14
SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW) Date Revision OWNERS CONSULTANT L&T S&L 31.08.2011 01 EPC CONTRACTOR L&T POWER, VADODARA CONTRACTORS CONSULTANT DCPL, KOLKATA Prepared by VVG EBOP CONTRACTOR AREVA T&D INDIA LIMITED Checked by VVG DOCUMENT NO. 5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 Approved by NAG REFERENCE DRAWING: Document No. Revision Document Name 00 245KV CVT Drawing Name Plate Details INTERCONNECTION CABLE DETAILS FOR 220KV BUS COUPLER (BAY #01) AREVA T&D INDIA Ltd. MADHYA PRADESH POWER GENERATING COMPANY LIMITED 5257PN100-MLW-E-SYD-GAD-1683 00 245KV CVT Drawing Name Plate Details 02 245KV CT Drawing Name Plate Details 02 245KV TARIFF METERING CT Drawing Name Plate Details 00 245KV CT JB TERMINAL DISTRIBUTION 00 245KV CVT JB TERMINAL DISTRIBUTION 02 245KV ISOLATOR Scheme Drawing 02 245KV CIRCUIT BREAKER Scheme Drawing 01 400KV/220KV ICT Scheme Drawing 00 PLCC Drawing (ABB) 02 AC KIOSK Drawing 02 CONTROL ROOM BUILDING PANEL ARRANGEMENT Layout 00 CABLE TRENCH Layout 02 DCDB Drawings 02 ACDB Drawings 5257PN100-MLW-E-SYD-ARR-0010 220KV ANNEXURE-1 5257PN100-MLW-E-SYD-SCH-1586 5257PN100-MLW-E-SYD-SCH-1524 5257PN100-MLW-E-SYD-SCH-3309 5257PN100-MLW-E-SYD-GAD-2501 5257PN100-MLW-E-SYD-CAB-0045 <5257PN100-MLW-E-SYD-SCH-2214> <5257PN100-MLW-E-SYD-SCH-2214> 5257PN100-MLW-E-SYD-GAD-1683 5257PN100-MLW-E-SYD-GAD-1633 220KV ANNEXURE-1 5257PN100-MLW-E-SYD-GAD-1633 LTSSTPP-AREVA-DWG-E-0011 02 ACDB Drawings 01 BMK Drawings 02 220KV CRP SCHEMATICS OF BUS COUPLER PROTECTION PANEL 01 220KV CRP SCHEMATICS OF BUS COUPLER & ICT#01 CONTROL PANEL 02 220KV CRP SCHEMATICS OF BUS BAR PROTECTION 02 220KV CRP SCHEMATICS OF ISLANDING PROTECTION CABLE NUMBERING SYSTEM 2 01 1 001 CABLE SL. NO. STARTING FROM 001 AND INCREMENT SUBSEQUENTLY <5257PN100-MLW-E-SYD-SCH-2103> 5257PN100-MLW-E-SYD-GAD-2396 & SCH-2397 5257PN100-MLW-E-SYD-GAD-2354 & SCH-2355 5257PN100-MLW-E-SYD-GAD-2372 & SCH-2373 5257PN100-MLW-E-SYD-GAD-2370 & SCH-2371 <5257PN100-MLW-E-SYD-SCH-2214> THIS FIELD WILL BE SELECTED ON FOLLOWING CONDITIONS: 1 FOR CABLES WITHIN SWYD EQUIPMENTS. 2 FOR CABLES FROM SWYD EQPT/BMK/JB TO CONTROL & RELAY PANEL 3 FOR CABLES WITHIN CONTROL AND RELAY PANLES 4 AC/DC POWER CABLE FOR CRP/PLCC/RTCC. BAY NUMBER (01) SWITCHYARD 7 FOR 765KV SWYD 4 FOR 400KV SWYD 2 FOR 220KV SWYD Note : 1 FOR 132/110KV SWYD a) Loop length after glanding shall be sum of width & height of panel/Equipment cubicle. 6 FOR 66KV SWYD b) Drum details/actual length shall be filled prior to cable laying at site 3 FOR 33KV SWYD c) Drum cutting schedule to be prepared by site Engineer prior to cable laying/cutting. 9 FOR 11KV SWYD 5 FOR AUX.SYSTEM 1 OF 18

201-BUS COUPLER_05.09

Embed Size (px)

Citation preview

Page 1: 201-BUS COUPLER_05.09

PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW) Date Revision

OWNERS CONSULTANT L&T S&L 31.08.2011 01

EPC CONTRACTOR L&T POWER, VADODARA

CONTRACTORS CONSULTANT DCPL, KOLKATA Prepared by VVG

EBOP CONTRACTOR AREVA T&D INDIA LIMITED Checked by VVG

DOCUMENT NO. 5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 Approved by NAG

REFERENCE DRAWING:

Document No. Revision Document Name

00 245KV CVT Drawing Name Plate Details

INTERCONNECTION CABLE DETAILS FOR

220KV BUS COUPLER (BAY #01)

AREVA T&D INDIA Ltd.

MADHYA PRADESH POWER

GENERATING COMPANY LIMITED

5257PN100-MLW-E-SYD-GAD-1683 00 245KV CVT Drawing Name Plate Details

02 245KV CT Drawing Name Plate Details

02 245KV TARIFF METERING CT Drawing Name Plate Details

00 245KV CT JB TERMINAL DISTRIBUTION

00 245KV CVT JB TERMINAL DISTRIBUTION

02 245KV ISOLATOR Scheme Drawing

02 245KV CIRCUIT BREAKER Scheme Drawing

01 400KV/220KV ICT Scheme Drawing

00 PLCC Drawing (ABB)

02 AC KIOSK Drawing

02 CONTROL ROOM BUILDING PANEL ARRANGEMENT Layout

00 CABLE TRENCH Layout

02 DCDB Drawings

02 ACDB Drawings

5257PN100-MLW-E-SYD-ARR-0010

220KV ANNEXURE-1

5257PN100-MLW-E-SYD-SCH-1586

5257PN100-MLW-E-SYD-SCH-1524

5257PN100-MLW-E-SYD-SCH-3309

5257PN100-MLW-E-SYD-GAD-2501

5257PN100-MLW-E-SYD-CAB-0045

<5257PN100-MLW-E-SYD-SCH-2214>

<5257PN100-MLW-E-SYD-SCH-2214>

5257PN100-MLW-E-SYD-GAD-1683

5257PN100-MLW-E-SYD-GAD-1633

220KV ANNEXURE-1

5257PN100-MLW-E-SYD-GAD-1633

LTSSTPP-AREVA-DWG-E-0011

02 ACDB Drawings

01 BMK Drawings

02 220KV CRP SCHEMATICS OF BUS COUPLER PROTECTION PANEL

01 220KV CRP SCHEMATICS OF BUS COUPLER & ICT#01 CONTROL PANEL

02 220KV CRP SCHEMATICS OF BUS BAR PROTECTION

02 220KV CRP SCHEMATICS OF ISLANDING PROTECTION

CABLE NUMBERING SYSTEM

2 01 1 001

CABLE SL. NO. STARTING FROM 001

AND INCREMENT SUBSEQUENTLY

<5257PN100-MLW-E-SYD-SCH-2103>

5257PN100-MLW-E-SYD-GAD-2396 & SCH-2397

5257PN100-MLW-E-SYD-GAD-2354 & SCH-2355

5257PN100-MLW-E-SYD-GAD-2372 & SCH-2373

5257PN100-MLW-E-SYD-GAD-2370 & SCH-2371

<5257PN100-MLW-E-SYD-SCH-2214>

AND INCREMENT SUBSEQUENTLY

THIS FIELD WILL BE SELECTED ON FOLLOWING CONDITIONS:

1 FOR CABLES WITHIN SWYD EQUIPMENTS.

2 FOR CABLES FROM SWYD EQPT/BMK/JB TO CONTROL & RELAY PANEL

3 FOR CABLES WITHIN CONTROL AND RELAY PANLES

4 AC/DC POWER CABLE FOR CRP/PLCC/RTCC.

BAY NUMBER (01)

SWITCHYARD

7 FOR 765KV SWYD

4 FOR 400KV SWYD

2 FOR 220KV SWYD

Note : 1 FOR 132/110KV SWYD

a) Loop length after glanding shall be sum of width & height of panel/Equipment cubicle. 6 FOR 66KV SWYD a) Loop length after glanding shall be sum of width & height of panel/Equipment cubicle. 6 FOR 66KV SWYD

b) Drum details/actual length shall be filled prior to cable laying at site 3 FOR 33KV SWYD

c) Drum cutting schedule to be prepared by site Engineer prior to cable laying/cutting. 9 FOR 11KV SWYD

5 FOR AUX.SYSTEM

1 OF 18

Page 2: 201-BUS COUPLER_05.09

VVG

PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW) Date Revision

OWNERS CONSULTANTL&T S&L 31.08.2011 01

EPC CONTRACTORL&T POWER, VADODARA VVG

CONTRACTORS CONSULTANTDCPL, KOLKATA

EBOP CONTRACTORAREVA T&D INDIA LIMITED

DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG

ACTUAL DRUM APPLICATION REF. DRAWING. NO :

FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.

CABLES WITHIN SWITCHYARD

CT -- CT--

1 2 01 1001 2-1 CTA-R 2-1 CTA JB 10CX2.5 1 15 1,2 R1S1 TB1-1 2-1 CTA JB-TB1-1 / R1S1 2-1 CTA-R-R1S1 / TB1-1 CORE-1 CPD KN17 SC51 SHT02

3.4 R1S2 TB1-2 2-1 CTA JB-TB1-2 / R1S2 2-1 CTA-R-R1S2 / TB1-2 CPD KN17 SC51 SHT02

5,6 R1S3 TB1-3 2-1 CTA JB-TB1-3 / R1S3 2-1 CTA-R-R1S3 / TB1-3 CPD KN17 SC51 SHT02

7,8 R1S4 TB1-4 2-1 CTA JB-TB1-4 / R1S4 2-1 CTA-R-R1S4 / TB1-4 CPD KN17 SC51 SHT02

9,10 SPARE

AREVA T&D INDIA LTD.

NO. OF

RUNSSIZE

CABLE NO. EQUIPMENT DESIGNATION ESTIMATED

LENGTH

INTERCONNECTION DETAILSSL.

NO

Prepared by

ROUTING DETAILS

Approved by

Ferrule Nos.

Checked by

INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)

9,10 SPARE

2 2 01 1002 2-1 CTA-R 2-1 CTA JB 10CX2.5 1 15 1,2 R2S1 TB2-1 2-1 CTA JB-TB2-1 / R2S1 2-1 CTA-R-R2S1 / TB2-1 CORE-2 CPD KN17 SC51 SHT02

3.4 R2S2 TB2-2 2-1 CTA JB-TB2-2 / R2S2 2-1 CTA-R-R2S2 / TB2-2 CPD KN17 SC51 SHT02

5,6 R2S3 TB2-3 2-1 CTA JB-TB2-3 / R2S3 2-1 CTA-R-R2S3 / TB2-3 CPD KN17 SC51 SHT02

7,8 R2S4 TB2-4 2-1 CTA JB-TB2-4 / R2S4 2-1 CTA-R-R2S4 / TB2-4 CPD KN17 SC51 SHT02

9,10 SPARE

3 2 01 1003 2-1 CTA-R 2-1 CTA JB 10CX2.5 1 15 1,2 R3S1 TB3-1 2-1 CTA JB-TB3-1 / R3S1 2-1 CTA-R-R3S1 / TB3-1 CORE-3 CPD KN17 SC51 SHT02

3.4 R3S2 TB3-2 2-1 CTA JB-TB3-2 / R3S2 2-1 CTA-R-R3S2 / TB3-2 CPD KN17 SC51 SHT02

5,6 R3S3 TB3-3 2-1 CTA JB-TB3-3 / R3S3 2-1 CTA-R-R3S3 / TB3-3 CPD KN17 SC51 SHT02

7,8 R3S4 TB3-4 2-1 CTA JB-TB3-4 / R3S4 2-1 CTA-R-R3S4 / TB3-4 CPD KN17 SC51 SHT02

9,10 SPARE

4 2 01 1004 2-1 CTA-R 2-1 CTA JB 10CX2.5 1 15 1,2 R4S1 TB4-1 2-1 CTA JB-TB4-1 / R4S1 2-1 CTA-R-R4S1 / TB4-1 CORE-4 CPD KN17 SC51 SHT02

3.4 R4S2 TB4-2 2-1 CTA JB-TB4-2 / R4S2 2-1 CTA-R-R4S2 / TB4-2 CPD KN17 SC51 SHT02

5,6 R4S4 TB4-3 2-1 CTA JB-TB4-3 / R4S4 2-1 CTA-R-R4S4 / TB4-3 CPD KN17 SC51 SHT02

7,8 R4S4 TB4-4 2-1 CTA JB-TB4-4 / R4S4 2-1 CTA-R-R4S4 / TB4-4 CPD KN17 SC51 SHT02

9,10 SPARE

5 2 01 1005 2-1 CTA-R 2-1 CTA JB 10CX2.5 1 15 1,2 R5S1 TB5-1 2-1 CTA JB-TB5-1 / R5S1 2-1 CTA-R-R5S1 / TB5-1 CORE-5 CPD KN17 SC51 SHT02

3.4 R5S2 TB5-2 2-1 CTA JB-TB5-2 / R5S2 2-1 CTA-R-R5S2 / TB5-2 CPD KN17 SC51 SHT02

5,6 R5S5 TB5-3 2-1 CTA JB-TB5-3 / R5S5 2-1 CTA-R-R5S5 / TB5-3 CPD KN17 SC51 SHT025,6 R5S5 TB5-3 2-1 CTA JB-TB5-3 / R5S5 2-1 CTA-R-R5S5 / TB5-3 CPD KN17 SC51 SHT02

7,8 R5S5 TB5-4 2-1 CTA JB-TB5-4 / R5S5 2-1 CTA-R-R5S5 / TB5-4 CPD KN17 SC51 SHT02

9,10 SPARE

6 2 01 1006 2-1 CTA-Y 2-1 CTA JB 10CX2.5 1 10 1,2 Y1S1 TB1-5 2-1 CTA JB-TB1-5 / Y1S1 2-1 CTA-Y-Y1S1 / TB1-5 CORE-1 CPD KN17 SC51 SHT02

3.4 Y1S2 TB1-6 2-1 CTA JB-TB1-6 / Y1S2 2-1 CTA-Y-Y1S2 / TB1-6 CPD KN17 SC51 SHT02

5,6 Y1S3 TB1-7 2-1 CTA JB-TB1-7 / Y1S3 2-1 CTA-Y-Y1S3 / TB1-7 CPD KN17 SC51 SHT02

7,8 Y1S4 TB1-8 2-1 CTA JB-TB1-8 / Y1S4 2-1 CTA-Y-Y1S4 / TB1-8 CPD KN17 SC51 SHT02

9,10 SPARE

7 2 01 1007 2-1 CTA-Y 2-1 CTA JB 10CX2.5 1 10 1,2 Y2S1 TB2-5 2-1 CTA JB-TB2-5 / Y2S1 2-1 CTA-Y-Y2S1 / TB2-5 CORE-2 CPD KN17 SC51 SHT02

3.4 Y2S2 TB2-6 2-1 CTA JB-TB2-6 / Y2S2 2-1 CTA-Y-Y2S2 / TB2-6 CPD KN17 SC51 SHT02

5,6 Y2S3 TB2-7 2-1 CTA JB-TB2-7 / Y2S3 2-1 CTA-Y-Y2S3 / TB2-7 CPD KN17 SC51 SHT02

7,8 Y2S4 TB2-8 2-1 CTA JB-TB2-8 / Y2S4 2-1 CTA-Y-Y2S4 / TB2-8 CPD KN17 SC51 SHT02

9,10 SPARE

8 2 01 1008 2-1 CTA-Y 2-1 CTA JB 10CX2.5 1 10 1,2 Y3S1 TB3-5 2-1 CTA JB-TB3-5 / Y3S1 2-1 CTA-Y-Y3S1 / TB3-5 CORE-3 CPD KN17 SC51 SHT02

3.4 Y3S2 TB3-6 2-1 CTA JB-TB3-6 / Y3S2 2-1 CTA-Y-Y3S2 / TB3-6 CPD KN17 SC51 SHT02

5,6 Y3S3 TB3-7 2-1 CTA JB-TB3-7 / Y3S3 2-1 CTA-Y-Y3S3 / TB3-7 CPD KN17 SC51 SHT02

7,8 Y3S4 TB3-8 2-1 CTA JB-TB3-8 / Y3S4 2-1 CTA-Y-Y3S4 / TB3-8 CPD KN17 SC51 SHT02

9,10 SPARE

9 2 01 1009 2-1 CTA-Y 2-1 CTA JB 10CX2.5 1 10 1,2 Y4S1 TB4-5 2-1 CTA JB-TB4-5 / Y4S1 2-1 CTA-Y-Y4S1 / TB4-5 CORE-4 CPD KN17 SC51 SHT02

3.4 Y4S2 TB4-6 2-1 CTA JB-TB4-6 / Y4S2 2-1 CTA-Y-Y4S2 / TB4-6 CPD KN17 SC51 SHT02

5,6 Y4S3 TB4-7 2-1 CTA JB-TB4-7 / Y4S3 2-1 CTA-Y-Y4S3 / TB4-7 CPD KN17 SC51 SHT02

7,8 Y4S4 TB4-8 2-1 CTA JB-TB4-8 / Y4S4 2-1 CTA-Y-Y4S4 / TB4-8 CPD KN17 SC51 SHT02

9,10 SPARE

10 2 01 1010 2-1 CTA-Y 2-1 CTA JB 10CX2.5 1 10 1,2 Y5S1 TB5-5 2-1 CTA JB-TB5-5 / Y5S1 2-1 CTA-Y-Y5S1 / TB5-5 CORE-5 CPD KN17 SC51 SHT02

3.4 Y5S2 TB5-6 2-1 CTA JB-TB5-6 / Y5S2 2-1 CTA-Y-Y5S2 / TB5-6 CPD KN17 SC51 SHT02

5,6 Y5S3 TB5-7 2-1 CTA JB-TB5-7 / Y5S3 2-1 CTA-Y-Y5S3 / TB5-7 CPD KN17 SC51 SHT02

7,8 Y5S4 TB5-8 2-1 CTA JB-TB5-8 / Y5S4 2-1 CTA-Y-Y5S4 / TB5-8 CPD KN17 SC51 SHT02

9,10 SPARE

11 2 01 1011 2-1 CTA-B 2-1 CTA JB 10CX2.5 1 15 1,2 B1S1 TB1-9 2-1 CTA JB-TB1-9 / B1S1 2-1 CTA-B-B1S1 / TB1-9 CORE-1 CPD KN17 SC51 SHT02

3.4 B1S2 TB1-10 2-1 CTA JB-TB1-10 / B1S2 2-1 CTA-B-B1S2 / TB1-10 CPD KN17 SC51 SHT02

5,6 B1S3 TB1-11 2-1 CTA JB-TB1-11 / B1S3 2-1 CTA-B-B1S3 / TB1-11 CPD KN17 SC51 SHT02

7,8 B1S4 TB1-12 2-1 CTA JB-TB1-12 / B1S4 2-1 CTA-B-B1S4 / TB1-12 CPD KN17 SC51 SHT02

9,10 SPARE

12 2 01 1012 2-1 CTA-B 2-1 CTA JB 10CX2.5 1 15 1,2 B2S1 TB2-9 2-1 CTA JB-TB2-9 / B2S1 2-1 CTA-B-B2S1 / TB2-9 CORE-2 CPD KN17 SC51 SHT02

3.4 B2S2 TB2-10 2-1 CTA JB-TB2-10 / B2S2 2-1 CTA-B-B2S2 / TB2-10 CPD KN17 SC51 SHT02

5,6 B2S3 TB2-11 2-1 CTA JB-TB2-11 / B2S3 2-1 CTA-B-B2S3 / TB2-11 CPD KN17 SC51 SHT02

7,8 B2S4 TB2-12 2-1 CTA JB-TB2-12 / B2S4 2-1 CTA-B-B2S4 / TB2-12 CPD KN17 SC51 SHT027,8 B2S4 TB2-12 2-1 CTA JB-TB2-12 / B2S4 2-1 CTA-B-B2S4 / TB2-12 CPD KN17 SC51 SHT02

9,10 SPARE

201-BUS COUPLER_05.09.2011 Page 2 of 18 Cables within SWYD

Page 3: 201-BUS COUPLER_05.09

VVG

PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW) Date Revision

OWNERS CONSULTANTL&T S&L 31.08.2011 01

EPC CONTRACTORL&T POWER, VADODARA VVG

CONTRACTORS CONSULTANTDCPL, KOLKATA

EBOP CONTRACTORAREVA T&D INDIA LIMITED

DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG

ACTUAL DRUM APPLICATION REF. DRAWING. NO :

FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.

CABLES WITHIN SWITCHYARD

AREVA T&D INDIA LTD.

NO. OF

RUNSSIZE

CABLE NO. EQUIPMENT DESIGNATION ESTIMATED

LENGTH

INTERCONNECTION DETAILSSL.

NO

Prepared by

ROUTING DETAILS

Approved by

Ferrule Nos.

Checked by

INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)

13 2 01 1013 2-1 CTA-B 2-1 CTA JB 10CX2.5 1 15 1,2 B3S1 TB3-9 2-1 CTA JB-TB3-9 / B3S1 2-1 CTA-B-B3S1 / TB3-9 CORE-3 CPD KN17 SC51 SHT02

3.4 B3S2 TB3-10 2-1 CTA JB-TB3-10 / B3S2 2-1 CTA-B-B3S2 / TB3-10 CPD KN17 SC51 SHT02

5,6 B3S3 TB3-11 2-1 CTA JB-TB3-11 / B3S3 2-1 CTA-B-B3S3 / TB3-11 CPD KN17 SC51 SHT02

7,8 B3S4 TB3-12 2-1 CTA JB-TB3-12 / B3S4 2-1 CTA-B-B3S4 / TB3-12 CPD KN17 SC51 SHT02

9,10 SPARE

14 2 01 1014 2-1 CTA-B 2-1 CTA JB 10CX2.5 1 15 1,2 B4S1 TB4-9 2-1 CTA JB-TB4-9 / B4S1 2-1 CTA-B-B4S1 / TB4-9 CORE-4 CPD KN17 SC51 SHT02

3.4 B4S2 TB4-10 2-1 CTA JB-TB4-10 / B4S2 2-1 CTA-B-B4S2 / TB4-10 CPD KN17 SC51 SHT02

5,6 B4S3 TB4-11 2-1 CTA JB-TB4-11 / B4S3 2-1 CTA-B-B4S3 / TB4-11 CPD KN17 SC51 SHT02

7,8 B4S4 TB4-12 2-1 CTA JB-TB4-12 / B4S4 2-1 CTA-B-B4S4 / TB4-12 CPD KN17 SC51 SHT02

9,10 SPARE

15 2 01 1015 2-1 CTA-B 2-1 CTA JB 10CX2.5 1 15 1,2 B5S1 TB5-9 2-1 CTA JB-TB5-9 / B5S1 2-1 CTA-B-B5S1 / TB5-9 CORE-5 CPD KN17 SC51 SHT02

3.4 B5S2 TB5-10 2-1 CTA JB-TB5-10 / B5S2 2-1 CTA-B-B5S2 / TB5-10 CPD KN17 SC51 SHT02

5,6 B5S3 TB5-11 2-1 CTA JB-TB5-11 / B5S3 2-1 CTA-B-B5S3 / TB5-11 CPD KN17 SC51 SHT02

7,8 B5S4 TB5-12 2-1 CTA JB-TB5-12 / B5S4 2-1 CTA-B-B5S4 / TB5-12 CPD KN17 SC51 SHT02

9,10 SPARE

BCVT

16 2 01 1016 2- B1CVT-R 2-1 CVT JB 7CX2.5 1 15 1,2 R1a1 TB1-1 2-1 CVT JB-TB1-1 / R1a1 2- B1CVT-R-R1a1 / TB1-1 WDG-1 CPD KN17 SC51 SHT07

3,4 SPARE CPD KN17 SC51 SHT07

5,6 R1n TB1-3 2-1 CVT JB-TB1-3 / R1n 2- B1CVT-R-R1n / TB1-3 CPD KN17 SC51 SHT07

7 SPARE

17 2 01 1017 2- B1CVT-R 2-1 CVT JB 7CX2.5 1 15 1,2 R2a1 TB2-1 2-1 CVT JB-TB2-1 / R2a1 2- B1CVT-R-R2a1 / TB2-1 WDG-2 CPD KN17 SC51 SHT07

3,4 SPARE CPD KN17 SC51 SHT07

5,6 R2n TB2-3 2-1 CVT JB-TB2-3 / R2n 2- B1CVT-R-R2n / TB2-3 CPD KN17 SC51 SHT07

7 SPARE

18 2 01 1018 2- B1CVT-R 2-1 CVT JB 7CX2.5 1 15 1,2 R3a1 TB3-1 2-1 CVT JB-TB3-1 / R3a1 2- B1CVT-R-R3a1 / TB3-1 WDG-3 CPD KN17 SC51 SHT07

3,4 SPARE CPD KN17 SC51 SHT07

5,6 R3n TB3-3 2-1 CVT JB-TB3-3 / R3n 2- B1CVT-R-R3n / TB3-3 CPD KN17 SC51 SHT07

7 SPARE

19 2 01 1019 2- B1CVT-R 2-1 CVT JB 7CX2.5 1 15 1,2 R4a1 TB4-1 2-1 CVT JB-TB4-1 / R4a1 2- B1CVT-R-R4a1 / TB4-1 WDG-4 CPD KN17 SC51 SHT07

3,4 SPARE CPD KN17 SC51 SHT07

5,6 R4n TB4-3 2-1 CVT JB-TB4-3 / R4n 2- B1CVT-R-R4n / TB4-3 CPD KN17 SC51 SHT07

7 SPARE

20 2 01 1020 2- B1CVT-Y 2-1 CVT JB 7CX2.5 1 10 1,2 Y1a1 TB1-4 2-1 CVT JB-TB1-4 / Y1a1 2- B1CVT-Y-Y1a1 / TB1-4 WDG-1 CPD KN17 SC51 SHT07

3,4 SPARE CPD KN17 SC51 SHT07

5,6 Y1n TB1-6 2-1 CVT JB-TB1-6 / Y1n 2- B1CVT-Y-Y1n / TB1-6 CPD KN17 SC51 SHT07

7 SPARE

21 2 01 1021 2- B1CVT-Y 2-1 CVT JB 7CX2.5 1 10 1,2 Y2a1 TB2-4 2-1 CVT JB-TB2-4 / Y2a1 2- B1CVT-Y-Y2a1 / TB2-4 WDG-2 CPD KN17 SC51 SHT07

3,4 SPARE CPD KN17 SC51 SHT07

5,6 Y2n TB2-6 2-1 CVT JB-TB2-6 / Y2n 2- B1CVT-Y-Y2n / TB2-6 CPD KN17 SC51 SHT07

7 SPARE

22 2 01 1022 2- B1CVT-Y 2-1 CVT JB 7CX2.5 1 10 1,2 Y3a1 TB3-4 2-1 CVT JB-TB3-4 / Y3a1 2- B1CVT-Y-Y3a1 / TB3-4 WDG-3 CPD KN17 SC51 SHT0722 2 01 1022 2- B1CVT-Y 2-1 CVT JB 7CX2.5 1 10 1,2 Y3a1 TB3-4 2-1 CVT JB-TB3-4 / Y3a1 2- B1CVT-Y-Y3a1 / TB3-4 WDG-3 CPD KN17 SC51 SHT07

3,4 SPARE CPD KN17 SC51 SHT07

5,6 Y3n TB3-6 2-1 CVT JB-TB3-6 / Y3n 2- B1CVT-Y-Y3n / TB3-6 CPD KN17 SC51 SHT07

7 SPARE

23 2 01 1023 2- B1CVT-Y 2-1 CVT JB 7CX2.5 1 10 1,2 Y4a1 TB4-4 2-1 CVT JB-TB4-4 / Y4a1 2- B1CVT-Y-Y4a1 / TB4-4 WDG-4 CPD KN17 SC51 SHT07

3,4 SPARE CPD KN17 SC51 SHT07

5,6 Y4n TB4-6 2-1 CVT JB-TB4-6 / Y4n 2- B1CVT-Y-Y4n / TB4-6 CPD KN17 SC51 SHT07

7 SPARE

24 2 01 1024 2- B1CVT-B 2-1 CVT JB 7CX2.5 1 15 1,2 B1a1 TB1-7 2-1 CVT JB-TB1-7 / B1a1 2- B1CVT-B-B1a1 / TB1-7 WDG-1 CPD KN17 SC51 SHT07

3,4 SPARE CPD KN17 SC51 SHT07

5,6 B1n TB1-9 2-1 CVT JB-TB1-9 / B1n 2- B1CVT-B-B1n / TB1-9 CPD KN17 SC51 SHT07

7 SPARE

25 2 01 1025 2- B1CVT-B 2-1 CVT JB 7CX2.5 1 15 1,2 B2a1 TB2-7 2-1 CVT JB-TB2-7 / B2a1 2- B1CVT-B-B2a1 / TB2-7 WDG-2 CPD KN17 SC51 SHT07

3,4 SPARE CPD KN17 SC51 SHT07

5,6 B2n TB2-9 2-1 CVT JB-TB2-9 / B2n 2- B1CVT-B-B2n / TB2-9 CPD KN17 SC51 SHT07

7 SPARE

26 2 01 1026 2- B1CVT-B 2-1 CVT JB 7CX2.5 1 15 1,2 B3a1 TB3-7 2-1 CVT JB-TB3-7 / B3a1 2- B1CVT-B-B3a1 / TB3-7 WDG-3 CPD KN17 SC51 SHT07

3,4 SPARE CPD KN17 SC51 SHT07

5,6 B3n TB3-9 2-1 CVT JB-TB3-9 / B3n 2- B1CVT-B-B3n / TB3-9 CPD KN17 SC51 SHT075,6 B3n TB3-9 2-1 CVT JB-TB3-9 / B3n 2- B1CVT-B-B3n / TB3-9 CPD KN17 SC51 SHT07

7 SPARE

201-BUS COUPLER_05.09.2011 Page 3 of 18 Cables within SWYD

Page 4: 201-BUS COUPLER_05.09

VVG

PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW) Date Revision

OWNERS CONSULTANTL&T S&L 31.08.2011 01

EPC CONTRACTORL&T POWER, VADODARA VVG

CONTRACTORS CONSULTANTDCPL, KOLKATA

EBOP CONTRACTORAREVA T&D INDIA LIMITED

DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG

ACTUAL DRUM APPLICATION REF. DRAWING. NO :

FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.

CABLES WITHIN SWITCHYARD

AREVA T&D INDIA LTD.

NO. OF

RUNSSIZE

CABLE NO. EQUIPMENT DESIGNATION ESTIMATED

LENGTH

INTERCONNECTION DETAILSSL.

NO

Prepared by

ROUTING DETAILS

Approved by

Ferrule Nos.

Checked by

INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)

27 2 01 1027 2- B1CVT-B 2-1 CVT JB 7CX2.5 1 15 1,2 B4a1 TB4-7 2-1 CVT JB-TB4-7 / B4a1 2- B1CVT-B-B4a1 / TB4-7 WDG-4 CPD KN17 SC51 SHT07

3,4 SPARE CPD KN17 SC51 SHT07

5,6 B4n TB4-9 2-1 CVT JB-TB4-9 / B4n 2- B1CVT-B-B4n / TB4-9 CPD KN17 SC51 SHT07

7 SPARE

28 2 01 1028 2- B2CVT-R 2-2 CVT JB 7CX2.5 1 15 1,2 R1a1 TB1-1 2-2 CVT JB-TB1-1 / R1a1 2- B2CVT-R-R1a1 / TB1-1 WDG-1 CPD KN17 SC51 SHT0828 2 01 1028 2- B2CVT-R 2-2 CVT JB 7CX2.5 1 15 1,2 R1a1 TB1-1 2-2 CVT JB-TB1-1 / R1a1 2- B2CVT-R-R1a1 / TB1-1 WDG-1 CPD KN17 SC51 SHT08

3,4 SPARE CPD KN17 SC51 SHT08

5,6 R1n TB1-3 2-2 CVT JB-TB1-3 / R1n 2- B2CVT-R-R1n / TB1-3 CPD KN17 SC51 SHT08

7 SPARE

29 2 01 1029 2- B2CVT-R 2-2 CVT JB 7CX2.5 1 15 1,2 R2a1 TB2-1 2-2 CVT JB-TB2-1 / R2a1 2- B2CVT-R-R2a1 / TB2-1 WDG-2 CPD KN17 SC51 SHT08

3,4 SPARE CPD KN17 SC51 SHT08

5,6 R2n TB2-3 2-2 CVT JB-TB2-3 / R2n 2- B2CVT-R-R2n / TB2-3 CPD KN17 SC51 SHT08

7 SPARE

30 2 01 1030 2- B2CVT-R 2-2 CVT JB 7CX2.5 1 15 1,2 R3a1 TB3-1 2-2 CVT JB-TB3-1 / R3a1 2- B2CVT-R-R3a1 / TB3-1 WDG-3 CPD KN17 SC51 SHT08

3,4 SPARE CPD KN17 SC51 SHT08

5,6 R3n TB3-3 2-2 CVT JB-TB3-3 / R3n 2- B2CVT-R-R3n / TB3-3 CPD KN17 SC51 SHT08

7 SPARE

31 2 01 1031 2- B2CVT-R 2-2 CVT JB 7CX2.5 1 15 1,2 R4a1 TB4-1 2-2 CVT JB-TB4-1 / R4a1 2- B2CVT-R-R4a1 / TB4-1 WDG-4 CPD KN17 SC51 SHT08

3,4 SPARE CPD KN17 SC51 SHT08

5,6 R4n TB4-3 2-2 CVT JB-TB4-3 / R4n 2- B2CVT-R-R4n / TB4-3 CPD KN17 SC51 SHT08

7 SPARE

32 2 01 1032 2- B2CVT-Y 2-2 CVT JB 7CX2.5 1 10 1,2 Y1a1 TB1-4 2-2 CVT JB-TB1-4 / Y1a1 2- B2CVT-Y-Y1a1 / TB1-4 WDG-1 CPD KN17 SC51 SHT08

3,4 SPARE CPD KN17 SC51 SHT083,4 SPARE CPD KN17 SC51 SHT08

5,6 Y1n TB1-6 2-2 CVT JB-TB1-6 / Y1n 2- B2CVT-Y-Y1n / TB1-6 CPD KN17 SC51 SHT08

7 SPARE

33 2 01 1033 2- B2CVT-Y 2-2 CVT JB 7CX2.5 1 10 1,2 Y2a1 TB2-4 2-2 CVT JB-TB2-4 / Y2a1 2- B2CVT-Y-Y2a1 / TB2-4 WDG-2 CPD KN17 SC51 SHT08

3,4 SPARE CPD KN17 SC51 SHT08

5,6 Y2n TB2-6 2-2 CVT JB-TB2-6 / Y2n 2- B2CVT-Y-Y2n / TB2-6 CPD KN17 SC51 SHT08

7 SPARE

34 2 01 1034 2- B2CVT-Y 2-2 CVT JB 7CX2.5 1 10 1,2 Y3a1 TB3-4 2-2 CVT JB-TB3-4 / Y3a1 2- B2CVT-Y-Y3a1 / TB3-4 WDG-3 CPD KN17 SC51 SHT08

3,4 SPARE CPD KN17 SC51 SHT08

5,6 Y3n TB3-6 2-2 CVT JB-TB3-6 / Y3n 2- B2CVT-Y-Y3n / TB3-6 CPD KN17 SC51 SHT08

7 SPARE

35 2 01 1035 2- B2CVT-Y 2-2 CVT JB 7CX2.5 1 10 1,2 Y4a1 TB4-4 2-2 CVT JB-TB4-4 / Y4a1 2- B2CVT-Y-Y4a1 / TB4-4 WDG-4 CPD KN17 SC51 SHT08

3,4 SPARE CPD KN17 SC51 SHT08

5,6 Y4n TB4-6 2-2 CVT JB-TB4-6 / Y4n 2- B2CVT-Y-Y4n / TB4-6 CPD KN17 SC51 SHT08

7 SPARE

36 2 01 1036 2- B2CVT-B 2-2 CVT JB 7CX2.5 1 15 1,2 B1a1 TB1-7 2-2 CVT JB-TB1-7 / B1a1 2- B2CVT-B-B1a1 / TB1-7 WDG-1 CPD KN17 SC51 SHT08

3,4 SPARE CPD KN17 SC51 SHT08

5,6 B1n TB1-9 2-2 CVT JB-TB1-9 / B1n 2- B2CVT-B-B1n / TB1-9 CPD KN17 SC51 SHT08

7 SPARE7 SPARE

37 2 01 1037 2- B2CVT-B 2-2 CVT JB 7CX2.5 1 15 1,2 B2a1 TB2-7 2-2 CVT JB-TB2-7 / B2a1 2- B2CVT-B-B2a1 / TB2-7 WDG-2 CPD KN17 SC51 SHT08

3,4 SPARE CPD KN17 SC51 SHT08

5,6 B2n TB2-9 2-2 CVT JB-TB2-9 / B2n 2- B2CVT-B-B2n / TB2-9 CPD KN17 SC51 SHT08

7 SPARE

38 2 01 1038 2- B2CVT-B 2-2 CVT JB 7CX2.5 1 15 1,2 B3a1 TB3-7 2-2 CVT JB-TB3-7 / B3a1 2- B2CVT-B-B3a1 / TB3-7 WDG-3 CPD KN17 SC51 SHT08

3,4 SPARE CPD KN17 SC51 SHT08

5,6 B3n TB3-9 2-2 CVT JB-TB3-9 / B3n 2- B2CVT-B-B3n / TB3-9 CPD KN17 SC51 SHT08

7 SPARE

39 2 01 1039 2- B2CVT-B 2-2 CVT JB 7CX2.5 1 15 1,2 B4a1 TB4-7 2-2 CVT JB-TB4-7 / B4a1 2- B2CVT-B-B4a1 / TB4-7 WDG-4 CPD KN17 SC51 SHT08

3,4 SPARE CPD KN17 SC51 SHT08

5,6 B4n TB4-9 2-2 CVT JB-TB4-9 / B4n 2- B2CVT-B-B4n / TB4-9 CPD KN17 SC51 SHT08

7 SPARE

201-BUS COUPLER_05.09.2011 Page 4 of 18 Cables within SWYD

Page 5: 201-BUS COUPLER_05.09

VVG

PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW) Date Revision

OWNERS CONSULTANTL&T S&L 31.08.2011 01

EPC CONTRACTORL&T POWER, VADODARA VVG

CONTRACTORS CONSULTANTDCPL, KOLKATA

EBOP CONTRACTORAREVA T&D INDIA LIMITED

DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG

ACTUAL DRUM APPLICATION REF. DRAWING. NO :

FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.

CABLES WITHIN SWITCHYARD

AREVA T&D INDIA LTD.

NO. OF

RUNSSIZE

CABLE NO. EQUIPMENT DESIGNATION ESTIMATED

LENGTH

INTERCONNECTION DETAILSSL.

NO

Prepared by

ROUTING DETAILS

Approved by

Ferrule Nos.

Checked by

INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)

CB INTERPOLE CABLING

40 2 01 1040 CB-R CBCC 19CX2.5 1 20 1 TB1-10 TB1-10 CBCC-TB1-10 / TB1-10 CB-R-TB1-10 / TB1-10 CLOSING COIL 5257PN100-MLW-E-SYD-SCH-1524 SHT03

2 TB1-16 TB1-16 CBCC-TB1-16 / TB1-16 CB-R-TB1-16 / TB1-16 CLOSING COIL 5257PN100-MLW-E-SYD-SCH-1524 SHT03

3 TB1-9 TB1-9 CBCC-TB1-9 / TB1-9 CB-R-TB1-9 / TB1-9 ANTI P/P 5257PN100-MLW-E-SYD-SCH-1524 SHT03

4 TB1-11 TB1-11 CBCC-TB1-11 / TB1-11 CB-R-TB1-11 / TB1-11 ANTI P/P 5257PN100-MLW-E-SYD-SCH-1524 SHT03

5 TB1-14 TB1-14 CBCC-TB1-14 / TB1-14 CB-R-TB1-14 / TB1-14 SF6 LOW PRE. 5257PN100-MLW-E-SYD-SCH-1524 SHT03 5 TB1-14 TB1-14 CBCC-TB1-14 / TB1-14 CB-R-TB1-14 / TB1-14 SF6 LOW PRE. 5257PN100-MLW-E-SYD-SCH-1524 SHT03

6 TB1-17 TB1-17 CBCC-TB1-17 / TB1-17 CB-R-TB1-17 / TB1-17 SF6 LOW PRE. 5257PN100-MLW-E-SYD-SCH-1524 SHT03

7 TB1-19 TB1-19 CBCC-TB1-19 / TB1-19 CB-R-TB1-19 / TB1-19 SF6 LOW PRE. 5257PN100-MLW-E-SYD-SCH-1524 SHT03

8 TB1-7 TB1-7 CBCC-TB1-7 / TB1-7 CB-R-TB1-7 / TB1-7 TC1 5257PN100-MLW-E-SYD-SCH-1524 SHT04

9 TB1-8 TB1-8 CBCC-TB1-8 / TB1-8 CB-R-TB1-8 / TB1-8 TC1 5257PN100-MLW-E-SYD-SCH-1524 SHT04

10 TB1-18 TB1-18 CBCC-TB1-18 / TB1-18 CB-R-TB1-18 / TB1-18 TC1 5257PN100-MLW-E-SYD-SCH-1524 SHT04

11 TB1-12 TB1-12 CBCC-TB1-12 / TB1-12 CB-R-TB1-12 / TB1-12 PD 5257PN100-MLW-E-SYD-SCH-1524 SHT04

12 TB1-13 TB1-13 CBCC-TB1-13 / TB1-13 CB-R-TB1-13 / TB1-13 PD 5257PN100-MLW-E-SYD-SCH-1524 SHT04

13 TB1-15 TB1-15 CBCC-TB1-15 / TB1-15 CB-R-TB1-15 / TB1-15 PD 5257PN100-MLW-E-SYD-SCH-1524 SHT04

14 SPARE

15 SPARE

16 SPARE

17 SPARE

18 SPARE

19 SPARE

41 2 01 1041 CB-R CBCC 19CX2.5 1 20 1 TB1-22 TB1-22 CBCC-TB1-22 / TB1-22 CB-R-TB1-22 / TB1-22 TC-2 5257PN100-MLW-E-SYD-SCH-1524 SHT05

2 TB1-23 TB1-23 CBCC-TB1-23 / TB1-23 CB-R-TB1-23 / TB1-23 TC-2 5257PN100-MLW-E-SYD-SCH-1524 SHT05

3 TB1-26 TB1-26 CBCC-TB1-26 / TB1-26 CB-R-TB1-26 / TB1-26 TC-2 5257PN100-MLW-E-SYD-SCH-1524 SHT05

4 TB1-24 TB1-24 CBCC-TB1-24 / TB1-24 CB-R-TB1-24 / TB1-24 SF6 L/O 5257PN100-MLW-E-SYD-SCH-1524 SHT05

5 TB1-25 TB1-25 CBCC-TB1-25 / TB1-25 CB-R-TB1-25 / TB1-25 SF6 L/O 5257PN100-MLW-E-SYD-SCH-1524 SHT05

6 TB1-29 TB1-29 CBCC-TB1-29 / TB1-29 CB-R-TB1-29 / TB1-29 IND. CB CL 5257PN100-MLW-E-SYD-SCH-1524 SHT06

7 TB1-30 TB1-30 CBCC-TB1-30 / TB1-30 CB-R-TB1-30 / TB1-30 IND. CB CL 5257PN100-MLW-E-SYD-SCH-1524 SHT06 7 TB1-30 TB1-30 CBCC-TB1-30 / TB1-30 CB-R-TB1-30 / TB1-30 IND. CB CL 5257PN100-MLW-E-SYD-SCH-1524 SHT06

8 TB1-31 TB1-31 CBCC-TB1-31 / TB1-31 CB-R-TB1-31 / TB1-31 IND. CB OPEN 5257PN100-MLW-E-SYD-SCH-1524 SHT06

9 TB1-32 TB1-32 CBCC-TB1-32 / TB1-32 CB-R-TB1-32 / TB1-32 IND. CB OPEN 5257PN100-MLW-E-SYD-SCH-1524 SHT06

10 TB1-33 TB1-33 CBCC-TB1-33 / TB1-33 CB-R-TB1-33 / TB1-33 IND. CB SPRING CHARGED 5257PN100-MLW-E-SYD-SCH-1524 SHT06

11 TB1-34 TB1-34 CBCC-TB1-34 / TB1-34 CB-R-TB1-34 / TB1-34 IND. CB SPRING CHARGED 5257PN100-MLW-E-SYD-SCH-1524 SHT06

12 TB1-27 TB1-27 CBCC-TB1-27 / TB1-27 CB-R-TB1-27 / TB1-27 SPRING CHARGED NC 5257PN100-MLW-E-SYD-SCH-1524 SHT06

13 TB1-28 TB1-28 CBCC-TB1-28 / TB1-28 CB-R-TB1-28 / TB1-28 SPRING CHARGED NC 5257PN100-MLW-E-SYD-SCH-1524 SHT06

14 SPARE

15 SPARE

16 SPARE

17 SPARE

18 SPARE

19 SPARE

42 2 01 1042 CB-R CBCC 24CX2.5 1 20 1 TB2-1 TB5-1 CBCC-TB5-1 / TB2-1 CB-R-TB2-1 / TB5-1 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

2 TB2-2 TB5-2 CBCC-TB5-2 / TB2-2 CB-R-TB2-2 / TB5-2 5257PN100-MLW-E-SYD-SCH-1524 SHT08

3 TB2-3 TB5-3 CBCC-TB5-3 / TB2-3 CB-R-TB2-3 / TB5-3 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

4 TB2-4 TB5-4 CBCC-TB5-4 / TB2-4 CB-R-TB2-4 / TB5-4 5257PN100-MLW-E-SYD-SCH-1524 SHT08

5 TB2-5 TB5-5 CBCC-TB5-5 / TB2-5 CB-R-TB2-5 / TB5-5 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

6 TB2-6 TB5-6 CBCC-TB5-6 / TB2-6 CB-R-TB2-6 / TB5-6 5257PN100-MLW-E-SYD-SCH-1524 SHT08

7 TB2-7 TB5-7 CBCC-TB5-7 / TB2-7 CB-R-TB2-7 / TB5-7 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

8 TB2-8 TB5-8 CBCC-TB5-8 / TB2-8 CB-R-TB2-8 / TB5-8 5257PN100-MLW-E-SYD-SCH-1524 SHT08 8 TB2-8 TB5-8 CBCC-TB5-8 / TB2-8 CB-R-TB2-8 / TB5-8 5257PN100-MLW-E-SYD-SCH-1524 SHT08

9 TB2-9 TB5-9 CBCC-TB5-9 / TB2-9 CB-R-TB2-9 / TB5-9 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

10 TB2-10 TB5-10 CBCC-TB5-10 / TB2-10 CB-R-TB2-10 / TB5-10 5257PN100-MLW-E-SYD-SCH-1524 SHT08

11 TB2-11 TB5-11 CBCC-TB5-11 / TB2-11 CB-R-TB2-11 / TB5-11 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

12 TB2-12 TB5-12 CBCC-TB5-12 / TB2-12 CB-R-TB2-12 / TB5-12 5257PN100-MLW-E-SYD-SCH-1524 SHT08

13 TB2-13 TB5-13 CBCC-TB5-13 / TB2-13 CB-R-TB2-13 / TB5-13 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

14 TB2-14 TB5-14 CBCC-TB5-14 / TB2-14 CB-R-TB2-14 / TB5-14 5257PN100-MLW-E-SYD-SCH-1524 SHT08

15 TB2-15 TB5-15 CBCC-TB5-15 / TB2-15 CB-R-TB2-15 / TB5-15 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

16 TB2-16 TB5-16 CBCC-TB5-16 / TB2-16 CB-R-TB2-16 / TB5-16 5257PN100-MLW-E-SYD-SCH-1524 SHT08

17 TB2-33 TB5-33 CBCC-TB5-33 / TB2-33 CB-R-TB2-33 / TB5-33 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

18 TB2-34 TB5-34 CBCC-TB5-34 / TB2-34 CB-R-TB2-34 / TB5-34 5257PN100-MLW-E-SYD-SCH-1524 SHT08

19 TB2-35 TB5-35 CBCC-TB5-35 / TB2-35 CB-R-TB2-35 / TB5-35 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

20 TB2-36 TB5-36 CBCC-TB5-36 / TB2-36 CB-R-TB2-36 / TB5-36

21 SPARE

22 SPARE

23 SPARE

24 SPARE

201-BUS COUPLER_05.09.2011 Page 5 of 18 Cables within SWYD

Page 6: 201-BUS COUPLER_05.09

VVG

PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW) Date Revision

OWNERS CONSULTANTL&T S&L 31.08.2011 01

EPC CONTRACTORL&T POWER, VADODARA VVG

CONTRACTORS CONSULTANTDCPL, KOLKATA

EBOP CONTRACTORAREVA T&D INDIA LIMITED

DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG

ACTUAL DRUM APPLICATION REF. DRAWING. NO :

FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.

CABLES WITHIN SWITCHYARD

AREVA T&D INDIA LTD.

NO. OF

RUNSSIZE

CABLE NO. EQUIPMENT DESIGNATION ESTIMATED

LENGTH

INTERCONNECTION DETAILSSL.

NO

Prepared by

ROUTING DETAILS

Approved by

Ferrule Nos.

Checked by

INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)

43 2 01 1043 CB-R CBCC 24CX2.5 1 20 1 TB2-17 TB5-17 CBCC-TB5-17 / TB2-17 CB-R-TB2-17 / TB5-17 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

2 TB2-18 TB5-18 CBCC-TB5-18 / TB2-18 CB-R-TB2-18 / TB5-18 5257PN100-MLW-E-SYD-SCH-1524 SHT08

3 TB2-19 TB5-19 CBCC-TB5-19 / TB2-19 CB-R-TB2-19 / TB5-19 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

4 TB2-20 TB5-20 CBCC-TB5-20 / TB2-20 CB-R-TB2-20 / TB5-20 5257PN100-MLW-E-SYD-SCH-1524 SHT08

5 TB2-21 TB5-21 CBCC-TB5-21 / TB2-21 CB-R-TB2-21 / TB5-21 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

6 TB2-22 TB5-22 CBCC-TB5-22 / TB2-22 CB-R-TB2-22 / TB5-22 5257PN100-MLW-E-SYD-SCH-1524 SHT08 6 TB2-22 TB5-22 CBCC-TB5-22 / TB2-22 CB-R-TB2-22 / TB5-22 5257PN100-MLW-E-SYD-SCH-1524 SHT08

7 TB2-23 TB5-23 CBCC-TB5-23 / TB2-23 CB-R-TB2-23 / TB5-23 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

8 TB2-24 TB5-24 CBCC-TB5-24 / TB2-24 CB-R-TB2-24 / TB5-24 5257PN100-MLW-E-SYD-SCH-1524 SHT08

9 TB2-25 TB5-25 CBCC-TB5-25 / TB2-25 CB-R-TB2-25 / TB5-25 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

10 TB2-26 TB5-26 CBCC-TB5-26 / TB2-26 CB-R-TB2-26 / TB5-26 5257PN100-MLW-E-SYD-SCH-1524 SHT08

11 TB2-27 TB5-27 CBCC-TB5-27 / TB2-27 CB-R-TB2-27 / TB5-27 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

12 TB2-28 TB5-28 CBCC-TB5-28 / TB2-28 CB-R-TB2-28 / TB5-28 5257PN100-MLW-E-SYD-SCH-1524 SHT08

13 TB2-29 TB5-29 CBCC-TB5-29 / TB2-29 CB-R-TB2-29 / TB5-29 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

14 TB2-30 TB5-30 CBCC-TB5-30 / TB2-30 CB-R-TB2-30 / TB5-30 5257PN100-MLW-E-SYD-SCH-1524 SHT08

15 TB2-31 TB5-31 CBCC-TB5-31 / TB2-31 CB-R-TB2-31 / TB5-31 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

16 TB2-32 TB5-32 CBCC-TB5-32 / TB2-32 CB-R-TB2-32 / TB5-32 5257PN100-MLW-E-SYD-SCH-1524 SHT08

17 TB2-37 TB5-37 CBCC-TB5-37 / TB2-37 CB-R-TB2-37 / TB5-37 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

18 TB2-38 TB5-38 CBCC-TB5-38 / TB2-38 CB-R-TB2-38 / TB5-38 5257PN100-MLW-E-SYD-SCH-1524 SHT08

19 TB2-39 TB5-39 CBCC-TB5-39 / TB2-39 CB-R-TB2-39 / TB5-39 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

20 TB2-40 TB5-40 CBCC-TB5-40 / TB2-40 CB-R-TB2-40 / TB5-40

21 SPARE

22 SPARE

23 SPARE

24 SPARE

44 2 01 1044 CB-Y CBCC 19CX2.5 1 15 1 TB1-10 TB2-10 CBCC-TB2-10 / TB1-10 CB-Y-TB1-10 / TB2-10 CLOSING COIL 5257PN100-MLW-E-SYD-SCH-1524 SHT03

2 TB1-16 TB2-16 CBCC-TB2-16 / TB1-16 CB-Y-TB1-16 / TB2-16 CLOSING COIL 5257PN100-MLW-E-SYD-SCH-1524 SHT03

3 TB1-9 TB2-9 CBCC-TB2-9 / TB1-9 CB-Y-TB1-9 / TB2-9 ANTI P/P 5257PN100-MLW-E-SYD-SCH-1524 SHT03 3 TB1-9 TB2-9 CBCC-TB2-9 / TB1-9 CB-Y-TB1-9 / TB2-9 ANTI P/P 5257PN100-MLW-E-SYD-SCH-1524 SHT03

4 TB1-11 TB2-11 CBCC-TB2-11 / TB1-11 CB-Y-TB1-11 / TB2-11 ANTI P/P 5257PN100-MLW-E-SYD-SCH-1524 SHT03

5 TB1-14 TB2-14 CBCC-TB2-14 / TB1-14 CB-Y-TB1-14 / TB2-14 SF6 LOW PRE. 5257PN100-MLW-E-SYD-SCH-1524 SHT03

6 TB1-17 TB2-17 CBCC-TB2-17 / TB1-17 CB-Y-TB1-17 / TB2-17 SF6 LOW PRE. 5257PN100-MLW-E-SYD-SCH-1524 SHT03

7 TB1-19 TB2-19 CBCC-TB2-19 / TB1-19 CB-Y-TB1-19 / TB2-19 SF6 LOW PRE. 5257PN100-MLW-E-SYD-SCH-1524 SHT03

8 TB1-7 TB2-7 CBCC-TB2-7 / TB1-7 CB-Y-TB1-7 / TB2-7 TC1 5257PN100-MLW-E-SYD-SCH-1524 SHT04

9 TB1-8 TB2-8 CBCC-TB2-8 / TB1-8 CB-Y-TB1-8 / TB2-8 TC1 5257PN100-MLW-E-SYD-SCH-1524 SHT04

10 TB1-18 TB2-18 CBCC-TB2-18 / TB1-18 CB-Y-TB1-18 / TB2-18 TC1 5257PN100-MLW-E-SYD-SCH-1524 SHT04

11 TB1-12 TB2-12 CBCC-TB2-12 / TB1-12 CB-Y-TB1-12 / TB2-12 PD 5257PN100-MLW-E-SYD-SCH-1524 SHT04

12 TB1-13 TB2-13 CBCC-TB2-13 / TB1-13 CB-Y-TB1-13 / TB2-13 PD 5257PN100-MLW-E-SYD-SCH-1524 SHT04

13 TB1-15 TB2-15 CBCC-TB2-15 / TB1-15 CB-Y-TB1-15 / TB2-15 PD 5257PN100-MLW-E-SYD-SCH-1524 SHT04

14 SPARE

15 SPARE

16 SPARE

17 SPARE

18 SPARE

19 SPARE

45 2 01 1045 CB-Y CBCC 19CX2.5 1 15 1 TB1-22 TB2-22 CBCC-TB2-22 / TB1-22 CB-Y-TB1-22 / TB2-22 TC-2 5257PN100-MLW-E-SYD-SCH-1524 SHT05

2 TB1-23 TB2-23 CBCC-TB2-23 / TB1-23 CB-Y-TB1-23 / TB2-23 TC-2 5257PN100-MLW-E-SYD-SCH-1524 SHT05

3 TB1-26 TB2-26 CBCC-TB2-26 / TB1-26 CB-Y-TB1-26 / TB2-26 TC-2 5257PN100-MLW-E-SYD-SCH-1524 SHT05

4 TB1-24 TB2-24 CBCC-TB2-24 / TB1-24 CB-Y-TB1-24 / TB2-24 SF6 L/O 5257PN100-MLW-E-SYD-SCH-1524 SHT05 4 TB1-24 TB2-24 CBCC-TB2-24 / TB1-24 CB-Y-TB1-24 / TB2-24 SF6 L/O 5257PN100-MLW-E-SYD-SCH-1524 SHT05

5 TB1-25 TB2-25 CBCC-TB2-25 / TB1-25 CB-Y-TB1-25 / TB2-25 SF6 L/O 5257PN100-MLW-E-SYD-SCH-1524 SHT05

6 TB1-29 TB2-29 CBCC-TB2-29 / TB1-29 CB-Y-TB1-29 / TB2-29 IND. CB CL 5257PN100-MLW-E-SYD-SCH-1524 SHT06

7 TB1-30 TB2-30 CBCC-TB2-30 / TB1-30 CB-Y-TB1-30 / TB2-30 IND. CB CL 5257PN100-MLW-E-SYD-SCH-1524 SHT06

8 TB1-31 TB2-31 CBCC-TB2-31 / TB1-31 CB-Y-TB1-31 / TB2-31 IND. CB OPEN 5257PN100-MLW-E-SYD-SCH-1524 SHT06

9 TB1-32 TB2-32 CBCC-TB2-32 / TB1-32 CB-Y-TB1-32 / TB2-32 IND. CB OPEN 5257PN100-MLW-E-SYD-SCH-1524 SHT06

10 TB1-33 TB2-33 CBCC-TB2-33 / TB1-33 CB-Y-TB1-33 / TB2-33 IND. CB SPRING CHARGED 5257PN100-MLW-E-SYD-SCH-1524 SHT06

11 TB1-34 TB2-34 CBCC-TB2-34 / TB1-34 CB-Y-TB1-34 / TB2-34 IND. CB SPRING CHARGED 5257PN100-MLW-E-SYD-SCH-1524 SHT06

12 TB1-27 TB2-27 CBCC-TB2-27 / TB1-27 CB-Y-TB1-27 / TB2-27 SPRING CHARGED NC 5257PN100-MLW-E-SYD-SCH-1524 SHT06

13 TB1-28 TB2-28 CBCC-TB2-28 / TB1-28 CB-Y-TB1-28 / TB2-28 SPRING CHARGED NC 5257PN100-MLW-E-SYD-SCH-1524 SHT06

14 SPARE

15 SPARE

16 SPARE

17 SPARE

18 SPARE

19 SPARE

201-BUS COUPLER_05.09.2011 Page 6 of 18 Cables within SWYD

Page 7: 201-BUS COUPLER_05.09

VVG

PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW) Date Revision

OWNERS CONSULTANTL&T S&L 31.08.2011 01

EPC CONTRACTORL&T POWER, VADODARA VVG

CONTRACTORS CONSULTANTDCPL, KOLKATA

EBOP CONTRACTORAREVA T&D INDIA LIMITED

DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG

ACTUAL DRUM APPLICATION REF. DRAWING. NO :

FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.

CABLES WITHIN SWITCHYARD

AREVA T&D INDIA LTD.

NO. OF

RUNSSIZE

CABLE NO. EQUIPMENT DESIGNATION ESTIMATED

LENGTH

INTERCONNECTION DETAILSSL.

NO

Prepared by

ROUTING DETAILS

Approved by

Ferrule Nos.

Checked by

INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)

46 2 01 1046 CB-Y CBCC 24CX2.5 1 15 1 TB2-1 TB6-1 CBCC-TB6-1 / TB2-1 CB-Y-TB2-1 / TB6-1 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

2 TB2-2 TB6-2 CBCC-TB6-2 / TB2-2 CB-Y-TB2-2 / TB6-2 5257PN100-MLW-E-SYD-SCH-1524 SHT08

3 TB2-3 TB6-3 CBCC-TB6-3 / TB2-3 CB-Y-TB2-3 / TB6-3 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

4 TB2-4 TB6-4 CBCC-TB6-4 / TB2-4 CB-Y-TB2-4 / TB6-4 5257PN100-MLW-E-SYD-SCH-1524 SHT08

5 TB2-5 TB6-5 CBCC-TB6-5 / TB2-5 CB-Y-TB2-5 / TB6-5 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

6 TB2-6 TB6-6 CBCC-TB6-6 / TB2-6 CB-Y-TB2-6 / TB6-6 5257PN100-MLW-E-SYD-SCH-1524 SHT08 6 TB2-6 TB6-6 CBCC-TB6-6 / TB2-6 CB-Y-TB2-6 / TB6-6 5257PN100-MLW-E-SYD-SCH-1524 SHT08

7 TB2-7 TB6-7 CBCC-TB6-7 / TB2-7 CB-Y-TB2-7 / TB6-7 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

8 TB2-8 TB6-8 CBCC-TB6-8 / TB2-8 CB-Y-TB2-8 / TB6-8 5257PN100-MLW-E-SYD-SCH-1524 SHT08

9 TB2-9 TB6-9 CBCC-TB6-9 / TB2-9 CB-Y-TB2-9 / TB6-9 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

10 TB2-10 TB6-10 CBCC-TB6-10 / TB2-10 CB-Y-TB2-10 / TB6-10 5257PN100-MLW-E-SYD-SCH-1524 SHT08

11 TB2-11 TB6-11 CBCC-TB6-11 / TB2-11 CB-Y-TB2-11 / TB6-11 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

12 TB2-12 TB6-12 CBCC-TB6-12 / TB2-12 CB-Y-TB2-12 / TB6-12 5257PN100-MLW-E-SYD-SCH-1524 SHT08

13 TB2-13 TB6-13 CBCC-TB6-13 / TB2-13 CB-Y-TB2-13 / TB6-13 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

14 TB2-14 TB6-14 CBCC-TB6-14 / TB2-14 CB-Y-TB2-14 / TB6-14 5257PN100-MLW-E-SYD-SCH-1524 SHT08

15 TB2-15 TB6-15 CBCC-TB6-15 / TB2-15 CB-Y-TB2-15 / TB6-15 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

16 TB2-16 TB6-16 CBCC-TB6-16 / TB2-16 CB-Y-TB2-16 / TB6-16 5257PN100-MLW-E-SYD-SCH-1524 SHT08

17 TB2-33 TB6-33 CBCC-TB6-33 / TB2-33 CB-Y-TB2-33 / TB6-33 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

18 TB2-34 TB6-34 CBCC-TB6-34 / TB2-34 CB-Y-TB2-34 / TB6-34 5257PN100-MLW-E-SYD-SCH-1524 SHT08

19 TB2-35 TB6-35 CBCC-TB6-35 / TB2-35 CB-Y-TB2-35 / TB6-35 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

20 TB2-36 TB6-36 CBCC-TB6-36 / TB2-36 CB-Y-TB2-36 / TB6-36

21 SPARE

22 SPARE

23 SPARE

24 SPARE

47 2 01 1047 CB-Y CBCC 24CX2.5 1 15 1 TB2-17 TB6-17 CBCC-TB6-17 / TB2-17 CB-Y-TB2-17 / TB6-17 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

2 TB2-18 TB6-18 CBCC-TB6-18 / TB2-18 CB-Y-TB2-18 / TB6-18 5257PN100-MLW-E-SYD-SCH-1524 SHT08

3 TB2-19 TB6-19 CBCC-TB6-19 / TB2-19 CB-Y-TB2-19 / TB6-19 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08 3 TB2-19 TB6-19 CBCC-TB6-19 / TB2-19 CB-Y-TB2-19 / TB6-19 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

4 TB2-20 TB6-20 CBCC-TB6-20 / TB2-20 CB-Y-TB2-20 / TB6-20 5257PN100-MLW-E-SYD-SCH-1524 SHT08

5 TB2-21 TB6-21 CBCC-TB6-21 / TB2-21 CB-Y-TB2-21 / TB6-21 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

6 TB2-22 TB6-22 CBCC-TB6-22 / TB2-22 CB-Y-TB2-22 / TB6-22 5257PN100-MLW-E-SYD-SCH-1524 SHT08

7 TB2-23 TB6-23 CBCC-TB6-23 / TB2-23 CB-Y-TB2-23 / TB6-23 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

8 TB2-24 TB6-24 CBCC-TB6-24 / TB2-24 CB-Y-TB2-24 / TB6-24 5257PN100-MLW-E-SYD-SCH-1524 SHT08

9 TB2-25 TB6-25 CBCC-TB6-25 / TB2-25 CB-Y-TB2-25 / TB6-25 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

10 TB2-26 TB6-26 CBCC-TB6-26 / TB2-26 CB-Y-TB2-26 / TB6-26 5257PN100-MLW-E-SYD-SCH-1524 SHT08

11 TB2-27 TB6-27 CBCC-TB6-27 / TB2-27 CB-Y-TB2-27 / TB6-27 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

12 TB2-28 TB6-28 CBCC-TB6-28 / TB2-28 CB-Y-TB2-28 / TB6-28 5257PN100-MLW-E-SYD-SCH-1524 SHT08

13 TB2-29 TB6-29 CBCC-TB6-29 / TB2-29 CB-Y-TB2-29 / TB6-29 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

14 TB2-30 TB6-30 CBCC-TB6-30 / TB2-30 CB-Y-TB2-30 / TB6-30 5257PN100-MLW-E-SYD-SCH-1524 SHT08

15 TB2-31 TB6-31 CBCC-TB6-31 / TB2-31 CB-Y-TB2-31 / TB6-31 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

16 TB2-32 TB6-32 CBCC-TB6-32 / TB2-32 CB-Y-TB2-32 / TB6-32 5257PN100-MLW-E-SYD-SCH-1524 SHT08

17 TB2-37 TB6-37 CBCC-TB6-37 / TB2-37 CB-Y-TB2-37 / TB6-37 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

18 TB2-38 TB6-38 CBCC-TB6-38 / TB2-38 CB-Y-TB2-38 / TB6-38 5257PN100-MLW-E-SYD-SCH-1524 SHT08

19 TB2-39 TB6-39 CBCC-TB6-39 / TB2-39 CB-Y-TB2-39 / TB6-39 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

20 TB2-40 TB6-40 CBCC-TB6-40 / TB2-40 CB-Y-TB2-40 / TB6-40

21 SPARE

22 SPARE

23 SPARE

24 SPARE 24 SPARE

48 2 01 1048 CB-B CBCC 19CX2.5 1 20 1 TB1-10 TB3-10 CBCC-TB3-10 / TB1-10 CB-B-TB1-10 / TB3-10 CLOSING COIL 5257PN100-MLW-E-SYD-SCH-1524 SHT03

2 TB1-16 TB3-16 CBCC-TB3-16 / TB1-16 CB-B-TB1-16 / TB3-16 CLOSING COIL 5257PN100-MLW-E-SYD-SCH-1524 SHT03

3 TB1-9 TB3-9 CBCC-TB3-9 / TB1-9 CB-B-TB1-9 / TB3-9 ANTI P/P 5257PN100-MLW-E-SYD-SCH-1524 SHT03

4 TB1-11 TB3-11 CBCC-TB3-11 / TB1-11 CB-B-TB1-11 / TB3-11 ANTI P/P 5257PN100-MLW-E-SYD-SCH-1524 SHT03

5 TB1-14 TB3-14 CBCC-TB3-14 / TB1-14 CB-B-TB1-14 / TB3-14 SF6 LOW PRE. 5257PN100-MLW-E-SYD-SCH-1524 SHT03

6 TB1-17 TB3-17 CBCC-TB3-17 / TB1-17 CB-B-TB1-17 / TB3-17 SF6 LOW PRE. 5257PN100-MLW-E-SYD-SCH-1524 SHT03

7 TB1-19 TB3-19 CBCC-TB3-19 / TB1-19 CB-B-TB1-19 / TB3-19 SF6 LOW PRE. 5257PN100-MLW-E-SYD-SCH-1524 SHT03

8 TB1-7 TB3-7 CBCC-TB3-7 / TB1-7 CB-B-TB1-7 / TB3-7 TC1 5257PN100-MLW-E-SYD-SCH-1524 SHT04

9 TB1-8 TB3-8 CBCC-TB3-8 / TB1-8 CB-B-TB1-8 / TB3-8 TC1 5257PN100-MLW-E-SYD-SCH-1524 SHT04

10 TB1-18 TB3-18 CBCC-TB3-18 / TB1-18 CB-B-TB1-18 / TB3-18 TC1 5257PN100-MLW-E-SYD-SCH-1524 SHT04

11 TB1-12 TB3-12 CBCC-TB3-12 / TB1-12 CB-B-TB1-12 / TB3-12 PD 5257PN100-MLW-E-SYD-SCH-1524 SHT04

12 TB1-13 TB3-13 CBCC-TB3-13 / TB1-13 CB-B-TB1-13 / TB3-13 PD 5257PN100-MLW-E-SYD-SCH-1524 SHT04

13 TB1-15 TB3-15 CBCC-TB3-15 / TB1-15 CB-B-TB1-15 / TB3-15 PD 5257PN100-MLW-E-SYD-SCH-1524 SHT04

14 SPARE

15 SPARE

16 SPARE

17 SPARE

18 SPARE

19 SPARE

201-BUS COUPLER_05.09.2011 Page 7 of 18 Cables within SWYD

Page 8: 201-BUS COUPLER_05.09

VVG

PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW) Date Revision

OWNERS CONSULTANTL&T S&L 31.08.2011 01

EPC CONTRACTORL&T POWER, VADODARA VVG

CONTRACTORS CONSULTANTDCPL, KOLKATA

EBOP CONTRACTORAREVA T&D INDIA LIMITED

DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG

ACTUAL DRUM APPLICATION REF. DRAWING. NO :

FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.

CABLES WITHIN SWITCHYARD

AREVA T&D INDIA LTD.

NO. OF

RUNSSIZE

CABLE NO. EQUIPMENT DESIGNATION ESTIMATED

LENGTH

INTERCONNECTION DETAILSSL.

NO

Prepared by

ROUTING DETAILS

Approved by

Ferrule Nos.

Checked by

INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)

49 2 01 1049 CB-B CBCC 19CX2.5 1 15 1 TB1-22 TB3-22 CBCC-TB3-22 / TB1-22 CB-B-TB1-22 / TB3-22 TC-2 5257PN100-MLW-E-SYD-SCH-1524 SHT05

2 TB1-23 TB3-23 CBCC-TB3-23 / TB1-23 CB-B-TB1-23 / TB3-23 TC-2 5257PN100-MLW-E-SYD-SCH-1524 SHT05

3 TB1-26 TB3-26 CBCC-TB3-26 / TB1-26 CB-B-TB1-26 / TB3-26 TC-2 5257PN100-MLW-E-SYD-SCH-1524 SHT05

4 TB1-24 TB3-24 CBCC-TB3-24 / TB1-24 CB-B-TB1-24 / TB3-24 SF6 L/O 5257PN100-MLW-E-SYD-SCH-1524 SHT05

5 TB1-25 TB3-25 CBCC-TB3-25 / TB1-25 CB-B-TB1-25 / TB3-25 SF6 L/O 5257PN100-MLW-E-SYD-SCH-1524 SHT05

6 TB1-29 TB3-29 CBCC-TB3-29 / TB1-29 CB-B-TB1-29 / TB3-29 IND. CB CL 5257PN100-MLW-E-SYD-SCH-1524 SHT06 6 TB1-29 TB3-29 CBCC-TB3-29 / TB1-29 CB-B-TB1-29 / TB3-29 IND. CB CL 5257PN100-MLW-E-SYD-SCH-1524 SHT06

7 TB1-30 TB3-30 CBCC-TB3-30 / TB1-30 CB-B-TB1-30 / TB3-30 IND. CB CL 5257PN100-MLW-E-SYD-SCH-1524 SHT06

8 TB1-31 TB3-31 CBCC-TB3-31 / TB1-31 CB-B-TB1-31 / TB3-31 IND. CB OPEN 5257PN100-MLW-E-SYD-SCH-1524 SHT06

9 TB1-32 TB3-32 CBCC-TB3-32 / TB1-32 CB-B-TB1-32 / TB3-32 IND. CB OPEN 5257PN100-MLW-E-SYD-SCH-1524 SHT06

10 TB1-33 TB3-33 CBCC-TB3-33 / TB1-33 CB-B-TB1-33 / TB3-33 IND. CB SPRING CHARGED 5257PN100-MLW-E-SYD-SCH-1524 SHT06

11 TB1-34 TB3-34 CBCC-TB3-34 / TB1-34 CB-B-TB1-34 / TB3-34 IND. CB SPRING CHARGED 5257PN100-MLW-E-SYD-SCH-1524 SHT06

12 TB1-27 TB3-27 CBCC-TB3-27 / TB1-27 CB-B-TB1-27 / TB3-27 SPRING CHARGED NC 5257PN100-MLW-E-SYD-SCH-1524 SHT06

13 TB1-28 TB3-28 CBCC-TB3-28 / TB1-28 CB-B-TB1-28 / TB3-28 SPRING CHARGED NC 5257PN100-MLW-E-SYD-SCH-1524 SHT06

14 SPARE

15 SPARE

16 SPARE

17 SPARE

18 SPARE

19 SPARE

50 2 01 1050 CB-B CBCC 24CX2.5 1 15 1 TB2-1 TB7-1 CBCC-TB7-1 / TB2-1 CB-B-TB2-1 / TB7-1 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

2 TB2-2 TB7-2 CBCC-TB7-2 / TB2-2 CB-B-TB2-2 / TB7-2 5257PN100-MLW-E-SYD-SCH-1524 SHT08

3 TB2-3 TB7-3 CBCC-TB7-3 / TB2-3 CB-B-TB2-3 / TB7-3 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

4 TB2-4 TB7-4 CBCC-TB7-4 / TB2-4 CB-B-TB2-4 / TB7-4 5257PN100-MLW-E-SYD-SCH-1524 SHT08

5 TB2-5 TB7-5 CBCC-TB7-5 / TB2-5 CB-B-TB2-5 / TB7-5 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

6 TB2-6 TB7-6 CBCC-TB7-6 / TB2-6 CB-B-TB2-6 / TB7-6 5257PN100-MLW-E-SYD-SCH-1524 SHT08

7 TB2-7 TB7-7 CBCC-TB7-7 / TB2-7 CB-B-TB2-7 / TB7-7 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

8 TB2-8 TB7-8 CBCC-TB7-8 / TB2-8 CB-B-TB2-8 / TB7-8 5257PN100-MLW-E-SYD-SCH-1524 SHT08 8 TB2-8 TB7-8 CBCC-TB7-8 / TB2-8 CB-B-TB2-8 / TB7-8 5257PN100-MLW-E-SYD-SCH-1524 SHT08

9 TB2-9 TB7-9 CBCC-TB7-9 / TB2-9 CB-B-TB2-9 / TB7-9 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

10 TB2-10 TB7-10 CBCC-TB7-10 / TB2-10 CB-B-TB2-10 / TB7-10 5257PN100-MLW-E-SYD-SCH-1524 SHT08

11 TB2-11 TB7-11 CBCC-TB7-11 / TB2-11 CB-B-TB2-11 / TB7-11 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

12 TB2-12 TB7-12 CBCC-TB7-12 / TB2-12 CB-B-TB2-12 / TB7-12 5257PN100-MLW-E-SYD-SCH-1524 SHT08

13 TB2-13 TB7-13 CBCC-TB7-13 / TB2-13 CB-B-TB2-13 / TB7-13 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

14 TB2-14 TB7-14 CBCC-TB7-14 / TB2-14 CB-B-TB2-14 / TB7-14 5257PN100-MLW-E-SYD-SCH-1524 SHT08

15 TB2-15 TB7-15 CBCC-TB7-15 / TB2-15 CB-B-TB2-15 / TB7-15 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

16 TB2-16 TB7-16 CBCC-TB7-16 / TB2-16 CB-B-TB2-16 / TB7-16 5257PN100-MLW-E-SYD-SCH-1524 SHT08

17 TB2-33 TB7-33 CBCC-TB7-33 / TB2-33 CB-B-TB2-33 / TB7-33 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

18 TB2-34 TB7-34 CBCC-TB7-34 / TB2-34 CB-B-TB2-34 / TB7-34 5257PN100-MLW-E-SYD-SCH-1524 SHT08

19 TB2-35 TB7-35 CBCC-TB7-35 / TB2-35 CB-B-TB2-35 / TB7-35 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

20 TB2-36 TB7-36 CBCC-TB7-36 / TB2-36 CB-B-TB2-36 / TB7-36

21 SPARE

22 SPARE

23 SPARE

24 SPARE

51 2 01 1051 CB-B CBCC 24CX2.5 1 15 1 TB2-17 TB7-17 CBCC-TB7-17 / TB2-17 CB-B-TB2-17 / TB7-17 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

2 TB2-18 TB7-18 CBCC-TB7-18 / TB2-18 CB-B-TB2-18 / TB7-18 5257PN100-MLW-E-SYD-SCH-1524 SHT08

3 TB2-19 TB7-19 CBCC-TB7-19 / TB2-19 CB-B-TB2-19 / TB7-19 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

4 TB2-20 TB7-20 CBCC-TB7-20 / TB2-20 CB-B-TB2-20 / TB7-20 5257PN100-MLW-E-SYD-SCH-1524 SHT08 4 TB2-20 TB7-20 CBCC-TB7-20 / TB2-20 CB-B-TB2-20 / TB7-20 5257PN100-MLW-E-SYD-SCH-1524 SHT08

5 TB2-21 TB7-21 CBCC-TB7-21 / TB2-21 CB-B-TB2-21 / TB7-21 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

6 TB2-22 TB7-22 CBCC-TB7-22 / TB2-22 CB-B-TB2-22 / TB7-22 5257PN100-MLW-E-SYD-SCH-1524 SHT08

7 TB2-23 TB7-23 CBCC-TB7-23 / TB2-23 CB-B-TB2-23 / TB7-23 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

8 TB2-24 TB7-24 CBCC-TB7-24 / TB2-24 CB-B-TB2-24 / TB7-24 5257PN100-MLW-E-SYD-SCH-1524 SHT08

9 TB2-25 TB7-25 CBCC-TB7-25 / TB2-25 CB-B-TB2-25 / TB7-25 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

10 TB2-26 TB7-26 CBCC-TB7-26 / TB2-26 CB-B-TB2-26 / TB7-26 5257PN100-MLW-E-SYD-SCH-1524 SHT08

11 TB2-27 TB7-27 CBCC-TB7-27 / TB2-27 CB-B-TB2-27 / TB7-27 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

12 TB2-28 TB7-28 CBCC-TB7-28 / TB2-28 CB-B-TB2-28 / TB7-28 5257PN100-MLW-E-SYD-SCH-1524 SHT08

13 TB2-29 TB7-29 CBCC-TB7-29 / TB2-29 CB-B-TB2-29 / TB7-29 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

14 TB2-30 TB7-30 CBCC-TB7-30 / TB2-30 CB-B-TB2-30 / TB7-30 5257PN100-MLW-E-SYD-SCH-1524 SHT08

15 TB2-31 TB7-31 CBCC-TB7-31 / TB2-31 CB-B-TB2-31 / TB7-31 NC CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

16 TB2-32 TB7-32 CBCC-TB7-32 / TB2-32 CB-B-TB2-32 / TB7-32 5257PN100-MLW-E-SYD-SCH-1524 SHT08

17 TB2-37 TB7-37 CBCC-TB7-37 / TB2-37 CB-B-TB2-37 / TB7-37 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

18 TB2-38 TB7-38 CBCC-TB7-38 / TB2-38 CB-B-TB2-38 / TB7-38 5257PN100-MLW-E-SYD-SCH-1524 SHT08

19 TB2-39 TB7-39 CBCC-TB7-39 / TB2-39 CB-B-TB2-39 / TB7-39 NO CONTACT 5257PN100-MLW-E-SYD-SCH-1524 SHT08

20 TB2-40 TB7-40 CBCC-TB7-40 / TB2-40 CB-B-TB2-40 / TB7-40

21 SPARE

22 SPARE

23 SPARE

24 SPARE

52 2 01 1052 2-152 2-189BE2 5CX2.5 1 35 1 TB4-19 TB7-19 2-189BE2-TB7-19 / TB4-19 2-152-TB4-19 / TB7-19 CB LOCAL CLOSING I/L CPD KN17 SC51 SHT1252 2 01 1052 2-152 2-189BE2 5CX2.5 1 35 1 TB4-19 TB7-19 2-189BE2-TB7-19 / TB4-19 2-152-TB4-19 / TB7-19 CB LOCAL CLOSING I/L CPD KN17 SC51 SHT12

2 TB4-42 TB7-20 2-189BE2-TB7-20 / TB4-42 2-152-TB4-42 / TB7-20 CPD KN17 SC51 SHT12

3 SPARE

4 SPARE

5 SPARE

201-BUS COUPLER_05.09.2011 Page 8 of 18 Cables within SWYD

Page 9: 201-BUS COUPLER_05.09

VVG

PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW) Date Revision

OWNERS CONSULTANTL&T S&L 31.08.2011 01

EPC CONTRACTORL&T POWER, VADODARA VVG

CONTRACTORS CONSULTANTDCPL, KOLKATA

EBOP CONTRACTORAREVA T&D INDIA LIMITED

DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG

ACTUAL DRUM APPLICATION REF. DRAWING. NO :

FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.

CABLES WITHIN SWITCHYARD

AREVA T&D INDIA LTD.

NO. OF

RUNSSIZE

CABLE NO. EQUIPMENT DESIGNATION ESTIMATED

LENGTH

INTERCONNECTION DETAILSSL.

NO

Prepared by

ROUTING DETAILS

Approved by

Ferrule Nos.

Checked by

INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)

53 2 01 1053 2-152 2-189AE2 5CX2.5 1 65 1 TB4-20 TB7-19 2-189AE2-TB7-19 / TB4-20 2-152-TB4-20 / TB7-19 CB LOCAL CLOSING I/L CPD KN17 SC51 SHT12

2 TB4-42 TB7-20 2-189AE2-TB7-20 / TB4-42 2-152-TB4-42 / TB7-20 CPD KN17 SC51 SHT12

3 SPARE

4 SPARE

5 SPARE 5 SPARE

54 2 01 1054 2-1 89A 2-1 89AE1 5CX2.5 1 14 1 TB3-24 TB1-3 2-1 89AE1-TB1-3 / TB3-24 2-1 89A-TB3-24 / TB1-3 DC, I/L CPD KN17 SC65 SHT10

2 TB3-25 TB1-4 2-1 89AE1-TB1-4 / TB3-25 2-1 89A-TB3-25 / TB1-4 X- spare TB shall be identified at site CPD KN17 SC65 SHT10

3 TB1-1 TB1-1 2-1 89AE1-TB1-1 / TB1-1 2-1 89A-TB1-1 / TB1-1 CPD KN17 SC51 SHT14

4 TB1-2 TB1-2 2-1 89AE1-TB1-2 / TB1-2 2-1 89A-TB1-2 / TB1-2 CPD KN17 SC51 SHT14

5 SPARE

55 2 01 1055 2-1 89B 2-1 89BE1 5CX2.5 1 14 1 TB3-24 TB1-3 2-1 89BE1-TB1-3 / TB3-24 2-1 89B-TB3-24 / TB1-3 DC, I/L CPD KN17 SC65 SHT11

2 TB3-25 TB1-4 2-1 89BE1-TB1-4 / TB3-25 2-1 89B-TB3-25 / TB1-4 CPD KN17 SC65 SHT11

3 TB1-1 TB1-1 2-1 89BE1-TB1-1 / TB1-1 2-1 89B-TB1-1 / TB1-1 CPD KN17 SC65 SHT11

4 TB1-2 TB1-2 2-1 89BE1-TB1-2 / TB1-2 2-1 89B-TB1-2 / TB1-2 CPD KN17 SC51 SHT14

5 SPARE CPD KN17 SC51 SHT14

56 2 01 1056 2-1 89A 2-1 89AE2 5CX2.5 1 14 1 TB4-48 TB1-3 2-1 89AE2-TB1-3 / TB4-48 2-1 89A-TB4-48 / TB1-3 DC, I/L CPD KN17 SC65 SHT10

2 TB4-49 TB1-4 2-1 89AE2-TB1-4 / TB4-49 2-1 89A-TB4-49 / TB1-4 CPD KN17 SC65 SHT10

3 TB1-1 TB1-1 2-1 89AE2-TB1-1 / TB1-1 2-1 89A-TB1-1 / TB1-1 CPD KN17 SC51 SHT14

4 TB1-2 TB1-2 2-1 89AE2-TB1-2 / TB1-2 2-1 89A-TB1-2 / TB1-2 CPD KN17 SC51 SHT14

5 SPARE

57 2 01 1057 2-1 89B 2-1 89BE2 5CX2.5 1 14 1 TB4-48 TB1-3 2-1 89BE2-TB1-3 / TB4-48 2-1 89B-TB4-48 / TB1-3 DC, I/L

2 TB4-49 TB1-4 2-1 89BE2-TB1-4 / TB4-49 2-1 89B-TB4-49 / TB1-4 CPD KN17 SC65 SHT11 2 TB4-49 TB1-4 2-1 89BE2-TB1-4 / TB4-49 2-1 89B-TB4-49 / TB1-4 CPD KN17 SC65 SHT11

3 TB1-1 TB1-1 2-1 89BE2-TB1-1 / TB1-1 2-1 89B-TB1-1 / TB1-1 CPD KN17 SC65 SHT11

4 TB1-2 TB1-2 2-1 89BE2-TB1-2 / TB1-2 2-1 89B-TB1-2 / TB1-2 CPD KN17 SC51 SHT14

5 SPARE X-SPARE TB SHALL BE ARRANGED AT SITE CPD KN17 SC51 SHT14

58 2 01 1058 2-1 89A 2-1 89AE1 5CX2.5 1 14 1 TB3-21 TB6-1 2-1 89AE1-TB6-1 / TB3-21 2-1 89A-TB3-21 / TB6-1 DI CPD KN17 SC65 SHT08

2 TB3-22 TB6-2 2-1 89AE1-TB6-2 / TB3-22 2-1 89A-TB3-22 / TB6-2 CPD KN17 SC65 SHT08

3 TB3-23 TB7-18 2-1 89AE1-TB7-18 / TB3-23 2-1 89A-TB3-23 / TB7-18 CPD KN17 SC65 SHT08

4 SPARE

5 SPARE

59 2 01 1059 2-1 89B 2-1 89BE1 5CX2.5 1 14 1 TB3-21 TB6-1 2-1 89BE1-TB6-1 / TB3-21 2-1 89B-TB3-21 / TB6-1 DI CPD KN17 SC65 SHT08

2 TB3-22 TB6-2 2-1 89BE1-TB6-2 / TB3-22 2-1 89B-TB3-22 / TB6-2 CPD KN17 SC65 SHT08

3 TB3-23 TB7-18 2-1 89BE1-TB7-18 / TB3-23 2-1 89B-TB3-23 / TB7-18 CPD KN17 SC65 SHT08

4 SPARE

5 SPARE

60 2 01 1060 2-1 89A 2-1 89AE2 5CX2.5 1 14 1 TB4-45 TB6-1 2-1 89AE2-TB6-1 / TB4-45 2-1 89A-TB4-45 / TB6-1 DI CPD KN17 SC65 SHT08

2 TB4-46 TB6-2 2-1 89AE2-TB6-2 / TB4-46 2-1 89A-TB4-46 / TB6-2 CPD KN17 SC65 SHT08

3 TB4-47 TB7-18 2-1 89AE2-TB7-18 / TB4-47 2-1 89A-TB4-47 / TB7-18 CPD KN17 SC65 SHT08

4 SPARE

5 SPARE 5 SPARE

61 2 01 1061 2-1 89B 2-1 89BE2 5CX2.5 1 14 1 TB4-45 TB6-1 2-1 89BE2-TB6-1 / TB4-45 2-1 89B-TB4-45 / TB6-1 DI CPD KN17 SC65 SHT08

2 TB4-46 TB6-2 2-1 89BE2-TB6-2 / TB4-46 2-1 89B-TB4-46 / TB6-2 CPD KN17 SC65 SHT08

3 TB4-47 TB7-18 2-1 89BE2-TB7-18 / TB4-47 2-1 89B-TB4-47 / TB7-18 CPD KN17 SC65 SHT08

4 SPARE

5 SPARE

62 2 01 2062 2- B189 2- B189E 5CX2.5 1 14 1 TB4-45 TB1-3 2- B189E-TB1-3 / TB3-21 2- B189-TB3-21 / TB1-3 DC, I/L CPD KN17 SC65 SHT11

2 TB4-46 TB1-4 2- B189E-TB1-4 / TB3-22 2- B189-TB3-22 / TB1-4 CPD KN17 SC65 SHT11

3 TB1-1 TB1-1 2- B189E-TB1-1 / TB3-23 2- B189-TB3-23 / TB1-1 CPD KN17 SC51 CHT15

4 TB1-2 TB1-2 2- B189E-TB1-2 / SPARE 2- B189-SPARE / TB1-2 CPD KN17 SC51 CHT15

5 SPARE

63 2 01 2063 2- B189 2- B189E 5CX2.5 1 14 1 TB3-21 TB6-1 2- B189E-TB6-1 / TB3-21 2- B189-TB3-21 / TB6-1 DI CPD KN17 SC65 SHT09

2 TB3-22 TB6-2 2- B189E-TB6-2 / TB3-22 2- B189-TB3-22 / TB6-2 CPD KN17 SC65 SHT09

3 TB3-23 TB7-18 2- B189E-TB7-18 / TB3-23 2- B189-TB3-23 / TB7-18 CPD KN17 SC65 SHT09

4 SPARE

5 SPARE

64 2 01 2064 2- B289 2- B289E 5CX2.5 1 14 1 TB4-45 TB1-3 2- B289E-TB1-3 / TB4-45 2- B289-TB4-45 / TB1-3 DC, I/L CPD KN17 SC65 SHT12

2 TB4-46 TB1-4 2- B289E-TB1-4 / TB4-46 2- B289-TB4-46 / TB1-4 CPD KN17 SC65 SHT12

3 TB1-1 TB1-1 2- B289E-TB1-1 / TB1-1 2- B289-TB1-1 / TB1-1 CPD KN17 SC51 SHT153 TB1-1 TB1-1 2- B289E-TB1-1 / TB1-1 2- B289-TB1-1 / TB1-1 CPD KN17 SC51 SHT15

4 TB1-2 TB1-2 2- B289E-TB1-2 / TB1-2 2- B289-TB1-2 / TB1-2 CPD KN17 SC51 SHT15

5 SPARE

201-BUS COUPLER_05.09.2011 Page 9 of 18 Cables within SWYD

Page 10: 201-BUS COUPLER_05.09

VVG

PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW) Date Revision

OWNERS CONSULTANTL&T S&L 31.08.2011 01

EPC CONTRACTORL&T POWER, VADODARA VVG

CONTRACTORS CONSULTANTDCPL, KOLKATA

EBOP CONTRACTORAREVA T&D INDIA LIMITED

DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG

ACTUAL DRUM APPLICATION REF. DRAWING. NO :

FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.

CABLES WITHIN SWITCHYARD

AREVA T&D INDIA LTD.

NO. OF

RUNSSIZE

CABLE NO. EQUIPMENT DESIGNATION ESTIMATED

LENGTH

INTERCONNECTION DETAILSSL.

NO

Prepared by

ROUTING DETAILS

Approved by

Ferrule Nos.

Checked by

INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)

65 2 01 2065 2- B289 2- B289E 5CX2.5 1 14 1 TB3-21 TB6-1 2- B289E-TB6-1 / TB3-21 2- B289-TB3-21 / TB6-1 DI CPD KN17 SC65 SHT09

2 TB3-22 TB6-2 2- B289E-TB6-2 / TB3-22 2- B289-TB3-22 / TB6-2 CPD KN17 SC65 SHT09

3 TB3-23 TB7-18 2- B289E-TB7-18 / TB3-23 2- B289-TB3-23 / TB7-18 CPD KN17 SC65 SHT09

4 SPARE

5 SPARE

201-BUS COUPLER_05.09.2011 Page 10 of 18 Cables within SWYD

Page 11: 201-BUS COUPLER_05.09

INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)

VVG

PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW)Date Revision

OWNERS CONSULTANTL&T S&L 31.08.2011 01

EPC CONTRACTORL&T POWER, VADODARA VVG

CONTRACTORS CONSULTANTDCPL, KOLKATA

EBOP CONTRACTORAREVA T&D INDIA LIMITED

DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG

ACTUAL DRUM APPLICATION REMARK REF. DRAWING. NO :

FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.

CABLES BETWEEN SWITCHYARD TO KIOSK-CR

Protection PANEL -- Protection PANEL--

1 2 01 2001 2-1 B1CVT JB P1 10CX2.5 1 73 1,2 TB1-1 TB1-17 P1-TB1-17 / TB1-1 2-1 B1CVT JB-TB1-1 / TB1-17 WDG-1 CPD KN17 SC51 SH07

3,4 TB1-4 TB1-19 P1-TB1-19 / TB1-4 2-1 B1CVT JB-TB1-4 / TB1-19 CPD KN17 SC51 SH07

5,6 TB1-7 TB1-21 P1-TB1-21 / TB1-7 2-1 B1CVT JB-TB1-7 / TB1-21 CPD KN17 SC51 SH07

7,8 TB1-9 TB1-23 P1-TB1-23 / TB1-9 2-1 B1CVT JB-TB1-9 / TB1-23 CPD KN17 SC51 SH07

9,10 SPARE

EQUIPMENT DESIGNATIONSL.

NO

Prepared by

Checked by

CABLE NO.

Approved byAREVA T&D INDIA LTD.

NO. OF

RUNSSIZE

INTERCONNECTION DETAILSESTIMATED

LENGTHROUTING DETAILS

Ferrule Nos.

9,10 SPARE

2 2 01 2002 2-1 B1CVT JB P1 10CX2.5 1 73 1,2 TB2-1 TB1-25 P1-TB1-25 / TB2-1 2-1 B1CVT JB-TB2-1 / TB1-25 WDG-2 CPD KN17 SC51 SH07

3,4 TB2-4 TB1-27 P1-TB1-27 / TB2-4 2-1 B1CVT JB-TB2-4 / TB1-27 CPD KN17 SC51 SH07

5,6 TB2-7 TB1-29 P1-TB1-29 / TB2-7 2-1 B1CVT JB-TB2-7 / TB1-29 CPD KN17 SC51 SH07

7,8 TB2-9 TB1-31 P1-TB1-31 / TB2-9 2-1 B1CVT JB-TB2-9 / TB1-31 CPD KN17 SC51 SH07

9,10 SPARE

3 2 01 2003 2-1 B1CVT JB P1 10CX2.5 1 73 1,2 TB3-1 TB1-33 P1-TB1-33 / TB3-1 2-1 B1CVT JB-TB3-1 / TB1-33 WDG-3 CPD KN17 SC51 SH07

3,4 TB3-4 TB1-35 P1-TB1-35 / TB3-4 2-1 B1CVT JB-TB3-4 / TB1-35 CPD KN17 SC51 SH07

5,6 TB3-7 TB1-37 P1-TB1-37 / TB3-7 2-1 B1CVT JB-TB3-7 / TB1-37 CPD KN17 SC51 SH07

7,8 TB3-9 TB1-39 P1-TB1-39 / TB3-9 2-1 B1CVT JB-TB3-9 / TB1-39 CPD KN17 SC51 SH07

9,10 SPARE

4 2 01 2004 2-1 B1CVT JB P1 10CX2.5 2 73 1,2 TB4-1 TB1-41 P1-TB1-41 / TB4-1 2-1 B1CVT JB-TB4-1 / TB1-41 WDG-4 TARIFF METERING CPD KN17 SC51 SH07

3,4 TB4-4 TB1-43 P1-TB1-43 / TB4-4 2-1 B1CVT JB-TB4-4 / TB1-43 CPD KN17 SC51 SH07

5,6 TB4-7 TB1-45 P1-TB1-45 / TB4-7 2-1 B1CVT JB-TB4-7 / TB1-45 CPD KN17 SC51 SH07

7,8 TB4-9 TB1-47 P1-TB1-47 / TB4-9 2-1 B1CVT JB-TB4-9 / TB1-47 CPD KN17 SC51 SH07

9,10 SPARE

5 2 01 2005 2-1 B2CVT JB P1 10CX2.5 1 91 1,2 TB1-1 TB2-1 P1-TB2-1 / TB1-1 2-1 B2CVT JB-TB1-1 / TB2-1 WDG-1 CPD KN17 SC51 SH08

3,4 TB1-4 TB2-3 P1-TB2-3 / TB1-4 2-1 B2CVT JB-TB1-4 / TB2-3 CPD KN17 SC51 SH08

5,6 TB1-7 TB2-5 P1-TB2-5 / TB1-7 2-1 B2CVT JB-TB1-7 / TB2-5 CPD KN17 SC51 SH085,6 TB1-7 TB2-5 P1-TB2-5 / TB1-7 2-1 B2CVT JB-TB1-7 / TB2-5 CPD KN17 SC51 SH08

7,8 TB1-9 TB2-7 P1-TB2-7 / TB1-9 2-1 B2CVT JB-TB1-9 / TB2-7 CPD KN17 SC51 SH08

9,10 SPARE

6 2 01 2006 2-1 B2CVT JB P1 10CX2.5 1 91 1,2 TB2-1 TB2-9 P1-TB2-9 / TB2-1 2-1 B2CVT JB-TB2-1 / TB2-9 WDG-2 CPD KN17 SC51 SH08

3,4 TB2-4 TB2-11 P1-TB2-11 / TB2-4 2-1 B2CVT JB-TB2-4 / TB2-11 CPD KN17 SC51 SH08

5,6 TB2-7 TB2-13 P1-TB2-13 / TB2-7 2-1 B2CVT JB-TB2-7 / TB2-13 CPD KN17 SC51 SH08

7,8 TB2-9 TB2-15 P1-TB2-15 / TB2-9 2-1 B2CVT JB-TB2-9 / TB2-15 CPD KN17 SC51 SH08

9,10 SPARE

7 2 01 2007 2-1 B2CVT JB P1 10CX2.5 1 91 1,2 TB3-1 TB2-17 P1-TB2-17 / TB3-1 2-1 B2CVT JB-TB3-1 / TB2-17 WDG-3 CPD KN17 SC51 SH08

3,4 TB3-4 TB2-19 P1-TB2-19 / TB3-4 2-1 B2CVT JB-TB3-4 / TB2-19 CPD KN17 SC51 SH08

5,6 TB3-7 TB2-21 P1-TB2-21 / TB3-7 2-1 B2CVT JB-TB3-7 / TB2-21 CPD KN17 SC51 SH08

7,8 TB3-9 TB2-23 P1-TB2-23 / TB3-9 2-1 B2CVT JB-TB3-9 / TB2-23 CPD KN17 SC51 SH08

9,10 SPARE

8 2 01 2008 2-1 B2CVT JB P1 10CX2.5 2 91 1,2 TB4-1 TB2-25 P1-TB2-25 / TB4-1 2-1 B2CVT JB-TB4-1 / TB2-25 WDG-4 TARIFF METERING CPD KN17 SC51 SH08

3,4 TB4-4 TB2-27 P1-TB2-27 / TB4-4 2-1 B2CVT JB-TB4-4 / TB2-27 CPD KN17 SC51 SH08

5,6 TB4-7 TB2-29 P1-TB2-29 / TB4-7 2-1 B2CVT JB-TB4-7 / TB2-29 CPD KN17 SC51 SH08

7,8 TB4-9 TB2-31 P1-TB2-31 / TB4-9 2-1 B2CVT JB-TB4-9 / TB2-31 CPD KN17 SC51 SH08

9,10 SPARE

9 2 01 2009 2-1 CTA JB P1 10CX2.5 1 25 1,2 TB2-1 TB1-9 P1-TB1-9 / TB2-1 2-1 CTA JB-TB2-1 / TB1-9 BACK UP CPD KN17 SC51 SH099 2 01 2009 2-1 CTA JB P1 10CX2.5 1 25 1,2 TB2-1 TB1-9 P1-TB1-9 / TB2-1 2-1 CTA JB-TB2-1 / TB1-9 BACK UP CPD KN17 SC51 SH09

3,4 TB2-5 TB1-11 P1-TB1-11 / TB2-5 2-1 CTA JB-TB2-5 / TB1-11 CPD KN17 SC51 SH09

5,6 TB2-9 TB1-13 P1-TB1-13 / TB2-9 2-1 CTA JB-TB2-9 / TB1-13 CPD KN17 SC51 SH09

7,8 TB2-12 TB1-15 P1-TB1-15 / TB2-12 2-1 CTA JB-TB2-12 / TB1-15 CPD KN17 SC51 SH09

9,10

10 2 01 2010 P1 2-1 CB 24CX2.5 1 45 1,2 TB3-8 TB4-13 2-1 CB-TB4-13 / TB3-8 P1-TB3-8 / TB4-13 DC-1, TRIP-1, TCS CB CPD KN17 SC51 SH12

3,4 TB3-9 TB4-14 2-1 CB-TB4-14 / TB3-9 P1-TB3-9 / TB4-14 CPD KN17 SC51 SH12

5,6 TB3-10 TB4-22 2-1 CB-TB4-22 / TB3-10 P1-TB3-10 / TB4-22 CPD KN17 SC51 SH12

7,8 TB3-11 TB1-5 2-1 CB-TB1-5 / TB3-11 P1-TB3-11 / TB1-5 CPD KN17 SC51 SH12

9,10 TB3-12 TB2-5 2-1 CB-TB2-5 / TB3-12 P1-TB3-12 / TB2-5 CPD KN17 SC51 SH12

11,12 TB3-13 TB3-5 2-1 CB-TB3-5 / TB3-13 P1-TB3-13 / TB3-5 CPD KN17 SC51 SH12

13 TB3-14 TB1-6 2-1 CB-TB1-6 / TB3-14 P1-TB3-14 / TB1-6 CPD KN17 SC51 SH12

14 TB3-15 TB1-8 2-1 CB-TB1-8 / TB3-15 P1-TB3-15 / TB1-8 CPD KN17 SC51 SH12

15 TB3-16 TB2-6 2-1 CB-TB2-6 / TB3-16 P1-TB3-16 / TB2-6 CPD KN17 SC51 SH12

16 TB3-17 TB2-8 2-1 CB-TB2-8 / TB3-17 P1-TB3-17 / TB2-8 CPD KN17 SC51 SH12

17 TB3-18 TB3-6 2-1 CB-TB3-6 / TB3-18 P1-TB3-18 / TB3-6 CPD KN17 SC51 SH12

18 TB3-19 TB3-8 2-1 CB-TB3-8 / TB3-19 P1-TB3-19 / TB3-8 CPD KN17 SC51 SH12

19-24 SPARE

201-BUS COUPLER_05.09.2011 Page 11 of 18 Cables between SWYD to Kiosk-CR

Page 12: 201-BUS COUPLER_05.09

INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)

VVG

PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW)Date Revision

OWNERS CONSULTANTL&T S&L 31.08.2011 01

EPC CONTRACTORL&T POWER, VADODARA VVG

CONTRACTORS CONSULTANTDCPL, KOLKATA

EBOP CONTRACTORAREVA T&D INDIA LIMITED

DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG

ACTUAL DRUM APPLICATION REMARK REF. DRAWING. NO :

FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.

CABLES BETWEEN SWITCHYARD TO KIOSK-CR

EQUIPMENT DESIGNATIONSL.

NO

Prepared by

Checked by

CABLE NO.

Approved byAREVA T&D INDIA LTD.

NO. OF

RUNSSIZE

INTERCONNECTION DETAILSESTIMATED

LENGTHROUTING DETAILS

Ferrule Nos.

11 2 01 2011 P1 2-1 CB 24CX2.5 1 45 1,2 TB3-32 TB4-15 2-1 CB-TB4-15 / TB3-32 P1-TB3-32 / TB4-15 DC-2, TRIP-2, TCS, Manual Trip-2 CPD KN17 SC51 SH13

3,4 TB3-33 TB4-16 2-1 CB-TB4-16 / TB3-33 P1-TB3-33 / TB4-16 CPD KN17 SC51 SH13

5,6 TB3-34 TB4-24 2-1 CB-TB4-24 / TB3-34 P1-TB3-34 / TB4-24 CPD KN17 SC51 SH13

7,8 TB3-35 TB1-20 2-1 CB-TB1-20 / TB3-35 P1-TB3-35 / TB1-20 CPD KN17 SC51 SH13

9,10 TB3-36 TB2-20 2-1 CB-TB2-20 / TB3-36 P1-TB3-36 / TB2-20 CPD KN17 SC51 SH13

11,12 TB3-37 TB3-20 2-1 CB-TB3-20 / TB3-37 P1-TB3-37 / TB3-20 CPD KN17 SC51 SH1311,12 TB3-37 TB3-20 2-1 CB-TB3-20 / TB3-37 P1-TB3-37 / TB3-20 CPD KN17 SC51 SH13

13 TB3-38 TB1-21 2-1 CB-TB1-21 / TB3-38 P1-TB3-38 / TB1-21 CPD KN17 SC51 SH13

14 TB3-39 TB1-23 2-1 CB-TB1-23 / TB3-39 P1-TB3-39 / TB1-23 CPD KN17 SC51 SH13

15 TB3-40 TB2-21 2-1 CB-TB2-21 / TB3-40 P1-TB3-40 / TB2-21 CPD KN17 SC51 SH13

16 TB3-41 TB2-23 2-1 CB-TB2-23 / TB3-41 P1-TB3-41 / TB2-23 CPD KN17 SC51 SH13

17 TB3-42 TB3-21 2-1 CB-TB3-21 / TB3-42 P1-TB3-42 / TB3-21 CPD KN17 SC51 SH13

18 TB3-43 TB3-23 2-1 CB-TB3-23 / TB3-43 P1-TB3-43 / TB3-23 CPD KN17 SC51 SH13

19-24 SPARE CPD KN17 SC51 SH13

12 2 01 2012 P1 2-1 CB 7CX2.5 1 45 1,2 TB3-20 TB4-21 2-1 CB-TB4-21 / TB3-20 P1-TB3-20 / TB4-21 REMOTE CLOSING, MANL TRIP-1 CPD KN17 SC51 SH12

3,4 TB3-22 TB4-22 2-1 CB-TB4-22 / TB3-22 P1-TB3-22 / TB4-22 CPD KN17 SC51 SH12

5,6 TB3-23 TB4-18 2-1 CB-TB4-18 / TB3-23 P1-TB3-23 / TB4-18 CPD KN17 SC51 SH12

7 SPARE

13 2 01 2013 P1 2-1 CB 5CX2.5 1 45 1,2 TB3-44 TB4-24 2-1 CB-TB4-24 / TB3-44 P1-TB3-44 / TB4-24 TRIP-2 CPD KN17 SC51 SH13

3,4 TB3-45 TB4-23 2-1 CB-TB4-23 / TB3-45 P1-TB3-45 / TB4-23 CPD KN17 SC51 SH13

5 SPARE

14 2 01 2014 2-1 CTA JB P1 10CX2.5 1 25 1,2 TB5-1 TB1-1 P1-TB1-1 / TB5-1 2-1 CTA JB-TB5-1 / TB1-1 BUS BAR PROTECTION CPD KN17 SC51 SH19

3,4 TB5-5 TB1-3 P1-TB1-3 / TB5-5 2-1 CTA JB-TB5-5 / TB1-3 CPD KN17 SC51 SH193,4 TB5-5 TB1-3 P1-TB1-3 / TB5-5 2-1 CTA JB-TB5-5 / TB1-3 CPD KN17 SC51 SH19

5,6 TB5-9 TB1-5 P1-TB1-5 / TB5-9 2-1 CTA JB-TB5-9 / TB1-5 CPD KN17 SC51 SH19

7,8 TB5-11 TB1-7 P1-TB1-7 / TB5-11 2-1 CTA JB-TB5-11 / TB1-7 CPD KN17 SC51 SH19

9,10 SPARE

15 2 01 2015 2-1 CB P1 5CX2.5 1 45 1 TB5-3 TB5-13 P1-TB5-13 / TB5-3 2-1 CB-TB5-3 / TB5-13 DI FOR BB PROTECTION CPD KN17 SC51 SH20

2 TB7-4 TB5-14 P1-TB5-14 / TB7-4 2-1 CB-TB7-4 / TB5-14 CPD KN17 SC51 SH20

3 TB7-12 TB5-15 P1-TB5-15 / TB7-12 2-1 CB-TB7-12 / TB5-15 CPD KN17 SC51 SH20

4 SPARE

5 SPARE

16 2 01 2016 2-189A P1 5CX2.5 1 80 1 TB4-27 TB5-16 P1-TB5-16 / TB4-27 2-189A-TB4-27 / TB5-16 DI FOR BB PROTECTION CPD KN17 SC51 SH20

2 TB4-28 TB5-17 P1-TB5-17 / TB4-28 2-189A-TB4-28 / TB5-17 CPD KN17 SC51 SH20

3 TB3-4 TB5-18 P1-TB5-18 / TB3-4 2-189A-TB3-4 / TB5-18 CPD KN17 SC51 SH20

4 SPARE

5 SPARE

17 2 01 2017 2-189B P1 5CX2.5 1 55 1 TB4-27 TB5-19 P1-TB5-19 / TB4-27 2-189B-TB4-27 / TB5-19 DI FOR BB PROTECTION CPD KN17 SC51 SH20

2 TB4-28 TB5-20 P1-TB5-20 / TB4-28 2-189B-TB4-28 / TB5-20 CPD KN17 SC51 SH20

3 TB3-4 TB5-21 P1-TB5-21 / TB3-4 2-189B-TB3-4 / TB5-21 CPD KN17 SC51 SH20

4 SPARE

5 SPARE5 SPARE

18 2 01 2018 BB2 P1 5CX2.5 1 100 1,2 TB1-13 TB5-11 P1-TB5-11 / TB1-13 BB2-TB1-13 / TB5-11 DC SUPPLY CPD KN17 SC59 SH04

3,4 TB1-14 TB5-12 P1-TB5-12 / TB1-14 BB2-TB1-14 / TB5-12 CPD KN17 SC51 SH20

5 SPARE

CONTROL PANEL

19 2 01 2019 2-1 CTA JB C1 10CX2.5 1 25 1,2 TB3-4 TB1-1 C1-TB1-1 / TB3-4 2-1 CTA JB-TB3-4 / TB1-1 METERING CPD KN17 SC65 SHT07

3,4 TB3-8 TB1-3 C1-TB1-3 / TB3-8 2-1 CTA JB-TB3-8 / TB1-3 CPD KN17 SC65 SHT07

5,6 TB3-12 TB1-5 C1-TB1-5 / TB3-12 2-1 CTA JB-TB3-12 / TB1-5 CPD KN17 SC65 SHT07

7,8 TB3-9 TB1-7 C1-TB1-7 / TB3-9 2-1 CTA JB-TB3-9 / TB1-7 CPD KN17 SC65 SHT07

9,10 SPARE

201-BUS COUPLER_05.09.2011 Page 12 of 18 Cables between SWYD to Kiosk-CR

Page 13: 201-BUS COUPLER_05.09

INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)

VVG

PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW)Date Revision

OWNERS CONSULTANTL&T S&L 31.08.2011 01

EPC CONTRACTORL&T POWER, VADODARA VVG

CONTRACTORS CONSULTANTDCPL, KOLKATA

EBOP CONTRACTORAREVA T&D INDIA LIMITED

DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG

ACTUAL DRUM APPLICATION REMARK REF. DRAWING. NO :

FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.

CABLES BETWEEN SWITCHYARD TO KIOSK-CR

EQUIPMENT DESIGNATIONSL.

NO

Prepared by

Checked by

CABLE NO.

Approved byAREVA T&D INDIA LTD.

NO. OF

RUNSSIZE

INTERCONNECTION DETAILSESTIMATED

LENGTHROUTING DETAILS

Ferrule Nos.

20 2 01 2020 C1 2-1 CB 19CX2.5 1 45 1 TB1C-7 TB5-9 2-1 CB-TB5-9 / TB1C-7 C1-TB1C-7 / TB5-9 DI OF CB & TROUBLES CPD KN17 SC65 SHT08

2 TB1P1-1 TB5-10 2-1 CB-TB5-10 / TB1P1-1 C1-TB1P1-1 / TB5-10 CPD KN17 SC65 SHT08

3 TB1P1-2 TB5-2 2-1 CB-TB5-2 / TB1P1-2 C1-TB1P1-2 / TB5-2 CPD KN17 SC65 SHT08

4 TB1P1-4 TB6-10 2-1 CB-TB6-10 / TB1P1-4 C1-TB1P1-4 / TB6-10 CPD KN17 SC65 SHT08

5 TB1P1-5 TB6-2 2-1 CB-TB6-2 / TB1P1-5 C1-TB1P1-5 / TB6-2 CPD KN17 SC65 SHT08

6 TB1P1-7 TB7-10 2-1 CB-TB7-10 / TB1P1-7 C1-TB1P1-7 / TB7-10 CPD KN17 SC65 SHT086 TB1P1-7 TB7-10 2-1 CB-TB7-10 / TB1P1-7 C1-TB1P1-7 / TB7-10 CPD KN17 SC65 SHT08

7 TB1P1-8 TB7-2 2-1 CB-TB7-2 / TB1P1-8 C1-TB1P1-8 / TB7-2 CPD KN17 SC65 SHT08

8 TB1P1-10 TB3-28 2-1 CB-TB3-28 / TB1P1-10 C1-TB1P1-10 / TB3-28 CPD KN17 SC65 SHT08

9 TB1P1-11 TB4-26 2-1 CB-TB4-26 / TB1P1-11 C1-TB1P1-11 / TB4-26 CPD KN17 SC65 SHT08

10 TB1P1-13 TB4-28 2-1 CB-TB4-28 / TB1P1-13 C1-TB1P1-13 / TB4-28 CPD KN17 SC65 SHT08

11 TB1P1-14 TB4-32 2-1 CB-TB4-32 / TB1P1-14 C1-TB1P1-14 / TB4-32 CPD KN17 SC65 SHT08

12 TB1P1-16 TB4-43 2-1 CB-TB4-43 / TB1P1-16 C1-TB1P1-16 / TB4-43 CPD KN17 SC65 SHT08

13 TB1P1-17 TB4-34 2-1 CB-TB4-34 / TB1P1-17 C1-TB1P1-17 / TB4-34 CPD KN17 SC65 SHT08

14 TB1P1-19 TB4-33 2-1 CB-TB4-33 / TB1P1-19 C1-TB1P1-19 / TB4-33 CPD KN17 SC65 SHT08

15-19 SPARE

21 2 01 2021 2-1 89A C1 14CX2.5 1 80 1 TB1-9 TBOD1-9 C1-TBOD1-9 / TB1-9 2-1 89A-TB1-9 / TBOD1-9 DC, CONTROL, I/L CPD KN17 SC65 SHT10

2 TB1-10 TBOD1-10 C1-TBOD1-10 / TB1-10 2-1 89A-TB1-10 / TBOD1-10 CPD KN17 SC65 SHT10

3 TB1-11 TBOD1-12 C1-TBOD1-12 / TB1-11 2-1 89A-TB1-11 / TBOD1-12 CPD KN17 SC65 SHT10

4 TB1-3 TBOD1-14 C1-TBOD1-14 / TB1-3 2-1 89A-TB1-3 / TBOD1-14 CPD KN17 SC65 SHT10

5 TB1-6 TBOD1-13 C1-TBOD1-13 / TB1-6 2-1 89A-TB1-6 / TBOD1-13 CPD KN17 SC65 SHT10

6 TB3-24 TBOD1-16 C1-TBOD1-16 / TB3-24 2-1 89A-TB3-24 / TBOD1-16 CPD KN17 SC65 SHT10

7 TB3-25 TBOD1-15 C1-TBOD1-15 / TB3-25 2-1 89A-TB3-25 / TBOD1-15 CPD KN17 SC65 SHT10

8 TB4-48 TBOD1-19 C1-TBOD1-19 / TB4-48 2-1 89A-TB4-48 / TBOD1-19 CPD KN17 SC65 SHT10

9 TB4-49 TBOD1-21 C1-TBOD1-21 / TB4-49 2-1 89A-TB4-49 / TBOD1-21 CPD KN17 SC65 SHT10

10 TB1-1 TB10-1 C1-TB10-1 / TB1-1 2-1 89A-TB1-1 / TB10-1 CPD KN17 SC51 SHT14

11 TB1-2 TB10-2 C1-TB10-2 / TB1-2 2-1 89A-TB1-2 / TB10-2 CPD KN17 SC51 SHT14

12-14 SPARE X-SPARE TB SHALL BE ARRANGED AT SITE

CB

DC SUPPLY TO BE

WIRED FROM P1

PANEL

12-14 SPARE X-SPARE TB SHALL BE ARRANGED AT SITE

22 2 01 2022 2-1 89B C1 14CX2.5 1 55 1 TB1-9 TBOE1-1 C1-TBOE1-1 / TB1-9 2-1 89B-TB1-9 / TBOE1-1 DC, CONTROL, I/L CPD KN17 SC65 SHT11

2 TB1-10 TBOE1-2 C1-TBOE1-2 / TB1-10 2-1 89B-TB1-10 / TBOE1-2 CPD KN17 SC65 SHT11

3 TB1-11 TBOE1-4 C1-TBOE1-4 / TB1-11 2-1 89B-TB1-11 / TBOE1-4 CPD KN17 SC65 SHT11

4 TB1-3 TBOE1-6 C1-TBOE1-6 / TB1-3 2-1 89B-TB1-3 / TBOE1-6 CPD KN17 SC65 SHT11

5 TB1-6 TBOE1-5 C1-TBOE1-5 / TB1-6 2-1 89B-TB1-6 / TBOE1-5 CPD KN17 SC65 SHT11

6 TB3-24 TBOE1-8 C1-TBOE1-8 / TB3-24 2-1 89B-TB3-24 / TBOE1-8 CPD KN17 SC65 SHT11

7 TB3-25 TBOE1-7 C1-TBOE1-7 / TB3-25 2-1 89B-TB3-25 / TBOE1-7 CPD KN17 SC65 SHT11

8 TB4-48 TBOE1-10 C1-TBOE1-10 / TB4-48 2-1 89B-TB4-48 / TBOE1-10 CPD KN17 SC65 SHT11

9 TB4-49 TBOE1-9 C1-TBOE1-9 / TB4-49 2-1 89B-TB4-49 / TBOE1-9 CPD KN17 SC65 SHT11

10 TB1-1 TB10-3 C1-TB10-3 / TB1-1 2-1 89B-TB1-1 / TB10-3 CPD KN17 SC51 SHT14

11 TB1-2 TB10-4 C1-TB10-4 / TB1-2 2-1 89B-TB1-2 / TB10-4 CPD KN17 SC51 SHT14

12-14 SPARE

23 2 01 2023 2-1 89A C1 14CX2.5 1 80 1 TB3-1 TB1C-9 C1-TB1C-9 / TB3-1 2-1 89A-TB3-1 / TB1C-9 DI OF ISO & E/S CPD KN17 SC65 SHT08

2 TB3-2 TB1P1-20 C1-TB1P1-20 / TB3-2 2-1 89A-TB3-2 / TB1P1-20 CPD KN17 SC65 SHT08

3 TB4-26 TB1P1-22 C1-TB1P1-22 / TB4-26 2-1 89A-TB4-26 / TB1P1-22 CPD KN17 SC65 SHT08

DC SUPPLY TO BE

WIRED FROM P1

PANEL

4 TB1-14 TB1O1-1 C1-TB1O1-1 / TB1-14 2-1 89A-TB1-14 / TB1O1-1 CPD KN17 SC65 SHT08

5 TB1-13 TB1O1-2 C1-TB1O1-2 / TB1-13 2-1 89A-TB1-13 / TB1O1-2 CPD KN17 SC65 SHT08

6 TB3-21 TB1C-10 C1-TB1C-10 / TB3-21 2-1 89A-TB3-21 / TB1C-10 CPD KN17 SC65 SHT08

7 TB3-22 TB1O1-4 C1-TB1O1-4 / TB3-22 2-1 89A-TB3-22 / TB1O1-4 CPD KN17 SC65 SHT08

8 TB3-23 TB1O1-5 C1-TB1O1-5 / TB3-23 2-1 89A-TB3-23 / TB1O1-5 CPD KN17 SC65 SHT08

9 TB4-45 TB1C-11 C1-TB1C-11 / TB4-45 2-1 89A-TB4-45 / TB1C-11 CPD KN17 SC65 SHT08

10 TB4-46 TB1O1-7 C1-TB1O1-7 / TB4-46 2-1 89A-TB4-46 / TB1O1-7 CPD KN17 SC65 SHT08

11 TB4-47 TB1O1-8 C1-TB1O1-8 / TB4-47 2-1 89A-TB4-47 / TB1O1-8 CPD KN17 SC65 SHT08

12-14 SPARE

24 2 01 2024 2-1 89B C1 14CX2.5 1 55 1 TB3-1 TB1C-12 C1-TB1C-12 / TB3-1 2-1 89B-TB3-1 / TB1C-12 DI OF ISO & E/S CPD KN17 SC65 SHT08

2 TB3-2 TB1O1-10 C1-TB1O1-10 / TB3-2 2-1 89B-TB3-2 / TB1O1-10 CPD KN17 SC65 SHT08

3 TB4-26 TB1O1-11 C1-TB1O1-11 / TB4-26 2-1 89B-TB4-26 / TB1O1-11 CPD KN17 SC65 SHT08

4 TB1-14 TB1O1-13 C1-TB1O1-13 / TB1-14 2-1 89B-TB1-14 / TB1O1-13 CPD KN17 SC65 SHT08

5 TB1-13 TB1O1-14 C1-TB1O1-14 / TB1-13 2-1 89B-TB1-13 / TB1O1-14 CPD KN17 SC65 SHT08

6 TB3-21 TB1C-13 C1-TB1C-13 / TB3-21 2-1 89B-TB3-21 / TB1C-13 CPD KN17 SC65 SHT08

7 TB3-22 TB1O1-16 C1-TB1O1-16 / TB3-22 2-1 89B-TB3-22 / TB1O1-16 CPD KN17 SC65 SHT08

8 TB3-23 TB1O1-17 C1-TB1O1-17 / TB3-23 2-1 89B-TB3-23 / TB1O1-17 CPD KN17 SC65 SHT08

9 TB4-45 TB1C-14 C1-TB1C-14 / TB4-45 2-1 89B-TB4-45 / TB1C-14 CPD KN17 SC65 SHT08

10 TB4-46 TB1O1-19 C1-TB1O1-19 / TB4-46 2-1 89B-TB4-46 / TB1O1-19 CPD KN17 SC65 SHT08

11 TB4-47 TB1O1-20 C1-TB1O1-20 / TB4-47 2-1 89B-TB4-47 / TB1O1-20 CPD KN17 SC65 SHT0811 TB4-47 TB1O1-20 C1-TB1O1-20 / TB4-47 2-1 89B-TB4-47 / TB1O1-20 CPD KN17 SC65 SHT08

12-14 SPARE

201-BUS COUPLER_05.09.2011 Page 13 of 18 Cables between SWYD to Kiosk-CR

Page 14: 201-BUS COUPLER_05.09

INTERCONNECTION CABLE DETAILS FOR �220KV BUS COUPLER (BAY #01)

VVG

PROJECT SHREE SINGAJI THERMAL POWER PROJECT, STAGE-I (2X600MW)Date Revision

OWNERS CONSULTANTL&T S&L 31.08.2011 01

EPC CONTRACTORL&T POWER, VADODARA VVG

CONTRACTORS CONSULTANTDCPL, KOLKATA

EBOP CONTRACTORAREVA T&D INDIA LIMITED

DOCUMENT NO.5257PN100 - MLW - E - SYD - INT - 0203-BAY 201 NAG

ACTUAL DRUM APPLICATION REMARK REF. DRAWING. NO :

FROM TO LENGTH DETAILS CORE FROM TO FROM TO SHEET NO.

CABLES BETWEEN SWITCHYARD TO KIOSK-CR

EQUIPMENT DESIGNATIONSL.

NO

Prepared by

Checked by

CABLE NO.

Approved byAREVA T&D INDIA LTD.

NO. OF

RUNSSIZE

INTERCONNECTION DETAILSESTIMATED

LENGTHROUTING DETAILS

Ferrule Nos.

25 2 01 2025 2- B189 C1 14CX2.5 1 70 1 TB1-9 TBOE1-11 C1-TBOE1-11 / TB1-9 2- B189-TB1-9 / TBOE1-11 DC, CONTROL, I/L CPD KN17 SC65 SHT11

2 TB1-10 TB0E1-12 C1-TB0E1-12 / TB1-10 2- B189-TB1-10 / TB0E1-12 CPD KN17 SC65 SHT11

3 TB1-11 TB0E1-14 C1-TB0E1-14 / TB1-11 2- B189-TB1-11 / TB0E1-14 CPD KN17 SC65 SHT11

4 TB1-3 TB0E1-15 C1-TB0E1-15 / TB1-3 2- B189-TB1-3 / TB0E1-15 CPD KN17 SC65 SHT11

5 TB1-6 TB0E1-16 C1-TB0E1-16 / TB1-6 2- B189-TB1-6 / TB0E1-16 CPD KN17 SC65 SHT11

6 TB4-45 TB0E1-19 C1-TB0E1-19 / TB4-45 2- B189-TB4-45 / TB0E1-19 CPD KN17 SC65 SHT116 TB4-45 TB0E1-19 C1-TB0E1-19 / TB4-45 2- B189-TB4-45 / TB0E1-19 CPD KN17 SC65 SHT11

7 TB4-46 TB0E1-21 C1-TB0E1-21 / TB4-46 2- B189-TB4-46 / TB0E1-21 CPD KN17 SC65 SHT11

8 TB1-1 TB10-5 C1-TB10-5 / TB1-1 2- B189-TB1-1 / TB10-5 CPD KN17 SC51 SHT15

9 TB1-2 TB10-6 C1-TB10-6 / TB1-2 2- B189-TB1-2 / TB10-6 CPD KN17 SC51 SHT15

10 SPARE

11 SPARE

12 SPARE

13 SPARE

14 SPARE

26 2 01 2026 2-B189 C1 10CX2.5 1 70 1 TB3-1 TB1C-18 C1-TB1C-18 / TB3-1 2-B189-TB3-1 / TB1C-18 DI OF ISO & E/S CPD KN17 SC65 SHT09

2 TB3-2 TB1N1-1 C1-TB1N1-1 / TB3-2 2-B189-TB3-2 / TB1N1-1 CPD KN17 SC65 SHT09

3 TB4-26 TB1N1-2 C1-TB1N1-2 / TB4-26 2-B189-TB4-26 / TB1N1-2 CPD KN17 SC65 SHT09

4 TB1-14 TB1N1-4 C1-TB1N1-4 / TB1-14 2-B189-TB1-14 / TB1N1-4 CPD KN17 SC65 SHT09

5 TB1-13 TB1N1-5 C1-TB1N1-5 / TB1-13 2-B189-TB1-13 / TB1N1-5 CPD KN17 SC65 SHT09

6 TB3-21 TB1C-19 C1-TB6-1 / TB3-21 2-B189-TB3-21 / TB6-1 CPD KN17 SC65 SHT09

7 TB3-22 TB1N1-7 C1-TB6-2 / TB3-22 2-B189-TB3-22 / TB6-2 CPD KN17 SC65 SHT09

8 TB3-23 TB1N1-8 C1-TB7-18 / TB3-23 2-B189-TB3-23 / TB7-18 CPD KN17 SC65 SHT09

9-10 SPARE

27 2 01 2027 2- B289 C1 14CX2.5 1 85 1 TB1-10 TBOF1-2 C1-TBOF1-2 / TB1-10 2- B289-TB1-10 / TBOF1-2 DC, CONTROL, I/L CPD KN17 SC65 SHT12

2 TB1-9 TBOF1-1 C1-TBOF1-1 / TB1-9 2- B289-TB1-9 / TBOF1-1 CPD KN17 SC65 SHT12

3 TB1-11 TBOF1-4 C1-TBOF1-4 / TB1-11 2- B289-TB1-11 / TBOF1-4 CPD KN17 SC65 SHT123 TB1-11 TBOF1-4 C1-TBOF1-4 / TB1-11 2- B289-TB1-11 / TBOF1-4 CPD KN17 SC65 SHT12

4 TB1-3 TBOF1-6 C1-TBOF1-6 / TB1-3 2- B289-TB1-3 / TBOF1-6 CPD KN17 SC65 SHT12

5 TB1-6 TBOF1-5 C1-TBOF1-5 / TB1-6 2- B289-TB1-6 / TBOF1-5 CPD KN17 SC65 SHT12

6 TB4-45 TBOF1-8 C1-TBOF1-8 / TB4-45 2- B289-TB4-45 / TBOF1-8 CPD KN17 SC65 SHT12

7 TB4-46 TBOF1-7 C1-TBOF1-7 / TB4-46 2- B289-TB4-46 / TBOF1-7 CPD KN17 SC65 SHT12

8 TB1-1 TB10-7 C1-TB10-7 / TB1-1 2- B289-TB1-1 / TB10-7 CPD KN17 SC51 SHT15

9 TB1-2 TB10-8 C1-TB10-8 / TB1-2 2- B289-TB1-2 / TB10-8 CPD KN17 SC51 SHT15

10 SPARE

11 SPARE

12 SPARE

13 SPARE

14 SPARE

28 2 01 2028 2- B289 C1 10CX2.5 1 85 1 TB3-1 TB1C-20 C1-TB1C-20 / TB3-1 2- B289-TB3-1 / TB1C-20 DI OF ISO & E/S CPD KN17 SC65 SHT09

2 TB3-2 TBIN1-10 C1-TBIN1-10 / TB3-2 2- B289-TB3-2 / TBIN1-10 CPD KN17 SC65 SHT09

3 TB4-26 TB1N1-11 C1-TB1N1-11 / TB4-26 2- B289-TB4-26 / TB1N1-11 CPD KN17 SC65 SHT09

4 TB1-14 TB1N1-13 C1-TB1N1-13 / TB1-14 2- B289-TB1-14 / TB1N1-13 CPD KN17 SC65 SHT09

5 TB1-13 TB1N1-14 C1-TB1N1-14 / TB1-13 2- B289-TB1-13 / TB1N1-14 CPD KN17 SC65 SHT09

6 TB3-21 TB1C-21 C1-TB1C-21 / TB3-21 2- B289-TB3-21 / TB1C-21 CPD KN17 SC65 SHT09

7 TB3-22 TB1N1-16 C1-TB1N1-16 / TB3-22 2- B289-TB3-22 / TB1N1-16 CPD KN17 SC65 SHT09

8 TB3-23 TB1N1-17 C1-TB1N1-17 / TB3-23 2- B289-TB3-23 / TB1N1-17 CPD KN17 SC65 SHT09

9-10 SPARE

Note: In isolator Panel following terminals to be added. 1. TB3:25-29 and TB4:49-53

Note: DC supply for iso and ISO/E/S shall be wired from P1 to C1, in the panel at site.(BUS WIRED AT SITE),TB10-spare TBs shall be arranged

201-BUS COUPLER_05.09.2011 Page 14 of 18 Cables between SWYD to Kiosk-CR