BRANCH JOINT INSTALLATION MANUALSelection of refrigerant piping size and use of Branch Joint
Prepare the pipe to be connected in the field.
Determine the piping sizes of each part from table 3, 4, 5.
Determine the branch joint from table 1.
When pipe is cut with a pipe cutter or the like remove burr, dust and foreign materials inside the pipe
and connect the pipe.
Always weld while flowing nitrogen, otherwise, the product may not operate due to sludge within the
pipe.
1
2
3
4
5
Table 1. Branch Join Kit
Table 2. Contents of branch joint kit
Branch Joint
ContentsGas side:1EA
Liquid side:1EA
Gas side:1EA
Liquid side:1EA1EA
Insulation Manual
Table 3. Branch pipe for connection between Outdoor Units
Outdoor Units
2
3
Branch Joint pipe
ARCNN20
ARCNN20,ARCNN30
Downward Indoor Unit total capacity
[kW(Btu/h)]
< 5.6 (19,100)
< 16 (54,600)
< 22.4 (76,400)
< 33 (112,600)
< 47 (160,400)
< 71 (242,300)
< 104 (354, 900)
104 (354,900)
6.35(1/4)
9.52(3/8)
9.52(3/8)
9.52(3/8)
12.7(1/2)
15.88(5/8)
19.05(3/4)
19.05(3/4)
12.7(1/2)
15.88(5/8)
19.05(3/4)
22.2(7/8)
28.58(9/8)
28.58(9/8)
34.9(13/8)
41.3(15/8)
Liquid pipe
[mm(inch)]
Gas pipe
[mm(inch)]
Table 4. Refrigerant pipe diameter from branch to branch (Fig1.- B,C,D)
Table 5. Between branching and Indoor Unit (Fig1 -a,b,c,d,e)
Indoor Unit capacity [kW(Btu/h)]
< 5.6(19,100)
< 16.0(54,600)
< 22.4(76,400)
6.35(1/4)
9.52(3/8)
9.52(3/8)
12.7(1/2)
15.88(5/8)
19.05(3/4)
Liquid pipe
[mm(inch)]
Gas pipe
[mm(inch)]
Models Gas pipe Liquid pipe
For example. Indicated 9.52 is the outer diameter(O.D..) of field jointed piping
[unit:mm]
ARBLN03321
ARBLN07121
ARBLN14521
ARBLN01621
I.D. 12.7
I.D. 15.88
I.D. 15.88
I.D. 15.88
I.D12.7
I.D12.7
I.D9.52I.D9.52
I.D9.52
I.D6.35
I.D6.35
I.D6.35
I.D19.05 I.D19.05
I.D19.05
O.D19.05O.D19.05
I.D12.7
I.D12.7
I.D15.88
I.D15.88
I.D22.2
I.D22.2I.D22.2
I.D25.4
I.D25.4
I.D12.7I.D12.7
I.D12.7
I.D6.35
I.D9.52
I.D9.52
I.D9.52
I.D6.35
I.D28.58
I.D28.58I.D28.58
I.D31.8
I.D31.8
I.D19.05
I.D22.2
O.D22.2
I.D15.88
I.D15.88
I.D12.7
I.D22.2
I.D19.05
O.D19.05
I.D12.7I.D15.88 I.D15.88
I.D15.88
I.D19.05
I.D19.05
I.D19.05
I.D12.7
I.D12.7
I.D9.52
O.D12.7
O.D12.7
I.D9.52
I.D6.35
I.D34.9 I.D41.3
I.D38.1
O.D22.2
I.D19.05
I.D15.88 I.D12.7
O.D15.88
I.D41.3
I.D38.1
I.D41.3
O.D38.1
O.D34.9I.D34.9
I.D34.9
I.D22.2
I.D28.58
I.D28.58I.D38.1
O.D28.58
I.D22.2
I.D19.05
I.D15.88I.D19.05
I.D22.2
I.D22.2
O.D19.05
O.D15.88
I.D12.7
I.D9.52
I.D19.05
I.D15.88I.D22.2
I.D12.7
I.D15.88
I.D19.05
O.D12.7
I.D9.52
I.D6.35
I.D19.05
O.D15.88
I.D28.58
O.D25.4
I.D34.9
O.D31.8
I.D12.7
O.D9.52
7/29/2019 2009 02 27 Installation Manual_y Branch_3850a25001k (1)
2/2
Figure1. Line Branch method
Insulation of Branch Joint
Fig. 2 Example Fig. 3 Example
Insulation material
(field spply)
Tape (field spply)
Lapped space of taping
Pipe cover
P/No.: 3850A25001K
Mount Liquid pipe 1 to pipe cover 2 in matching.Seal the joing section of pipe cover with inslatedsealing tape(field supply). (Refer to Fig. 2)
Apply the same procedures to the gas pipe also.
Note 1.
Note 2.
Apply insulation to all refrigerant piping (fieldsupply). When using the insulation materialsbeing marketed, employ heat resistant insulationmaterial (heat resistant temperature: 120C ormore)
As the pipe cover contracts slightly conducttaping in the field securely by providing lappedparts as shown in so that no gap will exit on thepiping cover and field supply insulation material.
Total pipe length = A+B+C+D+a+b+c+d+e 300m
: Outdoor Unit
: 1st branch (Y branch)
: Indoor Units
: Downward Indoor Unit
A
B
C
D
Total pipe length = A+B+C+D+a+b+c+d+e 300m
: Outdoor Unit
: 1st branch (Y branch)
: Indoor Units
: Downward Indoor Unit
A
B
C
D
Total pipe length = A+B+C+D+a+b+c+d+e 300m
Main
Sub
10m orless
A
B
C
D
E
: Outdoor Unit
: 1st branch (Y branch)
: Indoor Units
: Downward Indoor Unit
: Connection branch pipe between Outdoor Units: ARCNN20
Total pipe length = A+B+C+D+a+b+c+d+e 300m
A
B
C
D
E
F
10m orless
: Outdoor Unit
: 1st branch (Y branch)
: Indoor Units
: Downward Indoor Unit
: Connection branch pipe between Outdoor Units: ARCNN20
: Connection branch pipe between Outdoor Units: ARCNN30
Example) 5 Indoor Units connected Example) 5 Indoor Units connected Example) 5 Indoor Units connected Example) 5 Indoor Units connected
L50m
L150m
40m
h15m
L50m
L150m
40m 40m 40m
h15m
L50m
L150m
h15m
L50m
L150m
h15m
Longest p ipe length * Equivalent p ipe length
A+B+C+D+e 150m A+B+C+D+e 175m
Longest pipe length after 1st branch
B+C+D+e 40m
Difference in height(Outdoor Unit Indoor Unit)
H 50m (40m : Outdoor Unit is lower than Indoor Units)**
Difference in height (Indoor Unit Indoor Unit)
h 15m
L
l
H
h
Longest p ipe length * Equivalent p ipe length
A+B+C+D+e 150m A+B+C+D+e 175m
Longest pipe length after 1st branch
B+C+D+e 40m
Difference in height(Outdoor Unit Indoor Unit)
H 50m (40m : Outdoor Unit is lower than Indoor Units)**
Difference in height (Indoor Unit Indoor Unit)
h 15m
L
l
H
h
Longest p ipe length * Equivalent p ipe length
A+B+C+D+e 150m A+B+C+D+e 175m
Longest pipe length after 1st branch
B+C+D+e 40m
Difference in height(Outdoor Unit Indoor Unit)
H 50m (40m : Outdoor Unit is lower than Indoor Units)**
Difference in height (Indoor Unit Indoor Unit)
h 15m
L
l
H
h
Longest p ipe length * Equivalent p ipe length
A+B+C+D+e 150m A+B+C+D+e 175m
Longest pipe length after 1st branch
B+C+D+e 40m
Difference in height(Outdoor Unit Indoor Unit)
H 50m (40m : Outdoor Unit is lower than Indoor Units)**
Difference in height (Indoor Unit Indoor Unit)
h 15m
L
l
H
h
Insulation material
(field spply)
Tape (field spply)Liquid pipe