2010 Rooftop Training Webinair

2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Embed Size (px)

Citation preview

Page 1: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

2010 RooftopTraining Webinair

Page 2: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

High EfficiencyModels / Sizes

Type Carrier Bryant

YAC 48TC 580J 3-12.5 tons

PAC 50TC 558J 3-12.5 tons

PHP 50TCQ 548J 3-8.5 tons

Unit Size Designations Include Quantity of Compressors Indicator

A08 = 1-Compressor, 7.5 tonsD08 = 2-Compressor, 7.5 tons

Page 3: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Ultra High Efficiency Models / Sizes

Type Carrier Bryant

YAC 48HC 581J 3-12.5 tons

PAC 50HC 551J 3-12.5 tons

PHP 50HCQ 549J 3-8.5 tons

Unit Size Designations Include Quantity of Compressors Indicator

A08 = 1-Compressor, 7.5 tonsD08 = 2-Compressor, 7.5 tons

Page 4: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Carrier Model Number Identification (Sample)

48 Gas Ht

50 Elec Ht

TC-High Eff

HC Ultra High Eff

Heat Size

D-LH; E-MH; F-HH

L-Nox LH; M-Nox MH; N-Nox HH

S-SS LH; R-SS MH; T-SS HH, etc.

Refrigerant OptionsA-Std SystemD- 2 comp

Unit Sizes3-10 ton

Smoke Detector Option

Coil Coating Options

IFM Options

Voltage

Factory Revision

Base Unit Controls

0-ElectroMechanical

1-PremierLink

2-RTU-MP Control

Intake/Exhaust Opt

Service Options

Electrical Options

PackagingOptions

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

4 8 T C D A 0 4 A 1 A 5 - 0 A 0 A 0

Page 5: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Bryant Model Number Identification (Sample)

580J High EffGas/Elect

581J Ultra HiGas/Elect

558J High Eff Elect/Elect

548J High Eff Ht Pump

Voltage

Cooling Tons

06 = 5 ton

08=7.5 ton

14=12.5 ton

Ref System/Gas Options

A=Std Ref, Nat Gas Heat

B=Std Ref, Nat Gas Heat, Low NOx

D= 2-stg Comp, Al HX

F=2-stg Comp, SS HX

Heat Level

060=60,000

090=90,000

150=150,000

Coil Coating Options Factory Options

Packaging

Design Rev

Indoor Fan Options

Stg, Clg Coil Options

A=1 stg, Al/Cu-Al-Cu

D=1 stg, E-coat-Al/Cu

G=2 stg, Al/Al-Al/Cu

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

5 8 0 J E 0 6 A 0 7 2 A 1 A 0 A A -

Page 6: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

High Efficiency Models

Puron® (R-410A)

Fixed-Bore Acutrol Metering

Revised Liquid Header Designs

Page 7: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Revised Liquid Header

Original HeaderRevised Coil Design

(Can contain dimples or no dimples)

Page 8: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Rooftop Unit Installation3~12.5 ton SRT

48/50TC; 48/50HC; 48/50TM

580/558J; 581/551J; 580/558F

Page 9: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Outline• Warnings – Caution

Safety Fire Explosion Electrical Shock Refrigerant Cut Hazards

• Pre Planning• Placement/Setting Unit

Curb• Existing• New

Attach duct Lifting/Setting Unit

• Strapping/Top Crate• Unit Placement

Cautions:• Condensate Drain• Through the Pan/Curb

Connections

• Preparing unit for Start-Up Outside Air Hood Flue Hood Gas Piping Condensate Electrical Connections

• Power• Thermostat

• Economizer Assembly Types Hood Assembly Wiring Connection

• 2~10 vdc• 4~20 ma

Page 10: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

• Safety Improper installation, modification, service and

maintenance may cause personal and/or property damage.

Contact qualified installer, servicer or distributor for information or assistance

Wear safety glasses and work gloves.Have quenching cloth and fire extinguisher availableRead all Installation Instructions prior to beginning

workFollow all Local and National building and electrical

codes

Page 11: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

• Fire ExplosionDisconnect gas piping from unit when leak

testing

DO NOT exceed gas pressures greater than 0.5 psig/3450 Pa to gas valve, damage will occur

If pressure testing BELOW 0.5 psig, isolate gas valve from piping using shut-off valve

Page 12: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

• Electrical ShockBefore servicing or maintaining unit, turn off

power supply at disconnect/breaker and install Lock-Out tag

Test for voltage with multi-meter prior to performing service

Some installation may have more than one power source, i.e. dual power wiring and units with heat strips

Page 13: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

• RefrigerantPuron® (R-410A) refrigerant systems operate

at higher pressures than R-22 systems

Do not use R-22 components or service equipment on Puron® systems

POE oil can cause damage to roof of building. If spilled use dry absorbent materials to eliminate spill.

Page 14: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

• Cut HazardsAlways wear gloves, protective clothing and

safety glasses when handling sheet metal components. Failure to do this can result in cuts or abrasions.

Use caution when placing sheet metal components on rubber membrane roofing. Sharp edges can penetrate roofing.

Page 15: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Pre Planning

• Job Survey Consult Local Bldg Codes, NEC (National Electric Code) and

ANSI/NFPA 70 for installation requirements Determine unit location Check for overhead obstructions (for lifting) and proximity to

walls or parapets

• Plan for Unit Location Proper curb/unit support within structure Provide for Minimum Service and Safety clearances Clearances to combustible materials Allow for adequate Combustion and Ventilation

Page 16: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Pre Planning

• Service ClearanceA: 48” Unit disconnect

36” If “B” < 12”18” No disconnect, C/O18” Service 12” Minimum clearance

B: 42” Grounded surface (metal, masonry wall)

36” Non-electrically conductive (wood)

Flue products within 10 ftC: 36” Condensate drain

18”Minimum clearanceD: 48” Flue to combustible material

42” Grounded surface36” Non-electrically conductive

surfacesFresh Air Intakes within 10 ft

Page 17: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Placement/Setting Unit

• Sequence of Installation Install Curb Attached ductwork to curb Install Assy “Through the Pan” fittings Install Assy “Through the Curb” fittings Prepare Condensate drain (Center Drain) Rig and place unit Install Outdoor Air Hood Install Flue hood Install Gas piping Install Condensate drain connections Make Electrical Connections: Power – Control Install other accessories

Page 18: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Placement/Setting Unit• Curb

Installation• Level within tolerances

A-B 0.5”; B-C 1.0”; A-C 1.0”

• Insulate curb• Install cant strips• Install roof felt• Install flashing

Curb Gaskets

Curb Gasket Placements

A

B

C

Page 19: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Placement/Setting Unit• Attach Duct

To roof curb NOT unit (if vertical application) Curb gasket applied over duct flanges Maximum Cabinet Static*

• Lifting/Setting Unit• Use top crate of unit or spreader bars

when lifting.– Carefully lower top crate from roof once unit placed on curb

• Review the maximum weights of the units as listed in the Installation Instructions prior to lifting

* Measured below roof curb 003~014 // 024~150

Return Air w/o Economizer -0.35 in w.c.

Return Air w/ Economizer -0.45 in w.c.

Page 20: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Placement/Setting Unitprior to setting unit

• Cautions:1) Condensate Drain

• If condensate drain will exit unit horizontally proceed to setting unit

• If condensate drain will exit through the pan center drain and through the roof curb, install PVC fitting prior to setting unit.

• If not using center drain outlet, check to ensure outlet plug is installed and tight

2) Through the Pan Connections• Provides capability to draw

power, control wiring and field supplied gas piping

• Install prior to setting unit on curb

3) Through the Curb Connections• Provides capability to run

gas line up “under the curb” then exit “side of curb” to connect to unit

Page 21: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Placement/Setting Unitprior to setting unit

• Through the Pan • Through Curb Gas connection

Center Condensate Drain Hole

Page 22: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

• Unit Placement Existing Curb

• 04 ~07 units– ¼” between side rails

and curb– 0.0” on duct end

between end rail and curb

– Overhang Condenser end ¼”

• 08 ~ 14 units– ¼” between side rails

and curb– 0.0” on duct end

between end rail and curb

– Overhang Condenser end 3 5/16”

– Flush to Curb Label Adaptor Curbs

• Ensure “duct end” of unit is FLUSH to the end of the curb for proper sealing

Placement/Setting Unit04~07 size

08-12 size

Flush to Curb Label onBlower Access Panel

Page 23: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Preparing unit for Start-Up

• Outside Air HoodHood box located

behind filter access panel - Remove

Indoor coil access panel is “Economizer Hood Top” – swing up

Attach hood sides to hood top and attach to unit panel.

Attach hood divider to hood sides

Filter Access Panel

Indoor Coil Access panel

Page 24: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Economizer Assembly

• Types Manual

• Can be used in Vertical/Horizontal configuration

• Adjustable from 0% - 100% Two Position

• Can be used in Vertical/Horizontal configuration

• Adjustable from 25% - 100% Modulating

• Different Vertical/Horizontal• Provides for Minimum and Min

to100% OA capability based on OD conditions

Page 25: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Economizer Assembly

• Wiring Connection• Molex connector

located in R/A section2-10 vdcSingle or

Two-Stage stat4-20 ma

•Used with PremierLink – ComfortLink

•No Economizer Controller mounted

•12 pin Molex Connector•500 Ohm Resistor installed in econo harness

Page 26: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

• Flue Hood Secured to base pan beside

Burner compartment Attach with two screws Clearance to combustibles:

48”

• Flue Deflector (Accessory) CRFLUEDS001A00 2 ~ 12.5 ton units Reduces clearance to

combustibles to 18”

Preparing Unit for Start-Up

Page 27: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

• Gas Piping Local/National Codes

US (NFPA54/ANSI Z223.1 NFGC)CAN (CAN/CSA B149.1 & B149.2)

• Standard gas design Up to 2000’ Convertible up to 6000’

• US: Derate 4% per 1000’ above sea level• CAN: Derate 10% between 2000’ – 4500’

• Gas pressure at GV inlet Nat Gas: Min 4”w.c. - Max 13”w.c. LP Gas: Min 11”w.c. - Max 13”w.c. (req’s Accy Kit) Fitting size: ½” for 03~08 (024-090) units; ¾” 012~014

(120~150) units• Size piping for maximum pressure

drop of 0.5”w.c. between unit GV and gas source• Three Gas Line Approaches

Horizontal to GV (across roof) Thru-Curb (Kit required) Thru-Base Pan (Kit required)

• Always use “Back-Up” wrench on Gas Valve neck (wrench fitting) when connecting piping

Preparing Unit for Start-Up

Through the Curb

Through the Base Pan

Page 28: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

• Condensate Drain ¾” Connection: Two locations

• Horizontal– Exiting out the duct connection end of unit– Piping pitch: 1 inch per 10 ft away from unit – Do not use pipe smaller than ¾”– 4 inch trap recommended– Protect from freezing– Check “Center Drain Plug” for tightness

prior to setting unit on curb

• Center– Exiting below unit from center of

condensate pan– Remove “Center Drain Plug”– Piping pitch: 1 inch per 10 ft away from unit – Do not use pipe smaller than ¾”– 4 inch trap recommended– Protect from freezing (if necessary)

Preparing Unit for Start-Up

Page 29: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

• Electrical Connections Non Powered Convenience Outlet (C/0):

• Requires separate 125 vac 15amp circuit Unit Powered: Incorporates step down transformer

• Convenience Outlet– Connect transformer primary per diagram– Powered (always energized): Connect C/O wires to “Line”

side of disconnect or incoming power, or local codes– De-energized (powered with disconnect): Connect C/O wires

to “Load” side of disconnect, or local codes

• Power: All units except 208/230 vac factory wired for voltage

shown on unit name plate.• 208 vac requires Low Voltage transformer wiring.

Connect black from 230 vac tap on transformer to 208 vac transformer tap.

Units without FIOP Disconnect• Field power wires connect to Compressor Contactor “C”

terminals 11 – 13 and Indoor Fan Contactor Units with FIOP Disconnect

• Remove factory test leads on Line side of Disconnect, discard

• Additional info later

Preparing Unit for Start-Up

Page 30: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

• Field Control WiringThermostat:

• Single or Two Stage

PremierLink• Follow SI wiring

Preparing Unit for Start-Up

RTU-MP (FIOP only)

Page 31: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Microchannel Novation™ Condensing Coils

Page 32: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Outline

• What is Novation™ Condenser Coil

• Cleaning Procedures

• Repair Procedures

• RCD Repair Kit

Page 33: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

What is Novation™ Condenser Coil

• Novation CoilAl/AlConstructionRefrigerant Flow

Page 34: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Cleaning Procedures

• CleaningNo SolventsAir Pressure

Page 35: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Repair Procedures

Page 36: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Repair Procedures (Continued)

Page 37: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Repair Procedures (Continued)

Page 38: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Repair Procedures (Continued)

Page 39: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Repair Procedures (Continued)

Page 40: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Repair Procedures (Continued)

Page 41: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Repair Procedures (Continued)

Page 42: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Repair Procedures (Continued)

Page 43: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Repair Procedures (Continued)

Page 44: 2010 Rooftop Training Webinair. High Efficiency Models / Sizes TypeCarrierBryant YAC48TC580J3-12.5 tons PAC50TC558J3-12.5 tons PHP50TCQ548J3-8.5 tons

Novation™ RCD Repair Kit

• 50TJ660007

• Note: If refrigerant system is open, then replace liquid line drier