    BRANCH JOINT INSTALLATION MANUALSelection of refrigerant piping size and use of Branch Joint

    Prepare the pipe to be connected in the field.

    Determine the piping sizes of each part from table 3, 4, 5.

    Determine the branch joint from table 1.

    When pipe is cut with a pipe cutter or the like remove burr, dust and foreign materials inside the pipe

    and connect the pipe.

    Always weld while flowing nitrogen, otherwise, the product may not operate due to sludge within the

    pipe.

    1

    2

    3

    4

    5

    Table 1. Branch Join Kit

    Table 2. Contents of branch joint kit

    Branch Joint

    ContentsGas side:1EA

    Liquid side:1EA

    Gas side:1EA

    Liquid side:1EA1EA

    Insulation Manual

    Table 3. Branch pipe for connection between Outdoor Units

    Outdoor Units

    2

    3

    Branch Joint pipe

    ARCNN20

    ARCNN20,ARCNN30

    Downward Indoor Unit total capacity

    [kW(Btu/h)]

    < 5.6 (19,100)

    < 16 (54,600)

    < 22.4 (76,400)

    < 33 (112,600)

    < 47 (160,400)

    < 71 (242,300)

    < 104 (354, 900)

    104 (354,900)

    6.35(1/4)

    9.52(3/8)

    9.52(3/8)

    9.52(3/8)

    12.7(1/2)

    15.88(5/8)

    19.05(3/4)

    19.05(3/4)

    12.7(1/2)

    15.88(5/8)

    19.05(3/4)

    22.2(7/8)

    28.58(9/8)

    28.58(9/8)

    34.9(13/8)

    41.3(15/8)

    Liquid pipe

    [mm(inch)]

    Gas pipe

    [mm(inch)]

    Table 4. Refrigerant pipe diameter from branch to branch (Fig1.- B,C,D)

    Table 5. Between branching and Indoor Unit (Fig1 -a,b,c,d,e)

    Indoor Unit capacity [kW(Btu/h)]

    < 5.6(19,100)

    < 16.0(54,600)

    < 22.4(76,400)

    6.35(1/4)

    9.52(3/8)

    9.52(3/8)

    12.7(1/2)

    15.88(5/8)

    19.05(3/4)

    Liquid pipe

    [mm(inch)]

    Gas pipe

    [mm(inch)]

    Models Gas pipe Liquid pipe

    For example. Indicated 9.52 is the outer diameter(O.D..) of field jointed piping

    [unit:mm]

    ARBLN03321

    ARBLN07121

    ARBLN14521

    ARBLN01621

    I.D. 12.7

    I.D. 15.88

    I.D. 15.88

    I.D. 15.88

    I.D12.7

    I.D12.7

    I.D9.52I.D9.52

    I.D9.52

    I.D6.35

    I.D6.35

    I.D6.35

    I.D19.05 I.D19.05

    I.D19.05

    O.D19.05O.D19.05

    I.D12.7

    I.D12.7

    I.D15.88

    I.D15.88

    I.D22.2

    I.D22.2I.D22.2

    I.D25.4

    I.D25.4

    I.D12.7I.D12.7

    I.D12.7

    I.D6.35

    I.D9.52

    I.D9.52

    I.D9.52

    I.D6.35

    I.D28.58

    I.D28.58I.D28.58

    I.D31.8

    I.D31.8

    I.D19.05

    I.D22.2

    O.D22.2

    I.D15.88

    I.D15.88

    I.D12.7

    I.D22.2

    I.D19.05

    O.D19.05

    I.D12.7I.D15.88 I.D15.88

    I.D15.88

    I.D19.05

    I.D19.05

    I.D19.05

    I.D12.7

    I.D12.7

    I.D9.52

    O.D12.7

    O.D12.7

    I.D9.52

    I.D6.35

    I.D34.9 I.D41.3

    I.D38.1

    O.D22.2

    I.D19.05

    I.D15.88 I.D12.7

    O.D15.88

    I.D41.3

    I.D38.1

    I.D41.3

    O.D38.1

    O.D34.9I.D34.9

    I.D34.9

    I.D22.2

    I.D28.58

    I.D28.58I.D38.1

    O.D28.58

    I.D22.2

    I.D19.05

    I.D15.88I.D19.05

    I.D22.2

    I.D22.2

    O.D19.05

    O.D15.88

    I.D12.7

    I.D9.52

    I.D19.05

    I.D15.88I.D22.2

    I.D12.7

    I.D15.88

    I.D19.05

    O.D12.7

    I.D9.52

    I.D6.35

    I.D19.05

    O.D15.88

    I.D28.58

    O.D25.4

    I.D34.9

    O.D31.8

    I.D12.7

    O.D9.52

  • 7/29/2019 2009 02 27 Installation Manual_y Branch_3850a25001k (1)

    2/2

    Figure1. Line Branch method

    Insulation of Branch Joint

    Fig. 2 Example Fig. 3 Example

    Insulation material

    (field spply)

    Tape (field spply)

    Lapped space of taping

    Pipe cover

    P/No.: 3850A25001K

    Mount Liquid pipe 1 to pipe cover 2 in matching.Seal the joing section of pipe cover with inslatedsealing tape(field supply). (Refer to Fig. 2)

    Apply the same procedures to the gas pipe also.

    Note 1.

    Note 2.

    Apply insulation to all refrigerant piping (fieldsupply). When using the insulation materialsbeing marketed, employ heat resistant insulationmaterial (heat resistant temperature: 120C ormore)

    As the pipe cover contracts slightly conducttaping in the field securely by providing lappedparts as shown in so that no gap will exit on thepiping cover and field supply insulation material.

    Total pipe length = A+B+C+D+a+b+c+d+e 300m

    : Outdoor Unit

    : 1st branch (Y branch)

    : Indoor Units

    : Downward Indoor Unit

    A

    B

    C

    D

    Total pipe length = A+B+C+D+a+b+c+d+e 300m

    : Outdoor Unit

    : 1st branch (Y branch)

    : Indoor Units

    : Downward Indoor Unit

    A

    B

    C

    D

    Total pipe length = A+B+C+D+a+b+c+d+e 300m

    Main

    Sub

    10m orless

    A

    B

    C

    D

    E

    : Outdoor Unit

    : 1st branch (Y branch)

    : Indoor Units

    : Downward Indoor Unit

    : Connection branch pipe between Outdoor Units: ARCNN20

    Total pipe length = A+B+C+D+a+b+c+d+e 300m

    A

    B

    C

    D

    E

    F

    10m orless

    : Outdoor Unit

    : 1st branch (Y branch)

    : Indoor Units

    : Downward Indoor Unit

    : Connection branch pipe between Outdoor Units: ARCNN20

    : Connection branch pipe between Outdoor Units: ARCNN30

    Example) 5 Indoor Units connected Example) 5 Indoor Units connected Example) 5 Indoor Units connected Example) 5 Indoor Units connected

    L50m

    L150m

    40m

    h15m

    L50m

    L150m

    40m 40m 40m

    h15m

    L50m

    L150m

    h15m

    L50m

    L150m

    h15m

    Longest p ipe length * Equivalent p ipe length

    A+B+C+D+e 150m A+B+C+D+e 175m

    Longest pipe length after 1st branch

    B+C+D+e 40m

    Difference in height(Outdoor Unit Indoor Unit)

    H 50m (40m : Outdoor Unit is lower than Indoor Units)**

    Difference in height (Indoor Unit Indoor Unit)

    h 15m

    L

    l

    H

    h

    Longest p ipe length * Equivalent p ipe length

    A+B+C+D+e 150m A+B+C+D+e 175m

    Longest pipe length after 1st branch

    B+C+D+e 40m

    Difference in height(Outdoor Unit Indoor Unit)

    H 50m (40m : Outdoor Unit is lower than Indoor Units)**

    Difference in height (Indoor Unit Indoor Unit)

    h 15m

    L

    l

    H

    h

    Longest p ipe length * Equivalent p ipe length

    A+B+C+D+e 150m A+B+C+D+e 175m

    Longest pipe length after 1st branch

    B+C+D+e 40m

    Difference in height(Outdoor Unit Indoor Unit)

    H 50m (40m : Outdoor Unit is lower than Indoor Units)**

    Difference in height (Indoor Unit Indoor Unit)

    h 15m

    L

    l

    H

    h

    Longest p ipe length * Equivalent p ipe length

    A+B+C+D+e 150m A+B+C+D+e 175m

    Longest pipe length after 1st branch

    B+C+D+e 40m

    Difference in height(Outdoor Unit Indoor Unit)

    H 50m (40m : Outdoor Unit is lower than Indoor Units)**

    Difference in height (Indoor Unit Indoor Unit)

    h 15m

    L

    l

    H

    h

    Insulation material

    (field spply)

    Tape (field spply)Liquid pipe