500
CONSULTANT KIT 2020 Critical Power

 · 2 About Vertiv Vertiv (NYSE: VRT) brings together hardware, software, analytics and ongoing services to ensure its customers’ vital applications run continuously, perform optima

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

  • 1

    CONSULTANT KIT

    2020

    Critical Power

  • 2

    About Vertiv

    Vertiv (NYSE: VRT) brings together hardware, software, analytics and ongoing services to ensure its customers’ vital applications run continuously, perform optimally and grow with their business needs. As Architects of Continuity™, Vertiv solves the most important challenges facing today’s data centers, communication networks and commercial and industrial facilities with a portfolio of power, cooling and IT infrastructure solutions and services that extends from the cloud to the edge of the network. Headquartered in Columbus, Ohio, USA, Vertiv employs approximately 20,000 people and does business in more than 130 countries. For more information, and for the latest news and content from Vertiv, visit Vertiv.com.

  • 3

  • 4

    Nearly all aspects of our lives involve the use of technology. It is how we work and play and do anything in between. This connectivity or use of data is built into the very fabric of our society. It is vital to human progress. Vertiv believes there is a better way to meet this accelerating demand for data — one driven by passion and innovation.

    As industry experts and Architects of Continuity, we collaborate with our customers to envision and build future-ready infrastructures. We leverage our portfolio of hardware, software, analytics, and services, to ensure our customers’ vital applications run continuously, perform optimally, and scale with business needs.

    Data Centers: Hyperscale, Enterprise, Distributed IT/Edge, Colocation and CloudCommunication Networks: Macro Site, Central Off ice, Small Cell and Data CenterCommercial and Industrial: Healthcare, Manufacturing, Rail/Mass Transit, Power Generation and Oil and Gas

    KEY FACTS

    Public (NYSE:VRT)

    STATUS

    REVENUE

    HEADQUARTERS

    4.4 Billion

    Global: Columbus, Ohio, USARegional: China, India, Philippinesand United Kingdom

    (Fiscal 2019)

    Rob Johnson, CEO

    LEADERSHIP

    EMPLOYEES

    MAJOR CUTOMERS

    ~20,000 Worldwide

    Alibaba, Alstom, AmericaMovil, AT&T, China Mobile,Equinix, Ericsson, Reliance,Siemens, Telefonica, Tencent,Verizon and Vodafone

    Ensuring the continuity of today’s and tomorrow’s vital applications

    Critical Infrastructure and Solutions

    IT and Edge Infrastructure

    Services and Software Solutions

    Broad range of power, thermal, and IT and edge infrastructure, solutions and services portfolio

    GeographyOffering

    Americas

    EMEA

    AP

    Global, well-established footprint and supply-chain network

    End Market

    Data Centers

    Communications

    Commercial & Industrial

    Customers who operate in some of the world’s most critical industries

  • 5

    OUR PURPOSE

    We believe there is a better way to meet the worlds accelerating demand for data — one driven by passion and innovation.

    OUR PRESENCE

    US AND CANADAManuf. and Assembly Locations 7Service Centers 120+ Service Field Engineers 850+ Technical Support/Response 120+ Customer Experience Centers/Labs 4

    GLOBAL PRESENCE Manuf. and Assembly Locations 19Service Centers 270+ Service Field Engineers 2,700+ Technical Support/Response 330+ Customer Experience Centers/Labs 17

    LATIN AMERICA Manuf. and Assembly Locations 1Service Centers 20+ Service Field Engineers 300+ Technical Support/Response 25+ Customer Experience Centers/Labs 2

    EUROPE, MIDDLE EAST AND AFRICAManuf. and Assembly Locations 5Service Centers 70+ Service Field Engineers 600+ Technical Support/Response 95+ Customer Experience Centers/Labs 6

    ASIA PACIFICManuf. and Assembly Locations 6Service Centers 60+ Service Field Engineers 950+ Technical Support/Response 90+ Customer Experience Centers/Labs 5

  • 6

    WE DRIVE POSSIBILITY IN:

    DATA CENTERSCOMMERCIAL & INDUSTRIAL

    ENVIRONMENTSCOMMUNICATION

    NETWORKS

    Micro Edge Cloud Enterprise

    Prefab CoLo Hyperscale

    Healthcare Rail Transportation Power Generation

    Oil and Gas Mining Manufacturing

    Small Cell Macro Sites Central Off ice Data Center

    OUR FLAGSHIP BRANDS:

    Avocent® Liebert® Geist™

    IT Management

    Power and Thermal Management Power

    Distribution Monitoring

    Rack PDU

    Chloride® NetSure™

    Industrial AC UPS systems Industrial DC UPS systems Industrial DC-AC inverter systems Industrial grade modular AC and DC UPS systems BMS (Battery Monitoring systems) for safe area and hazardous area

    (Zone-1 rated)

    DC Power Outside Enclosures

    HOW IT ALL COMES TOGETHER

    Services and Software

    Solutions

    Large InfrastructureAC Power, DC Power, EnergyStorage, Industrial Solutions,Thermal

    IT and Edge InfrastructureEdge Systems, IT Systems, Rack,Rack PDU, Rack Thermal,Rack UPS

    We’re building a world where critical technologies always work.An agile operation focused on delivering innovative and intelligent technologies for vital applications.

  • 7

    OUR TECHNOLOGIES AND SERVICES

    Power Management

    UPS Power Distribution Battery Monitoring

    DC Power Solutions In-Rack Power Distribution Units

    Thermal Management

    Perimeter Cooling In-Row Cooling, SmartAisle™ Freecooling Chillers Evaporative Freecooling iCOM™ Controls

    IT Management

    Serial Console Consolidated Management Appliance High Performance KVM Desktop Secure KVM and KM Management Software

    Unified Infrastructure

    Rack/Row Level Design and Integration Room Level Design and Integration Site Level Design, Integration, and Build

    Software

    Data Center Monitoring Energy Management Power Management

    Capacity Management Remote Management Change Management

    Services

    PROJECT MAINTENANCE PERFORMANCE

    When launching new facilities or powering up new equipment, you want to do it right – right from the start

    Plan

    Design

    Engineer

    Integrate

    Commission

    Document

    Project Management

    Services to ensure that your business-critical infrastructure operates reliably, safely and efficiently

    Preventive and corrective maintenance

    Remote services and monitoring

    Cap / Fan / Battery replacements

    Repair

    Spare parts

    Full range of services designed to optimize infrastructure performance and reduce process complexity

    Assess

    Audit

    Model

    Configure

    Upgrade

    Train

  • 8

    Table of ContentsUNINTERRUPTIBLE POWER SUPPLY

    Liebert® GXT5 11BrochureGuide SpecificationsInstallation Size

    Liebert® GXT RT+ 33BrochureGuide Specifications

    Vertiv™ EDGE UPS 51Brochure

    Liebert® ITA2 62BrochureGuide SpecificationsInstallation Size

    Liebert® EXS 90BrochureGuide SpecificationsSite Planning DataInstallation Size

    Liebert® EXM 119BrochureGuide SpecificationsSite Planning DataInstallation Size

    Liebert® APM 150BrochureGuide SpecificationsSite Planning DataInstallation Size

    Liebert® EXL S1 228BrochureGuide SpecificationsSite Planning DataInstallation Size

    Liebert® Hipulse U 270BrochureGuide SpecificationsSite Planning DataInstallation Size

    Liebert® NXL 302BrochureInstallation Size

    Liebert® Trinergy Cube 314BrochureGuide Specifications

    MONITORING

    Trellis™ Smart Infrasight 346Brochure

    Liebert® RDU501 349Brochure

  • 9

    POWER CONDITIONING

    Liebert® AF2 355BrochureGuide Specifications

    POWER DISTRIBUTION

    Vertiv™ Geist PDUs 375Brochure

    Liebert® Busway 382BrochureGuide Specifications

    Liebert® SPM 1.0 393Brochure

    Liebert® SPM 2.0 398BrochureGuide Specifications

    STATIC TRANSFER SWITCH

    Liebert® LTS (10A-32A) 411BrochureInstallation Size

    Liebert® LTS (63-630A) 416Brochure

    Liebert® STS2 419BrochureGuide SpecificationsInstallation Size

    Liebert® Cross Chasis/Cabinet 438BrochureGuide Specifications

    Liebert® Cross Rack 452BrochureGuide Specifications

    INTEGRATED POWER TRENDS

    Liebert® APT 464Brochure

    Liebert® EPK 470Brochure

    ENCLOSURE

    Vertiv™ VE Rack 481BrochureInstallation Size

  • 10

    UninterruptiblePower Supply

  • 11

    Liebert® GXT5

    Intelligent, Versatile, and Reliable Power Protection for your Critical Applications

    750 VA to 3 kVA

  • 12

    Available in 750 VA/1/1.5/2/3 kVA ratings

    Top-level on-line double conversion UPS formission-critical applications

    Unity output power factor

    LCD multi-language color display (gravitysensing)

    full load

    Controllable and programmable outputsockets

    Integrated solution with batteries andelectronics

    External battery cabinets auto-detection

    Intelligent Communication ready

    Safety Agency Approved Category B IEC

    capability)

    Key Features

    The Vertiv™ Liebert® GXT5 UPS is an online double conversion UPS solution

    The Liebert® GXT5 is a single phase UPS built on the super reliable platform of GXT series- supporting over a million critical systems all over the world.

    application needs for both centralized and edge network applications.

    Scalable runtime options with matching external

    extended uninterrupted power is required. User friendly LCD interface as well as full network

    remote updates, make this system easy to deploy and simple to maintain.

    Sleep well knowing your business is protected by the premium products from Vertiv.

    Ideally suited for:

    Edge applications

    Network workstations

    Web and application servers

    Network closets

    Large network peripherals

    VoIP

    Liebert® GXT5 | Brochure

  • 13

    VertivTM Liebert® GXT5 Highlights

    Intelligent Battery Management

    New algorithm to estimate Battery health status and replacement date prediction.

    Unity power factor (PF=1.0)

    More active power available so more loads can be connected versus lower power factor systems thus saving space and cost.

    Even high efficiency up to 98% in Active ECO mode

    Superior protection with maximum

    High efficiency up to 94% in on-line mode

    means optimized energy management and lower heat dissipation, thus providing energy and cost savings.

    Colored graphic LCD display with gravity orientation

    User friendly interface to know UPS status and

    Rack / Tower design with short depth and flexible to install

    A more compact UPS that will use

    and leaves more space available for data equipment in a rack.

    Battery cabinets with auto-detection*

    your UPS is set upcorrectly to report available run time when used with external battery cabinets.

    Liebert® GXT5 | Brochure

  • 14

    Higher uptime with optional POD configuration

    When your computer system can not be without power, even for scheduled UPS maintenance, the Liebert MicroPOD Maintenance Bypass and Output Distribution Unit ensures continuous uptime. It allows you to manually transfer connected equipment to utility power via a maintenance bypass switch, permitting scheduled service or UPS replacement without the need to shut down connected equipment.

    Features include:

    2U height minimizes rack space requirements

    Easy plug-and-play installation

    Liebert GXT5 is Powered by All New RDU101

    The Powerful Future-ready Communication Tool

    Provides web access to the installed devices via popular webbrowsers - IE12 and later, Mozilla Firefox, Google Chrome andSafari.

    messaging.

    Supports environmental monitoring via Liebert SN Sensors fortemperature, humidity, leak detection, doors and contactclosures.

    Supports third-party protocols for building and networkmanagement applications for status and alarms (SNMP only).

    Enables Vertiv software tools and services, including Trellis™Enterprise, Trellis™ Power Insight and Vertiv™ LIFE™ Service.

    Provides a direct, high-speed USB connection to managed

    HTTPS messages and web access encryption with installable

    Options for SNMP v3 authentication support (none, MD5 orSHA), privacy support (none, DES or AES) and Traps.

    Warranty

    GXT5 comes with three years of standard warranty and an option for one or two-years warranty extension.

    Start-up

    Hassle-free multi-site deployment

    in the disposal of hazardous materials of existing UPS, when applicable.

    Preventive maintenance

    To increase equipment reliability thus higher availability.

    On-site service

    Should you experience a problem, we

    Customer Engineer to repair or replace your equipment, response guaranteed.

    POD configuration with UPS

    POWER SOURCE

    LOAD EQUIPMENT

    UPS

    Mirco POD

    Liebert MicroPOD

    Liebert® GXT5 | Brochure

  • 15

    Internal Battery

    CAPACITY 750W 1000W 1500W 2000W 3000W

    10% 107.3

    20% 50.1 36.2 36.7

    30% 33.7 32.7

    40% 33.7 22.2

    50% 25.7 16.3 10.7

    60% 12.7

    70% 16.7 11.5 10.1 6.3

    80% 5.0 5.1

    90% 12.1 6.7

    100% 10.5 5.6 3.2 3.3

    Internal Battery + 1 External Battery Cabinet

    CAPACITY 750W 1000W 1500W 2000W 3000W

    10% 332.7 350.3 260.2

    20% 136.3

    30% 163.7 127.1

    40% 127.1 63.1 63.3

    50% 103.2 76.3 70.2

    60% 55.1

    70% 72.0 50.7 31.0

    80% 26.2

    90% 53.0 32.7 22.0

    100% 33.3

    Internal Battery + 2 External Battery Cabinet

    CAPACITY 750W 1000W 1500W 2000W 3000W

    10% 612.3

    20% 325.3 231.0 233.3

    30% 213.1 156.6 157.2

    40% 116.1

    50% 135.1 125.3

    60% 112.1 103.5 73.5

    70%

    80% 112.1 50.1 50.6

    90% 73.0 61.7

    100%

    Internal Battery + 3 External Battery Cabinet

    CAPACITY 750W 1000W 1500W 2000W 3000W

    10% 650.5

    20%

    30% 316.1 223.1

    40% 316.1 167.7

    50% 132.6

    60% 161.6

    70% 125.6

    80% 161.6

    90% 66.5 67.6

    100% 130.2 57.1

    Internal Battery + 4 External Battery Cabinet

    CAPACITY 750W 1000W 1500W 2000W 3000W

    10% 1173.2

    20% 760.5

    30%

    40% 217.3

    50% 337.1 172.7 173.6

    60%

    70% 165.6

    80% 160.1

    90%

    100% 125.7 111.2

    Internal Battery + 5 External Battery Cabinet

    CAPACITY 750W 1000W 1500W 2000W 3000W

    10% 1373.2

    20% 736.7 550.0 556.0

    30% 367.6

    40% 270.3

    50% 211.1 212.5

    60% 350.0 260.6 177.1

    70%

    80% 260.6 176.3

    90% 232.1 113.0

    100% 156.3 101.6

    UPS Rear Ranel and Battery Runtime Chart

    Battery Run-time Chart (in min)

    750 VA / 1 KVA UPS Rear Panel 3 KVA UPS Rear Panel

    Liebert IntelliSlot port

    Non-programmable C13 output receptacles

    External battery connector

    RJ45USB Port

    RJ45/ RJ11

    Input circuit breaker reset button, 20A

    Terminal block

    Liebert IntelliSlot port External battery

    connector

    Input circuit breaker reset button, 10A

    Programmable C13 output receptacles

    USB Port

    RJ45 RJ45/ RJ11

    C14 input power pulg and cable

    Non-programmable C13 output receptacles

    Terminal block

    C20 Input power plug and cable

    Output circuit breaker reset button, 10A

    Non - programmable C19 output receptacles

    Programmable C13 output receptacles

    Liebert® GXT5 | Brochure

  • 16

    Technical Specifications

    Model Number GXT5-750IRT2UXL GXT5-1000IRT2UXL GXT5-1500IRT2UXL GXT5-2000IRT2UXL GXT5-3000IRT2UXL

    Ratings (VA/W ) 750 VA / 750 W 1000 VA / 1000 W 1500 VA / 1500 W 2000 VA / 2000 W 3000 VA / 3000W

    Dimensions and Weight

    Dimensions (mm) Unit, W×D×H

    Unit Weight (kg) 16.5 21

    Input

    Rated Volatge 230 VAC

    Rated Frequency 50 Hz / 60 Hz

    Frequency Range

    Power Factor

    Output

    Nominal Voltage

    Waveform Sine wave

    Inverter Overload Capability;

    60 seconds 2 seconds;

    Inverter Bypass

    Output Receptacles

    Internal Battery

    Rated Voltage 36 Vdc 72 Vdc

    Charger Current

    Type Valve-regulated, non-spillable, lead acid

    Qty x V x Rating

    End Cell Voltage

    Floating Voltage

    Battery Voltage Range

    General

    Operating Temperature

    Storage Temperature, °C

    Relative Humidity

    Operating Elevation Up to 3,000 m at 25°C without derating

    Audible Noise(1 m) front and

    Safety

    RFI/EMI CISPR22 Class A (RFI) / FCC Part 15 (Class A)

    Transportation ISTA Procedure 1A

    Note: *Specification are subject to change without any further notification

    **Battery autonomy times are based on operation at 25°C. The autonomy times are approximate and are based on fully charged batteries and can vary +/-5% because of battery manufacturing variances.

    Liebert® GXT5 | Brochure

  • 17

    Liebert® GXT5™

    GUIDE SPECIFICATIONS

    1.0 GENERAL

    Liebert® GXT5 | Guide Specifications

  • 18

    A.

    B.

    C.

    D.

    E.

    Liebert® GXT5 | Guide Specifications

  • 19

    Liebert® GXT5 | Guide Specifications

  • 20

    Liebert® GXT5 | Guide Specifications

  • 21

    Liebert® GXT5 | Guide Specifications

  • 22

    Liebert® GXT5 | Guide Specifications

  • 23

    2.0 PRODUCT

    Liebert® GXT5 | Guide Specifications

  • 24

    Liebert® GXT5 | Guide Specifications

  • 25

    Liebert® GXT5 | Guide Specifications

  • 26

    Liebert® GXT5 | Guide Specifications

  • 27

    Liebert® GXT5 | Guide Specifications

  • 28

    Liebert® GXT5 | Guide Specifications

  • 29

    Liebert® GXT5 | Guide Specifications

  • 30

    Liebert® GXT5 | Guide Specifications

  • 31

    Liebert® GXT5 | Guide Specifications

  • 32

    Liebert® GXT5 | Installation Size

  • 33

    Liebert® GXT RT+

    Essential, Aff ordable UPS for High Performance Protection

    1000 - 3000 VA 230 V

  • 34

    The Vertiv™ Liebert® GXT RT+ UPS is an online double conversion solution which offers power protection in an affordable, efficient system with deployment and operation flexibility.

    The high 0.9 power factor of the single-phase Liebert GXT RT+ enables continuous, reliable power to more connected devices from a wide range of input voltages while being energy efficient and, delivering maximum value.

    The ECO mode of operation for this already affordable UPS also drives energy cost savings for a compelling total cost of ownership (TCO).

    Being able to mount the Liebert GXT RT+ in a rack or tower is a convenience that adds to the value story as does the capability of the UPS to utilize up to six connected external battery cabinets for scalable runtimes.

    In addition to the extended runtime, having multiple monitoring options makes this compact UPS ideal for delivering best-in-class power protection to equipment deployed at the edge of networks or in space-constrained facilities.

    Liebert GXT RT+ Features

    Online technology with two stages of power conversion

    Output power factor higher than majority of comparable competitor models

    Flexible rack/tower form factor

    External battery cabinet compatibility

    User-friendly liquid crystal display (LCD)

    High efficiency ECO mode

    Smart battery charger design

    Wide input voltage operation (120-300V AC)

    UPS

    Rack Mounting Kit

    USB Cable

    Monitoring Software CD

    Quick Installation Guide

    Safety Instructions

    Input and Output Power Cables (Based on Power Rating)

    Plastic Tower Mounting Feet

    Rack Ears, Screws and Hardware

    What’s in the box?

    Liebert® GXT RT+ | Brochure

    Liebert® GXT RT+ | Brochure

  • 35

    Vertiv™ Liebert® GXT RT+ UPS

    Vertiv™ Liebert® GXT RT+ UPS Features and Benefits

    High power factor (0.9)More usable power enables more connected loads for space and cost savings.

    High efficiency ECO modeConfigurable operation mode for up to 95% efficiency helps toachieve energy savings and a lower TCO.

    ECO

    External battery cabinet capabilityConnected modules enable scalable runtime during failure of main utility power.

    Compact, flexible form factorOption of rack or tower mounting supports simplified UPS selection and deployment.

    User-friendly interfaceIntuitive LCD provides complete UPS status and configuration information at a glance.

    LCD

    Monitoring compatibilityNetwork interface or serial connections enable remote access to UPS for power consumption monitoring and configuration of alert notification parameters.

    Note: Front panel is the same for all power ratings while rear panels will vary. Shown here is a 3 kVA model.

    Liebert® GXT RT+ | Brochure

    Liebert® GXT RT+ | Brochure

  • 36

    Accessories

    Optional Connectivity Cards

    Webcards/SNMP devices enable direct connection to the internet and use of a standard web browser for power monitoring and management including controlled shutdown for multiple computer systems. Volt free contact (VFC) cards are available for applications requiring this type of monitoring.

    External Battery Modules

    Modules connected to new or existing deployments ensure reliable power and protection and enable scalable runtime for support during extended power outage situations.

    Liebert® MicroPOD Maintenance Bypass

    A 2U rack-mounted installation, available in several receptacle combinations, allows manual transfer of connected equipment to utility power ensuring network availability and business continuity during scheduled service or UPS replacement.

    IT

    ServersNetworking equipmentData storage

    Education

    Networking closetsNetworking equipmentOffice protection

    Finance

    Branch officesClosed-circuit televisions and data protectionATMs

    Government

    Distributed officesClosed-circuit television (CCTV) and data protectionSmall server and storage rooms

    Telecom

    5G mobile stationsAccess and “last mile”Small control rooms

    Industrial

    Manufacturing sitesControl equipment and programmable logic controllers (PLCs)Data and networking equipment

    Retail

    Several point of sale systemsNetworking and wiring closetsSecurity and voice over internet protocol (VoIP) telephony

    Edge

    Distributed cloud servicesContent providersSensors and data stations

    Key Applications

    Liebert® GXT RT+ | Brochure

    Liebert® GXT RT+ | Brochure

  • 37

    Vertiv™ Liebert® GXT RT+ UPS

    Technical SpecificationsGXTRT-1000IRT2UXL GXTRT-1500IRT2UXL GXTRT-2000IRT2UXL GXTRT-3000IRT2UXL

    Ratings (VA/W) 1000/900 1500/1350 2000/1800 3000/2700

    Dimensions, Millimeters

    Unit W x D x H 438 x 310 x 88 438 x 462 x 88 438 x 462 x 88 438 x 632 x 88

    Weight, KilogramsUnit 11 14.5 18.2 27.6

    Input AC Parameters*Nominal Voltage 230 VAC 230 VAC 230 VAC 230 VAC

    Range 120-300 VAC 120-300 VAC 120-300 VAC 120-300 VAC

    Frequency 40-70 Hz 40-70 Hz 40-70 Hz 40-70 Hz

    Input Power connector IEC60320 C14 IEC60320 C14 IEC60320 C14 IEC60320 C20

    Output AC Parameters

    Output Receptacles IEC60320 C13 x 6 IEC60320 C13 x 6 IEC60320 C13 x 6IEC60320 C13 x 6 IEC60320 C19 x1

    Output Voltage & Regulation (230V Typical, User Selectable)

    220/230/240 VAC ±1%

    220/230/240 VAC ±1%

    220/230/240 VAC ±1%

    220/230/240 VAC ±1%

    Waveform Sine wave Sine wave Sine wave Sine wave

    Utility (AC) Mode Overload

  • 38

    A.

    B.

    C.

    When used external battery cabinets, runtime is limited if the UPS output load is ≥70%. Please check runtime tables for details.

    External Battery CabinetsGXTRT-EBC24VRT2U GXTRT-EBC36VRT2U GXTRT-EBC48VRT2U GXTRT-EBC72VRT2U

    Unit W x D x H 438 x 410 x 88 438 x 410 x 88 438 x 510 x 88 438 x 630 x 88

    Weight 12.5 17.2 23.2 41.5

    Internal Batteries 2 x 2 x 12 V x 9 Ah 2 x 3 x 12 V x 9 Ah 2 x 4 x 12 V x 9 Ah 2 x 6 x 12 V x 9 Ah

    Compliance CE CE CE CE

    Monitoring Cards

    Network Communications

    GXT-MTPLUSAS400 AS400 card for GXT-MTPLUS

    WEBPROCARD SNMP Management Card for GXT-MTPLUS with FREE centralized monitoring software

    Battery Runtime Table

    UPS EBCRUN TIME IN MIN /LOAD

    25% 50% 69% 75% 80% 90% 100%

    1000VA

    Internal 19 9 5.3 5 3.5 3.5 3.1

    1 69 38 26 10 3.5 3.5 3.5

    2 129 70 48 10 3.5 3.5 3.5

    3 184 103 72 10 3.5 3.5 3.5

    4 240 139 95 10 3.5 3.5 3.5

    5 291 176 120 10 3.5 3.5 3.5

    6 335 213 145 10 3.5 3.5 3.5

    1500VA

    Internal 21 9 5.5 5.2 3.5 3.5 3.2

    1 76 38.5 26.2 10 3.5 3.5 3.5

    2 143 72 48 10 3.5 3.5 3.5

    3 203 106 72 10 3.5 3.5 3.5

    4 261 143 97 10 3.5 3.5 3.5

    5 321 180 123 10 3.5 3.5 3.5

    6 380 215 150 10 3.5 3.5 3.5

    2000VA

    Internal 23 9 5.7 6 3.5 3.5 3.2

    1 85 39 27 10 3.5 3.5 3.5

    2 159 73 50 10 3.5 3.5 3.5

    3 228 111 77 10 3.5 3.5 3.5

    4 300 151 104 10 3.5 3.5 3.5

    5 364 188 132 10 3.5 3.5 3.5

    6 423 225 160 10 3.5 3.5 3.5

    3000VA

    Internal 26 10.5 5.8 6 3.5 3.5 3.3

    1 95 42 28 10 3.5 3.5 3.5

    2 168 78 52 10 3.5 3.5 3.5

    3 242 115 79 10 3.5 3.5 3.5

    4 312 155 107 10 3.5 3.5 3.5

    5 380 195 136 10 3.5 3.5 3.5

    6 443 234 165 10 3.5 3.5 3.5

    Liebert® GXT RT+ | Brochure

    Liebert® GXT RT+ | Brochure

  • 39

    Liebert® GXT RT+1000-3000VA

    Rack-Tower 230V IEC typeGUIDE SPECIFICATIONS

    1.0 GENERAL

    1.1 SUMMARYThis specification shall define the electrical and mechanical characteristics and requirements for a continuous-duty, single-phase, on-line double conversion, solid-state uninterruptible power system (UPS). The UPS shall provide high-quality AC power for sensitive electronic equipment loads.

    1.2 STANDARDSThe UPS shall be designed in accordance with applicable sections of the current revision of the following documents. Where a conflict arises between these documents and statements made herein, the statements in this specification shall govern.

    SSAFETYY CE MARK; IEC/EN 62040-1: 2014

    RRFI/EMI IEC/EN 62040-2:2006+AC:2006SSURGEE IMMUNITYY EN 61000-4-5: 2005

    TTRANSPORTATION ISTA 2A

    The Quality management grade pertaining to the engineering and manufacturing facility is certificated to conform to the ISO 9001 international standards, specifically catering to the design and production of power protection systems for computers and other sensitive electronic devices.

    1.3 SYSTEM DESCRIPTION

    1.3.1 Modes of OperationThe UPS shall be designed to operate as a true on-line double conversion system in the following modes:AA. Normal - In normal operation incoming AC power shall be fed to the input power factor

    corrected (PFC) rectifier that converts the AC power to DC power for the inverter. In thismode, power shall also be derived from utility power for the battery charger. The inverter shallderive DC power from the PFC rectifier to regenerate filtered and regulated AC sinewavepower for the connected load. The unit shall begin charging the battery once the UPS isconnected to utility power, regardless of whether the UPS is ON or OFF. In the event of autility outage or severe abnormality (sag or swell), the inverter shall support the connectedload from battery power until the battery is discharged or the utility power returns, whicheveroccurs first.

    BB. Battery - Upon failure of utility / mains AC power, the critical AC load shall be supplied bythe inverter, which obtains power from the battery. There shall be no interruption in power tothe critical load upon failure or restoration of the utility / mains AC source.

    CC. Recharge - Upon restoration of utility / mains AC power, after a utility / mains AC poweroutage, the input converter shall automatically restart and resume supplying power to theinverter and the battery charger to recharge the battery.

    Liebert® GXT RT+ | Guide Specifications

    Liebert® GXT RT+ | Guide Specifications

  • 40

    D. Automatic Restart - Upon restoration of utility / mains AC power, after a utility / mains ACpower outage and complete battery discharge, the UPS shall automatically restart andresume supplying power to the critical load and the battery charger automatically rechargesthe battery. This feature shall be capable of being disabled by the user.

    EE. Bypass - The integral bypass shall perform an automatic transfer of the critical AC load fromthe inverter to the bypass source, in the event of an overload, PFC failure, internal overtemperature, DC bus overvoltage or inverter failure conditions.

    F. ECO – The UPS shall allow the user to enable and place the UPS in ECO mode of operationto reduce electrical consumption.

    1.3.2 Design RequirementsA. VoltageInput/output voltage specifications of the UPS shall be:

    Input: 120 - 300VAC, 50/60Hz, single-phase, 2-wire-plus-earth.Output: 230VAC default (user configurable: 220V, 230V, 240V) ±1%, 50/60Hz, single-phase,2-wire-plus-earth.

    B. Output Load CapacitySpecified output load capacity of the UPS shall be:

    1000VA/900 Watts at 0.9 power factor.1500VA/1350 Watts at 0.9 power factor.2000VA/1800 Watts at 0.9 power factor.3000VA/2700 Watts at 0.9 power factor.

    C. Internal BatteryThe UPS shall utilize valve-regulated, non-spillable, lead acid cells.D. Reserve Time (with internal battery)

    1000VA: 3 minutes1500VA: 3 minutes2000VA: 3 minutes3000VA: 3 minutes

    These times shall be at full load (PF=0.9)) with ambient temperature of 77°F (25°C) with resistive loading and internal batteries fully recharged. E. Battery RechargeThe UPS shall contain an internal battery charger designed to prolong battery life. Recharge timefor UPS internal batteries shall be 4 hours to 90% capacity (internal batteries) after a completedischarge with full load connected.

    1.3.3 Performance RequirementsThe solid-state power components, magnetic, electronic devices and over current protection devices will operate within the manufacturer’s recommended temperature when the UPS is operating at 100% critical load and maintain battery charging under either of the following conditions:

    Any altitude within the specified operating range ≤2000m elevation.Any ambient temperature within the specified operating range of 0°C to 40°C

    Liebert® GXT RT+ | Guide Specifications

    Liebert® GXT RT+ | Guide Specifications

  • 41

    E.

    1.3.3.1 AC Input to UPSA. Voltage ConfigurationThe UPS shall incorporate a variable input voltage (low line transfer) window feature that shall operate at the values in the following table, without drawing power from the batteries.

    Load Level 230 VAC

    Input Voltage

  • 42

    1.3.3.2 AC Output, UPS InverterVoltage Configuration

    230VAC default, 50/60Hz, single-phase, 2-wire-plus-earth, LCD or configuration programselectable (220V, 230V, 240V).

    Voltage Regulation

    Frequency Regulation

    Frequency Slew Rate

    Voltage Distortion

    Output Power Rating

    UPS will show power derating to 70% for operation in frequency converter mode.G. Inverter Overload Capability

    Nominal output voltage Overload capability

    230V AC

    130% transfer to bypass after 3 seconds

    For either VA or W detection. Warning and transfer to bypass in the periods described.For on-line or battery mode operation. Assuming ambient temperature

  • 43

    1.4 ENVIRONMENTAL CONDITIONSA. Ambient TemperatureOOperating: The ambient temperature range, when UPS is operational, shall be from 0 – 40ºC.There shall not be any degradation in the performance when operating in this range. Automaticderating shall occur for operation in higher ambient temperatures based on the following table.

    Ambient Temperature 0 – 40ºC 41ºC – 50ºCMaximum output load (for nominal conditions) 100% load 70% derating

    Relative Humidity

    Altitude

    D. Audible Noise

    1.5 USER DOCUMENTATION AND ITEMS BUNDLEDThe specified UPS system shall be supplied with a Safety Instruction & Quick Installation Guide (QIG) for ease of installation and UPS start up. A full user manual will be available for download from a website. The user manual shall include installation instructions, a functional description of the equipment with block diagrams, safety precautions, illustrations, step-by-step operating procedures and general maintenance guidelines. The included CD will shall also include a SW program (or download) to allow user customization of UPS operating parameters and UPS local port monitoring and computer/server shutdown. It will include plastic feet for mounting in tower form factor, as well as rail kit for rack mounting.

    1.6 WARRANTYThe UPS manufacturer shall warrant the UPS against defects in materials and workmanship for two (2) years. The no-hassle replacement warranty shall include shipping costs to the customer site for the new replacement. Optional one (1) and three (3) year full coverage extension warranties shall be available from the manufacturer (depending on country).

    Liebert® GXT RT+ | Guide Specifications

    Liebert® GXT RT+ | Guide Specifications

  • 44

    1.7 QUALITY ASSURANCE

    1.7.1 Manufacturer QualificationsMore than 40 years of experience in the design, manufacture, and testing of solid-state UPS systems shall be required. The manufacturer shall be quality certified to ISO 9001:2015 (or applicable).

    1.7.2 Factory TestingBefore shipment, the manufacturer shall fully and completely test the system to ensure compliance with the specification.

    Liebert® GXT RT+ | Guide Specifications

    Liebert® GXT RT+ | Guide Specifications

  • 45

    2.0 PRODUCT2.1 FABRICATION

    All materials and components making up the UPS shall be new, of current manufacture and shall not have been in prior service except as required during factory testing.

    2.1.1 WiringWiring practices, materials and coding shall be in accordance with the requirements the standards listed in Section 1.2 and other applicable codes and standards. All wiring shall be copper.

    2.1.2 CabinetThe UPS unit shall be composed of: input PFC converter, IGBT inverter, battery charger, input filter and internal bypass circuit; and batteries consisting of the appropriate number of sealed battery cells; and shall be housed in a rack-tower enclosure and shall meet the requirements of IP20. The UPS cabinet shall be cleaned, primed and painted RAL 7021 Black. Unit dimensions and weights shall be (rack mount orientation):

    UPS rating DimensionsD x W x H (mm)Weight(kgs.)

    1000VA 312 x 438 x 88 11.01500VA 462 x 438 x 88 14.5 2000VA 18.23000VA 632 x 438 x 88 27.6

    The UPS shall be able for mounting in rack or in tower form factor, using the accessories that may be required.

    2.1.3 Matching Battery CabinetsThe optional Rack-Tower battery cabinet shall contain valve-regulated, non-spill able, lead acid cells, housed in a separate cabinet that matches the UPS cabinet styling. The cabinet shall be cleaned and painted Black RAL 7021. The external battery system shall be sized to provide an additional reserve power specified in section 1.3.2 to the load. The matching battery cabinet shall include detachable, molded interconnect cable, circuit breaker over current protection and provisions for daisy-chain connection of additional battery cabinets. The dimensions and weight information of each optional external battery cabinet shall not exceed below values.

    UPS ratingCompatible External

    Battery Cabinet Dimensions

    D x W x H (mm)

    Weight(kgs.)

    1000VA 410 x 438 x 88 12.51500VA 410 x 438 x 88 17.22000VA 510 x 438 x 88 23.23000VA 632 x 438 x 88 41.5

    Liebert® GXT RT+ | Guide Specifications

    Liebert® GXT RT+ | Guide Specifications

  • 46

    2.1.4 CoolingThe UPS shall be forced-air cooled by an internally mounted, continuously operating fan and variable speed depending on the load conditions. Fan power shall be provided from the internal DC supply. Air intake shall be through the front of the unit and exhausted out the rear of the unit.

    2.2 COMPONENTS

    2.2.1 Input Converter2.2.1.1 General

    Incoming AC power shall be converted to a regulated DC output by the input converter supplying DC power to the inverter. The input converter shall provide input power factor correction (PFC) and input current distortion reduction.

    2.2.1.2 Input ProtectionThe UPS shall have built-in protection against under voltage, over current and overvoltage conditions including low-energy lightning surges, introduced on the primary AC source. The UPS shall have resettable input circuit breakers.

    2.2.1.3 Battery RechargeThe UPS shall contain an internal battery charger designed to prolong battery life. Recharge time for the internal UPS batteries shall be 4 hours to 90% capacity (full load discharge rate, internal batteries). There shall be DC overvoltage protection so that if the DC voltage exceeds the pre-set limit, the UPS will shut down automatically and the critical load will be transferred to bypass.

    2.2.2 Inverter 2.2.2.1 General

    The UPS inverter shall be a pulse-width-modulated (PWM) design capable of providing the specified AC output. The inverter shall convert DC power from the input converter output or the battery into precise sinewave AC power for supporting the critical AC load.

    2.2.2.2 OverloadThe inverter shall be capable of supplying current and voltage for overloads exceeding 100% and up to 130% of full load current. A visual indicator and audible alarm shall indicate overload operation. For greater currents or longer time duration, the inverter shall have electronic current-limiting protection to prevent damage to components. The inverter shall be self-protecting against any magnitude of connected output overload. Inverter control logic shall sense and disconnect the inverter from the critical AC load without the requirement to clear protective devices.

    2.2.2.3 Output FrequencyAn oscillator shall control the output frequency of the UPS. The inverter shall maintain the output frequency to ±0.5% of nominal frequency during Battery mode, Frequency Converter mode or when otherwise not synchronized to the utility/mains source.

    2.2.2.4 Output ProtectionThe UPS inverter shall employ electronic current limiting circuitry.

    Liebert® GXT RT+ | Guide Specifications

    Liebert® GXT RT+ | Guide Specifications

  • 47

    2.2.2.5 Battery Over Discharge ProtectionTo prevent battery damage from over discharging, the UPS control logic shall automatically raise the shutdown voltage set point; depending on output load and connected battery system at the onset of battery operation.

    2.2.3 Display and Controls2.2.3.1 General

    The UPS shall be provided with a microprocessor-based unit status display and controls section designed for convenient and reliable user operation. The monitoring functions such as voltages, currents, UPS status and alarm indicators shall be displayed on an LCD display.

    2.2.3.2 ControlsUPS startup and shutdown operations shall be accomplished by using push buttons on the front panel of the UPS. The display shall use three control buttons for ease of navigation and selection of the configurable parameters.

    2.2.3.2.1 Control ButtonsThe UPS display control button functionality shall be as followsON / Mute button:

    Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn on the UPS.Mute the alarm: When the UPS is on battery mode, press and hold this button for at least 5seconds to disable or enable the alarm system. But it will be automatically enable when nextwarnings or errors occur.Up key: Press this button to display previous selection in UPS setting mode.Switch to UPS self-test mode: Press and hold ON/Mute button for 5 seconds to enter UPSself-testing while in AC mode, ECO mode, or converter mode.

    OFF / Enter button: Turn off the UPS: Press and hold this button at least 2 seconds to turn off the UPS. UPS will bein standby mode under power normal or transfer to Bypass mode if the Bypass enable settingby pressing this button.Confirm selection key: Press this button to confirm selection in UPS setting mode.

    Select button: Switch LCD message: Press this button to change the LCD message for input voltage, inputfrequency, battery voltage, output voltage and output frequency.Setting mode: Press and hold this button for 5 seconds to enter UPS setting mode when UPSis in standby mode or bypass mode.Down key: Press this button to display next selection in UPS setting mode.

    ON/Mute + Select buttons: Switch to bypass mode: When the main power is normal, press ON/Mute and Select buttonssimultaneously for 5 seconds. Then UPS will enter to bypass mode. This action will beineffective when the input voltage is out of acceptable range.

    Liebert® GXT RT+ | Guide Specifications

    Liebert® GXT RT+ | Guide Specifications

  • 48

    2.2.3.2.2 Display and System IndicatorsThe UPS display will include company brand and it show the relevant UPS status information, including the following points:

    Load informationOperation mode information (on-line, bypass, ECO, battery, etc)Warning indicator and fault informationMost relevant UPS information (input voltage, output voltage, frequency, etc)Battery informationRemaining backup time

    2.2.3.2.3 Alarms/warning

    Low batteryOverloadBattery is not connectedOverchargeCharger failureBattery faultBypass voltage rangeBypass frequency unstableEEPROM error

    2.2.3.2.4 Configuration

    Output voltage settingFrequency converter enable/disableOutput frequency settingECO enable/disableBypass enable/disable when UPS is offBackup time settingsBattery total AH setting

    A bypass circuit shall be provided as an integral part of the UPS. The bypass control logic shall contain an automatic transfer control circuit that senses the status of the inverter logic signals and operating and alarms conditions. This control circuit shall provide a transfer of the load to the bypass source if available and if the inverter is not capable of powering the load (i.e., if there is an overload condition, if the unit is in Manual Bypass mode or if the voltage or frequency is out of tolerance).

    Liebert® GXT RT+ | Guide Specifications

    Liebert® GXT RT+ | Guide Specifications

  • 49

    The transfer control logic shall activate the bypass automatically, transferring the critical AC load to the bypass source, after the transfer logic senses one of the following conditions:

    UPS overloadUPS over temperaturePFC failureInverter failure

    Once the overload condition is reduced, the load shall be automatically transferred back to inverter power.

    2.2.5 Internal BatteryValve-regulated, non-spillable, lead acid cells (VRLA) shall be used as a stored-energy source for the specified UPS system. The battery shall be housed internal to the UPS cabinet and sized to support the inverter at rated load and power factor, with ambient temperature of 25°C (77°F) for a minimum of 3 minutes reserve time. The expected life of the battery shall be 3-5 years. The UPS units have the capability to allow the operator to replace the internal battery (user replaceable) online without shutting down the UPS system or connected loads. All UPS models shall allow connection of up to six external battery cabinets to provide extended run time capability. External battery cabinets shall match the UPS in aesthetics and color.

    The UPS shall feature an automatic battery test with the factory default test interval set at every eight weeks. The battery test shall ensure the capability of the battery to supply power to the inverter while loaded. If the battery fails the test, the UPS shall display a warning message to indicate the internal batteries need to be replaced. The battery test feature shall be user accessible by the push button on the front of the unit and with communication software.

    2.3 OUTPUT DISTRIBUTIONOutput distribution shall be integral to the UPS and located on the rear of the unit, according to the following description.

    UPS rating Output power sockets1000VA (6) EN60320-C131500VA (6) EN60320-C132000VA (6) EN60320-C133000VA (6) EN60320-C13(1) EN60320-C19

    The UPS shall include one (x1) communication port to allow the user to field-install an optional communication card. A Vertiv interface card may be installed during any state of UPS operation (On, Standby or Off states). Available Vertiv optional cards are described below:

    Vertiv Web CardThe optional Vertiv Web Card shall deliver SNMP and Web management to the UPS when connected to any 10 or 100 Mbit Ethernet network.

    Liebert® GXT RT+ | Guide Specifications

    Liebert® GXT RT+ | Guide Specifications

  • 50

    Vertiv Dry-contacts (relay) CardThe optional Vertiv Dry-contacts (relay) card shall provide contact closure for remote monitoring of alarm conditions in the UPS, delivering signals for On Battery (Utility failure), Bypass Active, Low Battery, UPS Fault and On UPS. The contacts shall be rated for 24VDC at 1A. Connections shall be to a DB9 female connector with cable provided by the end user.

    The USB port shall allow connection to a computer to use with a monitoring and shutdown software and for use with the UPS configuration program.

    serial port shall be made available with a DB9F connector on the rear of the UPS. This connector shall communicate with a monitoring and shutdown software for use with the UPS configuration program.

    Liebert® GXT RT+ | Guide Specifications

    Liebert® GXT RT+ | Guide Specifications

  • 51

    Vertiv™ EDGE UPS

    Superior Power Protection for Edge Applications

    500 - 3000 VA 230 V

  • 52

    Vertiv™ EDGE UPS

    The Vertiv™ EDGE UPS: Best-in-class battery backup and power protection for server, networking and EDGE applications.

    Vertiv™ EDGE is a family of highly reliable, efficient, manageable and flexible line interactive sinewave UPSs, with models ranging from 500VA to 3000VA in mini-tower, rack/tower and rack-mount form factors. With a 0.9 power factor, controllable outlets and extended runtime options, Vertiv EDGE is the right choice for protecting server and networking equipment in distributed and EDGE IT applications. Available in 1U and 2U options as well as a short-depth 3U 3000VA model, it can provide optimum runtime at the right size and power density in a cost effective UPS solution.

    Vertiv EDGE

    Reliable and powerful: 0.9 output power factor, ensuring more active power to protect larger loads

    Up to 6 auto-discoverable extended run battery cabinets for longer runtime

    Highly efficient: up to 98% in normal operation mode, providing energy and cost savings

    Up to 10 power outlets, with 3 controllable in a group for optimum battery usage

    Color graphic LCD display

    Advanced AVR design for a more stable output voltage regulation

    Standard 2-year warranty for both electronics and batteries

    At a Glance

    Compact Mini Tower design for tower servers and/or applications with no available rack

    Plug and play solution requiring no installation

    Vertiv™ Intellislot SNMP/Webcards available for remote power management and OS’s shutdown

    Compact 1U Rack Mount design for EDGE applications with limited rack space

    Comes with rack mounting hardware included

    Vertiv Intellislot SNMP/Webcards available for remote power management and OS’s shutdown

    Convertible rack/tower design with LCD display provides flexible installation options

    Extended runtime capability with external battery cabinets with autodetection, for hours of back-up time

    3000VA 3Us height with short depth (

  • 53

    External battery cabinetsThe Rack/Tower models allow longer runtimes thanks to the battery cabinets with auto-detection

    Efficiency up to 98%High efficiency in normal

    operation mode means an optimized energy

    management, thus providing energy savings

    High output power factor (0.9)It enables EDGE UPS to protect more loads and save space

    Flexibility Easy to install and a wide range of power

    ratings, from 500VA up to 3000VA, available in

    multiple form factors: mini-tower, 1U rack and

    rack/tower

    Leading technologyAdvanced AVR

    design (2 x boost / 1 buck taps) for a

    more stable output voltage regulation

    LCD displayColor and graphic LCD display for an intuitive user interface

    0.9PF

    Controllable outletsThe group of controllable outlets allows a power control of the load, helping to achieve longer runtime

    Vertiv™ EDGE Highlights

    LCDCOLOR

    EDGE UPS | Brochure

    Vertiv™ EDGE UPS | Brochure

  • 54

    Vertiv™ EDGE UPS

    UPS Unit

    USB Cable

    Printed Quick Installation and Guide Safety instructions

    Adjustable 4-post rack mounting kit (not included with Mini Tower)

    Support base for tower configuration (Rack/Tower Models Only)

    Power Assist software (free download from Vertiv.com)

    Input and output power cables (depending on rating and model type)

    What's in the boxReliable UPS Protection At The All-Important Network Edge

    The network edge is becoming increasingly important as companies seek to take advantage of Internet of Things, cloud computing and other applications that require localized compute power, networking services and data storage – all with low latency. Distributed and edge data centers are now no less important to business success than large centralized data centers, so must be afforded similar power protection.

    The Vertiv™ EDGE line interactive UPS family is intended for distributed IT and edge applications that require reliable, efficient power protection for server and networking equipment. It comes in mini-tower, rack tower and rack-mount form factors, with capacities ranging from 500VA to 3000VA. Each model has a 0.9 output power factor (PF), enabling them to protect larger loads than competing models of the same capacity.

    Vertiv EDGE UPSs support up to 6 extended-run battery cabinets (EBCs), providing more runtime at full load than comparable competing UPSs. Auto-detect features make the EBCs easy to add and configure.

    Vertiv EDGE UPSs are also highly manageable, with a colorful, graphical LCD screen for easy, intuitive on-site management, as well as optional SNMP support. Vertiv EDGE is compatible with the free Vertiv Power Assist software for local UPS status and shutdown of IT loads connected locally.

    A standard 2-year warranty for both electronics and batteries protects your UPS investment.

    Vertiv EDGE 1500VA Tower UPS

    Vertiv EDGE 1500VA 2Us Rack/Tower UPS

    Vertiv EDGE 3000VA 3Us Rack/Tower UPS

    Vertiv EDGE 1000VA 1U Rack UPS

    1. USB Port

    2. Output receptacles

    3. Programmable output group

    4. Input power socket

    5. Input circuit breaker

    6. Emergency Power Off (EPO) connector

    7. Intellislot® Port for optional cards

    8. Earth terminal

    9. Extended runtime battery connection

    10. Automatic battery detection terminal

    1

    1

    4

    4

    9

    9

    10

    10

    8

    8

    5

    5

    3

    3

    2

    2

    6

    6

    7

    7

    7

    EDGE UPS | Brochure

    Vertiv™ EDGE UPS | Brochure

  • 55

    Efficient & Green

    Maximize Power Protection

    Flexibility and Manageability

    High output PF: Each Vertiv EDGE UPS operates at 0.9 output power factor (PF), which means that more active power can be used to protect IT equipment. That enables Vertiv EDGE UPSs to protect larger loads compared to competing models of the same capacity with a lower PF.

    Advanced AVR design: Automatic voltage regulation smooths out power spikes, swells and brownouts without the UPS switching to battery mode and help to extend battery life. The advanced design with 2 x boost / 1 x buck increases or decreases voltages as required to prevent the load from extreme supply voltages.

    High temperature operation: Vertiv EDGE UPSs can operate at up to 40ºC at full power, and higher ambient temperature with derating applied.

    High efficiency: Vertiv™ EDGE UPSs operate at up to 98% efficiency in normal operation mode, saving on electricity costs throughout their lifetime.

    Extended battery life: Deep discharge protection prevents the potential damage that can occur when a UPS battery fully drains.

    Configurable “Green function”: When in battery mode with only very small loads, the UPS will automatically shut itself down to protect batteries.

    Programmable outlets: 3 of the 6 Vertiv EDGE outlets are configurable (1 group), enabling users to shut down less-critical loads in the event of an outage to optimize battery runtime.

    RoHS and REACH compliant: Ensures against the use of hazardous substances in UPSs.

    Easy to install, configure and operate: Auto-detect external battery modules and color LCD display help to make the UPS operation easier and the user interface more intuitive.

    Optional SNMP/web card: For advanced remote monitoring of status and OS's shutdown.

    Environmental monitoring: Optional web card also supports integration with environmental sensors, to detect excessive heat, moisture, motion and more.

    External battery cabinets: Attach up to 6 external battery modules to gain additional runtime.

    Remote Emergency Power Off: Allows the UPS to be remotely shut down during an emergency.

    Optional Liebert MicroPOD Output Distribution and Maintenance Bypass Module: When your computer system can’t be without power, even for scheduled UPS maintenance, the Liebert® MicroPOD ensures continuous uptime.

    PF0.9

    EDGE UPS | Brochure

    Vertiv™ EDGE UPS | Brochure

  • 56

    Vertiv™ EDGE UPS

    Vertiv™ EDGE UPS Accessories

    Vertiv™ VR Racks and Enclosures:Internal, welded frame with repetitive hold pattern delivers high load bearing capacity and additional mounting locations.

    Vertiv™ Geist™ PDUs: Effectively distribute UPS power throughout a rack environment while organizing power cords. Rack-, wall- or floor-mounted PDUs support a selection of NEMA, IEC and hardwired inputs. Rack PDUs can be preinstalled in the VR Rack.

    Rails and mounting hardware: 4-post rail kit and hardware to mount in a rack.

    External Battery Modules: Enable additional runtime to weather extended power outage situations. Modules are simple to install and auto-discoverable.

    Optional Connectivity Cards: Web and SNMP cards allow you to connect your Vertiv™ EDGE UPS to an Ethernet network and the Internet, to monitor and manage UPSs from a standard Web browser and, when needed, remotely provide graceful shutdown for multiple computer systems.

    Liebert® MicroPOD Maintenance Bypass:A 2U rack-mounted installation, available in several receptacle combinations, allows manual transfer of connected equipment to utility power ensuring network availability and business continuity during scheduled service or UPS replacement.

    EDGE UPS | Brochure

    Vertiv™ EDGE UPS | Brochure

  • 57

    Power Emergency: Comprehensive Service Support for Critical Systems

    Providing more than the standard warranty and extension program, this five-year protection program is valid for single-phase UPS units 3 kVA or smaller. Purchased only at the point of sale, the program includes:

    Advance replacement of faulty unit with unit shipped within eight working hours of incident ticket acknowledgement meaning a maximum of two business days after claim.

    100% coverage of electronic parts and failed batteries excluding battery misuse and/or reduced autonomy.

    Free shipping from the following European countries: Austria, Belgium, Croatia, Czech Republic, France, Germany, Ireland, Italy, Luxemburg, Poland, Portugal, Slovakia, Spain, Sweden, Switzerland, The Netherlands, Turkey, and United Kingdom.

    24x7 access to professional helpline.

    Key Benefits:

    Reduces the worry about critical equipment downtime.

    Ensures rapid recovery in the event of failure (within 24-48 hours).

    Our PurposeWe believe there is a better way to meet the world’s accelerating demand for data - one driven by passion and innovation.

    Our Presence

    Global Presence

    Manuf. and Assembly Locations 28

    Service Centers 250+

    Service Field Engineers 2,650+

    Technical Support/Response 300+

    Customer Experience Centers/Labs 16

    US and Canada

    Manuf. and Assembly Locations 13

    Service Centers 100+

    Service Field Engineers 850+

    Technical Support/Response 120+

    Customer Experience Centers/Labs 4

    Latin America

    Manuf. and Assembly Locations 1

    Service Centers 20+

    Service Field Engineers 240+

    Technical Support/Response 20+

    Customer Experience Centers/Labs 2

    Europe, Middle East And Africa

    Manuf. and Assembly Locations 9

    Service Centers 70+

    Service Field Engineers 590+

    Technical Support/Response 90+

    Customer Experience Centers/Labs 5

    Asia Pacific

    Manuf. and Assembly Locations 5

    Service Centers 60+

    Service Field Engineers 970+

    Technical Support/Response 80+

    Customer Experience Centers/Labs 5

    Power Emergency

    Technical support Hotline 24/7

    Parts included

    Response time 8 working hours

    Contract duration 5 years (10 with renewal)

    EDGE UPS | Brochure

    Vertiv™ EDGE UPS | Brochure

  • 58

    Vertiv™ EDGE UPS

    Technical Specifications - 1U Rack ModelsModel Number EDGE-500IRM1U EDGE-1000IRM1U EDGE-1500IRM1U

    Rating (VA/W) 500VA/450W 1000VA/900W 1500VA/1350W

    Dimensions, mm

    Unit (W x D x H) 438 x380 x 44 438 x 480 x 44 438 x 600 x 44

    Shipping (W x D x H) 550 x 620 x 200 570 x 700 x 200 570 x 780 x 200

    Weight, kg

    Unit 11 17 23

    Shipping 17 23 31

    Input AC Parameters

    Nominal VoltageSetting 230V 230V 230V

    Voltage Range Without Battery Operation (230V default)

    166 - 278 166 - 278 166 - 278

    Frequency Range (Hz) 55 - 65 55 - 65 55 - 65

    Input Power Connector IEC60320 C14 IEC60320 C14 IEC60320 C14

    Surge Protetion (J) 624 624 624

    Output AC Parameters

    Output Receptacles 3 + 3 IEC320 C13 3 + 3 IEC320 C13 3 + 3 IEC320 C13

    Output Receptacles - Controllable Yes - 1 group Yes - 1 group Yes - 1 group

    Output Voltage 200/208/220/230/240 200/208/220/230/240 200/208/220/230/240

    Waveform (Battery Operation) Sine Wave Sine Wave Sine Wave

    Transfer Time 4 - 6 ms Typical 4 - 6 ms Typical 4 - 6 ms Typical

    Output (AC Mode) Overload106% - 125% @ 60 s 126% - 150% @ 50 s 151% - 200% @ 2 s

    106% - 125% @ 60 s 126% - 150% @ 50 s 151% - 200% @ 2 s

    106% - 125% @ 60 s 126% - 150% @ 50 s 151% - 200% @ 2 s

    Efficiency (full load, line mode, typ) 96% 97% 97%

    Battery

    TypeValve-regulated, non-spillable,

    lead acidValve-regulated, non-spillable,

    lead acidValve-regulated, non-spillable,

    lead acid

    Quantity & Voltage & Capacity 2 x 6V x 9Ahr 4 x 6V x 9Ahr 6 x 6V x 9Ahr

    Recharge Time (internal batteries, typical)

    3 hr @ 90% 3 hr @ 90% 3 hr @ 90%

    Compatible External Battery Cabinet -- -- --

    Environmental

    Operating Temperature (ºC) (*) 0 to 40 0 to 40 0 to 40

    Storage Temperature (ºC) -25ºC to +55ºC without battery inside -25ºC to +55ºC without battery inside -25ºC to +55ºC without battery inside

    Relative Humidity (Operation) 20% to 90% 20% to 90% 20% to 90%

    Operating Altitude (m) 3000 3000 3000

    Audible Noise (line mode)

  • 59

    Technical Specifications - Tower ModelsModel Number EDGE-750IMT EDGE-1000IMT EDGE-1500IMT

    Rating (VA/W) 750VA/675W 1000VA/900W 1500VA/1350W

    Dimensions, mm

    Unit (W x D x H) 145 x 370 x 220 145 x 370 x 220 145 x 480 x 220

    Shipping (W x D x H) 230 x 450 x 325 230 x 450 x 325 230 x 570 x 325

    Weight, kg

    Unit 11 12 18

    Shipping 13 13 20

    Input AC Parameters

    Nominal VoltageSetting 230V 230V 230V

    Voltage Range Without Battery Operation (230V default)

    166 - 278 166 - 278 166 - 278

    Frequency Range (Hz) 55 - 65 55 - 65 55 - 65

    Input Power Connector IEC60320 C14 IEC60320 C14 IEC60320 C14

    Surge Protetion (J) 624 624 624

    Output AC Parameters

    Output Receptacles 3 + 2 IEC320 C13 3 + 3 IEC320 C13 3 + 3 IEC320 C13

    Output Receptacles - Controllable Yes - 1 group Yes - 1 group Yes - 1 group

    Output Voltage 200/208/220/230/240 200/208/220/230/240 200/208/220/230/240

    Waveform (Battery Operation) Sine Wave Sine Wave Sine Wave

    Transfer Time 4 - 6 ms Typical 4 - 6 ms Typical 4 - 6 ms Typical

    Output (AC Mode) Overload106% - 125% @ 60 s 126% - 150% @ 50 s 151% - 200% @ 2 s

    106% - 125% @ 60 s 126% - 150% @ 50 s 151% - 200% @ 2 s

    106% - 125% @ 60 s 126% - 150% @ 50 s 151% - 200% @ 2 s

    Efficiency (full load, line mode, typ) 95% 96% 97%

    Battery

    TypeValve-regulated, non-spillable,

    lead acidValve-regulated, non-spillable,

    lead acidValve-regulated, non-spillable,

    lead acid

    Quantity & Voltage & Capacity 2 x 12V x 9Ahr 2 x 12V x 10Ahr 4 x 12V x 9Ahr

    Recharge Time (internal batteries, typical)

    3 hr @ 90% 3 hr @ 90% 3 hr @ 90%

    Compatible External Battery Cabinet -- -- --

    Environmental

    Operating Temperature (ºC) (*) 0 to 40 0 to 40 0 to 40

    Storage Temperature (ºC) -25ºC to +55ºC without battery inside -25ºC to +55ºC without battery inside -25ºC to +55ºC without battery inside

    Relative Humidity (Operation) 20% to 90% 20% to 90% 20% to 90%

    Operating Altitude (m) 3000 3000 3000

    Audible Noise (line mode)

  • 60

    Vertiv™ EDGE UPS

    10

    Technical Specifications - 2-3Us Rack/Tower modelsModel Number EDGE-1500IRT2UXL EDGE-22000IRT2UXL EDGE-3000IRT2UXL EDGE-3000IRT3UXL

    Rating (VA/W) 1500VA/1350W 2200VA/1980W 3000VA/2700W 3000VA/2700W

    Dimensions, mm

    Unit (W x D x H) 438 x 510 x 88 438 x 630 x 88 438 x 630 x 88 438 x 485 x 132

    Shipping (W x D x H) 565 x 700 x 240 600 x 800 x 240 600 x 800 x 240 550 x 670 x 282

    Weight, kg

    Unit 20 27 32 36

    Shipping 30 35 42 42

    Input AC Parameters

    Nominal VoltageSetting 230V 230V 230V 230V

    Voltage Range Without Battery Operation (230V default)

    166 - 278 166 - 278 166 - 278 166 - 278

    Frequency Range (Hz) 55 - 65 55 - 65 55 - 65 55 - 65

    Input Power Connector IEC60320 C14 IEC60320 C20 IEC60320 C20 IEC60320 C20

    Surge Protetion (J) 624 624 624 624

    Output AC Parameters

    Output Receptacles 3 + 3 IEC320 C133 + 3 IEC320 C13 + 1 IEC320 C19

    3 + 3 IEC320 C13 + 1 IEC320 C19

    6 + 3 IEC320 C13 + 1 IEC320 C19

    Output Receptacles - Controllable

    Yes - 1 group Yes - 1 group Yes - 1 group Yes - 1 group

    Output Voltage 200/208/220/230/240 200/208/220/230/240 200/208/220/230/240 200/208/220/230/240

    Waveform (Battery Operation) Sine Wave Sine Wave Sine Wave Sine Wave

    Transfer Time 4 - 6 ms Typical 4 - 6 ms Typical 4 - 6 ms Typical 4 - 6 ms Typical

    Output (AC Mode) Overload106% - 125% @ 60 s 126% - 150% @ 50 s 151% - 200% @ 2 s

    106% - 125% @ 60 s 126% - 150% @ 50 s 151% - 200% @ 2 s

    106% - 125% @ 60 s 126% - 150% @ 50 s 151% - 200% @ 2 s

    106% - 125% @ 60 s 126% - 150% @ 50 s 151% - 200% @ 2 s

    Efficiency (full load, line mode, typ)

    97% 97% 98% 98%

    Battery

    TypeValve-regulated, non-spillable,

    lead acidValve-regulated, non-spillable,

    lead acidValve-regulated, non-spillable,

    lead acidValve-regulated, non-spillable,

    lead acid

    Quantity & Voltage & Capacity 4 x 12V x 9Ahr 6 x 12V x 7Ahr 6 x 12V x 10Ahr 6 x 12V x 10Ahr

    Recharge Time (internal batteries, typical)

    3 hr @ 90% 3 hr @ 90% 3 hr @ 90% 3 hr @ 90%

    Compatible External Battery Cabinet

    GXT5-EBC48VRT2U(E) GXT5-EBC72VRT2U(E) GXT5-EBC72VRT2U(E) GXT5-EBC72VRT2U(E)

    Environmental

    Operating Temperature (ºC) (*) 0 to 40 0 to 40 0 to 40 0 to 40

    Storage Temperature (ºC)-25ºC to +55ºC

    without battery inside-25ºC to +55ºC

    without battery inside-25ºC to +55ºC

    without battery inside-25ºC to +55ºC

    without battery inside

    Relative Humidity (Operation) 20% to 90% 20% to 90% 20% to 90% 20% to 90%

    Operating Altitude (m) 3000 3000 3000 3000

    Audible Noise (line mode)

  • 61

    11

    Vertiv™ EDGE Runtime Tables

    EDGE 1U Rack Models

    EDGE Tower models

    EDGE 2U-3Us Rack/Tower models

    Load % VA WEDGE-500IRM1U

    Internal Batteries Only

    100 500 450 5

    70 350 315 9

    50 250 225 15

    20 100 90 42

    Load % VA WEDGE-1500IRM1U

    Internal Batteries Only

    100 1500 1350 5

    70 1050 945 9

    50 750 675 15

    20 300 270 42

    Load % VA WEDGE-1000IRM1U

    Internal Batteries Only

    100 1000 900 5

    70 700 630 9

    50 500 450 15

    20 200 180 42

    Load % VA WEDGE-750IMT

    Internal Batteries Only

    100 750 675 5.9

    70 525 473 10

    50 375 338 17

    20 150 135 47

    Load % VA WEDGE-1500IMT

    Internal Batteries Only

    100 1500 1350 6

    70 1050 945 10

    50 750 675 17

    20 300 270 49

    Load % VA WEDGE-1000IMT

    Internal Batteries Only

    100 1000 900 5

    70 700 630 9

    50 500 450 15

    20 200 180 43

    Load % VA WEDGE-1500IRT2UXL

    Internal Batteries Only+1 EBC +3EBCs +6EBCs

    100 1500 1350 6 27 85 177

    70 1050 945 10 45 132 266

    50 750 675 17 68 192 382

    20 300 270 49 179 466 898

    Load % VA WEDGE-22000IRT2UXLInternal Batteries Only

    +1 EBC +3EBCs +6EBCs

    100 2200 1980 4.4 26 84 177

    70 1540 1386 8 42 130 266

    50 1100 990 14 65 192 385

    20 440 396 39 170 461 898

    Load % VA WEDGE-3000IRT2UXL

    & EDGE-3000IRT3UXLInternal Batteries Only

    +1 EBC +3EBCs +6EBCs

    100 3000 2700 6 19 61 129

    70 2100 1890 10 33 96 196

    50 1500 1350 16 51 144 286

    20 600 540 43 137 350 672

    EDGE UPS | Brochure

    Vertiv™ EDGE UPS | Brochure

  • 62

    Liebert® ITA2

    Compact, Eff icient, & Robust UPS for Critical Applications

    5-30kVA

  • 63

    In today's dynamic world, having basic power protection is not enough for enterprises. Business continuity is even more vital with digital trends constantly emerging and transforming the way you do business. In your critical system, you simply cannot a ford downtime or waste time recovering these systems after a disruption. What you need is a robust, high-speed, reliable UPS system which o fers perennial, round-the-clock protection for diverse applications.

    Our Solution

    The Liebert® ITA2™ is a fully-digital, highly reliable, double-conversion UPS solution that provides clean and consistent power. This highly e icient solution is ideal for various deployments, including IT racks, network closets, automation control systems, and precision instruments to small sized control rooms among other edge applications.

    Cutting–edge design enables seamless integration into variousecosystems

    Tailored for global deployment in a low carbon, compact footprint

    The ultimate level of engineering and dynamics that have gone beyond the development of this innovative, next-generation product facilitate top-notch availability and excellent performance at low ownership costs, giving you ultimate peace of mind.

    Application Areas

    Edge Networks

    Data Centers

    Automation industries

    Server Farms

    Workstations

    Telecom

    Liebert® ITA2™ 5-30kVA

    5-10kVA

    16-30kVA

    Liebert® ITA2 | Brochure

  • 64

    Robust structure withcutting edgechannelized air owdesign

    Wide input voltagerange, making it immuneto grid interference

    Rack-tower design forinstallation exibility

    Able to deliver boththree-phase and single-phase output2

    0.99 input power factorfor better grid orgenerator compatibility

    Powerful chargingcapability for minimumbattery recharging time

    Programmable outputoutlets/terminals withcascade protection toprotect key devicesduring heavy load2

    Integrated Ethernet portwith HTTP protocolcompatibility andstreamlined remotemonitoring

    Easy to install, repair,and maintain

    Compliance with seismicconduction and vehiclecarrying test

    Gravity sense LCDdisplay

    Turnkey dust-resistantdesign with ability tooperate under highambient temperature ofup to 50ºC

    Key FeaturesLiebert® ITA2™ o ers best-in-class e iciency of up to 96.5% in double conversion mode over a wide range of load conditions, resulting in signi cant OPEX cost savings. Liebert ITA2's ECO mode of opreration provides a superlative e iciency of up to 99%.

    Optimized modules minimizes the amount of used space in the rack

    Support base makes it convenient and stable to place on a oor

    Adjustable display panel ensures readability and ease of use

    Con guration easily extends to batteries and POD cabinet

    The Most Eff icient UPS

    The Most Flexible UPS

    The Most Compact UPS

    98%

    96%

    92%

    94%

    90%25% 50% 75%

    Load

    ECO Mode

    Double Conversion Mode

    100%

    Eff ic

    ienc

    y

    *Shown here the UPS and battery cabinets in a rack & tower arrangement.

    Liebert® ITA2 | Brochure

  • 65

    Dust-resistant Design

    Liebert® ITA2 | Brochure

    Available in di erent wattage variations, Liebert® ITA2™ is ideal in the edge of networks, light industrial applications and data centers, easily blending into any virtualized environment and providing comprehensive power protection at reduced operating costs.

    Reliability in a compact footprint

    Fully-digital control with high output voltageprecision

    Manages all the nine power problems includingsagging, spikes, and uctuations

    Built-in Ethernet port includes browser supportcompatibility with intelligent cards (SIC card,UNITY-DP, RDU_SIC cards, etc.)

    Built-in-power charger for fast charging reducesthe battery charging time

    Prolonged backup time through cascadedconnection

    Quality-tested for 1000 hours for extremedurability and tolerance even in stringentconditions

    High Availability

    Early Warning of UPS System Status

    Multiple audible and visual alarms instantly alert for critical issues.

    Periodic Battery Testing

    Provides automatic and manual self-diagnostic battery testing for peace of mind.

    Power-Factor Correction

    Prevents noise, harmonics, and distortion from being transferred to connected loads or fed back to the utility.

    Lightning and Surge Protection

    The transient voltage surge suppression circuitry inside the Liebert® ITA2™ provides additional protection for the connected equipment.

    Wide Input Voltage Window

    Prolongs battery life by allowing the UPS to maximize the use of utility power before being transferred to the battery when the input voltage exceeds the speci ed limits.

  • 66

    Intelligent Communications

    The Liebert® ITA2™ o ers an intuitive control panel, network connectivity communications card, and optional software monitoring, all designed to ensure visibility, control and peace of mind for manned or unmanned locations. You can even monitor key environmental and room conditions.

    Trellis™ Power Insight

    Trellis™ Power Insight is an application that can monitor your Liebert UPS systems and provide real-time trends for critical UPS performance management. In the event of a need to shutdown the UPS, the software ensures a graceful shutdown routine so that no damage occurs to the data or systems.

    POD - Optional Accessories

    The Liebert POD maintenance bypass and output distribution unit ensures continuous uptime when your critical system cannot a ord any power loss without power, even for scheduled UPS maintenance.

    It allows you to manually transfer connected equipment to utility power via a maintenance bypass switch, permitting scheduled service or UPS replacement without shutting down connected equipment. Features include:

    2U height minimizes rack space requirements

    Easy plug-and-play installation

    Liebert® ITA2 | Brochure

  • 67

    Liebert® ITA2 | Brochure

    Battery Backup Table

    UPS Model

    Battery Modules

    Backup Time in Minutes5kVA 4.5kVA 4kVA 3.5kVA 3kVA 2.5kVA 2kVA 1.5kVA 1kVA 0.5kVA

    5kVA

    1 6.8 7.8 9.2 11.2 13.9 17.9 24.3 35.6 58 122.4

    2 18 20.9 24.6 29.7 36.5 46 59.7 81.7 126.4 278.8

    3 31.9 36.6 42.6 50.2 60.2 74.1 94.5 128.3 207 435.7

    4 46.3 52.6 60.3 70.2 83.5 102.2 130.3 182.7 287.6 592.5

    5 60.4 68.1 77.8 90.3 107 131.4 171.6 237.1 368.2 749.3

    6 74.4 83.7 95.4 110.4 131.5 164.6 212.9 291.5 448.8 906.1

    UPS Model

    Battery Modules

    Backup Time in Minutes6kVA 5.4kVA 4.8kVA 4.2kVA 3.6kVA 3kVA 2.4kVA 1.8kVA 1.2kVA 0.6kVA

    6kVA

    1 5.1 6.1 7.1 8.6 10.8 13.9 19 28 46.9 101

    2 14 16.1 19.1 23 28.6 36.5 48.4 67 103.9 228.2

    3 24.7 28.7 33.6 40 48.5 60.2 77.6 105.6 167.6 359.7

    4 36.7 42 48.7 57 68 83.5 106.9 147.8 235.1 491.2

    5 48.8 55.3 63.3 73.6 87.5 107 138.3 193.5 302.6 622.8

    6 60.5 68.2 77.9 90.4 107.1 131.5 172.9 239.1 370.1 754.3

    UPS Model

    Battery Modules

    Backup Time in Minutes10kVA 9kVA 8kVA 7kVA 6kVA 5kVA 4kVA 3kVA 2kVA 1kVA

    10kVA

    2 4.8 5.5 7.4 10.2 14 18 24.6 36.5 59.7 126.4

    3 8.8 10.2 13.6 18.5 24.7 31.9 42.6 60.2 94.5 207

    4 13.7 15.9 21.1 28.4 36.7 46.3 60.3 83.5 130.3 287.6

    5 19.4 22.4 29.7 39.3 48.8 60.4 77.8 107 171.6 368.2

    6 25.8 29.6 38.6 50.6 60.5 74.4 95.4 131.5 212.9 448.8

    UPS Model

    Battery Modules

    Backup Time in Minutes16kVA 14.4kVA 12.8kVA 11.2kVA 9.6kVA 8kVA 6.4kVA 4.8kVA 3.2kVA 1.6kVA

    16kVA

    4 9.5 11 13 15.6 19.4 24.8 33.8 48.7 77.7 169.6

    6 16.8 19.6 23.1 27.8 34 42.9 56.2 77.9 121.7 271.9

    8 25.3 29.3 34.4 40.8 49.2 60.7 78.1 107.3 173.2 374.1

    10 34.4 39.5 45.9 53.8 63.9 78.4 100.3 138.9 225.2 476.3

    12 43.6 49.7 57.2 66.5 78.7 96.1 122.4 173.7 277.2 578.6

    UPS Model

    Battery Modules

    Backup Time in Minutes20kVA 18kVA 16kVA 14kVA 12kVA 10kVA 8kVA 6kVA 4kVA 2kVA

    20kVA

    4 6.9 8 9.5 11.5 14.3 18.3 24.8 36.7 60.3 130.3

    6 12.3 14.3 16.8 20.4 25.3 32.3 42.9 60.5 95.4 212.9

    8 18.5 21.5 25.3 30.5 37.5 46.8 60.7 84 131.8 295.5

    10 25.3 29.3 34.4 41 49.7 61.1 78.4 107.6 173.4 378.1

    12 32.6 37.5 43.6 51.4 61.6 75.2 96.1 132.3 215.1 460.7

    Note: Battery autonomy times and 5 year design life are based on operation at 25°C. Approximate autonomy times are based on fully charged batteries and can vary +/-5% due to battery manufacturing variances.

  • 68

    Technical Specifications

    Nominal Ratings (kVA) 5 6 10 16 20 30

    Long Backup Model ITA-05k00AL1102P00/ITA-05k00AE1102P00IITA-06k00AL1102P00/ITA-06k00AE1102P00

    ITA-10k00ALA102P00/ITA-10k00AEA102P00

    ITA-16k00AL3A02P00/ITA-16k00AE3A02P00

    ITA-20k00AL3A02P00/ITA-20k00AE3A02P000

    ITA-30k00AL3302P00

    Input Parameters

    Nominal Input Voltage (V) 220/230/240VAC 1-Phase, 2 Wire

    220/230/240VAC 1-Phase, 2 Wire

    380/400/415VAC 3-Phase, 4 Wire

    380/400/415VAC 3-Phase, 4 Wire

    176-288VAC at full load; 100-176VAC at linear derating; 100VAC at half load

    50/60

    40-70

    0.99

    Battery

    Battery Blocks Per String 12*, 16, 20 24*, 32, 34, 36, 38, 40 32, 34, 36, 38, 40

    Battery OptionP/C : ITA-BCI0020K01 ( built-in battery module of 16 block X 12V X 9AH)

    Battery cabinet Dimensions in rack arrangement - 430(W) x 739(D) x 85(H) Only external

    battery cabinet

    Output

    Nominal Output Voltage (V) 220/230/240 (1-phase)220/230/240VAC (1-Phase), 380/400/415VAC (3-Phase)

    380/400/415VAC

    (3-Phase)

    Nominal Output Frequency (Hz) 50/60

    Rated Power Factor (kW/kVA) Unity

    Voltage Harmonic Distortion (%)

  • 69

    Liebert® ITA2TM UPS Compact, Efficient & Robust UPS for Critical Applications

    5-20kW/kVA

    GUIDE SPECIFICATIONS

    1.0 GENERAL 1.1 Summary

    The specifications mentioned in this document describe the operation and functional requirements of a tower or rack mounted transformer-free Uninterruptible Power Supply (UPS) performing round-the-clock, classified as VFI-SS-111 in accordance with IEC/EN 62040-3 industry standards. The UPS will automatically maintain AC power within specified tolerances to the critical load, without any interruption (depending on the duration pertaining to the battery run time) during failure or deterioration of the mains power supply. The UPS system will be expandable to provide redundancy or load growth requirements.

    The manufacturer will design and furnish all materials and equipment that are fully compatible with electrical, environmental, and space conditions at the site. The UPS will include all the equipment to properly interface the AC power source to the intended load and will also be designed for unattended operation.

    1.2 STANDARDS

    The UPS along with the associated equipment and components will be manufactured in accordance with the following applicable standards:

    The UPS is CE marked in accordance with EEC directives 73/23 “low voltage” and 89/336 “electromagnetic compatibility”. The Quality management grade pertaining to the engineering and manufacturing facility is certificated to conform to the ISO 9001 international standards, specifically catering to the design and production of power protection systems for computers and other sensitive electronic devices.

    General safety requirements for the UPS EN62040-1/IEC62040-1

    EMC requirements for the UPS EN62040-2/IEC62040-2 (Class C2)

    Method of specifying the performance and test

    requirements of the UPS EN62040-3/IEC62040-3(VFI SS 111)

    safety of information technology equipment, including electrical business equipment

    EN60950

    Electromagnetic compatibility (EMC) IEC 61000-3-4, IEC 61000-4-2,4,5,6,8,11

    Moisture and dust test Factory certified. (Or)

    GB/T 2423.21-2008 Environmental testing for electrical and electronic

    products- Part 2: Test methods- Test M: low air pressure High Altitude test

    Energy star certified 2011/65/EU uninterruptible power supplies version 1.0 program

    requirements/ENERGY STAR UPS version 1.0 test method guidance

    Vehicle-carrying test

    GB/T21563-2008 Railway applications-Rolling stock equipment-shock and

    vibration test

    GB/T 4798.5-2007 Environmental conditions existing in the application of electric and electronic product- section 5: ground vehicle installations

    Liebert® ITA2 | Guide Specifications Liebert® ITA2 | Guide Specifications

  • 70

    Vertiv | Liebert® ITA2TM UPS 4 Guide Specifications | V03 | 13.8.18

    1.3 SYSTEM DESCRIPTION

    1.3.1 Design Requirements

    A. For non-redundant operation (applicable, not applicable), the UPS system will be sized to provide a minimum of ____ kVA / kW output.

    UPS Num in parallel system 1 2 3

    Output KVA 5/6/10/16/20 10/12/20/32/40 15/18/30/48/60

    B. For redundant operation (applicable, not applicable), the UPS system will be sized to provide a minimum of ____ kVA / kW output with ___ redundant UPS module(s) out of service.

    UPS Num in parallel system 2 3 4

    redundant number 1 1 2 1 2 3

    Output KVA 5/6/10/16/20 10/12/20/32/40 5/6/10/16/20 15/18/30/48/60

    The UPS will be able to supply all required power to full-rated output kVA loads with power factor ranging from 0.5 lagging to Unity. The UPS will also work from 0.9 to 0.5 leading power factors subject to de-rating.

    The battery modules (which match the UPS dimensions) will support the UPS with a capacity of ____ kW load for at least _____ minutes at 25°C at startup.

    Note: Select the appropriate number of battery modules to deliver the required battery autonomy period. The below details are

    considering 9AH/12V, 16No of batteries. (The autonomy times are approximate and are based on fully charged batteries and can

    vary +/-5% because of battery manufacturing variances.)

    To guarantee the backup time, it is recommended to configure at least two groups of battery modules for the 10kVA model.

    ModeModule

    number

    Backup time

    5kVA 4.5kVA 4kVA 3.5kVA 3kVA 2.5kV 2kVA 1.5kVA 1kVA 0.5kVA

    5kVA

    1 6.8 7.8 9.2 11.2 13.9 17.9 24.3 35.6 58.0 122.4

    2 18.0 20.9 24.6 29.7 36.5 46.0 59.7 81.7 126.4 278.8

    3 31.9 36.6 42.6 50.2 60.2 74.1 94.5 128.3 207.0 435.7

    4 46.3 52.6 60.3 70.2 83.5 102.2 130.3 182.7 287.6 592.5

    5 60.4 68.1 77.8 90.3 107.0 131.4 171.6 237.1 368.2 749.3

    6 74.4 83.7 95.4 110.4 131.5 164.6 212.9 291.5 448.8 906.1

    Model Module

    numbe

    Backup time

    6 kVA

    5.4 kVA

    4.8 kVA

    4.2 kVA

    3.6 kVA

    3 kVA

    2.4 kVA

    1.8 kVA

    1.2 kVA

    0.6 kVA

    6kVA

    1 5.1 6.1 7.1 8.6 10.8 13.9 19.0 28.0 46.9 101.0

    2 14.0 16.1 19.1 23.0 28.6 36.5 48.4 67.0 103.9 228.2

    3 24.7 28.7 33.6 40.0 48.5 60.2 77.6 105.6 167.6 359.7

    4 36.7 42.0 48.7 57.0 68.0 83.5 106.9 147.8 235.1 491.2

    5 48.8 55.3 63.3 73.6 87.5 107.0 138.3 193.5 302.6 622.8

    6 60.5 68.2 77.9 90.4 107.1 131.5 172.9 239.1 370.1 754.3

    Model Module

    number

    Backup time

    10 kVA

    9 kVA

    8 kVA

    7 kVA

    6 kVA

    5 kVA

    4 kVA

    3 kVA

    2 kVA

    1 kVA

    10kVA

    2 4.8 5.5 7.4 10.2 14.0 18.0 24.6 36.5 59.7 126.4

    3 8.8 10.2 13.6 18.5 24.7 31.9 42.6 60.2 94.5 207.0

    4 13.7 15.9 21.1 28.4 36.7 46.3 60.3 83.5 130.3 287.6

    5 19.4 22.4 29.7 39.3 48.8 60.4 77.8 107.0 171.6 368.2

    6 25.8 29.6 38.6 50.6 60.5 74.4 95.4 131.5 212.9 448.8

    Liebert® ITA2 | Guide Specifications

    Liebert® ITA2 | Guide Specifications

  • 71

    Vertiv | Liebert® ITA2TM UPS 5 Guide Specifications | V03 | 13.8.18

    To guarantee the backup time, it is recommended to configure at least four groups of battery modules for the 20kVA model.

    1.3.2 Modes of Operation The UPS will operate in the following modes:

    A. Normal: The UPS inverter continuously supplies the critical AC load. The rectifier draws power from the commercial AC source and converts it into DC power for the inverter and the battery charger. The battery charger maintains the battery in a fully-charged and optimum operational condition. The inverter converts the DC power into clean and regulated AC power which is supplied to the critical load (conditioned line).

    B. ECO Mode: The critical AC load will be continuously powered by the bypass with the inverter available to power the load if the bypass source voltage or frequency exceeds adjustable parameters of power quality.

    C. Battery: Upon failure or degradation of the primary AC source, the load will be supplied through the inverter drawing power from the battery. Visible and audible signals will alert the user during this operating state. The remaining autonomy time will be calculated by a diagnostic algorithm. Once the end of discharge (EoD) voltage is reached, the UPS will automatically disconnect the battery (internal or external) without the need for external devices.

    D. Recharge: If the primary AC source returns within tolerance limits prior to a UPS automatic end of discharge shutdown, the rectifier will recommence powering the inverter and simultaneously recharging the battery through the battery converter. When the inverter has synchronized with the bypass, the UPS will recommence operating in double conversion mode without any break (0 ms) in the supply to the load.

    If the primary AC source does not return within tolerance limits and the UPS performs an automatic end of discharge shutdown, the UPS will recommence operating in bypass mode until it is manually transferred to the inverter. Alternatively, it can be set to start in static bypass mode and automatically transfer to double conversion mode after a time delay, from the moment the rectifier start is complete and the bypass source is back within the synchronization windows. The time delay is selectable between 1 and 999 seconds (default: 10 seconds). During the selected delay, the UPS will charge the battery and phase-lock the inverter with bypass. If the inverter is unable to phase-lock the bypass at the end of the selected window, the load will remain fed by the bypass and the user will be prompted to confirm or cancel an interrupted transfer.

    E. Bypass: If the UPS must be taken out of service, the static transfer switch will transfer the load to the bypass source. The transfer process will cause no interruption in power to the critical load. An optional external wrap-around maintenance bypass will be used to ensure full isolation of the unit for the service of internal components while providing safety from arc flash.

    Model Module

    numbe

    Backup time

    16 kVA

    14.4 kVA

    12.8 kVA

    11.2 kVA

    9.6 kVA

    8 kVA

    6.4 kVA

    4.8 kVA

    3.2 kVA

    1.6 kVA

    16kVA

    4 9.5 11.0 13.0 15.6 19.4 24.8 33.8 48.7 77.7 169.6

    6 16.8 19.6 23.1 27.8 34.0 42.9 56.2 77.9 121.7 271.9

    8 25.3 29.3 34.4 40.8 49.2 60.7 78.1 107.3 173.2 374.1

    10 34.4 39.5 45.9 53.8 63.9 78.4 100.3 138.9 225.2 476.3

    12 43.6 49.7 57.2 66.5 78.7 96.1 122.4 173.7 277.2 578.6

    Model Module

    number

    Backup time

    20 kVA

    18 kVA

    16 kVA

    14 kVA

    12 kVA

    10 kVA

    8 kVA

    6 kVA

    4 kVA

    2 kVA

    20kVA

    4 6.9 8.0 9.5 11.5 14.3 18.3 24.8 36.7 60.3 130.3

    6 12.3 14.3 16.8 20.4 25.3 32.3 42.9 60.5 95.4 212.9

    8 18.5 21.5 25.3 30.5 37.5 46.8 60.7 84.0 131.8 295.5

    10 25.3 29.3 34.4 41.0 49.7 61.1 78.4 107.6 173.4 378.1

    12 32.6 37.5 43.6 51.4 61.6 75.2 96.1 132.3 215.1 460.7

    Liebert® ITA2 | Guide Specifications

    Liebert® ITA2 | Guide Specifications

  • 72Vertiv | Liebert® ITA2TM UPS 6 Guide Specifications | V03 | 13 818

    performance criteria, except for the power outage backup time capability. If multiple battery strings are used, each string will be capable of being electrically isolated for safety during maintenance.

    G. Parallel: Inherent scalability features should be available to meet higher capacity and higher reliability requirements. Under normal operating conditions, the power delivered to the load will be equally shared between number of UPS units connected to the parallel bus with a tolerance of 5%. In the event of a unit failure or overload, the system will transfer to the bypass source.

    H. Common Battery (for