    INSTALLATION INSTRUCTION

    Part 1 Wall-mounted Split Type

    Premier Heat Pumps v9.08

  • 8/8/2019 2008 10 Aircon Installation Instruction

    2/15

    INSTALLATION - Toolsrequired2.1Tools

    Screw driver

    Assembly,disassmbly

    Hand drill

    Indoor installationplate fixing

    Ruler, knife

    Ruler: Length &distancemeasurement.Knife: Tape cutting

    Gas leak detector& soup water

    Leak inspection

    Thermometer Hex. wrench(Large side: 4mm, 5mm)

    Temperaturemeasurement atIndoor suctioninlet/discharge outlet.

    Service valveoperating

    Core drill(diameter 70mm)

    Wall through

    Monkey spanner(300mm): 2EA

    Indoor/Outdoorpipe connection

    Torque wrench

    Indoor/outdoorpipe connection

    Hook meter(for current measurement)

    Current, voltage,resistance

    measurement

    Insulationresistance meter

    Flare tool set

    Insulation resistancemeasurement

    (Electric shock prevention)

    Pipe cutting,Burr removal

    Level

    Clamp meter

    Thermometer

    Drive torch Mega tester

    2.2Accessory

    Connnection cable

    Indoor-Outdoorwire connnection

    Winter cover

    Outdoor protectionin a unusedseason

    like winter

    Anti-vibrationrubber

    Vibration absorptionof outdoor

    Band

    Wire & pipefinishing

    Adhesive

    Finishing

    Drain hose

    Drainage

    Refrigerant pipe(for high/low pressure)

    Refrigerant circuitconnection to

    Indoor/Outdoor.

    Putty

    Chaging of wall-through hole

    Vinyl tape

    Wire & pipefinishing

    Remocon fixture

    Remocon hanger

    Fixture clampingscrew

    Remocon fixturefixing

    Remocon

    Remark: Some of the above parts are provided by the installer and not included in the standard air-conditioner.

    3

    Premier Heat Pumps - Air conditioner installation / service manual

  • 8/8/2019 2008 10 Aircon Installation Instruction

    3/15

    A

    l

    3.Splittypeinstallation3.1Selectthebestlocation

    3.1.1Indoorunit

    1)Donothaveanyheatorsteamneartheunit.2)Selectaplacewheretherearenoobstaclesinfrontof

    theunit.

    3)Makesurethatcondensationdrainagecanbeconve-nientlyroutedaway.

    4)Donotinstallnearadoorway.

    5)Ensurethat thespacearoundthe leftand rightof theunitismorethan5cm.Theunitshouldbeinstalledashighonthewallaspossible, allowingaminimumof

    5cmfromceiling.6)Useastudfindertolocatestudstopreventunneces-

    sarydamagetothewall.

    More than 5cm More than 5cm

    More than 2.3m More than 5cm

    Installtheindoorunitonthewallwheretheheightfromthefloorsmorethan2.3meters.

    CAUTION

    3.1.2Outdoorunit

    1)Ifanawningisbuiltovertheunittopreventdirectsun-lightorrainexposure,makesurethatheatradiationfromthecondenserisnotrestricted.

    2)Ensurethatthespacearoundthebackandsidesismorethan10cm.Thefrontoftheunitshouldhavemorethan70cmofspace.

    3)Donotplaceanimalsandplantsinthepathofthewarmair.

    4)Taketheairconditionerweightintoaccountandselect

    aplacewherenoiseandvibrationareminimum.5)Selectaplacesothatthewarmairandnoisefromthe

    airconditionerdonotdisturbneighbors.

    More than 10cm More than 10cm

    More than 60cm

    MoreMore than 70cm than 60cm

    6)RooftopInstallations:Iftheoutdoorunitisinstalledonaroofstructure,be

    suretoleveltheunit.Ensuretheroofstructureandanchoringmethodareadequatefortheunitlocation.Consultlocalcodesregardingrooftopmounting.

    3.2Pipinglengthandelevation

    Capacity(Btu/h)

    PipeSize StandardLength

    (m)

    Max.ElevationB (m)

    Max.lengthA (m)

    AdditionalRefrigerant

    (g/m)GAS LIQUID

    7K, 9K 3/8" 1/4" 3or5 5 10 20

    12K 1/2" 1/4 3.5or5 5 10 20

    18K 1/2" 1/4" 4.5 5 15 30

    24K 5/8" 3/8" 5 5 15 30

    *Bothgasandliquidinterconnectingpipesmustbe

    insulatedasapair,butitisnotnecessarytoindi-viduallyinsulatethem.

    Incasemorethan5m

    Capacityisbasedonstandardlengthandmaximumallowancelengthisonthebasisofreliability.

    Oiltrapshouldbeinstalledevery5~7meters.

    Oil trap

    Outdoor unit

    Indoor unitB

    Outdoor unit

    Indoor unit

    A

    B

    CAUTION

    4

  • 8/8/2019 2008 10 Aircon Installation Instruction

    4/15

    3.3Howtofixinstallationplate

    Thewallyouselectshouldbestrongandsolidenoughtopreventvibration

    3.3.1 MounttheinstallationplateonthewallwithfourtypeAscrews.Ifmountingtheunitonaconcretewall,useanchorbolts.

    Mounttheinstallationplatehorizontallybyaligningthecenter-lineusingalevel.

    Installation Plate

    Marking-off line

    Thread

    Weight

    Type "A" screw

    3.3.2 Measurethewallandmarkthecenterline.Itisalsoimportanttousecautionconcerningthelocationoftheinstallationplate-routingofthewiringtopoweroutletsisthroughthewallstypically.Drillingtheholethroughthewallforpipingconnectionsmustbedonesafely.

    Left rear piping Right rear pipingD

    A,B

    A,B,CC

    DA,B,D

    C

    A

    B,DC

    70mmHole Center Installation plate

    Forrightrearpipingandleftrearpiping,drawalineinthedirectionofthearrowmarked"D".The

    meetingpointofthetwolinesisthecenterofthehole.

    Thepositionofthecenterofthehole.

    Leftholecoreposition Rightholecoreposition

    DD

    D D

    3.4Drillaholeinthewall

    Drillthepiping holewitha 70mmhole coredrill.

    Drillthepipingholeateithertherightortheleftwiththeholeslightlyslantedtotheoutdoorside.

    WALL

    5-7mm

    (0

    .2~0.3

    ")

    Indoor Outdoor

    5

  • 8/8/2019 2008 10 Aircon Installation Instruction

    5/15

    Air Conditioner Service Manual

    3.5Flaringworkandconnectionofpiping

    3.5.1Flaringwork

    Maincauseforgasleakageisduetodefectinflaring D.Flaringwork

    work.Carryoutcorrectflaringworkinthefollowing Carryoutflaringworkusingflaringtoolasshown

    procedure. below.

    A.Cutthepipesandthecable.1)Usethepipingkitaccessoryorthepipespur-

    chasedlocally.2)Measurethedistancebetweentheindoorandthe

    outdoorunit.

    3)Cutthepipesalittlelongerthanmeasureddis-tance.

    4)Cutthecable1.5mlongerthanthepipelength.

    Outsidediameter A

    mm inch mm

    6.35 1/4 1.0~1.3

    9.52 3/8 0.8~1.0

    12.7 1/2 0.5~0.8

    15.88 5/8 0.5~0.8

    Firmlyholdcopperpipeinadieinthedimensionshownin

    Copper

    90

    thetableabove.

    Slanted Uneven Roughpipe

    Cone

    YokeBar

    Handle

    Bar"A"

    B.Burrsremoval Copper pipe1)Completelyremoveallburrsfromthe cutcross

    sectionofpipe/tube.Clamp handle

    Red arrow mark

    2)Puttheendofthecoppertube/pipeinadownwarddirectionasyouremoveburrsinordertoavoid E.Checkdroppingburrsintothetubing. 1)Comparetheflaredworkwithfigurebelow.

    2)Ifflareisnotedtobedefective,cutofftheflaredsec-Pipe tionanddoflaringworkagain.

    Reamer

    Smooth all roundPoint down Inside is shiny without scratches

    Surfacedamaged

    Cracked Uneventhickness

    = Improper flaring =

    C PuttingnutonInclined

    Removeflarenutsattachedtoindoorandoutdoor

    unit,thenputthemonpipe/tubehavingcompleted

    Even length

    all roundburrremoval.

    (notpossibletoputthemonafterflaringwork)

    Flare nut

    Copper tube

    6

  • 8/8/2019 2008 10 Aircon Installation Instruction

    6/15

    CoolingModelCapacity(Btu/h) HeatPumpModel

    7K,9K,12K,18K

    24K

    Air Conditioner Service Manual

    3.5.2 Connectionofpiping--Indoor

    1)Preparing theindoor unit'spipinganddrainhoseforinstallationthroughthewall.

    2)Removetheplastictubingretainer(seeillustration

    below)andpullthetubinganddrainhoseawayfromchassis.

    3)Replacetheplastictubingholderintheoriginalposi-tion.

    CAUTIONWheninstall ,makesurethattheremainingpartsmustberemovedclearlysoasnottodamagethepipinganddrainhose,especiallypowercordandconnectingcable.

    Forrightrearpiping

    A.Routetheindoortubingandthedrainhoseinthedirectionofrearright. Indoor tubing

    Drain hose

    B.Inserttheconnectingcableintotheindoorunitfromtheoutdoorunitthroughthepipinghole.1)Donotconnectthecabletotheindoorunit.

    2)Makeasmallloopwiththecableforeasyconnectionlater.

    3)Connectingcable

    Lengthofcon- Gas side piping

    nectingcable74cm Liquid side piping

    Cable

    C.Tapethetubing,drainhoseandtheconnectingcable.Besurethatthedrainhoseislocatedatthelowestsideofthebundle.Locatingattheuppersidecancausedrainpantooverflowinsidetheunit.

    Indoor tubing

    Connecting Drain hosecable

    Gas sideConnecting

    pipingcable

    Liquid side

    Drain hose piping

    NOTE:Ifthedrainhoseisroutedinsidetheroom,insulatethe

    hosewithaninsulationmaterial* sothatdrippingfrom"sweat-ing"(condensation)willnotdamagefurnitureorfloors.

    *Foamedpolyethyleneorequivalentisrecommended.

    D.IndoorunitinstallationHook theindoorunitontotheupperportionof the

    installationplate.(Engagethetwohooksofthereartopoftheindoorunitwiththeupperedgeoftheinstallationplate.)Ensurethatthehooksareproperly

    seatedontheinstallationplatebymovingitleftand

    right.

    Connecting

    cable

    Drain hose

    Pressthelowerleftandrightsidesoftheunitagainstthe

    installationplateuntilthehooksengageintotheirslots(click-

    ingsound).

    E.Connectingthepipingstotheindoorunitanddrainhosetodrainpipe.

    Alignthecenterofthepipingsandsufficientlytightentheflarenutbyhand.

    Indoor unit tubing Flare nut Pipings

    7

  • 8/8/2019 2008 10 Aircon Installation Instruction

    7/15

    PHP Air Conditioner Service Manual

    Tightentheflarenutwithawrench.

    Spanner (fixed)

    Flare nut

    Connection pipeTorque wrench

    Indoor unit tubing

    Capacity(Btu/h)

    PipeSize[Torque]

    GAS LIQUID

    7K,9K 3/8"[4.2kg.m] 1/4"[1.8kg.m]

    12K,18K 1/2"[5.5kg.m] 1/4"[1.8kg.m]

    24K 5/8"[6.6kg.m] 3/8"[4.2kg.m]

    Whenextendingthedrainhoseattheindoorunit,installthedrainpipe.

    Drain pipe

    Indoor unit drain hose

    Vinyl tape(narrow)Adhesive

    F.Wraptheinsulationmaterialaroundtheconnectingportion.

    Overlaptheconnectionpipeinsulationmaterialandthe

    indoorunitpipeinsulationmaterial.Bindthemtogetherwithvinyltapesothatthereisnogap.

    Plastic bands Insulation material

    Wraptheareawhichaccommodatestherearpiping

    housingsectionwithvinyltape.

    Connection Indoorunit pipepipe

    Vinyl tape Wrap with vinyl tape(wide)

    Vinyl tape(narrow)

    Connecting cable

    Pipe

    Bundlethepipinganddrainhosetogetherbywrapping

    themwithvinyltapeovertherangewithinwhichtheyfitintotherearpipinghousingsection.

    Wrap with vinyl tape

    Pipe

    Vinyl tape(wide)

    Drain hose

    Forleftrearpiping

    A.Routetheindoortubingwiththedrainhosetotherequiredpipingholeposition.

    B.Insertthepiping,drainhoseandtheconnectingcableintothepipinghole.

    Connecting cable

    Drain pipe

    Pipe

    8

  • 8/8/2019 2008 10 Aircon Installation Instruction

    8/15

    PHP Air Conditioner Service Manual

    C.Inserttheconnectingcableintotheindoorunit.

    1)Don'tconnectthecabletotheindoorunit.2)Makeasmallloopwiththecableforeasyconnection

    later.

    D.Tapethetubing,drainhoseandtheconnectingcable.

    Connectingcable

    CoolingModelCapacity (Btu/h) HeatPumpModel

    Loop

    7K,9K,12K,18K

    24K

    E.Indoorunitinstallation

    1)Hangtheindoorunitfromthehooksatthetopoftheinstallationplate.

    2)Insertthespaceretc.betweentheindoorunitandtheinstallationplateandseparatethebottomoftheindoor

    unitfromthewall.

    Indoor unit

    Spacer

    Installation plate

    F.Connectingthepipingstotheindoorunitand thedrainhosetodrainpipe.

    Align thecenter ofthepipingsandsufficiently tightentheflarenutbyhand.

    Indoor unit tubing Flare nut Pipings

    Tightentheflarenutwithawrench.

    Spanner (fixed)

    Flare nut

    Connection pipeTorque wrench

    Indoor unit tubing

    Capacity(Btu/h)

    PipeSize[Torque]

    GAS LIQUID

    7K,9K 3/8"[4.2kg.m] 1/4"[1.8kg.m]

    12K,18K 1/2"[5.5kg.m] 1/4"[1.8kg.m]

    24K 5/8"[6.6kg.m] 3/8"[4.2kg.m]

    Whenextending thedrain hoseattheindoorunit,installthedrainpipe.

    Drain hose

    Indoor unit drain hose

    Vinyl tape (narrow)Adhesive

    G.Wraptheinsulationmaterialaroundtheconnect-ingportion.

    Overlaptheconnectionpipeheatinsulationandtheindoorunitpipeheatinsulationmaterial.Bindthemtogetherwithvinyltapesothatthereisnogap.

    Plastic bandsInsulation material

    Wraptheareawhichaccommodatestherearpipinghousingsectionwithvinlytape.

    Connection Indoor

    unit pipingpipe

    Wrap with vinyl tapeVinyl tape

    Vinyl tape(narrow)

    Connecting cable

    Pipe

    9

  • 8/8/2019 2008 10 Aircon Installation Instruction

    9/15

    3/8"[4.2kg.m] 1/4"[1.8kg.m]

    1/2"[5.5kg.m] 1/4"[1.8kg.m]

    24K 5/8"[6.6kg.m] 3/8"[4.2kg.m]

    PipeSize[Torque]Capacity(Btu/h) GAS LIQUID

    12K,18K

    7K,9K

    PHP Air Conditioner Service Manual

    Bundlethepipinganddrainhosetogetherbywrappingthemwithclothtapeovertherangewithinwhichtheyfit

    intotherearpipinghousingsection.

    Wrap with vinyl tape

    Pipe

    Vinyl tape

    Drain hose

    H.Reroutethepipingsandthedrainhoseacrossthebackofthechassis.

    Piping forpassage throughpiping hole

    I.Setthepipingsandthedrainhosetothebackofthechassiswiththetubingholder.

    Hooktheedgeoftubingholdertotaponchassisandpushthebottomoftubingholdertobeengagedatthebottomofchassis.

    Taping

    J.Indoorunitinstallation1)Removethespacer.

    2)Ensurethatthehooksareproperlyseatedontheinstallationplatebymovingitleftandright.

    Connectingcable

    Drain hose

    Pressthelowerleftandrightsidesoftheunitagainst

    theinstallationplateuntilthehooksengageintotheir

    slots(clickingsound).

    3.5.3Connectionofthepipes-Outdoor

    A.Alignthecenterofthepipingsandsufficientlytightentheflarenutbyhand.

    B.Finally,tightentheflarenutwithtorquewrenchuntilthewrenchclicks.

    Whentighteningtheflarenutwithtorquewrench,ensurethedirectionfortighteningfollowsthearrowonthewrench.

    Outdoor unit

    Gas side piping(Bigger diameter)

    Liquid side piping(Smaller diameter)

    Torque wrench

    10

  • 8/8/2019 2008 10 Aircon Installation Instruction

    10/15

    PHP Air Conditioner Service Manual

    3.6Connectingthecablebetweenindoorunitandoutdoorunit

    3.6.1ConnectthecabletotheIndoorunit.

    Connectthecabletotheindoorunitbyconnecting

    thewirestotheterminalsonthecontrolboardindi-

    viduallyaccordingtotheoutdoorunitconnection .(Ensurethatthecolorofthewiresoftheoutdoor unitandtheterminalNo.arethesameasthoseofthe

    indoorunit.)

    7K~18Kcoolingmodel

    Terminalontheindoorunit

    Terminalontheoutdoorunit 1 N

    1 N

    BROWN BLUE GREEN/YELLOW

    BROWN BLUE GREEN/YELLOW

    7K~18Kheatpumpmodel

    Terminalontheindoorunit

    Terminalontheoutdoorunit

    24K coolingmodel

    Terminalontheindoorunit

    Power supply

    1

    1

    N

    N

    2

    2

    3

    3

    1 N L

    BROWN BLUE GREEN/YELLOW RED

    WHITE BLUE

    YELLOW

    BROWN

    BROWN

    BROWNWHITE BLUE

    RED YELLOWBLUE GREEN/YELLOW

    GREEN/YELLOW

    . 24K heat pump model

    CAUTION

    Thepowercord connectedtotheindoorunitshouldbe

    compliedwiththefollowingspecifications

    (TypeH05VV-F(Indoor),H07RN-F(Outdoor)approvedbyHARorSAA).

    Thepowerconnectingcable connectedtotheindoor

    andoutdoorunitshouldbecompliedwiththefollowing

    specifications

    (TypeH07RN-FapprovedbyHARorSAA).

    Theconnectingcableconnectedtotheindoorandout-

    doorunitshouldbecompliedwiththefollowingspecifi-

    cations

    (TypeH07RN-FapprovedbyHARorSAA).

    NORMAL

    CROSS-SECTIONAL

    AREA 2.5mm2

    (18K: 1.5mm2, 7K~14K: 1.0mm2)

    NORMAL

    CROSS-SECTIONAL

    AREA 2.5mm2

    (18K: 1.5mm2, 7K~14K: 1.0mm2)

    NORMAL

    CROSS-SECTIONAL

    AREA 0.75mm2

    Terminalontheoutdoorunit 1 N LL N

    LTerminal on the indoor unit 1 2 3 N

    L N

    YELLOWWHITE

    Power supply

    RED

    L N

    GREEN/YELLOW

    BROWN BLUE

    BLUEBROWN

    GREEN/YELLOW

    YELLOWWHITE RED

    1 2 3

    .

    Terminal on the outdoor unit

    AirConditioner

    Main power source

    Circuit Breaker

    Use a circuit

    breaker or time

    delay fuse.

    Circuit Breaker

    Use a 25A circuit

    breaker or time

    delay fuse.

    AirConditioner

    Main power source

    ~18KModel

    Ifapowerplugisnottobeused,provideacircuitbreakerbetweenpowersourceandtheunitasshownbelow.

    CAUTION

    24K~Model

    Ifapowerplugisnottobeused,provideacircuitbreakerbetweenpowersourceandtheunitasshownbelow.

    11

  • 8/8/2019 2008 10 Aircon Installation Instruction

    11/15

    PHP Air Conditioner Service Manual

    3.6.2Connectthecabletotheoutdoorunit

    A.Removethecontrolcoverfromtheunitbyloosen-ingthescrew.

    Connectthewirestotheterminalsonthecontrol

    boardindividually.B.Securethecableontothecontrolboardwiththecordclamp.

    C.Refixthecontrolcovertotheoriginalpositionwiththescrew.

    D.Usearecognizedcircuitbreaker20A(18K),25A(24K)betweenthepowersourceandtheunit.Adisconnectingdevicetoadequatelydis-connectallsupplylinesmustbefitted.

    Terminal block

    Over 5mm

    Control cover

    Power cord

    (power connecting

    cable)

    Connecting cable

    Outdoor unit

    CAUTION

    Aftertheconfirmationoftheaboveconditions,preparethewiringasfollows:

    1)Neverfailtohaveanindividualpowercircuitspecificallyfortheairconditioner.Asforthemethod

    ofwiring,beguidedbythecircuitdiagrampostedontheinsideofcontrolcover.

    2)Thescrewwhichfastenthewiringinthecasingofelectricalfittingsareliabletocomeloose

    fromvibrationstowhichtheunitissubjectedduringthecourseoftransportation.Checkthem

    andmakesurethattheyarealltightlyfastened.

    (Iftheyareloose,itcouldcauseburn-outofthewires.)

    3)Specificationofpowersource.

    4)Confirmthatelectricalcapacityissufficient.

    5)Seetothatthestartingvoltageismaintainedatmorethan90percentoftheratedvoltage

    markedonthenameplate.

    6)Confirmthatthecablethicknessisasspecifiedinthepowersourcespecification.

    (Particularlynotetherelationbetweencablelengthandthickness.

    7)Alwaysinstallanearthleakagecircuitbreakerinawetormoistarea.

    8)Thefollowingwouldbecausedbyvoltagedrop.

    Vibrationofamagneticswitch,whichwilldamagethecontactpoint,fusebreaking,disturbanceofthenormalfunctionoftheoverload.

    9)Themeansfordisconnectionfromapowersupplyshallbeincorporatedinthefixedwiringand

    haveanairgapcontactseparationofatleast3mmineachactive(phase)conductors.

    12

  • 8/8/2019 2008 10 Aircon Installation Instruction

    12/15

    PHP Air Conditioner Service Manual

    3.7CheckingtheDrainageandformingthepipings

    3.7.1Checkingthedrainage

    A.Toremovethefrontpanelfromtheindoorunit,

    removethefrontpanelfromtheindoorunitcabinet.1)Settheairdirectionlouversup-and-downtotheposi-

    tion(horizontally)byhand.2)Remove 3 screws that retain the f ront panel .

    Pullthelowerleftandrightsidesofthegrilletowardyouandliftitoff.

    ChassisGrille

    Remove screws (3places)

    B.Tocheckthedrainage.

    1)Pouraglassofwaterontheevaporator.2)Ensurethewaterflowsthroughthedrainhoseofthe

    indoorunitwithoutanyleakageandgoesoutthedrain

    exit.

    , ,

    , ,

    C.Drainpiping

    Thedrainhoseshouldpointdownwardforeasydrainflow.

    Downward slope

    Donotmakedrainpiping.

    AccumulatedDo not raise

    drain water

    Air Tip of drain hose Less thandipped in water

    50mm gap

    WaterWater WaterWaving

    leakage Ditchleakage leakage

    3.7.2Formthepiping

    A.Formthepipingbywrappingtheconnectingportionoftheindoorunitwithinsulationmaterialandsecureitwithtwokindsofvinyltapes.

    Ifyouwanttoconnectanadditionaldrainhose,theendofthedrainoutletshouldberoutedabovetheground.Securethedrainhoseappropriately.

    B Incaseswheretheoutdoorunitisinstalledbelowtheindoorunitperformthefollowing.1)Tapethepiping,drainhoseandconnectingcablefrom

    downtoup.2)Securethetappedpipingalongtheexteriorwallusing

    saddleorequivalent.

    Seal small openingsaround pipings with agum type sealer.

    Taping

    Drainhose

    Pipings

    Connecting

    ,

    cable

    Trap is required to prevent waterfrom entering into electrical parts.

    C.IncaseswheretheOutdoorunitisinstalledabovetheIndoorunitperformthefollowing.

    1)Tapethepipingandconnectingcablefromdowntoup.

    2)Securethetapedpipingalongtheexteriorwall.Formatrap,topreventwaterenteringtheroom.

    3)Fixthepipingontothewallbysaddleorequivalent.

    Seal small openings

    around pipings with agum type sealer.

    Trap

    ,

    Trap

    Trap is required to prevent waterfrom entering into electrical parts.

    13

  • 8/8/2019 2008 10 Aircon Installation Instruction

    13/15

    PHP Air Conditioner Service Manual

    3.8Airpurging

    3.8.1Airpurging

    Airandmoistureremainingintherefrigerantsystem

    haveundesirableeffectsasindicatedbelow.1)Pressureinthesystemrises.2)Operatingcurrentrises.3)Cooling(orheating)efficiencydrops.

    4)Moistureintherefrigerantcircuitmayfreezeandblockcapillarytubing.

    5)Watermayleadtocorrosionofpartsintherefrigera-

    tionsystem.Therefore,theindoorunitandtubingbetweentheindoorandoutdoorunitmustbeleaktestedandevacuatedto

    removeanynoncondensablesandmoisturefromthesystem.

    3.8.2Airpurgingwithvacuumpump

    A.PreparationCheck that each tube(both liquidandgassidetubes)

    betweentheindoorandoutdoorunitshavebeenprop-

    erlyconnectedandallwiringforthetestrunhasbeencompleted.Remove theservicevalve caps fromboththegasandtheliquidsideontheoutdoorunit.Note

    thatboththeliquidandthegassideservicevalvesontheoutdoorunitarekeptclosedatthisstage.

    B.Leaktest

    Connectthemanifoldvalve(withpressuregauges)anddrynitrogengascylindertothisserviceportwith

    chargehoses.

    Besuretouseamanifoldvalveforairpurging.Ifitisnotavailable,useastopvalveforthispurpose.The"Hi"knobofthemanifoldvalvemustalwaysbekeptclose.

    CAUTION

    Pressurizethesystemtonomorethan150P.S.I.G.

    withdrynitrogengasandclosethecylindervalvewhenthegaugereadingreached150P.S.I.G.Next,testfor

    leakswithliquidsoap.

    Toavoidnitrogenenteringtherefrigerantsysteminaliquidstate,thetopofthecylindermustbehigherthanitsbottomwhenyoupressurizethesystem.Usually,thecylinderisusedinaverticalstandingposition.

    CAUTION

    Doaleaktestofalljointsofthetubing(bothindoorandoutdoor)andbothgasandliquidsideservicevalves.Bubblesindicatealeak.Besuretowipeoffthesoap

    withacleancloth.Afterthesystemisfoundtobefreeofleaks,relievethe

    nitrogenpressurebylooseningthechargehosecon-

    nectoratthenitrogencylinder.Whenthesystempres-sureisreducedtonormal,disconnectthehosefromthecylinder.

    14

  • 8/8/2019 2008 10 Aircon Installation Instruction

    14/15

    Requiredtimeforevacuationwhen30gal/hvacuumpumpisused

    10min.ormore 15min.ormore

    Iftubinglengthisless

    than10m(33ft)

    iftubinglengthislonger

    than10m(33ft)

    PHP Air Conditioner Service Manual

    Soapwatermethod

    (1)Removethecapsfromthe2-wayand3-wayvalves.

    (2)Removetheservice-portcapfromthe3-wayvalve.

    (3)Toopenthe2-wayvalveturnthevalvestemcounter-clockwiseapproximately90,waitforabout2~3sec,and

    closeit.(4)Applyasoapwateroraliquidneutraldetergentonthe

    indoorunitconnectionoroutdoorunitconnectionsbyasoftbrushtocheckforleakageoftheconnectingpointsofthepiping.

    (5)Ifbubblescomeout,thepipeshaveleakage.

    C.EvacuationConnectthechargehoseenddescribedinthepreced-

    ingstepstothevacuumpumptoevacuatethetubingandindoorunit.

    Confirmthe"Lo"knobofthemanifoldvalveisopen.Then,runthevacuumpump.Theoperationtimeforevacuationvarieswithtubinglengthandcapacityofthepump.Thefollowingtable

    showsthetimerequiredforevacuation.

    Whenthedesiredvacuumisreached,closethe"Lo"knobofthemanifoldvalveandstopthevacuumpump.

    D.Finishingthejob

    1)Withaservicevalvewrench,turnthevalvestemofliq-

    uidsidevalvecounter-clockwisetofullyopenthevalve.

    2)Turn thevalve stemofgasside valvecounter-clock-

    wisetofullyopenthevalve.3)Loosenthe chargehoseconnectedto thegasside

    serviceportslightlytoreleasethepressure,then

    removethehose.4)Replacetheflarenutanditsbonnetonthegasside

    serviceportand fastentheflarenutsecurelywithan

    adjustablewrench.Thisprocessisveryimportanttopreventleakagefromthesystem.

    5)Replacetheservicevalvecapsatboththegasand

    theliquidsideandfastenthemtight.Thiscompletesairpurgingwithavacuumpump.Theairconditionerisnowreadytotestrun.

    Outdoor unitCover control

    Gas side(Bigger diameta)

    3-way valve Liquid side(close) (Smaller diameta)

    Hexagonal2-way valvewrench(open)

    Cap

    Service port cap

    Indoor unit

    Outdoor unit

    Manifold valve

    PressureLo Hi

    gauge

    Open Close

    Vacuum pump

    15

  • 8/8/2019 2008 10 Aircon Installation Instruction

    15/15

    PHP Air Conditioner Service Manual

    3.9Testrunning

    1)Checkthatalltubingandwiringhavebeenproperlyconnected.

    2)Checkthatthegasandliquidsideservicevalvesare

    fullyopen.

    A.Prepareremotecontrol

    1)Removethebatterycoverbypullingitaccordingtothe arrow

    direction.2)Insertnewbatteriesmakingsure

    thatthe(+)and()of battery

    areinstalledcorrectly.3)Reattachthecoverbypushingit

    backintoposition.

    NOTE:

    Use1.5voltbatteries.Donotuserechargeablebatteries.

    Removethebatteriesfromtheremotecontrolifthesystemisnotgoingtobeusedforalongtime.

    B.Settlementofoutdoorunit

    1) Anchortheoutdoorunitwitha bolt andnuttightlyandhorizontallyonaconcreteorrigidmount.

    2)Wheninstallingonthewall,rooforrooftop,anchor

    themountingbasesecurelywithanailorwireassum-ingtheinfluenceofwindandearthquake.3)Inthecasewhenthevibrationoftheunitisconveyed

    tothehose,securetheunitwithananti-vibrationrub-ber.

    Bolt

    Tubing connection

    C.Evaluationoftheperformance

    Operateunitfor15~20minutes,thencheckthesystemrefrigerantcharge:1.Measurethepressureofthegassideservicevalve.

    2.Measurethetemperatureoftheintakeanddischargeofair.

    3.Ensurethedifferencebetweentheintaketemperatureandthedischargeismorethan8C(Cooling)or

    reversely(Heating).

    Discharge air

    Intake temperature

    Discharge temperature

    4.Forreference;thegassidepressureofoptimumcondi-

    tionisasbelow.(Cooling)

    OutsideambientTEMP. Thepressureofthegassideservicevalve

    35C(95F) 4~6kg/cm2.G(56.8~85.2P.S.I.G.)

    NOTE:Iftheactualpressurearehigherthanshown,thesystemismostlikelyover-charged,andchargeshouldberemoved.Iftheactualpressurearelowerthanshown,thesystemismostlikelyundercharged,andchargeshouldbeadded.

    Theairconditionerisnowreadyforuse.

    PUMPDOWN

    Thisisperformedwhentheunitistoberelocatedortherefrigerantcircuitisserviced.PumpDownmeanscollectingallrefrigerantintheout-doorunitwithoutlossinrefrigerantgas.

    CAUTION:BesuretoperformPumpDownprocedurewiththeunitcoolingmode.

    PumpDownProcedure1.Connectalow-pressuregaugemanifoldhosetothe

    chargeportonthegassideservicevalve.

    2.Openthegassideservicevalvehalfwayandpurgetheairfromthemanifoldhoseusingtherefrigerantgas.

    3.Closetheliquidsideservicevalve(allthewayin).

    4.Turnontheunit'soperatingswitchandstartthecoolingoperation.

    5.Whenthelow-pressuregaugereadingbecomes1to0.5kg/cm2.G(14.2to7.1P.S.I.G.),fullyclosethegassidevalvestemandthenquicklyturnofftheunit.Atthattime,PumpDownhasbeencompletedandallrefrigerantgaswillhavebeencollectedintheoutdoorunit.

    16