Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
2002 IS Catalog
116 Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Introduction ............................................................................................................................. 117Rotation Speed Limit Alarm
KFD2-DWB-Ex1.D (24 VDC) ............................................................................................................... 118KFA5-DWB-Ex1.D (120 VAC) .............................................................................................................. 119KFA6-DWB-Ex1.D (240 VAC) .............................................................................................................. 120
Rotation Speed Converter (Digital to analog converter)KFU8-FSSP-1.D (24 VDC, 120 or 240 VAC) ...................................................................................... 121KFD2-UFC-Ex1 (24 VDC without display) .......................................................................................... 122KFD2-UFC-Ex1.D (24 VDC with display) ............................................................................................. 123KFU8-UFC-Ex1 (24 VDC, 120 or 240 VAC without display) ............................................................... 124KFU8-UFC-Ex1.D (24 VDC, 120 or 240 VAC with display) ................................................................ 125
Universal Logic ControlsKFD2-UFT-Ex2.D (24 VDC) ................................................................................................................. 126KFU8-UFT-Ex2.D (24 VDC, 120 or 240 VAC) ...................................................................................... 127
TimerKFD2-DU-Ex1.D (24 VDC) ................................................................................................................... 128KFA5-DU-Ex1.D (120 VAC) ................................................................................................................. 129KFA6-DU-Ex1.D (240 VAC) ................................................................................................................. 130KFD2-CRG-Ex1.D (24 VDC) ................................................................................................... 131KFU8-CRG-Ex1.D (24 VDC, 120 or 240 VAC) ........................................................................ 132
Latching RelayKFA5-SR2-Ex2.W.IR (120 VAC) .............................................................................................. 133KFA6-SR2-Ex2.W.IR (240 VAC) .............................................................................................. 134
Universal Limit Alarm (Voltage, current, RTD, T/C)KFD2-GU-Ex1 (24 VDC Intrinsic safety applications) .......................................................................... 135
Page
2002 IS Catalog
117Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Logic controls typically convert analog voltage or current inputs to signals that monitor for speed,direction, frequency or time. Some logic controls feature relay outputs that can be used to selectminimum and maximum values. These versatile modules can be used for level control, for poweringtransmitters, or for a multitude of general-purpose and intrinsically safe applications.
When combined with P+F N3 output sensors, the following switch isolators act as logic controlsand can be used to detect the direction of moving targets:
• KFD2-SR2-Ex2.W (see page 11)• KFD2-SR2-Ex2.2S (see page 12)• KFA5-SR2-Ex2.W (see page 15)• KFA6-SR2-Ex2.W (see page 16)• KFD2-SOT2-Ex2 (see page 21)• KFA5-SOT2-Ex2 (see page 24)• KFA6-SOT2-Ex2 (see page 25)• KFD2-ST2-Ex2 (see page 26)
To be used as direction detection, these logic controls must be connected to a bistable, N3 outputsensors found in the 2002 P+F Sensor Catalog. These sensors have outputs that latch when atarget passes through the ring and do not unlatch until the target passes in the opposite direction.For more information about these switch isolators, refer to the pages indicated above. For assistancewith direction detection applications, contact a GreenTeam representative at (330) 486-0002 or e-mail usat [email protected].
Introduction
Direction Detection with Special P+F NAMUR Sensors
118
Technical Data
Connection Diagram
Model Number
2002 IS CatalogLogic
Contr
ols
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
KFD2-DWB-Ex1.D
Logic ControlsRotational SpeedLimit Alarm
The KFD2-DWB-Ex1.D monitors foroverspeed or underspeed conditions bycomparing the input frequency to the user-programmed reference frequency. Thereference frequency is easily programed bypush buttons mounted on the front panel.An overspeed or underspeed condition issignaled via the relay outputs. Leadbreakage and short circuits in the sensorare indicated by a red LED and throughthe collective error output via Power Rail.The start-up override feature sets relayoutputs to default conditions programmedby the user, for up to 1,000 seconds.
24 VDC supply
Operating range 0.06-300,000RPM (0.001-5,000 Hz)
Relay outputs
Push-button programmable
Collective error messaging
LCD display
Lead breakage (LB) and shortcircuit (SC) monitoring
17
1618
111012
13
14
23
24
Output 1
Output 2
Start Up Override
Supply 24 VDC
KFD2-DWB-Ex1.D
Collective Error Messaging
1
3
Input 1
LB/SCLB/SC LB
R2
R1R1
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
Power Supply Terminals 23, 24 or power railNominal voltage 20-30 VDCPower consumption 2 W
Input (intrinsically safe) Terminals 1+, 3-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs
Outputs (not intrinsically safe)Relay output 1 (SPDT) Terminals 10, 11 and 12Relay output 2 (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ø ≥ 0.7; 40 VDC / 2 A
Mechanical life ≥ 5 x 107 operationsEnergizing / de-energizing ≈ 20 ms/ ≈20 ms
Entity ParametersFM control drawing no. 116-0200
Transfer CharacteristicsFrequency range 0.001-5,000 Hz
MechanicalHousing Type C3 (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)
Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)
Class I, Div 1, Group A-G:Class I, Zone 0, II C
119
Technical Data
Connection Diagram
Model Number
2002 IS CatalogLogic
Contro
ls
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Logic ControlsRotational SpeedLimit Alarm
The KFA5-DWB-Ex1.D monitors for anoverspeed or underspeed condition bycomparing the input frequency to the userprogrammed reference frequency. Thereference frequency is easily programmedby the use of a keypad located on the frontof the unit. An overspeed or underspeedcondition is signaled via the relay outputs.Lead breakage and short circuits in thesensor are indicated by a red LED. Thestart-up override feature sets relay outputsto default conditions programmed by theuser, for up to 1,000 seconds.
120 VAC supply
Operating range 0.06-300,000RPM (0.001-5,000 Hz)
Relay outputs
Push-button programmable
Start-up override
LCD display
Lead breakage (LB) and shortcircuit (SC) monitoring
KFA5-DWB-Ex1.D
17
1618
111012
13
14
23
24
Output 1
Output 2
Start Up Override
Supply 120 VAC
KFA5-DWB-Ex1.D
1
3
Input 1
LB/SCLB/SC LB
R2
R1R1
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
Power Supply Terminals 23, 24Nominal voltage 120 VACPower consumption 2 VA
Input (intrinsically safe) Terminals 1+, 3-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs
Outputs (not intrinsically safe)Relay output 1 (SPDT) Terminals 10, 11, 12Relay output 2 (SPDT) Terminals 16, 17, 18Contact load 250 VAC / 2 A / cos ø > 0.7; 40 VDC / 2 A
Mechanical life ≥ 5 x 107 operationsEnergizing / de-energizing ≈ 20 ms / ≈ 20 ms
Entity ParametersFM control drawing no. 116-0200
Transfer CharacteristicsFrequency range 0.001-5,000 Hz
MechanicalHousing Type C3 (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)
Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)
Class I, Div 1, Group A-G:Class I, Zone 0, II C
120
Technical Data
Connection Diagram
Model Number
2002 IS CatalogLogic
Contr
ols
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Logic ControlsRotational SpeedLimit Alarm
The KFA6-DWB-Ex1.D monitors for anoverspeed or underspeed condition bycomparing the input frequency to the userprogrammed reference frequency. Thereference frequency is easily programmedby the use of a keypad located on the frontof the unit. An overspeed or underspeedcondition is signaled via the relay outputs.Lead breakage and short circuits in thesensor are indicated by a red LED. Thestart-up override feature sets relay outputsto default conditions programmed by theuser, for up to 1,000 seconds.
KFA6-DWB-Ex1.D
240 VAC supply
Operating range 0.06-300,000RPM (0.001-5,000 kHz)
Relay outputs
Push-button programmable
Start-up override
LCD display
Lead breakage (LB) and shortcircuit (SC) monitoring
17
1618
111012
13
14
23
24
Output 1
Output 2
Start Up Override
Supply 240 VAC
KFA6-DWB-Ex1.D
1
3
Input 1
LB/SCLB/SC LB
R2
R1R1
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
Power Supply Terminals 23, 24Nominal voltage 240 VACPower consumption 2 VA
Input (intrinsically safe) Terminals 1+, 3-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs
Outputs (not intrinsically safe)Relay output 1 (SPDT) Terminals 10, 11 and 12Relay output 2 (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ø > 0.7; 40 VDC / 2 A
Mechanical life ≥ 5 x 107 operationsEnergizing / de-energizing ≈ 20 ms / ≈ 20 ms
Transfer CharacteristicsFrequency range 0.001-5,000 Hz
Entity ParametersFM control drawing number 116-0200
MechanicalHousing Type C3 (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)
Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)
Class I, Div 1, Group A-G:Class I, Zone 0, II C
121
Technical Data
Connection Diagram
Model Number
2002 IS CatalogLogic
Contro
ls
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Digital to AnalogConverter
The KFU8-FSSP-1.D converts a digitalinput signal into an analog output signalfor connection to standard current orvoltage input devices. A scaleable digitalpulse output is provided to isolate andtransfer the digital signal. The inputfrequency range is easily programmed withthe push buttons on the front panel.Alternatively, the unit can be programmedto record the input frequency range. Thesame unit can be powered from 24 VDC,120 VAC or 240 VAC.
KFU8-FSSP-1.D
24 VDC, 120 or 240 VAC supply
Operating range 0.06-599,940RPM (0.001-9,999 kHz)
Analog current and voltage output
Push-button programmable
LED display
KFU8-FSSP-1.D
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
Power SupplyNominal voltage 240 VAC, < 5 VA, terminals 16, 18
120 VAC, < 5 VA, terminals 17, 1824 VDC, < 5 W, terminals 11, 12
Inputs (not intrinsically safe)Nominal data NAMUR, 2-, 3- or 4- wire DCInput pulse length / interval ≥ 40 µs / ≥ 40 µs
Output (not intrinsically safe)Nominal voltage term. 5, 6: 0-10/2-10 VDC, resolution 10 mVNominal current term. 4, 5: 0-20 / 4-20 mA, resolution 20 µA,Measurement accuracy ≤ 0.2 % of the final valueTemperature drift ≤ 0.005 % / ºC of the final value
MechanicalHousing Type B4 (see page 387)Dimensions (mm) 107 x 40 x 115Weight 300 g (10.6 oz.)
Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)
122
Technical Data
Connection Diagram
Model Number
2002 IS CatalogLogic
Contr
ols
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
24 VDC supply
Operating range 0.06-300,000RPM (0.001-5,000 kHz)
Analog and digital outputs
PC programmable
Lead breakage (LB) and shortcircuit (SC) monitoring
10
171618192087
1314
Output 1
Output 2
Output 3
Output 4 0/4-20 mA
Start Up Override
KFD2-UFC-Ex1
Programming JackGND
TxDRxD
Collective Error Messaging
12
11
2324
Supply 24 VDC
1
3
Input 1
LB/SCLB/SC LB
R2
R1R1
Universal FrequencyConverter
This universal frequency converter convertsa digital input signal into an analog outputsignal for connection to standard currentinput devices. A passive transistor outputisolates and transfers the digital signal.Two relay outputs can be programmedto actuate at desired frequencies. The unitis programmable with a PC and thePACTware configuration software. Adebounce filter eliminates extraneoussignals from relay bounce.
Lead breakage and short circuits in thesensor are indicated by a red LED andthrough the collective error output viaPower Rail.
KFD2-UFC-Ex1
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
Power Supply Terminals 23, 24 or power railNominal voltage 20-30 VDCPower consumption 2.2 W
Input (intrinsically safe) Terminals 1+, 3-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs
Outputs (not intrinsically safe)Relay output 1 (SPDT) Terminals 10, 11 and 12Relay output 2 (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ø ≥ 0.7; 40 VDC / 2AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 ms
Output 3 (passive transistor) Terminals 19+ and 20-Nominal current 50 mA, short circuit-protectedLogic 1 voltage drop < 2.5 VLogic 0 output switched off (leakage < 10 µA)
Output 4 (current) Terminals 8+ and 7-Open circuit voltage ≤ 24 VDCOutput current 0-20 mA or 4-20 mAError signal Downscale < 3.6 mA, upscale ≥ 22 mA
Load ≤ 650 Ω
Entity ParametersFM control drawing no. 116-0200
MechanicalHousing Type C3 (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)
Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)
Class I, Div 1, Group A-G:Class I, Zone 0, II C
123
Technical Data
Connection Diagram
Model Number
2002 IS CatalogLogic
Contro
ls
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Universal FrequencyConverter withDisplay
This universal frequency converter convertsa digital input signal into an analog outputsignal for connection to standard currentinput devices. A passive transistor outputisolates and transfers the digital signal.Two relay outputs can be programedto actuate at desired frequencies. Theunits is programmable with a PC andthe PACTware configuration software. Adebounce circuit eliminates extraneoussignals from relay bounce.
Lead breakage and short circuits in thesensor are indicated by a red LED andthrough the collective error output viaPower Rail.
KFD2-UFC-Ex1.D
24 VDC supply
Operating range 0.06-300,000RPM (0.001-5,000 kHz)
Analog and digital outputs
Push-button and PCprogrammable
LCD display
Lead breakage (LB) and shortcircuit (SC) monitoring
Power Supply Terminals 23, 24 or power railNominal voltage 20-30 VDCPower consumption 2.2 W
Input (intrinsically safe) Terminals 1+, 3-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs
Outputs (not intrinsically safe)Relay output 1 (SPDT) Terminals 10, 11 and 12Relay output 2 (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ø > 0.7; 40 VDC / 2AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈20 ms
Output 3 (passive transistor) Terminals 19+ and 20-Nominal current 50 mA, short circuit-protectedLogic 1 voltage drop < 2.5 VLogic 0 output switched off (leakage < 10 µA)
Output 4 (current) Terminals 8+ and 7-Open circuit voltage ≤ 24 VDCOutput current 0-20 mA or 4-20 mAError signal Downscale < 3.6 mA, upscale ≥ 22 mALoad ≤ 650 Ω
Entity parametersFM control drawing no. 116-0200
MechanicalHousing Type C3 (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)
Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
10
171618192087
1314
Output 1
Output 2
Output 3
Output 4 0/4-20 mA
Start Up Override
KFD2-UFC-Ex1.D
Programming JackGND
TxDRxD
Collective Error Messaging
12
11
1
3
Input 1
LB/SCLB/SC LB
R2
R1R1
2324
Supply 24 VDC
Class I, Div 1, Group A-G:Class I, Zone 0, II C
124
Technical Data
Connection Diagram
Model Number
2002 IS CatalogLogic
Contr
ols
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Universal FrequencyConverter
This universal frequency converterconverts a digital input signal into ananalog output signal for connection tostandard current input devices. A passivetransistor output isolates and transfers thedigital signal. Two relay outputs can beprogrammed to actuate at desiredfrequencies. The unit is programmable witha PC and the PACTware configurationsoftware. A debounce circuit eliminatesextraneous signals from relay bounce. Thesame unit can be powered from 24 VDC,120 VAC or 240 VAC.
Lead breakage and short circuits in thesensor are indicated by a red LED.
KFU8-UFC-Ex1
Can supply 24 VDC, 120 or240 VAC
Operating range 0.06-300,000RPM (0.001-5,000 kHz)
Analog and digital outputs
PC programmable
Lead breakage (LB) and shortcircuit (SC) monitoring
10
171618192087
1314
Output 1
Output 2
Output 3
Output 4 0/4-20 mA
Start Up Override
KFU8-UFC-Ex1
Programming JackGND
TxDRxD
12
11
23
24
1
3
Input 1
LB/SCLB/SC LB
R2
R1R1
Supply 24 VDC 120 VAC 240 VAC
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
Power Supply Terminals 23, 24Nominal voltage 20-90 VDC; 48-250 VACPower consumption 2.2 W; 3 VA
Input (intrinsically safe) Terminals 1+, 3-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs
Outputs (not intrinsically safe)Relay output 1 (SPDT) Terminals 10, 11 and 12Relay output 2 (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ≥ 0.7; 40 VDC/2AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 ms
Output 3 (passive transistor) Terminals 19+ and 20-Nominal current 50 mA, short circuit-protectedLogic 1 voltage drop < 2.5 VLogic 0 output switched off (leakage ≤ 10 µA)
Output 4 (current) Terminals 8+ and 7-Open circuit voltage ≤ 24 VDCOutput current 0-20 mA or 4-20 mAError signal Downscale ≤3.6 mA, upscale≥22mALoad ≤ 650 Ω
Entity ParametersFM control drawing no. 116-0200
MechanicalHousing Type C3 (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)
Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)
Class I, Div 1, Group A-G:Class I, Zone 0, II C
125
Technical Data
Connection Diagram
Model Number
2002 IS CatalogLogic
Contro
ls
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Universal FrequencyConverter withDisplay
KFU8-UFC-Ex1.D
This universal frequency converterconverts a digital input signal into ananalog output signal for connection tostandard current input devices. A passivetransistor output isolates and transfers thedigital signal. Two relay outputs can beprogrammed to actuate at desiredfrequencies. The unit is programmable byusing push buttons on the front panel, orwith a PC and the PACTware configurationsoftware. A debounce circuit eliminatesextraneous signals from relay bounce. Thesame unit can be powered from 24 VDC, 120VAC or 240 VAC.
Lead breakage and short circuits in thesensor are indicated by a red LED.
Can supply 24 VDC, 120 or240 VAC
Operating range 0.06-300,000RPM (0.001-5,000 kHz)
Analog and digital outputs
Push-button and PCprogrammable
LCD display
Lead breakage (LB) and shortcircuit (SC) monitoring
10
171618192087
1314
Output 1
Output 2
Output 3
Output 4 0/4-20 mA
Start Up Override
KFU8-UFC-Ex1.D
Programming JackGND
TxDRxD
12
11
23
24
1
3
Input 1
LB/SCLB/SC LB
R2
R1R1
Supply 24 VDC 120 VAC 240 VAC
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
Power Supply Terminals 23, 24Nominal voltage 20-90 VDC ; 48-250 VACPower consumption 2.2 W; 3 VA
Input (intrinsically safe) Terminals 1+, 3-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs
Outputs (not intrinsically safe)Relay output 1 (SPDT) Terminals 10, 11 and 12Relay output 2 (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ø ≥ 0.7; 40 VDC / 2AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 ms
Output 3 (passive transistor) Terminals 19+ and 20-Nominal current 50 mA, short circuit-protectedLogic 1 voltage drop < 2.5 VLogic 0 output switched off (leakage ≤ 10 µA)
Output 4 (current) Terminals 8+ and 7-Open circuit voltage ≤ 24 VDCOutput current 0-20 mA or 4-20 mAError signal Downscale ≤ 3.6 mA, upscale ≥ 22 mALoad ≤ 650 Ω
Entity ParametersFM control drawing no. 116-0200
MechanicalHousing Type C3 (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)
Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)
Class I, Div 1, Group A-G:Class I, Zone 0, II C
126
Technical Data
Connection Diagram
Model Number
2002 IS CatalogLogic
Contr
ols
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
Power Supply Terminals 23, 24 or Power RailNominal voltage 20-30 VDCPower consumption 2.5 W
Input (intrinsically safe) Terminals 1+, 3-; 4+,6-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs
Outputs (not intrinsically safe)Relay output 1 (SPDT) Terminals 10, 11 and 12Relay output 2 (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ø ≥ 0.7; 40 VDC / 2AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 ms
Output 3, 4 (passive transistor) Terminals 19+ and 20- and 21+Nominal current 50 mA, short circuit-protectedLogic 1 voltage drop < 2.5 VLogic 0 output swiched off (leakage ≤ 10 µA)
MechanicalHousing Type C3 (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)
Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)
Class I, Div 1, Group A-G:Class I, Zone 0, II C
KFD2-UFT-Ex2.D
Direction /SynchronizationMonitor
The KFD2-UFT-Ex2.D can function as a rotationdirection indicator or synchronization monitor.Programming is simple with the PACTwareconfiguration software or with the on-boarddisplay and buttons. PACTware is available atwww.am.pepperl-fuchs.com.
The input and output circuits are galvanicallyisolated allowing connection to intrinsically safefield devices in hazardous areas.
Lead breakage and short circuits in the sensorare indicated by a red LED and through thecollective error output via Power Rail.
Dual input
0.001 Hz - 5 kHz input frequency
Two relay outputs
Two isolated electronic outputs
PC or push-buttonprogrammable
Programmable output functions
Lead breakage (LB) and shortcircuit (SC) monitoring
Start-up override
127
Technical Data
Connection Diagram
Model Number
2002 IS CatalogLogic
Contro
ls
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Class I, Div 1, Group A-G:Class I, Zone 0, II C
KFU8-UFT-Ex2.D
Direction /SynchronizationMonitor
The KFU8-UFT-Ex2.D can function as arotation direction indicator or synchronizationmonitor. Programming is simple with thePACTware configuration software or with theon-board display and buttons. PACTware isavailable at www.am.pepperl-fuchs.com.
The input and output circuits are galvanicallyisolated allowing connection to intrinsicallysafe field devices in hazardous areas.
Lead breakage and short circuits in thesensor are indicated by a red LED.
Dual input
24 VDC, 120 VAC or 240 VACsupply
0.001 Hz - 5 kHz input frequency
Two relay outputs
Two isolated electronic outputs
PC or push-buttonprogrammable
Programmable output functions
Lead breakage (LB) and shortcircuit (SC) monitoring
Start-up override
Supply 24 VDC 120 VAC 240 VAC
KFU8-UFT-Ex2.D
Input 2
Input 1
LB/SCLB/SC LB
R2
R1R1
R2
R1R1
2324
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
Power Supply Terminals 23, 24Nominal voltage 20-90 VDC ; 48-253 VACPower consumption 2.5 W; 4 VA
Input (intrinsically safe) Terminals 1+, 3-; 4+,6-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs
Outputs (not intrinsically safe)Relay output 1 (SPDT) Terminals 10, 11 and 12Relay output 2 (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ø ≥ 0.7; 40 VDC / 2AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 ms
Output 3, 4 (passive transistor) Terminals 19+ and 20- and 21+Nominal current 50 mA, short circuit-protectedLogic 1 voltage drop < 2.5 VLogic 0 output switched off (leakage ≤ 10 µA)
MechanicalHousing Type C3 (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)
Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)
128
Technical Data
Connection Diagram
Model Number
2002 IS CatalogLogic
Contr
ols
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Timer With Display
This highly configurable timer is commonlyused in applications requiring an on-delay, off-delay, one-shot or pulse lengthening.Programming is easy: simply use the push-buttons to select the options in the on-linemenu. This unit not only provides isolationbetween the input and output signal, it is anintrinsic safety barrier so equipment insidehazardous locations can be connected.
Lead breakage and short circuits in the sensorare indicated by a red LED and through thecollective error output via Power Rail.
KFD2-DU-Ex1.D
24 VDC supply
Input frequency up to 100 Hz
Relay output and transistoroutput
Push-button programmable
Lead breakage (LB) and shortcircuit (SC) monitoring
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
111012
1314
2324
Output 1
Output 2
Reset
Supply 24 VDC
KFD2-DU-Ex1.D
Collective Error Messaging
19
20
1
3
Input 1
LB/SCLB/SC LB
R2
R1R1
Power Supply Terminals 23, 24 or Power RailNominal voltage 20-30 VDCPower consumption 1.8 W
Input (intrinsically safe) Terminals 1+, 3-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs
Outputs (not intrinsically safe)Relay output 1 (SPDT) Terminals 10, 11, 12Contact load 250 VAC / 2 A / cos ø = 0.7; 40 VDC / 2 AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 ms.Time delay 0-3600 s
Output 2 (passive transistor) Terminals 19+, 20-Nominal current 50 mA, short-circuit protected
Transfer CharacteristicsFrequency range 0.001-100 Hz
MechanicalHousing Type C3 (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)
Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)
Class I, Div 1, Group A-G:Class I, Zone 0, II C
129
Technical Data
Connection Diagram
Model Number
2002 IS CatalogLogic
Contro
ls
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Class I, Div 1, Group A-G:Class I, Zone 0, II C
Timer With Display
This highly configurable timer is commonlyused in applications requiring an on-delay,off-delay, one-shot or pulse lengthening.Programming is easy: simply use the push-buttons to select the options in the on-linemenu. This unit not only provides isolationbetween the input and output signal, it isintrinsically safe so equipment insidehazardous locations can be connected.
Lead breakage and short circuits in thesensor are indicated by a red LED.
KFA5-DU-Ex1.D
120 VAC supply
Input frequency up to 100 Hz
Relay output and transistoroutput
Push-button programmable
Lead breakage (LB) and shortcircuit (SC) monitoring
Power Supply Terminals 23, 24Nominal voltage 120 VACPower consumption 2 VA
Inputs (intrinsically safe) Terminals 1+, 3-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs
Outputs (not intrinsically safe)Relay Output 1 (SPDT) Terminals 10, 11, 12Contact load 250 VAC / 2 A / cos ø = 0.7; 40 VDC / 2 AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 msTime delay 0-3600 s
Output 2 (passive transistor) Terminals 19+, 20-Nominal current 50 mA, short-circuit protected
Transfer CharacteristicsFrequency range 0.001-100 Hz
MechanicalHousing Type C3 (See page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)
Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
111012
1314
2324
Output 1
Output 2
Reset
Supply 120 VAC
KFA5-DU-Ex1.D
19
20
1
3
Input 1
LB/SCLB/SC LB
R2
R1R1
Class I, Div 1, Group A-G:Class I, Zone 0, II C
130
Technical Data
Connection Diagram
Model Number
2002 IS CatalogLogic
Contr
ols
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Timer With Display
This highly configurable timer is commonlyused in applications requiring an on-delay,off-delay, one-shot or pulse lengthening.Programming is easy: simply use the push-buttons to select the options in the on-linemenu. This unit not only provides isolationbetween the input and output signal, it is anintrinsic safety barrier, so equipment insidehazardous locations can be connected.
Lead breakage and short circuits in thesensor are indicated by a red LED.
KFA6-DU-Ex1.D
240 VAC supply
Input frequency up to 100 Hz
Relay output and transistoroutput
Push-button programmable
Lead breakage (LB) and shortcircuit (SC) monitoring
Power Supply Terminals 23, 24Nominal voltage 240 VACPower consumption 2 VA
Input (intrinsically safe) Terminals 1+,3-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 50 µs / ≥ 50 µs
Outputs (not intrinsically safe)Relay output 1 (SPDT) Terminals 10, 11, 12Contact load 250 VAC / 2 A / cos ø = 0.7; 40 VDC / 2 A
Mechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 ms.Time delay 0-3600 s
Output 2 (passive transistor) Terminals 19+, 20-Nominal current 50 mA, short-circuit protected
Transfer CharacteristicsFrequency range 0.001-100 Hz
MechanicalHousing Type C3 (See page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)
Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
111012
1314
2324
Output 1
Output 2
Reset
Supply 240 VAC
KFA6-DU-Ex1.D
19
20
1
3
Input 1
LB/SCLB/SC LB
R2
R1R1
Class I, Div 1, Group A-G:Class I, Zone 0, II C
131
Technical Data
Connection Diagram
Model Number
2002 IS CatalogLogic
Contro
ls
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
KFD2-CRG-Ex1.D
TransmitterPower Supply
The KFD2-CRG-Ex1.D is suited for a variety ofmeasuring tasks. 2- and 3-wire transmittersas well as active power supplies with 0/4-20mA signals can be connected.
Two relays and an active 0/4-20 mA currentoutput are available.
The current output is freely scalable. The inputhas a lead breakage and short circuitmonitoring function.
The device is operated by means of PCsoftware (PACTware) or via the push-buttonson the front panel.
Lead breakage and short circuits in the sensorare indicated by a red LED and through thecollective error output via Power Rail.
24 VDC supply
Analog input 0/4 -20 mA
Analog output 0/4-20 mA
Two relay outputs
Each output individuallyprogrammable as high or lowalarm or error message output
Push-button or PCprogrammable
Lead breakage (LB) and shortcircuit (SC) monitoring
8
7
Output 1
Output 2
Supply 24 VDC
KFD2-CRG-Ex1.D
11
1012
Collective Error Messaging
17
16
18
23
24
0/4-20mA Output
I
(+) 1
3 3 3
2
(+) 1
2
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
Class I, Div 1, Group A-G:Class I, Zone 0, II C
Power Supply Terminals 23+, 24-Nominal voltage 20-30 VDCPower consumption 2.5 W
Input (intrinsically safe) Terminals 1, 2, ,3Input signal 0/4-20 mAAvailable voltage > 15 V at 20 mAInput resistance 45 Ω
Outputs (not intrinsically safe)Relay output I (SPDT) Terminals 10, 11 and 12Relay output II (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ≥ 0.7; 40 VDC / 2AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 ms
Output III Terminals 8+, 7-Current range 0/4-20 mALoad ≤ 650 ΩFault signal downscale I ≤ 3.6mA, upscale I ≥ 21mA
Transfer CharacteristicsMeasuring time ≥ 100 msTemperature current measurement: 0.003% / ºC
current output: 0.005% / ºCcurrent measurement & output:0.006% / ºC
MechanicalHousing Type C3 (See page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)
Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)
132
Technical Data
Connection Diagram
Model Number
2002 IS CatalogLogic
Contr
ols
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Timer With Display
KFU8-CRG-Ex1.D
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
8
7
Output 1
Output 2
KFU8-CRG-Ex1.D
11
1012
17
16
18
23
24
0/4-20mA Output
I
(+) 1
3 3 3
2
(+) 1
2
Supply 24 VDC 120 VAC 240 VAC
Class I, Div 1, Group A-G:Class I, Zone 0, II C
The KFD2-CRG-Ex1.D is suited for a varietyof measuring tasks. 2- and 3-wiretransmitters as well as active power supplieswith 0/4-20 mA signals can be connected.
Two relays and an active 0/4-20 mA currentoutput are available.
The current output is freely scalable. Theinput has a lead breakage and short circuitmonitoring function.
The device is operated by means of PCsoftware (PACTware) or via the push-buttonson the front panel.
Lead breakage and short circuits in thesensor are indicated by a red LED.
24 VDC, 120 or 240 VAC supply
Analog input 0/4 -20 mA
Analog output 0/4-20 mA
Two relay outputs
Each output individuallyprogrammable as high or lowalarm or error message output
Push-button or PCprogrammable
Lead breakage (LB) and shortcircuit (SC) monitoring
Power Supply Terminals 23+, 24-Nominal voltage 20-90 VDC or 48-253 VACPower consumption 2.2 W / 4 VA
Input (intrinsically safe) Terminals 1, 2, ,3Input signal 0/4-20 mAAvailable voltage > 15 V at 20 mAInput resistance 45 Ω
Outputs (not intrinsically safe)Relay output I (SPDT) Terminals 10, 11 and 12Relay output II (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ≥ 0.7; 40 VDC / 2AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 ms
Output III Terminals 8+, 7-Current range 0/4-20 mALoad ≤ 650 ΩFault signal downscale I ≤ 3.6mA, upscale I ≥ 21mA
Transfer CharacteristicsMeasuring time ≥ 100 msTemperature current measurement: 0.003% / ºC
current output: 0.005% / ºCcurrent measurement & output:0.006% / ºC
MechanicalHousing Type C3 (See page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)
Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)
133
Technical Data
Connection Diagram
Model Number
2001 IS CatalogLogic
Contro
ls
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Latching RelaySwitch Isolator
This isolator is a galvanically isolatedintrinsic safety barrier with a latching relayfor level control, pump up/pump down, orother switch/logic applications. The leadbreakage feature of this barrier requires aconnection of a 10 kΩ resistor in parallelwith the contact when using a mechanicalswitch. NAMUR proximity sensors,however, are designed with the LBfunction and make external resistorsunnecessary. If an LB fault occurs, thesignal output relay reverts to the de-energized state. The output de-energizesif the unit loses power. When power isrestored, the output relay returns to thesame state it held before the interruption.
KFA5-SR2-Ex2.W.IR
Dual-channel
120 VAC supply
Lead breakage (LB) and shortcircuit (SC) monitoring
Power Supply Terminals 14, 15Nominal voltage 120 VACPower consumption 1.5 W
Inputs (intrinsically safe) Terminals 1+, 3-; 4+, 6-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 10 ms / ≥ 10 ms
Output (Not intrinsically safe)Relay Output (2 SPDT) Terminals 7, 8, 9 ; 10, 11, 12Contact load 250 VAC / 4 A / cos ø > 0.7; 40 VDC/4AMechanical life ≥107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 ms
Transfer CharacteristicsSwitching frequency ≤ 10 Hz
MechanicalHousing Type C (See page 387)Dimensions (mm) 110 x 20 x 70Weight 150 g (5.3 oz.)
Ambient Temperature -20ºC to +60ºC (0ºF to +140ºF)
KFA5-SR2-Ex2.W.IR
8
7
9
14
Output 1
Output 2
Supply 120 VAC15
11
10
12
Input 2
Input 1
LB/SCLB/SC LB
R2
R1 R1
R2
R1 R1
Class I, Div 1, Group A-G:Class I, Zone 0, II C
134
Technical Data
Connection Diagram
Model Number
2001 IS CatalogLogic
Contr
ols
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Input 2
Input 1
LB/SCLB/SC LB
R2
R1 R1
R2
R1 R1
KFA6-SR2-Ex2.W.IR
Supply 240 VAC
Latching RelaySwitch Isolator
This isolator is a galvanically isolated,intrinsic safety barrier with a latching relayfor level control, pump up/pump down, orother switch/logic applications. The leadbreakage feature of this barrier requires aconnection of a 10 kΩ resistor in parallelwith the contact when using a mechanicalswitch. NAMUR proximity sensors;however, are designed with the LBfunction and make external resistorsunnecessary. If an LB fault occurs, thesignal output relay reverts to the de-energizedstate. The output de-energizes if the unitloses power. When power is restored, theoutput relay returns to the same state itheld before the interruption.
KFA6-SR2-Ex2.W.IR
Dual-channel
240 VAC supply
Lead breakage (LB) and shortcircuit (SC) monitoring
Power Supply Terminals 14, 15Nominal voltage 240 VACPower consumption ≤ 1.5 W
Inputs (intrinsically safe) Terminals 1+, 3-; 4+, 6-Nominal data per NAMUR, ≈ 8VDC, ≈ 8mAInput pulse length / interval ≥ 10 ms / ≥ 10 ms
Output (Not intrinsically safe)Relay output (2 SPDT) Terminals 7, 8, 9; 10, 11, 12Contact load 250 VAC / 4 A / cos ø ≥ 0.7; 40 VDC 4AMechanical life ≥107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 ms
Transfer CharacteristicsSwitching frequency ≤ 10 Hz
MechanicalHousing Type C (See page 387)Dimensions (mm) 110 x 20 x 70Weight 150 g (5.3 oz.)
Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)
Class I, Div 1, Group A-G:Class I, Zone 0, II C
135
Technical Data
Connection Diagram
Model Number
2001 IS CatalogLogic
Contro
ls
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
The KFD2-GU-Ex1 accepts a varietyof inputs and provides a relay tripwhenever it reaches a user-programmedset point. This unit is configuredwith a K-ADP1 adapter, PACTwaresoftware and a PC. Terminal K-CJC isavailable for thermocouples when internalcompensation is desired. K-ADP1,PACTware and K-CJC are sold separately.
KFD2-GU-Ex1
24 VDC supply
T/C, RTD, current and voltageinputs
2 programmable trip points
Lead breakage monitoring
8
79
14
31
1
Output 1
Output 2
Supply 24 VDC
KFD2-GU-Ex1
3
Hazardous Area
2
5
4
6
15
11
10122 wire
Input for RTDs 3 wire
wire2 4
312
2
2
5
6
Input for voltage supply
Input for voltage supply
Cold junction compensation on
Input for thermocouples
0V-20 mA 4V-20 mA
0V-10V 2V-10V
Programming JackGND
TxDRxD
Power Supply Terminals 14+ , 15- or Power RailNominal voltage 20-30 VDCPower consumption ≈ 1.5 W
Inputs (intrinsically safe)Thermocouple (terminals 1,2) B,E,J,K,L,N,R,S or TRTD (terminals 1, 2, 3, 4) 2-, 3+, or 4-wide (N;100 or P+100)Voltage (terminals 2-, 6+) 0/2-10VDC wireCurrent (terminals 2-, 5+) 0/4-20mA
Outputs (not intrinsically safe)Relay Output 1 (SPDT) Terminals 7, 8 and 9Relay Output 2 (SPDT) Terminals 10, 11 and 12Contact load 250 VAC / 2 A / cos ø ≥ 0.6
Transfer characteristicsCalibrated accuracy PT100: 0.01% + 0.2ºC (4-wire)
T/C: 0.05% + 1.2ºCVoltage (0-10 V): 0.02% + 500µVCurrent (0-20 mA): 0.02% + 1 µA
Temperature Drift PT100: (0.0015% + 0.01ºC) / ºCT/C: (0.004% + 0.01ºC) / ºCVoltage: 0.007% / ºCCurrent: 0.0055% / ºC
MechanicalHousing Type C (See page 387)Dimensions (mm) 115 x 20 x 118Weight 150 g (5.3 oz.)
Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
Class I, Div 1, Group A-G,Zone 0, IIC
I.S. AnalogLimit Alarm LogicControls
2002 IS Catalog
136 Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
2002 IS Catalog
137Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com