Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
1
2015 SIGNIFICANT CHANGES TO RESIDENTIAL CODES WITH WASHINGTON AMENDMENTSPRESENTED BY: Building Industry Association of Washington
Effective Date• New codes become effective July 1, 2016– Permit obtained up to June 30, 2016, structures are built using today’s (2012) codes;– Permit obtained on or after July 1, 2016, structures are built using the new (2015) set of adopted codes.
2015 Washington StateEnergy Code
Based on the 2015 InternationalEnergy Conservation Code® (IECC®)
Special thanks to the staff of the WSUEnergy Program for their assistanceand providing graphics in this section
www.energy.wsu.edu
Mandate: Reduce building energy consumption 70 percent over 25 years. • The Washington state legislature and the Governor’s Office
have directed the State Building Code Council to adopt energy codes to reduce energy use in newly constructed residential and nonresidential buildings.
• Federal Law also requires the state to meet minimum energy savings standards.
• Building energy efficiency is the single largest factor in the region’s future electric needs.
• Reduction of 70% by 2030 as compared to the 2006 Washington State Energy Code
• R104.2 Inspections– Revised to list and describe the required insulation inspections as:• Footing and Foundation inspection• Framing and Rough-‐in inspection• Wall inspection• Plumbing Rough-‐in inspection• Mechanical Rough-‐in inspection
– Final inspection shall include verification of the installation of all required building systems, equipment and controls and their proper operation and required number of high efficacy lamps and fixtures
R401.2 Tools for Compliance • Prescriptive• Total UA Alternative – WSU form *• Performance Approach – as required in R405
Check WSU’s Energy Code webpage for compliance tool information as it becomes available: www.energy.wsu.edu/code
NOTE: Energy Rating Index (ERI/HERS Index) is not an approved compliance path in WA state.
*REScheck no longer available in WA State
• R401.3 Certificate (IECC change) Editorial changes for clarity, allows more flexibility in the placement of the certificate.– A wall in the space where the furnace is located, a utility room, or an approved location inside the building. (was within 3 feet of the electrical panel)
NOTE: No change to required content for compliance certificate
• R402.4.4 Combustion air (IECC) new sectionrequires:–Mechanical rooms with outside combustion air ducts providing combustion air to open combustion shall be located outside of the building thermal envelope or enclosed in a room isolated from inside the thermal envelope.
– Two exceptions: (1) direct vent appliances with both intake and exhaust pipes installed continuous to the outside and (2) fireplaces and stoves complying with the IECC and Section R1006 of the IRC.
• R402.4.1.2 Air Leakage Testing (State amendment) No change to minimum requirement of 5 Air Changes Per Hour (ACH) EXCEPTIONS:1. Additions less than 500 square feet of
conditioned floor area.2. Additions tested with the existing home having a
combined maximum air leakage rate of 7 ACH. To qualify for this exception, the date of construction of the existing home must be prior to the 2009 WSEC.
• Ducts outside the building thermal envelope shall be insulated to a minimum of R-‐8 (same).
• Ducts within a concrete slab or in the ground shall be insulated to R-‐10 with insulation designed to be used below grade. (was R-‐8).
R403.3.1 Insulation (Prescriptive) (State amendment)
2012 Duct Testing 2015 Duct Leak/Test
R101.3.2.1 Duct Testing R403.3 Duct Leakage
No test required if ducts and air handler are entirely in conditioned space
No Change
The test results shall be provided to the building official and the homeowner
A written report of the results shall be signed by the party conducting the test and provided to the code official.
• R403.5.3 Hot water pipe insulation (Prescriptive) Insulation for hot water pipe, both within and outside the conditioned space, shall have a minimum thermal resistance of R-‐3.– Exception: Pipe insulation is permitted to be discontinuous where it passes through studs, joists or other structural members and where the insulated pipes pass other piping, conduit or vents, provided the insulation is installed tight to each obstruction.
• R403.7.1 Electric resistance zone heated units (State amendment) All detached one-‐ and two-‐family dwellings and multiple single-‐family dwellings (townhouses) up to three stories in height above grade plane using electric zonal heating as the primary heat source shall install an inverter-‐driven ductless mini-‐split heat pump in the largest zone in the dwelling. Building permit drawings shall specify the heating equipment type and location of the heating system.– Exception: Total installed heating capacity of 2 kW per dwelling unit or less.
NOTE: 1.0 Credit allowed for this option under Section R406 3d still applies.
• R405.3 Performance Based Compliance (State amendment) Changes to simulated energy performance requirements per square foot of conditioned floor area:
1. Less than 1500 sq. ft. from (97) to 80 percent2. 1500 to 5000 sq. ft. from (89) to 72 percent3. Over 5,000 sq. ft. from (83) to 66 percent
Exception: For structures serving Group R-‐2 occupancies, the annual energy consumption shall be less than or equal to 85 percent of the annual energy consumption of the standard reference design.
• Section 5 Existing Buildings (IECC change). All requirements for existing buildings were consolidated and moved into a new section (Section 5) and broken out into Additions, Alterations, Repairs and Change of Use. Historic Buildings are no longer exempt.
• R406 Additional Energy Efficiency Requirements. Mandatory (State amendment) Section was expanded to include all low-‐rise residential dwelling and sleeping units, not just IRC buildings, and increase number of credits required for each dwelling type.
1. Small dwelling unit less than 1500 sq. ft. in conditioned floor area with less than 300 sq. ft of fenestration area. Additions to buildings that are greater than 500 sq. ft. of heated floor area but less than 1500 sq. ft (.5) 1.5 credits
2. Medium dwelling unit that are not included in #1 or #3. (1.5) 3.5 credits
Exception: Dwelling units serving R-‐2 occupancies shall require 2.5 credits
3. Large dwelling units exceeding 5000 sq. ft. of conditioned floor area (2.5) 4.5 credits
Exception: Dwelling units serving R-‐2 occupancies shall require 2.5 credits
4. Additions less than 500 sq. ft. .5 credits
These are informative and not part of the code unless specifically referenced in the adoptive ordinance.
Appendix RA – Recommended procedure for worst-‐case testing of atmospheric venting systems under R402.4 or R405 conditions
Appendix RB – RB – Solar-‐ready provisions – detached one-‐and two-‐family dwellings, multiple single family dwellings (townhouses)
Appendix RD – Exterior Design Conditions, Table C-‐1 Outdoor Design Temperatures
Chapters 1 and 2ADMINISTRATION R101.2 Scope – Accessory
Structures
• Maximum height from 2 to 3 stories
• Technical requirements removed from definition
• Removes square footage limitations
R104.11 Alternative Materials, Design and Methods of Construction and EquipmentBuilding Official continues to have authority to approve equivalent alternatives.Building Official must give written explanation of disapprovals
R301.2.1.1.1 Sunrooms
Comply with AAMA/NPEA/NSA 2100-‐125 Categories
Habitable and non-‐habitable
Conditioned and unconditioned
R302.2 Townhouse Separation
• 2015 Code: R302.2 Townhouses. Each townhouse shall be considered a separate building and shall be separated by fire resistance rated wall assemblies meeting the requirements of Section R302.1 for exterior walls. Common walls separating townhouses shall be assigned a fire resistance rating in accordance with Section R302.2 Item 1 or Item 2.
• R302.2 Common walls separating townhouses must be rated for 2 hours without a sprinkler system and 1 hour with a fire sprinkler
To accommodate the tiny house industry, the 120 square foot minimum habitable area requirement has been deleted
R304.1 Minimum Habitable Room Area
R311.4, 311.7.11, R311.7.12 Alternating Tread Devices and Ship Ladders• Added to the stair provisions
• Washington Amendment allows for use as a means of egress within an individual dwelling unit for access to areas of 200 sq. ft or less.
R312.1.2 Guard Height
• Deletes provision for measuring guard height from surface of adjacent fixed seating
• Measure from Deck Floor, not fixed seating height (IRC Only)
R314 Smoke Alarms• R314.3 Added Location: Not less than 3ft horizontally from door of a bathroom
• R314.3.1 Minimum distance from cooking appliances
Type of Alarm Separation
Ionization 20 Ft
Ionization with alarm-‐silencing switch
10 ft
Photoelectric 6 ft
R315 Carbon Monoxide Alarm Additions
• CO alarm in bedroom when a fuel-‐fired appliance is in the bedroom or adjoining bathroom
• Requires one alarm on each level
R315 Carbon Monoxide Alarms (continued)
• Power supplied by house wiring with battery backup
• Battery-‐operated permitted for alterations, repairs, and additions to existing buildings
• Exterior work no longer triggers CO alarm provisions for existing buildings (decks)
• CO detection systems only require detectors in locations prescribed by the code (NOT NFPA 720)
R326 Swimming Pools, Spas and Hot Tubs
• The design and construction of pools and spas shall comply with the INTERNATIONAL SWIMMING POOL AND SPA CODE (ISPSC)
• Appendix G Swimming Pools, Spas and Hot Tubs
R403.1 (1) Minimum Footing Size
• Modification divides minimum footing size and thickness into three expanded tables based on the type of construction being supported:– Light-‐frame construction, light frame with veneer and concrete or masonry
– Values based on the type of foundation:• slab on grade• crawl space• basement
Section 5 – All About Decks
• Table for Maximum Joist Spacing• Deck Ledger Connections – reorganized and clarified• Alternative Lateral Load Connection Diagrams• New span tables specific to decks; offers prescriptive guidance• New table for Deck Posts
Table R602.3(1) Fastening Schedule• Provides multiple nail size options• Includes ‘gun nails’• Uses dimensions of commonly used power driven, box and common nail size
NEW SECTION – includes setbacks and building separation due to radiant heat issues• Insulated vinyl siding – continuous
insulation and improved moisture control
• Polypropylene siding requires separation:
• 5 foot lot lines• 10 foot building on other lot• Specific fastening requirements
R703.11 – 703.14 Insulated Vinyl Siding and Polypropylene Siding
Appendix R Light Straw-‐Clay Construction• New Addition to Code• Prescriptive provisions• Light straw-‐clay walls are nonbearing infill around a
structural frame
Appendix S Strawbale Construction• New Addition to Code• Prescriptive provisions for strawbale construction• Strawbale walls may be bearing walls or nonbearing infill
around a structural frame depending upon the method of construction and detailing.
• Appendix S contains requirements for both construction methods.
IRC Appendix “U” Solar-Ready Provisions, approved by the SBCC
– Solar Ready Zone: a section or sections of the roof or building overhang designated and reserved for the future installation of a solar photovoltaic or solar thermal system.
– Not mandatory- available for local adoption.
– Reserves a zone on the roof of a house with solar access for future installation • Area shall be not less than 300 sq ft exclusive of
mandatory access or set back areas as required by the International Fire Code
– Saves homeowner money if they choose solar at a later date
• No re-routing of plumbing vents, chimneys or other obstructions
*Effective July 1, 2016 --- See attachment on Electrical Code Requirements
Emergency Rule – 502 Facilities• Establish regulatory guidance for marijuana processing or
extraction facilities as permitted under Initiative 502.• Emergency Rule provides for construction permit and
operational requirements.• The 2015 code changes related to cannabis growing and
processing are found in both the Building Code and the Fire Code
• Resources and Links from the BIAW website www.biaw.com
• Industry Issues Tab• Select ‘Residential Building Codes and Updates’
• State Building Code Council -‐https://fortress.wa.gov/ga/apps/sbcc
Lead Rule Stakeholder Meetings “Hiatus”
• There will be no changes to the current lead rules in WA State for 6 mos to 2 years. Must continue to comply on Federal and Tribal Job Sites.– Goal is to eliminate BLLs (blood lead levels) in all adults that are higher than 10 μg/dl (micrograms/deciliter). Currently can still be on job site at 50 μg/dl
– Discussion included employee baseline lead level medical exams of certain occupations, increased personal protective gear, employee training requirements, engineering and work practice controls
– Setting 3 levels of “Trigger Tasks” – L&I hiring new FTE
Lead Based Paint• Under the United States Environmental Protection Agency’s Lead-Based Paint
Renovation, Repair, and Painting (RRP) Program. Construction firms must apply for and receive EPA Certification to disturb paint as part of their work in pre-1978 housing and child-occupied facilities.
• Anyone disturbing more than 6 sq. ft. (interior) & 20 sq. ft. (exterior) of lead-based paint must get the training.
• BIAW Education offers Certification and Recertification classes.• THE FINES HURT! Firms who knowingly or willingly violate the RRP
Program requirements could face penalties of up to $10,000 per day, per violation and/or face imprisonment.
• Rulemaking begins: Department of Commerce wants to increase certification fees. First meeting for stakeholders is June 29 1:30-3:30 in Olympia.
Member Question
• If the General Contractor is lead certified doing work in a pre-‐1978 home, do sub-‐contractors need to be lead certified as well?
• No, if the General Contractor did all the demo and cleaned up the site of all lead dust and debris prior to the sub beginning their work, sub does not have to practice lead safe work practices and does not have to be a RRP (Renovation, Repair, and Painting) certified renovator or firm. – DanoSummers, Dept. of Commerce
Crystalline Silica
• No statewide requirement (yet) Federal and Tribal jurisdictions only.
• OSHA issued final rule March 25, 2016– Effective June 23, 2016• Construction Employers have until June 23, 2017 to comply.
The standard applies to all occupational exposures to respirablecrystalline silica in construction work, except where employeeexposures will remain below 25 micrograms per cubic meter ofair (25 μg/m3) as an 8-‐hour time-‐weighted average (TWA) underany foreseeable conditions.
• Examples of tasks with low exposures include; mixing mortar; pouring concrete footers, slab foundation and foundation walls; removing concrete formwork; and finishing drywall.
• Permissible Exposure Limit (PEL)
• Workers must be protected from respirable crystalline silica exposures above the permissible exposure limit of 50 μg/m3 (micrograms of silica per cubic meter of air), averaged over an eight-‐hour day.
Specified Exposure Control Methods (Table 1)
• Employers can either use: 1) a control method in Table 1 of the construction standard; or 2) they can measure workers’ exposure to silica and independently decide which dust controls – if any are required –work best to limit exposures on the jobsite.
Working in Federal and Tribal jurisdictions
• Written exposure control plan• Medical Surveillance• Hazard Communication Plan• Training• Recordkeeping
Fair Labor Standards Act• US Dept of Labor issued a new overtime rule that goes into
effect Dec. 1, 2016. • Where differences exist between WA State and new Federal
overtime regs, an employer must follow the regulation that is most favorable to the worker.
• New rule did not change salary basis or standard duties; did increase salary level criteria. Doubled annual salary level: was $23,660 now $47,476
• Salary threshold will be adjusted every 3 yrs. • Employees will be due time and a half if they make less than
$47,476 and work more than 40 hrs/wk. – $913/wk (up from $455/wk)
• Outside Sales Staff are exempt.
Congressional Action
• Lawmakers have introduced the “Protecting Workplace Advancement and Opportunity Act.” (S. 2707 and H.R. 4773)
• NAHB requests contacting WA State members of Congress and ask for support of these bills.
• Susan Del Bene (1st), Rick Larsen (2nd), Jim McDermott (7th) and Adam Smith (9th)
More information on OSHA’s Final Rule on Crystalline Silica (Construction) can be found at: https://www.osha.gov/silica/If you should have any questions about this OSHA rule or other construction safety issues, please feel free to contact BIAW Codes Coordinator Al Audette at (360) 352-‐7800 or [email protected]
WISHA Safety Plan• All employers in Washington State are required to create a written
Accident Prevention Program (APP).
• To meet written program and other APP requirements, businesses need to do the following:– Look around to identify workplace hazards that could hurt employees.– Find and apply ways to reduce or eliminate hazards.– Provide a detailed safety orientation to employees so they
understand the possible hazards of their particular job and how to work safely.
– The Consultation Section of the Department of Labor and Industries may be called on for assistance at any time. If you would like information or help in setting up your individual program, please feel free to call the toll-‐free number: 1-‐800-‐423-‐7233.
DOSH Penalties Increase as of 9/1/15
• 1st time repeat x2• 2nd time repeat x5• 3rd time repeat x8• 4th time repeat x12• 5th time repeat x15
Jan Rohila [email protected] Services Director
Al Audette [email protected]’t Affairs and Codes Coordinator
Mark Shaffer [email protected] Field Services Director
Building Industry Association of Washington(360)352-‐7800 www.biaw.com
This presentation is not intended as a substitute for the code books referenced and is offered as a resource to recognize significant changes and locate them in the applicable code book. Attendees understand the information provided is made with no express or implied warranty and that Building Industry Association of Washington and its staff accept no liability or responsibility for any errors or omissions in the content or for damages as a result of relying on information contained within this powerpoint presentation.