Upload
minh-vien
View
215
Download
0
Embed Size (px)
Citation preview
7/28/2019 2-Standard Voltage Transformer
1/4
HCMC PC SPECIFICATION
STANDARD VOLTAGE INSTRUMENT TRANSFORMER
I. SCOPE :
This specification covers the supply of standard voltageinstrument transformer.
II. STANDARD OF MANUFACTURE AND TEST :The equipment shall conform to the latest edition of theappropriate IEC specification or ASTM standard.
III. DESCRIPTION:
1. Function of equipment :- The standard voltage instrument transformer used to be as
reference transformer for voltage transformer measurement.- Test method : conform to the specification of IEC standard
2. Technical specification :- Insulation : Dry insulation or SF6 insulation.- Primary voltage : 8.4 - 12 -14.4 - 24KV- Secondary Voltage : 120V
-Voltage error : 0.005%
- Phase angel : 0.5 min
- Load : Max.15VA/ cos = 1- Test voltage : 60KV
IV. REQUIREMENT OF TECHNICAL EQUIPMENT :- Technical description, data sheet, catalogues and other
material submitted with the quotation must enable thepurchaser to thoroughly evaluate the proposals as to it
compliance with the inquiry specification.- Minimum requirements : Detail summary of deviations to the inquiry specification Complete inquiry data sheet expressed at section V Catalog containing outline dimension, technical data List of main equipment and completed accessories which
can perform all function described in section III have thefollowing requirements :. Individual cost of main equipment and each accessory
. Total cost of main equipment and completed accessory. Manufactures code of main equipment and each accessory
/var/www/apps/conversion/tmp/scratch_5/138239121.doc 1/4
7/28/2019 2-Standard Voltage Transformer
2/4
HCMC PC SPECIFICATION
STANDARD VOLTAGE INSTRUMENT TRANSFORMER
Connection diagram
Certificate of quality management
V. REQUIREMENT OF DOCUMENT INCASE OF BIDWINNING :
1. Documents required to be provide for commission :In order to ensure the quality of supplied goods, in case of bidwinning, the Tenderer shall supply the following documents forthe Purchaser :
-Manufacturers Certificate of Quality.
- Certificate of Origin issued by Chamber of Commerce of themanufacturing country.
- Certificate of calibration of equipment approved by anindependent lawful organization.
2. Documents required to be provide in accompany withsupplied products :
The Supplier shall enclose the following documents for supplied
products :- 01 catalog.- 01 instruction manual of installation, operation andmaintenance.
VI. REQUIREMENT OF INSTALLATION AND INSTRUCTIONFOR USE :
The Supplier shall ensure to supply the following service :-
Installation the equipment completely.- Instruction to Purchasers staff how to use this equipment on
site.- Trial run this equipment.
VII. DATA SHEET:
/var/www/apps/conversion/tmp/scratch_5/138239121.doc 2/4
7/28/2019 2-Standard Voltage Transformer
3/4
HCMC PC SPECIFICATION
STANDARD VOLTAGE INSTRUMENT TRANSFORMER
N DESCRIPTION REQUIREMENTS
QUOTED
1. Manufacturer2. Country of origin3. Manufacturer s code4. Standard of manufacture and
test5. Standard of quality management6. Organization which approved
certificate of qualitymanagement
7. In case of bid winning, theTenderer shall supply thefollowing documents for thePurchaser :- Manufacturers Certificate ofQuality.- Certificate of Origin issued by
Chamber of Commerce of themanufacturing country.- Certificate of calibration ofequipment approved by anindependent lawful organization.
YesYes
Yes
8. List of main equipment andcompleted accessories met allrequirements of section IV issupplied in tender proposal.
Yes
9. Quoted main equipment andcompleted accessories describedin above list can perform allfunction described in section IIIwithout addition of othernecessary materials.
Yes
10. The Supplier shall ensure tosupply the following service :- Installation the equipment
completely.- Instruction to Purchasers staff
Yes
Yes
/var/www/apps/conversion/tmp/scratch_5/138239121.doc 3/4
7/28/2019 2-Standard Voltage Transformer
4/4
HCMC PC SPECIFICATION
STANDARD VOLTAGE INSTRUMENT TRANSFORMER
how to use this equipment on
site.- Trial run this equipment.
Yes
11. Function of equipment It use to bestandard
transformer forvoltage
transformermeasurement
12. Methods for determination Conform to IEC
standard13. Material of insulation Dry or SF614. Primary voltage 8.4-12-14.4-
24KV15. Secondary voltage 120V16. Voltage Error 0.005%
17. Phase angel 0.5 min
18. Load Max. 15VA/
cos = 1
19. Power frequency withstandvoltage (dry for 01 minute)
60 KV
20. - Dimensions :+ Width+ Height+ Depth
- Weight
The tendererhas to quote thedimensions andweight ofstandard voltagetransformer thatcan be
fabricated.
/var/www/apps/conversion/tmp/scratch_5/138239121.doc 4/4