IM 05P01D81-11EN page 1/6
Contents1. Safety Precautions2. ModelandSuffixCodes3. How to Install4. HardwareSpecifications5. HowtoConnectWires6. TerminalWiringDiagrams7. Setup Procedure8. Operations9. Troubleshooting
IntroductionThankyouforpurchasingtheUT35A/MDL,UT32A/MDLController.Thisoperationguidedescribestheinstalling,wirings,setupflow,andtroubleshootingoftheUT35A/MDLandUT32A/MDL.Theguideshouldbeprovidedtotheenduserof this product.Besure to read thisoperationguidebeforeusing theproduct inorder toensurecorrectoperation.Fordetailsofeachfunction,refertotheelectronicmanual.Beforeusingtheproduct,refertothetableofModelandSuffixCodestomakesurethatthedeliveredproduct isconsistentwith themodelandsuffixcodesyouordered.Alsomakesurethatthefollowingitemsareincludedinthepackage.
•Controller(themodelyouordered) .........................................................x1•UnitLabel(L4502VZ) ..............................................................................x1•TagLabel(L4502VE) ..............................................................................x1(Onlywhenordered.)•OperationGuide(thisdocument) ............................................................x3(A3size)(InstallationandWiring,InitialSettings,Operations,andParameters)
lTargetReadersThisguideisintendedforthefollowingpersonnel;• Engineersresponsibleforinstallation,wiring,andmaintenanceoftheequipment.• Personnelresponsiblefornormaldailyoperationoftheequipment.
1. Safety PrecautionsThefollowingsymbol isusedonthe instrument. It indicatesthepossibilityof injury totheuserordamagetotheinstrument,andsignifiesthattheusermustrefertotheuser’smanualforspecialinstructions.Thesamesymbolisusedintheuser’smanualonpagesthattheuserneedstoreferto,togetherwiththeterm“WARNING”or“CAUTION.”
WARNING
Calls attention to actions or conditions that could cause serious or fatal injury to the user, and indicates precautions that should be taken to prevent such occurrences.
CAUTION
Calls attention to actions or conditions that could cause injury to the user or damage to the instrument or property and indicates pre-cautions that should be taken to prevent such occurrences.
AC
AC/DC
Theequipmentwhollyprotectedbydoubleinsulationorreinforcedinsulation.
Functionalgroundingterminals (Donotusethisterminalasaprotectivegroundingterminal).
NoteIdentifiesimportantinformationrequiredtooperatetheinstrument.
Warning and Disclaimer(1)YOKOGAWAmakesnowarrantiesregardingtheproductexceptthosestatedin
theWARRANTYthatisprovidedseparately.
(2)Theproductisprovidedonan"asis"basis.YOKOGAWAassumesnoliabilitytoanypersonorentity forany lossordamage,director indirect,arisingfromtheuse of the product or from any unpredictable defect of the product.
Safety,Protection,andModificationoftheProduct(1) Inorder toprotect thesystemcontrolledbythisproductandtheproduct itself,
andtoensuresafeoperation,observethesafetyprecautionsdescribed in theuser’smanual.Useof the instrument inamannernotprescribedhereinmaycompromise the product's functions and the protection features inherent in the device.Weassumenoliabilityforsafety,orresponsibilityfortheproduct'squality,performanceorfunctionalityshouldusersfailtoobservetheseinstructionswhenoperatingtheproduct.
(2) Installationof protectionand/or safety circuitswith respect toa lightningprotector;protectiveequipmentforthesystemcontrolledbytheproductandtheproductitself;foolprooforfail-safedesignofaprocessorlineusingthesystemcontrolledbytheproductortheproductitself;and/orthedesignandinstallationofotherprotectiveandsafetycircuitsaretobeappropriatelyimplementedasthecustomer deems necessary.
(3)BesuretousethesparepartsapprovedbyYOKOGAWAwhenreplacingpartsor consumables.
(4)Thisproduct isnotdesignedormanufacturedtobeusedincriticalapplicationsthatdirectlyaffector threatenhuman lives.Suchapplications includenuclearpower equipment, devices using radioactivity, railway facilities, aviationequipment,airnavigation facilities,aviation facilities,andmedicalequipment.If soused, it is theuser’s responsibility to include in thesystemadditionalequipmentanddevicesthatensurepersonnelsafety.
(5)Modificationoftheproductisstrictlyprohibited.(6)Thisproductisintendedtobehandledbyskilled/trainedpersonnelforelectricdevices.(7)ThisproductisULRecognizedComponent.InordertocomplywithULstandards,
end-productsarenecessarytobedesignedbythosewhohaveknowledgeoftherequirements.
WARNING
lPower Supply Ensure that the instrument’s supply voltage matches the voltage
of the power supply before turning ON the power.l Do Not Use in an Explosive Atmosphere Do not operate the instrument in locations with combustible
or explosive gases or steam. Operation in such environments constitutes an extreme safety hazard. Use of the instrument in environments with high concentrations of corrosive gas (H2S, SOX, etc.) for extended periods of time may cause a failure.
l Do Not Remove Internal Unit The internal unit should not be removed by anyone other than
YOKOGAWA's service personnel. There are dangerous high voltage parts inside. Additionally, do not replace the fuse by yourself.
l Damage to the Protective Construction Operation of the instrument in a manner not specified in the
user’s manual may damage its protective construction.
CAUTION
This instrument is an EMC class A product. In a domestic environ-ment this product may cause radio interference in which case the user needs to take adequate measures.
2. ModelandSuffixCodes
UT35A/MDLModel Suffixcode
Optional suffixcode
Description
UT35A /MDL(Required)
DigitalIndicatingController(Powersupply:100-240VAC)(providedwithretransmissionoutputor15VDClooppowersupply,2DIs,and3DOs)
Type1:Basic control
-0 Standard type
-2 Heating/coolingtype
Type2:Functions
0 None2 5additionalDIs,5additionalDOs
Type3:Opennetworks
0 None
1 RS-485communication(Max.38.4kbps,2-wire/4-wire)
2 Ethernetcommunication(withserialgatewayfunction)
3 CC-Linkcommunication(withModbusmasterfunction)
4 PROFIBUS-DPcommunication(withModbusmasterfunction)
5 DeviceNetcommunication(withModbusmasterfunction)Fixedcode -1 Temperatureunit:degC°FCasecolor 1 Black(Lightcharcoalgray)Fixedcode -00 Always"-00"
Optionalsuffixcodes
/MDL(Required)
MountonDINrail(withoutthedisplaypartsandkeys)(*1)
/LP 24VDClooppowersupply(*1)/DC Powersupply24VAC/DC/CT Coating(*2)/CV Terminalcover
*1: When/MDLoptionand/LPoptioniscombined,only“0”canbespecifiedforType2code.*2: Whenthe/CToptionisspecified,theUT35Adoesnotconformtothesafetystandards(UL
andCSA)andCEmarking(Productswith/CToptionarenotintendedforEEA-market).
UT32A/MDLModel Suffixcode
Optional suffixcode
Description
UT32A /MDL(Required)
DigitalIndicatingController(Powersupply:100-240VAC)(providedwithretransmissionoutputor15VDClooppowersupply,2DIs,and3DOs)
Type1:Basic control
-0 Standard type
-2 Heating/coolingtype
Type2:Functions
0 None1 RS-485communication(Max.38.4kbps,2-wire/4-wire)(*1)
Type3:Open networks
0 None3 CC-Linkcommunication(withModbusmasterfunction)
Fixedcode -1 Temperatureunit:degC°FCasecolor 1 Black(Lightcharcoalgray)Fixedcode -00 Always"-00"
Optionalsuffixcodes
/MDL(Required)
MountonDINrail(withoutthedisplaypartsandkeys) (*2)(*3)
/LP 24VDClooppowersupply(*3)/HA Heaterbreakalarm(*4)/DC Powersupply24VAC/DC/CT Coating(*5)/CV Terminalcover
*1: When/LPoptionisspecified,theRS-485communicationofthetype2code“1”is2-wiresystem.*2: The/MDLoptionisspecified,themodelandsuffixcodesarefollows: UT32A-010-11-00/x/MDL UT32A-003-11-00/x/MDL UT32A-210-11-00/x/MDL*3: When/MDLoptionand/LPoptioniscombined,“3”cannotbespecifiedforType3code.*4: The/HAoptioncanbespecifiedonlyinthecombinationofType2code“1”andType3code“0.”*5: Whenthe/CToptionisspecified,theUT32Adoesnotconformtothesafetystandards(UL
andCSA)andCEmarking(Productswith/CToptionarenotintendedforEEA-market).
Accessories (sold separately)Thefollowingisanaccessorysoldseparately.• LL50AParameterSettingSoftware
Model Suffixcode DescriptionLL50A -00 ParameterSettingSoftware
• ExternalPrecisionResistorModel Suffixcode Description
X010 SeetheGeneralSpecifications(*) ResistanceModule
*:Necessarytoinputthecurrentsignaltothevoltageinputterminal.• TerminalCover ForUT35A:ModelUTAP001;ForUT32A:ModelUTAP002• User’sManual(A4size) Note:User’sManualcanbedownloadedfromawebsite.• Brackets Partnumber:L4502TP(2pcsforupperandlowersides)
3. How to Install
Installation LocationThe instrument shouldbe installed in indoor locationsmeeting the followingconditions:• Instrumented panel This instrument isdesignedtobemounted inan instrumentedpanel.Mount theinstrumentinalocationwhereitsterminalswillnotinadvertentlybetouched. Be sure to mount the instrument in a panel with a door.• Well ventilated locations Mounttheinstrumentinwellventilatedlocationstopreventtheinstrument’sinter-naltemperaturefromrising.
However,makesurethattheterminalportionsarenotexposedtowind.Exposureto wind may cause the temperature sensor accuracy to deteriorate. To mount mul-tiple indicatingcontrollers,seetheexternaldimensionswhichfollow. Ifmountingother instrumentsadjacent to the instrument,complywith theseexternaldimen-sionstoprovidesufficientclearancebetweentheinstruments.
• Locations with little mechanical vibration Installtheinstrumentinalocationsubjecttolittlemechanicalvibration.• Horizontal location Mounttheinstrumenthorizontallyandensurethatitislevel,withnoinclinationtotherightorleft.
NoteIf the instrument ismovedfroma locationwith lowtemperatureand lowhumiditytoaplacewithhightemperatureandhighhumidity,or if thetemperaturechangesrapidly,condensationwill result.Moreover, in thecaseof thermocouple inputs,measurementerrorswillresult.Toavoidsuchasituation,leavetheinstrumentinthenewenvironmentunderambientconditionsformorethan1hourpriortousingit.
Donotmounttheinstrumentinthefollowinglocations:• Outdoors• Locations subject to direct sunlight or close to a heater Install the instrument in a location with stable temperatures that remain close to an averagetemperatureof23°C.Donotmountitinlocationssubjecttodirectsunlightorclosetoaheater.Doingsoadverselyaffectstheinstrument.
• Locations with substantial amounts of oily fumes, steam, moisture, dust, or corrosive gases
Thepresenceofoily fumes,steam,moisture,dust,orcorrosivegasesadverselyaffectstheinstrument.Donotmounttheinstrumentinlocationssubjecttoanyofthese substances.
• Areasnearelectromagneticfieldgeneratingsources Donotplacemagnetsortoolsthatgeneratemagnetismneartheinstrument.Iftheinstrument isusedin locationsclosetoastrongelectromagneticfieldgeneratingsource,themagneticfieldmaycausemeasurementerrors.
• Areasclosetoflammablearticles Absolutelydonotplacetheinstrumentdirectlyonflam-mablesurfaces. Ifsuchacircumstance isunavoidableandtheinstrumentmustbeplacedclosetoaflammableitem,provideashieldforitmadeof1.43mmthickplatedsteel or 1.6 mm thick unplated steel with a space of at least150mmbetweenitandtheinstrumentonthetop,bottom,andsides.
• Areas subject to being splashed with water
WARNING
Be sure to turn OFF the power supply to the controller before in-stalling it on the panel to avoid an electric shock.
Mounting on a DIN RailInserttheDINrailintothetopareaofDINrailgroove(attwolocations)ontherearpanel,andsecureinplacewiththebottomslidelock.
DIN rail
DIN rail
Slide lockUT35A/MDL: 2, UT32A/MDL: 1
Fit into here
Push
CAUTION
Make sure that foreign materials do not enter the inside of the in-strument through the case’s slit holes.
150 mm150 mm
150 mm
150 mm
OperationGuideIM 05P01D81-11EN
UT35A/MDL, UT32A/MDLControllers (Mount on DIN Rail)Operation Guide
This operation guide describes installation, wiring, and other tasks required to make the controller ready for operation.
1st Edition : Apr. 2015
For details of the each function, refer to the electronic manual. User's manuals can be downloaded or viewed at the following URL.
Functional
Enhancement
http://www.yokogawa.com/ns/ut/im/
www.yokogawa.com/ns
YOKOGAWA ELECTRIC CORPORATIONNetwork Solutions Business Division
2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPANYOKOGAWA CORPORATION OF AMERICA
Head office and for product sales2 Dart Road, Newnan, Georgia 30265, USA
YOKOGAWA EUROPE B.V.Headquarters
Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS
All Rights Reserved, Copyright © 2015 Yokogawa Electric Corporation
IM 05P01D81-11EN page 2/6
Removing from the DIN RailInsertaflat-bladescrewdriver(guideline:100mmshaft length,6mmbladewidth,0.8mmbladethickness)intothebottomslidelockholeandpulldowntoreleasetheslide lock.OntheUT55A/MDL, thereare twoslide locks.Releasetheotherslidelockafteryoureleasethefirstslide lock.Whenbothslide locksareunlocked, theinstrumentcanberemovedfromtheDINrail.
DIN rail
Slide lockUT35A/MDL: 2, UT32A/MDL: 1
Pull
Push up
DIN rail
4. HardwareSpecifications
WARNING
This instrument is for Measurement Category No.1.Do not use it for measurements in locations falling under Measure-ment Categories No.2, No.3, and No.4.
Internal Wiring
Outlet
Entrance IVCable
III TO( I )
II
Category IEC/EN/CSA・UL 61010-1: 2001 EN 61010-2-030 Remarks
No.1 Measurement CategoryI O(Other) For measurements performed on circuits not direct-
lyconnectedtoMAINS.
No.2 Measurement CategoryII
Measurement CategoryII
For measurements performed on circuits directly connectedtothelow-voltageinstallation.
No.3 Measurement CategoryIII
Measurement CategoryIII
Formeasurementsperformedinthebuildinginstal-lation.
No.4 Measurement CategoryIV
Measurement CategoryIV
For measurements performed at the source of the low-voltageinstallation.
InputSpecifications
UniversalInput(Equippedasstandard)• Numberofinputs:1• Inputtype,instrumentrange,andmeasurementaccuracy:Seethetablebelow,
Input Type Instrument Range
AccuracyºC ºF
Thermo-couple
K-270.0to1370.0ºC -450.0to2500.0ºF ±0.1%ofinstrumentrange±1digitfor
0°Cormore ±0.2%ofinstrumentrange±1digitforlessthan0°C ±2%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleK±1%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleT
-270.0to1000.0ºC -450.0to2300.0ºF-200.0to500.0ºC -200.0to1000.0ºF
J -200.0to1200.0ºC -300.0to2300.0ºF
T-270.0to400.0ºC -450.0to750.0ºF
0.0to400.0ºC -200.0to750.0ºF
B 0.0to1800.0ºC 32to3300ºF
±0.15%ofinstrumentrange±1digitfor400°Cormore ±5%ofinstrumentrange±1digitforlessthan400°C
S 0.0to1700.0ºC 32to3100ºF±0.15%ofinstrumentrange±1digit
R 0.0to1700.0ºC 32to3100ºF
N -200.0to1300.0ºC -300.0to2400.0ºF±0.1%ofinstrumentrange±1digit±0.25%ofinstrumentrange±1digitforlessthan0°C
E -270.0to1000.0ºC -450.0to1800.0ºF ±0.1%ofinstrumentrange±1digitfor0°Cormore ±0.2%ofinstrumentrange±1digitforlessthan0°C ±1.5%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleE.
L -200.0to900.0ºC -300.0to1600.0ºF
U-200.0to400.0ºC -300.0to750.0ºF
0.0to400.0ºC -200.0to1000.0ºF
W 0.0to2300.0ºC 32to4200ºF ±0.2%ofinstrumentrange±1digit(Note2)
Platinel 2 0.0to1390.0ºC 32.0to2500.0ºF ±0.1%ofinstrumentrange±1digit
PR20-40 0.0to1900.0ºC 32to3400ºF
±0.5%ofinstrumentrange±1digitfor800°Cormore Accuracyisnotguaranteedforlessthan800°C.
W97Re3-W75Re25 0.0to2000.0ºC 32to3600ºF ±0.2%ofinstrumentrange±1digit
RTD
JPt100-200.0to500.0ºC -300.0to1000.0ºF ±0.1%ofinstrumentrange±1digit
(Note1)-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit
Pt100-200.0to850.0ºC -300.0to1560.0ºF ±0.1%ofinstrumentrange±1digit
(Note1)-200.0to500.0ºC -300.0to1000.0ºF-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit
Standardsignal0.400to2.000V
±0.1%ofinstrumentrange±1digit
1.000to5.000V4.00to20.00mA
DCvoltage/current
0.000to2.000V0.00to10.00V0.00to20.00mA-10.00to20.00mV0.0to100.0mV
Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,andpowerfrequencyat50/60Hz.
Note1: ±0.3°C±1digitintherangebetween0and100°C,±0.5°C±1digitintherange between-100and200°C.
Note2: W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988
•Inputsampling(control)period:200ms•Burnoutdetection: FunctionsatTC,RTD,andstandardsignal. Upscale,downscale,andoffcanbespecified. Forstandardsignal,burnoutisdeterminedtohaveoccurredifitis0.1Vor0.4 mAorless.
•Inputbiascurrent:0.05µA(forTCorRTD)•Measuredcurrent(RTD):About0.16mA•Inputresistance: TCormVinput:1MΩormore Vinput:About1MΩ mAinput:About250Ω
•Allowablesignalsourceresistance: TCormVinput:250Ωorless Effectsofsignalsourceresistance:0.1µV/Ωorless DCvoltageinput:2kΩorless Effectsofsignalsourceresistance:About0.01%/100Ω• Allowablewiringresistance: RTDinput:Max.150Ω/wire(Theconductorresistancebetweenthethreewires shallbeequal.)
Wiringresistanceeffect:±0.1ºC/10Ω• Allowableinputvoltage/current: TC,mV,mAandRTDinput:±10VDC Vinput:±20VDC mAinput:±40mA• Noiserejectionratio: Normalmode:40dBormore(at50/60Hz) Commonmode:120dBormore(at50/60Hz) For100-240VAC, thepower frequencycanbesetmanually.Automatic detectionisalsoavailable.
For24VAC/DC,thepowerfrequencycanbesetmanually.• Referencejunctioncompensationerror: ±1.0ºC(15to35ºC),±1.5ºC(-10to15ºCand35to50ºC)• Applicablestandards:JIS/IEC/DIN(ITS-90)forTCandRTD
ContactInputSpecifications• Numberofinputs:SeethetableofModelandSuffixCodes.• Inputtype:No-voltagecontactinputortransistorcontactinput• Inputcontactrating:12VDC,10mAormore Useacontactwithaminimumon-currentof1mAormore.• ON/OFFdetection: No-voltagecontactinput: Contactresistanceof1kΩorlessisdeterminedas“ON”andcontact resistanceof50kΩormoreas“OFF.” Transistorcontactinput: Inputvoltageof2Vorlessisdeterminedas“ON”andleakagecurrentmust notexceed100µAwhen“OFF.”• Minimumstatusdetectionholdtime:Controlperiod+50ms• Use:SPswitch,operationmodeswitch,andeventinput
AnalogOutputSpecifications• Numberofoutputs: Controloutput:1 Cooling-sidecontroloutputofHeating/cooling type (Retransmissionoutput terminal):1
• Outputtype:Currentoutputorvoltagepulseoutput• Currentoutput:4to20mADCor0to20mADC/loadresistanceof600Ωorless• Currentoutputaccuracy:±0.1%ofspan(±5%ofspanfor1mAorless) Theaccuracy isthat inthestandardoperatingconditions:23±2°C,55±10%RH, andpowerfrequencyat50/60Hz.
• Voltagepulseoutput: Use:Timeproportionaloutput On-voltage:12Vormore/loadresistanceof600Ωormore Off-voltage:0.1VDCorless Timeresolution:10msor0.1%ofoutput,whicheverislarger
RetransmissionOutputSpecifications• Numberofoutputs:Retransmissionoutput;1,sharedwith15VDC looppowersupplyorCooling-sidecontroloutput.
• Currentoutput:4to20mADCor0to20mADC/loadresistanceof600Ωorless• Currentoutputaccuracy(conversionaccuracyfromPVdisplayonthesetscale):±0.1%ofspan(±5%ofspanfor1mAorless)
Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH, andpowerfrequencyat50/60Hz. This isnotconversionaccuracythroughinputandoutputbut theperformanceof
transmission output itself.
15VDCLoopPowerSupplySpecifications(SharedwithretransmissionoutputorCooling-sidecontroloutput.)• Powersupply:14.5to18.0VDC• Maximumsupplycurrent:About21mA(withshort-circuitcurrentlimitingcircuit)
StepResponseTimeSpecificationsWithin1s(63%ofanalogoutputresponsetimewhenastepchangeof10to90%ofinputspanisapplied)
External Dimensions
UT35A/MDL
37(1.46)
96(3.78) 20(0.79) 100(3.94)
Note:TrigonometryGeneral tolerance = ±(JIS B 0401-1998 tolerance class IT18)/2
Unit: mm(inch)
60(2.36)
DIN railTH35-75A
Cable for LL50
Minimum cable curvature: R40 (1.57)
4.3(0.17)
4(0.
16)
90 (3
.54)
min
.(r
equi
red
for r
emov
ing
the
inst
rum
ent f
rom
the
DIN
rail)
120
(4.7
2) m
in.
(requ
ired
for i
nser
ting/
rem
ovin
g th
e ca
ble
for L
L50A
)
91.6
(3.6
1)
114(
4.49
)10
0(3.
94)
94.6
(3.7
2)
UT32A/MDL
15(0.59)
48.2(1.90) 20(0.79) 100(3.94)
Unit: mm(inch)
60(2.36)
DIN railTH35-75A
Cable for LL50
4.3(0.17)
4(0.
16)
91.6
(3.6
1)
114(
4.49
)10
0(3.
94)
94.6
(3.7
2)
Note:TrigonometryGeneral tolerance = ±(JIS B 0401-1998 tolerance class IT18)/2
Minimum ca
ble curva
ture: R40 (1
.57)
90 (3
.54)
min
.(r
equi
red
for r
emov
ing
the
inst
rum
ent f
rom
the
DIN
rail)
120
(4.7
2) m
in.
(requ
ired
for i
nser
ting/
rem
ovin
g th
e ca
ble
for L
L50A
)
IM 05P01D81-11EN page 3/6
RelayContactOutputSpecifications• Contacttypeandnumberofoutputs: Controloutput:contactpoint1c;1point Heating/coolingtype:contactpoint1a;2pointsforbothheatingandcoolingsides Alarmoutput:contactpoint1a;3points(commonisindependent)• Contactrating: Contactpoint1c(controloutput):250VAC,3Aor30VDC,3A(resistanceload) Contactpoint1a(controloutput):240VAC,3Aor30VDC,3A(resistanceload) Contactpoint1a(alarmoutput):240VAC,1Aor30VDC,1A(resistanceload)• Use:Timeproportionaloutput,alarmoutput,FAILoutput,etc.• Timeresolutionofcontroloutput:10msor0.1%ofoutput,whicheverislargerNote:Thecontroloutputshouldalwaysbeusedwithaloadof10mAormore. Thealarmoutputshouldalwaysbeusedwithaloadof1mAormore.
TransistorContactOutputSpecifications• Numberofoutputs:SeethetableofModelandSuffixCodes.• Outputtype:Opencollector(SINKcurrent)• Outputcontactrating:Max.24VDC,50mA• Outputtimeresolution:Min.200ms• Use:Alarmoutput,FAILoutput,etc.
HeaterBreakAlarmSpecifications• Numberofinputs:2• Numberofoutputs:2(transistorcontactoutput)• Use:Measurestheheatercurrentusinganexternalcurrenttransformer(CT)andgeneratesaheaterbreakalarmwhenthemeasuredvalueis lessthanthebreakdetectionvalue.
• Currenttransformerinputresistance:About9.4Ω• Currenttransformerinputrange:0.0to0.1Arms(0.12Armsormorecannotbeapplied.)• Heatercurrentsettingrange:OFF,0.1to300.0Arms Heatercurrentmeasuredvaluedisplayrange:0.0to360.0Arms Note:TheCTratiocanbeset.CTratiosettingrange:1to3300• RecommendedCT:CTfromU.R.D.,Ltd. CTL-6-S-H:CTratio800,measurablecurrentrange:0.1to80.0Arms CTL-12L-30:CTratio3000,measurablecurrentrange:0.1to180.0Arms• Heatercurrentmeasurementperiod:200ms• Heatercurrentmeasurementaccuracy:±5%ofcurrent transformer input rangespan±1digit(CTerrorisnotincluded.)
• Heatercurrentdetectionresolution:Within1/250ofcurrenttransformerinputrangespan• BreakdetectionOn-time:Min.0.2second(fortimeproportionaloutput)
24VDCLoopPowerSupplySpecifications• Use:Powerissuppliedtoa2-wiretransmitter.• Powersupply:21.6to28.0VDC• Ratedcurrent:4to20mADC• Maximumsupplycurrent:About30mA(withshort-circuitcurrentlimitingcircuit.)
MaintenacePortSpecificationsThemaintenanceport isusedtoconnectadedicatedcablewhenusingtheLL50AParameterSettingSoftware (soldseparately).Through thisport, youcansetcontrollerparameters,downloadladderprograms,andsoon.Fordetails,seetheLL50AUser’sManual(IM05P05A01-02EN).
Dedicated cable
LL50A Parameter Setting Software
To USB terminal
NoteUseLL50Awiththecontrollerturnedon.(Thededicatedcablemustbeconnected.LL50ALight-loaderadaptercannotbeused.)ThemaintenanceportisnotisolatedfromthePVinputterminal.Usetheportonlyformaintenancepurposes,suchasforsettingthecontrollerparameters.
SafetyandEMCStandards• Safety: Compliantwith IEC/EN61010-1 (CE), IEC/EN61010-2-030 (CE),approvedbyCAN/CSAC22.2No.61010-1(CSA),approvedbyUL61010-1.
ControllerwithDINrail(option/MDL):CEmarkingscheduled Installationcategory:II Pollutiondegree:2 Measurementcategory:I(CATI)(UL,CSA) O(Other)(CE) Ratedmeasurementinputvoltage:Max.10VDC Ratedtransientovervoltage:1500V(*) *ThisisareferencesafetystandardvalueformeasurementcategoryIofIEC/EN/CSA/
UL61010-1.Thisvalueisnotnecessarilyaguaranteeofinstrumentperformance.• EMCstandards: CompliantwithCEmarking EN61326-1ClassA,Table2(Foruseinindustriallocations), EN61326-2-3 *Theinstrumentcontinuestooperateatameasurementaccuracyofwithin±20%ofthe
rangeduringtesting. EN55011ClassA,Group1 EN61000-3-2ClassA EN61000-3-3 EMCRegulatoryArrangementinAustraliaandNewZealand(forallmodelinclud-
ingLL50A) EN55011ClassA,Group1• KCmarking: Electromagneticwave interferencepreventionstandard,electromagneticwave
protection standard compliance
Construction,Installation,andWiring• Construction:Panelmounttype• Material:Polycarbonate(Flameretardancy:UL94V-0) DINrailmountingbracketmaterial:Panelsteelsheet• Casecolor:Black(Lightcharcoalgray)• Weight:1kgorless• Externaldimensions(mm): UT35A/MDL:96(width)x114(height)x100(depth) UT32A/MDL:48.2(width)x114(height)x100(depth)• CompatibleDINrails:TH35-7.5Fe,TH35-7.5Aℓ,JISC2812• Mountingposition:Horizontal.• Wiring:M3screwterminalwithsquarewasher(forsignalwiringandpowerwiring)
PowerSupplySpecificationsandIsolation• Powersupply: Ratedvoltage:100-240VAC(+10%/-15%),50/60Hz 24VAC/DC(+10%/-15%)(for/DCoption)• Powerconsumption:UT35A:18VA(DC:9VA,AC:14VAif/DCoptionisspecified) UT32A:15VA(DC:7VA,AC:11VAif/DCoptionisspecified)• Databackup:Nonvolatilememory• Powerholduptime:20ms(for100VACdrive)• Withstandingvoltage Betweenprimaryterminalsandsecondaryterminals:2300VACfor1minute(UL,CSA) Betweenprimaryterminalsandsecondaryterminals:3000VACfor1minute(CE) Betweenprimaryterminals:1500VACfor1minute Betweensecondaryterminals:500VACfor1minute (Primaryterminals:Power*andrelayoutputterminals;Secondaryterminals: AnalogI/Osignalterminals,contactinputterminals,communicationterminals andfunctionalgroundingterminals.)
*:Powerterminalsfor24VAC/DCmodelsarethesecondaryterminals.• Insulationresistance:Betweenpowersupplyterminalsandagroundingterminal20MΩormoreat500VDC
• Isolationspecifications
PV (universal ) input terminals / remote input terminals
Control relay (contact point c/contact point a x 2) output terminals
Alarm-1 relay (contact point a) output terminals
Alarm-2 relay (contact point a) output terminals
Alarm-3 relay (contact point a) output terminals
Contact input terminals (all)RS-485 communication terminals
24 V DC loop power supply terminals
Contact output (transistor) terminals
Ethernet communication terminal
PROFIBUS-DP/DeviceNet/CC-Link communication terminals
Current transformer input terminals
Control, retransmission (analog) output terminals(not isolated between the analog output terminals)
Internalcircuits
Powersupply
The circuits divided by lines are insulated mutually.
EnvironmentalConditions
Normal Operating Conditions:• Ambienttemperature:-10to50°C IftheCC-Linkoptionisspecified,0to50°CforUT35A/MDL;0to40°CforUT32A/MDL.(side-by-sidemounting:0to50°CforUT55A/MDL;0to40°CforUT52A/MDL)
• Ambienthumidity:20to90%RH(nocondensationallowed)
• Magneticfield:400A/morless• Continuousvibrationat5to9Hz:Halfamplitudeof1.5mmorless,1oct/minfor90minuteseachinthethreeaxisdirections
Continuousvibrationat9to150Hz:4.9m/s2orless,1oct/minfor90minuteseachinthethreeaxisdirections
• Short-periodvibration:14.7m/s2,15secondsorless• Shock:98m/s2orless,11ms• Altitude:2000morlessabovesealevel• Warm-uptime:30minutesormoreafterthepoweristurnedon• Startuptime:Within10seconds *: TheLCD(aliquidcrystaldisplay)isusedforadisplayportionofthisproduct.
TheLCDhasacharacteristicthatthedisplayactionbecomeslateatthelow temperature.However,thecontrolfunctionisnotaffected.
Transportation and Storage Conditions:• Temperature:-25to70ºC• Temperaturechangerate:20ºC/horless• Humidity:5to95%RH(nocondensationallowed)
Effects of Operating Conditions• Effectofambienttemperature: VoltageorTCinput:±1µV/ºCor±0.01%ofF.S./ºC,whicheverislarger Currentinput:±0.01%ofF.S./ºC RTDinput:±0.05ºC/ºC(ambienttemperature)orless Analogoutput:±0.02%ofF.S./ºCorless• Effectofpowersupplyvoltagefluctuation Analoginput:±0.05%ofF.S.orless Analogoutput:±0.05%ofF.S.orless (Eachwithinratedvoltagerange)
5. How to Connect Wires
WARNING
• Wiring work must be carried out by a person with basic electrical knowledge and practical experience.
• Be sure to turn OFF the power supply to the controller before wiring to avoid an electric shock. Use a tester or similar device to ensure that no power is being supplied to a cable to be connected.
• As a safety measure, always install a circuit breaker (an IEC 60947-compatible product, 5 A, 100 V or 220 V AC) in an easily accessible location near the instrument. Moreover, provide indication that the switch is a device for turning off the power to the instrument.
• Install the power cable keeping a distance of more than 1 cm from other signal wires.
• The power cable is required to meet the IEC standards concerned or the requirements of the area in which the instrument is being installed.
• Wiring should be installed to conform to NEC (National Electrical Code: ANSI/NFPA-70) or the wiring construction standards in countries or regions where wiring will be installed.
• For control relay output, alarm relay output, and power terminal connections, use heat-resistant cables.
• Since the insulation provided to each relay output terminal is Functional insulation, provide Reinforced insulation to the external of the device as necessary. (Refer to the drawing below.)
This product
Functional insulation
A safety voltage circuit
A safety voltage circuit
This product
Reinforced insulation
Reinforced insulation
Functional insulation
A hazardous voltage circuit
A hazardous voltage circuit
A safety voltage circuit
A safety voltage circuit
This product
Reinforced insulation
Reinforced insulation
Functional insulation
A hazardous voltage circuit
A hazardous voltage circuit
A hazardous voltage circuit
A hazardous voltage circuit
CAUTION
• When connecting two or more crimp-on terminal lugs to the single terminal block, bend the crimp-on terminal lugs before tightening the screw.
• Note that the wiring of two or more crimp-on terminal lugs to the single high-voltage terminal of the power supply and relay, etc. does not comply with the safety standard.
CAUTION
• Provide electricity from a single-phase power supply. If the power is noisy, install an isolation transformer on the primary side, and use a line filter on the secondary side. When measures against noise are taken, do not install the primary and secondary power cables close to each other.
• If there is a risk of external lightning surges, use a lightning arrester etc.
• For TC input, use shielded compensating lead wires for wiring. For RTD input, use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires.
• Since the control output relay has a life span (resistance load of 100,000 times), use the auxiliary relay to perform ON/OFF control.
• The use of inductance (L) loads such as auxiliary relays, motors and solenoid valves causes malfunction or relay failure; always insert a CR filter for use with alternating current or a diode for use with direct current, as a spark-removal surge suppression circuit, into the line in parallel with the load.
• After completing the wiring, the terminal cover is recommended to use for the instrument.
RecommendedCrimp-onTerminalLugs
(A)
(F)
(ød)
5.5 3.3
Recommendedtighteningtorque:0.6N·m Applicablewiresize:Powersupplywiring1.25mm2 or moreApplicable terminal lug Applicable wire size mm2 (AWG#) (φd) (A) (F)M3 0.25to1.65(22to16) 3.3 5.5 4.2
CableSpecificationsandRecommendedCablesPurpose Name and Manufacturer
Powersupply,relaycontactoutputs 600VGradeheat-resistantPVCinsulatedwires,JISC3317(HIV),0.9to2.0mm2
Thermocouple Shieldedcompensatingleadwires,JISC1610Forthermocoupleinput(PVinputandremoteinputwithdirectinput),shieldedcompensatingleadwireofcross-sectionalarealessthanorequalto0.75mm2isrecommended.Ifthecross-sectionalareaiswide,thereferencejunctioncompensationerrormaybelarge.
RTD Shieldedwires(three/fourconductors),UL2482(HitachiCable)Othersignals(otherthancontactinput/output) Shielded wiresOthersignals(contactinput/output) UnshieldedwiresRS-485communication Shielded wiresEthernetcommunication 100BASE-TX(CAT-5)/10BASE-TPROFIBUS-DPcommunication DedicatedcableforPROFIBUS-DP(Shieldedtwo-wires)DeviceNetcommunication DedicatedcableforDeviceNet(Shieldedfive-wires)CC-Linkcommunication DedicatedcableforCC-Link(Shieldedthree-wires)
PROFIBUS-DP/CC-LinkConnector(wiringside)(Partnumber:A1987JT)DeviceNetConnector(wiringside)(Partnumber:L4502BW)Recommendedtighteningtorque:0.5to0.6N·m
DC Relay Wiring
R
External DC power supplyRelayUT35A/UT32A
UT’s contact
Diode(Mount it directlyto the relay coilterminal (socket).)
Relay(Use one with a relay coil rating
less than the UT’s contact rating.)
AC Relay Wiring
UT35A/UT32A
R
UT’s contact CR filter(Mount it directlyto the relay coilterminal (socket).)
External AC power supply
Relay(Use one with a relay coilrating less than the UT’s
contact rating.)
Transistor Output Wiring
power+ –
UTDO
LoadCOM
IM 05P01D81-11EN page 4/6
6. Terminal Wiring Diagrams
CAUTION
• Do not use an unassigned terminal as the relay terminal. Do not use a 100-240 V AC power supply for the 24 V AC/DC
model; otherwise, the instrument will malfunction.
UT35A/MDL
E4-terminal area
E3-terminal area
PV
E1-terminal area
PV inputTC input RTD input
Voltage (mV, V) input
A
+
-
+
-
Current (mA) input
+
-
B
b
(Suffix code: Type 1=-2)
(Suffix code: Type 1=-2)
(24 V AC/DC power supply: Optional suffix code /DC)
(Equippedas standard)
Power supply
101
102
103
104
105
106
107
108
109
110
111
501
502
503
504
505
506
507
508
509
510
511
512
407
408
409
410
411
412
301
302
303
304
305
306
201
202
203
204
205
206
207
208
210
211
212
Cooling-side control output
101-112
501-512
401-412
301-306
201-212
ALM (Equipped as standard)Contact output
External contact output (relay)
AL3
AL2
AL1
Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load)
Alarm-3 output(PV high limit)
Alarm-2 output( PV low limit)
Alarm-1 output(PV high limit)
Common
Common
Common
UT104
105
106
107
108
109
100-240 V AC power supply
N
L
Allowable range: 100-240 V AC (+10%/-15%) (free voltage) 50/60 Hz shared
110
111
24 V AC/DC power supply
-
+
110
111
202
203
201
202
203
202
203
203
204
RET/OUT2Current/voltage pulse output
0-20 mA DC,4-20 mA DC,Voltage pulse (12V)
+
-
205
206
Factory default: PV input type is undefined.
OUT(Suffix code: Type1=-0)
Control output
101
102
Relay contact output
103
NC
NO
COM
Contact rating: 250 V AC, 3 A 30 V DC, 3 A (resistance load)
Factory default: Control output is relay.
OUTCurrent/voltage pulse output
0-20 mA DC,4-20 mA DC,Voltage pulse (12 V)
+
Retransmission output
+
-
Default: 4-20 mA DC
Default: Undefined
0-20 mA DC,4-20 mA DC
Control output (Suffix code: Type1=-0 or -2)
15 V DC loop power supply
14.5-18.0 V DC(Max. 21 mA DC)
+
-
207
208
207
- 208
207
208
Can be used for retransmission output or 15 V DC loop power supply when current/voltage pulse output is not used for control output.Current output range can be changed.
RETRetransmission output
4-20 mA DC or0-20 mA DC
15 V DC loop power supply
14.5-18.0 V DC(Max. 21 mA DC)
+
-
+
-
Default: 4-20 mA DC
Default: PV retransmission
Load resistance 600 Ω or less
Retransmission output (Equipped as standard)
205
206
205
206
Can be used for 15 V DC loop power supply when not used for retransmission output.
DI (Equipped as standard)Contact input
Contact rating: 12 V DC, 10 mA or more
External contact input
DI2
DI1
COM
AUTO when DI1=ONMAN when DI1=OFF
STOP when DI2=ONRUN when DI2=OFF
Common
DI2
DI1
COM
+5V
+5V
No-voltagecontact
Transistor contactUT UT
210
211
212
210
211
212
Function can be assigned to the terminals with no function.
112
112 112
N
L
Can not be used for retransmission output or 15 V DC loop power supply when current/voltage pulse output is used.Can be used for retransmission output or 15 V DC loop power supply when control output is not used.Current output range can be changed.
Heating/cooling control outputHeating/cooling relay contact output
NO
Heating-side
Cooling-side
NO
COM
Contact rating: 240 V AC, 3 A 30 V DC, 3 A (resistance load)
101
102
103
OUTOUT2
(Suffix code: Type 2=2)Contact inputExternal contact input
DI11
DI12
DI13
DI14
DI15
COMCommon
DI11
DI12
COM+5V
+5V
No-voltage contact Transistor contact
Contact rating: 12 V DC, 10 mA or more
DI13+5V
DI14+5V
DI15+5V
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
UT UT
301
302
303
304
305
306
301
302
303
304
305
306
Function can be assigned to the terminals with no function.
DI
E1-Terminal Area301-306
+
24 V DC loop power supply
21.6-28.0 V DC(Max. 30 mA DC)
−
24 V DC loop power supply
505
506
LPS24(Optional suffix code /LP)
(Suffix code: Type 2=2)Contact outputExternal contact output
DO42
DO41
DO43
DO44
DO45
COM
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
Common
UT501
502
503
504
505
506
DO
Transistor contact rating: 24 V DC, 50 mAFunction can be assigned to the terminals with no function.
E4-Terminal Area501-506E4-terminal area
E3-terminal area
E1-terminal area
101
102
103
104
105
106
107
108
109
110
111
501
502
503
504
505
506
507
508
509
510
511
512
407
408
409
410
411
412
301
302
303
304
305
306
201
202
203
204
205
206
207
208
210
211
212
101-112
501-512
401-412
301-306
201-212
112
(Suffix code: Type 3=2)
Ethernet communication (with gateway function)
10BASE-T/100BASE-TXRJ45 connector
ColorLitUnlit
Amber100M bps10M bps
Green
LinkedActiveLink failure
Color
LitBlinkUnlit
Upper side LED (baud rate)
Lower side LED (link activity)
RS-485
RSB(+)
RSA(-)
SG
407
408
409
ETHRRS-485
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
RS-485 communication(Suffix code: Type 3=1)
407
408
409
410
411
RS485
E3-Terminal Area401-412
(Suffix code: Type 3=4)
PROFIBUS-DP communication (with Modbus master)
Pin1
2
Signal name DescriptionVP
RxD/TxD-P
3 RxD/TxD-N
4 DGND5 SHIELD
+5V bus powerData signal (positive data receive/transmit)
Data signal (negative data recive/transmit)
Signal groundShield ground
RS-485
RSB(+)
RSA(-)
SG
407
408
409
PROF
If the UT is located at the end of a segment for the PROFIBUScommunication wiring,terminating resistors are separately needed.These are to be prepared by users. (390 Ω: 2 pcs. 220 Ω: 1 pc., or an activeterminator.)
VP
RxD/TxD-PData line
Data line
390Ω
220Ω
390ΩRxD/TxD-N
DGND
CHKRDYERR
LEDCHK(red)
RDY(green)
Lit Unlit
ERR(red)
User profile error Normal
NormalNot connected, orcommunicationfailure (flashing)
NormalCommunicatingsuccessfully
No power, or Communication failure
1
2
3
4
5
(Suffix code: Type 3=3)
CC-Link communication (with Modbus master)
RS-485
RSB(+)
RSA(-)
SG
407
408
409
CC-L
If the UT is located at the end of a segment for the CC-Linkcommunication wiring,terminating resistors are separately needed.These are to be prepared by users. (110 Ω: 1 pc.)
DA
DB
110Ω
LEDCHK(red)
L ERR(red)
L RUN(green)
Lit Unlit
CHK
L RUNL ERR
User profile error/Address error Normal
Normal
Pin12
Signal name Description
DA
DB3 DG4
SLD
5
FG
RX/TX + signal
RX/TX - signal
Flame ground
RX/TX signal ground
Shield
NormalCommunicating successfully
Communication failure (CRC error)
No carrier detected/Communication timeout
1
2
3
4
5
(Suffix code: Type 3=5)
DeviceNet communication (with Modbus master)
RS-485
RSB(+)
RSA(-)
SG
407
408
409
DNET
If the UT is located at the end of a segment for the DeviceNetcommunication wiring,terminating resistors are separately needed.These are to be prepared by users. (121 Ω: 1 pc.)
CAN_H
CAN_L
121Ω
LEDCHK(red)
MNS(green/red)
Lit/flashing Unlit
User profile error Normal
Pin12
Signal name Description
CAN_H
CAN_L
3
V+
4
V-5
DRAINRX/TX + signal
RX/TX - signal
Shield/Drain wire
DeviceNet power supply 24V
DeviceNet power supply common
Normal, communicating successfully (green, lit).Not connected (green, flashing).
Critical link failure (red, lit).Connection timeout (red, flashing)
At power-on/Communication faulted (green/red, flashing)
No electricity
CHK
MNS
1
2
3
4
5
IM 05P01D81-11EN page 5/6
UT32A/MDL
(Suffix code: Type 1=-2)
(Suffix code: Type1=-0) Retransmission output
4-20 mA DC or0-20 mA DC
15 V DC loop power supply
14.5-18.0 V DC(Max. 21 mA DC)
+
-
+
-
Default: 4-20 mA DC
Default: PV retransmission
Load resistance 600 Ω or less
Retransmission output (Equipped as standard)PV inputTC input RTD input
Voltage (mV, V) input
A
+
-
+
-
Current (mA) input
+
-
B
b
(Equipped as standard)Control output
Relay contact output
NC
NO
COM
Contact rating: 250 V AC, 3 A 30 V DC, 3 A (resistance load)
111
301
302
303
304
305
306
201
202
203
204
205
206
207
208
210
101
102
103
104
105
106
107
108
109
110
211
212
Current/voltage pulse output
0-20 mA DC,4-20 mA DC,Voltage pulse (12 V)
-
Heating/cooling control output(Suffix code: Type 1=-2)
Cooling-side control output
Heating/cooling relay contact output
NO
Heating-side
Cooling-side
NO
COM
Contact rating: 240 V AC, 3 A 30 V DC, 3 A (resistance load)
E1-terminal area101-112
301-312
201-212
101
102
103
202
203
201
202
203
202
203
203
204
205
206
205
206
101
102
103
+ 205
206
Factory default: Control output is relay.Can be used for 15 V DC loop power supply when not used for retransmission output.
PV RET
(Equipped as standard)Contact input
Contact rating: 12 V DC, 10 mA or more
External contact input
DI2
DI1
COM
AUTO when DI1=ONMAN when DI1=OFF
STOP when DI2=ONRUN when DI2=OFF
Common
DI2
DI1
COM
+5V
+5V
No-voltagecontact
Transistor contactUT UT
210
211
212
210
211
212
Function can be assigned to the terminals with no function.
DI
(Equipped as standard)Contact output
External contact output (relay)
AL3
AL2
AL1
Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load)
Alarm-3 output(PV high limit)
Alarm-2 output(PV low limit)
Alarm-1 output(PV high limit)
Common
Common
Common
UT104
105
106
107
108
109
ALM
OUT
OUT
RET/OUT2
Factory default: PV input type is undefined.
Current/voltage pulse output
0-20 mA DC,4-20 mA DC,Voltage pulse (12 V)
+
-
Retransmission output
+
-
Default: 4-20 mA DC
Default: Undefined
0-20 mA DC,4-20 mA DC
Control output (Suffix code: Type1=-0 or -2)
15 V DC loop power supply
14.5-18.0 V DC(Max. 21 mA DC)
+
-
207
208
207
208
207
208
Can be used for retransmission output or 15 V DC loop power suppy when current/voltage pulse output is not used for control output.Current output range can be changed.
OUT
OUT2
112
Power supply24 V AC/DC power supply
-
+
100-240 V AC power supply
Allowable range: 100-240 V AC (+10%/-15%) (free voltage) 50/60 Hz shared
N
L
(24 V AC/DC power supply: Optional suffix code /DC)
110
111
110
111
112 112
N
L
Can not be used for retransmission output or 15 V DC loop power suppy when current/voltage pulse output is used for control output.Can be used for retransmission output or 15 V DC loop power suppy when control output is not used.Current output range can be changed.
(Optional suffix code /HA)Heater break alarmHeater current detection input
CT1
CT2
COM
310
311
312
HBAExternal contact output (transistor)
Transistor contact rating: 24 V DC, 50 mA
Heater break alarm-1output
Heater break alarm-2output
Common
HAL1
HAL2
COM
UT307
308
309
307
308
309
310
311
312
+
24 V DC loop power supply
21.6-28.0 V DC(Max. 30 mA DC)
-
24 V DC loop power supply
(Suffix code: Type 2=0 and optional suffix code /LP)305
306
LPS24
E1-Terminal Area301-306
RS-485
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
RS-485 communication(Suffix code: Type 2=1)
301
302
303
304
305
RS485
RS-485
RSB(+)
RSA(-)
SG
RS-485 communication/24 V DC loop power supply
+
24 V DC loop power supply
21.6-28.0 V DC(Max. 30 mA DC)
-
301
302
303
305
306
RS485/LPS24(Suffix code: Type 2=1 and optional suffix code /LP)
CC-Link communication (with Modbus master)
(Suffix code: Type 3=3)FG: Flame ground
SLD: Shield
DG: TX/RX signal ground
DB: RX/TX signal - signal
DA: RX/TX signal + signal
CHK(red)(Lit: User profile error/Adress error, Unlit: Normal)
L ERR(red)(Lit: Communication failure(CRC error), Unlit: Normal)
L RUN(green)(Lit: Normal, Unlit: No carrier detected/Communication timeout)
Not used
301
302
303
304
305
306
307
308
309
RS-485
RSB(+)
RSA(-)
SG
310
311
312
DB
DA
110Ω
CC-LIf the UT is located at the end of a segment for the CC-Link communication wiring,terminating resistors are separately needed.These are to be prepared by users. (110 Ω: 1 pc.)
• AuthorisedRepresentativeintheEEA YokogawaEuropeBV.(Address:Euroweg2,3825HDAmersfoort,TheNether-lands) istheAuthorisedRepresentativeofYokogawaElectricCorporationforthisProductintheEEA.
• Printed ManualsModel Description
UT35A/UT32ADigitalIndicatingControllerOperationGuide(Standardcodemodel) IM05P01D31-11ENUT35A/UT32ADigitalIndicatingControllerOperationGuide(Detailedcodemodel) IM05P01D31-15ENUT35A/MDL,UT32A/MDLController(MountonDINRail)OperationGuide(Standardcodemodel)
IM05P01D81-11EN
UT32A-DDigitalIndicatingController(Dual-looptype)OperationGuide IM05P08D31-11ENUT32A-D/MDLController(Dual-looptype,MountonDINRail)OperationGuide IM05P08D81-11ENUT35A/RSP,UT32A/RSPDigitalIndicatingController(Non-isolatedRSP)OperationGuide(Standardcodemodel)
IM05P01D31-81EN
UT32ADigitalIndicatingController(Entrymodel)OperationGuide(Standardcodemodel) IM05P01F31-11ENPrecautionsontheUseoftheUTAdvancedSeries IM05P01A01-11EN
• ElectronicManuals Youcandownloadthelatestmanualsfromthefollowingwebsite: URL:http://www.yokogawa.com/ns/ut/im/
Model DescriptionUT35A/UT32ADigitalIndicatingControllerOperationGuide(Standardcodemodel) IM05P01D31-11ENUT35A/UT32ADigitalIndicatingControllerOperationGuide(Detailedcodemodel) IM05P01D31-15ENUT35A/MDL,UT32A/MDLController(MountonDINRail)OperationGuide(Standardcodemodel)
IM05P01D81-11EN
UT35A/UT32ADigitalIndicatingControllerUser’sManual IM05P01D31-01ENUT32A-DDigitalIndicatingController(Dual-looptype)OperationGuide IM05P08D31-11ENUT32A-D/MDLController(Dual-looptype,MountonDINRail)OperationGuide IM05P08D81-11ENUT32A-D,UT32A-D/MDLDigitalIndicatingControllerUser’sManual IM05P08D31-01ENUT35A/RSP,UT32A/RSPDigitalIndicatingController(Non-isolatedRSP)OperationGuide(Standardcodemodel)
IM05P01D31-81EN
UT32ADigitalIndicatingController(Entrymodel)OperationGuide(Standardcodemodel)
IM05P01F31-11EN
UT32ADigitalIndicatingController(Entrymodel)User’sManual(Standardcodemodel) IM05P01F31-01ENUTAdvancedSeriesCommunicationInterface(RS-485,Ethernet)User’sManual IM05P07A01-01ENUTAdvancedSeriesCommunicationInterface(OpenNetwork)User’sManual IM05P07A01-02ENLL50AParameterSettingSoftwareInstallationManual IM05P05A01-01ENLL50AParameterSettingSoftwareUser’sManual IM05P05A01-02ENPrecautionsontheUseoftheUTAdvancedSeries IM05P01A01-11EN
• GeneralSpecificationModel Description
UT35A/UT32ADigitalIndicatingController GS05P01D31-01ENUT35A/MDL,UT32A/MDLController(MountonDINRail) GS05P01D81-11ENUT32A-DDigitalIndicatingController(Dual-looptype) GS05P08D31-01ENUT32A-D/MDLController(Dual-looptype,MountonDINRal) GS05P08D81-01ENLL50AParameterSettingSoftware GS05P05A01-01EN
* Thelasttwocharactersofthemanualnumberandgeneralspecificationnumberindicatethelanguageinwhichthemanualiswritten.
IM 05P01D81-11EN page 6/6
7. Setup ProcedureThe following flowchartshows thesetupprocedure forUT35A/MDLandUT32A/MDL.PerformsetupthroughcommunicationortheLL50AParameterSettingSoftware(soldseparately).
Install and wire a controller.
Monitoring and control of regular operations
Adjust PID using auto-tuning or manually for PID control.
(Set parameters through communication.)
Operation
NO
YES
PID tuning
Installationand wiring
Power ON
ParameterSettings
ParameterSettings
Use LL50ASoftware?
LL50A: Parameter setting software (sold separately)See the LL50A Parameter Setting Software User’s Manual (IM 05P05A01-01EN).Use LL50A with the controller turned on. (The dedicated cable must be connected. LL50A Light-loader adapter cannot be used.)The maintenance port is not isolated from the PV input terminal. Use the port only for maintenance purposes, such as for setting the controller parameters.
To set parameters through communication, you need to create a program on the host device side. For controller parameter information (registers, relays), see the following manuals.• For setup through RS485 serial
communication or Ethernet communication, see the UTAdvanced Series Communi-cation Interface User’s Manual (IM 05P07A01-01EN).
• For setup through an open network, see the UTAdvanced Series Communication Interface (Open Network) User’s Manual (IM 05P07A01-02EN).
8. OperationsThecontrollerstatuscanbeverifiedwiththeLED.
Status LED Lit/Blinks DescriptionNormal Green LitCommunicationerror Green Blinks Checkthecommunicationwiringandsettings.
Instrument failure Red Lit Parametererror/Hardwarefailure/Ladderprogramcorruption.
Input error Red BlinksSensorburnout,inputover
Checktheinputwiringandsettings.
LED lamp
UT35A/MDL Front(with terminal cover)
UT32A/MDL Front(with terminal cover)
Check theoperatingstatus (run/stop,auto/manual, remote/local, etc.) of thecontroller throughcommunicationor theLL50AParameterSettingSoftware(soldseparately).Fordetails,see the(1)UT35A/UT32ADigital IndicatingControllerUser’sManual(IM05P01D31-01EN), (2)UTAdvancedSeriesCommunication Interface(RS-485,Ethernet)User’sManual(IM05P07A01-01EN),and(3)LL50AParameterSettingSoftwareUser’sManual(IM05P05A01-02EN).
9. TroubleshootingIfaproblemappearstobecomplicated,contactoursalesrepresentatives.
Is the controllerdefective?
Contact us for repair. Problem solved.
The LED lamp is unlit.
Yes
Yes
No
Yes
No
No
Yes
Check wiring of thepower terminals.
The LED lamp is flashing
in red.
(I/O signal failure?)
The LED lamp is lit in red.
Yes
No
Check the supply voltage.
Check the specifications and polarity
of connected devices .Check the communication-
related parameters.
Check the specificationsof communication
devices.
Check thecommunication wiring.
(Communication failure?)
Yes
Normal?
Check the specificationsof the controller.
Yes
NoCorrect?
Correct the error(s).
Check the I/O specificationsof the controller.
The LED lamp is flashing
in green.
Errors at Power OnTheerrorsshownbelowmayoccurinthefaultdiagnosiswhenthepoweristurnedon.(FordetailsofSetpointdisplayandinput/outputactionwheneacherroroccurs,seeUser’sManual.)YoucanviewthedetailsofeacherrorthroughcommunicationortheLL50AParameterSettingSoftware(soldseparately).(Viewontheregistermonitor.)Fordetailsoneachregister,seetheUTAdvancedSeriesCommunicationInterface(RS485,Ethernet)User’sManual(IM05P07A01-01EN).
LED display Register that displays error details Error description Cause and diagnosis Remedy
Unlit — FaultyMCURAM/MCUROM MCURAM/MCUROMarefailed. Faulty.Contactusforrepair.
Red,lit
Setupparameter(PA.ER)(Registerno.:2068)Bit0=1 System data error System data is corrupted. Faulty.Contactusforrepair.
Setupparameter(PA.ER)(Registerno.:2068)Bit1=1 Calibrationvalueerror Initializedtocalibrateddefaultvaluebecauseofcorruptedfactorydefaultvalue. Faulty.Contactusforrepair.
Setupparameter(PA.ER)(Registerno.:2068)Bit2=1
User(parameter)defaultvalueerror
Userparameteriscorrupted.Initializedtofactorydefaultvalue. Checkandreconfiguretheinitialized
settingparameters.Errorindicationiserased when the power is turned on again.
Setupparameter(PA.ER)(Registerno.:2068)Bit4=1 Setup parameter error Setup parameter data is corrupted.
Initializedtouserdefaultvalue.Setupparameter(PA.ER)(Registerno.:2068)Bit5=1 Operation parameter error Operation parameter data is corrupted.
Initializedtouserdefaultvalue.Setupparameter(PA.ER)(Registerno.:2068)Bit8=1 FaultyFRAM Datawriting(storing)toFRAMisimpossible. Faulty.Contactusforrepair.
Setupparameter(OP.ER)(Registerno.:2070)E1-terminal:Bit0=1E2-terminal:Bit1=1E3-terminal:Bit2=1E4-terminal:Bit4=1
Nonrespondinghardwareofextendedfunction(E1toE4-terminalareas)
Inconsistenceofsystemdataandhardwareofextendedfunction.Nonrespondingcommunicationbetweenhardwareofextendedfunction(E1toE4-terminalareas).
Faulty.Contactusforrepair.
Setupparameter(LA.ER)(Registerno.:2012)Bit0=1 Corruptedladderprogram Ladderprogramiscorrupted.
Operateswithoutladderprogram. Downloadtheladderprogramagain.
Green,blinks Setupparameter(OP.ER)(Registerno.:2070)Bit10=1 Userprofileerror Userprofileiscorrupted. Downloadtheuserprofileagain.
Errors during OperationTheerrorsshownbelowmayoccurduringoperation.(Forinput/outputactionwheneacherroroccurs,seeUser’sManual.)YoucanviewthedetailsofeacherrorthroughcommunicationortheLL50AParameterSettingSoftware(soldseparately).(Viewontheregistermonitor.)Fordetailsoneachregister,seetheUTAdvancedSeriesCommunicationInterface(RS485,Ethernet)User’sManual(IM05P07A01-01EN).
LED display Register that displays error details Error description Cause and diagnosis Remedy
Red,lit
Setupparameter(AD1.E)(Registerno.:2001)Bit0=1
AnaloginputterminalADCerror•PVinput AnaloginputterminalADvalueerror Faulty.Contactusforrepair.
Setupparameter(AD1.E)(Registerno.:2001)Bit5=1
UniversalinputterminalRJCerror•PVinput UniversalinputterminalRJCerror
Faulty.Contactusforrepair.SettheparameterRJCtoOFFtoeraseerror indication.
Red,blinks
Setupparameter(AD1.E)(Registerno.:2001)Bit8=1
Analoginputterminalburnouterror•PVinput Analoginputterminalsensorburnout
Checkwiringandsensor.Errorindicationiserasedinnormaloperation.
Setupparameter(PV1.E)(Registerno.:2002)Bit0=1 PVinputburnouterror BurnoutofanaloginputconnectedtoPV
Checkwiringandsensorofconnectedanaloginputterminals.Errorindicationiserasedinnormaloperation.
Setupparameter(PV1.E)(Registerno.:2002)Over-scale:Bit4=1Under-scale:Bit5=1
PVinputover-scalePVinputunder-scale(PVvaluesoutof-5to105%)
PVinputisoutof-5to105%.Alsooccurswhenthedataoutofrangewhichistheladder calculation result is input.
Checkanaloginputvalueorladderprogram.
ChecktheerrorinLL50Asoftware.
Setupparameter(LA.ER)(Registerno.:2012)Overflow:Bit1=1Ladderprogramerror:Bit1=1Loadfactorover100%:Bit4=1Loadfactorover200%:Bit5=1
Laddercalculationoverflow Floatingpointcomputationforladdercalculationisinfinite. Checktheladderprogram.
Loadfactorover100% Computationdoesnotendwithinthecontrolperiod(loadfactoris100%ormore).Changethecontrolperiodorreducethe number of steps for the ladder program.
Loadfactorover200%(Forcedend) Computationdoesnotendwithinthecontrolperiod(loadfactoris200%ormore). Changethecontrolperiodorreducethe
numberofstepsfortheladderprogram.
Ladderprogramerror Ladderprogramiscorrupted.Downloadtheladderprogramagain.Iftheerrorindicationisstillnoterased,thereisafault.Contactusforrepair.
Green,blinks
Setupparameter(OP.ER)(Registerno.:2070)E1-terminal:Bit8=1E3-terminal:Bit10-=1E4-terminal:Bit12=1
Peer-to-peercommunicationerror Peer-to-peercommunicationerrorCheckthatthetargetdevicesareconnected correctly.Recoveryatnormalreceipt.
ChecktheerrorinLL50Asoftware.
Setupparameter(PV1.E)(Registerno.:2002)Bit14=1 Auto-tuningtime-out Auto-tuningdoesnotendevenwhen24hourshaveelapsedafterthestartof
tuning.Checktheprocess.Holddownanykeytoerase the error indication
Green,blinks
Setupparameter(OP.ER)(Registerno.:2070)E1-terminal:Bit8=1E3-terminal:Bit10-=1E4-terminal:Bit12=1
Communicationerror(RS-485communication)
FramingparityerrorBufferoverflowInter-charactertime-outChecksumerror(PClinkcommunicationwithchecksum)CRCcheckerror(Modbus/RTU)LRCcheckerror(Modbus/ASCII)
Checkthecommunicationparameters.Recoveryatnormalreceipt.Holddownanykeytostopblinking.
Communicationerror(coordinatedoperation)
InconsistenceofloopbetweencoordinatedmasterandslavesCheckthecommunicationparameters.Recoveryatnormalreceipt.Changefromremotetolocalmodetostopblinking.Whenthemodeischangedfromremotetolocal,SPtrackingdoesnotworkevenifitissettoON.
Communicationfromcoordinatedmasterisinterruptedfor2seconds.
Userprofileerror Userprofileiscorrupted. Downloadtheuserprofileagain.
Red,lit Setupparameter(PA.ER)(Registerno.:2068)Bit8=1 FaultyFRAM Writing(storing)datatoFRAMisimpossible. Faulty.Contactusforrepair.
Unlit — FaultyMCU/DCU(ROM/RAMerror,corrupted) MCU/DCUiscorrupted. Faulty.Contactusforrepair.