78
2005 National Building Code of Canada Seismic Design Changes Impact on Insurance Industry

2005 National Building Code of Canada Seismic Design Changes

Embed Size (px)

Citation preview

Page 1: 2005 National Building Code of Canada Seismic Design Changes

2005 National Building Code of Canada

Seismic Design ChangesSeismic Design Changes

Impact on Insurance Industry

Page 2: 2005 National Building Code of Canada Seismic Design Changes

NBCC 2005 Seismic Design Changes

Page 3: 2005 National Building Code of Canada Seismic Design Changes

Gravity Element Failures

Page 4: 2005 National Building Code of Canada Seismic Design Changes

Reinforced Concrete Column Confinement

Page 5: 2005 National Building Code of Canada Seismic Design Changes

What Causes Earthquakes

Page 6: 2005 National Building Code of Canada Seismic Design Changes

2002

Plattsburgh

NY

Page 7: 2005 National Building Code of Canada Seismic Design Changes

Population

NBCC communities

Page 8: 2005 National Building Code of Canada Seismic Design Changes

“Risk”

Page 9: 2005 National Building Code of Canada Seismic Design Changes

Cascadia Subduction

Zone

1700 A.D.

Magnitude 9

Page 10: 2005 National Building Code of Canada Seismic Design Changes

Jan de Fuca Plate Slip

Page 11: 2005 National Building Code of Canada Seismic Design Changes
Page 12: 2005 National Building Code of Canada Seismic Design Changes

2005 National Building Code of Canada Seismic Design

• Basics of Seismic Design

• Changes Incorporated in 2005 NBCC

• Seismic Loads – New Hazard Map

• Structural Analysis

• Rationale Behind the Changes

• Changes in CSA A23.3 Design Of Concrete Structures Standard.

• Implications for the Insurance Industry

Page 13: 2005 National Building Code of Canada Seismic Design Changes

Factors Influencing Seismic Effects

• EQ Magnitude

• Type of EQ

• Distance

• Soil

• Structure

Page 14: 2005 National Building Code of Canada Seismic Design Changes

Ductility – Dissipating Seismic Energy

Page 15: 2005 National Building Code of Canada Seismic Design Changes

Structural Response To Earthquakes

Page 16: 2005 National Building Code of Canada Seismic Design Changes

Acceleration Response Spectrum

V = m x a

Page 17: 2005 National Building Code of Canada Seismic Design Changes

Natural Modes of Building Vibration

� Seismic Motion �

Page 18: 2005 National Building Code of Canada Seismic Design Changes

Concrete Plastic Hinges

Page 19: 2005 National Building Code of Canada Seismic Design Changes

Seismic Shake Table Testing

Page 20: 2005 National Building Code of Canada Seismic Design Changes

Ductility - Shear Wall Structures

( a ) = 1 .5 ( b ) = 2 .0 ( c ) = 3 .5

≥ 0 .0 0 2 0

0 .0 0 1 5≥

≤ 5 0 0 m m

3≤

0 .0 0 2 5

0 .0 0 2 5

5 0 0 m m

≤ 3

4 5 0 m m

0 .0 0 2 5

0 .0 0 2 5

T ie s @ ≤ 1 6

4 8≤

H o o p s @

2 4≤

6≤

/ 2

≤ 3 0 0 m m ( p la s t ic h in g e )

Page 21: 2005 National Building Code of Canada Seismic Design Changes

Braced Steel Structures

Page 22: 2005 National Building Code of Canada Seismic Design Changes

2005 NBCC - Uniform Hazard Spectrum

• More uniform margin of collapse (NEHRP),

1997 and Building Seismic Safety Council,

1997)

• Seismic hazard at a lower probability of

exceedance, nearer probability of failure exceedance, nearer probability of failure

• Maximum considered earthquake ground

motion

• 2% in 50 year probability of exceedance

(2500 year return period)

• New seismic hazard maps

Page 23: 2005 National Building Code of Canada Seismic Design Changes

2005 NBCC Seismic Design

Bad News

• 1995 Seismic Risk Level

– 10% in 50 yrs => 1 / 475 yrs return period

• 2005 New Seismic Risk Level• 2005 New Seismic Risk Level

– 2% in 50 yrs => 1 / 2400 yrs return period

• Good News:

500 x 5 ≠ 2500

Page 24: 2005 National Building Code of Canada Seismic Design Changes

Hazard

Page 25: 2005 National Building Code of Canada Seismic Design Changes

Probabilistic

seismic

hazard

Double

integration to

give hazard

Page 26: 2005 National Building Code of Canada Seismic Design Changes

Rates of

activity, and

sizes of the

biggest events biggest events

were

underestimated

Page 27: 2005 National Building Code of Canada Seismic Design Changes

Different

rates,

different

errors in errors in

rates for

magnitude-

recurrence

curves Mx

Page 28: 2005 National Building Code of Canada Seismic Design Changes

Some

data do

not

appear to appear to

fit the

simple

model

Page 29: 2005 National Building Code of Canada Seismic Design Changes

Highest value of:-

Full Robust Hazard Model

Highest value of:-

Probabilistic H model

Probabilistic R model

Deterministic Cascadia model

Probabilistic Stable craton model

Page 30: 2005 National Building Code of Canada Seismic Design Changes

Base Shear NBCC 1995 vs 2005

V =VE

RU

VE = v S I F W

1995

V =S (Ta) Mv IE

Rd Ro

W

VE = v S I F W

2005

Page 31: 2005 National Building Code of Canada Seismic Design Changes

Design Spectral Accelerationdefined by 4 spectral hazard parameters

and 2 site factors

( ) ( )( ) ( )

smaller, is whichever

20or 50

s 20for 20

.SF.SF

.T.SFTS

aaav

aa

=

≤=

( )( )( ) s 04for 202

s 02for 02

s 01for 01

s 50for

smaller, is whichever

.T.SF

.T.SF

.T.SF

.T

av

av

av

≥=

==

==

=

Page 32: 2005 National Building Code of Canada Seismic Design Changes

Influence Of Soil

• The Soil Factor

Can change the characteristics of earthquake motions.

• Poor - deep loose sand; silty clays; sand and gravel; and soft, saturated granular soils.

Amplify earthquake forces on water-saturated soils

• Good - bedrock stiff soils.

Much less vibration is transferred through the

foundation to the structure above.

Page 33: 2005 National Building Code of Canada Seismic Design Changes

Site Classification for Seismic Site Response

• A = hard rock

• B = rock

• C = dense soil or soft rock• C = dense soil or soft rock

• D = stiff soil

• E = > 3 m of “soft soil”

• F = others (liquefiable, peat, etc.)

Page 34: 2005 National Building Code of Canada Seismic Design Changes

Design Spectral Response Acceleration – Class “C” Soil

0.2

0.4

0.6

0.8

1.0

S(T)

Vancouver

Montreal

Toronto

Saskatoon

0.0

0.2

0 1 2 3 4

T, s

Page 35: 2005 National Building Code of Canada Seismic Design Changes

Conversion factors have been derived to ensure

all hazard values are for site Class C

Page 36: 2005 National Building Code of Canada Seismic Design Changes

Uniform Hazard Spectra

Page 37: 2005 National Building Code of Canada Seismic Design Changes
Page 38: 2005 National Building Code of Canada Seismic Design Changes

Uniform

Hazard

Spectra

probabilistic

and and

Cascadia

Page 39: 2005 National Building Code of Canada Seismic Design Changes

Deaggregation of hazard

contributions by magnitude and distance

Page 40: 2005 National Building Code of Canada Seismic Design Changes

Deaggregation of hazard

contributions by magnitude and

distance

Page 41: 2005 National Building Code of Canada Seismic Design Changes
Page 42: 2005 National Building Code of Canada Seismic Design Changes

New probability level will lead to

more uniform protection

500 x 5 ≠ 2500

Page 43: 2005 National Building Code of Canada Seismic Design Changes

Uniform Hazard Spectrum

• More uniform margin of collapse (NEHRP),

1997 and Building Seismic Safety Council,

1997)

• Seismic hazard at a lower probability of

exceedance, nearer probability of failure exceedance, nearer probability of failure

• Maximum considered earthquake ground

motion

• 2% in 50 year probability of exceedeance

(2500 year return period)

• New seismic hazard maps

Page 44: 2005 National Building Code of Canada Seismic Design Changes

General Requirements NBCC 2005

Seismic Structural Design

• Design for clearly defined load paths

• Must have a clearly defined Seismic

Force Resisting System (SFRS)Force Resisting System (SFRS)

• Stiff elements not part of SFRS to be

separated from structural components

or made part of SFRS and accounted

for in analysis

Page 45: 2005 National Building Code of Canada Seismic Design Changes

Base Shear NBCC 1995 vs 2005

V =VE

RU

VE = v S I F W

1995

V =S (Ta) Mv IE

Rd Ro

W

=

2005

Page 46: 2005 National Building Code of Canada Seismic Design Changes

Ro (Overstrength) Factor 1.3-1.7

V =S (Ta) Mv IE

Rd Ro

W

V =Ve W

R R RR R Ro yieldsize sh mech= φ

Rd = Ductility 1.5 ����4.0

V =Ve

Rd Ro

W

Page 47: 2005 National Building Code of Canada Seismic Design Changes

Ro (Overstrength) Factor

Ro depends on the system :1.3 – 1.7

Mpb

α Mpb α Mpb

Mpb

-

- -

+

Page 48: 2005 National Building Code of Canada Seismic Design Changes

(a) = 1.5 (b) = 2.0 (c) = 3.5

Rd= 1.5 - 4.0

≥ 0.0020

0.0015≥

≤ 500 mm

3≤

0.0025

0.0025

500 mm

≤ 3

450 mm

0.0025

0.0025

Ties @ ≤16

48≤

Hoops @

24≤

6≤

/2

≤ 300 mm (plastic hinge)

Page 49: 2005 National Building Code of Canada Seismic Design Changes

(a) = 1.5 (b) = 2.5 (c) = 4.0

/2 /2 /2 /2

>>>

450 mm

/6

>>>

450 mm

/6

≤≤≤

16

48

≤≤≤

8

24

≤ 300 mm

/2

≤≤≤

8

24

≤ 300 mm

/4

≤≤≤

6

100 mm

≤ confinement

/4

≤≤≤

8

24

≤ 300 mm

/4

steel2 2 2 2 2 2

Rd

1

1

1

1

1

1

SECTION 2 - 2SECTION 1 - 1 SECTION 1 - 1 SECTION 1 - 1SECTION 2 - 2 SECTION 2 - 2

Page 50: 2005 National Building Code of Canada Seismic Design Changes

(a) = 1.5 (b) = 2.0 (c) = 3.5, 4.0

stirrups@ /2≤

Beams Diagonalbars hoops

Beamsstirrups@ @ 6≤

24

100 mm

≤≤≤

8

24

≤ 300 mm

/4

Page 51: 2005 National Building Code of Canada Seismic Design Changes

Ve=

R Factors

V

Ve

VV

RUe=1995:

VV

R Re

d o

=

∆e∆

V = / R R d oVe

Ve / Rd

2005:

Page 52: 2005 National Building Code of Canada Seismic Design Changes

Effect of R values

EX

PE

CT

ED

FO

RC

E

R =

2.0

R =

4.0

TARGET DISPLACEMENT

EX

PE

CT

ED

FO

RC

E

Page 53: 2005 National Building Code of Canada Seismic Design Changes

Base shear comparison

R/C Ductile shear walls, Rd = 3.5

Soil Class C

0.12

VAN - 2004

MTL - 2004

0.0 1.0 2.0 3.0 4.0Period (s)

0.00

0.04

0.08

V /

W

MTL - 2004

TOR - 2004

VAN - 1995

MTL - 1995

TOR - 1995

Page 54: 2005 National Building Code of Canada Seismic Design Changes

Influence of RdRo (R/C SFRS)

Montreal, Soil Class C

0.20

0.25 R/C SFRS - Montreal

Conv. Construction

MD Walls

D Walls

0.0 1.0 2.0 3.0 4.0Period (s)

0.00

0.05

0.10

0.15

V /

W

D Walls

D Partially coupled walls

D Coupled walls

MD MRFs

D MRFs

Page 55: 2005 National Building Code of Canada Seismic Design Changes

Influence of RdRo (R/C SFRS)

Vancouver, Soil Class C

0.30

0.40 R/C SFRS - Vancouver

Conv. Construction

MD Walls

D Walls

0.0 1.0 2.0 3.0 4.0Period (s)

0.00

0.10

0.20

V /

W

D Walls

D Partially coupled walls

D Coupled walls

MD MRFs

D MRFs

Page 56: 2005 National Building Code of Canada Seismic Design Changes

2005 NBCC Seismic Analysis

• Better consideration of irregularities

• Requires more dynamic analysis

• Better consideration of torsional sensitivity

• Lateral storey drift limit increased: 2% -> • Lateral storey drift limit increased: 2% -> 2.5%. Relates to structural damage.

• Post-disaster buildings shall not have any irregularity

Page 57: 2005 National Building Code of Canada Seismic Design Changes

Types of structural irregularities

1 Vertical stiffness irregularity

2 Weight (mass) irregularity

3 Vertical geometric irregularity

4 In-plane discontinuity4 In-plane discontinuity

5 Out-of-plane offsets

6 Discontinuity in capacity (weak storey)

7 Torsional sensitivity

8 Non-orthogonal systems

Page 58: 2005 National Building Code of Canada Seismic Design Changes

Irregularity trigger

When:

IE·Fa·Sa(0.2) > 0.35

+ any one of the 8 irregularity types,+ any one of the 8 irregularity types,

the building is considered as irregular

Page 59: 2005 National Building Code of Canada Seismic Design Changes

Types of Irregularities

1 Vertical Stiffness

lateral stiffness of the SFRS in a storey:

< 70% of that in any adjacent storey, or

< 80% of the average stiffness of the 3

storeys above or below.storeys above or below.

Page 60: 2005 National Building Code of Canada Seismic Design Changes

Types of Irregularities

2 Weight (Mass)

weight of a storey > 150% of weight of anadjacent storey.

(a roof lighter than a floor below is excluded) (a roof lighter than a floor below is excluded)

Page 61: 2005 National Building Code of Canada Seismic Design Changes

Types of Irregularities

3 Vertical Geometric

horizontal dimension of the SFRS in a storey > 130% of that in any adjacent storey.

(one-storey penthouse excluded)(one-storey penthouse excluded)

Page 62: 2005 National Building Code of Canada Seismic Design Changes

Types of Irregularities

4 In-Plane Discontinuity

• in-plane offset of an element of the SFRS,

or

• reduction in lateral stiffness of an element in • reduction in lateral stiffness of an element in the storey below.

Page 63: 2005 National Building Code of Canada Seismic Design Changes

Types of Irregularities

5 Out-of-Plane Offsets

discontinuity of lateral force path

e.g., out-of-plane offsets

of the elements of the SFRS.of the elements of the SFRS.

Top FloorsBottom Floors

Page 64: 2005 National Building Code of Canada Seismic Design Changes

Types of Irregularities

6 Discontinuity in Capacity - Weak Storey

storey shear strength less than

that in the storey above.

(Storey shear strength = total of all elements of the (Storey shear strength = total of all elements of the SFRS in the direction considered)

Page 65: 2005 National Building Code of Canada Seismic Design Changes

Types of Irregularities

7 Torsional sensitivity

if the ratio B > 1.7.

B = δδδδmax / δδδδavg

δ δ δ δ calculated for static loads applied at ±±±± 0.10 Dδ δ δ δ calculated for static loads applied at ±±±± 0.10 Dn

Plan

Page 66: 2005 National Building Code of Canada Seismic Design Changes

Types of Irregularities

8 Non-orthogonal systems

SFRS not oriented along a set of orthogonal axes.

Plan

Page 67: 2005 National Building Code of Canada Seismic Design Changes

Seismic Importance Factor

Importance

Category IE

Low 0.8Low 0.8

Normal 1.0

High 1.3

Post Disaster 1.5

Page 68: 2005 National Building Code of Canada Seismic Design Changes

Modern Design Codes

• SEAOC 1988/NBC 1990

• CSA A23.3 1984 Canadian Concrete Design Code

• Introduced “Capacity Design”

Page 69: 2005 National Building Code of Canada Seismic Design Changes

Concrete Plastic Hinges

Page 70: 2005 National Building Code of Canada Seismic Design Changes

Overview of Clause 21 Changes

• Introduced a “ductility” limit state for plastic hinges in walls and coupling beams

• Rotational capacity ≥ Rotational demand

∆ f ( R d R o - γ w )

idicθθ ≥

υ id

hw

hw

- L

w/2

Lw

Lw/2

Page 71: 2005 National Building Code of Canada Seismic Design Changes

Plastic Hinges to Absorb Energy

Page 72: 2005 National Building Code of Canada Seismic Design Changes

NBCC Concrete Ductile

Systems

SINGLE WALL

Rd = 2.0 Rd = 4.0

COUPLED WALL

Rd = 2.5

MOMENT FRAME

Rd = 3.5 Rd = 4.0Rd = 3.5

Page 73: 2005 National Building Code of Canada Seismic Design Changes

Un-Classified Systems

OUTRIGGER WALLFRAME WALLWALL - COLUMNS BRACED FRAME

Page 74: 2005 National Building Code of Canada Seismic Design Changes

Earthquake Design Factor of

Safety

• “Earthquake” Factored Load Design

– Factored Load ≈ 0.15 to 0.5 x Expected

LoadLoad

– Factored Bending Resistance ≈ 0.17 to 0.6

x Expected Load

– “Factor of Safety” ≈ 0.17 to 0.6

Page 75: 2005 National Building Code of Canada Seismic Design Changes

Philosophical Underpinning

• Earthquakes are rare events, the design event has a 2% probability of exceedance in 50 years. That is, in an assumed 50 year building life, there is a 98% chance year building life, there is a 98% chance that the building will not experience an earthquake of this magnitude in its design life.

• Therefore design only for life safety, not asset protection, the building may be irreparable but no one dies.

Page 76: 2005 National Building Code of Canada Seismic Design Changes

2005 NBCC – Objective Based Format

• Part 1 – Objectives of the Code

• Part 2 – Prescriptive Solutions to Objectives

• 1995• 1995

• Firewalls with a fire rating of 2 hrs or less shall

be constructed of concrete or masonry.

• 2005

• Firewalls with a fire rating of 2 hrs or less not

explicitly required to be masonry or concrete.

Page 77: 2005 National Building Code of Canada Seismic Design Changes

Further Information

Commentary J - NBCC 2005Canadian J. of Civil Engineering, April 2003:

- overview and background of changes- seismic hazard maps

- ground amplification factors- ground amplification factors- equivalent static load method- force modification factors- torsion- dynamic analysis- foundation rocking- non-structural components

Page 78: 2005 National Building Code of Canada Seismic Design Changes

Thank YouThank You