36
1 SDI-C-2011 Standard for Composite Steel Floor Deck-Slabs 1 30 November 2011 2 3 1. General 4 5 1.1 Scope: 6 A. This Standard for Composite Steel Floor Deck-Slabs, hereafter referred to as the 7 Standard, shall govern the materials, design, and erection of composite concrete slabs 8 utilizing cold formed steel deck functioning as a permanent form and as reinforcement 9 for positive moment in floor and roof applications in buildings and similar structures. 10 B. The Appendices shall be part of the Standard. 11 C. The User Notes, User Note Attachments, and Commentary shall not be part of the 12 Standard. 13 14 User Note: User Notes, User Note Attachments, and Commentary are intended to 15 provide practical guidance in the use and application of this Standard. 16 17 D. Where the Standard refers to “designer,” this shall mean the entity that is responsible to 18 the Owner for the overall structural design of the project, including the steel deck. 19 20 User Note: This is usually the Structural Engineer of Record. 21 22 E. Equations that appear in this Standard are compatible with the inch-pounds system of 23 units. However, any consistent system of units shall be permitted to be used. SI units 24 or equations shown in parentheses in this standard are for information only, and are not 25 part of this Standard. 26 F. Terms not defined in this Standard, AISI S100 or AISI/AISC shall have the ordinary 27 accepted meaning for the context for which they are intended. 28 G. It shall be permitted to specify deck base metal thickness either by dimensional 29 thickness, or by gage when the relationship of base metal thickness to gage has been 30 defined by the deck manufacturer. However, for the purpose of design, the 31 dimensional thickness shall be used. 32 33 User Note: Both AISI and SDI now specify steel thickness in terms of design 34 thickness in lieu of gage thickness. Gage thicknesses, however, are still commonly 35 referred to in the metal deck industry. Table UN-1.1 shows common gages and 36 corresponding uncoated design and minimum steel thicknesses. 37 38 Table UN-1.1 39 Gage No. Design Thickness Minimum Thickness 1 in. mm. in. mm. 22 0.0295 0.75 0.028 0.71 20 0.0358 0.91 0.034 0.86 18 0.0474 1.20 0.045 1.14 16 0.0598 1.52 0.057 1.44 1 Minimum thickness is 95% of the design thickness 40 41 42 1.2 Reference Codes, Standards, and Documents: 43 44

2 30 November 2011 3 4 1 User Note - Sputo and Lammert

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

1

SDI-C-2011 Standard for Composite Steel Floor Deck-Slabs 1 30 November 2011 2

3

1. General 4

5

1.1 Scope: 6

A. This Standard for Composite Steel Floor Deck-Slabs, hereafter referred to as the 7

Standard, shall govern the materials, design, and erection of composite concrete slabs 8

utilizing cold formed steel deck functioning as a permanent form and as reinforcement 9

for positive moment in floor and roof applications in buildings and similar structures. 10

B. The Appendices shall be part of the Standard. 11

C. The User Notes, User Note Attachments, and Commentary shall not be part of the 12

Standard. 13

14

User Note: User Notes, User Note Attachments, and Commentary are intended to 15

provide practical guidance in the use and application of this Standard. 16

17

D. Where the Standard refers to “designer,” this shall mean the entity that is responsible to 18

the Owner for the overall structural design of the project, including the steel deck. 19

20

User Note: This is usually the Structural Engineer of Record. 21

22

E. Equations that appear in this Standard are compatible with the inch-pounds system of 23

units. However, any consistent system of units shall be permitted to be used. SI units 24

or equations shown in parentheses in this standard are for information only, and are not 25

part of this Standard. 26

F. Terms not defined in this Standard, AISI S100 or AISI/AISC shall have the ordinary 27

accepted meaning for the context for which they are intended. 28

G. It shall be permitted to specify deck base metal thickness either by dimensional 29

thickness, or by gage when the relationship of base metal thickness to gage has been 30

defined by the deck manufacturer. However, for the purpose of design, the 31

dimensional thickness shall be used. 32

33

User Note: Both AISI and SDI now specify steel thickness in terms of design 34

thickness in lieu of gage thickness. Gage thicknesses, however, are still commonly 35

referred to in the metal deck industry. Table UN-1.1 shows common gages and 36

corresponding uncoated design and minimum steel thicknesses. 37

38

Table UN-1.1 39

Gage No. Design Thickness Minimum Thickness1

in. mm. in. mm.

22 0.0295 0.75 0.028 0.71

20 0.0358 0.91 0.034 0.86

18 0.0474 1.20 0.045 1.14

16 0.0598 1.52 0.057 1.44

1 Minimum thickness is 95% of the design thickness 40 41

42

1.2 Reference Codes, Standards, and Documents: 43

44

2

A. Codes and Standards: The following documents or portions thereof are referenced in 45

this standard and shall be considered part of the requirements of this Standard. Where 46

these documents conflict with this standard, the requirements of this Standard shall 47

control: 48

: 49

1. American Concrete Institute (ACI) 50

a. ACI 318-11, Building Code Requirements for Structural Concrete 51

2. American Iron and Steel Institute (AISI) 52

a. AISI S100-07 w/S2-10, North American Specification for the Design of 53

Cold-Formed Steel Structural Members, Including Supplement 2 54

(February 2010) 55

b. AISI S905-08, Test Methods for Mechanically Fastened Cold-Formed 56

Steel Connections 57

c. AISI S907-08, Test Standard for Cantilever Test Method for Cold-58

Formed Steel Diaphragms 59

d. AISI/AISC, Standard Definitions for Use in the Design of Steel 60

Structures, 2007 edition 61

3. American Institute of Steel Construction (AISC) 62

a. ANSI/AISC 360-10, Specification for Structural Steel Buildings 63

4. American Society for Testing and Materials (ASTM) 64

a. ASTM A615 / A615M - 09b Standard Specification for Deformed and 65

Plain Carbon-Steel Bars for Concrete Reinforcement 66

b. ASTM A653 / A653M - 10 Standard Specification for Steel Sheet, 67

Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by 68

the Hot-Dip Process 69

c. ASTM A706 / A706M - 09b Standard Specification for Low-Alloy 70

Steel Deformed and Plain Bars for Concrete Reinforcement 71

d. ASTM A820 / A820M – 06, Standard Specification for Steel Fibers for 72

Fiber-Reinforced Concrete 73

e. ASTM A1008 / A1008M - 10, Standard Specification for Steel, Sheet, 74

Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-75

Strength Low-Alloy with Improved Formability, Solution Hardened, 76

and Bake Hardenable 77

f. ASTM A1064 / A1064M - 10 Standard Specification for Steel Wire and 78

Welded Wire Reinforcement, Plain and Deformed, for Concrete 79

g. ASTM C1116 / C1116M - 10 Standard Specification for Fiber-80

Reinforced Concrete 81

h. ASTM D7508 / D7508M - 10 Standard Specification for Polyolefin 82

Chopped Strands for Use in Concrete 83

5. American Society of Civil Engineers (ASCE) 84

a. SEI/ASCE 7-10, Minimum Design Loads for Buildings and Other 85

Structures 86

6. American Welding Society (AWS) 87

a. AWS D1.1:2010, Structural Welding Code-Steel 88

b. AWS D1.3:2008, Structural Welding Code-Sheet Steel 89

7. Steel Deck Institute (SDI) 90

a. SDI-T-CD-2011, Test Standard for Composite Steel Deck-Slabs 91

92

3

B. Reference Documents: The following documents or portions thereof are referenced in 93

this standard and shall be considered part of the requirements of this Standard. Where 94

these documents conflict with this standard, requirements of this Standard shall govern: 95

1. Steel Deck Institute (SDI) 96

a. SDI-DDM, Diaphragm Design Manual, 3rd

Edition, including 97

Appendices I through VI 98

99

User Note: The following documents are referenced within the user notes: 100

1. American Association of State Highway and Transportation Officials 101

(AASHTO) 102

a. AASHTO LRFD Bridge Design Specifications, Customary U.S. Units, 103

5th Edition, with 2010 Interim Revisions 104

2. American Concrete Institute (ACI) 105

a. ACI 215R-92, Considerations for Design of Concrete Structures 106

Subjected to Fatigue Loading 107

b. ACI 302.1R-04, Guide for Concrete Floor and Slab Construction 108

c. ACI 224.1R-07, Causes, Evaluation, and Repair of Cracks in Concrete 109

Structures 110

d. ACI 318-11, Building Code Requirements for Structural Concrete 111

e. ACI 544 3R-08, Guide for the Specification, Proportioning and 112

Production of Fiber Reinforced Concrete 113

f. ACI Concrete Terminology, http://terminology.concrete.org 114

3. American Institute of Steel Construction (AISC) 115

a. AISC Design Guide No. 11, Floor Vibrations Due to Human Activity, 116

1997 117

4. American Iron and Steel Institute (AISI) 118

a. AISI S100-07 w/S2-10, North American Specification for the Design of 119

Cold-Formed Steel Structural Members, Including Supplement 2 120

(February 2010) 121

b. AISI S907-08, Test Standard for Cantilever Test Method for Cold-122

Formed Steel Diaphragms 123

5. American Society for Testing and Materials (ASTM) 124

a. ASTM A653 / A653M - 10 Standard Specification for Steel Sheet, 125

Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by 126

the Hot-Dip Process 127

b. ASTM A1008 / A1008M - 10, Standard Specification for Steel, Sheet, 128

Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-129

Strength Low-Alloy with Improved Formability, Solution Hardened, 130

and Bake Hardenable 131

c. ASTM E119 - 10b,, Standard Test Methods for Fire Tests of Building 132

Construction and Materials 133

6. Concrete Reinforcing Steel Institute (CRSI) 134

a. CRSI Manual of Standard Practice, 28th

Edition, 2009 135

7. Steel Deck Institute (SDI) 136

a. SDI-CDD, Composite Deck Design Handbook, 2nd

Edition 137

b. SDI-DDM, Diaphragm Design Manual, 3rd

Edition, including 138

Appendices I through VI 139

c. SDI-MDCQ, Metal Deck and Concrete Quantities (SDI White Paper) 140

d. SDI-MOC, Manual of Construction with Steel Deck, 2nd

Edition 141

4

e. SDI Position Statement “Use of Composite Steel Floor Deck in Parking 142

Garages.” 143

8. Underwriters Laboratories (UL) 144

a. Fire Resistance Directory 145

9. Wire Reinforcing Institute (WRI) 146

a. WWR-500-R-10, Manual of Standard Practice-Structural Welded Wire 147

Reinforcement 148

149

1.3 Construction Documents: The construction documents shall describe the composite slabs that 150

are to be constructed and shall include not less than the following information: 151

A. Loads 152

1. Composite slab loads as required by the applicable building code. Where 153

applicable, load information shall include concentrated loads. 154

2. Assumed construction phase loads. 155

B. Structural framing plans for all composite slabs showing the size, location and type of 156

all deck supports. 157

C. Deck and Deck Attachment 158

1. Depth, type (profile), and design thickness. 159

2. Deck material (including yield strength) and deck finish, 160

3. Deck attachment type, spacing, and details. 161

D. Concrete and Reinforcing 162

1. Specified concrete strength, f’c 163

2. Specified concrete density (and tolerance if required for fire rating assembly) 164

3. Specified strength or grade of reinforcing steel or welded wire reinforcement (if 165

used) 166

4. Size, extent and location of all reinforcement (if used) 167

5. Slab thicknesses 168

6. Discontinuous fiber reinforcement material, type and dosage (if used). 169

170

User Note: The following is an example of a composite slab as it could be specified 171

on the contract drawings: “Composite slab shall consist of 2 inch deep G-60 172

galvanized composite steel deck, design thickness 0.0358 inch (20 gage), (Type XX by 173

XX, Inc or approved equivalent) with 3 inch thick, 3000 psi, normal-weight concrete 174

topping (total thickness = 5 inches) reinforced with XXX.” 175

176

2. Products 177

178

2.1 Material: 179

180

A. All sheet steel used for deck or accessories shall have a minimum specified yield stress 181

that meets or exceeds 33 ksi (230 Mpa). 182

1 For the case where the steel deck acts as a form, design yield and tensile 183

stresses shall be determined in accordance with AISI S100, Section A2. 184

2. For the case where the steel deck acts as tensile reinforcement for the composite 185

deck-slab, the steel shall conform to AISI S100, Section A2. When the ductility 186

of the steel measured over a two-inch (50 mm) gage length is 10% or greater, 187

the maximum design yield stress shall not exceed the lesser of 50 ksi or Fy. 188

When the ductility of the steel measured over a two-inch (50 mm) gage length 189

is less than 10%, the maximum design yield stress shall not exceed the lesser of 190

50 ksi (345 Mpa) or 0.75 Fy. 191

5

3. When the ductility of the steel used for deck, measured over a two-inch (50 192

mm) gage length, is less than 10%, the ability of the steel to be formed without 193

cracking or splitting shall be demonstrated. 194

195

B. Sheet steel for deck shall conform to AISI S100, Section A2. 196

197

Commentary: Most steel deck is manufactured from steel conforming to ASTM 198

A1008 /A1008M, Structural Sheet for uncoated or uncoated top/painted bottom deck or 199

from ASTM A653 / A653M, Structural Sheet for galvanized deck. In most cases the 200

designer will choose one finish or the other. However, both types of finish may be 201

used on a project, in which case the designer must indicate on the plans and project 202

specifications the areas in which each is used. (Refer to Section 2.3 of this standard). 203

Stainless steel is not recommended due to the lack of available performance data. 204

205

C. Sheet steel for accessories that carry defined loads shall conform to AISI S100, Section 206

A2. Sheet steel for non-structural accessories that do not carry defined loads shall be 207

permitted to be any steel that is adequate for the proposed application. 208

D. Concrete and Reinforcement: 209

1. Concrete placed on steel deck shall conform to ACI 318, Chapters 3, 4 and 5, 210

except as modified by Sections 2.1.D.2 and 2.1.D.3. 211

2. The specified concrete compressive strength shall not be less than 3000 psi (21 212

MPa). The maximum compressive strength used to calculate the strength of the 213

composite deck-slab shall not exceed 6000 psi (42 MPa). 214

215

User Note: Load tables and labeled fire resistant rated assemblies may require concrete 216

compressive strengths in excess of 3000 psi. The average compressive strength of the 217

concrete may exceed 6000 psi, but a maximum strength of 6000 psi is to be used in 218

calculating the strength of the composite deck-slab. 219

220

3. Admixtures containing chloride salts or other substances that are corrosive or 221

otherwise deleterious to the steel deck and embedded items shall not be 222

permitted. 223

4. Steel Reinforcing shall conform to the following: 224

a. Deformed reinforcing bars: ASTM A615 or ASTM A706. 225

b. Welded wire reinforcement: ASTM A1064. 226

c. Other deformed reinforcing bars or welded wire reinforcement as 227

permitted by ACI 318, Section 3.5.3. 228

5. Discontinuous fiber reinforcement shall conform to the following: 229

a. Steel fibers: ASTM A820. 230

b. Macrosynthetic fibers: ASTM D7508. 231

232

2.2 Tolerance of Delivered Material: 233

A. The minimum uncoated steel thickness as delivered to the job site shall not at any 234

location be less than 95% of the design thickness, however lesser thicknesses shall be 235

permitted at bends, such as corners, due to cold-forming effects. 236

237

User Note: The minimum delivered thickness is in accordance with AISI S100. 238

239

B. Panel length shall equal the specified panel length, plus or minus ½ inch (13mm). 240

C. Panel cover width shall be no less than 3/8 inch (10 mm) less than the specified panel 241

width, nor more than 3/4 inch (19 mm) greater than the specified width. 242

6

D. Panel camber and/or sweep shall not be greater than 1/4 inch in a 10 foot length (6 mm 243

in 3 m). 244

E. Panel end out of square shall not exceed 1/8 inch per foot of panel width (10 mm per 245

m). 246

247 2.3 Finish: 248

A. Galvanizing shall conform to ASTM A653 / A653M 249

B. A shop coat of primer paint (bottom side only) shall be applied to steel sheet if 250

specified by the designer. 251

C. The finish on the steel deck shall be specified by the designer. 252

253

Commentary: The finish on the steel composite deck must be specified by the 254

designer and be suitable for the environment to which the deck is exposed within the 255

finished structure. Because the composite deck is the positive bending reinforcement 256

for the slab, its service life should at least be equal to the design service live of the 257

structure. Zinc-Aluminum finishes are not recommended. When composite deck with 258

an unpainted top and painted bottom is used, the primer coat is intended to protect the 259

steel for only a short period of exposure in ordinary atmospheric conditions and shall 260

be considered an impermanent and provisional coating. In highly corrosive or chemical 261

atmospheres or where reactive materials could be in contact with the steel deck, special 262

care in specifying the finish should be used, which could include specialized coatings 263

or materials. If specifying painted deck in areas that require spray-on fireproofing, the 264

paint must be permitted by the applicable fire rated assembly. Not all paints are 265

approved for fire rated assemblies. This requirement must be clearly called out in the 266

contract documents. In general, there are three types of fire resistive assemblies; those 267

achieving the fire resistance by membrane protection, direct applied protection, or with 268

an unprotected assembly. Of these three, only the systems that utilize direct applied 269

protection are concerned with the finish of the steel deck. In these systems, the finish 270

of the steel deck can be the factor that governs the fire resistance rating that is 271

achieved. In assemblies with direct applied fire protection the finish (paint) is critical. 272

In the Underwriters Laboratories Fire Resistance Directory, some deck manufacturing 273

companies have steel deck units that are classified in some of the D700, D800, and 274

D900-series concrete and steel floor units. These classified deck units (Classified Steel 275

Floor and Form Units) are shown as having a galvanized finish or a 276

phosphatized/painted finish. These classified deck units have been evaluated for use in 277

these specific designs and found acceptable. 278

279

280

2.4 Design: 281

A. Deck as a form 282

1. Design by either Allowable Strength Design (ASD) or Load and Resistance 283

Factor Design (LRFD) shall be permitted. The section properties and allowable 284

strength (ASD) or design strength (LRFD) for the steel deck shall be computed 285

in accordance with AISI S100. 286

2. Deck shall be evaluated for strength under the following load combinations: 287

a. Allowable Stress Design 288

289

wdc + wdd + wlc (Eq. 2.4.1) 290

291

wdc + wdd + Plc (Eq. 2.4.2) 292

293

7

wdd + wcdl (Eq. 2.4.3) 294

295

Where: 296

wdc = dead weight of concrete 297

wdd = dead weight of the steel deck 298

wlc = uniform construction live load (combined with fluid 299

concrete) not less than 20 psf (0.96 kPa) 300

wcdl = uniform construction live load (combined with bare 301

deck), not less than 50 psf (2.40 kPa) 302

Plc = concentrated construction live load per unit width of 303

pounds on a 1 foot width (2.19 kN on a 1 meter width) 304

305

User Note: The uniform construction live load of 20 psf is considered adequate for 306

typical construction applications that consist of concrete transport and placement by 307

hose and concrete finishing using hand tools. The designer typically has little control 308

over means-and-methods of construction, and should bring to the attention of the 309

constructor that bulk dumping of concrete using buckets, chutes, or handcarts, or the 310

use of heavier motorized finishing equipment such as power screeds, may require 311

design of the deck as a form using uniform construction live loads, wlc ,of 50 psf or 312

greater. Section A1.3.1 requires that the designer include the assumed construction 313

loads in the construction documents and it is suggested that the constructions 314

documents require verification of adequacy by the constructor. 315

316

User Note: The designer should account for additional loads attributable to concrete 317

ponding due to deflections of the structural system, including deck and support 318

framing. See SDI-MDCQ for additional information. 319

320

b. Load and Resistance Factor Design 321

322

1.6wdc + 1.2wdd + 1.4wlc (Eq. 2.4.4) 323

324

1.6wdc + 1.2wdd + 1.4Plc (Eq. 2.4.5) 325

326

1.2wdd + 1.4wcdl (Eq. 2.4.6) 327

328

Commentary: The load factor used for the dead weight of the concrete is 1.6 because 329

of delivering methods and an individual sheet can be subjected to this load. The use of 330

a load factor of 1.4 for construction load in LRFD design is calibrated to provide 331

equivalent design results in ASD design. Refer to the commentary of AISI S100 for 332

additional information. 333

334

3. Cantilever spans shall be evaluated for strength under the following load 335

combinations: 336

a. Allowable Strength Design: Equations 2.4.1 and 2.4.2 shall be applied 337

to both the cantilever span and the adjacent span. The concentrated 338

construction live load (Plc) shall be applied at the end of the cantilever. 339

b. Load and Resistance Factor Design: Equations 2.4.4 and 2.4.5 shall be 340

applied to both the cantilever span and the adjacent span. The 341

concentrated construction live load (Plc) shall be applied at the end of 342

the cantilever. 343

4. Special loading considerations: 344

8

a. The specified construction live loads shall be increased when required 345

by construction operations. 346

b. Loads shall be applied in a sequence that simulates the placement of the 347

concrete, in accordance with Appendix 1. Rational analysis shall be 348

permitted to be used for developing shear and moment diagrams and 349

calculating deflections for non-uniform spans. 350

351

Commentary: The loading shown in Figure 1 of Appendix 1 is representative of the 352

sequential loading of fresh concrete on the deck. The 150 pound per foot of width (2.19 353

kN per 1 m of width) load is the equivalent of distributing a 300 pound (1.33 kN) 354

worker over a 2 foot (600 mm) width. Experience has shown this to be a conservative 355

distribution. 356

357

Single span deck conditions have no redundancy because they are statically 358

determinate, as opposed to multi-span conditions that are statically indeterminate. 359

Because of this lack of redundancy, additional consideration should be given to proper 360

specification of construction live and dead loads. Allowable construction spans for 361

single-span deck may be shorter than for multi-span applications, and the designer 362

must consider this in locations where it is impossible to install the deck in a multi-span 363

condition, such as between stair and elevator towers. Whenever possible, the deck 364

should be designed as a multi-span system that does not require shoring during 365

concrete placement. 366

The specified construction live loads reflect nominal loads from workers and 367

tools and do not include loads of equipment such as laser screeds or power trowels nor 368

additional concrete weight due to ponding. If anticipated construction activities 369

include these additional loads, they should be considered in the design. 370

371 5. Deck Deflection 372

a. Calculated deflections of the deck as a form shall be based on the load 373

of the concrete as determined by the design slab thickness and the self-374

weight of the steel deck, uniformly loaded on all spans, shall be limited 375

to the lesser of 1/180 of the clear span or 3/4 inch (19 mm). Calculated 376

deflections shall be relative to supporting members. 377

b. The deflection of cantilevered deck as a form, as determined by slab 378

thickness and self-weight of the steel deck, shall not exceed a/90, where 379

“a” is the cantilever length, nor 3/4 inches (19 mm). 380

381

Commentary: The deflection calculations do not take into account construction loads 382

because these are considered to be temporary loads. The deck is designed to always be 383

in the elastic range, so removal of temporary loads will allow the deck to recover, 384

unless construction overloads cause the stress in the deck to exceed the elastic limits of 385

the deck. The supporting structural steel also deflects under the loading of the concrete. 386

The designer is urged to check the deflection of the total system. Typical load 387

tables are based on uniform slab thickness. If the designer wants to include additional 388

concrete loading on the deck because of frame deflection, the additional load should be 389

shown on the design drawings or stated in the deck section of the contract documents. 390

391

6. Minimum Bearing and Edge Distance: Minimum bearing lengths and fastener 392

edge distances shall be determined in accordance with AISI S100. 393

394

9

User Note: Figure 2 in Appendix 1 indicates support reactions. The designer should 395

check the deck web crippling capacity based on available bearing length. 396

397

7. Diaphragm Shear Capacity: Diaphragm strength and stiffness shall be 398

determined utilizing the bare steel deck capacity without concrete in accordance 399

with: 400

a. SDI-DDM 401

b. Tests conducted in accordance with AISI S907 402

c. Other methods approved by the building official. 403

404

Commentary: Unless otherwise required by the governing building code, safety 405

factors and resistance factors should be as shown in Table D5 of AISI S100 for bare 406

steel deck diaphragms. When SDI-DDM is the basis of diaphragm design, fasteners 407

and welds that do not have flexibility and strength properties listed in SDI-DDM 408

Section 4 can demonstrate flexibility and strength properties through testing in 409

accordance with AISI S905 or other testing methods. Fastener or weld strength 410

defined in AISI S100 or other methods can be used with the SDI-DDM method. 411

It is always conservative to neglect the contribution of sidelap connections to 412

diaphragm strength and stiffness. Side lap fillet weld and top seam and side seam weld 413

flexibility can be calculated in accordance with SDI-DDM Section 4.4 and sidelap fillet 414

weld and side seam weld strength can be calculated in accordance with AISI S100. 415

416

8. Connections: Deck shall be attached to supports to resist loads and to provide 417

structural stability for the supporting member Connections shall be designed 418

in accordance with AISI S100 or strengths shall be determined by testing in 419

accordance with AISI S905. Tests shall be representative of the design. When 420

tests are used and the design allows either end laps or single thickness 421

conditions, both conditions shall be tested. 422

423

B. Deck and Concrete as a Composite Slab: 424

1. Strength: Strength of the composite deck-slab shall be determined in 425

accordance with one of the following methods 426

a. “Prequalified Section Method” as per Appendix 2. 427

b. “Shear Bond Method” as per Appendix 3. 428

c. Full scale performance testing as per SDI-T-CD. 429

d. Other methods approved by the building official. 430

2. Deck shall be evaluated for strength under the load combinations required by 431

the applicable building code. In the absence of a building code, the load 432

combinations prescribed by ASCE 7 shall be used. 433

3. Load Determination: The superimposed load capacity shall be determined by 434

deducting the weight of the slab and the deck from the total load capacity. 435

Unless composite deck-slabs are designed for continuity, slabs shall be assumed 436

to act on simple spans. 437

438 Commentary: Most published live load tables are based on simple span analysis of 439

the composite system; that is, a continuous slab is assumed to crack over each support 440

and to carry load as a series of simple spans. 441

442

Commentary: By using the reference analysis techniques or test results, the deck 443

manufacturer determines the live loads that can be applied to the composite deck-slab 444

combination. The results are usually published as uniform load tables. For most 445

10

applications, the deck thickness and profile is selected so that shoring is not required; 446

the live load capacity of the composite system is usually more than adequate for the 447

superimposed live loads. In calculating the section properties of the deck, AISI S100 448

may require that compression zones in the deck be reduced to an “effective width,” but 449

as tensile reinforcement, the total area of the cross section may be used. (See 450

Appendix 3) 451

Coatings other than those tested may be investigated, and if there is evidence 452

that their performance is better than that of the tested product, additional testing may 453

not be required. 454

455

4. Concrete: Specified concrete compressive strength (f’c) shall comply with 456

Section 2.1 and shall not be less then 3000 psi (21 MPa), nor less than that 457

required for fire resistance ratings or durability. 458

459 Commentary: Load tables are generally calculated by using a concrete strength of 460

3000 psi (21 MPa). Composite slab capacities are not greatly affected by variations in 461

concrete compressive strength; but if the strength falls below 3000 psi (21 MPa), it 462

would be advisable to check shear anchor design for composite beam action. 463

464

a. Minimum Cover: The concrete thickness above the top of the steel deck 465

shall not be less than 2 inches (50 mm), nor that required by any 466

applicable fire resistance rating requirements. Minimum concrete cover 467

for reinforcement shall be in accordance with ACI 318. 468

5. Deflection: Deflection of the composite slab shall be in accordance with the 469

requirements of the applicable building code. 470

a. Cross section properties shall be calculated in accordance with 471

Appendix 4. 472

b. Additional deflections resulting from concrete creep, where applicable, 473

shall be calculated by multiplying the immediate elastic deflection due 474

to the sustained load by the following factors: 475

i. (1.0) for load duration of 3 months 476

ii. (1.2) for load duration of 6 months 477

iii. (1.4) for load duration of 1 year 478

iv. (2.0) for load duration of 5 years. 479

480

Commentary: Live load deflections are seldom a controlling design factor. A 481

superimposed live load deflection of span/360 is typically considered to be acceptable. 482

The deflection of the slab/deck combination can be predicted by using the average of 483

the cracked and uncracked moments of inertia as determined by the transformed 484

section method of analysis. Refer to Appendix 4 of this standard or SDI-CDD. 485

486

User Note: Limited information on creep deflections is available. This method is 487

similar to the procedure for reinforced concrete slabs. Because the steel deck initially 488

carries the weight of the concrete, only the superimposed loads should be considered 489

when creep deflections are a concern. 490

491

492

User Note: Floor vibration performance is the result of the behavior of entire floor 493

system, including the support framing. The designer should check vibration 494

performance using commonly accepted methods, which may include AISC Design 495

Guide No. 11. 496

11

497

6. Special Loads: The following loads shall be considered in the analysis and 498

calculations for strength and deflection: 499

a. Suspended Loads. 500

b. Concentrated Loads 501

c. Moving Loads 502

d. Cyclic Loads 503

504

7. One-way Shear Strength: This section shall be used to determine the one-way 505

shear strength of the composite deck-slab. 506

507

ccvDscvn AfVVV '4φφφφ ≤+= (Eq. 2.4.7a) (in-lb) 508

ccvDscvn AfVVV '172.0φφφφ ≤+= (Eq. 2.4.7b) (SI) 509

510

Where: 511

512

ccc AfV'2λ= (Eq. 2.4.8a) (in-lb) 513

ccc AfV'086.0 λ= (Eq. 2.4.8b) (SI) 514

515

VD = shear strength of the steel deck section calculated in accordance 516

with AISI S100, kips (kN) 517

Ac = concrete area available to resist shear, in2 (mm

2), see Figure 2-1. 518

λ = 1.0 where concrete density exceeds 130 lbs/ft3

(2100 kg/m3); 519

0.75 where concrete density is equal to or less than 130 lbs/ft3

520

(2100 kg/m3). 521

φv = 0.75 522

φs = 0.85 523

12

524 525

Figure 2-1 One-Way Shear Parameters 526 527

8. Punching Shear Resistance: The critical surface for calculating punching shear 528

shall be perpendicular to the plane of the slab and located outside of the 529

periphery of the concentrated load or reaction area. The factored punching 530

shear resistance, Vpr, shall be determined as follows: 531

532

( ) cocvcocvcpr hbfhbfV '4'42 φφβ ≤+= (Eq. 2.4.9a) (in-lb) 533

( ) cocvcocvcpr hbfhbfV '172.0'42043.0 φφβ ≤+= (Eq. 2.4.9b) (SI) 534

535

Where: 536

bo = perimeter of critical section, in. (mm) 537

hc = thickness of concrete cover above steel deck, in. (mm) 538

βc = ratio of long side to short side of concentrated load or reaction 539

area 540

φv = 0.75 541

542

9. Concentrated Loads: Concentrated loads shall be permitted to be laterally 543

distributed perpendicular to the deck ribs in accordance with this section. 544

13

Alternate lateral load distributions based on rational analysis shall be permitted 545

when allowed by the building official. 546

a. Concentrated loads shall be distributed laterally (perpendicular to the 547

ribs of the deck) over an effective width, be. The load distribution over 548

the effective width, be, shall be uniform. 549

b. The concrete above the top of steel deck shall be designed as a 550

reinforced concrete slab in accordance with ACI 318, transverse to the 551

deck ribs, to resist the weak axis moment, Mwa, over a width of slab 552

equal to W. Appropriate load factors as required by ACI 318 shall be 553

applied to the weak axis moment. 554

555

bm = b2 + 2 tc + 2 tt (Eq. 2.4.10) 556

557

be = bm + (2)(1-x/L)x ≤ 106.8 (tc/h) for single 558

span bending (Eq. 2.4.11) 559

560

be = bm + (4/3)(1-x/L)x ≤ 106.8 (tc/h) for 561

continuous span bending when reinforcing steel is provided in the 562

concrete to develop negative bending. (Eq. 2.4.12) 563

564

be = bm + (1-x/L)x ≤ 106.8 (tc/h) for shear 565

(Eq. 2.4.13) 566

567

W = L/2 + b3 ≤ L (Eq. 2.4.14) 568

569

Mwa = 12 P be / (15W) in-lb per foot [ P be / (15 W) N-570

mm per mm ] (Eq. 2.4.15) 571

572

Where: 573

574

be = Effective width of concentrated load, perpendicular to 575

the deck ribs, in (mm) 576

bm = Projected width of concentrated load, perpendicular to 577

the deck ribs, measured at top of steel deck, in (mm) 578

b2 = Width of bearing perpendicular to the deck ribs, in (mm) 579

b3 = Length of bearing parallel to the deck ribs, in (mm) 580

h = Depth of composite deck-slab, measured from bottom of 581

steel deck to top of concrete slab, in (mm) 582

L = Deck span length, measured from centers of supports, in 583

(mm) 584

Mwa = Weak axis bending moment, perpendicular to deck ribs, 585

of width, in.-lbs, (N-mm per mm of width) 586

P = Magnitude of concentrated load, lbs (N) 587

tc = Thickness of concrete above top of steel deck, in (mm) 588

tt = Thickness of rigid topping above structural concrete (if 589

any), in (mm) 590

W = Effective length of concentrated load, parallel to the deck 591

ribs, in (mm) 592

x = Distance from center of concentrated load to nearest 593

support, in (mm) 594

595

14

596 Figure 2-2 597

598

599 600

Figure 2-3 601 602

15

User Note: Figures 2-2 and 2-3 illustrate the dimensions associated with this section. 603

604

Commentary: The designer should take into account the sequence of loading. 605

Suspended loads may include ceilings, light fixtures, ducts or other utilities. The 606

designer should be informed of any loads to be applied after the composite slab has 607

been installed. Care should be used during the placement of suspended loads on all 608

types of hanger tabs or other hanging devices for the support of ceilings so that an 609

approximate uniform loading is maintained. The individual manufacturer should be 610

consulted for allowable loading on single hanger tabs. Improper use of hanger tabs or 611

other hanging devices could result in the overstressing of tabs and/or the overloading of 612

the composite deck-slab. 613

614 Commentary: Composite floor deck is not recommended as the only concrete 615

reinforcement for use in applications where the floor is loaded with repeated lift truck 616

(forklift) or similar heavy wheeled traffic. (Lift trucks are defined as small power 617

operated vehicles that have devices for lifting and moving product. The definition of 618

lift trucks does not include manually operated “pallet jacks.”) Loading from lift trucks 619

includes not only moving gravity loads, but also includes vertical impact loading and 620

in-plane loading effects from starting, stopping, and turning. The repetitive nature of 621

this loading, including impact, fatigue, and in-plane effects can be more detrimental to 622

the slab-deck performance than the gravity loads. Suspended floor slabs subjected to 623

lift truck traffic have special design requirements to ensure the fatigue stress in the 624

reinforcement is low to keep the cracks sufficiently tight and serviceable to minimize 625

crack spalling due to the hard wheel traffic. The design should only use the steel deck 626

as a stay-in-place form. Structural concrete design recommendations contained in ACI 627

215R and AASHTO-LRFD are suggested for guidance in the design of these slabs. 628

Due consideration for the stiffness of the supporting framing should be given by the 629

designer. 630

Composite floor deck has successfully been used in applications that are loaded 631

by occasional “scissor lift” use, and in warehouses with industrial racks without lift 632

truck traffic and in areas serviced by “pallet jacks.” Proper analysis and design for 633

moving and point loads must be performed. 634

635

Commentary: For additional information regarding the use of composite steel deck in 636

parking structure applications, refer to the SDI Position Statement “Use of Composite 637

Steel Floor Deck in Parking Garages.” 638

639

10. Negative Reinforcement: When the slab is designed for negative moments, the 640

deck shall be designed to act in the negative moment region only as a permanent form. 641

Concrete in negative moment regions shall be designed by the designer as a 642

conventional reinforced concrete slab in accordance with ACI 318. Design moments 643

and shears shall be permitted to be calculated by any acceptable method of analysis 644

which considers continuity. The coefficient method of Chapter 8 of ACI 318 shall be 645

considered to be an acceptable analysis method. 646

647

Commentary: Composite steel deck does not function as compression reinforcing 648

steel in areas of negative moment. If the designer desires a continuous slab, then 649

negative bending reinforcing should be designed using conventional reinforced 650

concrete design techniques in compliance with ACI 318. The reinforcement chosen for 651

temperature and shrinkage reinforcement most likely will not supply sufficient area of 652

reinforcement for negative bending over the supports. 653

16

654

11. Cantilevered Slabs: At cantilevered slabs, the deck shall be considered to act 655

only as a permanent form. The slab shall be designed by the designer for 656

negative bending in accordance with ACI 318. 657

658

Commentary: At cantilevered slabs, the deck acts only as a permanent form. 659

Composite steel deck does not function as compression reinforcing steel at cantilevers. 660

Negative bending reinforcing at the cantilever should be designed using conventional 661

reinforced concrete design techniques in compliance with ACI 318. The reinforcement 662

chosen for temperature and shrinkage reinforcing most likely will not supply sufficient 663

area of reinforcement for negative bending at the cantilever. 664

665

12. Diaphragm Shear Capacity: Diaphragm strength and stiffness shall be 666

determined in accordance with: 667

a. SDI-DDM 668

b. Tests conducted in accordance with AISI S907 669

c. Other methods approved by the building official. 670

671

Commentary: Unless otherwise required by the governing building code, when using 672

the SDI-DDM method, the safety and resistance factors found in the SDI-DDM should 673

be used, When SDI-DDM is the basis of diaphragm design, fasteners and welds that do 674

not have flexibility and strength properties listed in SDI-DDM Section 4 can 675

demonstrate flexibility and strength properties through testing in accordance with AISI 676

S905 or other testing methods. Fastener or weld strength defined in AISI S100 or other 677

methods can be used with the SDI-DDM method. It is always conservative to neglect 678

the contribution of sidelap connections to diaphragm strength and stiffness. Side lap 679

fillet weld and top seam and side seam weld flexibility can be calculated in accordance 680

with SDI-DDM Section 4.4 and sidelap fillet weld and side seam weld strength can be 681

calculated in accordance with AISI S100. 682

When strength is based on test, the safety and resistance factors should be determined 683

in accordance with AISI S100 Chapter F, but should shall not be less critical than those 684

for concrete diaphragms contained in ACI 318, Section 9.3. The following statistical 685

data may be used with AISI S100 for calculating the resistance factor: 686

βo = 3.50 687

Mm = 1.10 688

Vm = 0.10 689

Fm = 0.90 690

Vf = 0.10 691

Pm = 1.00 692

This statistical data is based on a connection limit state, and is differs from the data in 693

the SDI T-CD standard for gravity loads. When using this data, the factor if safety 694

should be calculated in accordance with AISI S100, Section F. 695

696

User Note: In instances where the required diaphragm capacity exceeds what can be 697

calculated using SDI-DDM, a designer can potentially develop additional capacity by 698

designing the diaphragm as a reinforced concrete diaphragm in accordance with ACI 699

318. This design option as a concrete diaphragm is outside the scope of this standard. 700

701

13. Reinforcement for Temperature and Shrinkage: 702

17

a. Reinforcement for crack control purposes other than to resist stresses 703

from quantifiable structural loadings shall be permitted to be provided 704

by one of the following methods: 705

1. Welded wire reinforcement or reinforcing bars with a minimum 706

area of 0.00075 times the area of the concrete above the deck 707

(per foot or meter of width), but not be less than the area 708

provided by 6 x 6 – W1.4 x W1.4 (152 x 152 – MW9 x MW9) 709

welded wire reinforcement. 710

2. Concrete specified in accordance with ASTM C1116, Type I, 711

containing steel fibers meeting the criteria of ASTM A820, Type 712

I , Type II, or Type V, at a dosage rate determined by the fiber 713

manufacturer for the application, but not less than 25 lb/cu yd 714

(14.8 kg/cu meter). 715

3. Concrete specified in accordance with ASTM C1116, Type III, 716

containing macrosynthetic fibers meeting the criteria of ASTM 717

D7508 at a dosage rate determined by the fiber manufacturer for 718

the application, but not less than 4 lb./cu yd (2.4 kg/m3). 719

720

721

User Note: It is suggested that if fibers are used for this purpose, that the designer 722

include quality control provisions in accordance with ACI 544 3R in the project 723

specifications. 724

725 Commentary: Concrete floor slabs employing Portland cement will start to 726

experience a reduction in volume as soon as they are placed. Where shrinkage is 727

restrained, cracking will occur in the floor. The use of the appropriate types and 728

amount of reinforcement for shrinkage and temperature movement control is intended 729

to result in a larger number of small cracks in lieu of a fewer number of larger cracks. 730

Even with the best floor design and proper construction, it is unrealistic to expect crack 731

free floors. Every owner should be advised by both the designer and contractor that it 732

is normal to expect some amount of cracking and that such occurrence does not 733

necessarily reflect adversely on either the adequacy of the floor’s design or quality of 734

the construction. 735

736

Cracking can be reduced when the causes are understood and preventative steps are 737

taken in the design phase. The major factors that the designer can control concerning 738

shrinkage and cracking include cement type, aggregate type and gradation, water 739

content, water/cement ratio, and reinforcement. 740

741

Most measures that can be taken to reduce concrete shrinkage will also reduce the 742

cracking tendency. Drying shrinkage can be reduced by using less water in the mixture 743

and the largest practical maximum-size aggregate. A lower water content can be 744

achieved by using a well-graded aggregate and lower initial temperature of the 745

concrete. Designers are referred to ACI 302.1R and ACI 224.1 for additional 746

information. 747

748

Although cracking is inevitable, properly placed reinforcement used in adequate 749

amounts will reduce the width of individual cracks. By distributing the shrinkage 750

strains, the cracks are distributed so that a larger number of narrow cracks occur 751

instead of a few wide cracks. Additional consideration by the designer may be 752

required to further limit the size and frequency of cracks. Additional provisions for 753

18

crack control are frequently required where concrete is intended to be exposed, floors 754

that will be subjected to wheel traffic, and floors which will receive an inflexible floor 755

covering material (such as tile). 756

757

Modifications to fiber dosages will vary depending upon the specific fiber 758

manufacturers’ recommendations. As a general rule, reduced crack widths can be 759

achieved by increasing the amount of steel reinforcement or by increasing the fiber 760

dosage and/or minimizing the shrinkage potential of the concrete. 761

762

Because composite deck-slabs are typically designed as a series of simple spans, 763

flexural cracks may form over supports. Flexural cracking of the concrete in negative 764

moment regions of the slab (over beams and girders) is not typically objectionable 765

unless the floor is to be left exposed or covered with inflexible floor coverings. 766

Flexural cracking and crack widths can be minimized by one or more of the following: 767

1.) by paying strict attention to preventing overloads at deck midspan during 768

construction, as this is a common source of flexural cracks; 2.) utilizing a stiffer steel 769

deck; 3.) reducing the slab span. If flexural cracks must be strictly controlled, 770

consideration should be given to designing the composite deck-slab for negative 771

moments over supports (both beams and girders) and providing appropriate reinforcing 772

steel at these supports. 773

774

14. Fire Resistance: The designer shall consider required fire resistance ratings in 775

the design of the composite slab. 776

777

Commentary: Fire rating requirements may dictate the concrete strength or density. 778

Many fire rated assemblies that use composite floor decks are available. In the 779

Underwriters Laboratories Fire Resistance Directory, the composite deck constructions 780

show hourly ratings for restrained and unrestrained assemblies. ASTM E119 provides 781

information in Appendix X3 titled “Guide for Determining Conditions of Restraint for 782

Floor and Roof Assemblies and for Individual Beams”, indicating that deck attached to 783

steel or concrete framing, and interior spans of wall supported deck may be considered 784

to be restrained, while end spans of wall supported deck should be considered to be 785

unrestrained . Designers should be aware that some fire rated assemblies set limits on 786

load capacity and/or place restrictions on fastener type and spacing. 787

788

2.5 Accessories: 789

A. Accessories for structural applications shall be of dimensions and thickness suitable for 790

the application, and shall be designed in accordance with AISI S100 or AISC 360, as 791

applicable. 792

793

Commentary: For convenience, minimum suggested pour stop thicknesses (gages) 794

are shown in User Note Attachment 1. For applications that exceed the scope of the 795

attachment, alternate designs in accordance with AISI S100 and AISC 360 are 796

acceptable. 797

798

3. Execution 799

800

3.1 Installation/General: 801

A. Temporary shoring, if required, shall be designed to resist the loads indicated in 802

Section 2.4.A.2. The shoring shall be designed and installed in accordance with 803

19

standards applicable to the specific shoring system and shall be left in place until the 804

concrete attains 75% of its specified design strength. 805

806

User Note: Typical practice is to retain shoring in place for a minimum of 7 days. 807

808

B. Deck Support Attachment: Steel deck shall be anchored to structural supports by arc 809

spot welds, fillet welds, or mechanical fasteners. The average attachment spacing of 810

deck at supports perpendicular to the span of the deck panel shall not exceed 12 inches 811

(300 mm) on center, with the maximum attachment spacing not to exceed 18 inches 812

(460 mm), unless more frequent fastener spacing is required for diaphragm design. The 813

deck shall be adequately attached to the structure to prevent the deck from slipping off 814

the supporting structure. 815

816

User Note: When the side lap is a standing seam interlock, it may be permissible to 817

only attach the female side, subject to design requirements, when the female hem holds 818

the male leg down. When the side lap is a nestable side lap a single fastener through 819

both sheets of steel deck is acceptable to secure both sheets. 820

821

C. Deck Sidelap Fastening: For deck with spans less than or equal to 5 feet (1.5 m), side 822

lap fasteners shall not be required. unless required for diaphragm design. For deck 823

with spans greater than 5 feet (1.5 m), side laps shall be fastened at intervals not to 824

exceed 36 inches (1 m) on center, unless more frequent fastener spacing is required for 825

diaphragm design, using one of the following methods: 826

1. Screws with a minimum diameter of 0.190 inches (4.83 mm) (#10 diameter) 827

2. Crimp or button punch 828

3. Arc spot welds 5/8 inch (16 mm) minimum visible diameter, minimum 1-1/2 829

inch (38 mm) long fillet weld, or other weld shown to be substantially 830

equivalent through testing in accordance with AISI S905, or by calculation in 831

accordance with AISI S100, or other equivalent method approved by the 832

building official. 833

4. Other equivalent methods approved by the building official. 834

835

User Note: The above side lap spacing is a minimum. Service loads or diaphragm 836

design may require closer spacing or larger side lap welds. Good metal-to-metal 837

contact is necessary for a good side lap weld. When welding, burn holes are to be 838

expected and are not a grounds for rejection. The SDI does not recommend fillet 839

welded or arc spot welded sidelaps for deck that is thinner than 0.0358 inch design 840

thickness (20 gage) due to difficulty in welding thinner material. 841

842

D. Deck Perimeter Attachment Along Edges Between Supports: For deck with spans less 843

than or equal to 5 feet (1.5 m), perimeter attachment shall not be required, unless 844

required for diaphragm design. For deck with spans greater than 5 feet (1.5 m), 845

perimeter edges of deck panels between span supports shall be fastened to supports at 846

intervals not to exceed 36 inches (1 m) on center, unless more frequent fastener spacing 847

is required for diaphragm design, using one of the following methods: 848

1. Screws with a minimum diameter of 0.190 inches (4.83 mm) (#10 849

diameter) 850

2. Arc spot welds with a minimum 5/8 inch (16 mm) minimum visible 851

diameter, or minimum 1-1/2 inch (38 mm) long fillet weld. 852

3. Powder actuated or pneumatically driven fasteners. 853

854

20

User Note: This condition is often referred to as parallel attachment to supports, 855

referring to the support members running parallel or nearly parallel with the flutes of 856

the deck panel. Number 10 screws may not be adequate at thicker edge supports and 857

may fracture due to driving torque resistance. A minimum of a Number 12 screw is 858

recommended at parallel edge supports thicker than 14 gage (0.0747 inch) and a 859

Number14 screw may be required for thicker and harder steels. 860

861

E. Support at the perimeter of the floor shall be designed and specified by the designer. 862

F. Cantilevers: 863

1. Side laps shall be attached at the end of the cantilever and at a maximum 864

spacing of 12 inches (300 mm) on center from the cantilevered end at each 865

support. 866

2. Each deck corrugation shall be fastened at both the perimeter support and the 867

first interior support. 868

3. The deck shall be completely attached to the supports and at the side laps 869

before any load is applied to the cantilever. 870

4. Concrete shall not be placed on the cantilever before concrete is placed on the 871

adjacent span. 872

G. Fastener edge distance shall be as required by the applicable fastener design standard. 873

H. Deck bearing surfaces to be welded shall be brought into contact as required by AWS 874

D1.3, Section 5.3.2. 875

876

User Note: Out of plane support flanges can create knife-edge supports and air gaps 877

between the deck and support. This makes welding more difficult and allows 878

distortion under screw or power actuated fastener washers or heads. Inherent 879

tolerances of the supporting structure should be considered. 880

881

3.2 Welding 882

A. All welding of deck shall be in accordance with AWS D1.3. Each welder shall 883

demonstrate the ability to produce satisfactory welds using a procedure in accordance 884

with ANSI/AWS D1.3. 885

886

User Note: SDI-MOC describes a weld quality control test procedure that can be used 887

as a preliminary check for welding machine settings under ambient conditions. 888

889

B. For connection of the deck to the supporting structure, weld washers shall be used with 890

arc spot welds on all deck units with metal thickness less than 0.028 inches (22 gage) 891

(0.71 mm). Weld washers shall be a minimum thickness of 0.050 inches (1.27 mm) and 892

have a nominal 3/8 inch (10 mm) diameter hole. Weld washers shall not be used 893

between supports along the sidelaps. 894

C. Where weld washers are not required, a minimum visible 5/8 inch (16 mm) diameter 895

arc spot weld or arc seam weld of equal perimeter shall be used. Weld metal shall 896

penetrate all layers of deck material at end laps and shall have good fusion to the 897

supporting members. 898

D. When used, fillet welds to support structure shall be at least 1-1/2 inches (38 mm) long. 899

E. When steel headed stud anchors are installed to develop composite action between the 900

beam or joist and the concrete slab, the steel headed steel anchor shall be permitted as a 901

substitute for an arc spot weld to the supporting structure. Steel headed steel anchors 902

shall be installed in accordance with AWS D1.1. 903

904

3.3 Mechanical Fasteners 905

21

A. Mechanical fasteners, either powder actuated, pneumatically driven, or screws, shall be 906

permitted to fasten deck to supporting framing if fasteners meet project strength and 907

service requirements. 908

B. When the fasteners are powder actuated or pneumatically driven, the strength per 909

fastener used to determine the maximum fastener spacing and the minimum structural 910

support thickness shall be based on the manufacturers’ applicable fastener test report or 911

other documentation acceptable to the designer and building official. 912

C. Screws shall be acceptable for use without restriction on structural support thickness, 913

however, the screw selected shall have a grip range compatible with the combined 914

thickness of the deck and supporting member. 915

916

User Note: Mechanical fasteners (screws, powder or pneumatically driven fasteners, 917

etc.) are recognized as viable anchoring methods, provided the type and spacing of the 918

fastener satisfies the design criteria. Documentation in the form of test data, design 919

calculations, or design charts should be submitted by the fastener manufacturer as the 920

basis for obtaining approval. Strength of mechanically fastened connections are 921

dependant upon both deck and support thickness. 922

923

3.4 Accessory Attachment: 924

A. Structural accessories shall be attached to supporting structure or deck as required for 925

transfer of forces, but at a spacing not to exceed 12 inches (300 mm) on center. Non-926

structural accessories shall be attached to supporting structure or deck as required for 927

serviceability, but spaced not to exceed 24 inches (600 mm) on center. 928

B. Mechanical fasteners or welds shall be permitted for accessory attachment. 929

930

3.5 Cleaning Prior to Concrete Placement: 931

A. Surfaces shall be cleaned of debris, including but not limited to, welding rods, stud 932

ferrules that are broken free from the stud, and excess fasteners, prior to concrete 933

placement. 934

935

3.6 Reinforcing steel shall be installed when required by the construction documents. 936

937

User Note: The CRSI Manual of Standard Practice and the WRI Manual of Standard 938

Practice are recommended as references for reinforcing steel placement. 939

APPENDIX 1Composite Deck Construction Loading Diagrams

FIGURE 1Loading Diagrams and

Bending Moments

FIGURE 2Loading Diagrams

and Support Reactions

FIGURE 3Loading Diagrams and

Defl ections

Simple Span Condition

Double Span Condition

Triple Span Condition

Notes for Figures 1, 2, and 3

P = Plc = concentrated construction live load

I = in4/ft. (mm4/m) - deck moment of inertia

W1 = wdc + wdd = slab weight + deck weight

W2 = wlc = uniform construction live load

E = 29.5 x 106 psi (203,000 MPa)

l = clear span length (ft.) (m)

Dimensional consistency requires consistent units when calculating deflections.

P

W1

+M=0.25Pl+0.125W1l2

+M=0.125(W1+W2)l2

W1 W2

P

W1

+M=0.203Pl+0.096W1 l2

+M=0.096(W1+W2)l2

W1W2

l-M=0.125(W1+W2)l2

l

l l

l l

l

l

W1W2

P

W1

+M=0.20Pl+0.094W1l2

+M=0.094(W1+W2)l2

W1W2

l-M=0.117(W1+W2)l2

l

l l

l l

W1W2

l

l

l

Simple Span Condition

Double Span Condition

Triple Span Condition

W1

l

Δ=0.0130W1 l4

EI

l

Δ=0.0054W1 l4

EI

lW1

l

Δ=0.0069W1 l4

EI

lW1

l

Simple Span Condition

Double Span Condition

Triple Span Condition

W1

l

Pext=0.5(W1+W2)l

l

Pext=0.375(W1+W2)l

Pint=1.25(W1+W2)l

lW1

l

Pext=0.4(W1+W2)l

Pint=1.1(W1+W2)l

lW1

l

Pext Pint Pext

Pext Pext

Pext Pint Pint Pext

W2

W2

W2

W1

l

Pext=0.5(W1)l+P

Pext Pext

P

l

Pext=0.375(W1)l+P

Pint=1.25(W1)l+P

lW1

Pext Pint Pext

P P

l

Pext=0.4(W1)l+P

Pint=1.1(W1)l+P

lW1

lPext Pint Pint Pext

P P

User Note:

See section 1.3 for requirement for construction loads to be shown on construction documents and section 2.4.A for construction loads, including single spans.

SDI LOAD DIAGRAMS 1-15-10.indd 3SDI LOAD DIAGRAMS 1-15-10.indd 3 4/26/2011 4:55:36 PM4/26/2011 4:55:36 PM

1

Appendix 2 2000

30 November 2011 2001

2002

Strength Determination of Composite Deck-Slab by Pre-qualified Section Method 2003 2004

A2.1 General 2005

1. This appendix provides methods for the calculation of strength of 2006

composite steel deck-slabs. It shall be permitted to use this method if steel 2007

headed stud anchors (studs) are not present on the beam flange supporting 2008

the composite steel deck, or if steel headed stud anchors are present in any 2009

quantity. 2010

2. Limitations: 2011

A. Deck shall be limited to galvanized or uncoated steel decks with 2012

embossments meeting the requirements for Type I, Type II, or 2013

Type III patterns as shown in Figure A2.1, A2.2, A2.3, and A2.4. 2014

The design embossment height, ph, shall not be less than 0.035 in 2015

(0.89 mm) and shall not be greater than 0.105 in (2.67 mm). 2016

Embossments shall not be less than 90% of the design embossment 2017

depth. 2018

B. The embossment factor, ps, shall not be less than that defined in 2019

Table A2-1. 2020

2021

Table A2-1 Minimum Embossment Factor 2022

Deck Embossment

Type

Nominal Deck

Depth

Minimum ps

1

1

1

2

2

2

3

3

3

1.5 in

2.0 in

3.0 in

1.5 in

2.0 in

3.0 in

1.5 in

2.0 in

3.0 in

5.5

12.0

18.0

5.5

8.5

8.5

5.5

10.0

12.0

2023

a. For Type 1 deck embossments: 2024

2025

ps1 = 12 (le / S) (Eq. A2-1) 2026

2027

b. For Type 2 deck embossments: 2028

2029

ps2 = 12 ( l1 + l2 ) / S (Eq. A2-2) 2030

2031

c. For Type 3 deck embossments: 2032

2033

ps1 = 12 (sum of l1 lengths within S1) / S1 2034

2

(Eq. A2-3) 2035

2036

ps2 = 12 (sum of l2 lengths within S2) / S2 2037

(Eq. A2-4) 2038

2039 Figure A2.1 – Type 1 Embossments with length measured along centerline 2040

2041

2042 Figure A2.2 – Type 2 Embossments 2043

2044

2045 2046

Figure A2.3 – Type 3 Embossments 2047

2048

2049

3

Figure A2.4 – Embossment Section Details 2050

2051

C. The web angle measured from the horizontal plane, θ, shall be 2052

limited to values between 55° and 90° and the webs shall have no 2053

reentrant bends in their flat width. 2054

D. The deck section depth, dd, shall be less than or equal to 3 in. (75 2055

mm) 2056

E. All sheet steel used for deck shall comply with Section 2.1 of this 2057

Standard. 2058

F. Concrete shall comply with Section 2.1 of this Standard. 2059

G. The concrete thickness above the steel deck shall be equal to or 2060

greater than 2 inches (50mm). 2061

H. Composite deck-slabs shall be classified as under-reinforced. 2062

Composite deck-slabs that are classified as over-reinforced shall 2063

not be designed using the procedures of this Appendix. 2064

a. Slabs with (c/d) less than the balanced condition ratio (c/d)b 2065

shall be considered under-reinforced, whereas slabs with 2066

(c/d) greater than or equal to (c/d)b shall be considered 2067

over-reinforced. The compression depth ratio shall be 2068

calculated as: 2069

2070

( )1'85.0 βdbf

FAdc

c

ys= (Eq. A2-5) 2071

The compression depth ratio for the balanced condition 2072

shall be calculated as: 2073

2074

2075

( ) ( )

( )dE

F

dhdc

s

y

db

003.0

003.0

+

−= (Eq. A2-6) 2076

2077

Where: 2078

As = area of steel deck, in2/ft (mm

2/m) of slab 2079

width 2080

b = unit width of compression face of composite 2081

slab, 12 in.(1000 mm) 2082

c = distance from extreme compression fiber to 2083

composite neutral axis, in. (mm) 2084

d = distance from extreme compression fiber to 2085

centroid of steel deck, in. (mm) 2086

dd = overall depth of steel deck profile, in. (mm) 2087

Es = modulus of elasticity of steel deck, psi 2088

(MPa) 2089

fc’ = specified compressive strength of concrete, 2090

psi (MPa) 2091

4

Fy = specified yield strength of steel deck, psi 2092

(MPa) 2093

h = nominal out-to-out depth of slab, in. (mm) 2094

β1 = 0.85 if fc’ ≤ 4000 psi (27.58 MPa) 2095

65.01000

'05.005.11 ≥

−=

cfβ if fc’> 4000 psi 2096

(Eq. A2-7a) (in-lb) 2097

2098

β1 = 1.09 – 0.008fc’ ≥ 0.65 if fc’ > 27.58 MPa 2099

(Eq. A2-7b) (SI) 2100

2101 5. The strength of a composite deck-slab shall be the least of the following 2102

strength limit states: 2103

A. Flexural strength 2104

B. One-way shear strength in accordance with Section 2.4.B.7 2105

6. For load combinations that include concentrated loads, punching shear in 2106

accordance with Section 2.4.B.8 shall be considered. 2107

7. Cracked section properties shall be determined by Appendix 4. 2108

2109

A2.2 Flexural Strength: This section shall be used to determine the flexural strength of 2110

the composite deck-slab. 2111

1. The nominal moment capacity shall be calculated as follows: 2112

2113

A. The resisting moment, Mno, of the composite section shall be 2114

determined based on cracked section properties. 2115

2116

ФsMno = Фs K My (Eq. A2-8) 2117

2118

Where: 2119

My = Yield moment for the composite deck-slab, 2120

considering a cracked cross section 2121

= Fy Icr / (h-ycc) (Eq A2-9) 2122

2123

K = (K3/K1) ≤ 1.0 (Eq. A2-10) 2124

Fy = yield stress of steel deck, psi (MPa) 2125

h = slab depth measured from top of concrete to bottom 2126

of deck, in (mm) 2127

Icr = cracked section moment of inertia, in4 (mm

4) 2128

Mno = nominal resisting moment, kip-in (N-mm) 2129

ycc = distance from top of slab to neutral axis of cracked 2130

section, in (mm) 2131

Фs = 0.85 2132

Mnt = Nominal moment capacity 2133

K1, K3 = Coefficients of deck profile and embossment pattern 2134

2135

B. K3 shall be calculated as follows 2136

5

2137

K3 = 1.4 2138

2139

User Note: Using K3 = 1.4 is appropriate for typical deck applications 2140

where the floor is multiple deck panels wide. For instances where the 2141

floor is relatively narrow, measured perpendicular to the deck span, the 2142

following equation may yield more accurate (conservative) results. 2143

K3 = 0.87 + 0.0688N – 0.00222N2

≤ 1.4 (Eq. A2-11) 2144

2145

C. K1 shall be calculated as follows 2146

2147

For Type 1 Embossment Deck Panels: 2148

2149

K1 = 0.07 (DW)0.5

/ ph ≤ 1.55 (Eq. A2-12) 2150

2151

For Type 2 Embossment Deck Panels: 2152

2153

K1 = 15 (t) / [DW (ph)0.5

] (Eq. A2-13) 2154

2155

For Type 3 Embossment Deck Panels: 2156

2157

11 s1 12 s21

s1 s2

(K )p +(K )pK =

p +p (Eq. A2-14)

2158

2159

Where: 2160

Dw = Width of flat portion of the deck web, in. 2161

K11 = K1 calculated for Type 1 embossments in Type 3 2162

pattern 2163

K12 = K1 calculated for Type 2 embossments in Type 3 2164

pattern 2165

N = Number of cells in a slab width 2166

= w / R 2167

w = Slab width, in.(mm) 2168

R = Repeating pattern or cell spacing, in.(mm) 2169

ph = Embossment height, in. 2170

t = Deck thickness, in. 2171

2172

A2.3 Allowable Strength Design 2173

Allowable Strength Design shall be permitted as an alternate design method. 2174

2175

1. Allowable Strength for Bending: This section shall be used to determine 2176

the bending strength of the composite deck-slab. 2177

2178

M = Ka C Fy Sc (Eq. A2-15) 2179

2180

MLL = M - MDL (Eq. A2-16) 2181

6

2182

Where: 2183

2184

Ka = (K3/K1) ≤ 1.0 (Eq. A2-17) 2185

2186

M = Allowable moment capacity of composite slab-deck, kip-in 2187

(N-mm) 2188

2189

MLL = Allowable superimposed load moment capacity, kip-in (N-2190

mm) 2191

2192

MDL = Positive moment caused by casting of the concrete, not 2193

including temporary construction loads, kip-in (N-mm) 2194

2195

C = 0.60 2196

2197

Fy = Yield stress of steel deck, ksi (Mpa) 2198

2199

Sc = Elastic section modulus of the fully composite deck-slab 2200

2201

2. Allowable Strength for One-way Shear: This section shall be used to 2202

determine the one-way shear strength of the composite deck-slab. 2203

2204

V = Vc + VD (Eq. A2-18) 2205

2206

Where: 2207

2208

V = Allowable one-way shear strength of composite deck-slab 2209

2210

Vc = Allowable shear resistance of concrete area, Ac 2211

2212

ccc AfV'1.1 λ= (Eq. A2-19a) (in-lb) 2213

ccc AfV'0473.0 λ= (Eq. A2-19b) (SI) 2214

2215

VD = Allowable shear strength of the steel deck section 2216

calculated in accordance with AISI S100, kips (kN) 2217

Ac = Concrete area available to resist shear, in2 (mm

2), see 2218

Figure 2-1. 2219

λ = 1.0 where concrete density exceeds 130 lbs/ft3

(2100 2220

kg/m3); 2221

0.75 where concrete density is equal to or less than 130 2222

lbs/ft3

(2100 kg/m3). 2223

2224

7

User Note: Further description of the allowable stress design method is 2225

found in SDI-CDD, including tables that list values for the elastic section 2226

modulus. 2227

Appendix 3 3000 3001

Strength Determination of Composite Deck-Slab by Shear Bond Method 3002

30 November 2011 3003 3004

A3.1 General 3005

1. This Appendix provides methods for the calculation of strength of 3006

composite steel deck-slabs by the shear bond method. It shall be permitted 3007

to use this method if steel headed stud anchors (studs) are not present on 3008

the beam flange supporting the composite steel deck, or if steel headed 3009

stud anchors are present in any quantity. 3010

2. Limitations: 3011

A. Deck shall be limited to galvanized or top surface uncoated steel 3012

decks. 3013

B. All sheet steel used for deck shall comply with Section 2.1 of this 3014

Standard. 3015

C. Concrete shall comply with Section 2.1 of this Standard. 3016

D. The concrete thickness above the steel deck shall be equal to or 3017

greater than 2 inches (50mm). 3018

3. The strength of a composite deck-slab shall be the least of the following 3019

strength limit states: 3020

A. Shear bond resistance 3021

B. Flexural strength 3022

C. One-way shear strength in accordance with Section 2.4.B.7 3023

4. For load combinations that include concentrated loads, punching shear in 3024

accordance with Section 2.4.B.8 shall be considered. 3025

3026

A3.2 Shear bond Resistance 3027

3028

1. The ultimate shear bond resistance of a composite slab section shall be 3029

calculated using parameters determined from a testing program of full-3030

scale slab specimens in accordance with SDI-T-CD. The factored shear 3031

bond resistance (Vr) of a composite slab shall be determined as follows: 3032

3033

tVr VV φ= (Eq. A3-1) 3034

3035

Where, 3036

Vr = factored shear bond resistance, pounds/ft (N/m) of slab 3037

width, 3038

Vt = tested shear bond resistance, pounds/ft (N/m) of slab width, 3039

determined in accordance with SDI-T-CD, 3040

φv = shear bond resistance factor 3041

= 0.75 3042

3043

2. The permissible uniform load for shear bond shall be: 3044

3045

LVW tvr 2φ= (Eq. A3-2) 3046

3047

Where: 3048

L = deck design span, ft. (m) 3049

3050

A3.3 Flexural Strength 3051

1. Composite slabs subject to flexural failure shall be classified as under-3052

reinforced or over-reinforced slabs depending on the compression depth 3053

ratio, (c/d). Slabs with (c/d) less than the balanced condition ratio (c/d)b 3054

shall be considered under-reinforced, whereas slabs with (c/d) greater than 3055

or equal to (c/d)b shall be considered over-reinforced. The compression 3056

depth ratio shall be calculated as: 3057

3058

( )1' βdbf

FAdc

c

ys= (Eq. A3-3) 3059

3060

The compression depth ratio for the balanced condition shall be calculated as: 3061

3062

3063

( ) ( )

( )dE

F

dhdc

s

y

db

003.0

003.0

+

−= (Eq. A3-4) 3064

3065

Where: 3066

As = area of steel deck, in2/ft (mm

2/m) of slab width 3067

b = unit width of compression face of composite slab, 12 3068

in.(1000 mm) 3069

c = distance from extreme compression fiber to composite 3070

neutral axis, in. (mm) 3071

d = distance from extreme compression fiber to centroid of 3072

steel deck, in. (mm) 3073

dd = overall depth of steel deck profile, in. (mm) 3074

Es = modulus of elasticity of steel deck, psi (MPa) 3075

fc’ = specified compressive strength of concrete, psi (MPa) 3076

Fy = specified yield strength of steel deck, psi (MPa) 3077

h = nominal out-to-out depth of slab, in. (mm) 3078

β1 = 0.85 if fc’ ≤ 4000 psi (27.58 MPa) 3079

65.01000

'05.005.11 ≥

−=

cfβ if fc’> 4000 psi 3080

3081

β1 = 1.09 – 0.008fc’ ≥ 0.65 if fc’ > 27.58 MPa 3082

3083

2. Under-reinforced Slabs (c/d)< (c/d)b 3084

A. The factored moment resistance, in positive bending, of an under-3085

reinforced composite slab shall be taken as: 3086

3087

Mru = φs My (Eq. A3-5) 3088

3089

My = Yield moment for the composite deck-slab, considering a 3090

cracked cross section 3091

= Fy Icr / (h-ycc) 3092

3093

Where, 3094

3095

φs = 0.85 3096

Fy = yield stress of steel deck, psi (MPa) 3097

Icr = cracked section moment of inertia, in4 (mm

4) 3098

h = slab depth, in (mm) 3099

ycc = distance from top of slab to neutral axis of cracked section, 3100

in (mm) 3101

3102

3. Over-reinforced Slabs (c/d) ≥ (c/d)b 3103

A. The factored moment resistance, in positive bending, of an over-3104

reinforced composite slab shall be determined by: 3105

3106

( )2' 11 cdcbfM ccro ββφ −= (Eq. A3-6) 3107

3108

Where: 3109

3110

+=

22

2mm

mdcρρ

ρ (Eq. A3-7) 3111

3112

bd

As=ρ (Eq. A3-8) 3113

1'β

ε

c

cus

f

Em = (Eq. A3-9) 3114

3115

Es = 29,500,000 psi (203000 MPa) 3116

εcu = 0.003 3117

φc = 0.65 3118

3119

B. Equation (A3-6) is valid only for composite slabs where no part of 3120

the steel deck has yielded. 3121

1

Appendix 4 4000

30 November 2011 4001 4002

Section Properties of Composite Deck-Slabs 4003 4004

A4.1 General 4005

This appendix provides methods for the calculation of geometric cross section 4006

properties for composite steel deck cross sections with concrete. 4007

4008

User Note: This method will provide conservative results for slabs with 4009

reinforcing. The designer may choose to use alternate methods that consider the 4010

contribution of the reinforcing steel in this case. 4011

4012

A4.2 Transformed Composite Neutral Axis 4013

The distance ycc from the extreme compression fiber of the concrete to the neutral 4014

axis of the transformed composite section shall be determined from Figure A4-1 4015

and Equations A4-1 and A4-3. 4016

4017 4018

4019

Figure A4-1 – Composite Section 4020

4021

4022

Notes: 1. Section shows non-cellular deck. Section shall be either cellular, a 4023

blend of cellular and non-cellular, or non-cellular deck. Unless 4024

testing is performed that demonstrates that the interlocking device 4025

is capable of developing the full strength of the cross-section, only 4026

the element in contact with the concrete shall be considered in the 4027

design. 4028

2. C.G.S. = centroidal neutral axis of full, unreduced cross 4029

section of steel deck, in. (mm) 4030

3. Cs = pitch of deck ribs in. (mm) 4031

4. N.A. = neutral axis of transformed composite section 4032

5. Wr = average deck rib width in. (mm) 4033

6. dd = depth of deck in. (mm) 4034

2

7. h = overall slab depth in. (mm) 4035

8. hc = depth of concrete above steel deck in. (mm) 4036

4037

A4.3 Moment of Inertia of the Cracked Section 4038

4039

For the cracked moment of inertia 4040

4041

( )

ρ−ρ+ρ= nnn2dy2

cc ≤ hc (Eq. A4-1) 4042

4043

where 4044

ρ = bd

As 4045

As = area of steel deck per unit slab width in2. (mm

2) 4046

b = unit slab width (12 inches in imperial units) 4047

d = distance from top of concrete to centroid of steel deck 4048

n = modular ratio = c

s

E

E 4049

Es = 29500 ksi (203,000 MPa) 4050

4051

Ec = modulus of elasticity of concrete 4052

= wc1.5

(f’c)0.5

,ksi (0.043wc1.5

(f’c)0.5

,MPa) 4053

4054

wc = concrete unit weight, pcf (kg/m3) 4055

4056

'cf = concrete strength, ksi (MPa) 4057

4058

cccs ydy −= where ycc shall be determined from Equation A4-1. 4059

4060

The cracked moment of inertia transformed to steel, Ic ,shall be calculated using 4061

Equation A4-2. 4062

4063

sf2css

3ccc IyAy

n3

bI ++= (Eq. A4-2) 4064

4065

where 4066

Isf = moment of inertia of the full (unreduced) steel deck per unit 4067

slab width. in4. (mm

4) 4068

4069

4070

A4.4 Moment of Inertia of the Uncracked Section 4071

For the uncracked moment of inertia 4072

4073

( )

sdrsc

sddrs

2c

cc

C

bdWnAbh

C

bd5.0hdWdnAbh5.0

y

++

−++

= (Eq. A4-3) 4074

3

4075

The uncracked moment of inertia transformed to steel, Iu ,shall be calculated using 4076

Equation A4-4. 4077

4078

cccs ydy −= where ycc shall be determined from Equation A4-3. 4079

4080

( ) ( )

−−++++−+=

2dcc

2d

s

dr2csssf

2ccc

c3c

u d5.0yh12

d

nC

bdWyAIh5.0y

n

bh

n12

bhI 4081

(Eq. A4-4) 4082

4083

A4.5 Moment of Inertia of the Composite Section 4084

The moment of inertia of the composite section considered effective for deflection 4085

computations shall be calculated by Equation A4-5. 4086

4087

2

III cud

+= (Eq. A4-5) 4088

4089

4090

USER NOTE ATTACHMENT 1Pour Stop Selection Table

NOTES: This Selection Chart is based on the following criteria:

1. Normal weight concrete 150 PCF (2,400 kg/m3).

2. Horizontal and vertical deß ection is limited to 1/4” (6.3mm) maximum for concrete dead load.

3. Design stress is limited to 20 KSI (138 MPa) for concrete dead load temporarily increased by one-third for the construction live load of 20 PSF (0.96 kPa).

4. Pour Stop Selection Chart does not consider the effect of the performance, deß ection, or rotation of the pour stop support which may include both the supporting deck and/or the frame.

5. Vertical leg return lip is recommended for all types (gages).

6. This selection table is not meant to replace the judgment of experienced structural engineers and should be considered as a reference only.

SLAB

DEPTH(INCHES)

SLAB

DEPTH(mm)

OVERHANG - INCHES (mm)

0 1 2 3 4 5 6 7 8 9 10 11 12

0 25 51 76 102 127 152 178 203 229 254 279 305

POUR STOP TYPES

4.00 102 20 20 20 20 18 18 16 14 12 12 12 10 10

4.25 108 20 20 20 18 18 16 16 14 12 12 12 10 10

4.50 114 20 20 20 18 18 16 16 14 12 12 12 10 10

4.75 121 20 20 18 18 16 16 14 14 12 12 10 10 10

5.00 127 20 20 18 18 16 16 14 14 12 12 10 10

5.25 133 20 18 18 16 16 14 14 12 12 12 10 10

5.50 140 20 18 18 16 16 14 14 12 12 12 10 10

5.75 146 20 18 16 16 14 14 12 12 12 12 10 10

6.00 152 18 18 16 16 14 14 12 12 12 10 10 10

6.25 159 18 18 16 14 14 12 12 12 12 10 10

6.50 165 18 16 16 14 14 12 12 12 12 10 10

6.75 171 18 16 14 14 14 12 12 12 10 10 10

7.00 178 18 16 14 14 12 12 12 12 10 10 10

7.25 184 16 16 14 14 12 12 12 10 10 10

7.50 191 16 14 14 12 12 12 12 10 10 10

7.75 197 16 14 14 12 12 12 10 10 10 10

8.00 203 14 14 12 12 12 12 10 10 10

8.25 210 14 14 12 12 12 10 10 10 10

8.50 216 14 12 12 12 12 10 10 10

8.75 222 14 12 12 12 12 10 10 10

9.00 229 14 12 12 12 10 10 10

9.25 235 12 12 12 12 10 10 10

9.50 241 12 12 12 10 10 10

9.75 248 12 12 12 10 10 10

10.00 254 12 12 10 10 10 10

10.25 260 12 12 10 10 10

10.50 267 12 12 10 10 10

10.75 273 12 10 10 10

11.00 279 12 10 10 10

11.25 286 12 10 10

11.50 292 10 10 10

11.75 298 10 10

12.00 305 10 10

TYPESDESIGN

THICKNESS(INCHES)

DESIGN

THICKNESS(mm)

20 0.0358 0.91

18 0.0474 1.20

16 0.0598 1.52

14 0.0747 1.90

12 0.1046 2.66

10 0.1345 3.42

SDI LOAD DIAGRAMS 1-15-10.indd 2 1/18/2010 7:16:44 AM