Number K86644/02
Issued July 9th, 2015
Valid until July 10th, 2016
Declaration of Conformity, based on parts of CEN/TR 15276-1, regarding
DSPA
Non-Pressurized Condensed Aerosol Generators and
Components
Kiwa Nederland B.V.
Groningenweg 10
Postbus 256
2800 AG Gouda
Tel. +31-182-820460
Fax +31-182-820465
Internet www.kiwafss.nl
Company
DSPA B.V.
Hulzenseweg 10-20
6534 AN NIJMEGEN
P.O. Box 6572
6503 GB NIJMEGEN
The Netherlands
Tel. +31 24 352 25 73
Fax +31 24 37 87 583
www.dspa.nl
This declaration consists of 12 pages.
Publication of this declaration is allowed.
Note: Publication of only this front page or parts of the declaration is considered as “not valid”.
STATEMENT BY KIWA
With this declaration, Kiwa declares that legitimate confidence exists that the
products supplied by
DSPA B.V.
comply with the technical specifications as laid down in this product
declaration and marked with the Kiwa®-mark in the manner as indicated in this
product declaration.
Bouke Meekma
Kiwa
Kiwa®
product declaration K86644/02 Page 2 of 12
DSPA Non-Pressurized Condensed Aerosol Generators and Components
Declaration
This product declaration is based on test protocol PRO10-001-AFG-nk rev 06 and parts of CEN/TR 15276-1.
Generator specifications
The products mentioned below belong to this product declaration.
DSPA 11-1, DSPA 11-2, DSPA 11-3, DSPA 11-4, DSPA 11-5, DSPA 11-6, DSPA 11-7 and DSPA 8-1.
Type Housing Red coated steel
Activation
DSPA 11-1 Disk, radial, double shaped plate Electrical
DSPA 11-2 Disk, radial, double shaped plate Electrical
DSPA 11-3 Disk, radial, double shaped plate Electrical
DSPA 11-4 Disk, radial, double shaped plate Electrical
DSPA 11-5 Disk, radial, double shaped plate Electrical
DSPA 11-6 Disk, radial, double shaped plate Electrical
DSPA 11-7 Disk, axial, double shaped plate Electrical
DSPA 8-1 Cylindrical, axial Electrical
Non-pressurized generator.
Application and use
Condensed aerosol extinguishing systems for total flooding applications in normally unoccupied and unoccupiable areas, primarily related
to buildings, plant and other specific applications, utilising electrically non-conducting aerosol fire extinguishants.
The following are typical of such hazards, but the list is not exhaustive:
a) Electrical and electronic hazards;
b) Telecommunications facilities;
c) Flammable and combustible liquids and gases;
Where aerosol generators are used in a potentially explosive application, the suitability of the generator to the atmosphere for the
determined life shall be assessed.
The fire extinguishing components shall be suitable for extinguishing fires of the following classes:
• Class A according EN2
• Class B according EN2
Conditions for application
• The numbers and types of the extinguishing components have to be determined in conformity with the guidelines and calculation
methods of the supplier.
• Distribution is to be done by supplier or companies authorised by the supplier.
• Before usage an instruction is to be given by a trainer or instructor for this product authorized by the supplier.
• The installation and maintenance of the fire extinguishing components have to take place according to the specifications of the
supplier, CEN/TR 15276-2 or evaluation guideline BRL-K23003
Point of interest during use or limitation of use
The condensed aerosol extinguishing components should not be used on fires involving the following unless relevant testing by accredited testing laboratories has been carried out to the satisfaction of the Authority:
• Chemicals containing their own supply of oxygen, such as cellulose nitrate;
• Mixtures containing oxidizing materials, such as sodium chlorate or sodium nitrate;
• Chemicals capable of undergoing auto thermal decomposition, such as some organic peroxides;
• Reactive metals (such as sodium, potassium, magnesium, titanium and zirconium), reactive hydrides, or metal amides, some of
which may react violently with the extinguishants;
• Oxidizing agents such as nitric oxides and fluorine;
• Pyrophoric materials such as white phosphorous or metallo-organic compounds.
The above list may not be exhaustive.
Kiwa®
product declaration K86644/02 Page 3 of 12
DSPA Non-Pressurized Condensed Aerosol Generators and Components
• The design, installation, service and maintenance of aerosol generators should be performed by those competent persons in fire
extinguishing system technology.
• The hazards, against which these aerosol generators offer protection, and any limitations on their use, should be included in the
system supplier’s design manual.
• Effects of agent particulate residue on sensitive equipment and other objects should be considered when using condensed aerosol
extinguishing agents in spaces containing that type of equipment.
• Under certain conditions the potential for explosive atmospheres may exist. Areas where such potential may exist are classified as
hazardous. Condensed aerosols may be used in hazardous areas subject to the supplier obtaining the specific listings and
approvals for such areas from the appropriate authorities.
• Where aerosol generators are used in potentially explosive atmosphere, the compatibility of the generator to the atmosphere for the
determined lifetime should be assessed. The EU Directive 94/9/EC (ATEX Directive) should be taken into consideration.
• Local applications 1) of condensed aerosol extinguishing systems are not covered by this product declaration.
• Local applications require a pre-engineered and pre-designed system which has been tested and approved for a specific application
by a authority such as Kiwa or by an accredited testing laboratory.
1)
a local application is used for the extinguishment of surface fires in flammable liquids, gasses, and shallow solids, where the
enclosure does not conform to the requirements for total flooding.
Manual
At delivery the product should be accompanied by an operation manual in the English language, known and authorized by Kiwa.
The supplier shall prepare and maintain documentation. The supplier shall prepare installation and user documentation. This
documentation shall compromise at least the following:
a) A general description of the components;
b) A technical specification including:
1. Information mentioned in drawings, parts list, description of function, operating instructions, the minimum distance from the
generator outlet to the first obstacle, the minimum and maximum mass of aerosol compound discharged from the generator and
actuation inside an explosive atmosphere;
2. Sufficient information to permit an assessment of the compatibility with other components of the system (if applicable e.g.
mechanical, electric or software compatibility);
c) Installation instructions including mounting instructions;
d) Operating instructions;
e) Maintenance instructions.
Marking
The products should be marked with the Kiwa®-mark.
Place of the mark Required specifications Method of marking
• On the generator
• Name of the product and supplier
• Supplier’s type designation
• Production date and serial number
• Mass of aerosol-forming compound
• Temperature range
• Storage humidity range
• Service life
• Distances as specified in table 5
• Reference to the application
instructions
• Certification mark
• Fire Class A according EN2
• Fire Class B according EN2
• Non-erasable and non-detachable;
• Non-flammable;
• Permanent an legible
Kiwa®
product declaration K86644/02 Page 4 of 12
DSPA Non-Pressurized Condensed Aerosol Generators and Components
Recommendations for Customers
Check at the time of delivery whether:
• The supplier has delivered in accordance with the agreement;
• The mark and the marking method are correct;
• The products show no visible defects as a result of transport etc.
If you should reject a product on the basis of the above, please contact:
• DSPA B.V.
and, if necessary,
• Kiwa Nederland B.V.
Consult the suppliers processing guidelines for the proper storage and transport methods.
Kiwa®
product declaration K86644/02 Page 5 of 12
DSPA Non-Pressurized Condensed Aerosol Generators and Components Cross reference CEN/TR 15276-1, Fixed fire fighting systems - Condensed aerosol extinguishing systems - Part 1: Requirements and test methods for components, February 2009
Chapter Description Demand 1) Result Remarks
1. Scope Implemented
2. Normative references Implemented
3 Terms and definitions Implemented
4 Component requirements
4.1 Condensed aerosol generator A See DSPA Manual
V7.3 2015
4.2 Solid aerosol-forming compound A See DSPA Manual
V7.3 2015
4.3 Cooling mechanism A See DSPA Manual
V7.3 2015
See table 5
4.4 Ignition device
4.4.1 General Implemented
4.4.2 Electrical ignition device Implemented
4.4.3 Thermal ignition device N/A
4.4.4 Other methods of ignition device N/A
4.5 End plate and housing Implemented
See DSPA Manual
V7.3 2015
4.6 Extinguishants Implemented
See DSPA Manual
V7.3 2015
5. Condensed aerosol generator requirements
5.1 General A Implemented
See 5.16 and 7.3
See table 2
See table 5
5.2 Extinguishing factor A Implemented
See 7.4
See table 1
5.3 Agent distribution A Implemented
See 7.5
See table 3
5.4 Discharge time A Implemented
See 7.6
See table 4
Kiwa®
product declaration K86644/02 Page 6 of 12
DSPA Non-Pressurized Condensed Aerosol Generators and Components
Chapter Description Demand 1) Result Remarks
5.5 Ambient temperature and humidity operation ranges A Temperature
limitations from -40
°C to +75°C and ambient humidity up
to 95 %.
See 7.7
5.6 Service life A See 7.8
5.7 Shelf life and storage conditions Not relevant in
relationship to
this product
declaration
See DSPA Manual
V7.3 2015
5.8 Corrosion A Implemented
See 7.9 and 7.10
5.9 Vibration A Implemented
See 7.11
5.10 Mechanical shock A Implemented
See 7.12 and 7.13
5.11 Discharge temperature
5.11.1 General Implemented
5.11.2 Casing temperature Not tested See 7.14
5.11.3 Aerosol flow temperature A Implemented
See DSPA Manual
V7.3 2015
See 7.14
See table 5
5.12 Ignition device
5.12.1 General Implemented
5.12.2 Electrical ignition device A Implemented
See 7.15
5.12.3 Thermal ignition device N/A
5.13 Function reliability A Implemented
See 7.16
5.14 Open fire conditions Not tested
5.15 Accessories A Implemented
See 7.9, 7.11, 7.12
and 7.13.
5.16 Documentation A Pass See DSPA Manual
V7.3 2015
Kiwa®
product declaration K86644/02 Page 7 of 12
DSPA Non-Pressurized Condensed Aerosol Generators and Components
Chapter Description Demand 1) Result Remarks
6 Marking A Pass See DSPA Manual
V7.3 2015
7. Test methods
7.1 Conditions A Implemented
7.2 Samples A Implemented
7.3 Conformity A Implemented
See DSPA Manual
V7.3 2015
7.4 Extinguishing factor determination A Implemented
See DSPA Manual
V7.3 2015
See specific test in
Annex A.
See table 1
7.5 Coverage determination A Implemented
See DSPA Manual
V7.3 2015
See specific test in
Annex A.
See table 3
7.6 Discharge time test A Implemented
See DSPA Manual
V7.3 2015
See 7.16.1
See table 4
7.7 Temperature and humidity operation range tests
7.7.1 Object of the test
7.7.2 Test procedure
7.7.3 Low temperature Test
A Pass Implemented
DSPA 11-3, DSPA
11-6, DSPA 11-7 and
DSPA 8-1 were
tested.
DSPA 11-1, DSPA
11-2, DSPA 11-4 and
DSPA 11-5 are
members of the
same generator
family as DSPA 11-3
and DSPA 11-6.
7.8 Accelerated ageing test
7.8.1 Test time
7.8.2 Test procedure
A Pass All types
116 test days at 90
ºC = 15 years based
on UL 2775
See DSPA Manual
V7.3 2015
7.9 Corrosion test A Pass Implemented
DSPA 11-3, DSPA
Kiwa®
product declaration K86644/02 Page 8 of 12
DSPA Non-Pressurized Condensed Aerosol Generators and Components
Chapter Description Demand 1) Result Remarks
11-6, DSPA 11-7 and
DSPA 8-1 were
tested.
DSPA 11-1, DSPA
11-2, DSPA 11-4 and
DSPA 11-5 are
members of the
same generator
family as DSPA 11-3
and DSPA 11-6.
7.10 Stress corrosion test A Pass Materials used in the
construction are not
susceptible to
ammonia stress
corrosion
7.11 Vibration test A Pass Implemented
DSPA 11-3, DSPA
11-6, DSPA 11-7 and
DSPA 8-1 were
tested.
DSPA 11-1, DSPA
11-2, DSPA 11-4 and
DSPA 11-5 are
members of the
same generator
family as DSPA 11-3
and DSPA 11-6.
Type 8.1 only at 0,5G
7.12 Impact test A Pass
7.13 Drop test A Pass Implemented
DSPA 11-3, DSPA
11-6, DSPA 11-7 and
DSPA 8-1 were
tested.
DSPA 11-1, DSPA
11-2, DSPA 11-4 and
DSPA 11-5 are
members of the
same generator
family as DSPA 11-3
and DSPA 11-6.
7.14 Casing and aerosol flow temperatures test
7.14.1 Casing temperatures test Not tested
7.14.2 Aerosol flow temperature test A Implemented
See DSPA Manual
V7.3 2015
See 7.16
See table 5
7.15 Ignition performance test A Pass 500 ignition devices
are tested
Kiwa®
product declaration K86644/02 Page 9 of 12
DSPA Non-Pressurized Condensed Aerosol Generators and Components
Chapter Description Demand 1) Result Remarks
7.16 Function test
7.16.1 Discharge time A Pass See table 4
7.16.2 Aerosol flow temperatures A Pass See table 5
7.16.3 Test procedure A Pass
7.16.4 Casing temperature test Not tested
7.16.5 Discharged mass A Pass See DSPA Manual
V7.3 2015
See table 2
7.16.6 Explosive atmosphere actuation test Not tested
7.16.7 Requirements Implemented
7.17 Heat exposure test Not tested
7.18 Explosive atmosphere test Not tested
Annex A (normative) Extinguishing factor/coverage test procedure
A1 General Implemented
A2 Principle Implemented
A3 Extinguishing system Implemented
A4 Extinguishing factor Implemented
A5 Aerosol generator distribution verification tests
A5.1 Minimum height/maximum coverage test A Pass See table 3
A5.2 Maximum height test A Pass See table 3
A6 Extinguishing factor tests
A6.1 Wood crib test A Not tested
A6.2 n-Heptane pan test A Pass See table 1
A6.3 Polymeric sheet fire test
A6.3.2.2 Polymethyl methacrylate (PMMA);
A6.3.2.2 Polypropylene,
A6.3.2.2 Acrylonitrile-butadiene-styrene polymer (ABS)
A Pass See table 1
A6.4 Composite wood fire test
A6.4.2.2 Reformed wood (chops) both sides plastic lined
A6.4.2.2 MDF (Medium Density Fibreboards) according to
EN 622 and EN 316 not lined
A6.4.2.2 Multilayers plywood ( kiln spruce or fir) not lined
A Pass See table 1
A7 Aerosol generator explosive atmosphere test
A7.1 Actuation test inside an explosive atmosphere
environment.
Not tested
1) A = Applicable N/A = Not Applicable Not tested
Kiwa®
product declaration K86644/02 Page 10 of 12
DSPA Non-Pressurized Condensed Aerosol Generators and Components
Tests not performed (with requirements):
• 5.11.2 Casing temperature
• 5.14 Open fire conditions
• 7.16.6 Explosive atmosphere actuation test
• 7.17 Heat exposure test
• A6.1 Wood crib test
Kiwa®
product declaration K86644/02 Page 11 of 12
DSPA Non-Pressurized Condensed Aerosol Generators and Components
Product specifications
Table 1
Fire
Class
Listing According
CEN/TR 15276-1
Pre burn
time
Soak
period
Test room Density
EN2 Material / fuel in
seconds
in
seconds
in m3 in grams per m3
A Polymethylmethacrylate A.6.3 210 600 112.12 97
A Polypropylene A.6.3 210 600 112.12 58
A ABS A.6.3 210 600 112.12 87
A Reformed wood (chops) A.6.4 360 600 112.12 29
A MDF A.6.4 360 600 112.12 59
A Multilayers plywood A.6.4 360 600 112.12 87
B Heptane A.6.2 30 30 112.12 34
Table 2
Type Efficiency in %
DSPA 11-1 100
DSPA 11-2 88 - 100
DSPA 11-3 90 - 100
DSPA 11-4 100
DSPA 11-5 94 - 100
DSPA 11-6 100
DSPA 11-7 100
DSPA 8-1 100
Table 3
Type Housing
Type and
Discharge
method
Agent distribution according CEN/TR 15276-1 and ISO 15779
Minimum height /
Maximum area coverage (in m)
Maximum height /
Maximum area coverage (in m)
DSPA 11-1 Disk, radial 0.5 3.66 x 1.22 1.83 1.22 x 1.22
DSPA 11-2 Disk, radial 0.5 3.66 x 2.44 2.44 1.22 x 1.22
DSPA 11-3 Disk, radial 0.5 3.66 x 2.44 2.44 1.22 x 1.22
DSPA 11-4 Disk, radial 1.22 3.66 x 3.66 3.05 1.83 x 1.83
DSPA 11-5 Disk, radial 1.22 4.88 x 3.66 3.66 2.44 x 2.44
DSPA 11-6 Disk, radial 1.22 7.32 x 3.66 3.66 2.44 x 2.44
DSPA 11-7 Disk, axial 1.22 7.32 x 1.22 3.05 1.83 x 1.83
DSPA 8-1 Cylinder, axial 2.44 9.76 x 3.66 4.88 4.88 x 3.66
Kiwa®
product declaration K86644/02 Page 12 of 12
DSPA Non-Pressurized Condensed Aerosol Generators and Components Table 4
Type Discharge time
In Sec
DSPA 11-1 6 - 10
DSPA 11-2 9 - 15
DSPA 11-3 14 - 26
DSPA 11-4 19 - 31
DSPA 11-5 40 - 60
DSPA 11-6 30 - 50
DSPA 11-7 30 - 50
DSPA 8-1 67 - 89
Table 5
Type Distance in m
75°C 200°C 400°C
DSPA 11-1 0.5 0.15 0.05
DSPA 11-2 0.5 0.15 0.05
DSPA 11-3 0.5 0.15 0.05
DSPA 11-4 1.0 0.25 0.15
DSPA 11-5 1.0 0.25 0.15
DSPA 11-6 1.5 0.35 0.15
DSPA 11-7 1.5 0.50 0.10
DSPA 8-1 1.5 0.75 0.15