schneider-electric.com/mv-distribution

2017 Catalogue

Ringmaster

Medium Voltage Distribution

Page 2: 2017 Catalogue - s; E
Page 3: 2017 Catalogue - s; E

schneider-electric.com | 1Ringmaster Catalogueschneider-electric.com | 1

General contents

Presentation 3

Ring main units 21

Circuit breaker, metering and switches

41

Remote control 87

Installation drawings 93

Schematic diagrams 105

Accessories & options 127

Order form 138

Page 4: 2017 Catalogue - s; E

schneider-electric.com2 | Ringmaster Catalogue

Presentation

Page 5: 2017 Catalogue - s; E

schneider-electric.com | 3Ringmaster Catalogue

Overview 4

Description 5

Switchgear description 6

Applications 7

Standards and quality 12

Protection Time Fuse Link (TFL)

VIP protection relays

13

Remote terminal unit 15

Network remote control 16

Ringmaster selection guide 17

Range selection process 18

Presentation

Page 6: 2017 Catalogue - s; E

schneider-electric.com4 | Ringmaster Catalogue

Presentation Overview

We are proud to present the new Ringmaster RN2d, built on its best selling predecessor RN2c. RN2d is an SF6 insulated Ring Main Unit (RMU) for medium voltage networks up to 13.8kV with improvements guided by customer feedback and Design Failure Mode Effect Analysis (DFMEA).

The RN2d has safety, reliability, and flexibility at its core and becomes a smart RMU when integrated with the Easergy T300 feeder RTU.

Schneider Electric is a global specialist in energy management with operations in more than 100 countries, offers integrated solutions across multiple market segments, including leading positions in utilities and infrastructure, industries, residential and non residential buildings and datacenters.

Focused on making energy safe, reliable, efficient, productive and green Schneider Electric invests significantly in R&D to come up with product and services to meet future needs of the market.

Page 7: 2017 Catalogue - s; E

schneider-electric.com | 5Ringmaster Catalogue

Presentation Description

Ringmaster is a range of SF6 Insulated ring main units and the ideal choice for all your MV applications.From simple transformer protection, or sectionalising with remote control, to multi-panel metered consumer switchboards, the Ringmaster range from Schneider Electric offers a solution.

Quality engineering for extreme climates enables Ringmaster to provide flexibility for any location.

Covering a wide range of options with an indoor and outdoor IP54 design and ratings up to 13.8 kV, 630 A and 21 kA, Ringmaster has proved successful in markets around the world.

Product advantagesSimple, clear operation combined with compact size, high functionality and reliability extends the applications of the Ringmaster range.

Reduced risk Fully certified internal arc design in accordance with latest international standards.

Indoor/outdoor design No need for expensive switchrooms.

Self-powered protection Not reliant on costly battery chargers.

Compact Reduced dimensions, gives reduced civil costs.

Virtually maintenance free Low lifetime costs.

Modular design Quick, simple & easy to install.

Proven quality Assured consistent quality. ISO 9001 quality certification.

Environmental Manufacture to ISO 14001 environmental standards.

Direct mounting to transformer No cable connection needed thus cost saving in term of cable and cable connection when directly mounted to transformers

Plug in motor Directly mountable to a pre-wired live RMU on site, in less than 1 min.

SCADA compatible with Remote Terminal Unit (RTU): Easergy T300

High performance Switch rated up to 5000 numbers mechanical operations.

PE40

438

Page 8: 2017 Catalogue - s; E

schneider-electric.com6 | Ringmaster Catalogue

Presentation Switchgear description

PE57

061

Free standing, non-extensible, cable connected ring main unit.

Transformer mounted, non-extensible ring main unit, incorporated in a packaged substation.

Free standing, extensible cable connected ring main unit

Transformer mounted, extensible ring main unit, incorporated in a packaged substation.

Free standing, non-extensible circuit breaker.

Cable connected extensible switchboard.

Free standing, non-extensible, top entry, cable connected ring main unit.

PE57

064

PE57

062

PE57

065

PE57

063

PE57

066

PE57

070

General characteristics• Gas pressure indicator as standard• Anti-reflex operating handle with facilities for

electrical operation• Interlocked MV cable test access (no need to remove

cable terminations or use loose earthing devices)• Type C bushing offers flexibility of wide choice of

3rd party screened & unscreened termination system

• Integral self-powered protection with TFL, adjustable curve & relay options

• IP54 enclosure• Simple to follow mimic providing user-friendly

operation• Earth screened cast-resin gas module

• Range of dry type metering units• Mechanical tripped on-fault indication• Resin encapsulated busbars in air bus chamber

for extensible version• Direct coupling to transformers or cable connection• Remote monitoring & control through Easergy T300

range of FRTUs.

PM10

5722

A multitude of configurationsA variety of different panel types are available for each unit within the range, together with a number of optional accessories enabling Ringmaster to satisfy the most complex system specification.

Page 9: 2017 Catalogue - s; E

schneider-electric.com | 7Ringmaster Catalogue

Presentation Applications

Schneider Electric regards its customers as commercial partners, who, like us, demand the highest standards of excellence in terms of products, projects and services.

Schneider Electric is proud to provide the solutions to meet their needs.

Schneider Electric operates the largest, dedicated sales force in the electrical industry.

Sales engineers have specialist expertise and an understanding of the customer needs within each of the following market sectors:

• Building systems and solutions• Industrial systems and solutions• Energy and infrastructure systems and solutions• Package substations• Mining industry.

PE58

311

With over 100 years experience in the electrical industry, Schneider Electric has established itself as a world leader in the supply and manufacture of products for the distribution, monitoring and control of electrical power.

Page 10: 2017 Catalogue - s; E

schneider-electric.com8 | Ringmaster Catalogue

Presentation Applications Building and Industries

Schneider Electric offer a wide range of solutions in the area of industries and building management services and uses its expertise in all of these applications to protect people and equipment.

Schneider Electric means greater comfort, lower operating costs and enhanced safety.Our products and services adapt to each specific business and environment, from discrete manufacturing and production lines to continuous processes in a wide variety of industries and buildings such as:

• Retail• Education• Health• Entertainment centres• Offices• Warehouses• Agriculture• Factory• Private residential• Public residential.• Automotive• Food and beverage• Pharmaceuticals• Construction materials• Waste management.

Across a wide range of applications including:• Conveyors• Packaging• Materials handling• Hoisting.

Principal customers in the construction market:• Contracting authorities• Main contractors• Building engineers.

PE58

312

The real reason for putting technology into buildings is to simplify tasks, enhance safety and improve the quality of life.

Schneider Electric knows this and has created attractive, functional products for the residential building sector. Well being comfort and entertainment are key concepts in this area.

PE57

008

Page 11: 2017 Catalogue - s; E

schneider-electric.com | 9Ringmaster Catalogue

Presentation Applications Energy and infrastructure

Today, electrical substation and network protection, monitoring and control are highly effective in reducing outage time.

Proven technologies offer a wide range of simple, efficient and flexible solutions for optimised, step by step investments.

InfrastructureSchneider Electric is involved in developing infrastructure and transportation systems around the world. In areas where no failures can be tolerated, such as road and rail equipment, harbour installations and airports, Schneider Electric provides solutions in electrical distribution, control and monitoring, automation and supervision.

Key markets• Electricity distribution• Water• Rail• Airports• Seaports• Defence• Gas• Telecommunications• Road.

Principal customers in the electric power market • Power suppliers involved in generation and distribution• Utility companies• Major contractors• Large end user sites• Government departments.

PE58

315

PE58

316

Schneider Electric is involved in the entire electrical distribution chain from power plants to end users. Customer demand for complete availability, uncompromising quality and safety has made the search for excellence our key mission.

Page 12: 2017 Catalogue - s; E

schneider-electric.com10 | Ringmaster Catalogue

Presentation

schneider-electric.com10 |

ApplicationsMining

Robust and simple solution for mine MV networkRingmaster is a range of MV switchgear with a genuine IP 54 design to maximise resistance to the toughest environment:• Dust• Pollution• Humidity.

Cost effective and simple • The IP54 degree of protection of the Ringmaster’s housing makes it possible

to be used in the most aggressive environment. No consideration needs to be taken for an external enclosure, saving cost compared to traditional solutions.

• A virtually maintenance free design is achieved having all MV contacts housed in a sealed for life IP67 SF6 gas filled enclosure.

• Underground handling in narrow tunnels and lifts is simplified by compact dimensions and light weight.

Robust and reduced risk for people• Unlike air insulated switchgear, Ringmaster offers full encapsulation and no

primary conductor is exposed to the ambient air. Contact with conductive particles present in dusty environment is avoided, greatly reducing the risk of partial discharge and flash over.

• Operator safety is maximised with an advanced design fully compliant to the latest internal arc classification as per IEC62271-200.

Over 5000 functions of Ringmaster protect mine networks worldwide• BHP Billiton, Rio Tinto, Gold Fields, Alcoa, CSA Global, Newcrest, Xstrata,

Gloucester Coal, Aditya Birla Group, AngloGold Ashanti, Anglo Coal, ASSMANG.

PE58

318

PM10

5701

Page 13: 2017 Catalogue - s; E

schneider-electric.com | 11Ringmaster Catalogue

Presentation

One stop engineered solutions

Features• One contact• Complete system, delivered as one unit• Typical drawing and technical specification with tender• Metering facilities-optional• Remote control-optional• Free breathing, conservator or hermetically sealed tank option• Premium quality of Schneider Electric• Direct coupled MV & LV equipment• Additional enclosure option.

Expertise in developing solutions for specialised applications• Unit substations have MV and LV switchgear located on the same side of the

transformer tank• In-line substations have MV and LV switchgear mounted on opposite ends of the

transformer tank• Compact or mini substations for lower rating applications• Specialised substations are designed to meet specific requirement.

For example, MV and LV switchgear can be mounted at a 90° angle on the transformer tank

• Remote control options enable network automation for secondary distribution.

PE58

324

ApplicationsPackage substations

One stop engineered package substationEase of specification is guaranteed by one point of contact from initial enquiry through manufacture, delivery, commissioning and after sales service. Schneider Electric engineers design specific engineered solutions to fulfil customer requirements.

Flexibility of tailored configurations are available from the wide range of Schneider Electric products which include:• Transformers from 315 kVA to 2000 kVA (up to 5 MVA for special applications)• Extensible and non-extensible Ringmaster MV switchgear• LV SAIF and shielded fusegear from 800 A to 3200 A• LV acb and mccb pillars up to 3200 A• Automation and monitoring systems• Tailor made enclosures can be mounted on the transformer underbase to provide

single lift complete installation.

Protection of operators is ensured by direct coupling of the individual elements with provision for isolation for maintenance.

Cost savings are achieved by reducing the foundation area requirement due to the direct coupling which requires minimum cabling and reduced maintenance. Space requirements are minimised by direct connection, logistics costs minimalised because the complete substation is delivered as a single unit. One stop package substations also reduce the time commitment needed by customers for the overall project.

The diversity of configurations range from compact design, unit, in-line or specialised systems dependent on application requirement.Transformers can be either free breathing, conservator or hermetically sealed type. Substations can have remote control and automation.

Schneider Electric engineered package substation solutions tailored to customers requirement using products from our comprehensive range.

This provides customers with a convenient single source package substation with minimum time and costs.

Page 14: 2017 Catalogue - s; E

schneider-electric.com12 | Ringmaster Catalogue

Presentation Standards and quality

Conformity with standards in forceRingmaster meets the current national or international standards in force:(IEC, BS, IS). The main electro-technical standards cover:• The design of the functional units and switchgear• Medium voltage switchgear (interruption, sectionalising, insulation)• Current and voltage transformers• Low voltage switchgear• SF6 gas• Cables and conductors• Graphs and diagrams• Tests• International electro-technical vocabulary.

A quality and safety approachBoth sites ie. Leeds in UK and Hyderabad in India, are, for many years, been committed to a global quality approach and are certified:• ISO 9001: 2000• ISO 14001: 2004• OHSAS 18001 :2007 - ISO 50001:2011.

Tests on the devicesVarious factory tests are carried out on Ringmaster before it is shipped to the customer:• Tank leak-tightness test• Mechanical test for control mechanisms• Dielectric tests.

The Ringmaster switchboards comply with the requirements of the following standards and regulations:

Description IEC standard IEC classes EN standardSwitchboard IEC 62271-200

IEC 62271-1LSC partition class PMContinuity of service of the cable connection and fuse compartments: LSC2A (1)

EN 62271-200EN 62271-1

Behaviour in the event of internal faults IEC 62271-200 EN 62271-200

Earthing switch IEC 62271-102 E2 EN 62271-102

Ring switch IEC 62271-103 M1, E3(1), C1

Circuit-breaker IEC 62271-100 M1, E2 EN 62271-100

Current transformer IEC 60044-1 EN 60044-1

Voltage transformer IEC 60044-2 EN 60044-2

Voltage presence indicators IEC 61958 EN 61958

Voltage detection systems IEC 61243-5 EN 61243-5

Protection against accidental contact, foreign bodies and ingress of water

IEC 60529 EN 60529 1

Installation HD 637 SOperation of the electrical equipment EN 50110

PE58

325

Ringmaster meets the following standards: IEC 62271-100, IEC 60265, IEC 62271-200, BS EN 60265 and ENA TS 41-36.

Manufactured to BS EN ISO 9001.

Environmental Management System BSEN ISO 14001 OHSAS 18001 Management of Health and Safety.

(1) For RMR ranges: E2

Page 15: 2017 Catalogue - s; E

schneider-electric.com | 13Ringmaster Catalogue

Presentation ProtectionTime Fuse Link (TFL)

DE6

0249

TFL protectionAn effective low cost option without compromising reliability.CT operated trip coils (with TFL) provides phase overcurrent and earth fault inverse time protection, the characteristic being given by a Time Fuse Link (TFL).This option is suitable for transformer protection up to 1600 kVA.

Recommended Time Fuse Link (TFL) settings to ESI 12-6Voltage Transformer rated power (kVA)

(kV) 200 315 500 800 1000 1250 1600CT ratio = 50/5 3.3 10 A TFL

earth fault setting = 25 A (instantaneous trip)

150 A LV fuse

6.6 5 A 10 A 15 A TFL

150 A 250 A 400 A LV fuse

11 3 A 5 A 10 A 15 A TFL

200 A 300 A 400 A 560 A LV fuse

13.8 3 A 5 A 10 A 15 A TFL

200 A 300 A 400 A 560 A LV fuse

CT ratio 3.3 5 A 10 A 15 A TFL

= 100/5

earth fault setting = 30 A (instantaneous trip)

150 A 250 A 400 A LV fuse

6.6 5 A 7.5 A 12.5 A 15 A TFL

250 A 400 A 560 A 560 A LV fuse

11 5 A 7.5 A 10 A 12.5 A 15 A TFL

400 A 560 A 630 A 630 A 630 A LV fuse

13.8 5 A 7.5 A 10 A 12.5 A 15 A TFL

400 A 560 A 630 A 630 A 630 A LV fuse

• Low cost• Fast clearance of LV faults• Simple to replace• Proven protection to EA standards• Fast tripping for MV earth faults• Improved discrimination with LV fuse

Principle of operationThe current transformer feeds a trip coil that is normally shunted by a time fuse link. In the event of a fault the fuse ruptures, diverting all the fault current through the trip coil, tripping the breaker. A residually connected trip coil provides instantaneous earth fault protection.

Protection application guideProduct CE2, CN2, RN2d, RE2d CE6, RN6dApplication Transformers Transformers Ring feeders Incomers

200-1600 kVA 400-3800 kVA 1900-12000 kVA 1900-12000 kVA 1900-12000 kVA

Time fuse Link b

IDMT VIP 400 b b b b

Note: a protection co-ordination study may be necessary to verify the type of protection. Consult your local Schneider Electric sales engineer if in doubt.

Protection selection guidePrimary current (A) 10 20 80 100 125 200 630Equivalent transformer rating at 11 kV 200 kVA 400 kVA 1600 kVA 1900 kVA 2400 kVA 3800 kVA 12000 kVA

Application Panel Protection

Transformer protection

CE2/CN2 Time Fuse Link b b b

RE2d/RN2d IDMT-VIP 40/45 b b b b b

RE2d/RN2d IDMT - VIP 400 b b b b b

Feeder protection CE6/RN6d IDMT - VIP 400 b b b b

DE6

0245

-1

Page 16: 2017 Catalogue - s; E

schneider-electric.com14 | Ringmaster Catalogue

Presentation ProtectionVIP protection relays

PM10

0573

VIP 40/45

PM10

0578

VIP 400

VIP 40/45 & VIP 400 - self-powered integrated protection relay

Optimised performance for transformer, incomer, feeder and bus riser protection• Complete engineered and pre-tested protection system: dedicated CT and low

power actuator (Mitop)• Savings on space and cabling time• Optimised for circuit breaker to work together in an optimum manner:• Simple protection, easy to implement• Perfectly adapted to dedicated applications

VIP 40/45: designed for transformer protection• MV/LV transformer protection up to 200A• Dedicated protection curve to protect against overloads, short-circuits and earth

faults with straight-forward settings• Designed up to 200 A circuit breakers to replace fuse-switch solutions

VIP 400: designed for buildings and MV/LV substation utilities• Substation protection (incomers, feeders, bus risers) using 200/630A circuit

breaker• MV/LV transformer protection instead of VIP 40/45 if more functions are required• DT (Definite Time) and IDMT (Inverse Definite Minimum Time) standardised

tripping curves• Switchgear diagnostics• Multi-language display• Metering functions

Transformer protection

General use

protection

VIP 40 VIP 45 VIP 400Phase overcurrent (ANSI 50-51) b b b

Earth fault phase (ANSI 51N)Standard (sum of current method) b bHigh sensitivity (earth fault CTs)

Thermal overload (ANSI 49) bCold load pick-upMeasurement functionsPhase current b b bEarth current b bPhase peak demand current b b bLoad history Cumulative time bControl and monitoring functions

Trip indicationLocal (with origin of the fault) b b bRemote (one contact) (3) b b b3 output relays

Trip circuit supervision (ANSI 74TC) b b b

Time-tagged eventsLocal on display (5 last trips) bRemote, via communication

External tripping input

Overcurrent & breaking profile Number of phase and earth trips bSerial communication port Modbus RS485Power supply

Type of supplySelf-powered or auxiliary self self selfMinimum load current to activate the VIP 4A 4A 7A (2)

Schneider Electric functional units including a circuit breaker core unit can be equipped for self powered protection with:

- A VIP 40, 45 or 400 protection relays, integrated in an optimised functional block to form a protection system dedicated to the application

- Simple protection, easy to implement

- High sensitivity sensors to provide the highest level of reliability and sensitivity from 0.2 A to 20 In.

Page 17: 2017 Catalogue - s; E

Transformer protection

General use

protection

VIP 40 VIP 45 VIP 400Phase overcurrent (ANSI 50-51) b b b

Earth fault phase (ANSI 51N)Standard (sum of current method) b bHigh sensitivity (earth fault CTs)

Thermal overload (ANSI 49) bCold load pick-upMeasurement functionsPhase current b b bEarth current b bPhase peak demand current b b bLoad history Cumulative time bControl and monitoring functions

Trip indicationLocal (with origin of the fault) b b bRemote (one contact) (3) b b b3 output relays

Trip circuit supervision (ANSI 74TC) b b b

Time-tagged eventsLocal on display (5 last trips) bRemote, via communication

External tripping input

Overcurrent & breaking profile Number of phase and earth trips bSerial communication port Modbus RS485Power supply

Type of supplySelf-powered or auxiliary self self selfMinimum load current to activate the VIP 4A 4A 7A (2)

Presentation Remote Terminal UnitT300 telecontrol

Ringmaster and Easergy T300

Control your Ringmaster remotely

The Schneider Electric Easergy T300 telecontrol cabinet, which links the Ringmaster to a control centre’s automation system, allows you to manage a secondary distribution network from a remote point. Network faults can be identified and isolated and the network reconfigured in seconds without manual intervention, which substantially improves the quality of supply.

The compact and Modular Easergy T300 can be easily mounted directly onto the Ringmaster, saving installation costs and valuable floor space.

Telecontrol equipment can be added any time after installation. This makes Ringmaster RMU’s even more cost-effective to install, since a control system can be bought separately if needed at a later date.

PM10

5713

Ringmaster RN2d with Easergy T300

EM10

0102

EM10

0101

EM10

0103

Home pageMonitoring / Data / StatusDiagnostic / Events

Easergy T300 web server pages

schneider-electric.com | 15Ringmaster Catalogue

Page 18: 2017 Catalogue - s; E

Presentation Network remote control SCADA

Continuity of service through modular, modern feeder automation solution

Schneider Electric offers you a complete solution, including:• Easergy T300 telecontrol interface,• Switchgear that is adapted for telecontrol.

PE56

312

L500 network monitoring screen

DE4

0901

EN

PE57

073E

N

RN2d RN2d RN2d

RN2dRN2d RN2d

Network control centre

HV/MV

Communication network

MV ring

Easergy L500, a cost effective solution to immediately improve your SAIDI (1)

Easergy L500 is a SCADA providing all the functions needed to operate the MV network in real time• Pre-configured with Easergy range products:• MV/LV substations equipped with T300 or Flair 200C

- overhead line equipped with Flite 116/G200• Broad range of transmission supports: Radio, GSM, GPRS, PSTN, LL, FO.

Advantages• Simple implementation:

- one to two weeks only for 20 MV/LV substations - configuration, training and handling within a few days

• Short return on investment• Simple and fast evolutions by operations managers• Service quality and operations rapidly improved.

(1) SAIDI: System Average Interruption Duration IndexNota: Please consult us for other SCADA platforms, PACiS, OaSys.

schneider-electric.com16 | Ringmaster Catalogue

Page 19: 2017 Catalogue - s; E

schneider-electric.com | 17Ringmaster Catalogue

Presentation

AccessoriesAccessories for the Ringmaster range are supplied either fitted or loose, where stated enabling simple panel configuration on site. Details of accessories are contained within the panel type pages.

Need more information?If your requirements are not listed, please contact your local Schneider Electric representative at: www.schneider-electric.com/b2b/en/support/

Electronic catalogue requestsElectronic copies of this selection guide are available free of charge upon request. For this, and other MV literature, please email your full contact details to Email: [email protected]

RN2d or RN6d RE2d MU2d or

MU6d CN2 SN6 CE2 or CE6 SE6

200 A or 630 A non extensiblering main unit

200 A extensible

ring main unit

200 A or 630 A feeder

metering unit

200 A non extensible circuit breaker

630 A non

extensible switch

200 A or 630 A extensible

circuit breaker

630 A extensible

switch

PE57

072-

1

Ringmaster selection guide

Key to product referencesRingmaster is available as standard panel types, allowing easy selection and specification. The product references are made up as follows:

R Ring main unit 2 200 A

C Standalone circuit breaker 6 630 A

S Stand-alone switch 16 16 kA

N Non-Extensible 21 21 kA

E Extensible

MU Metering unit

Example: RN2d-T1/21 = Ringmain unit with 2nos load break switch and 1no, 200 A circuit breaker, non-extensible, 21kA fault rating.

The Ringmaster catalogue allows easy selection and specification, based on a broad range of worldwide applications. Included in this publication is: • panel type specifications • details of optional accessories• schematic diagrams• Installation drawings.

Page 20: 2017 Catalogue - s; E

schneider-electric.com18 | Ringmaster Catalogue

Presentation Range selection process

200A 630A 200A 630A

Protection systems (TFL / Relay) electrical operation

Options

Complete the order form

T1 - TFLT5 - Glass TFL

T2 - VIP400T3 - VIP40T4 - VIP45

200A 630A

Select CTs / VTs

Accessories selection (Padlocks, gland plates etc.)

Metering unitsRing main units

Ringmaster rangeRing main unit

Ringmaster 630 A Breaker Switch Breaker

Non extensible / extensible 16 kA or 21 kA

630A

Accessories selection

Selection Matrix

Page 21: 2017 Catalogue - s; E

schneider-electric.com | 19Ringmaster Catalogue

Notes

Page 22: 2017 Catalogue - s; E

schneider-electric.com20 | Ringmaster Catalogue

Ring main units

Page 23: 2017 Catalogue - s; E

schneider-electric.com | 21Ringmaster Catalogue

Ring main units

Characteristics Electrical and Mechanical

22

Non-extensible ring main unitsSpecification

Accessories

23

Non-extensible ring main units 200 ARN2d-T1, RN2d-T2, RN2d-T3, RN2d-T4, RN2d-T5

26

Non-extensible ring main units 630 ARN6d-T1

31

Extensible ring main unitsSpecification

Accessories

32

Extensible ring main units 200 ARE2d-T1, RE2d-T2, RE2d-T3, RE2d-T4

35

Page 24: 2017 Catalogue - s; E

schneider-electric.com22 | Ringmaster Catalogue

Ring main units Characteristics Electrical and Mechanical

Characteristics of RingmasterRated voltage (Ur) kV 12 13.8Rated frequency (fr) Hz 50/60 50/60Rated lightning impulse withstand voltage (Up) kV 75 95Rated power frequency withstand voltage (Ud) kV 28 38Rated currentRing switches (Ir) A 630 630Circuit breaker (Ir) A 200/630 200/630Ring switch rated short time withstand, 3 s (Ik) kA 16 21Ring switch earth short time withstand, 3 s (Ik) kA 16 21Ring switch peak making current (Ip) kA 40 52.5Ring switch earth peak making current (Ip) kA 40 52.5Circuit breaker short time withstand, 3 s (Ik) kA 16 21Ciruit breaker earth short time withstand, 3 s (Ik) kA 16 21Circuit breaker peak making current (Ip) kA 40 53Circuit breaker earth peak making current (Ip) kA 40 53

Internal arc withstand - gas enclosure (1 s) kA 21 (A-FLR) 21 (A-FLR)*

Internal arc withstand - cable box (1 s) kA 13.1(AF)**

Number of operating cyclesMechanical: ring switch (main) 5000 5000

ring switch 5000 5000ring switch (earth) 1000 1000circuit breaker (main) 2000 2000circuit breaker (earth) 1000 1000circuit breaker (at rated short circuit breaking current)

11 10

SF6 gasPressure bar G 0.35 0.55Weight (RN2d/RN6d) g 516 592Weight (RE2d) g 612 703

*: 21kA (AF) as option - Please consult us for details.** 21kA (AF) - Please consult us.

Page 25: 2017 Catalogue - s; E

Ring main units Non-extensible ring main unitsSpecification

RN2d-T1TFL

RN2d-T2VIP 400

RN2d-T3VIP 40

RN2d-T4VIP 45

RN2d-T5Glass TFL

RN6d-T1VIP 400

EnvironmentIndoor / outdoor b b b b b bIP54 b b b b b bTransformer mounted b b b b b bFreestanding O O O O O bRatingsBusbars 630 A b b b b b bCircuit breaker normal rated current 200 A b b b b bCircuit breaker normal rated current 630 A bSwitch normal rated current 630 A b b b b b b12 kV 16 kA 3 seconds 75 kV BIL b b b b b b13.8 kV 21 kA 3 seconds 95 kV BIL O O O O O ORing switch cable earth switch 16 kA 3 seconds b b b b b bRing switch cable earth switch 21 kA 3 seconds O O O O O OCircuit breaker earth switch 3.15 kA b b b b b bMechanismIndependent manual b b b b b bProvision for motorised mechanism LH ring switch b b b b b bProvision for motorised mechanism RH ring switch b b b b b bProvision for motorised mechanism circuit breaker O O O O O OProtection & control - circuit breakerCT’s dual ratio - 100/50/5 A class X b bCT’s ratio - 200/1 A class X bCT’s ratio - 200/100/1 5P20CT’s ratio - 500/200/1 A class X b bCT’s ratio - 800/400/1 A class X bCT’s ratio - 800/400/1 5P20Overcurrent & earth fault CT operated trip coils - TFL bOvercurrent & earth fault CT operated trip coils - glass TFL bOvercurrent relay - VIP 40 bOvercurrent & earth fault relay - VIP 45 bIDMT overcurrent & earth fault relay - VIP 400 b bMulti voltage shunt trip coil O b b b b bIndicationMechanical ON/OFF b b b b b bMechanical EARTH/MAIN b b b b b bVPIS indication 6.6 - 13.8 kV b b b b b bGas pressure indicator (-25°C to +55°C) b b b b b bRSW aux contacts 1NO & 1NC O O O O O OTest facilityIntegral ring cable test facility b b b b b bIntegral circuit breaker test facility O O O O O bStandard featuresOperating handle b b b b b bCable (see available cable kit accessories)Bottom entry up 1 x 3C 300 mm2 b b b b b bBottom entry up 3 x 1C 630 mm2 b b b b b bTop entry cables (indoor only) O O O O O OOrder codes12 kV, 16 kA, 75 kV BIL

RN2d-T1/16 RN2d-T2/16 RN2d-T3/16 RN2d-T4/16 RN2d-T5/16 RN6d-T1/16

13.8 kV, 21 kA, 95 kV BILRN2d-T1/21 RN2d-T2/21 RN2d-T3/21 RN2d-T4/21 RN2d-T5/21 RN6d-T1/21

Key: b Standard feature O Optional feature

schneider-electric.com | 23Ringmaster Catalogue

Page 26: 2017 Catalogue - s; E

Ring main units Non-extensible ring main unitsAccessories

RN2d- T1 TFL

RN2d-T2VIP 400

RN2d-T3VIP 40

RN2d-T4VIP 45

RN2d-T5Glass FL

RN6d-T1VIP 400 Kit no.

Cable kitsCircuit breaker cable box v v v v v RMD-F47Circuit breaker cable box with integral cable test facility v v v v v b RMD-F325Gland plate 1 x 3C O O O O O O RMD-A316Gland plate 3 x 1C O O O O O O RMD-A319Small gland plate 1 x 3C O O O O O O RMD-A322Blank galvanised gland plate O O O O O O RMD-A320Galvanised steel wiping plate 1 x 3C O O O O O RMD-A10Galvanised steel wiping plate 3 x 1C O O O O O O RMD-A11Galvanised steel wiping plate 1 x 3C O O O O O O RMD-A105Tubular gland 1 x 3C O O O O O O RMD-A12Tubular gland 3 x 1C O O O O O O RMD-A13Small tubular gland O O O O O O RMD-A106CES5 gland O O O O O O RMD-A120CES5 gland plate 1 x 3C O O O O O O RMD-A321CES5 gland adaptor O O O O O O RMD-A525Top entry cables RH cable box (indoor only) v v v v v v RMD-F303Top entry cables LH cable box (indoor only) v v v v v v RMD-F302RSW extension box for 2 x 3C cables (left hand) v v v v v v RMD-F523RSW extension box for 2 x 3C (right hand) v v v v v v RMD-F522Angled gland plate 1 x 3C O O O O O O RMD-A317Split gland plate 1 x 3C O O O O O O RMD-A318Installation itemsTransformer mounting kit v v v v v v RMD-A461Extension trunking (to clear transformer radiators) O O O O O O RMD-A20Set of padlocks - 11 no O O O O O O RMD-A343Anti-vandal fixings, including tool O O O O O O RMD-A344Foundation bolts (not required for transformer mounting) O O O O O O RMD-A22Multicore pilot glands O O O O O O RMD-A342Time Fuse Link O O O O O O RMD-A17RN2d to MU2d installation kit v v v v v v RMD-A350Ariel mounting bracket O O O O O O RMD-A201Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

schneider-electric.com24 | Ringmaster Catalogue

Page 27: 2017 Catalogue - s; E

Ring main units Non-extensible ring main unitsAccessories

RN2d-T1TFL

RN2d-T2VIP 400

RN2d-T3VIP 40

RN2d-T4VIP 45

RN2d-T5Glass TFL

RN6d-T1VIP 400 Kit no.

Operational itemsOperating handle b b b b b b RMD-F345LH ring switch control auxiliary sw for motorised mechanism provision

v v v v v vRMD-F328

LH ring switch termination block for motorised mechanism provision (not FRTU)

v v v v v vRMD-F363

RH ring switch control auxiliary sw for motorised mechanism provision

v v v v v vRMD-F329

RH ring switch termination block for motorisedmechanism provision (not FRTU)

v v v v v vRMD-F364

Provision for motorised mechanism circuit breaker v v v v v b RMD-F543Motorised mechanism v v v v v v RMD-F507Shunt trip coil (20-250 V DC, 110-250 V AC) TFL

v v v v v vRMD-F581

Shunt trip coil (20-250 V DC, 110-250 V AC) VIP

v v v v v vRMD-F582

Ring switch cable VPIS indication (3.3-13.8 kV)

v v v v v vRMD-F341

Circuit breaker cable VPIS indication (11-13.8 kV)

v v v v v vRMD-F340

Phase indication device O O O O O O RMD-A374Emergency trip push button v v v v v v RMD-F339Gas pressure switch for remote indication only v v v v v v RMD-F368Mechanical interlocksCircuit breaker - key free, EARTH ON v v v v v v RMD-F337Circuit breaker - key free, MAIN OFF v v v v v v RMD-F338Switch - key free, SWITCH OFF LH v v v v v v RMD-F335Switch - key free, SWITCH OFF RH v v v v v v RMD-F336N. B. specify lock symbol at time of ordering (3 digits max) not available with motor mechanisms

Earth fault passage indication (choose provision kit and an EFPI required if not using Easergy T300)Phase & earth fault provision for Easergy T300 O O O O O O RMD-F310EFPI provision kit, inside cable box O O O O O O RMD-A304EFPI provision kit, CT outside cable box O O O O O O RMD-A305EFPI provision kit, inside cable box, top entry O O O O O O RMD-A308EFPI provision kit, outside cable box, top entry O O O O O O RMD-A309Bowden “RR” EFPI and CT O O O O O O RMD-A422Bowden STD EFPI type NB O O O O O O RMD-A277Bowden LV reset EFPI type NB1 O O O O O O RMD-A278Bowden LV reset & alarm type NB2 O O O O O O RMD-A279N. B. above CT’s are ring type for split core - please consult Schneider Electric

Key: v Factory fitted accessory O Loose accessory, assembled on site

schneider-electric.com | 25Ringmaster Catalogue

Page 28: 2017 Catalogue - s; E

Ring main units Non-extensible ring main unit 200 A RN2d-T1

Protection & control - CBOvercurrent and earth fault protection using CT operated trip coils with provision for time fuse links Protection CT’s - 100/50/5 A class X

Transformer ratingsSee table on Time Fuse Link - page13

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 21kA 1s IAC class A-FLR for gas enclosure *Internal arc 13.1kA 1s IAC AF classification for cable boxes **Normal current rating 630 A/200 ANormal rated voltage 12/13.8 kV

Normal rated BIL 75/95 kV

Operating mechanismIndependent manual

Standard featuresRing cable earth switch, 16/21 kA 3 sTransformer earth switch, 16/21 kA 3 sAnti-reflex operating handleProvision for motorised mechanism LH/RH ring switch with plug interface

IndicationMechanical tripped on fault flag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 1NCCB earth position selected 1NOCB earth ON, 1NO

Test facilityIntegral ring switch cable test facility

CableBottom entry up to 1 x 3C 300 mm2

Bottom entry up to 3 x 1C 630 mm2

DE6

0180

DE6

0181

Accessories

CB, LH, RH motor kits

LH, RH ring switch indication 1NO 1NC earth On 1NOMulti voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCVPIS indicationInverted cable boxes (indoor only)Transformer mounting kitFreestanding tee-off cable box

Order information

Code RatingRN2d-T1/16 16 kA, 12 kV, 75 kV BILRN2d-T1/21 21 kA, 13.8 kV, 95 kV BIL

Transformer protection up to 1.6 MVA at 11 kV

[*] 21kA (AF) - Please consult us.[**] 21kA (AF) - Please consult us.

schneider-electric.com26 | Ringmaster Catalogue

Page 29: 2017 Catalogue - s; E

Ring main units Non-extensible ring main unit 200 A RN2d-T2

Protection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 400. In accordance with IEC 60255 and BS142Protection CT’s - 200/1 A class X• Setting range:

- Overcurrent: 20-200 A - Earth fault: 2-160 A

Transformer ratingsSee table on Time Fuse Link - page 13

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 21kA 1s IAC class A-FLR for gas enclosure *Internal arc 13.1kA 1s IAC class AF for cable boxes **Normal current rating 630 A/200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manual

Standard featuresRing cable earth switch, 16/21 kA 3 sTransformer earth switch, 16/21 kA 3 sAnti-reflex operating handleProvision for motorised mechanism LH/RH ring switch with plug interfaceMulti voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCVPIS indication

IndicationMechanical tripped on fault flag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 1NCCB earth position selected 1NOCB earth ON, 1NO

Test facilityIntegral ring switch cable test facility

CableBottom entry up to 1 x 3C 300 mm2

Bottom entry up to 3 x 1C 630 mm2

DE6

0180

DE6

0185

AccessoriesCB LH, RH motor kitsLH, RH ring switch indication 1NO 1NC earth On 1NOInverted cable boxes (indoor only)Transformer mounting kit

Freestanding tee-off cable box

Order information

Code RatingRN2d-T2/16 16 kA, 12 kV, 75 kV BILRN2d-T2/21 21 kA, 13.8 kV, 95 kV BIL

[*] 21kA (AF) - Please consult us.[**] 21kA (AF) - Please consult us.

schneider-electric.com | 27Ringmaster Catalogue

Transformer protection up to 3.5 MVA at 11 k

Page 30: 2017 Catalogue - s; E

Ring main units

Protection & control - CBSelf powered overcurrent relay, VIP 40. Protection CT’s - 500/200/1 A class X• Setting range: 500/1 A

- Overcurrent: 20-200 A• Setting range: 200/1 A

- Overcurrent: 8-80 A

Transformer ratingsSee table on Time Fuse Link - page13

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 21kA 1s IAC class A-FLR for gas enclosure *Internal arc 13.1kA 1s IAC class AF for cable boxes **Normal current rating 630 A/200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manual

Standard featuresRing cable earth switch, 16/21 kA 3 sTransformer earth switch, 16/21 kA 3 sAnti-reflex operating handleProvision for motorised mechanism LH/RH ring switch with plug interface

IndicationMechanical tripped on fault flag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 1NCCB earth position selected 1NOCB earth ON, 1NO

Test facilityIntegral ring switch cable test facility

CableBottom entry up to 1 x 3C 300 mm2

Bottom entry up to 3 x 1C 630 mm2

Non-extensible ring main unit 200 A RN2d-T3

DE6

0180

DE6

0182

AccessoriesCB, LH, RH motor kitLH, RH ring switch indication 1NO 1NC earth On 1NOMulti voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCVPIS indicationInverted cable box (indoor only)Transformer mounting kitFreestanding tee-off cable box

Order information

Code RatingRN2d-T3/16 16 kA, 12 kV, 75 kV BILRN2d-T3/21 21 kA, 13.8 kV, 95 kV BIL [*] 21kA (AF) - Please consult us.

[**] 21kA (AF) - Please consult us.

schneider-electric.com28 | Ringmaster Catalogue

MV transformer protection

Page 31: 2017 Catalogue - s; E

Ring main units

Protection & control - CBSelf powered overcurrent and earth fault relay, VIP 45.Protection CT’s - 500/200/1 A class XCH30 core balance CT• Setting range: 500/1 A

- Overcurrent: 20-200 A - Earth fault: 25-300 A

• Setting range: 200/1 A - Overcurrent: 8-80 A - Earth fault: 10-120 A

Transformer ratingsSee table on Time Fuse Link - page13

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 21kA 1s IAC class A-FLR for gas enclosure *Internal arc 13.1kA 1s IAC class AF for cable boxes **Normal current rating 630 A/200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manual

Standard featuresRing cable earth switch, 16/21 kA 3 sTransformer earth switch, 16/21 kA 3 sAnti-reflex operating handleProvision for motorised mechanism LH/RH ring switch with plug interface

IndicationMechanical tripped on fault flag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 1NCCB earth position selected 1NOCB earth ON, 1NO

Test facilityIntegral ring switch cable test facility

CableBottom entry up to 1 x 3C 300 mm2

Bottom entry up to 3 x 1C 630 mm2

Non-extensible ring main unit 200 A RN2d-T4

DE6

0180

DE6

0183

AccessoriesCB, LH, RH motor kitsLH, RH ring switch indication 1NO 1NC earth On 1NOMulti voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCVPIS indicationInverted cable boxes (indoor only)Transformer mounting kitFreestanding tee-off cable box

Order information

Code RatingRN2d-T4/16 16 kA, 12 kV, 75 kV BILRN2d-T4/21 21 kA, 13.8 kV, 95 kV BIL

MV transformer protection

[*] 21kA (AF) - Please consult us.[**] 21kA (AF) - Please consult us.

schneider-electric.com | 29Ringmaster Catalogue

Page 32: 2017 Catalogue - s; E

Ring main units

Protection & control - CBOvercurrent and earth fault protection using CT operated trip coils with provision for time fuse links (glass fuse link)Protection CT’s - 100/50/5 A class X

Transformer ratingsSee table on Time Fuse Link - page13

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 21kA 1s IAC class A-FLR for gas enclosure *Internal arc 13.1kA 1s IAC class AF for cable boxes **Normal current rating 630 A/200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manual

Standard featuresRing cable earth switch, 16/21 kA 3 sTransformer earth switch, 16/21 kA 3 sAnti-reflex operating handleProvision for motorised mechanism LH/RH ring switch with plug interface

IndicationMechanical tripped on fault flag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 1NCCB earth position selected 1NOCB earth ON, 1NO

Test facilityIntegral ring switch cable test facility

CableBottom entry up to 1 x 3C 300 mm2

Bottom entry up to 3 x 1C 630 mm2

Non-extensible ring main unit 200 A RN2d-T5

DE6

0180

DE6

0184

AccessoriesCB, LH, RH motor kitsLH, RH ring switch indication 1NO 1NC earth On 1NOMulti voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCVPIS indicationInverted cable boxes (indoor only)Transformer mounting kitFreestanding tee off cable box

Order information

Code RatingRN2d-T5/16 16 kA, 12 kV, 75 kV BILRN2d-T5/21 21 kA, 13.8 kV, 95 kV BIL

Transformer protection up to 1.6 MVA at 11 kV

[*] 21kA (AF) - Please consult us.[**] 21kA (AF) - Please consult us.

schneider-electric.com30 | Ringmaster Catalogue

Page 33: 2017 Catalogue - s; E

Ring main units

Protection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 400. In accordance with IEC 60255 and BS142Protection CT’s - 800/400/1 A class X

• Setting range: 800/1 A ratio - Overcurrent: 80-800 A - Earth fault: 8-640 A

• Setting range: 400/1 A - Overcurrent: 40-400 A - Earth fault: 4-320 A

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 21kA 1s IAC class A-FLR for gas enclosure *Internal arc 13.1kA 1s IAC class AF for cable boxes **Normal current rating 630 A/630 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manual

Standard featuresCircuit breaker earth switch 16/21 kARing cable earth switch, 16/21 kA 3 sAnti-reflex operating handleProvision for motorised mechanism LH/RH ring switch and circuit breaker with plug interface

IndicationMechanical tripped on fault flag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 1NCCB earth position selected 1NOCB earth ON, 1NO

Test facilityIntegral ring switch and circuit breaker test facility

CableBottom entry up to 1 x 3C 300 mm2

Bottom entry up to 3 x 1C 630 mm2

Non-extensible ring main unit 630 A RN6d-T1

DE6

0180

DE6

0186

AccessoriesCB, LH, RH motor kitsLH, RH ring switch indication 1NO 1NC earth On 1NOMulti voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCVPIS indicationInverted cable boxes (indoor only)Freestanding

Order information

Code RatingRN6d-T1/16 16 kA, 12 kV, 75 kV BILRN6d-T1/21 21 kA, 13.8 kV, 95 kV BIL [*] 21kA (AF) - Please consult us.

[**] 21kA (AF) - Please consult us.

schneider-electric.com | 31Ringmaster Catalogue

Network sectionalising up to 12 MVA 11 kV

Page 34: 2017 Catalogue - s; E

Ring main units Extensible ring main unitsSpecification

RE2d-T1 TFL

RE2d-T2 VIP 400

RE2d-T3 VIP 40

RE2d-T4 VIP 45

EnvironmentIndoor / outdoor b b b bIP54 b b b bTransformer mounted b b b bFreestanding b b b bExtensible (RHS) O O O ORatingsBusbars 630 A b b b bCircuit breaker normal rated current 200 A b b b bCircuit breaker normal rated current 630 ASwitch normal rated current 630 A b b b b12 kV 16 kA 3 seconds 75 kV BIL b b b b13.8 kV 21 kA 3 seconds 95 kV BIL O O O ORing switch cable earth switch 16 kA 3 seconds b b b bRing switch cable earth switch 21 kA 3 seconds O O O OCircuit breaker earth switch 3.15 kA b b b bExtensible RMU busbar chamber 630 A O O O OMechanismIndependent manual b b b bProvision for motorised mechanism LH ring switch b b b bProvision for motorised mechanism RH ring switch b b b bProvision for motorised mechanism circuit breaker O O O OProtection & control - circuit breakerCT’s dual ratio - 100/50/5 A class X bCT’s ratio - 200/1 A class X bCT’s dual ratio 200/100/1 A 5P20CT’s ratio - 500/200/1 A class X b bOvercurrent & earth fault CT operated trip coils - TFL bOvercurrent relay - VIP 40 bOvercurrent & earth fault relay - VIP 45 bIDMT overcurrent & earth fault relay - VIP 400 bIDMT relay Sepam 10Multi voltage shunt trip coil (see accessories) O b b bIndicationMechanical ON/OFF b b b bMechanical EARTH/MAIN b b b bVPIS indication 6.6 - 13.8 kV b b b bGas pressure indicator (-25°C to +55°C) b b b bRSW aux contacts 1NO & 1NC O O O OTest facilityIntegral ring cable test facility b b b bStandard featuresOperating handle b b b bCable (see available cable kit accessories)Bottom entry up 1 x 3C 300 mm2 b b b bBottom entry up 3 x 1C 630 mm2 b b b bTop entry cables (indoor only) (left hand side only) O O O OOrder codes12 kV, 16 kA, 75 kV BIL RE2d-T1/16 RE2d-T2/16 RE2d-T3/16 RE2d-T4/1613.8 kV, 21 kA, 95 kV BIL RE2d-T1/21 RE2d-T2/21 RE2d-T3/21 RE2d-T4/21Key: b Standard feature O Optional feature

schneider-electric.com32 | Ringmaster Catalogue

Page 35: 2017 Catalogue - s; E

Ring main units Extensible ring main unitsAccessories

RE2d-T1 TFL

RE2d-T2 VIP 400

RE2d-T3 VIP 40

RE2d-T4 VIP 45

Kit no.

Cable kitsExtensible ring main units v v v v RMD-F47Gland plate 1 x 3C O O O O RMD-A316Gland plate 3 x 1C O O O O RMD-A319Small gland plate 1 x 3C O O O O RMD-A322Blank galvanised gland plate O O O O RMD-A320Galvanised steel wiping gland 1 x 3C O O O O RMD-A10Galvanised steel wiping gland 3 x 1C O O O O RMD-A11Small galvanised steel wiping gland 1 x 3C O O O O RMD-A105Tubular gland 1 x 3C O O O O RMD-A12Tubular gland 3 x 1C O O O O RMD-A13Small tubular gland 1 x 3C O O O O RMD-A106CES5 gland O O O O RMD-A120CES5 gland plate 1 x 3C O O O O RMD-A321CES5 gland plate adaptor O O O O RMD-A525Top entry cables LH cable box (indoor only) v v v v RMD-A317Angled gland plate 1 x 3C O O O O RMD-A318Split gland plate 1 x 3C O O O O RMR-A318Installation itemsTransformer mounting kit v v v v RMD-A461Extension trunking (to clear radiators) O O O O RMD-A20Set of padlocks - 11 no O O O O RMD-A343Anti-vandal fixings, including tool O O O O RMD-A344Foundation bolts (not required for transformer mounting) O O O O RMD-A22Multicore pilot glands O O O O RMD-A342Time Fuse Link (set of 2 - specify rating as table page 133) O O O O RMD-A17RE2d to MU2 installation kit v v v v RMD-A350Extensible busbar chamber 630 A O O O O RMD-F369Ariel mounting bracket O O O O RMD-A201Operational itemsOperating handle b b b b RMD-F345LH ring switch control auxiliary sw for motorised mechanism provision v v v v RMD-F328LH ring switch termination block for motorised mechanism provision (not Easergy)

v v v v RMD-F363

RH ring switch control auxiliary sw for motorised mechanism provision v v v v RMD-F329RH ring switch termination block for motorised mechanism provision (not Easergy)

v v v v RMD-F364

Provision for motorised mechanism circuit breaker v v v v RMD-F543Motorised mechanism v v v v RMD-F507Shunt trip coil (20-250 V DC, 110-250 V AC) TFL v v v v RMD-F581Shunt trip coil (20-250 V DC, 110-250 V AC) VIP v v v v RMD-F582Ring switch cable VPIS indication (3.3-13.8 kV) v v v v RMD-F341Circuit breaker VPIS indication (11-13.8 kV) v v v v RMD-F340Phase indication device v v v v RMD-A374Emergency trip push button v v v v RMD-F339Gas pressure switch for remote indication only v v v v RMD-F368Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

schneider-electric.com | 33Ringmaster Catalogue

Page 36: 2017 Catalogue - s; E

Ring main units Extensible ring main unitsAccessories

RE2d-T1 TFL

RE2d-T2 VIP 400

RE2d-T3 VIP 40

RE2d-T4 VIP 45

Kit no.

Mechanical interlocksCircuit breaker - key free, earth on v v v v RMD-F337Circuit breaker - key free, main off v v v v RMD-F338Switch - key free, switch off LH v v v v RMD-F335Switch - key free, switch off RH v v v v RMD-F336N. B. specify lock symbol at time of ordering (3 digits max) not available with motor mechanisms

Earth fault passage indication (choose provision kit and an EFPI required if not using Easergy T300)Phase & earth fault provision for Easergy T300 O O O O RMD-F310EFPI provision kit, inside cable box O O O O RMD-A304EFPI provision kit, CT outside cable box O O O O RMD-A305EFPI provision kit, inside cable box, top entry O O O O RMD-A308EFPI provision kit, outside cable box, top entry O O O O RMD-A309Bowden “RR” EFPI and CT O O O O RMD-A422Bowden STD EFPI type NB O O O O RMD-A277Bowden LV reset EFPI type NB1 O O O O RMD-A278Bowden LV reset & alarm type NB O O O O RMD-A279

N. B. above CT’s are ring type for split core - please consult Schneider ElectricKey: v Factory fitted accessory O Loose accessory, assembled on site

schneider-electric.com34 | Ringmaster Catalogue

Page 37: 2017 Catalogue - s; E

Ring main units Extensible ring main unit 200 A RE2d-T1

Protection & control - CBOvercurrent and earth fault protection using CT operated trip coils with provision for time fuse links.Protection CT’s - 100/50/5 A class X

Transformer ratingsSee table on Time Fuse Link - page 13

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 21kA 1s IAC class A-FLR for gas enclosure *Internal arc 13.1kA 1s IAC class AF for cable boxes **Normal current rating 630 A/200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manual

Standard featuresRing switch cable earth switch, 16/21 kA 3 sTransformer earth switch, 16/21 kA 3 sAnti-reflex operating handleExtensible (RHS)Provision for motorised mechanism LH/RH ring switch with plug interface

IndicationMechanical tripped on fault flag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 1NCCB earth position selected 1NOCB earth ON, 1NO

Test facilityIntegral ring switch test facility

CableBottom entry up to 1 x 3C 300 mm2

Bottom entry up to 3 x 1C 630 mm2

Accessories

DE6

0211

DE6

0187

CB, LH, RH motor kitsLH, RH ring switch indication 1NO 1NC earth On 1NOMulti voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCVPIS indicationIntegral circuit breaker test facilityInverted cable boxes LH, CB (indoor only)Transformer mounting kitFreestanding tee-off cable box

Order information

Code RatingRE2d-T1/16 16 kA, 12 kV, 75 kV BILRE2d-T1/21 21 kA, 13.8 kV, 95 kV BIL

Multiple transformer feeders or network switching points

schneider-electric.com | 35Ringmaster Catalogue

[*] 21kA (AF) - Please consult us.[**] 21kA (AF) - Please consult us.

Page 38: 2017 Catalogue - s; E

Ring main units Extensible ring main unit 200 A RE2d-T2

Protection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 400. In accordance with IEC 60255 and BS 142.Protection CT’s - 200/1 A class X

• Setting range: - Overcurrent: 20-200 A - Earth fault: 2-160 A

Transformer ratingsSee table on Time Fuse Link - page13

DocumentsInstallation drawing ref: RMINST-22Schematic drawing ref: RMSCH-03

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 21kA 1s IAC class A-FLR for gas enclosure *Internal arc 13.1kA 1s IAC class AF for cable boxes **Normal current rating 630 A/200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manual

Standard featuresRing switch cable earth switch, 16/21 kA 3 sTransformer earth switch, 16/21 kA 3 sAnti-reflex operating handleExtensible (RHS)Provision for motorised mechanism LH/RH ring switch

IndicationMechanical tripped on fault flag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 1NCCB earth position selected 1NOCB earth ON, 1NO

Test facilityIntegral ring switch test facility

CableBottom entry up to 1 x 3C 300 mm2

Bottom entry up to 3 x 1C 630 mm2

DE6

0211

DE6

0188

Multiple transformer feeders or network switching points

Accessories CB, LH, RH motor kitsLH, RH ring switch indication 1NO 1NC Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCVPIS indicationInverted cable box LH CB (indoor only)Transformer mounting kitFreestanding tee-off cable box

Order information

Code RatingRE2d-T2/16 16 kA, 12 kV, 75 kV BILRE2d-T2/21 21 kA, 13.8 kV, 95 kV BIL

schneider-electric.com36 | Ringmaster Catalogue

[*] 21kA (AF) - Please consult us.[**] 21kA (AF) - Please consult us.

Page 39: 2017 Catalogue - s; E

Extensible ring main unit 200 A RE2d-T3

Protection & control - CBSelf powered overcurrent relay, VIP 40.Protection CT’s - 500/200/1 A class X

• Setting range: 500/1 A - Overcurrent: 20-200 A

• Setting range: 200/1 A - Overcurrent: 8-80 A

Transformer ratingsSee table on Time Fuse Link - page13

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 21kA 1s IAC class A-FLR for gas enclosure *Internal arc 13.1kA 1s IAC class AF for cable boxes **Normal current rating 630 A/200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manual

Standard featuresRing switch cable earth switch, 16/21 kA 3 sTransformer earth switch, 16/21 kA 3 sAnti-reflex operating handleExtensible (RHS)Provision for motorised mechanism LH/RH ring switch

IndicationMechanical tripped on fault flag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 1NCCB earth position selected 1NOCB earth ON, 1NO

Test facilityIntegral ring switch test facility

CableBottom entry up to 1 x 3C 300 mm2

Bottom entry up to 3 x 1C 630 mm2

DE6

0211

DE6

0189

AccessoriesCB, LH, RH motor kitLH, RH ring switch indication 1NO 1NCMulti voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCVPIS indicationInverted cable boxes LH, CB (indoor only)Transformer mounting kit

Freestanding tee-off cable box

Or der information

Code RatingRE2d-T3/16 16 kA, 12 kV, 75 kV BILRE2d-T3/21 21 kA, 13.8 kV, 95 kV BIL

Ring main units

schneider-electric.com | 37Ringmaster Catalogue

[*] 21kA (AF) - Please consult us.[**] 21kA (AF) - Please consult us.

MV transformer protection

Page 40: 2017 Catalogue - s; E

Extensible ring main unit 200 A RE2d-T4

Protection & control - CBProtection & control - CBSelf powered overcurrent and earth fault relay, VIP 45.Protection CT’s - 500/200/1 A class with CH30 core balance CT

• Setting range: 500/1 A - Overcurrent: 20-200 A - Earth fault 25-300 A

• Setting range: 200/1 A - Overcurrent: 8-80 A - Earth fault 10-120 A

Transformer ratingsSee table on Time Fuse Link - page 13

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 21kA 1s IAC class A-FLR for gas enclosure *Internal arc 13.1kA 1s IAC class AF for cable boxes **Normal current rating 630 A/200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manual

Standard featuresRing switch cable earth switch, 16/21 kA 3 sTransformer earth switch, 16/21 kA 3 sAnti-reflex operating handleExtensible (RHS)Provision for motorised mechanism LH/RH ring switch

IndicationMechanical tripped on fault indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 1NCEarth position selected 1NOEarth ON, 1NO

Test facilityIntegral ring switch test facility

CableBottom entry up to 1 x 3C 300 mm2

Bottom entry up to 3 x 1C 630 mm2

DE6

0211

DE6

0190

AccessoriesCB, LH, RH motor kit LH, RH ring switch indication 1NO 1NCMulti voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCVPIS indicationInverted cable boxes LH, CB (indoor only)Transformer mountingFreestanding tee-off cable box

Order information

Code RatingRE2d-T4/16 16 kA, 12 kV, 75 kV BILRE2d-T4/21 21 kA, 13.8 kV, 95 kV BIL

schneider-electric.com38 | Ringmaster Catalogue

Ring main units

[*] 21kA (AF) - Please consult us.[**] 21kA (AF) - Please consult us.

MV transformer protection

Page 41: 2017 Catalogue - s; E

Notes

schneider-electric.com | 39Ringmaster Catalogue

Page 42: 2017 Catalogue - s; E

schneider-electric.com40 | Ringmaster Catalogue

Circuit breaker metering and switches

Page 43: 2017 Catalogue - s; E

schneider-electric.com | 41Ringmaster Catalogue

Circuit breaker, metering and switches

Characteristics - Electrical & Mechanical 42

Non-extensible circuit breakers 200 ASpecification - Accessories

CN2-T1, CN2-T6

43

45

Non-extensible switches 630 ASpecification - Accessories

SN6-S1, SN6-S2

47

49

Non-extensible metering units 200 ASpecification - Accessories

MU2d-M1/16, MU2d-M2/16, MU2d-M3/16

51

53

Non-extensible metering units 630 ASpecification - Accessories

MU6d-N**

56

58

Extensible circuit breakers 200 ASpecification - Accessories

CE2-T30, CE2-T7, CE2-T*, CE2-T31, CE2-T**, CE2-T35, CE2-T33, CE2-T34

59

62

67

Extensible circuit breakers 630 A Specification - Accessories

CE6-T4, CE6-T*, CE6-T8, CE6-T25, CE6-T**

70

72

Extensible switches 630 A Specification - Accessories

SE6-S1, SE6-S2, SE6-E1

76

78

Extensible bus-section 630 ASpecification - Accessories

SE6-B1, CE6-B3, CE6-B5

81

83

Page 44: 2017 Catalogue - s; E

Characteristics - Electrical & Mechanical

Circuit breaker, metering and switches

Characteristics of RMR switchRated voltage (Ur) kV 12 13.8Rated frequency (fr) Hz 50/60 50/60Rated lightning impulse withstand voltage (Up) kV 75 95Rated power frequency withstand voltage (Ud) kV 28 38Rated currentSwitches (Ir) A 630 630Switch rated short time withstand, 3 s (Ik) kA 16 21Switch earth short time withstand, 3 s (Ik) kA 16 21Switch peak making current (Ip) kA 40 53Switch earth peak making current (Ip) kA 40 53Internal arc withstand kA 16 21Number of operating cyclesMechanical: switch (main) 1000 1000

switch (in option) 2000 2000switch (earth) 1000 1000

SF6 gasPressure bar G 0.35 0.55Weight g 429 493

Characteristics of RMR circuit breakerRated voltage (Ur) kV 12 13.8Rated frequency (fr) Hz 50/60 50/60Rated lightning impulse withstand voltage (Up) kV 75 95Rated power frequency withstand voltage (Ud) kV 28 38Rated currentCircuit breaker (Ir) A 200/630 200/630Circuit breaker short time withstand, 3 s (Ik) kA 16 21Ciruit breaker earth short time withstand, 3 s (Ik) kA 16 21Circuit breaker peak making current (Ip) kA 40 53Circuit breaker earth peak making current (Ip) kA 40 53Number of operating cyclesMechanical: circuit breaker (main) 2000 2000

circuit breaker (earth) 1000 1000circuit breaker (at rated short circuit breaking current)

11 10

SF6 gasPressure bar G 0.35 0.55Weight g 429 493

schneider-electric.com42 | Ringmaster Catalogue

Page 45: 2017 Catalogue - s; E

Circuit breaker, metering and switches

Non-extensible circuit breakers 200 ASpecification

CN2-T9VIP 400

CN2-T6TFL

EnvironmentIndoor / outdoor b bIP54 b b

RatingsNormal rated current 200 A b b12 kV 16 kA 3 seconds 75 kV BIL b b13.8 kV 21 kA 3 seconds 95 kV BIL O OCable earth switch 16 kA 3 seconds b bCable earth switch 21 kA 3 seconds O OTransformer earth switch 3.15 kA 3 seconds b b

MechanismIndependent manual b b

Protection & control - circuit breakerCT’s dual ratio - 100/50/5 A class X bCT’s ratio - 200/1 A class X bCT’s dual ratio 200/100/1 A 5P20Overcurrent & earth fault CT operated trip coils bTime fuse Link OIDMT overcurrent & earth fault relay - VIP 400 bIDMT overcurrent and earth fault relay Sepam 1020 V-250 shunt trip coil b bCircuit breaker auxiliary switch 1NO 2NC b b

IndicationMechanical ON/OFF b bMechanical EARTH/MAIN b bVPIS indication (6.6 - 13.8 kV) O OAuxiliary switch contacts 1NO 2NC b bGas pressure indicator b b

Test facilityIntegral cable test facility b b

Standard featuresOperating handle b bTransformer earth switch 3.15 kA 3 seconds b b

Cable (see available cable kit accessories)Bottom entry up 300 mm2 1 x 3C b bBottom entry up 630 mm2 3 x 1C b bKey: b Standard feature O Optional feature

schneider-electric.com | 43Ringmaster Catalogue

Page 46: 2017 Catalogue - s; E

Circuit breaker, metering and switches

Non-extensible circuit breakers 200 AAccessories

CN2-T9VIP 400

CN2-T6TFL Kit no.

Cable kitsTee-off cable box v v RMR-F47Gland plate 1 x 3C O O RMR-A48Gland plate 3 x 1C O O RMR-A49Angled gland plates (RMR) O O RMR-A50Blank aluminium gland plate O O RMR-A52Brass wiping gland 1 x 3C O O RMR-A10Brass wiping gland 3 x 1C O O RMR-A11Tubular gland 1 x 3C O O RMR-A12Tubular gland 3 x 1C O O RMR-A13CES5 gland plate 1 x 3C O O RMR-A132Installation itemsSet of padlocks - 6 no O O RMR-A18/6Anti-vandal fixings, including tool O O RMR-A19Foundation bolts (not required for transformer mounting) O O RMR-A22Multicore pilot glands O O RMR-A16Time Fuse Link (set of 2 - specify rating as table page 133) O RMR-A17Operational itemsOperating handle b b RMR-A23VPIS indication (6.6-13.8 kV) v v RMR-F108Neon lamp test unit (including lamp) O O RMR-A24Neon lamp O O RMR-A81VAP 6 test unit for VIP 400 O RMR-A202Mechanical interlocksKey free, earth on v v RMR-F85Key free, unit off v v RMR-F86Transformer earth switch, key free, earth on v v RMR-F110N. B. specify lock symbol at time of ordering (3 digits max) not available with motor mechanismsOrder codes12 kV, 16 kA, 75 kV BIL CN2-T9/16 CN2-T6/1613.8 kV, 21 kA, 95 kV BIL CN2-T9/21 CN2-T6/21Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

schneider-electric.com44 | Ringmaster Catalogue

Page 47: 2017 Catalogue - s; E

Circuit breaker, metering and switches

Non-extensible circuit breaker 200 ACN2-T9

Transformer protection up to 3.5 MVA

Protection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 400. In accordance with IEC 60255 and BS142Protection CT’s - 200/1 A class X• Setting range:

- Overcurrent: 20-200 A - Earth fault: 2-160 A

Shunt trip coil, 20 V DC-250 V AC

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manual

Standard featuresTee-off earth switch, 3.15 kA 3 sCable earth switch, 16/21 kA 3 sAnti-reflex operating handle

IndicationMechanical tripped on fault indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 2 NC

Test facilityIntegral cable test facilities

CableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1C

DE6

0250

AccessoriesTee-off cable boxGlands and platesInterlocksPlease refer to accessories list.

Order information

Code RatingCN2-T9/16 16 kA, 12 kV, 75 kV BILCN2-T9/21 21 kA, 13.8 kV, 95 kV BIL

schneider-electric.com | 45Ringmaster Catalogue

Page 48: 2017 Catalogue - s; E

Circuit breaker, metering and switches

Non-extensible circuit breaker 200 ACN2-T6

Transformer protection up to 1.5 MVA

Protection & control - CBOvercurrent and earth fault protection using CT operated trip coils with provision for time fuse links.Protection CT’s - 100/50/5 A class XShunt trip coil, 20 V DC-250 V AC

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manual

Standard featuresTransformer earth switch, 16/21 kA 3 sCable earth switch, 16/21 kA 3 sAnti-reflex operating handle

IndicationMechanical tripped on fault indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 2 NC

Test facilityIntegral cable test facilities

CableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1C

DE6

0192

AccessoriesTee-off cable boxGlands and platesInterlocksPlease refer to accessories list.

Order information

Code RatingCN2-T6/16 16 kA, 12 kV, 75 kV BILCN2-T6/21 21 kA, 13.8 kV, 95 kV BIL

schneider-electric.com46 | Ringmaster Catalog

Page 49: 2017 Catalogue - s; E

Circuit breaker, metering and switches

Non-extensible switches 630 ASpecification

SN6-S1 Manual operation

SN6-S2Provision for actuator

EnvironmentIndoor / outdoor b bIP54 b b

RatingsNormal rated current 630 A b b13.8 kV 21 kA 3 seconds 95 kV BIL b bCable earth switch 21 kA 3 seconds b bTransformer earth switch 3.15 kA 3 seconds b b

MechanismIndependent manual b bProvision for actuator 24 V DC bActuator 24 V DC O

IndicationMechanical ON/OFF b bMechanical EARTH/MAIN b bVPIS indication (6.6 - 13.8 kV) O OAuxiliary switch contacts 1NO 2NC bPhase and earth fault detection CT’s for Easergy T300 OProvision for EFPI O O

Test facilityIntegral cable test facility b b

Standard featuresOperating handle b bTransformer earth switch 3.15 kA 3 seconds b b

Cable (see available cable kit accessories)Bottom entry up 300 mm2 1 x 3C b bBottom entry up 630 mm2 3 x 1C b bKey: b Standard feature O Optional feature

schneider-electric.com | 47Ringmaster Catalogue

Page 50: 2017 Catalogue - s; E

schneider-electric.com48 | Ringmaster Catalogue

Circuit breaker, metering and switches

Non-extensible switches 630 AAccessories

SN6-S1 Manual operation

SN6-S2Provision for actuator Kit no.

Cable kitsTee-off cable box v v RMR-F47Gland plate 1 x 3C O O RMR-A48Gland plate 3 x 1C O O RMR-A49Angled gland plates (RMR) O O RMR-A50 Blank aluminium gland plate O O RMR-A52Brass wiping gland 1 x 3C O O RMR-A10Brass wiping gland 3 x 1C O O RMR-A11Tubular gland 1 x 3C O O RMR-A12Tubular gland 3 x 1C O O RMR-A13CES5 gland plate 1 x 3C O O RMR-A132Installation itemsSet of padlocks - 6 no O O RMR-A18/6Anti-vandal fixings, including tool O O RMR-A19

Foundation bolts (not required for transformer mounting) O O RMR-A22

Multicore pilot glands O O RMR-A16Operational itemsOperating handle b b RMR-A23VPIS indication (6.6-13.8 kV) v v RMR-F108Neon lamp test unit (including lamp) O O RMR-A24Neon lamp O O RMR-A81Actuator 24 V DC v RMR-F67Mechanical interlocksKey free, earth on v RMR-F85Key free, unit off v RMR-F86Transformer earth switch, key free, earth on v v RMR-F110

N. B. specify lock symbol at time of ordering (3 digits max) not available with motor mechanisms

Order codes13.8 kV, 21 kA, 95 kVBIL SN6-S1/21 SN6-S2/21Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

Actuator panel types Switches

Page 51: 2017 Catalogue - s; E

schneider-electric.com | 49Ringmaster Catalogue

Circuit breaker, metering and switches

Switch disconnector

Protection & control - CBNon-automatic

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 13.8 kVNormal rated BIL 95 kV

Operating mechanismIndependent manual

Standard featuresTransformer earth switch, 16/21 kA 3 sCable earth switch, 21 kA 3 sAnti-reflex operating handle

IndicationMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicator

Test facilityIntegral cable test facilities

CableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1C

Non-extensible switch 630 ASN6-S1

DE6

0193

AccessoriesTee-off cable boxVPIS indicationGlands and platesInterlocks

Please refer to accessories list.

Order information

Code RatingSN6-S1/21 21 kA, 13.8 kV, 95 kV BIL

Page 52: 2017 Catalogue - s; E

schneider-electric.com50 | Ringmaster RN2d Catalog

Circuit breaker, metering and switches

Switch disconnector

Protection & control - CBNon-automatic

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 13.8 kVNormal rated BIL 95 kV

Operating mechanismIndependent manualProvision for actuator, 24 V DC

Standard featuresTransformer earth switch, 16/21 kA 3 sCable earth switch, 21 kA 3 sAnti-reflex operating handle

IndicationMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorAuxiliary contacts 1NO 2NC Earth selected auxiliary contact 1NO

Test facilityIntegral cable test facilities

CableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1C

Non-extensible switch 630 A SN6-S2

DE6

0194

SN6 Fin

AccessoriesTee-off cable boxActuator, 24 V DCVPIS indicationGlands and platesPlease refer to accessories list.

Order information

Code Rating

SN6-S2/21 21 kA, 13.8 kV, 95 kV BIL

Page 53: 2017 Catalogue - s; E

schneider-electric.com | 51Ringmaster RN2d Catalog

Circuit breaker, metering and switches

MU2d-M1/16 MU2d-M2/16 MU2d-M3/16EnvironmentIndoor / outdoor b b bIP54 b b b

RatingsNormal rated current 200 A b b b12 kV 16 kA 1 second 75 kV BIL b b b

Metering (1)

CT’s -50/25/5 A 0.5s 7.5 VA bCT’s -100/50/5 A 0.5s 10 VA bCT’s -200/100/5 A 0.5s 10 VA bVT’s -11 kV/110 V 0.5 50 VA b b b

Cable (see available cable kit accessories)Bottom entry up 300 mm2 1 x 3C O O O

Bottom entry up 630 mm2 3 x 1C O O O

Key: b Standard feature O Optional feature(1) CT’s - 2 phases (L1 & L3), VT’s phase to phase. 6.6 kV VT’s are available - Contact Schneider Electric

Non-extensible metering unit 200 ASpecification

Page 54: 2017 Catalogue - s; E

schneider-electric.com52 | Ringmaster RN2d Catalog

Circuit breaker, metering and switches

MU2d-M1/16 MU2d-M2/16 MU2d-M3/16 Kit no.Cable kitsTee-off cable box v v v RMR-F47Gland plate 1 x 3C O O O RMR-A48Gland plate 3 x 1C O O O RMR-A49Angled gland plates (RMU) O O O RMR-A51Blank aluminium gland plate O O O RMR-A52Brass wiping gland 1 x 3C O O O RMR-A10Brass wiping gland 3 x 1C O O O RMR-A11Tubular gland 1 x 3C O O O RMR-A12Tubular gland 3 x 1C O O O RMR-A13CES5 gland plate 1 x 3C O O O RMR-A132Installation itemsSet of padlocks - XX no O O O RMR-A18/6Foundation bolts (not required for transformer mounting) O O O RMR-A22Multicore pilot glands O O O RMR-A16RMU - MU2d installation kit O O O RMD-A350*Freestanding installation kit O O O RMR-A90Order codes12 kV, 16 kA, 75 kV BIL MU2d-M1/16 MU2d-M2/16 MU2d-M3/16Key: v Factory fitted accessory O Loose accessory, assembled on site

* please consult Schneider Electric

Non-extensible metering unit 200 AAccessories

Page 55: 2017 Catalogue - s; E

schneider-electric.com | 53Ringmaster RN2d Catalog

Circuit breaker, metering and switches

Non-extensible metering unit 200 AMU2d-M1/16

Non-extensible metering unit

Protection & control - CBN/A

Metering transformers• Metering CT’s L1 & L3 phases

- 50/25/5 A - 7.5 VA class 0.5s

• Metering VT ph - ph - 11 kV/110 V 50 VA - class 0.5

EnvironmentIndoor/outdoorIP54

RatingsShort time withstand 16 kA 1 sNormal current rating 200 ANormal rated voltage 12 kVNormal rated BIL 75 kV

Standard featuresDirect coupling between RMU and transformer (optional freestanding cable connection)

Cable connectionBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1C

DE6

0210

AccessoriesCable boxGlands and platesInstallation kitsPlease refer to accessories list.

Order information

Code RatingMU2d-M1/16 16 kA, 12 kV, 75 kV BIL

Page 56: 2017 Catalogue - s; E

schneider-electric.com54 | Ringmaster Catalogue

Circuit breaker, metering and switches

Non-extensible metering unit 200 AMU2d-M2/16

Non-extensible metering unit

Protection & control - CBN/A

Metering transformers• Metering CT’s L1 & L3 phases

- 100/50/5 A - 10 VA class 0.5s

• Metering VT ph - ph - 11 kV/110 V 50 VA - class 0.5

EnvironmentIndoor/outdoorIP54

RatingsShort time withstand 16 kA 1 sNormal current rating 200 ANormal rated voltage 12 kVNormal rated BIL 75 kV

Standard featuresDirect coupling between RMU and transformer (optional freestanding cable connection)

Cable connectionBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessories Cable boxGlands and platesInstallation kitsPlease refer to accessories list.

DE6

0210

Order information

Code RatingMU2d-M2/16 16 kA, 12 kV, 75 kV BIL

Page 57: 2017 Catalogue - s; E

schneider-electric.com | 55Ringmaster Catalogue

Circuit breaker, metering and switches

Non-extensible metering unit 200 AMU2d-M3/16

Non-extensible metering unit

Protection & control - CBN/A

Metering transformers• Metering CT’s L1 & L3 phases

- 200/100/5 A - 10 VA class 0.5s

• Metering VT ph - ph - 11 kV/110 V 50 VA - class 0.5

EnvironmentIndoor/outdoorIP54

RatingsShort time withstand 16 kA 1 sNormal current rating 200 ANormal rated voltage 12 kVNormal rated BIL 75 kV

Standard featuresDirect coupling between RMU and transformer(optional freestanding cable connection)

Cable connectionBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1C

DE6

0210

AccessoriesCable boxGlands and platesInstallation kitsPlease refer to accessories list.

Order information

Code RatingMU2d-M3/16 16 kA, 12 kV, 75 kV BIL

Page 58: 2017 Catalogue - s; E

schneider-electric.com56 | Ringmaster Catalogue

Circuit breaker, metering and switches

Non-extensible metering units 630 ASpecification

MU6d-N1 MU6d-N2 M6A-N3 MU6d-N5EnvironmentIndoor / outdoor b b b bIP54 b b b b

RatingsNormal rated current 630 A b b b b12 kV 16 kA 1 second 75 kV BIL b b b b

Metering (1)

CT’s - 400/600/5 A 10 VA bCT’s - 600/5 A 10 VA bCT’s - 400/5 A 10 VA bCT’s - 600/300/5 A 10 VA bVT’s - 11 kV/110 V 0.5 50 VA b b bVT’s - 11 kV/6.6 kV/110 V 0.5 50 VA b

Cable (see available cable kit accessories)Bottom entry up 300 mm2 1 x 3C O O O OBottom entry up 630 mm2 3 x 1C O O O OKey: b Standard feature O Optional feature(1) CT’s - 2 phases (L1 & L3), VT’s phase to phase 6.6 kV VT’s are available - Contact Schneider Electric

Page 59: 2017 Catalogue - s; E

schneider-electric.com | 57Ringmaster Catalogue

Circuit breaker, metering and switches

Non-extensible metering units 630 AAccessories

MU6d-N1 MU6d-N2 MU6d-N3 MU6d-N5 Kit no.Cable kitsTee-off cable box v v v v RMR-F47Gland plate 1 x 3C O O O O RMR-A48Gland plate 3 x 1C O O O O RMR-A49Angled gland plates (RMU) O O O O RMR-A51 Blank aluminium gland plate O O O O RMR-A52Brass wiping gland 1 x 3C O O O O RMR-A10Brass wiping gland 3 x 1C O O O O RMR-A11Tubular gland 1 x 3C O O O O RMR-A12Tubular gland 3 x 1C O O O O RMR-A13CES5 gland plate 1 x 3C O O O O RMR-A132Installation itemsSet of padlocks - XX no O O O O RMR-A18/6Foundation bolts (not required for transformer mounting) O O O O RMR-A22Multicore pilot glands O O O O RMR-A16RMU - MU6d installation kit O O O O RMD-A350*Freestanding installation kit O O O O RMR-A90Order codes12 kV, 16 kA, 75 kVBIL MU6d-N1 MU6d-N2 MU6d-N3 MU6d-N5Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

* please consult Schneider Electric

Page 60: 2017 Catalogue - s; E

schneider-electric.com58 | Ringmaster Catalogue

Circuit breaker, metering and switches

Non-extensible metering units 630 AMU6d-N**

Non-extensible metering unit

Protection & control - CBN/A

Metering transformers• Metering CT’s L1 & L3 phases (16 kA, 12 kV, 75 kV BIL)

10 VA class 0.5s N1/16 N2/16 N3/16 N5/16400/200/5 A b600/5 A b400/5 A b600/300/5 A b

• Metering VT ph - ph (16 kA, 12 kV, 75 kV BIL)50 VA class 0.5 N1/16 N2/16 N3/16 N5/1611 kV/110 V b b b11 kV/6.6 kV/110 V b

EnvironmentIndoor/outdoorIP54

RatingsShort time withstand 16 kA 1 sNormal current rating 630 ANormal rated voltage 12 kVNormal rated BIL 75 kV

Standard featuresDirect coupling between RMU and transformer(optional freestanding cable connection)

Cable connectionBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1C

DE6

0210

AccessoriesCable boxGlands and platesInstallation kitsPlease refer to accessories list.

Order information

Code RatingMU6d-N** 16 kA, 12 kV, 75 kV BIL

Page 61: 2017 Catalogue - s; E

schneider-electric.com | 59Ringmaster Catalogue

Circuit breaker, metering and switches

Extensible circuit breakers 200 ASpecification

(*) See complete titles footer CE2- T30

CE2- T3

CE2- T7

CE2- T32

CE2- T31

CE2- T35

CE2- T36

CE2- T33

CE2- T34

CE2- T37

CE2- T38

CE2- T39

EnvironmentIndoor / outdoor b b b b b b b b b b b bIP54 b b b b b b b b b b b bRatingsBusbars 630 A b b b b b b b b b b b bCircuit breaker normal rated current 200 A b b b b b b b b b b b b12 kV 16 kA 3 seconds 75 kV BIL b b b b b b b b b b b b13.8 kV 21 kA 3 seconds 95 kV BIL O O O O O O O O O O O OCable earth switch 16 kA 3 seconds b b b b b b b b b b b bCable earth switch 21 kA 3 seconds O O O O O O O O O O O OMechanismIndependent manual b b b b b b b b b b b bProvision for actuator 24 V DC b b b bActuator 24 V DC O O O OOperating handle b b b b b b b b b b b bProtection systemCT’s dual ratio - 500/200/1 A class x b bOvercurrent relay - VIP 40 bCT’s dual ratio - 100/50/5 A class X bCT’s dual ratio 200/100/1 A 5P20CT ratio - 200/1 A class X b b b b b b b b bOvercurrent & earth fault CT operated trip coils bOvercurrent & earth fault relay VIP 45 bTime fuse link OIDMT overcurrent & earth fault relay - VIP 400 b b b b b b b b b20 V-250 shunt trip coil b b b b b b b b b b b bAuxiliary switch 1NO 2NC b b b b b b b b b b b bMeteringCT’s -200/100/5 A 0.5s 10 VA b b b b b b bVT’s -13.8 kV/110 V 0.5 10 VA 13.8/110 V/110 V 0.5 50 VA 3P 20 VA b b

VT’s -11 kV/110 V 0.5 50 VA b b bVT’s -6.6 kV/110 V 0.5 50 VA b bVT’s phase - phase, CT’s L1 & L3 b b b bVT’s phase - earth, CT’s L1, L2 & L3 b b bIndicationMechanical ON/OFF b b b b b b b b b b b bMechanical EARTH/MAIN b b b b b b b b b b b bCable VPIS indication (6.6 - 13.8 kV) O O O O O O O O O O O OAuxiliary switch contacts 1NO 2NC b b b b b b b b b b b bEarth selected auxiliary contacts 1NO b b b bTest facilityIntegral cable test facility b b b b b b b b b b b bCable Bottom entry up to 300 mm2 1 x 3C b b b b b b b b b b b bBottom entry up to 630 mm2 3 x 1C b b b b b b b b b b b bTop entry cables O O O O O O O O O O O OKey: b Standard feature O Optional feature(*) Complete titles:CE2-T30-VIP400 --> CE2-T30/400CE2-T33/40

Page 62: 2017 Catalogue - s; E

schneider-electric.com60 | Ringmaster Catalogue

Circuit breaker, metering and switches

Extensible circuit breakers 200 AAccessories

(*) See complete titles footer

CE2- T30

CE2- T40

CE2- T7

CE2- T32

CE2- T31

CE2- T35

CE2- T36

CE2- T33

CE2- T34

CE2- T37

CE2- T38

CE2- T39 Kit no.

Cable kitsGland plate 1 x 3C O O O O O O O O O O O O RMR-A48Gland plate 3 x 1C O O O O O O O O O O O O RMR-A49Angled gland plates (RMR) O O O O O O O O O O O O RMR-A50Blank aluminium gland plate O O O O O O O O O O O O RMR-A52Brass wiping gland 1 x 3C O O O O O O O O O O O O RMR-A10Brass wiping gland 3 x 1C O O O O O O O O O O O O RMR-A11Tubular gland 1 x 3C O O O O O O O O O O O O RMR-A12Tubular gland 3 x 1C O O O O O O O O O O O O RMR-A13CES5 gland plate 1 x 3C O O O O O O O O O O O O RMR-A132Top entry cables standard panels v v v v v RMR-F93Top entry cables MU6 only v v v v v v v RMR-F94Installation items3 phase busbars 630 A O O O O O RMR-A143 phase busbars 630 A O O O O O O O RMR-A78Busbar end kit O O O O O O O O O O O O RMR-A15Set of padlocks - 6 no O O O O O O O O O O O O RMR-A18/6Foundation bolts (not required for transformer mounting) b b b b b b b b b b b b RMR-A22

Multicore pilot glands O O O O O O O O O O O O RMR-A16Time Fuse Link O RMR-A17Operational itemsOperating handle b b b b b b b b b b b b RMR-A23Cable VPIS indication (6.6 - 13.8 kV) v v v v v v v v v v v v RMR-F108

Neon lamp test unit (including lamp) v v v v v v v v v v v v RMR-A24

Neon lamp O O O O O O O O O O O RMR-A81Actuator 24 V DC v v v RMR-F67Polarity conversion kit (1) v v v RMR-F391Mechanical interlocksKey free, EARTH ON v v v v v v RMR-F85Key free, MAIN OFF v v v v v v RMR-F86

N. B. specify lock symbol at time of ordering (3 digits max) not available with motor mechanisms

Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site (1) Only required when unit is used with RE2d ring main units and automation.

(*) Complete titles:CE2-T30-VIP400 --> CE2-T30/400CE2-T33/40

Page 63: 2017 Catalogue - s; E

schneider-electric.com | 61Ringmaster Catalogue

Circuit breaker, metering and switches

Extensible circuit breakers 200 AAccessories

(*) See complete titles footer

CE2- T30

CE2- T40

CE2- T7

CE2- T32

CE2- T31

CE2- T35

CE2- T36

CE2- T33

CE2- T34

CE2- T37

CE2- T38

CE2- T39 Kit no.

Earth fault passage indication (choose provision kit and an EFPI required if not using Easergy T300)EFPI provision kit, inside cable box O O O O O O O O O O O O RMR-F30

Bowden STD EFPI type NB O O O O O O O O O O O O RMR-A277

Bowden LV reset EFPI type NB1 O O O O O O O O O O O O RMR-A278

Bowden LV reset & alarm type NB2 O O O O O O O O O O O O RMR-A279

Bowden “RR” EFPI and CT O O O O O O O O O O O O RMR-A56

Fundamentals ER “FIND” EFPI and CT O O O O O O O O O O O O RMR-A57

Ancillary itemsTool box O O O O O O O O O O O O RMR-A80Order code12 kV, 16 kA, 75 kV BIL CE2-

T30/16CE2- T3/16

CE2- T7/16

CE2- T32/16

CE2- T31/16

CE2- T35/16

CE2- T36/16

CE2- T33/16

CE2- T34/16 N/A CE2-

T38/16 N/A

13.8 kV, 21 kA, 95 kV BIL CE2- T30/21

CE2- T3/21

CE2- T7/21

CE2- T32/21

CE2- T31/21

CE2- T35/21

CE2- T36/21

CE2- T33/21

CE2- T34/21

CE2- T37/21 N/A CE2-

T39/21Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

(*) Complete titles:CE2-T30-VIP400 --> CE2-T30/400CE2-T33/40

Page 64: 2017 Catalogue - s; E

schneider-electric.com62 | Ringmaster Catalogue

Circuit breaker, metering and switches

Extensible circuit breaker 200 ACE2-T30

Feeder protection up to 3.5 MVA at 11 kV

Protection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 400. In accordance with IEC 60255 and BS142.Protection CT’s - 200/1 A class XShunt trip coil, 20 V DC-250 V AC• Setting range:

- Overcurrent: 20-200 A - Earth fault: 2-160 A

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manual

Standard featuresCable earth switch, 16/21 kA 3 sAnti-reflex operating handle

IndicationMechanical tripped on fault flag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2NCGas pressure indicator

Test facilityIntegral cable test facilities

CableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1C

DE6

0251

AccessoriesVPIS indicationGlands and platesInterlocksOperating handleBusbar kitTop entry cablesPlease refer to accessories list.

Order information

Code RatingCE2-T30/16 16 kA, 12 kV, 75 kV BILCE2-T30/21 21 kA, 13.8 kV, 95 kV BIL

Page 65: 2017 Catalogue - s; E

schneider-electric.com | 63Ringmaster Catalogue

Circuit breaker, metering and switches

Extensible circuit breaker 200 ACE2-T7

Transformer protection up to 1.5 MVA at 11 kV

Protection & control - CBOvercurrent and earth fault protection using CT operated trip coils with provision for time fuse links.Protection CT’s - 100/50/5 A class XShunt trip coil, 20 V DC-250 V AC

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manual

Standard featuresCable earth switch, 16/21 kA 3 sAnti-reflex operating handle

IndicationMechanical tripped on fault flag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2NCGas pressure indicator

Test facilityIntegral cable test facility

CableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1C

DE6

0196

AccessoriesVPIS indicationGlands and platesInterlocksOperating handleBusbar kitTop entry cables

Please refer to accessories list.

Order information

Code RatingCE2-T7/16 16 kA, 12 kV, 75 kV BILCE2-T7/21 21 kA, 13.8 kV, 95 kV BIL

Page 66: 2017 Catalogue - s; E

schneider-electric.com64 | Ringmaster Catalogue

Circuit breaker, metering and switches

Extensible circuit breaker 200 ACE2-T*

Feeder protection up to 3.5 MVA at 11 kV

Protection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 400. In accordance with IEC 60255 and BS142.Protection CT’s - 200/1 A class XShunt trip coil, 20 V DC-250 V AC• Setting range:

- Overcurrent: 20-200 A - Earth fault: 2-160 A

Metering transformers• Metering CT’s L1 & L3 phases

- 200/100/5 A - 10 VA class 0.5s

• Metering VT - see below

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manualAnti-reflex operating handle

Standard featuresCable earth switch, 16/21 kA 3 s

IndicationMechanical tripped on fault flag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2NCGas pressure indicator

Test facilityIntegral cable test facility

CableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1C

DE6

0252

(Select VT rating and switchgear rating from table below).

Accessories VPIS indicationGlands and platesInterlocksOperating handleBusbar kitTop entry cablesPlease refer to accessories list.

Order information

16 kA, 12 kV, 75 kV BIL

CE2- T40/16

CE2- T32/16 N/A CE2-

T38/16

21 kA, 13.8 kV, 95 kV BIL

CE2- T40/21

CE2- T32/21

CE2- T37/21 N/A

Metering VT information:Phase to phase

b b

Phase to earth b b6.6 kV/110 V b11 kV/110 V (1) b b13.8 kV/110 V b(1) Please consult Schneider Electric when ordering units with 95 kV BIL voltage Tel: +44 (0)113 290 3500

Page 67: 2017 Catalogue - s; E

schneider-electric.com | 65Ringmaster Catalogue

Circuit breaker, metering and switches

Extensible circuit breaker 200 ACE2-T31

Feeder protection up to 3.5 MVA at 11 kV

Protection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 400. In accordance with IEC 60255 and BS142. Protection CT’s - 200/1 A class XShunt trip coil, 20 V DC-250 V AC• Setting range:

- Overcurrent: 20-200 A - Earth fault: 2-160 A

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manualProvision for actuator, 24 V DC

Standard featuresCable earth switch, 16/21 kA 3 sAnti-reflex operating handle

IndicationMechanical tripped on fault flag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2 NCEarth selected auxiliary contact1NOGas pressure indicator

Test facilityIntegral cable test facility

CableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1C

DE6

0253

AccessoriesActuator, 24 V DCVPIS indicationGlands and platesInterlocksOperating handleBusbar kitTop entry cables

Please refer to accessories list.

Order information

Code RatingCE2-T31/16 16 kA, 12 kV, 75 kV BILCE2-T31/21 21 kA, 13.8 kV, 95 kV BIL

Page 68: 2017 Catalogue - s; E

schneider-electric.com66 | Ringmaster Catalogue

Circuit breaker, metering and switches

Extensible circuit breaker 200 ACE2-T**

Feeder protection up to 3.5 MVA at 11 kV

Protection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 400. In accordance with IEC 60255 and BS142.Protection CT’s - 200/1 A class XShunt trip coil, 20 V DC-250 V AC• Setting range:

- Overcurrent: 20-200 A - Earth fault: 2-160 A

Metering transformers• Metering CT’s

- 200/100/5 A - 10 VA class 0.5s

• Metering VT - see below

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manualProvision for actuator, 24 V DC

Standard featuresCable earth switch, 16/21 kA 3 sAnti-reflex operating handle

IndicationMechanical tripped on fault indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2NCEarth selected auxiliary contact1NOGas pressure indicator

Test facilityIntegral cable test facility

CableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1C

DE6

0254

(Select VT rating and switchgear rating from table below).

AccessoriesActuator, 24 V DCVPIS indicationGlands and platesInterlocksOperating handleBusbar kitTop entry cablesPlease refer to accessories list.

Order information

16 kA, 12 kV, 75 kV BIL CE2-T36/16 N/A

21 kA, 13.8 kV, 95 kV BIL CE2-T36/21 CE2-T39/21

Metering VT information:Phase to phase b

Phase to earth b6.6 kV/110 V b11 kV/110 V (1)

13.8 kV/110 V bGeneral arrangement drawing

RMINST-02 Page 96

RMINST-02 Page 96

Schematic diagram RMSCH-20 Page 124

RMSCH-36 Page 130

(1) Please consult Schneider Electric when ordering units with 95 kV BIL voltage Tel: +44 (0)113 290 3500

Page 69: 2017 Catalogue - s; E

schneider-electric.com | 67Ringmaster Catalogue

Circuit breaker, metering and switches

Extensible circuit breaker 200 ACE2-T35

DE6

0254

AccessoriesVPIS indicationGlands and platesInterlocksOperating handleBusbar kitTop entry cablesPlease refer to accessories list.

Order information

Code RatingCE2-T35/16 16 kA, 12 kV, 75 kV BILCE2-T35/21 21 kA, 13.8 kV, 95 kV BIL

Feeder protection up to 3.5 MVA at 11 kV

Protection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with IEC 60255 and BS142.Protection CT’s - 200/1 A class XShunt trip coil, 20 V DC-250 V AC• Setting range:

- Overcurrent: 20-200 A - Earth fault: 2-160 A

Metering transformers• Metering CT’s

- 200/100/5 A - 10 VA class 0.5s

• Metering VT ph - ph - 11 kV/110 V 50 VA - class 0.5

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manualActuator, 24 V DC

Standard featuresCable earth switch, 16/21 kA 3 sAnti-reflex operating handle

IndicationMechanical tripped on fault indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2NCEarth selected auxiliary contact1NOGas pressure indicator

Test facilityIntegral cable test facility

CableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1C

Page 70: 2017 Catalogue - s; E

schneider-electric.com68 | Ringmaster Catalogue

Circuit breaker, metering and switches

Extensible circuit breaker 200 ACE2-T33

Feeder protection up to 2.5 MVA at 11 kV

Protection & control - CBSelf powered overcurrent relay, VIP 40.Protection CT’s - 500/200/1 A class X• Setting range: 500/1 A

- Overcurrent: 20-200 A• Setting range: 200/1 A

- Overcurrent: 8-80 A

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manual

Standard featuresCable earth switch, 16/21 kA 3 sAnti-reflex operating handle

IndicationMechanical tripped on fault flag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2NCGas pressure indicator

Test facilityIntegral cable test facilities

CableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1C

DE6

0251

AccessoriesVPIS indicationGlands and platesInterlocksOperating handleBusbar kitTop entry cablesPlease refer to accessories list.

Order information

Code RatingCE2-T33/16 16 kA, 12 kV, 75 kV BILCE2-T33/21 21 kA, 13.8 kV, 95 kV BIL

Page 71: 2017 Catalogue - s; E

schneider-electric.com | 69Ringmaster Catalogue

Circuit breaker, metering and switches

Extensible circuit breaker 200 ACE2-T34

Feeder protection up to 2.5 MVA at 11 kV

Protection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 45. Protection CT’s - 500/200/1 A class XCH30 core balance CT• Setting range: 500/1 A

- Overcurrent: 20-200 A - Earth fault: 25-300 A

• Setting range: 200/1 A - Overcurrent: 8-80 A - Earth fault: 10-120 A

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manual

Standard featuresCable earth switch, 16/21 kA 3 sAnti-reflex operating handle

IndicationMechanical tripped on fault flag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2NCGas pressure indicator

Test facilityIntegral cable test facilities

CableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1C

DE6

0255

AccessoriesVPIS indicationGlands and platesInterlocksOperating handleBusbar kitTop entry cablesPlease refer to accessories list.

Order information

Code RatingCE2-T34/16 16 kA, 12 kV, 75 kV BILCE2-T34/21 21 kA, 13.8 kV, 95 kV BIL

Page 72: 2017 Catalogue - s; E

Circuit breaker, metering and switches

(*) See complete titles footer CE6- T30

CE6- T33

CE6- T39

CE6- T31

CE6- T34

CE6- T35

CE6- T36

CE6- T38

CE6- T37

EnvironmentIndoor / outdoor b b b b b b b b bIP54 b b b b b b b b bRatingsBusbars 630 A b b b b b b b b bCircuit breaker normal rated current 630 A b b b b b b b b b12 kV 16 kA 3 seconds 75 kV BIL b b b b b b b b b13.8 kV 21 kA 3 seconds 95 kV BIL O O O O O O O O OCable earth switch 16 kA 3 seconds b b b b b b b b bCable earth switch 21 kA 3 seconds O O O O O O O O OMechanismIndependent manual b b b b b b b b bProvision for actuator 24 V DC b b b bActuator 24 V DC O O O OOperating handle b b b b b b b b bProtection systemCT ratio - 800/1 A class X b b b b b b b b bCT dual ratio 800/400/1 A 5P20IDMT overcurrent & earth fault relay - VIP 400 b b b b b b b b b20 V-250 V shunt trip coil b b b b b b b b bAuxiliary switch 1NO 2NC b b b b b b b b bMeteringCT’s - 400/200/5 A 0.5s 10 VA b b b b b b bVT’s - 13.8 kV/110 V/110 V/ 0.5 50 VA 3P 20 VA b bVT’s - 11 V/110 V 0.5 50 VA b b bVT’s - 6.6 kV/110 V 0.5 50 VA b bVT’s - phase - phase, CT’s L1 & L3 b b b bVT’s phase - earth, CT’s L1, L2 & L3 b b bIndicationMechanical ON/OFF b b b b b b b b bMechanical EARTH/MAIN b b b b b b b b bCable VPIS indication (6.6 - 13.8 kV) O O O O O O O O OAuxiliary switch contacts 1NO 2NC b b b b b b b b bIndication CT 600/5 A 5 VA CLS 1 L2 ph b b b b b b b b bAmmeter 0-600 A b b b b b b b b bEarth selected auxiliary contacts 1NO b b bGas pressure indicator b b b b b b b b bTest facilityIntegral cable test facility b b b b b b b b bCable Bottom entry up to 300 mm2 1 x 3C b b b b b b b b bBottom entry up to 630 mm2 3 x 1C b b b b b b b b bTop entry cables O O O O O O O O OKey: b Standard feature O Optional feature(*) Complete titles:CE6-T30-VIP400 --> CE6-T30/400

Extensible circuit breakers 630 ASpecification

schneider-electric.com70 | Ringmaster Catalogue

Page 73: 2017 Catalogue - s; E

Circuit breaker, metering and switches

(*) See complete titles footer CE6- T30

CE6- T33

CE6- T39

CE6- T31

CE6- T34

CE6- T35

CE6- T36

CE6- T38

CE6- T37

Kit no.

Cable kitsGland plate 1 x 3C O O O O O O O O O RMR-A48Gland plate 3 x 1C O O O O O O O O O RMR-A49Angled gland plates (RMR) O O O O O O O O O RMR-A50Blank aluminium gland plate O O O O O O O O O RMR-A52Brass wiping gland 1 x 3C O O O O O O O O O RMR-A10Brass wiping gland 3 x 1C O O O O O O O O O RMR-A11Tubular gland 1 x 3C O O O O O O O O O RMR-A12Tubular gland 3 x 1C O O O O O O O O O RMR-A13CES5 gland plate 1 x 3C O O O O O O O O O RMR-A132Top entry cables standard panels v v RMR-F93Top entry cables MU6 only v v v v v v v RMR-F94Installation items3 phase busbars 630 A O O RMR-A143 phase busbars 630 A O O O O O O O RMR-A78Busbar end kit O O O O O O O O O RMR-A15Set of padlocks - 6 no O O O O O O O O O RMR-A18/6Foundation bolts (not required for transformer mounting)

b b b b b b b b b RMR-A22

Multicore pilot glands O O O O O O O O O RMR-A16Operational itemsOperating handle b b b b b b b b b RMR-A23Cable VPIS indication (6.6 - 13.8 kV) v v v v v v v v v RMR-A108Neon lamp test unit (including lamp) O O O O O O O O O RMR-A24Neon lamp O O O O O O O O O RMR-A81Actuator 24 V DC v v v v RMR-F67Polarity conversion kit (1) v v v v RMR-F391Mechanical interlocksKey free, EARTH ON v v v v v RMR-F85Key free, MAIN OFF v v v v v RMR-F86N. B. specify lock symbol at time of ordering ( 3 digits max) not available with motor mechanisms

Earth fault passage indication (choose provision kit and an EFPI required if not using Easergy T200E)EFPI provision kit, inside cable box O O O O O O O O O RMR-F30Bowden STD EFPI type NB O O O O O O O O O RMR-A277Bowden LV reset EFPI type NB1 O O O O O O O O O RMR-A278Bowden LV reset & alarm type NB2 O O O O O O O O O RMR-A279Bowden “RR” EFPI and CT O O O O O O O O O RMR-A56Fundamentals ER “FIND” EFPI and CT O O O O O O O O O RMR-A57Ancillary itemsTool box O O O O O O O O O RMR-A80Order code12 kV, 16 kA, 75 kV BIL CE6-

T4/16CE6- T5/16

CE6- T6/16

CE6- T8/16

CE6- T9/16

CE6-T10/16

N/A N/A CE6-T24/16

13.8 kV, 21 kA, 95 kV BIL CE6- T4/21

CE6- T5/21

CE6- T6/21

CE6- T8/21

CE6- T9/21

CE6-T10/21

CE6-T22/21

CE6-T23/21

N/A

Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site (1) Only required when unit is used with RE2d ring main units and automation.(*) Complete titles:CE6-T30-VIP400 --> CE6-T30/400

Extensible circuit breakers 630 ASpecification

schneider-electric.com | 71Ringmaster Catalogue

Page 74: 2017 Catalogue - s; E

Circuit breaker, metering and switches

Feeder protection up to 12 MVA at 11 kV

Protection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 400. In accordance with IEC 60255 and BS142.Protection CT’s - 800/1 A class XShunt trip coil, 20 V DC-250 V AC• Setting range:

- Overcurrent: 80-800 A - Earth fault: 8-640 A

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manual

Standard featuresCable earth switch, 16/21 kA 3 sAnti-reflex operating handle

IndicationMechanical tripped on fault flag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2 NCAmmeter 0-600 AIndication CT L2 ph - 600/5 A class 1.0, 5 VAGas pressure indicator

Test facilityIntegral cable test facility

CableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1C

Extensible circuit breaker 630 ACE6-T30

DE6

0256

AccessoriesVPIS indicationGlands and platesInterlocksBusbar kitTop entry cables

Please refer to accessories list.

Order information

Code RatingCE6-T30/16 16 kA, 12 kV, 75 kV BILCE6-T30/21 21 kA, 13.8 kV, 95 kV BIL

schneider-electric.com72 | Ringmaster Catalogue

Page 75: 2017 Catalogue - s; E

Circuit breaker, metering and switches

Extensible circuit breaker 630 ACE6-T*

Feeder protection up to 12 MVA at 11 kV

Protection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 400. In accordance with IEC 60255 and BS142.Protection CT’s - 800/1 A class XShunt trip coil, 20 V DC-250 V AC• Setting range:

- Overcurrent: 80-800 A - Earth fault: 8-640 A

Metering transformers• Metering CT’s

- 400/200/5 A - 10 VA class 0.5s

• Metering VT - see below

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manual

Standard featuresCable earth switch, 16/21 kA 3 sAnti-reflex operating handle

IndicationMechanical tripped on fault flag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2 NCAmmeter 0-600 AIndication CT L2 ph - 600/5 A class 1.0, 5 VAGas pressure indicator

Test facilityIntegral cable test facility

CableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1C

DE6

0197

(Select VT rating and switchgear rating from table below).

AccessoriesActuator, 24 V DCVPIS indicationGlands and platesInterlocksBusbar kitTop entry cablesPlease refer to accessories list.

Order information

16 kA, 12 kV, 75 kV BIL

CE6- T 33/16

CE6- T39/16 N/A CE6-

T37/16

21 kA, 13.8 kV, 95 kV BIL

CE6- T33/21

CE6- T39/21

CE6- T36/21 N/A

Metering VT information:Phase to phase

b b

Phase to earth b b6.6 kV/110 V b11 kV/110 V (1) b b13.8 kV/110 V b(1) Please consult Schneider Electric when ordering units with 95 kV BIL voltage Tel: +44 (0)113 290 3500

schneider-electric.com | 73Ringmaster Catalogue

Page 76: 2017 Catalogue - s; E

Circuit breaker, metering and switches

Extensible circuit breaker 630 ACE6-T31

Feeder protection up to 12 MVA at 11 kV

Protection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 400. In accordance with IEC 60255 and BS142.Protection CT’s - 800/1 A class XShunt trip coil, 20 V DC-250 V AC• Setting range:

- Overcurrent: 80-800 A - Earth fault: 8-640 A

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manualProvision for actuator, 24 V DC

Standard featuresCable earth switch, 16/21 kA 3 sAnti-reflex operating handle

IndicationMechanical tripped on fault flag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2 NCEarth selected auxiliary contact1NOAmmeter 0-600 AIndication CT L2 ph - 600/5 A class 1.0, 5 VAGas pressure indicator

Test facilityIntegral cable test facility

CableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1C

DE6

0257

AccessoriesActuator, 24 V DCVPIS indicationGlands and platesInterlocksBusbar kitTop entry cables

Please refer to accessories list.

Order information

Code RatingCE6-T31/16 16 kA, 12 kV, 75 kV BILCE6-T31/21 21 kA, 13.8 kV, 95 kV BIL

Page 77: 2017 Catalogue - s; E

Circuit breaker, metering and switches

Extensible circuit breaker 630 ACE6-T**

Feeder protection up to 12 MVA at 11 kV

Protection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 400. In accordance with IEC 60255 and BS142.Protection CT’s - 800/1 A class XShunt trip coil, 20 V DC-250 V AC• Setting range:

- Overcurrent: 80-800 A - Earth fault: 8-640 A

Metering transformers• Metering CT’s

- 400/200/5 A - 10 VA class 0.5s

• Metering VT - see below

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manual

Standard featuresCable earth switch, 16/21 kA 3 sAnti-reflex operating handle

IndicationMechanical tripped on fault flag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2 NCEarth selected auxiliary contactsAmmeter 0-600 AIndication CT L2 ph- 600/5 A class 1.0, 5 VAGas pressure indicator

Test facilityIntegral cable test facility

CableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1C

DE6

0199

(Select VT rating and switchgear rating from table below).

AccessoriesVPIS indicationGlands and platesInterlocksBusbar kitTop entry cablesPlease refer to accessories list.

Order information

16 kA, 12 kV, 75 kV BIL

CE6- T34/16

CE6- T35/16

N/A

21 kA, 13.8 kV, 95 kV BIL

CE6- T34/21

CE6- T35/21

CE6- T38/21

Metering VT information:Phase to phase

b b

Phase to earth b6.6 kV/110 V b11 kV/110 V (1) b13.8 kV/110 V b(1) Please consult Schneider Electric when ordering units with 95 kV BIL voltage Tel: +44 (0)113 290 3500

Page 78: 2017 Catalogue - s; E

schneider-electric.com76 | Ringmaster Catalogue

Circuit breaker, metering and switches

Extensible switches 630 ASpecification

SE6-S1Manual operation

SE6-S2Provision for actuator

SE6-E1Busbar earth-switch

manual operationEnvironmentIndoor / outdoor b b bIP54 b b b

RatingsBusbars 630 A b b bSwitch normal rated current 630 A b b b13.8 kV 21 kA 3 seconds 95 kV BIL b b bCable earth switch 21 kA 3 seconds b b

MechanismIndependent manual b b bProvision for actuator 24 V DC bActuator 24 V DC OOperating handle b b b

IndicationMechanical ON/OFF b bMechanical EARTH/MAIN b b bCable VPIS indication (6.6-13.8 kV) v vBusbar VPIS indication (6.6-13.8 kV) v vAuxiliary switch contacts1NO 1 NC vPhase and earth fault detection CT’s for Easergy T300 OEFPI provision only CT inside box O O bGas pressure indicator b b b

Test facilityIntegral cable test facility b b

Integral test facilityRH/LH busbar earthing b

Cable (see available cable kit accessories)Bottom entry up to 300 mm2 1 x 3C b bBottom entry up to 630 mm2 3 x 1C b bTop entry cables O OKey: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

Page 79: 2017 Catalogue - s; E

schneider-electric.com | 77Ringmaster Catalogue

Circuit breaker, metering and switches

Extensible switches 630 AAccessories

SE6-S1Manual

operation

SE6-S2Provision for

actuator

SE6-E1Busbar earth-switch manual

operation

Kit no.

Cable kitsGland plate 1 x 3C O O RMR-A48Gland plate 3 x 1C O O RMR-A49Angled gland plates (RMR) O O RMR-A50Blank aluminium gland plate O O RMR-A52Galvanised steel wiping gland 1 x 3C O O RMR-A10Galvanised steel wiping gland 3 x 1C O O RMR-A11Tubular gland 1 x 3C O O RMR-A12Tubular gland 3 x 1C O O RMR-A13CES5 gland plate 1 x 3C O O RMR-A132Top entry cables v v RMR-F93Installation items3 phase busbars 630 A O O v RMR-A14Set of padlocks - 6 no O O O RMR-A18/6Busbar end kit (1 end kit required per switchboard) O O O RMR-A15Foundation bolts (not required for transformer mounting) b b b RMR-A22

Multicore pilot glands O RMR-A16Operational itemsOperating handle b b b RMR-A23Cable VPIS indication (6.6-13.8 kV) v v RMR-F108Cable and busbar VPIS indication (6.6-13.8 kV) v v RMR-F92Neon lamp test unit (including lamp) O O RMR-A24Neon lamp O O RMR-A81Actuator 24 V DC v RMR-F67Polarity conversion kit (1) v RMR-F391Mechanical interlocksKey free, earth ON v v RMR-F85Key free, main OFF v RMR-F86N. B. specify lock symbol at time of ordering ( 3 digits max) not available with motor mechanismsIndication EFPI provision kit, inside cable box O O RMR-F30Bowden STD EFPI NB O O RMR-A277Bowden LV reset EFPI type NB1 O O RMR-A278Bowden LV reset & alarm type NB2 O O RMR-A279Bowden “RR” EFPI and CT O O RMR-A56Fundamentals ER “FIND” EFPI and CT O O RMR-A57Ancillary itemsTool box O O O RMR-A80Order code13.8 kV, 21 kA, 95 kV BIL, 0.55bG SE6-S1/21 SE6-S2/21 SE6-E1/21Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site (1) Only required when unit is used with RE2d ring main units and automation.

Page 80: 2017 Catalogue - s; E

schneider-electric.com78 | Ringmaster Catalogue

Circuit breaker, metering and switches

Switch disconnector

Protection & control - CBNon-automatic

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 13.8 kVNormal rated BIL 95 kV

Operating mechanismIndependent manual

Standard featuresCable earth switch, 21 kA 3 sAnti-reflex operating handles

IndicationMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicator

Test facilityIntegral cable test facility

CableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1C

Extensible switch 630 A SE6-S1

DE6

0201

AccessoriesVPIS indicationGlands and platesInterlocksBusbar kitTop entry cablesPlease refer to accessories list.

Order information

Code RatingSE6-S1/21 21 kA, 13.8 kV, 95 kVBIL

Page 81: 2017 Catalogue - s; E

schneider-electric.com | 79Ringmaster Catalogue

Circuit breaker, metering and switches

Extensible switch 630 A SE6-S2

Switch disconnector

Protection & control - CBNon-automatic

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 13.8 kVNormal rated BIL 95 kV

Operating mechanismIndependent manualProvision for actuator, 24 V DC

Standard featuresCable earth switch, 21 kA 3 sAnti-reflex operating handle

IndicationMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2NCEarth selected auxiliary contact 1NOGas pressure indicator

Test facilityIntegral cable test facility

CableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1C

DE6

0202

AccessoriesActuator, 24 V DCVPIS indicationGlands and platesInterlocksBusbar kitTop entry cablesPlease refer to accessories list.

Order information

Code RatingSE6-S2/21 21 kA, 13.8 kV, 95 kV BIL

Page 82: 2017 Catalogue - s; E

schneider-electric.com80 | Ringmaster Catalogue

Circuit breaker, metering and switches

Extensible switch 630 A SE6-E1

Busbar earthing switch

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 13.8 kVNormal rated BIL 95 kV

Operating mechanismIndependent manual

Standard featuresCable earth switch, 21 kA 3 sAnti-reflex operating handle

IndicationMechanical earth/main indicatorGas pressure indicator

Test facilityN/A

CableN/A

DE6

0203

AccessoriesInterlocksBusbar kitPlease refer to accessories list.

Order information

Code RatingSE6-E1/21 21 kA, 13.8 kV, 95 kV BIL

Page 83: 2017 Catalogue - s; E

schneider-electric.com | 81Ringmaster Catalogue

Circuit breaker, metering and switches

Extensible bus-section 630 ASpecification

SE6-B1Bus-section manual

CE6-B9Bus-section manual

Metering

CE6-B10Bus-section manual

Metering Provision for actuator

EnvironmentIndoor / outdoor b b bIP54 b b bRatingsBusbars 630 A b b bCircuit breaker normal rated current 630 A b bSwitch normal rated current 630 A b12 kV 16 kA 3 seconds 75 kV BIL b b13.8 kV 21 kA 3 seconds 95 kV BIL b O ORH busbar earth switch 16 kA 3 seconds b bRH busbar earth switch 21 kA 3 seconds b O OMechanismIndependent manual b b bProvision for actuator 24 V DC bActuator 24 V DC OOperating handle b b bProtection systemCT ratio - 800/1 A class X b bIDMT overcurrent & earth fault relay - VIP 400 b b20- 250 V shunt trip coil b bAuxiliary switch1NO 2 NC b bMeteringCT’s - 400/200/5 A 0.5s 10 VA b bVT’s - 11 kA/110 V 0.5 50 VA b bVT’s phase - phase, CT’s L1 & L3 b bIndicationMechanical ON/OFF b b bMechanical EARTH/MAIN b b bEarth selected auxiliary contact1NO bRH busbar VPIS indication O O OAuxiliary switch contacts1NO 2NC b bIndication CT 600/5 A 5 VA CLS 1 L2 phase b bAmmeter 0-600 A b bGas pressure indicator b b bIntegral test facilityRH busbar earthing b b bLH busbar earthing ( using SE6-E1) O O OKey: b Standard feature O Optional feature

Page 84: 2017 Catalogue - s; E

schneider-electric.com82 | Ringmaster Catalogue

Circuit breaker, metering and switches

Extensible bus-section 630 AAccessories

SE6-B1Bus-section

manual

CE6-B9Bus-section

manual Metering

CE6-B10Bus-section

manual Metering

Provision for actuator

Kit no.

Installation items3 phase busbars 630 A RMR-A143 phase busbars 630 A (Joggle metering) v v v RMR-A793 phase busbars 630 A double width (metering) v v v RMR-A78Set of padlocks - XX no O O O RMR-A18/6Busbar end kit (1 end kit required per switchboard) O O O RMR-A15Foundation bolts (not required for transformer mounting) b b b RMR-A22

Multicore pilot glands O O RMR-A16Operational itemsOperating handle b b b RMR-A23LH and RH busbar VPIS indication v v v RMR-F92Neon lamp test unit (including lamp) O O RMR-A24Neon lamp O O O RMR-A81Actuator 24 V DC v RMR-F67Polarity conversion kit (1) v RMR-F391Mechanical interlocksKey free, earth ON v v RMR-F85Key free, main OFF v v RMR-F86N. B. specify lock symbol at time of ordering ( 3 digits max) not available with motor mechanismsAncillary itemsTool box O O O RMR-A80Order code12 kV, 16 kA, 75 kV BIL N/A CE6-B9/16 CE6-B10/1613.8 kV, 21 kA, 95 kV BIL SE6-B1/21 CE6-B9/21 CE6-B10/21General arrangement drawing RMINST-01

Page 95RMINST-01

Page 95RMINST-01

Page 95Schematic drawing N/A RMSCH-21

Page 125RMSCH-22 Page 126

Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site (1) Only required when unit is used with RE2d ring main units and automation.

Page 85: 2017 Catalogue - s; E

schneider-electric.com | 83Ringmaster Catalogue

Circuit breaker, metering and switches

Extensible bus-section 630 A SE6-B1

Bus-section disconnector

Protection & control Non-automatic

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 13.8 kVNormal rated BIL 95 kV

Operating mechanismIndependent manual

Standard featuresRH busbar earth switch, 21 kA 3 sAnti-reflex operating handle

IndicationMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicator

Test facilityIntegral RH busbar test facility

CableN/A

DE6

0204

AccessoriesVPIS indicationInterlocksBusbarsPlease refer to accessories list.

Order information

Code RatingSE6-B1/21 21 kA, 13.8 kV, 95 kV BIL

Page 86: 2017 Catalogue - s; E

schneider-electric.com84 | Ringmaster RN2d Catalog

Circuit breaker, metering and switches

Extensible bus-section 630 A CE6-B9

Bus-section circuit breaker

Protection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 400. In accordance with IEC 60255 and BS142. Protection CT’s - 800/1 A class XShunt trip coil, 20 V DC-250 V AC• Setting range:

- Overcurrent: 80-800 A - Earth fault: 8-640 A

Metering transformers• Metering CT’s

- 400/200/5 A - 10 VA class 0.5s

• Metering VT ph-ph - 11 kV/110 V 50 VA - class 0.5

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manual

Standard featuresRH busbar earth switch, 16/21 kA 3 sAnti-reflex operating handle

IndicationMechanical tripped on fault flag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2 NCAmmeter 0-600 AIndication CT L2 ph- 600/5 A class 1.0 5 VAGas pressure indicator

Test facilityIntegral RH busbar test facility

CableN/A

DE6

0258

AccessoriesVPIS indicationInterlocksBusbarsPlease refer to accessories list.

Order information

Code RatingCE6-B9/16 16 kA, 12 kV, 75 kV BILCE6-B9/21 21 kA, 13.8 kV, 95 kV BIL

Page 87: 2017 Catalogue - s; E

schneider-electric.com | 85Ringmaster RN2d Catalog

Circuit breaker, metering and switches

Extensible bus-section 630 A CE6-B10

Bus-section circuit breaker

Protection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 400. In accordance with IEC 60255 and BS142.Protection CT’s - 800/1 A class XShunt trip coil, 20 V DC-250 V AC• Setting range:

- Overcurrent: 80-800 A - Earth fault: 8-640 A

Metering transformers• Metering CT’s

- 400/200/5 A - 10 VA class 0.5s

• Metering VT ph-ph - 11 kV/110 V 50 VA - class 0.5

EnvironmentIndoor/outdoorIP54

RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 13.8 kVNormal rated BIL 75/95 kV

Operating mechanismIndependent manualProvision for actuator, 24 V DC

Standard featuresRH busbar earth switch, 16/21 kA 3 sAnti-reflex operating handle

IndicationMechanical tripped on fault flag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2 NCEarth selected auxiliary contacts1NOAmmeter 0-600 AIndication CT L2 ph- 600/5 A class 1.0 5 VAGas pressure indicator

Test facilityIntegral RH busbar test facility

CableN/A

DE6

0259

AccessoriesActuator, 24 V DCVPIS indicationInterlocksBusbars

Please refer to accessories list.

Order information

Code RatingCE6-B10/16 16 kA, 12 kV, 75 kV BILCE6-B10/21 21 kA, 13.8 kV, 95 kV BIL

Page 88: 2017 Catalogue - s; E

schneider-electric.com86 | Ringmaster Catalogue

Remote control

Page 89: 2017 Catalogue - s; E

schneider-electric.com | 87Ringmaster Catalogue

Remote control

Telecontrol cabinetEasergy T300 - General description

Easergy T300 - OVR

Easergy T300 - OVR - Datasheet

88

89

89

Page 90: 2017 Catalogue - s; E

schneider-electric.com88 | Ringmaster Catalogue

Remote control Remote controlEasergy T300 telecontrol cabinet (FRTU)

Ready-to-use Panel Solution

• A ready to use panel catalog is available off-the-shelf for fast

delivery and installation.

• The panel catalog is also modular and flexible in order to

offer the just enough solution.

• The web configurator allows you to build your configuration

(hardware and software) in one click.

T300 is offered as a compact Feeder RTU solution standardised in a complete panel build and corresponds to the standard requirements of the MV/LV substation. Therefore, this solution is modular and can be adapted to the requirements of the customer.

All configurations can be extended on site with different Easergy T300 modules. You can consult our Engineering centers to design or customise a dedicated solution. Three types of enclosure are available in standard, depending on the environmental installation:

• Indoor controller panel • Outdoor controller panel, wall mounting or pole mounting• Indoor and outdoor monitoring, wall mounting or pole mounting

Three types of enclosure are offered in standard:

• T300-IV1: Vertical wall mounting cabinet for indoor application • T300-OVR: Vertical wall mounting cabinet for outdoor application• T300-OM1: Indoor and outdoor medium monitor panel

Note :For further details on Easergy T300, please refer: T300 Catalog ref NRJED314621EN

T300

_clo

sed

T300

_ope

n

Information presented in front panel of modules is visible through a window, without opening the door.

All in one panel (“Indoor Vertical version” – T300-IV1)

Page 91: 2017 Catalogue - s; E

schneider-electric.com | 89Ringmaster Catalogue

Remote control Telecontrol cabinetEasergy T300 - OVR

• Mounting:

– Wall mounting - vertically

– The enclosure can be attached to the

Ringmaster using the standard T300 fixing kit

• Protection indice: IP54 - IK09

• Paint color reference: RAL 7012

• Dimensions Basic enclosure:

L380 x H600 x P275 mm

• Weight: 40 kg

• Material: Metallic

T300-OVR Characteristics

T300

_OVR

Modules assembled on a DIN rail including:

1 LV150 module

1 AC 1Ph+N breaker

1 Battery 24 Ah or 38 Ah

Ringmaster specific AMP switch and current transformer connectors

Opened door contact (option)

Antenna surge arrestor (optional accessory)

1 Power Supply PS501 Front Head Unit HU2501 to 4 modules Switch Controller SC150

Connected internally to a digital input and enables remote indication of the door status (open/closed)

Connection

• All cable access is located on the lower part of the enclosure

• An adjustable sliding plate at the lower part of the enclosure facilitates entry to the switch and current cables and also locks the cable glands

• All switch and current cable connections are compatible with the Ringmaster standard

For GSM/3G or radio purpose. Avoid surge and deterioration due to antenna overvoltage.

T300-OVR cabinet Outdoor Vertical version

Order code: (Please contact us)

Page 92: 2017 Catalogue - s; E

schneider-electric.com90 | Ringmaster Catalogue

Remote control

Easergy T300 OVR-2 SW

Easergy T300 OVR-3 SW

Easergy T300-OVR-4 SW

EnvironmentIndoor / outdoor b b bIP54 b b b

CommunicationModbus master b b bIEC 870-5-101 and IEC 870-5-104 b b bDNP3 b b bRS232 modem box b b b2G/3G modem box b b b3G/4G modem box b b b

Standard featuresFreestanding/wall mounted/ switchgear mounted b b bRemovable radio bracket ( no radio supplied) b b b

Inputs to cabinetSwitch open - per switch b b bSwitch closed - per switch b b bEarth selector earth/mains - per switch b b b2 spare per switch b b b

Control output to switchgearTo switch Open switch b b b

Close switch b b bReset external FPI b b b

Output to SCADASwitch open b b bSwitch closed b b bEarth selector earth/mains b b bFault passage indication - phase and/or earth fault b b bFault passage indication – directional phase and/or earth fault

b b b

From cabinet Local/remote failure b b bMains/equipment failure b b bBattery and charger alarms b b b

Telecontrol cabinetEasergy T300 - OVR datasheet

Page 93: 2017 Catalogue - s; E

schneider-electric.com | 91Ringmaster Catalogue

Remote control

Easergy T300 OVR-2 SW

Easergy T300 OVR-3 SW

Easergy T300-OVR-4 SW

Local controlPush button open/close switch b b b

Local/remote selector b b b

Reset/test integral FPI b b b

Automation ON/OFF b b b

Test LEDs b b b

Local indicationHU250 heartbeat status b b b

T300 equipment status b b b

Wi-fi status b b b

Communication status with modules b b b

Automation status ON/OFF b b b

Automation locked status b b b

AC supply ON/OFF b b b

Voltage output for switchgear motorON/OFF b b b

Voltage output for transmissiondevices ON/OFF b b b

Battery fault b b b

Local/Remote Status b b b

Main switch position(open, closed, intermediate) b b b

Earth switch position b b b

Fault detection status with direction b b b

Voltage presence status b b b

Battery and chargerAC voltage input: 90 to 264 Vac - 50/60 Hz single phase b b b

DC voltage input: 110 to 220 Vdc b b b

12 Vdc IEDs – 36W b b b

12 Vdc telecom – 18W b b b

24 Vdc switchgear b b b

10 kV insulation and 20 kV surge b b b

Operating temperature range : -40° C to 70° C b b b

Storage temperature range: -40° C to 70° C b b b

Battery 24 AH Autonomy on 20 degrees C, without sleep mode 3 hours after loss of supply with 10 c/o switch operations

b b b

Key: b Standard feature O Optional feature

Telecontrol cabinetEasergy T300 - OVR datasheet

Page 94: 2017 Catalogue - s; E

schneider-electric.com92 | Ringmaster Catalogue

Installation drawing

Page 95: 2017 Catalogue - s; E

schneider-electric.com | 93Ringmaster Catalogue

Installation drawings

Typical switchboard 94

Extensible units 95

Non-extensible unit 98

Extensible ring main unitc/w tee off cable box

95

Non-extensible ring main unitsfor transformer mounting unit

c/w MU2 metering unit & tee off cable box

100

Non-extensible metering unit 102

Telecontrol cabinet 103

Page 96: 2017 Catalogue - s; E

schneider-electric.com94 | Ringmaster Catalogue

Installation drawings Typical switchboard

799

DE5

9806

Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric Note: for civil engineering and recommendations for internal arc clearances please consult our installation and maintenance instructions or contact Schneider Electric

Page 97: 2017 Catalogue - s; E

schneider-electric.com | 95Ringmaster Catalogue

Installation drawingsD

E598

07

Panel type Page numberSE6-B1 83CE6-B9 84CE6-B10 85Approximate weight: 450 kg

Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric

Note: for civil engineering and recommendations for internal arc clearances please consult our installation and maintenance instructions or contact Schneider Electric.

799

Extensible unitSwitch& Circuit breaker (SE6-B1 ,CE6-B3,CE6-B5)

Page 98: 2017 Catalogue - s; E

schneider-electric.com96 | Ringmaster Catalogue

Installation drawingsD

E598

08

Extensible unitCircuit breaker

799

Panel type Page numberCE2-T40 64CE2-T32 64CE2-T35 67CE2-T36 66CE2-T37 64CE2-T38 64CE2-T39 66CE6-T33 73CE6-T39 73CE6-T34 75CE6-T35 75CE6-T36 73CE6-T38 75CE6-T37 73Approximate weight: 450 kg

Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric

Note: for civil engineering and recommendations for internal arc clearances please consult our installation and maintenance instructions or contact Schneider Electric.

Page 99: 2017 Catalogue - s; E

schneider-electric.com | 97Ringmaster Catalogue

Installation drawings Extensible unitSwitch & circuit breaker

799

DE5

9809

Panel type Page numberCE2-T30 62CE2-T7 63CE2-T31 65CE6-T30 72CE6-T31 74SE6-S1 78SE6-S2 79SE6-E1 80Approximate weight: 250 kg

Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric.Note: for civil engineering and recommendations for internal arc clearances please consult our installation and maintenance instructions or contact Schneider Electric.

Page 100: 2017 Catalogue - s; E

schneider-electric.com98 | Ringmaster Catalogue

Installation drawings Non-extensible unitSwitch &circuit breaker

DE5

9811

Panel type Page numberCN2-T9 45CN2-T6 46SN6-S1 49SN6-S2 50Approximate weight: 250 kg

Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric Tel: +44 (0)113 290 3500

Note: for civil engineering and recommendations for internal arc clearances please consult our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric Tel: +44 (0)113 290 3500

Page 101: 2017 Catalogue - s; E

schneider-electric.com | 99Ringmaster Catalogue

Installation drawings Extensible ring main unitc/w tee off cable box

DE5

9810

Panel type Page numberRE2d-T1 35RE2d-T2 36RE2d-T3 37RE2d-T4 38Approximate weight: 300 kg

Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric.

Note: for civil engineering and recommendations for internal arc clearances please consult our installation and maintenance instructions or contact Schneider Electric.

575

439

RH ring switchcable box

LH ring switchcable box

Concrete plinth(Depth as required)

Extensible Bushing Cover

510

PLINTH

EXTENSIBLE EXTENSIBLE

1510

1955

1209

747

374

1320

878

779

Page 102: 2017 Catalogue - s; E

schneider-electric.com100 | Ringmaster Catalogue

Installation drawings Non-extensible ring main unitfor transformer mounting unit

DE5

9812

DE6

0268

Panel type Page numberRN2d-T1 26RN2d-T2 27RN2d-T3 28RN2d-T4 29RN2d-T5 30RN6d-T1 31Approximate weight: 300 kg

Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric

Note: for civil engineering and recommendations for internal arc clearances please consult our installation and maintenance instructions or contact Schneider Electric.

Page 103: 2017 Catalogue - s; E

schneider-electric.com | 101Ringmaster Catalogue

Installation drawings Non-extensible ring main unitc/w MU2d metering unit & tee off cable box

DE5

9814

Panel type Page numberMU2d-M1 53MU2d-M2 54MU2d-M3 55MU6d-N1 58MU6d-N2 58MU6d-N3 58MU6d-N5 58Approximate weight: 200 kg (MU2d only)MU2d shown connected to a non-extensible ring main unit

Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric

Note: for civil engineering and recommendations for internal arc clearances please consult our installation and maintenance instructions or contact Schneider Electric.

Page 104: 2017 Catalogue - s; E

schneider-electric.com102 | Ringmaster Catalogue

Installation drawings Non-extensible metering unitD

E598

13

Panel type Page numberMU2d-M1 53MU2d-M2 54MU2d-M3 55MU6d-N1 58MU6d-N2 58MU6d-N3 58MU6d-N5 58Approximate weight: 450 kg

Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric.

Note: for civil engineering and recommendations for internal arc clearances please consult our installation and maintenance instructions or contact Schneider Electric.

Page 105: 2017 Catalogue - s; E

schneider-electric.com | 103Ringmaster Catalogue

Installation drawings Telecontrol cabinetD

E598

15

Panel type Page numberEasergy T300 89Approximate weight: 30 kg (Easergy only)

Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric Tel: +44 (0)113 290 3500

Note: for civil engineering and recommendations for internal arc clearances please consult our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric Tel: +44 (0)113 290 3500

Page 106: 2017 Catalogue - s; E

schneider-electric.com104 | Ringmaster Catalogue

Schematic diagrams

Page 107: 2017 Catalogue - s; E

schneider-electric.com | 105Ringmaster Catalogue

Schematic diagrams

Schematic legendsSpecification

106

Ring main units accessories 108

Non-extensible / extensible ring main units 106

Non-extensible ring main unit 114

Non-extensible metering unit 115

Non-extensible / extensible circuit breaker units 116

Non-extensible circuit breaker units 116

Extensible circuit breaker units 117

Non-extensible switch units 139

Telecontrol unit block diagram 141

Page 108: 2017 Catalogue - s; E

schneider-electric.com106 | Ringmaster Catalogue

Schematic diagrams Schematic legendsSpecification

Fuse scheduleF1F2

VT secondary 16 A/link meteringVT secondary 2 A/link metering

Legends

EPSMRRL1RL2528996TFL/b/a/cASTCITC505150N51NINCMEFPIEPSREPSLESRESLTRS

earth position selected auxiliarymechanism reset switchclose relayopen relaycircuit breakerswitchdirect acting trip coiltime fuse linknormally closed auxiliary contactnormally open auxiliary contactnormally open make auxiliary contactammetershunt trip coilintegral trip coilinstantaneous overcurrenttime delayed overcurrentinstantaneous earth faulttime delayed earth faultminimum operating currentactuatorearth fault passage indicatorearth position selector rightearth position selector leftearth switch rightearth switch lefttrip reset spring

Symbols

DE6

0269

CT & VT Ratios Panel type CT1 CT2 CT3 CT4 VT1 VT2RN2d-T1 100/50/5 A

Class X

RN2d-T2 200/1 AClass X

RN2d-T3 500/200/1 AClass X

RN2d-T4 500/200/1 AClass X

RN2d-T5 100/50/5 AClass X

RN6d-T1 800/400/1 AClass X

RE2d-T1 100/50/5 AClass X

RE2d-T2 200/1 AClass X

RE2d-T3 500/200/1 AClass X

RE2d-T4 500/200/1 AClass X

MU2d-M1 50/25/5 A7.5 VA Class 0.5s

11000/110 V50 VA Class 0.5

MU2d-M2 100/50/5 A10 VA Class 0.5s

11000/110 V50 VA Class 0.5

MU2d-M3 200/100/5 A10 VA Class 0.5s

11000/110 V50 VA Class 0.5

CN2-T1 200/1 AClass X

CN2-T6 100/50/5 AClass X

CE2-T7 100/50/5 AClass X

CE2-T30 200/1 AClass X

CE2-T31 200/1 AClass X

CE2-T33 200/1 AClass X

CE2-T34 200/1 AClass X

Note: Please contact Schneider Electric for schematics not covered in this catalogue

Page 109: 2017 Catalogue - s; E

schneider-electric.com | 107Ringmaster Catalogue

Schematic diagrams Schematic legendsSpecification

Conditions1. All relays de-energised2. Switches shown in open position3. Auxiliary switch only operated between main ‘ON’ and main ‘OFF’ position (i.e. does not operate in earth position).CT and VT types

CTICT2CT3CT4VT1VT2

3 phase protection CT’s1 phase indication CT2 phase metering CTEasergy T300 phase & earth fault CtPh-Ph metering VT (2 phases)Ph-E metering VT (3 phases)

CT & VT Ratios Panel type CT1 CT2 CT3 CT4 VT1 VT2

CE6-T30 800/1 AClass X

600/5 A5 VA Class 1.0

CE6-T31 800/1 AClass X

600/5 A5 VA Class 1.0

SE6-S2 800/1 AClass X

600/5 A5 VA Class 1.0

500/1 AClass X

SN6-S2 800/1 AClass X

600/5 A5 VA Class 1.0

500/1 AClass X

Note: Please contact Schneider Electric for schematics not covered in this catalogue

Page 110: 2017 Catalogue - s; E

schneider-electric.com108 | Ringmaster Catalogue

Schematic diagrams

RMD-F328RMD-F507 RMD-F363

RMD-F329RMD-F507 RMD-F364

L1 L2 L3

EASERGY T300 CT’s FOR INTERNAL FAULTPASSAGE INDICATOR RMD-F310

DE5

9820

Ring main units accessories

Page 111: 2017 Catalogue - s; E

schneider-electric.com | 109Ringmaster Catalogue

Schematic diagrams Ring main units accessories

DE5

9821

RMD-F507 RMD-F365 (F581 and F582)

RMD-F368

RMD-F581RMD-F582

Page 112: 2017 Catalogue - s; E

schneider-electric.com110 | Ringmaster Catalogue

Schematic diagrams

L1

L 2

L3

PROVISION FORSHUNT TRIP COIL

DE5

9822

-1

Non-extensible / extensible ring main unit

Panel type Page numberRN2d-T1 26RE2d-T1 35For explanation of symbols see page 106

Page 113: 2017 Catalogue - s; E

schneider-electric.com | 111Ringmaster Catalogue

Schematic diagramsD

E598

24-1

Panel type Page numberRN2d-T3 28RE2d-T3 37For explanation of symbols see page 106

Non-extensible / extensible ring main unit

b 52

a 52

1 ES

1 EPS

INDICATION

E.S. CLOSE IND.

E.P.S. IND.

OPEN IND.

CLOSE IND.

44

43

42

41

40

L3

L1

L4COMMON

L7

L5

89L 89R52

CLASS: 5P25L1

L3

L2

51IDMT RELAY

VIP 40

B

ITC

K8

K7

MITOP COILD

E

+

-

Page 114: 2017 Catalogue - s; E

schneider-electric.com112 | Ringmaster Catalogue

Schematic diagramsD

E598

23-1

Panel type Page numberRN2d-T2 27RE2d-T2 36For explanation of symbols see page 106

Non-extensible / extensible ring main unit

b52

a52

1ES

1EPS

INDICATION

E.S. CLOSE IND.

E.P.S. IND.

OPEN IND.

CLOSE IND.

44

43

42

41

40

L3

L1

L4COMMON

L7

L5

89L 89R52

CLASS: 5P25L1

L3

L2

51IDMT RELAY

VIP 400

B

ITC

K8

K7

MITOP COIL

D

E

+

-

Page 115: 2017 Catalogue - s; E

schneider-electric.com | 113Ringmaster Catalogue

Schematic diagrams Non-extensible / extensible ring main unit

DE5

9825

-1

Panel type Page numberRN2d-T4 29RE2d-T4 38For explanation of symbols see page 106

b52

a52

1ES

1EPS

INDICATION

E.S. CLOSE IND.

E.P.S. IND.

OPEN IND.

CLOSE IND.

44

43

42

41

40

L3

L1

L4 COMMON

L7

L5

89L 89R52

CLASS: 5P25L1

L3

L2

51IDMT RELAY

VIP 45

B

ITC

K8

K7

MITOP COIL

D

E

+

-

Page 116: 2017 Catalogue - s; E

schneider-electric.com114 | Ringmaster Catalogue

Schematic diagrams Non-extensible ring main unitD

E598

26

Panel type Page numberRN6d-T1 31For explanation of symbols see page 106

89L 89R52

CLASS: 5P25L1

L3

L2

ITC

K8

K7

MITOP COIL

+

-

b52

a52

1ES

1EPS

INDICATION

E.S. CLOSE IND.

E.P.S. IND.

OPEN IND.

CLOSE IND.

44

43

42

41

40

L3

L1

L4 COMMON

L7

L5

51IDMT RELAY

VIP 45

B

D

E

Page 117: 2017 Catalogue - s; E

schneider-electric.com | 115Ringmaster Catalogue

Schematic diagrams Non-extensible metering unitD

E598

34

Panel type Page numberMU2d-M1 53MU2d-M2 54MU2d-M3 55MU6d-N1 58MU6d-N2 58MU6d-N3 58MU6d-N5 58For explanation of symbols see page 106

L1 L3

Page 118: 2017 Catalogue - s; E

schneider-electric.com116 | Ringmaster RN2d Catalog

Schematic diagrams Non-extensible circuit breaker units

DE5

9833

Panel type Page numberCN2-T6 46For explanation of symbols see page 106

L1 L 2 L3

Page 119: 2017 Catalogue - s; E

schneider-electric.com | 117Ringmaster Catalogue

Schematic diagrams Extensible circuit breaker units

DE5

9828

Panel type Page numberCE2-T7 63For explanation of symbols see page 106

L1 L 2 L3

Page 120: 2017 Catalogue - s; E

schneider-electric.com118 | Ringmaster Catalogue

Schematic diagrams Extensible circuit breaker units

DE5

9830

Panel type Page numberCE6-T30 72For explanation of symbols see page 106

S2

S1

P

P1

2

22

21 D131

A

D190 24

23

D170

D170

REMOVE LINKFOR REMOTEINDICATION

11

12

14

13

15

L11

L7

L9

L5

L3

16L1

52/b

52/b

52/a

52

52/cK5

STC

1

3

2

K3

K2

K4

CONTACTSAUXILIARYSPARE

SHUNTTRIPCOIL

COMMON

20-48V DC

110-250V AC/DC

CLASS: 5P25

L1

L3

L2

51IDMT RELAY

VIP 400

B

ITC

K8

K7

MITOP COIL

D

E

+

-

CLASS: 1.0BURDEN: 5VARATIO: 600/5A L2

D131

D130

Page 121: 2017 Catalogue - s; E

schneider-electric.com | 119Ringmaster Catalogue

Schematic diagrams Extensible circuit breaker units

DE5

9835

Panel type Page numberCE2-T33 68For explanation of symbols see page 106

STC

K5

52

52/b

52/b

12

14

13

15

L7L9

L5L3

52/a 16L1

11L11

CONTACTSAUXILIARYSPARE

3

2K2

K4

1K352/c

SHUNTTRIPCOIL

COMMON

20-48V DC

110-250V AC/DC

CLASS: 5P25L1

L3

L2

51IDMT RELAY

VIP 40

B

ITC

K8

K7

MITOP COIL

D

E

+

-

Page 122: 2017 Catalogue - s; E

schneider-electric.com120 | Ringmaster Catalogue

Schematic diagrams Extensible circuit breaker units

DE5

9835

-1

Panel type Page numberCE2-T34 69For explanation of symbols see page 106

STC

K5

52

52/b

52/b

12

14

13

15

L7L9

L5L3

52/a 16L1

11L11

CONTACTSAUXILIARYSPARE

3

2K2

K4

1K352/c

SHUNTTRIPCOIL

COMMON

20-48V DC

110-250V AC/DC

CLASS: 5P25L1

L3

L2

51IDMT RELAY

VIP 40

B

ITC

K8

K7

MITOP COIL

D

E

+

-

Page 123: 2017 Catalogue - s; E

schneider-electric.com | 121Ringmaster Catalogue

Schematic diagrams Extensible circuit breaker units

DE5

9837

Panel type Page numberCE2-T31 65For explanation of symbols see page 106

RL2/3

RL2/4M

MR/1K15

K13

K23RL1/2

52/b

K17

K21 K25

RL1/3

RL1/4

RL2/2

EPS/1

K19 32L15

RL2/1RL2

52/b

RL1/1RL129

28

27

26

25K11

K9K22K20

X

31

30

K10

K12L13

11

12

14

13

15

L11

L7L9

L5L3

16L1

52/b

52/b

52/a

EPS/2

52

52/cK5

STC

1

3

2

K3

K2

K4

SELECTED

COMMON

SUPPLY24V DC

-+

ACTUATOR

EARTHCLOSE

OPEN

CONTACTSAUXILIARYSPARE

POSITION

SHUNTTRIPCOIL

COMMON

20-48V DC

110-250V AC/DC

CLASS: 5P25

L1

L3

L2

51IDMT RELAY

VIP 400

B

ITC

K8

K7

MITOP COIL

D

E

+

-

Page 124: 2017 Catalogue - s; E

schneider-electric.com | 122Ringmaster Catalogue

Schematic diagrams Extensible circuit breaker units

DE5

9841

Panel type Page numberCE6-T31 74For explanation of symbols see page 106

S2

S1

P

P1

2

22

21 D131

A

D190 24

23

D170D170

REMOVE LINKFOR REMOTEINDICATION

RL2/3RL2/4

M

MR/1 K15

K13

K23RL1/2

52/b

K17

K21 K25

RL1/3

RL1/4

RL2/2

EPS/1

K19 32L15

RL2/1RL252/b

RL1/1RL129

28

27

26

25K11

K9K22K20

X

31

30

K10

K12L13

11

12

14

13

15

L11

L7L9

L5L3

16L1

52/b

52/b

52/a

EPS/2

52

52/cK5

STC

1

3

2

K3

K2

K4

SELECTED

COMMON

SUPPLY24V DC

-+

ACTUATOR

EARTHCLOSE

OPEN CONTACTSAUXILIARYSPARE

POSITION

SHUNTTRIPCOIL

COMMON

20-48V DC

110-250V AC/DC

CLASS: 5P25

L1

L3

L2

51IDMT RELAY

VIP 400

B

ITC

K8

K7

MITOP COIL

D

E

+

-

CLASS: 1.0BURDEN: 5VARATIO: 600/5A

L2

D131

D130

Page 125: 2017 Catalogue - s; E

schneider-electric.com | 123Ringmaster Catalogue

Schematic diagrams Non-extensible switch unitsD

E598

44

Panel type Page numberSN6-S2 50For explanation of symbols see page 106

L1 L 2 L3 Easergy T300

Page 126: 2017 Catalogue - s; E

schneider-electric.com124 | Ringmaster Catalogue

Schematic diagrams Non-extensible switch unitsD

E598

45

Panel type Page numberSE6-S2 79For explanation of symbols see page 106

L1 L 2 L3 Easergy T300

Page 127: 2017 Catalogue - s; E

schneider-electric.com | 125Ringmaster Catalogue

Notes

Page 128: 2017 Catalogue - s; E

schneider-electric.com126 | Ringmaster Catalogue

Accessories & options

Page 129: 2017 Catalogue - s; E

schneider-electric.com | 127Ringmaster Catalogue

Accessories & options

Accessories descriptionMV substation remote monitoring unit - Flair 200C

Voltage indicator and relay - VD23

Fault passage indicators - Flair 21D and 22D

Motorisation

Other accessories

128

Tee-off cable box fitted to SN6/CN2 133

Ringmaster range cabling accessories 134

Page 130: 2017 Catalogue - s; E

schneider-electric.com128 | Ringmaster Catalogue

Accessories & options Accessories descriptionMV substation remote monitoring unitFlair 200C

MV substation remote monitoring unit Flair 200CA product dedicated to remote monitoring of MV substations with a high level of function integration

Easergy Flair 200C is a remote monitoring unit designed to be installed in the MV substations of a public-private distribution network or in customers’ substations. Easergy Flair 200C is a tool that complements control units for MV substations (Easergy T300) and conventional fault passage indicators (Easergy Flair).

Easergy Flair 200C is specially designed to meet customers’ requirements for the management of MV substations. It provides compact, open solutions:• Fault passage indicator compatible with any type of earthing system • Substation monitoring: sending of an alarm in the event of an incident

in the substation for efficient maintenance• Power monitoring unit on the MV and LV network for improved monitoring

of load curves and improved power distribution efficiency• Substation digital concentrator for interfacing between the substation’s

communicating equipment and the control centre • Communication with the remote control centre with call management upon alarm.

PE57

570 Flair 200C

The Flair 200C is an efficient tool for reducing repair and fault finding times. It improves quality of service and operation for power supply companies.

Page 131: 2017 Catalogue - s; E

• Various combinations: - presence or absence voltage relay - zero sequence voltage relay - phase-to-neutral or phase-to-phase voltage - phase selection.

• Easy to install: - compact 96 x 48 mm DIN format - terminal connection for VPIS-VO - no need for HV transformer - hot installation - auto-adaptation of nominal voltage.

Voltage indicator and relay VD23FeaturesThe VD23 is a compact voltage relay for 3 kV to 36 kV, 50/60 Hz mediumvoltage networks. It is associated with a capacitive divider and a VPIS-VO.• 2 output relays based on 2 functional modes:

- R1 = Voltage presence (typically used for automatic transfer switching) - R2 = Voltage absence (typically used for interlocking of earthing switch).

• Thresholds can be set as a percent of phase-to-neutral voltage (V), phase-to-phase voltage (U) or residual voltage (VO)

• All combinations of voltage conditions are possible: - 3 phases and residual: V1+V2+V3+VO - 3 phases: V1+V2+V3 or U12+U13+U23 - single phase: Vo, V1, V2, V3, U12, U13 or U23

• Output is a tripping order via two output relays with a normal or inverse active position

• Signalling and tripping outputs may be set with a delay.

Display principle• Voltage value (% of Un) of L1, L2 and L3 shown on the display• Voltage presence/absence indication via LED• Settings by front pushbuttons and LCD

- thresholds, delays and smart parameters - display of all settings on LCD.

• Auto-adaptation of the nominal system voltage• Check on voltage status.

Advanced settingsAll the combinations can be set with microswitches on the rear of the device. The use of two relays provides safety backup operation for each combination

6 microswitches: 1: Ph-N voltage(V) / Ph-Ph voltage(U)2: Direct / inverse action on output relays3: Phase 1 used / not used4: Phase 2 used / not used5: Phase 3 used / not used6: Residual voltage used / not used

1 2 3 4 5 6

10

Wiring (with VPIS-VO)All the combinations can be set with microswitches on the rear of the device. The use of two relays provides safety backup operation for each combination.

VD23

PE57

787

VPIS-VO

VD23

L1L2L3

DM

1000

60

Voltagepresence

24-48 Vdc

Voltageabsence

The VD23 is a voltage detecting system for automatic transfer system or interlock applications.

schneider-electric.com | 129Ringmaster Catalogue

Accessories & options Accessories descriptionMV substation remote monitoring unitVoltage indicator and relay VD23

Page 132: 2017 Catalogue - s; E

schneider-electric.com130 | Ringmaster Catalogue

Accessories & options Accessories descriptionFault passage indicatorsFlair 21D and Flair 22D

These devices use cutting-edge technology to detect earth faults on underground MV networks with isolated, resistor-earthed or directly earthed neutral and overcurrents on all networks.

• Self-powered, the fault current passage detection and indication system operates continuously

• Adjustment-free, they are immediately operational (numerous manual adjustments are however possible)

• Compact, their DIN format easily fits in MV cubicles

• Smart, they offer an ammeter/digital maximeter function.

• Earth fault sensitivity as low as 5 A• Display of settings and faulty phase • Automatic reset

Applications and main featuresThe Flair range increases your power availability by providing indicatorssuitable for fault locating and MV network load management.• Indication of phase-phase and phase-earth faults• Display of settings• Indication of the faulty phase• Display of the load current including peak demand and frequency.

These fault passage indicators are reliable and easy to use.• Automatic setting on the site• Fault indication with LED or outdoor lamp• 15-year battery life for Flair 22D• More accurate fault detection if Flair 22D is connected to voltage presence

indication system (VPIS) voltage output• Can be factory-mounted in Premset cubicles or added on the site• Easy on-site addition without removing MV cables using split-type current sensor.

Fault detection functionsOvercurrent detection• Automatic mode for adjustment-free calibration of detection thresholds• Manual mode for special override settings:

- Flair 21D: 4 detection thresholds from 200 A to 800 A, in 200 A increments, selectable via microswitches

- Flair 22D: 8 detection thresholds from 100 A to 800 A, in 50 A increments, configurable via the front panel keypad.

• Fault acknowledge time: - Flair 21D: 40 ms - Flair 22D (configurable via the front panel keypad)

- Type A from 40 to 100 ms in 20 ms increments - Type B from 100 to 300 ms in 50 ms increments.

Earth fault detection

The detector checks the 3 phases for current variations (di/dt). A time delay of 70 s is applied for fault confirmation by the upstream protective device.• Automatic mode for adjustment-free calibration of detection thresholds• Manual mode for special override settings:

- Flair 21D: 6 detection thresholds from 40 to 160 A, via microswitches - Flair 22D (configurable via the front panel keypad):

- Type A from 20 to 200 A, in 10 A increments - Type B from 5 to 30 A in 5 A increments and 30 to 200 A in 10 A.

• Inrush function: prevents unnecessary detection in the event of load switch-on. Incorporates a 3 s time delay for fault filtering at network power up. The Inrush function can be disabled via configuration on Flair 22D.

Fault indication functionSignallingAs soon as a fault is confirmed, the indication device is activated.• Fault indication via a red LED on the front panel• Indication of the faulty phase (earth fault) on LCD display• Optional remoting of indication to external flashing lamp• Activation of a contact for retransmission to the SCADA system.

Indication reset• Automatic reset upon load current recovery (configurable time delay on Flair 22D)• Manual reset via front panel button• Reset via external Reset input• Reset by time delay: fixed (4 hr) for Flair 21D and adjustable using front

panel keypad (2 hr to 16 hr) for Flair 22D.

Flair 21D

Flair 22D

PE57

783

PE57

784

Flair 21D, 22D is a family of DIN format fault passage indicators. They are small in size, self-powered and adapt automatically to the network.

Page 133: 2017 Catalogue - s; E

Display principle• The load current is displayed continuously• When a fault is detected, the faulty phase is indicated• Use the buttons on the front panel to scroll through settings and measurements.

Selection tableFlair 21D Flair 22D

Power supply Self-powered b bDual-powered b (1)

Detection Overcurrent b bEarth-fault b b

Display (4 digit LCD)

Ammeter b bMaximeter b b

Options SCADA interface (relay) b bExternal lamp b bExternal reset bExtended setting (keypad) b

Communication 2-voltage output relaysSerial communication port

(1) By lithium battery

Characteristics per product

Model Description Fault passage indicator with single power supply (self-powered)Flair 21D Detector with autonomous power supply

External indicator lamp output powered by battery (BVP) Fault passage indicator with dual power supplyFlair 22D Detector with autonomous power supply and lithium battery

External indicator lamp output powered by the Flair (BVE)Zero sequence CT option (type B setup)Interface with VPIS-VO possible to confirm the fault by voltage absence

Standard applications

Flair 21D Maintenance-free, adjustment-free fault detectorFlair 22D Fault detector for networks with very low load current (< 2 A)

with possibility of manual adjustments.

Clear, comprehensive display

Connection diagrams

Sensors

The Flair 21D, 22D range uses an integrated detection system composed of indicators and dedicated CTs.

Integrated sensors are normally placed around the bushings. Split CTs can be placed around cables for retrofit purposes.

Flair 22DEasergy

L1L2L3

I max.

EMS58352

AEsc

TestReset

DE5

8715

L3 L2L1

Reset

Reset

VPIS-VOoption

Flair 21D

Flair 22D

L3 L2L1

Indication

Indication

DM

1000

48Accessories & options Accessories description

Fault passage indicatorsFlair 21D and Flair 22D

schneider-electric.com | 131Ringmaster Catalogue

Page 134: 2017 Catalogue - s; E

schneider-electric.com132 | Ringmaster Catalogue

Accessories & options Accessories descriptionMotorisation

Simple, fast and efficient motorisation solutionAs the world moves towards more smart networks, the remote operation of RMUs will become more necessary.

Ringmaster with its “Plug-in” motor design offers customers to convert their pre-wired manual operated RMUs to motorised, remotely controlled in a couple of minutes.

The plug-in motor-gear assembly, called as “Motor-pack” can be directly plugged on to the mechanism on site, in live or dead condition of the Ring Main Unit. Providing customer the benefit of enormous time saving, easiness and flexibility.

This “Motorpack” is universal in nature as the same Motorpack can be used to motorise either switch or circuit breaker.

The whole motor unit just needs a screw to secure it in position once fitted on the Ring Main Unit.

DSC

0457

DSC

0456

Page 135: 2017 Catalogue - s; E

AccessoriesThese are dispatched either:• Fitted to the unit within the works - these are accessories that are either too bulky,

or need testing prior to despatchie; tee-off cable box• Loose, boxed, for you to assemble on site. These items are either those that need

to be supplied loose to ease installation: ie a gland plate, or test equipment.

RMD-A14/A15/A78/A79

Busbar assemblies• Each kit comprises a three phase set of busbars, 630 A• Specify at time of ordering:

- 1 off RMD-A15 - end panel kit, plus busbar kits - Quantity required = No. of panels - 1

Note: Different busbar kits are required for metering units and bus-sectionsBusbars are dispatched loose.

RMD-A17

Time Fuse Links• 2 off time fuse links for overcurrent protection

Order code RatingRMD-A17/3 3 ampRMD-A17/5 5 ampRMD-A17/7 7.5 ampRMD-A17/10 10 ampRMD-A17/12 12.5 ampRMD-A17/15 15 amp

DE6

0245

-1D

E602

70

Schneider Electric are able to provide a number of accessories to enhance the basic unit specifications. These accessories are detailed within the panel type specifications

RMD-A15RMD-A14

RMD-A15RMD-A79RMD-A78

schneider-electric.com | 133Ringmaster Catalogue

Accessories & options Accessories descriptionOther accessories

Page 136: 2017 Catalogue - s; E

schneider-electric.com134 | Ringmaster Catalogue

Accessories & options Tee-off cable box fitted to SN6/CN2

DE6

0247

Panel type Page numberCN2-T1 45CN2-T6 46SN6-S1 49SN6-S2 50Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric Tel: +44 (0)113 290 3500

Page 137: 2017 Catalogue - s; E

DE5

9850

Panel type Page numberCE2 59-60-61CE6 70-71SE6 76-77CN2 43-44SN6 47-48Approximate weight: 250 kg

799

schneider-electric.com | 135Ringmaster Catalogue

Accessories & options Ringmaster range cabling accessories

Page 138: 2017 Catalogue - s; E

schneider-electric.com136 | Ringmaster Catalogue

Order form

Page 139: 2017 Catalogue - s; E

schneider-electric.com | 137Ringmaster Catalogue

Order form

Order formGuide Metering & Bus section

138

Page 140: 2017 Catalogue - s; E

schneider-electric.com138 | Ringmaster Catalogue

Order form Guide Metering & Bus section

Panel types

Motor provision

VT Confi- guration

Service voltage

Rated voltage

Secon- dary voltage

VT output/class CT primary/secondary current

CT output/class

MU2d (200 A Ring Main Unit metering)

MU2d-M1 NA 2 ph - ph 11 kV 12 kV 110 V 50 VA Class 0.5 50/25/5 7.5 VA Class 0.5s

MU2d-M2 NA 2 ph - ph 11 kV 12 kV 110 V 50 VA Class 0.5 100/50/5 10 VA Class 0.5s

MU2d-M3 NA 2 ph - ph 11 kV 12 kV 110 V 50 VA Class 0.5 200/100/5 10 VA Class 0.5s

MU2d- M12

NA 3 ph - earth 11 kV 13.8 kV 110 V 50 VA Class 0.5 + 20 VA Neutral voltage protection

200/100/5 10 VA Class 0.5s

CE2-T (200 A metered circuit breaker)CE2-T32 No motor 2 ph - ph 6.6 12 110 V 50 VA Class 0.5 200/100/5 A 10 VA class 0.5s

CE2-T36 Motor fittable 2 ph - ph 6.6 12 110 V 50 VA Class 0.5 200/100/5 A 10 VA class 0.5s

CE2-T40 No motor 2 ph - ph 11 12 110 V 50 VA Class 0.5 200/100/5 A 10 VA class 0.5s

CE2-T35 Motor fittable

2 ph - ph 11 12 110 V 50 VA Class 0.5 200/100/5 A 10 VA class 0.5s

CE2-T38 No motor 3 ph - earth 11 17.5 110 V 50 VA Class 0.5 + 20 VA Neutral voltage protection

200/100/5 A 10 VA class 0.5s

CE2-T37 No motor 3 ph - earth 13.8 17.5 110 V 50 VA Class 0.5 + 20 VA Neutral Voltage Protection

200/100/5 A 10 VA class 0.5s

CE2-T39 Motor fittable

3 ph - earth 13.8 17.5 110 V 50 VA Class 0.5 + 20 VA Neutral voltage protection

200/100/5 A 10 VA class 0.5s

CE6-T (630 A metered circuit breaker)CE6-T39 No motor 2 ph - ph 6.6 12 110 V 50 VA Class 0.5 400/200/5 A 10 VA class 0.5s

CE6-T35 Motor fittable

2 ph - ph 6.6 12 110 V 50 VA Class 0.5 400/200/5 A 10 VA class 0.5s

CE6-T33 No motor 2 ph - ph 11 12 110 V 50 VA Class 0.5 400/200/5 A 10 VA class 0.5s

CE6-T34 Motor fittable

2 ph - ph 11 12 110 V 50 VA Class 0.5 400/200/5 A 10 VA class 0.5s

CE6-T36 No motor 3 ph - earth 13.8 17.5 110 V 50 VA Class 0.5 400/200/5 A 10 VA class 0.5s

CE6-T38 Motor fittable

3 ph - earth 13.8 17.5 110 V 50 VA Class 0.5 400/200/5 A 10 VA class 0.5s

CE6-T37 No motor 3 ph - earth 11 17.5 110 V 50 VA Class 0.5 + 20 VA Neutral voltage protection

400/200/5 A 10 VA class 0.5s

CE6-B (630 A bus section circuit breaker)

CE6-B9 No motor 2 ph - ph 11 12 110 V 50 VA Class 0.5 400/200/5 A 10 VA class 0.5s

CE6-B10 Motor fittable

2 ph - ph 11 12 110 V 50 VA Class 0.5 400/200/5 A 10 VA class 0.5s

SE6-B (630 A bus section switch)SE6-B1 No motor No VT No VT No VT No VT No VT No CT No CT

SE6-E (630 A busbar earthing switch)SE6-E1 No motor No VT No VT No VT No VT No VT No CT No CT

Page 141: 2017 Catalogue - s; E

schneider-electric.com | 139Ringmaster Catalogue

Order form Notes

Page 142: 2017 Catalogue - s; E

November 2017 SE10176©2017 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.

About Schneider Electric

Schneider Electric is leading the Digital Transformation of Energy Management and Automation in Homes, Buildings, Data Centers, Infrastructure and Industries.

With global presence in over 100 countries, Schneider is the undisputable leader in Power Management – Medium Voltage, Low Voltage and Secure Power, and in Automation Systems. We provide integrated efficiency solutions, combining energy, automation and software.

In our global Ecosystem, we collaborate with the largest Partner, Integrator and Developer Community on our Open Platform to deliver real-time control and operational efficiency.

We believe that great people and partners make Schneider a great company and that our commitment to Innovation, Diversity and Sustainability ensures that Life Is On everywhere, for everyone and at every moment. www.schneider-electric.com

This document has beenprinted on recycled paper

Schneider Electric

United KingdomStafford Park 5, TelfordShropshire TF3 3BLTel: 0870 608 8 608Fax: 0870 608 8 606

www.schneider-electric.co.uk

IrelandHead office, Block AMaynooth Business CampusMaynooth, Co. Kildare W23 Y7X0Tel: 1 800 805 800Fax: (01) 601 2201

www.schneider-electric.ie