the live load of the area served.

• Not required to exceed 100 psf.

Page 13: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

Deck Collapse

Page 14: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

IBC 3109 Swimming Pools, Spas and Hot Tubs

• 3109.1 The design and construction of pools shall comply with the City of Columbia 2015 “Swimming Pool Ordinance and Guide for Swimming Pool Design and Operation”. This document may be found in Chapter 11, Article VIII, Ord. No. 22439.

• 3109.2 Barrier requirements must meet the standards of the 2018 International Swimming Pool and Spa Code (ISPSC) Section 305.

• Where spas or hot tubs are equipped with a lockable safety cover complying with ASTM F1346 and swimming pools are equipped with a powered safety cover that complies with ASTM F1346, the areas where those spas, hot tubs or pools are located shall not be required to comply with Sections 305.2 through 305.7.(Barrier Requirements)

Page 15: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

2018 International Existing Building Code Section 1106-Storm Shelters

1106.1 Addition to a Group E occupancy. Where an addition is added to an existing Group E occupancy located in an area where the shelter design wind speed for tornados is 250 mph in accordance with Figure 304.2(1)of ICC 500 and the occupant load in the addition is 50 or more, the addition shall have a storm shelter constructed in accordance with ICC 500.

Page 16: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

2018 IEBC Section 1106 Storm Shelters Continued

1106.1.1Required occupant capacity. The required occupant capacity of the storm shelter shall include all buildings on the site, and shall be the greater of the following: 1. The total occupant load of the classrooms, vocational rooms and offices in the Group E occupancy. 2. The occupant load of any indoor assembly space that is associated with the Group E occupancy. Exceptions: 1. Where an addition is being added on an existing Group E site, and where the addition is not of sufficient size to accommodate the required occupant capacity of the storm shelter for all of the buildings on-site, the storm shelter shall at a minimum accommodate the required capacity for the addition. 2. Where approved by the code official, the required occupant capacity of the shelter shall be permitted to be reduced by the occupant capacity of any existing storm shelters on the site

Page 17: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

2018 International Fire Code (IFC) Section 1103.5.1

Section 1103.5.1 was expanded to have a retroactive requirement requiring “Where alcoholic beverages are consumed in a Group A-2 occupancy having an occupant load of 300 or more, the fire area containing the Group A-2 occupancy shall be equipped with an automatic sprinkler system in accordance with Section 903.3.1.1. This provision was a response to the Station Nightclub fire of 2003 in Warwick, Rhode Island that killed 100 people and injured 230. The characteristics of the Station Nightclub and activities associated with the fire were discerned to be very dissimilar to the establishments/activities that would be effected by this provision in Columbia, Mo. An amendment was proposed and adopted to delete this new provision.

Page 18: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

2018 International Fire Code (IFC) Section 3105

• In the 2015 IFC Section 3105 was introduced regulating Temporary Stage Canopies. A Temporary Stage Canopy is defined as “A temporary ground supported membrane-covered frame structure used to cover stage areas and support equipment in the production of outdoor entertainment events. The 2018 IFC expanded these regulations to govern all Temporary Event Structures which are defined as “Any temporary ground-supported structure, platform, stage, stage scaffolding or rigging, canopy, tower supporting audio or visual effects equipment or similar structures not regulated within the scope of the International Building Code.”

Page 19: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

2018 International Fire Code (IFC) Section 3105 Continued

• The BCCC and Fire Department agreed this change to the code, in particular the associated documentation and special inspections, was over-reaching/burdensome for the needs of our community. An amendment was proposed and adopted to replace “Temporary Special Event Structure” with the 2015 language of “Temporary Stage Canopy.” The intent is to enforce these requirements for Temporary Stage Canopies only as in the 2015 IFC. Other temporary structures will be evaluated for safety per IBC standards.

Page 20: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

2018 INTERNATIONAL RESIDENTIAL CODE

• Very few major changes. Mainly reformatting and clarification. • Many previous amendments have been removed because the

code caught up with us or the commission believed they are no longer necessary.

• Enforcement of Manual J requirements changes. • New standards for location of electric meters.

Page 21: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

City of Columbia Code of Ordinances Sec. 27-96 – Meter Location

Meters shall normally be installed outdoors in a location approved by the department. New Standard: Meter will be mounted on the dwelling at the closest point from the transformer or secondary box (No more than 6 feet back from the corner), such that the service conduit does not cross under sidewalks, driveways or other obstructions. Meters mounted at other locations on the dwelling will be approved only if the customer furnishes and installs the conduit system per Water & Light standards and inspection. These standards will be: -3" schedule 40 PVC conduit -36" radius bends -Slip joint coupling below meter -3 feet of earth cover -Conduit to be installed from meter to 10 feet from transformer or secondary box. -Conduit must be inspected by CWL prior to backfill.

Page 22: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

DESIGN CRITERIA & MANUAL J • Table R301.2.(1) Climatic and Geographic Design Criteria NOW INCLUDES Manual J

criteria. • The requirement for a Manual J assessment or engineered equivalent has been in the

IRC for several editions. To assist the designer, jurisdictions will now include variables for Manual J assessments with other climatic and geographic design criteria available from the building department.

• Building and Site Development (BSD) has required the Manual J to be posted at the final inspection since the 2012 IRC was adopted. We have discovered the Manual J design criteria has not been uniform and accurate.

• With the overwhelming movement toward energy compliance alternatives to the Energy Code it is imperative the Manual J design criteria match the energy compliance documents. BSD will now require the manual J to be onsite at rough-ins to verify these documents match. (Energy Compliance documents contain the inputs for accurate Manual J reports and should be shared with the HVAC contractor!)

Page 23: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

TABLE R301.2(1)

MANUAL J DESIGN CRITERIA

Page 24: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

Proposed Manual J Checklist

Page 25: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

R 302.6 Dwelling-garage fire separation

• The previous amendment requiring five-eighth inch (5/8”)

gypsum board instead of one-half inch (1/2”) gypsum to separate the dwelling from the garage has been removed. Five-eighth inch (5/8”) gypsum is still required for separation from habitable rooms above the garage.

• Separation requirements from the garage are as depicted in Table R302.6 with no amendment.

Page 26: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

R303.4 MECHANICAL VENTILATION

• The previous amendment to this section allowed “an insulated duct from the outside connected to the return air or HVAC unit ahead of the filter with a balancing damper may be provided” to meet ventilation requirements.

• This method alone is not consistent with the code or alternative energy compliance methods.

• Mechanical ventilation must be engineered or meet the alternative energy code compliance documents.

Page 27: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

R315 CARBON MONOXIDE ALARMS

• R315 .5 Interconnectivity. Where more than one carbon monoxide alarm is required the 2018 IRC requires carbon monoxide alarm devices to be interconnected in such a manner that the actuation of one alarm will activate all of the alarms in the individual dwelling unit. • Physical interconnection is not required where listed wireless alarms are

installed and all alarms sound upon activation of one alarm. • As with smoke alarms this interconnection requirement is amended and

omitted for alterations in dwelling units no more than two (2) stories. • As with the amendment to smoke alarm requirements in alterations the

carbon monoxide alarms may be battery operated if the dwelling unit is no more than two (2) stories.

Page 28: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

R326 SWIMMING POOLS, SPAS AND HOT TUBS

• R326.1 The design and construction of pools shall comply with the City of Columbia 2015 “Swimming Pool Ordinance and Guide for Swimming Pool Design and Operation”. This document may be found in Chapter 11, Article VIII, Ord. No. 22439.

• R326.2 Barrier requirements must meet the standards of the 2018 International Swimming Pool and Spa Code (ISPSC) Section 305.

• Where spas or hot tubs are equipped with a lockable safety cover complying with ASTM F1346 and swimming pools are equipped with a powered safety cover that complies with ASTM F1346, the areas where those spas, hot tubs or pools are located shall not be required to comply with Sections 305.2 through 305.7.(Barrier Requirements)

Page 29: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

Pool/Spa Barrier Requirements

• 305.2.1 Barrier height and clearances. Barrier heights and clearances shall be in accordance with all of the following: • The top of the barrier shall be not less than 48 inches (1219 mm) above grade where measured on the side of the

barrier that faces away from the pool or spa. Such height shall exist around the entire perimeter of the barrier and for a distance of 3 feet (914 mm) measured horizontally from the outside of the required barrier.

• The vertical clearance between grade and the bottom of the barrier shall not exceed 2 inches (51 mm) for grade surfaces that are not solid, such as grass or gravel, where measured on the side of the barrier that faces away from the pool or spa.

• The vertical clearance between a surface below the barrier to a solid surface, such as concrete, and the bottom of the required barrier shall not exceed 4 inches (102 mm) where measured on the side of the required barrier that faces away from the pool or spa.

• Where the top of the pool or spa structure is above grade, the barrier shall be installed on grade or shall be

mounted on top of the pool or spa structure. Where the barrier is mounted on the top of the pool or spa, the vertical clearance between the top of the pool or spa and the bottom of the barrier shall not exceed 4 inches (102 mm).

Page 30: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

Pool/Spa Barrier Requirements Con’t.

• 305.2.2 Openings. Openings in the barrier shall not allow passage of a 4-inch- diameter (102 mm) sphere. • 305.2.3 Solid barrier surfaces. Solid barriers that do not have openings shall not contain indentations or protrusions that form handholds and footholds, except for normal construction tolerances and tooled masonry joints.

Page 31: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

Pool/Spa Barrier Requirements Con’t. • 305.2.4 Mesh fence as a barrier. • The bottom of the mesh fence shall be not more than 1 inch (25 mm) above the deck or installed

surface or grade. • The maximum vertical clearance from the bottom of the mesh fence and the solid surface shall not

permit the fence to be lifted more than 4 inches (102 mm) from grade or decking. • The fence shall be designed and constructed so that it does not allow passage of a 4-inch (102 mm)

sphere under any mesh panel. The maximum vertical clearance from the bottom of the mesh fence and the solid surface shall be not greater than 4 inches (102 mm) from grade or decking.

• An attachment device shall attach each barrier section at a height not lower than 45 inches (1143 mm) above grade. Common attachment devices include, but are not limited to, devices that provide the security equal to or greater than that of a hook-and-eye-type latch incorporating a spring-actuated retaining lever such as a safety gate hook.

• Where a hinged gate is used with a mesh fence, the gate shall comply with Section 305.3.3. • Patio deck sleeves such as vertical post receptacles that are placed inside the patio surface shall be

of a nonconductive material. • Mesh fences shall not be installed on top of onground residential pools.

Page 32: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

Pool/Spa Barrier Requirements Con’t. • 305.2.5 Closely spaced horizontal members. Where the barrier is composed of horizontal and vertical members and the distance between the tops of the horizontal members is less than 45 inches (1143 mm), the horizontal members shall be located on the pool or spa side of the fence. Spacing between vertical members shall not exceed 13/4 inches (44 mm) in width. Where there are decorative cutouts within vertical members, spacing within the cutouts shall not exceed 13/4 inches (44 mm) in width. • 305.2.7 Chain link dimensions. The maximum opening formed by a chain link fence shall be not more than 13/4 inches (44 mm). Where the fence is provided with slats fastened at the top and bottom that reduce the openings, such openings shall be not greater than 13/4 inches (44 mm).

Page 33: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

Pool/Spa Barrier Requirements Con’t. • 305.2.8 Diagonal members. Where the barrier is composed of diagonal members, the maximum opening formed by the diagonal members shall be not greater than 13/4 inches (44 mm). The angle of diagonal members shall be not greater than 45 degrees (0.79 rad) from vertical. • 305.2.9 Clear zone. There shall be a clear zone of not less than 36 inches (914 mm) between the exterior of the barrier and any permanent structures or equipment such as pumps, filters and heaters that can be used to climb the barrier. • 305.2.10 Poolside barrier setbacks. The pool or spa side of the required barrier shall be not less than 20 inches (508 mm) from the water’s edge

Page 34: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

Pool/Spa Barrier Requirements Con’t. • 305.3 Gates. Access gates shall comply with the requirements of Sections 305.3.1 through 305.3.3 and shall be equipped to accommodate a locking device. Pedestrian access gates shall open outward away from the pool or spa, shall be self-closing and shall have a self-latching device. • 305.3.1 Utility or service gates. Gates not intended for pedestrian use, such as utility or service gates, shall remain locked when not in use. • 305.3.2 Double or multiple gates. Double gates or multiple gates shall have not fewer than one leaf secured in place and the adjacent leaf shall be secured with a self latching device. The gate and barrier shall not have openings larger than 1/2 inch (12.7 mm) within 18 inches (457 mm) of the latch release mechanism. The self-latching device shall comply with the requirements of Section 305.3.3.

Page 35: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

Pool/Spa Barrier Requirements Con’t.

• 305.3.3 Latches. Where the release mechanism of the self-latching device is located less than 54 inches (1372 mm) from grade, the release mechanism shall be located on the pool or spa side of the gate not less than 3 inches (76 mm) below the top of the gate, and the gate and barrier shall not have openings greater than 1/2 inch (12.7 mm) within 18 inches (457 mm) of the release mechanism. • 305.4 Structure wall as a barrier. Members of the committee

believe this section to be onerous/difficult to enforce.

Page 36: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

Pool/Spa Barrier Requirements Con’t. • 305.4 Structure wall as a barrier. DELETE IN the IRC-REMAIN in IBC Where a wall of a dwelling or structure serves as part of the barrier and where doors or windows provide direct access to the pool or spa through that wall, one of the following shall be required: • Operable windows having a sill height of less than 48 inches (1219 mm) above the indoor finished

floor and doors shall have an alarm that produces an audible warning when the window, door or their screens are opened. The alarm shall be listed and labeled as a water hazard entrance alarm in accordance with UL 2017. In dwellings or structures not required to be Accessible units, Type A units or Type B units, the operable parts of the alarm deactivation switches shall be located 54 inches (1372 mm) or more above the finished floor. In dwellings or structures required to be Accessible units, Type A units or Type B units, the operable parts of the alarm deactivation switches shall be located not greater than 54 inches (1372 mm) and not less than 48 inches (1219 mm) above the finished floor.

• A safety cover that is listed and labeled in accordance with ASTM F1346 is installed for the pools and spas.

• An approved means of protection, such as self-closing doors with self-latching devices, is provided. Such means of protection shall provide a degree of protection that is not less than the protection afforded by Item 1 or 2.

Page 37: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

Pool/Spa Barrier Requirements Con’t. • 305.5 Onground residential pool structure as a barrier. An onground residential pool wall structure or a barrier mounted on top of an onground residential pool wall structure shall serve as a barrier where all of the following conditions are present: • Where only the pool wall serves as the barrier, the bottom of the wall is on grade, the top of the

wall is not less than 48 inches (1219 mm) above grade for the entire perimeter of the pool, the wall complies with the requirements of Section 305.2 and the pool manufacturer allows the wall to serve as a barrier.

• Where a barrier is mounted on top of the pool wall, the top of the barrier is not less than 48 inches (1219 mm) above grade for the entire perimeter of the pool, and the wall and the barrier on top of the wall comply with the requirements of Section 305.2.

• Ladders or steps used as means of access to the pool are capable of being secured, locked or removed to prevent access except where the ladder or steps are surrounded by a barrier that meets the requirements of Section 305.

• Openings created by the securing, locking or removal of ladders and steps do not allow the passage of a 4-inch (102 mm) diameter sphere.

• Barriers that are mounted on top of onground residential pool walls are installed in accordance with the pool manufacturer’s instructions.

Page 38: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

Pool/Spa Barrier Requirements Con’t. • 305.6 Natural barriers. In the case where the pool or spa area abuts the edge of a lake or other natural body of water, public access is not permitted or allowed along the shoreline, and required barriers extend to and beyond the water’s edge not less than 18 inches (457 mm), a barrier is not required between the natural body of water shoreline and the pool or spa. • 305.7 Natural topography. Natural topography that prevents direct access to the pool or spa area shall include but not be limited to mountains and natural rock formations. A natural barrier approved by the governing body shall be acceptable provided that the degree of protection is not less than the protection afforded by the requirements of Sections 305.2 through 305.5.

Page 39: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

R802.5.2.2 Rafter Ties

• R802.5.2.2 Rafter ties. Wood rafter ties shall be not less than 2 inches by 4 inches (51 mm × 102 mm) installed in accordance with Table R802.5.2 at each rafter. Other approved rafter tie methods shall be permitted. (Rafter ties shall be spaced not more than four (4) feet (1219 mm) on center.

Page 40: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

Chapter 11 Energy Efficiency

As recommended by the 2019 International Energy Conservation Code Committee it was voted to adopt Chapter 11 as written. This will eliminate previous amendments to this chapter and will also eliminate the “Residential Energy Code Requirements Diagram”. At this time the vast majority of builders here in Columbia are using performance based compliance alternatives (Columbia is well ahead of the curve on this and many other jurisdictions are following this same trend nationwide). These methods provide much more flexibility for dwelling unit components/characteristics. To follow a prescriptive path after adoption of the 2018 IRC will require third party energy code compliance documentation/plans, verification of energy code compliance as built, and third party certification.

Page 41: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

Appendix F, Radon Control Methods

• AF103.4.2Concrete joints. (Added this code cycle) Control joints, isolation joints, construction joints, and any other joints in concrete slabs or between slabs and foundation walls shall be sealed with a caulk or sealant. Gaps and joints shall be cleared of loose material and filled with polyurethane caulk or other elastomeric sealant applied in accordance with the manufacturer’s recommendations. Because of significant concrete shrinkage and movement the committee suggested this addition to the appendix would be wasteful and proposed deletion of this requirement. This section is deleted by amendment.

Page 42: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

APPENDIX Q TINY HOUSES

A new appendix Q covers provisions for Tiny Houses , defined as dwellings with a maximum floor area of 400 square feet. Many concessions pertaining to ceiling height, room area, lofts, loft access, and egress roof access meeting emergency escape and rescue opening standards are given to make Tiny Houses a viable option.

Page 43: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

2018 International Energy Conservation Code

Significant changes and clarifications

Page 44: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

2018 IECC Commercial Changes Highlights

• Commercial • Initial estimate of 2-5% energy efficiency improvement. • Mechanical Section (C 403): Reorganized, so all provisions for a type of equipment or system are in one place • Appendix CA Solar-Ready Zone • Definition of “Approved”: Change from “Approval by the code official as a result of investigation and tests conducted by him or her, or by nationally recognized organizations” to “Acceptable to the code official” • ASHRAE 90.1-2016 referenced as alternative standard.

Page 45: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

Envelope C402.3.1--Heated Slab Insulation

R-5 continuous insulation required under heated slabs for both commercial and residential(Already in IMC 1209.5.1)

Page 46: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

Table C402.1.4 Garage Door Glazing

• A U-factor of .31 has been added to table 402.1.4 as a minimum requirement for garage doors with glazing.

Page 47: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

C403.4.4 Expanded Variable Frequency Drives

• Controls expanded to include systems greater than or equal to 300,000 BTU. (Was 500,000 BTU)

• Pumps and fans with combined pump motor capacity of 2hp (down from 5hp) must automatically vary flow.

Page 48: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

C403.6.1 Improved HVAC Turndown W/Direct Digital Control (DDC)

• Reduced minimum airflow from 30% to 20% of maximum

Page 49: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

C403.7.6 Guestroom Automatic Controls

• Automatic HVAC control now required for buildings with over 50 guestrooms in Group R-1. (Hotels, Motels) Temperature setpoint controls to raise the cooling setpoint and lower the heating setpoint by not less than 4 degrees from the occupant setpoint within 30 minutes after the occupants have left the guestroom. Raise the cooling setpoint to 80 degrees and the heating setpoint to 60 degrees when unoccupied for 16 hours or a networked guestroom control system indicates the room is unrented and unoccupied for more than 30 minutes.

Page 50: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

C404.3 Water Storage Tank Heat Traps

• Heat Traps now required for hot water storage tanks, not just water heaters.

Page 51: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

C405.2 Luminaire Level Lighting Controls

• Allows for luminaire lighting controls to take the place of centralized controls • Must include occupancy sensor and ambient light sensor

Page 52: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• Open office areas now must have occupancy sensors. -Control zones not greater than 600sf -Automatically turn off within 20 minutes -General lighting power in each control zone reduced by not less than 80% of the full zone general lighting in a reasonably uniform pattern within 20 minutes of occupants leaving the zone -Daylight responsive controls activate general lighting

Office Area Occupancy Sensors LIGHTING C405 .2.1.3

Page 53: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• Does not require daylight-responsive controls If 40% lower than wattage allowance • Office Allowance—0.79 w/sf • Threshold for Daylight-responsive controls – 0.47 w/sf

Daylight Responsive Exception LIGHTING C405.2.3

Page 54: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• Daylight shutoff required-lights shall be automatically turned

off when daylight is present. • Decorative lighting (building façade and landscape

lighting)shut off during non-business hours • Other lighting setback requirements– 30% watts minimum • Time switch control functionality

Increased Exterior Lighting Controls LIGHTING C405.2.6

Page 55: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• Reduces demand from 30W/ft to 8W/ft

Track Lighting Demand Reduction INTERIOR LIGHTING-C405.3.1

Page 56: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• Office 0.82 to 0.79 – 4% reduction • Library 1.19 to 0.82 – 32% reduction

Reduced Lighting Power Allowances INTERIOR LIGHTING POWER ALLOWANCES

Page 57: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• Low voltage dry-type transformers and motors have new efficiency requirements.

Increased Efficiencies C405.6 AND 405.7

Page 58: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• Additional option packages are provided such as; -Enhanced envelope performance 15% below the total UA of the building thermal envelope in accordance with Section C402.1.5 -Reduced air infiltration. The measured air-leakage rate of the building envelope shall not exceed .25 cfm/sf under a pressure differential of .3 inches water column.

Option Packages C406 ADDITIONAL EFFICIENCY OPTIONS

Page 59: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• A maximum on-site renewable energy cost reduction of 5% is now a component of C407.3 the performance based compliance approach.

• Requires documentation which demonstrates the reduction in energy use associate with on-site renewable energy.

• Clarifies that renewable energy purchased from off-site sources shall be the same in the standard reference design and proposed design.

Commercial Renewable Energy Cost Reduction Credit Limits

C407-TOTAL BUILDING PERFORMANCE

Page 60: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

Building O&M must be provided to the building owner. 1. Manufacturer’s information. 2. Specifications and recommendations. 3. Programming procedures and data points. 4. Other means of illustrating to the owner how equipment and

systems are intended to be maintained and operated. 5. Required maintenance actions shall be clearly stated on

readily visible label. Shall include title of maintenance manual or publication number.

Operations and Maintenance (O&M)

C408.1.1 MAINTENANCE INFORMATION

Page 61: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• A commissioning plan shall be developed by a registered design professional or approved agency.

• Systems shall be balanced in accordance with generally accepted engineering standards.

• A preliminary commissioning report of commissioning test procedures and results shall be completed and certified by the registered design professional or approved agency and provided to the building owner or owner’s authorized agent.

• Final inspections take place AFTER the code official receives a copy of the preliminary report from the owner or owner’s authorized agent.

C408.2 COMMISSIONING PLAN, BALANCING, FUNCTIONAL TESTING, AND DOCUMENTATION.

Page 62: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• Prior to the final mechanical and plumbing inspections, the registered design professional or approved agency shall provide evidence of mechanical systems commissioning and completion. Construction document notes shall clearly indicate provisions for commissioning and completion.

• Exceptions: The following systems are exempt: 1. Mechanical systems and service water heating systems in buildings where the total mechanical equipment capacity is less than 480,000 Btu/h cooling capacity and 600,000Btu/h combined service water- heating and space-heating capacity. 2. Systems with economizers that serve individual dwelling units and sleeping units.

C408.2 MECHANICAL SYSTEMS AND SERVICE WATER HEATING SYSTEMS COMMISSIONING AND COMPLETION REQUIREMENTS.

Page 63: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• The construction documents shall specify that a Final Commissioning Report shall be provided to the building owner or owner’s authorized agent within 90 days of receipt of the certificate of occupancy. The report shall include the following:

1. Results of the functional performance tests. 2. Disposition of deficiencies found during testing, including details of corrective measures used or proposed. 3. Functional performance test procedures used during the commissioning process including measurable criteria for test acceptance, provided herein for repeatability.

COMMISSIONING PLAN, BALANCING, FUNCTIONAL TESTING, AND DOCUMENTATION.

Page 64: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• Prior to passing final inspection, the registered design professional shall provide evidence that the lighting control systems have been tested to ensure that control hardware and software are calibrated, adjusted, programmed and in proper working condition in accordance with the construction documents and manufacturer’s instructions.

• The construction documents shall specify that the documents described in this section be provided to the building owner or owner’s authorized agent within 90 days of the date of receipt of the certificate of occupancy.

C408.3 FUNCTIONAL TESTING OF LIGHTING CONTROLS

Page 65: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• A solar-ready zone shall be located on the roof of buildings that are five stories or less in height above grade plane, and are oriented between 110 degrees and 270 degrees of true north OR have low slope roofs.

Exceptions: A building where the licensed design professional (LDP) certifies the solar zone cannot be met because of extensive rooftop equipment, obstructions, etc. A building w/permanently installed on-site renewable energy system. Bldg. shaded more than 70% daylight hours/yr. LDP certifies the incident solar radiation available is not suitable. • The total solar-ready zone shall not be less than 40% of the roof area.

Total roof area minus skylights, occupied areas, vegetative areas, mandatory access or setback required by IFC.

SOLAR READY ZONE-COMMERCIAL APPENDIX CA ADDED/ADOPTED

Page 66: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• CA 103.5 Roof loads and documentation. A collateral load of not less than 5 pounds per square foot shall be included in the gravity and lateral design calculations for the solar-ready zone. The structural design loads for the roof dead load and roof live load shall be indicated on the construction documents.

• CA 103.6 Interconnection pathway. Construction documents shall indicate pathways for routing of conduit or piping from the solar-ready zone to the electric service panel or service hot water system.

Roof loads, interconnection pathways, reserved space, certificate. APPENDIX CA SOLAR-READY ZONE CONTINUED

Page 67: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• CA 103.7 Electrical service reserved space. The main electrical service panel shall have a reserved space to allow installation of a dual-pole circuit breaker for future solar electric installation and shall be labeled “For Future Solar Electric.”

• CA 103.8 Construction documentation certificate. A permanent certificate, indicating the solar-ready zone and other requirements of this section, shall be posted near the electrical distribution panel, water heater or other conspicuous location by the builder or registered design professional.

Roof loads, interconnection pathways, reserved space, certificate.

APPENDIX CA SOLAR-READY ZONE CONTINUED

Page 68: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

RESIDENTIAL 2018 IECC Changes Highlights

Page 69: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

-Modest improvement in window U-factors for Climate Zone 4 -Do not confuse this minimum window requirement with requirement to meet energy compliance documents.

Window U-Factors R402.1.2 THERMAL ENVELOPE

Page 70: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• Provides allowance for duct insulation in buried duct work (for simulated energy performance analysis)

• 403.3.7-Ducts are considered inside a conditioned space if buried in ceiling insulation per 403.3.6.

Ducts Buried in Ceiling Insulation R403.3.6/403.3.7 THERMAL ENVELOPE

Page 71: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• Increases high efficiency lighting to 90% from 75%. • 90% of permanently installed fixtures shall contain only high

efficiency lamps. • Eliminates the low voltage exception.

High Efficiency Lighting R404.1-LIGHTING

Page 72: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• Increases maximum ERI score from 54 to 62 in climate zone 4. • Clarifies where on-site renewable energy is included for

compliance the building must meet the mandatory requirements of Section R406.2 and the thermal envelope shall be equal to or greater than the requirements of the 2015 IECC.

• The ANSI/RESNET/ICC 301-2014 is now a referenced standard in the code as the basis for ERI calculation. Additionally ANSI/RESNET/ICC 380-2016 is now a referenced standard for building envelope testing.

Less Stringent Target Requirements TABLE R406.4-MAXIMUM ENERGY RATING INDEX

Page 73: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• All applications for new single family detached, duplexes and townhomes must include energy code compliance documentation.

• Energy Code Compliance reports from an approved inspection agency are required to be submitted to the Building Official and posted in the dwelling at an approved location.

IECC R101.5.1/IRC N1101.3 RESIDENTIAL ENERGY CODE COMPLIANCE DOCUMENTATION

Page 74: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• 210.52 (c)(3) Peninsular Countertop Spaces—By amendment to this section an outlet is required to be placed at the end of a peninsula cabinet (s).

• 250.64 Grounding Electrode Conductor Installation. (B) Securing and Protection Against Physical Damage (4) In Contact with the Earth. The NEC now clarifies the grounding electrode conductor must be protected in conduit until it is buried.

Code/Amendment Changes

2017 NATIONAL ELECTRICAL CODE

Page 75: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• 250.94 Bonding for Communication Systems.—This section was previously deleted by amendment but is now required.

This will require the use of an “Intersystem Bonding Termination Device” or a bus-bar of sufficient length to accommodate 3 terminations.

Code/Amendment Changes

2017 NATIONAL ELECTRICAL CODE

Page 76: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• 300.5 Underground Installations. (D) (4)By amendment electrical metallic tubing has been removed from the list of approved protection.

• 406.12 Tamper-Resistant Receptacles—The areas requiring tamper resistant receptacles has been greatly expanded. The deletion, by amendment, of the requirement for tamper resistant receptacles in dwelling units remains. Also deleted by amendment are new requirements for tamper resistant receptacles in business offices and corridors.

Code/Amendment Changes Continued

2017 NATIONAL ELECTRICAL CODE

Page 77: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• 422.16 (B) (2) (6) The receptacle for a built in dishwasher shall

be located in the space adjacent to the space occupied by the dishwasher.

By Amendment: The receptacle serving a built in dishwasher shall be permitted in the space occupied by the dishwasher unless manufacturer instructions require the outlet to be in an adjacent cabinet.

Code/Amendment Changes Continued

2017 NATIONAL ELECTRICAL CODE

Page 78: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• 691 Large-Scale Photovoltaic (PV) Electric Power Production

Facility • The requirements for PV systems are covered in Article 690.

That is, until such installations become large enough to be called large-scale PV systems.

• This new article covers the installation of large-scale PV electric power production facilities with a generating capacity of no less than 5,000 kW, and not under exclusive utility control.

Code/Amendment Changes Continued

2017 NATIONAL ELECTRICAL CODE

Page 79: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• 700.10 Wiring, Emergency System • (A) Identification. Examples for emergency identification have

been added to this section by amendment. • Examples: Components (boxes, enclosures, raceways,

exposed cable) may be permanently marked using red color or stenciled “Emergency System”.

Code/Amendment Changes Continued

2017 NATIONAL ELECTRICAL CODE

Page 80: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub

• 109.2.1 Time limit. (Added by amendment) If an order is

issued to board-up the openings of a structure out of compliance with this code, the structure shall be brought into compliance and the structure shall not remain boarded-up longer than ninety (90) days from the date of the notice.

Only one substantial change-Time Limit on Boarding up of Openings INTERNATIONAL PROPERTY MAINTENANCE CODE

Page 81: 2018 International Building Code - Columbia, Missouri · 2018 International Building Code • Very few consequential changes. ... provision was a response to the Station Nightclub