    Standar PDE STP Chair PM PM Email NEC Reference

    429

    Jeff

    DesJarlais

    Diana

    Pappas

    Jordan Alan McGrath [email protected]

    430.102(A), Exception 3. An exception permits

    valve actuator motors to be provided with a

    warning marking and provision for locking if the

    valve will not be installed in sight of field

    disconnect means.

    429

    Jeff

    DesJarlais

    Diana

    Pappas

    Jordan Alan McGrath [email protected] 430.2. Defines Valve Actuator Motors.

    486

    Jake

    Killinger

    Bradley

    Schmidt

    Marcia

    Kawate [email protected]

    250.8. Establishes basic requirements for

    terminal connectors and means to connect

    equipment for grounding and bonding.

    489

    Jeff

    Hidaka

    Bradley

    Schmidt Patricia Sena [email protected]

    610.31. Section 610.31 (Runway Conductor

    Disconnecting Means) was revised to require

    the The provision for locking or adding a lock

    to the disconnecting means shall be installedon or at the switch or circuit breaker used as

    the disconnecting means and shall remain in

    place with or without the lock installed. Portable

    means for adding a lock to the switch or circuit

    breaker shall not be permitted as the means

    required to be installed at and remain with the

    equipment.

    mailto:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]
  • 7/31/2019 2008 NEC Changes - Copy

    2/22

  • 7/31/2019 2008 NEC Changes - Copy

    3/22

  • 7/31/2019 2008 NEC Changes - Copy

    4/22

    Standar PDE STP Chair PM PM Email NEC Reference

    639

    Lou

    Chavez

    Sarah

    Brooks Megan Cahill [email protected]

    725,130(B) exception 3. Listing of intrusion

    protection systems with bare, class 2

    conductors

    845

    Jeff

    Hidaka

    Bradley

    Schmidt Valara Davis [email protected]

    200.2(B). Requires that a neutral (grounded)

    system conductor be connected through

    terminals and not to use the enclosure as part

    of the current carrying path.

    891

    Robert

    Osborne

    Bradley

    Schmidt Tim Corder [email protected]

    110.20. Movement of enclosure environmental

    types from Article 430 to Article 110. Inclusion

    of switchboards, panelboards, industrial control

    panels, motor control centers and meter

    sockets.

    At the January 2006 ROP Meetings, UL staff

    and NEMA staff verified that Type 1 ratings had

    been required in practice, although the wording

    in some of the affected standards is not precise

    in stating this.

    891

    Robert

    Osborne

    Bradley

    Schmidt Tim Corder [email protected]

    200.2(B). Requires that a neutral (grounded)

    system conductor be connected throughterminals and not to use the enclosure as part

    of the current carrying path.

    891

    Robert

    Osborne

    Bradley

    Schmidt Tim Corder [email protected]

    519 (new section). New Article 519, "Control

    Systems for Permanent Amusement

    Attractions", was accepted by Panel 15 which

    opens the door for new categories of industrial

    control devices such as control panels for

    these systems.

    891

    Robert

    Osborne

    Bradley

    Schmidt Tim Corder [email protected]. Expanded requirements for capacity and

    Ratings of optional standby systems.

    mailto:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]
  • 7/31/2019 2008 NEC Changes - Copy

    5/22

    Standar PDE STP Chair PM PM Email NEC Reference

    1008

    Paul

    Barnhart

    Bradley

    Schmidt

    Esther

    Espinoza [email protected]

    700.9(D)(3). Added clause regarding control

    conductors between transfer equipment and

    the emergency generator.

    1008

    Paul

    Barnhart

    Bradley

    Schmidt Tim Corder [email protected]. Expanded requirements for capacity and

    Ratings of optional standby systems.

    1042

    Robert

    Wozniak Joe Musso Mitch Gold [email protected]

    406.11 Requires use of tamper resistant

    receptacles

    1042

    Robert

    Wozniak Joe Musso Mitch Gold [email protected]. Requires disconnecting means to be

    rated 125% of total of disconnected loads.

    1047

    Joe

    Murnane

    Bradley

    Schmidt Susan Malohn [email protected]

    517.18(B) and 517.19(B)(2). In critical care

    areas receptacles shall have an integral light

    indicating the receptacle is powered or be part

    of a listed headwall assembly that provides

    indication of power to each receptacle.

    1072

    Tom

    Cybula

    Diana

    Pappas

    Jordan Camille Alma [email protected]

    300.40. The change to the second paragraph

    of 300.40 provides a more defined connection

    requirement for shielding components to a

    grounding conductor, to a grounding busbar, or

    to a grounding electrode for shielded

    conductors in excess of 600 volts, rather than

    just that the shield be grounded.

    1072

    Tom

    Cybula

    Diana

    Pappas

    Jordan Camille Alma [email protected]

    310.13. Three additional, larger sizes ofconductors were added to Table 310.13D.

    Those sizes are as follows:1001 1250

    kcmil1251 1500 kcmil1501 2000 kcmil.

    1277

    Tom

    Cybula

    Diana

    Pappas

    Jordan Camille Alma [email protected]

    336.104. Added additional language which

    permits Type TC to be provided with nickel or

    nickel coated copper conductors.

    mailto:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]
  • 7/31/2019 2008 NEC Changes - Copy

    6/22

    Standar PDE STP Chair PM PM Email NEC Reference

    1569

    Tom

    Cybula

    Diana

    Pappas

    Jordan Camille Alma [email protected]

    330.104. Added additional language which

    permits Type MC to be provided with nickel or

    nickel coated copper conductors.

    1598 Ed Joseph

    Diana

    Pappas

    Jordan

    Heather

    Sakellariou [email protected]

    410.16(A)(3). Permits LED or fluorescent

    luminaires that qualify and are identified to be

    installed within the defined storage space of a

    clothes closet.

    1684

    George

    Walbrecht

    Diana

    Pappas

    Jordan Paul Lloret [email protected]

    300.7(B), FPN. Information on new Table

    355.44 for expansion characteristics for

    reinforced thermosetting resin conduit (RTRC)

    has been added.

    An expansion and contraction formula has

    been added to this FPN for aluminum conduit

    and aluminum electrical metallic tubing.

    1703

    Tim

    Zgonena

    Bradley

    Schmidt Susan Malohn [email protected]

    690.31(B). (B) Single-Conductor Cable. Single-

    conductor cable typeUSE-2, and single-

    conductor cable listed and labeled

    asphotovoltaic (PV) wire shall be permitted in

    exposed outdoorlocations in photovoltaicsource circuits for photovoltaicmodule

    interconnections within the photovoltaic

    array.Exception: Raceways shall be used when

    required by 690.31(A).

    1703

    Tim

    Zgonena

    Bradley

    Schmidt Susan Malohn [email protected]

    690.31(F). (F) Flexible, Fine-Stranded Cables.

    Flexible, fine strandedcables shall be

    terminated only with terminals,lugs, devices, or

    connectors that are identified and listed forsuch

    use.

    1703

    Tim

    Zgonena

    Bradley

    Schmidt Susan Malohn [email protected]

    690.33. (C) Type. The connectors shall be of

    the latching or lockingtype. Connectors that are

    readily accessible and that are used in circuits

    operating at over 30 volts, nominal, maximum

    system voltage for dc circuits, or 30 volts for

    accircuits, shall require a tool for opening

    mailto:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]
  • 7/31/2019 2008 NEC Changes - Copy

    7/22

    Standar PDE STP Chair PM PM Email NEC Reference

    1703

    Tim

    Zgonena

    Bradley

    Schmidt Susan Malohn [email protected]

    690.33. (E) Interruption of Circuit. Connectors

    shall be either (1)or (2): (1) Be rated for

    interrupting current without hazard to the

    operator.(2) Be a type that requires the use of

    a tool to open and marked Do Not Disconnect

    Under Load or Not for Current Interrupting.

    1703

    Tim

    Zgonena

    Bradley

    Schmidt Susan Malohn

    690.35. (C) Ground-Fault Protection. All

    photovoltaic source and output circuits shall be

    provided with a ground-fault protection device

    or system that complies with (1) through (3):(1)

    Detects a ground fault.(2) Indicates that a

    ground fault has occurred(3) Automatically

    disconnects all conductors or causes the

    inverter or charge controller connected to thefaulted circuit to automatically cease supplying

    power to output circuits.(D) The photovoltaic

    source conductors shall consist of the

    following:(1) Nonmetallic jacketed

    multiconductor cables(2) Conductors installed

    in raceways, or (3) Conductors listed and

    identified as Photovoltaic (PV)Wire installed as

    exposed, single conductors. (F) The

    photovoltaic power source shall be labeled with

    the following warning at each junction box,

    combiner box, disconnect disconnect, anddevice where energized, ungrounded circuits

    may be exposed during service:WARNING

    ELECTRIC SHOCK HAZARD. THE DC

    CONDUCTORS OF THIS PHOTOVOLTAIC

    SYSTEM ARE UNGROUNDED AND MAY BE

    ENERGIZED.(G) The inverters or charge

    controllers used in systems with

    ungrounded photovoltaic source.

    1741

    Tim

    Zgonena

    Bradley

    Schmidt Susan Malohn [email protected]

    690.31(F). (F) Flexible, Fine-Stranded Cables.

    Flexible, fine strandedcables shall be

    terminated only with terminals,lugs, devices, or

    connectors that are identified and listed forsuch

    use.

    mailto:[email protected]:[email protected]:[email protected]:[email protected]
  • 7/31/2019 2008 NEC Changes - Copy

    8/22

  • 7/31/2019 2008 NEC Changes - Copy

    9/22

    Standar PDE STP Chair PM PM Email NEC Reference

    2021

    Robert

    Wozniak Joe Musso Mitchell Gold [email protected]. Requires disconnecting means to be

    rated 125% of total of disconnected loads.

    2024

    George

    Walbrecht

    Diana

    Pappas

    Jordan Paul Lloret [email protected]

    725.154(B) and (C) with changes in the 2005

    NEC in 725.179(I), (J), and (K). General-

    Purpose-signaling raceways, riser-signalingraceways, and plenum-signaling raceways

    have been added in the last and in this Code

    cycle.

    2200

    Tim

    Zgonena

    Diana

    Pappas

    Jordan

    Elizabeth

    Sheppard [email protected]

    250.35. Establishes requirements for a

    bonding jumper between the generator and the

    first disconnecting means.

    2200

    Tim

    Zgonena

    Diana

    Pappas

    Jordan

    Elizabeth

    Sheppard [email protected] 445.18. Added lockable in the open position

    2200

    Tim

    Zgonena

    Diana

    Pappas

    Jordan

    Elizabeth

    Sheppard [email protected]

    590.6, last sentence. A new last sentence has

    been added to 590.6 stating that ground fault

    protection for personnel shall apply to power

    derived from an electric utility company or from

    an on-site-generated power source.

    2200

    Tim

    Zgonena

    Diana

    Pappas

    Jordan

    Elizabeth

    Sheppard [email protected]

    700.12(B)(6). Added reference to the

    disconnecting means requirements for outdoor

    generator sets.

    2200

    Tim

    Zgonena

    Diana

    Pappas

    Jordan

    Elizabeth

    Sheppard [email protected]

    700.9(D)(3). Added clause regarding control

    conductors between transfer equipment and

    the emergency generator.

    mailto:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]
  • 7/31/2019 2008 NEC Changes - Copy

    10/22

    Standar PDE STP Chair PM PM Email NEC Reference

    2200

    Tim

    Zgonena

    Diana

    Pappas

    Jordan

    Elizabeth

    Sheppard [email protected]

    701.11(B)(5). Added reference to the

    disconnecting means requirements for outdoor

    generator sets.

    2200

    Tim

    Zgonena

    Diana

    Pappas

    Jordan

    Elizabeth

    Sheppard [email protected]

    702.11. Added reference to the disconnecting

    means requirements for outdoor generator

    sets.

    508A

    John

    Kovacik

    Bradley

    Schmidt Megan Cahill [email protected]

    200.2(B). Requires that a neutral (grounded)

    system conductor be connected through

    terminals and not to use the enclosure as part

    of the current carrying path.

    508A

    John

    Kovacik

    Bradley

    Schmidt Megan Cahill [email protected]

    250.122(D)(2). Sets the sizing for the

    equipment grounding conductor for motor

    starter equipment with an instantaneous trip

    circuit breaker or motor circuit protector.

    508A

    John

    Kovacik

    Bradley

    Schmidt Megan Cahill [email protected]

    519 (new section). New Article 519, "Control

    Systems for Permanent Amusement

    Attractions", was accepted by Panel 15 which

    opens the door for new categories of industrial

    control devices such as control panels for

    these systems.

    514A

    George

    Walbrecht

    Bradley

    Schmidt Susan Malohn [email protected]

    250.146(A). Sets requirements for when wiring

    device yoke is grounded by connection to anexposed work cover and a bonding jumper is

    not required. Two fastners that provide good

    security and the flat metal to metal cover

    corner connection to the box.

    mailto:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]
  • 7/31/2019 2008 NEC Changes - Copy

    11/22

    Standar PDE STP Chair PM PM Email NEC Reference

    514A

    George

    Walbrecht

    Bradley

    Schmidt Susan Malohn [email protected]

    250.8(A)(6) Requires that thread forming

    machine screw-type fasteners engage not less

    than two threads

    514D

    George

    Walbrecht

    Bradley

    Schmidt Beth Northcott [email protected]

    406.4(D) Ex 2. This removes any material that

    would hinder the complete seating of an

    attachment plug of the type, intended for use

    with the receptacle.

    60601-1

    Joe

    Murnane

    Bradley

    Schmidt Barbara Davis [email protected]

    517.160(A)(5). The isolated power systems

    conductor identification colors for isolated

    conductors 1, 2 and 3 (3 for 3-phase only) have

    changed to the below:Isolated conductor no. 1

    Orange with a distinctive colored stripe other

    than white, green or gray.Isolated conductorno. 2 Brown with a distinctive colored stripe

    other than white, green or gray.Isolatedconductor no. 1 Yellow with a distinctive

    colored stripe other than white, green or gray.

    6A

    George

    Walbrecht

    Diana

    Pappas

    Jordan Paul Lloret [email protected]

    300.7(B), FPN. Information on new Table

    355.44 for expansion characteristics for

    reinforced thermosetting resin conduit (RTRC)

    has been added.

    An expansion and contraction formula has

    been added to this FPN for aluminum conduit

    and aluminum electrical metallic tubing.

    mailto:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]
  • 7/31/2019 2008 NEC Changes - Copy

    12/22

    Comment

    If UL 429 is revised to include valve

    actuator motors, then additional wording

    may help provide more design flexibility of

    these products.

    Revise the Standard to cover these

    products.

    No immediate change necessary but

    questions have been raised about using

    standard listed connectors vs. connectors

    listed specifically for grounding and

    bonding.

    This additional requirement maypotentially affect current lock-off device

    Listings within UL's Circuit Breaker

    Accessories (DIHS) category and

    requirements within sub-clause 14.8 of the

    UL 489 standard. Some lock-off device

    Listings may require review to determine

    that they are not portable or removable

    after installation. The Panel stated during

    the meetings that they believe multiple

    lock hasps are accessories and are not

    affected by this requirement, i.e. thesedevices already comply with the intent of

    this code change.

    This wording was accepted for similar

    disconnect device requirements

    referenced in Articles 610, 620, 625, 647

    & 665.

  • 7/31/2019 2008 NEC Changes - Copy

    13/22

    Comment

    This additional requirement may

    potentially affect current lock-off device

    Listings within UL's Circuit Breaker

    Accessories (DIHS) category and

    requirements within sub-clause 14.8 of theUL 489 standard. Some lock-off device

    Listings may require review to determine

    that they are not portable or removable

    after installation. The Panel stated during

    the meetings that they believe multiple

    lock hasps are accessories and are not

    affected by this requirement, i.e. these

    devices already comply with the intent of

    this code change.

    This wording was accepted for similardisconnect device requirements

    referenced in Articles 610, 620, 625, 647

    & 665.

    This additional requirement may

    potentially affect current lock-off device

    Listings within UL's Circuit Breaker

    Accessories (DIHS) category and

    requirements within sub-clause 14.8 of the

    UL 489 standard. Some lock-off deviceListings may require review to determine

    that they are not portable or removable

    after installation. The Panel stated during

    the meetings that they believe multiple

    lock hasps are accessories and are not

    affected by this requirement, i.e. these

    devices already comply with the intent of

    this code change.

    This wording was accepted for similardisconnect device requirements

    referenced in Articles 610, 620, 625, 647

    & 665.

  • 7/31/2019 2008 NEC Changes - Copy

    14/22

    Comment

    This additional requirement may

    potentially affect current lock-off device

    Listings within UL's Circuit Breaker

    Accessories (DIHS) category and

    requirements within sub-clause 14.8 of theUL 489 standard. Some lock-off device

    Listings may require review to determine

    that they are not portable or removable

    after installation. The Panel stated during

    the meetings that they believe multiple

    lock hasps are accessories and are not

    affected by this requirement, i.e. these

    devices already comply with the intent of

    this code change.

    This wording was accepted for similardisconnect device requirements

    referenced in Articles 610, 620, 625, 647

    & 665

    Need to verify the when these listed

    assemblies are used. The terminal for the

    equipment grounding conductor is

    adequate.

    The Listing evaluations of these type

    devices need to take this into account

    from a replacement and neutral loading

    (e.g. will single component faults result in

    harmonics) point of view for design and

    installation instructions.

    Opportunity for new industrial control

    devices (control panels, power

    distribution equipment, etc) that are

    allowed under the new section

  • 7/31/2019 2008 NEC Changes - Copy

    15/22

    Comment

    Although this has been a long standing

    practice in the burglar alarm industry, it

    may be helpful to incorporate this text or a

    reference to it within UL 639.

    These standards may need to be reviewedto ensure that when arranged for a neutral

    supply that a neutral bus or terminals be

    provided so that the enclosure is not used

    in the neutral current carrying path.

    Verify that Type I has been required to be

    marked based on 49.21.1 and no action is

    needed. Note the 11th Edition clearly

    addresses this issue.

    These standards may need to be reviewed

    to ensure that when arranged for a neutral

    supply that a neutral bus or terminals beprovided so that the enclosure is not used

    in the neutral current carrying path.

    Opportunity for certification of industrial

    control devices (control panels, power

    distribution equipment, etc) that are

    allowed under the new section

    Will require automatic optional standby

    systems to either be suitable for full load

    on both sources, or have load

    management system. This may require

    standards revision.

  • 7/31/2019 2008 NEC Changes - Copy

    16/22

    Comment

    Provisions must be made in transfer

    switches for emergency and in generators

    which may be used in emergency systems

    to keep the generator control wiring

    independent of all other wiring. This may

    require standards revision.Will require automatic optional standby

    systems to either be suitable for full load

    on both sources, or have load

    management system. This may require

    standards revision.

    Revise standard to indicate that if a

    baseboard heater is provided with a

    receptacle the receptacle shall be

    tamperproof when the heater is installed in

    a residential application.

    Standards need to be revised to reflect

    increased ampacity requirement for unit

    switches serving as disconnecting means.

    For KEWV, KEZR and KEXS equipment

    the receptacles in critical care areas will

    need to have power on indicators.

    This change would provide a better

    defined connection point for the ground

    shield for high voltage cable and we may

    want to incorporate

    UL 1072, Table 1.1 will need to be revised

    to reflect the larger size conductors now

    allowed by the NEC. Specifically, the first

    row, second column needs to be revised

    to allow conductors up to 2000 kcmil.

    Presently, UL 1277 requirements do not

    address nickel or nickel coated copper

    conductors. A standards change is

    needed to allow this option.

  • 7/31/2019 2008 NEC Changes - Copy

    17/22

    Comment

    Presently, UL 1569 requirements do not

    address nickel or nickel coated copper

    conductors. A standards change is

    needed to allow this option.

    Will require new performance, marking

    requirements, Guide card and markingguide revisions. Due to the delay getting

    revisions processed in this Trinational

    Standard a CRD will be issued first so that

    by end of first quarter 2008 certification

    requirements will be in place.

    Provides expansion and contraction

    formulas for both raceway types.

    UL should only allow use of PV wire,

    USE2 cable or equivalent for general

    outdoor PV modules.

    Connectors need to be rated for the wire

    type.

    Since we have no control over installation

    locations all PV connectors need to be

    built such that they can only be opened

    via the use of a tool.

  • 7/31/2019 2008 NEC Changes - Copy

    18/22

    Comment

    Since we have no control over installation

    locations all PV connectors need to be

    built such that they can only be opened

    via the use of a tool.

    Need marking no disconnect under loadunless evaluated for disconnect under

    load.

    PV modules used in ungrounded arrays

    need UL PV wire to comply.

    Connectors need to be rated for the wire

    type.

  • 7/31/2019 2008 NEC Changes - Copy

    19/22

    Comment

    PV modules used in ungrounded arrays

    need UL PV wire to comply.

    May need to revise/ provide guidance on

    minimum sizing of combined AC and DC

    grounging.

    This could require either OCP or product

    evaluation for current limitation on both

    sides of conductors between energy

    storage and inverter / charger circuits.

    Inverters with charger circuit may need

    equalization voltage marking.

  • 7/31/2019 2008 NEC Changes - Copy

    20/22

    Comment

    Standards need to be revised to reflect

    increased ampacity requirement for unit

    switches serving as disconnecting means.

    These raceways are being used toenclose not only optical fiber cables but

    also Class 2 and Class 3 cables of the

    appropriate rating.

    Where a listed generator is supplied with

    a disconnecting means the bonding

    jumper sized according to NEC would be

    required.

    Where a generator is not provided with an

    integral disconnect, the disconnect isinstalled in the field and this clause

    applies the field installation rather than the

    generator itself. Generators provided with

    integral disconnects shall have provisions

    for locking the disconnect in the open

    position. Possible revisions necessary to

    standard.

    This change helps bolster therequirements that GFCI protection for

    personnel is required even for generator-

    derived power.

    Integral disconnecting means shall be

    suitable for use as service equipment

    when the generator is used in emergency

    systems. This may require standards

    revision

    Provisions must be made in transfer

    switches for emergency and in generators

    which may be used in emergency systems

    to keep the generator control wiring

    independent of all other wiring. This may

    require standards revision.

  • 7/31/2019 2008 NEC Changes - Copy

    21/22

    Comment

    Integral disconnecting means shall be

    suitable for use as service equipment

    when the generator is used in legally

    required standby systems. This may

    require standards revision

    Integral disconnecting means shall besuitable for use as service equipment

    when the generator is used in emergency

    systems. This may require standards

    revision.

    These standards may need to be reviewed

    to ensure that when arranged for a neutral

    supply that a neutral bus or terminals be

    provided so that the enclosure is not used

    in the neutral current carrying path.Need to verify the when these listed

    assemblies are used, the terminal for the

    equipment grounding conductor is

    adequate.

    Opportunity for new industrial control

    devices (control panels, power

    distribution equipment, etc) that are

    allowed under the new section

    Confirm that covers meet these

    requirements and that assemblies of

    devices in these covers are correct.

  • 7/31/2019 2008 NEC Changes - Copy

    22/22

    Comment

    Revise Clause 8.1.1( C)

    Presently, UL 514D, para. 4.1.1 prohibits

    a cover plate or outlet box hood that is

    used with a receptacle shall not hinder the

    complete seating of an attachment plug of

    the type intended for use with the

    receptacle.

    For KEWV, KEYQ2 and KEXS equipment

    the conductor identification colors will

    need to change to those indicated.

    Provides expansion and contraction

    formulas for both raceway types.