PROJECTTITLE:
IN
NOVATIVETYRES
1M
WC
APTIVESOLARPV
POWERPLANT
SHEETTITLE:
TITLESHEET
Engineer:I hereby certify that this drawing
by me or under my supe
Date
Date Marks
DESIGNED BY
DRAWN BY:
CHECKED BY:
SUPERVISED BY:
Drawing Number
T100
INNOVATIVE TYRES, HALOL, GUJARATUTILITY SCALE SOLAR PV POWER PLANT
1. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY
PERMITS AND APPROVALS PRIOR TO STARTING ANY WORK.
2. EXISTING UTILITIES SHALL REMAIN IN SERVICE AND IN
PLACE UNLESS NOTED OTHERWISE. INTERRUPTION OF
SERVICE SHALL BE KEPT TO A MINIMUM ANDONLY WITH
THE APPROVAL OF THE ENGINEER AND CONTRACTING
OFFICER.
3. WORK SHALL BE PERFORMED IN ACCORDANCE WITH
APPLICABLE OSHA REGULATIONS.
4. CONTRACTOR TO VERIFY AND CHECK THE DIMENSIONS
AND DETAIL PRIOR TO THE START OF CONSTRUCTION. ANY
DISCREPANCY SHALL BE IMMEDIATELY REPORTED TO THE
ENGINEER FOR CLARIFICATIONANBD RESOLUTION.
5. CONTRACTOR SHALL EXERCISE DUE CARE AND DILIGENCE
TO AVOID DAMAGE TO EXISTING UTILITIES, STRUCTURES OR
OTHER SITE IMPROVEMENTS NOT DESIGNATED TO BE
REMOVED OR MODIFIED. ANY DAMAGE TO EXISTING
IMPROVEMENTS NOT DESIGNATED TO BE REMOVED OR
MODIFIED SHALL BE RESTORED TO THEIR ORIGINAL
CONDITION OR BETTER.
SHEET NO. DWG NO. DESCRIPTION
1 OF 09
2 OF 09
3 OF 09
4 OF 09
5 OF 09
6 OF 09
7 OF 09
8 OF 09
T100
G101
S101
E101
E102
E103
D101
D102
TITLE SHEET
GENERAL NOTES
SITE LAYOUT
POWER ONE-LINE DIAGRAM (1)
POWER ONE-LINE DIAGRAM (2)
POWER ONE-LINE DIAGRAM (3)
SPV MODULE DATASHEET
SOLAR INVERTER DATASHEET
ABBREVIATIONDRAWING INDEX
LOCATION MAP VICINITY MAP GENERAL NOTES
NORMALIZED PRODUCTION PER INSTALLED kWp
(1000kWdc NOMINAL POWER)
kWh/kWp/day
OMSAISOLAR
CONSULTING
BURDWANWBINDIA
7/26/2019 1MW_ROOFTOP_SOLAR_PV_POWER_PLANT_PERMIT (1).pdf
2/9
PROJECTTITLE:
INNOVATIVETYRES
1M
WG
RIDCONNECTED
SOLARPVPOWERSYSTEM
SHEETTITLE:
GENERALNOTES
ELECTRICAL
Engineer:I hereby certify that this drawin
by me or under my supe
Date
Date Marks
DESIGNED BY
DRAWN BY:
CHECKED BY:
SUPERVISED BY:
Drawing Number
G101
GENERAL NOTES:
1.DO NOTSCALE DRAWINGS, IF UNABLETO LOCATEDIMENSIONSFOR ANY ITEMOF WORK, CONSULTARCHITECT/ENGINEERFORDIRECTIONSBEFOREPROCEEDING.
2.IN THEABSENCE OF THEEXACT ROOFDIMENSIONS,THE DRAWING WILLBASED ONGOOGLEMAP, THEREFORETHESEMAYNOTBE ACCURATE.CONTRACTOR ON SITE TO VERIFYALL OBSTACLESON THE ROOF ANDENSUREALL REQUIREDCLEARENCES WITH AUTHORITY HAVING JURISDICTION(S) PRIOR TO INSTALLATION, ORDERING MATERIAL OR
FABRICATION
3.CONTRACTOR SHALL OBTAINELECTRICALAND OTHERPERMITSPRIOR TOINSTALLATIONANDSHALL COORDINATEALLINSPECTIONS BY THECITY INSPECTORS,TESTING/ COMMISSIONING BY THEUTILITYCO. ANDACCEPTANCEBY THECLIENT, AS NEEDED.
4.ROUTINGOR RACEWAYSMATERIAL SHALLBE AT THE OPTIONOF THECONTRACTOR, WITHIN THE CODE,UNLESSOTHERWISENOTED ANDSHALLBE COORDINATED WITH OTHERTRADES.
5. IF THEROOF MATERIALOR ROOF STRUCTUREIS NOT ADEQUATE FOR PVI NSTALLATION, CALL ENGINEER PRIOR TOINSATLL.THECONTRACTORISRESPONSIBLETOVERIFY THAT ROOF IS CAPABLE OF WITHSTANDINGTHE EXTRAWEIGHT.
6.WHENEVER A DISCREPANCY IN QUANTITY OF EQUIPMENT ARISES ON THE DRAWING OR SPECIFICATIONS, THECONTRACTOR SHALL BERESPONSIBLE FOR PROVIDINGAND INSTALLING ALL MATERIAL AND SERVICES REQUIREDBYSTRICTEST CONDITIONSNOTED ON THE DRAWING OR IN THE SPECIFICATIONS TO ENSURE COMPLETE COMPLIANCEAND
LONGEVITY OF THEOPERABLESYSTEMREQUIRED BYTHE ARCHITECT/ENGINEER
7.THIS DESIGNI SFULLY BASEDON THE INFORMATION PROVIDED BYTHE DEVELOPER,ANY MODIFICATIONSOR REMOVALOF THE LOGO OFTHE EPC;"VARIETAS PROJECTMANAGERS &ENGINEERS" IS NOT ALLOWED AND WILL RENDER THISDESIGN VOID.
8.THE WORKING CLEARANCE AROUNDTHE EXISTING ELECTRICAL EQUIPMENTS AS WELL AS THE NEW ELECTRICALEQUIPMENTWILL BE MAINTAINEDIN ACCORDANCE WITH.
9.ADEQUATE SPACING MUSTBE MAINTAINEDBETWEEN ANY PLUMBING/SEWERVENTS EXTENDINGTHROUGH THEROOFANDUNDERSIDE OF THEPHOTOVOLTAIC PANELS(6''MINIMUM RECOMMENDED).
ELECTRICAL NOTES AND STANDARDS TO FOLLOW:
GENERAL NOTES
IEC 60050V(826)
IEC 60068
IEC 60364-7-712
IEC 60439-1
IEC 60755
IEC 61215
IEC 61683
IEC 61701
IEC 61724
IEC 61730
IEC 62305
IEC 62446
IEC 62548
IEC 62109-1:2010
IEC 62116
ELECTRICAL INSTALLATIONS OF BUILDINGS
ENVIRONMENTAL TESTING
REQUIREMENTSFOR SPECIAL INSTALLATIONS OR LOCATIONS SOLAR PHOTOVOLTAIC(PV) POWER SUPPLYSYSTEMS
LOWVOLTAGESWITCHGEAR &CONTROLGEAR ASSEMBLIES
GENERAL REQUIREMENTS FOR RESIDUAL CURRENT OPERATEDPROTECTIVE DEVICES(OCPD)
CRYSTALLINE SILICONTERRESTIAL PHOTOVOLTAIC(PV) MODULES DESIGNQUALIFICATION ANDTYPE APPROVAL
EFFICIENCY MEASUREMENTSANDENVIRONMENTAL TESTS OFPOWER CONDITIONINGUNITS(PCUs)
PVMODULESTOBE USED IN A HIGHLYCORROSIVE ATMOSPHERE
PHOTOVOLTAIC SYSTEMPERFORMANCE MONITORING GUIDELINES FOR MEASUREMENT,DATAEXCHANGEANDANALYSIS
PART-2:REQUIREMENTSFOR CONSTRUCTION&PART-2:REQUIREMENTSFOR TESTING, FOR SAFETYQUALIFICATION
LIGHTINGPROTECTION
GRIDCONNECTED PHOTOVOLTAIC SYSTEMSMINIMUM REQUIREMENTSFOR SYSYTEM DOCUMENTATION,COMMISSIONING TESTSANDINSPECTION
PHOTOVOLTAIC ARRAYSDESIGNREQUIREMENTS
SAFETY OFPOWER CONVERTERS FOR USE INPHOTOVOLTAIC POWER SYSTEMS
UTILITY-INTERCONNECTEDPHOTOVOLTAICINVERTERSTEST PROCEDURE OF ISLANDINGPREVENTIONMEASURES
IEC 61727
IEC 61000
IEC 62305
IEC 61643-11
TUV 2PfG1169
AS1319
APPLICABLEJUNCTIONBOX
STANDARDS
IEC 60664
IEC 50548
IEC 60529
IEC 60269
IEC 62208
EN60715
APPLICABLESWITCHBOARD
STANDARDS
ICE 60947
PHOTOVOLTAIC SYSTEMS -CHARACTERISTICSOFTHEUTILITYINTERFACES
ELECTROMAGNETICCOMPATIBILITY(EMC)
LIGHTNINGPROTECTIONSTANDARD
LOWVOLTAGESURGE PROTECTIVE DEVICES REQUIREMNETS&TESTS FOR SPDs IN PHOTOVOLTAICAPPLICATIONS
TUV INTERNAL CABLESTANDARD
SAFETY SIGNSFOR THE OCCUPATIONAL ENVIRONMENT
CREEPAGE DISTANCES ANDCLEARANCES
JUNTION BOXES
DEGREESOFPROTECTION PROVIDEDBYTHE ENCLOSURES
LOWVOLTAGEFUSES
COPPER BUS BARS /TERMINAL BLOCKS HOUSEDIN THE JUNCTIONBOX WITHSUITABLE TERMINATIONTHREADS
CHROMATEDDINRAIL
LOWVOLTAGEACSWITCHGEAR ANDCONTROL GEARS SPECIFICATIONS
IEC 60439
IEC 60947
IEC 60529
IEC 60404
IEC 62056
IEC 60364
IEC 60947.2
IEC 60439
IEC EN 60269-1
IEC 60529
APPLICABLESTANDARDSFOR LOW
VOLTAGE ACCABLES
IEC 60840
IEC 60502
IEC 60227,60228
APPLICABLELOCAL STANDARDS
LOWVOLTAGEACSWITCHGEAR ANDCONTROL GEARSASSEMBLIES
GENERAL REQUIREMENTS FOR ACSWITCHGEAR &CONTROLGEAR VOLTAGE
7/26/2019 1MW_ROOFTOP_SOLAR_PV_POWER_PLANT_PERMIT (1).pdf
3/9
PROJECTTITLE:
INNOVATIVETYRES
1M
WG
RIDCONNECTED
SOLARPVPOWERSYSTEM
SHEETTITLE:
POWERONE-LINE
DIAGRAM
PVtoSTRINGS
Engineer:
I hereby certify that this drawing
by me or under my supe
Date
Date Marks
DESIGNED BY
DRAWN BY:
CHECKED BY:
SUPERVISED BY:
Drawing Number
E101
POWER ONE-LINE DIAGRAM
PV TO STRINGS
6 sq.mm
BARE COPPER
GROUNDING WIRE
+
-
+
-
+
-
+
-
RAIL
GROUNDING LUG
1
STRING #G1, 20 MODULES
-
....
-
+
+
----
RAIL
GROUNDING LUG
6
-
....
-
+
+
-
+
-
+
-
+
-
RAIL
GROUNDING LUG
11
-
....
-
+
+
----
RAIL
GROUNDING LUG
16
-
....
-
+
6 sq.mm PV WIRE
6 sq.mm PV WIRE
20
MODULE MFR: JINKO SOLARMODEL: JKM250P
VOC
= 37.7V
VMP
= 30.5V
ISC
= 8.85A
IMP = 8.20A
PV MODULE RATINGS @ STC
OMSAISOLAR
CONSULTING
7/26/2019 1MW_ROOFTOP_SOLAR_PV_POWER_PLANT_PERMIT (1).pdf
4/9
PROJECTTITLE:
INNOVATIVETYRES
1M
WG
RIDCONNECTED
SOL
ARPVPOWERSYSTEM
SHEETTITLE:
POWERONE-LINE
DIAGRAM
STRINGSTOINVERTERTOSUB-PANEL
Engineer:I hereby certify that this drawin
by me or under my sup
Date
Date Marks
DESIGNED BY
DRAWN BY:
CHECKED BY:
SUPERVISED BY:
Drawing Number
E102
#10 AWG THWNMODULE/RACKING
EGC
+-
+-
+-
+-
DC.1
RAILGROUNDING LUG
1 .... .... 20
#10 AWG THWNMODULE/RACKING
EGC
+-
+-
+-
+-
DC.1
RAILGROUNDING LUG
1 .... ....
STRING#A1, 2MODULES
STRING #B1, 20 MODULES
#10 AWG THWNMODULE/RACKING
EGC
+-
+-
+-
+-
DC.1
RAILGROUNDING LUG
1 .... ....
STRING #C1, 20 MODULES
CONDUIT
114" EMT
DC.2
+- +- +- +- +- +- +- +-GMPPT
1MPPT
2
"INV#1"INGETEAM 24TL-U-M480WITH BOTHDC & ACDISCONNECT
&ARC-FUALT INTEREPTER
L3L2
NG
L1
DC DISC.
AC DISC. (n)
40A/3P
GNEU
(n)200A 3P
NEW PV SUB-PANEL, "SP1"200A BUSMINUMUM,277/480V 4W
CONDUIT
1- "
EMT
AC.1
CONDUIT
1-" E
MT
AC.2
#10 AWG THWNMODULE/RACKING
EGC
--
DC.1
RAILGROUNDING LUG
....
#10 AWG THWNMODULE/RACKING
EGC
+-
+-
+-
+-
DC.1
RAILGROUNDING LUG
1 .... ....
STRING#E1,20 MODULES
CONDUIT
114" EMT
DC.2
+-
+-
+-
+-
RAILGROUNDING LUG
1 .... ....
STRING #D1, 20 MODULES
--
STRING #A2, 20 MODULES
STRING #B2, 20 MODULES
STRING #C2, 20 MODULES
"INV#2"
& ARC-FUALT INTEREPTER
STRING #E2, 20 MODULES
STRING #D2, 20 MODULES
STRING #E3, 20 MODULES
STRING #D3, 20 MODULES
STRING #A3, 20 MODULES
STRING #B3, 20 MODULES
STRING #C3, 20 MODULES
"INV#3"
& ARC-FUALT INTEREPTER
INVERTER MFR: INGETEAM
INVERTER MODEL: 24TL U M480DC VOLT RATING = 1000V
OPERATING VOLTAGE =580-950V
DC MAX USABLE INPUT CURRENT:
PER MPPT = 27APER INVERTER = 54A
AC MAX RATED OUTPUT POWER = 24000W
AC MAX OUTPUT CURRENT
MIN WIRE SIZE = 29A * 125% = 36.25AMIN (OCPD) = 40A, AVAILABLE (OCPD) =40A
MODULE MFR: ZINKO SOLARMODEL: 250Wp
VOC
= 37.7V
VMP
= 30.5V
ISC
= 8.85A
IMP = 8.20A
21
21
21
21
= 29A
C IR CU IT DE SC RI PT IO N C ON DU CT OR S IZ E/ TY PE C ON DU IT S I ZE */ QT Y
(DC) SOLARSTRING
WIRING2-CORE 6 sq.mm FA
(DC) STRINGTO INVERTER (5
STRINGS) (5)2-CORE 6 sq.mm (2) 1- in
(AC) INVERTER TOCOMBINER BOX (5INVERTERS) (5)4-CORE 16 sq.mm (1) 1- in
(AC) GECGROUNDING (1)BARECOPPER10mm (1) 1 in
(DC) GECGROUNDING (1)BARECOPPER6mm (1) in
1-WAY WIRETRAVELVOLTAGE
@MAXPOWER
- 622 Vdc
350 ft 622 Vdc
140 ft 480VAC
65 ft 480VAC
450 ft 622 Vdc
CURRENT
@MAXPOWERVOLTAGEDROP(%)
8.53A 0.5%
2*8.53A 0.5%
29A 0.80%
- -
- -
(A)
(B)
(C)
(D)
(E)
POWER ONE-LINE DIAGRAM
STRINGS TO INVERTER TO SUB-PANEL
40A/3P
40A/3P
PV MODULE RATINGS @ STC
PV INVERTER RATINGS
STRING #E4, 20 MODULES
STRING #D4, 20 MODULES
STRING #A4, 20 MODULESSTRING #B4, 20 MODULES
STRING #C4, 20 MODULES
"INV#4"
& ARC-FUALT INTEREPTER
40A/3P40A/3P
STRING #E5, 20 MODULES
STRING #D5, 20 MODULES
STRING #A5, 20 MODULES
STRING #B5, 20 MODULES
STRING #C5, 20 MODULES
"INV#5"
& ARC-FUALT INTEREPTER
INGETEAM 24TL-U-M480WITH BOTH DC & AC DISCONNECT
INGETEAM 24TL-U-M480WITH BOTHDC & ACDISCONNECT
INGETEAM 24TL-U-M480WITH BOTHDC & ACDISCONNECT
INGETEAM 24TL-U-M480WITH BOTH DC & AC DISCONNECT
OMSAISOLAR
CONSULTING
BURDWAN,WB,INDIA
7/26/2019 1MW_ROOFTOP_SOLAR_PV_POWER_PLANT_PERMIT (1).pdf
5/9
PROJECTTITLE:
INNOVATIVETYRES
1M
WG
RIDCONNECTED
SOL
ARPVPOWERSYSTEM
SHEETTITLE:
POWERLINE
DIAGRAM
Engineer:
I hereby certify that this drawing
by me or under my supeDate I
Date Marks
DESIGNED BY
DRAWN BY:
CHECKED BY:
SUPERVISED BY:
Drawing Number
E103
(n)
AC.2
G
H1
H2 H3
NEW 1250kVATRANSFORMER#1
SECONDARY
14kV Delta
PRIMARY
480 Wye
G
X1
X2 X3
H0
ARRAY CONFIGURATIONNo. of Inverters:40
Strings Per Inverter: 5
(n)
40A/3P
GNEU
(n)
200A 3P
NEW PV SUB-PANEL, "SP1"200A BUSMINUMUM, 277/480V 4W
CONDUIT
1-"EMT
AC.2
40A/3P
40A/3P
40A/3P
40A/3P
INV#1
A#1, 20SPVMODULES
B#1, 20SPVMODULES
C#1, 20SPVMODULES
D#1, 20SPVMODULES
E#1, 20SPVMODULES
INV#2
A#2, 20SPVMODULES
B#2, 20SPVMODULES
C#2, 20SPVMODULES
D#2, 20SPVMODULES
E#2, 20SPVMODULES
INV#3
A#3, 20SPVMODULES
B#3, 20SPVMODULES
C#3, 20SPVMODULES
D#3, 20SPVMODULES
E#3, 20SPVMODULES
INV#4
A#4,20SPVMODULES
B#4, 20SPVMODULES
C#4, 20SPVMODULES
D#4,20SPVMODULES
E#4, 20SPVMODULES
INV#5
A#5, 20SPVMODULES
B#5,20SPVMODULES
C#5, 20SPVMODULES
D#5, 20SPVMODULES
E#5, 20SPVMODULES
TOTALSTRINGSIZE = 25kWp,
5x20SPV
INV#6
TOTALSTRINGSIZE = 25kWp,5x20SPV
INV#7
TOTALSTRINGSIZE = 25kWp,5x20SPV
TOTALSTRINGSIZE = 25kWp,
5x20SPV
TOTALSTRINGSIZE = 25kWp,5x20SPV
INV#8
INV#9
INV#10
NEW PV SUB-PANEL, "SP2"200A BUSMINUMUM,277/480V 4W
40A/3P
40A/3P
40A/3P
40A/3P
40A/3P
INPUT SIDE
OUTPUT SIDE
200A3P
TOTALSTRINGSIZE = 25kWp,5x20SPV
INV#11
TOTALSTRINGSIZE = 25kWp,
5x20SPV
INV#12
TOTALSTRINGSIZE = 25kWp,
5x20SPV
TOTALSTRINGSIZE = 25kWp,5x20SPV
TOTALSTRINGSIZE = 25kWp,5x20SPV
INV#13
INV#14
INV#15
NEW PV SUB-PANEL, "SP3"200A BUSMINUMUM, 277/480V 4W
40A/3P
40A/3P
40A/3P
40A/3P
40A/3P
INPUT SIDE
OUTPUT SIDE
200A3P
TOTALSTRINGSIZE = 25kWp,5x20SPV
INV#16
TOTALSTRINGSIZE = 25kWp,5x20SPV
INV#17
TOTALSTRINGSIZE = 25kWp,
5x20SPV
TOTALSTRINGSIZE = 25kWp,5x20SPV
TOTALSTRINGSIZE = 25kWp,
5x20SPV
INV#18
INV#19
INV#20
NEW PV SUB-PANEL, "SP4"200A BUSMINUMUM, 277/480V 4W
40A/3P
40A/3P
40A/3P
40A/3P
40A/3P
INPUT SIDE
OUTPUT SIDE
200A3P
TOTALSTRINGSIZE = 25kWp,
5x20SPV
INV#21
TOTALSTRINGSIZE = 25kWp,5x20SPV
INV#22
TOTALSTRINGSIZE = 25kWp,5x20SPV
TOTALSTRINGSIZE = 25kWp,
5x20SPV
TOTALSTRINGSIZE = 25kWp,5x20SPV
INV#23
INV#24
INV#25
NEW PV SUB-PANEL, "SP5"200A BUSMINUMUM, 277/480V 4W
40A/3P
40A/3P
40A/3P
40A/3P
40A/3P
INPUT SIDE
OUTPUT SIDE
200A3P
TOTALSTRINGSIZE = 25kWp,
5x20SPV
INV#26
TOTALSTRINGSIZE = 25kWp,
5x20SPV
INV#27
INV#28
NEW PV SUB-PANEL, "SP6"200A BUSMINUMUM, 277/480V 4W
40A/3P
40A/3P
40A/3P
INPUT SIDE
TOTALSTRINGSIZE = 25kWp,5x20SPV
INV#31
TOTALSTRINGSIZE = 25kWp,
5x20SPV
INV#32
TOTALSTRINGSIZE = 25kWp,
5x20SPV
TOTALSTRINGSIZE = 25kWp,5x20SPV
TOTALSTRINGSIZE = 25kWp,5x20SPV
INV#33
INV#34
INV#35
NEW PV SUB-PANEL,"SP7"200A BUSMINUMUM, 277/480V 4W
40A/3P
40A/3P
40A/3P
40A/3P
40A/3P
INPUT SIDE
OUTPUT SIDE
200A3P
TOTALSTRINGSIZE = 25kWp,5x20SPV
INV#36NEW PV SUB-PANEL, "SP8"
200A BUSMINUMUM, 277/480V 4W
INPUT SIDE
200A 3P
POWER ONE-LINE DIAGRAM
COMPLETE SOLAR PV SYSTEM
OMSAISOLAR
CONSULTING
BURDWAN,WB,INDIA
o m s s c o n s u l t i n g @ g m a i l c o m
AC SIDECOMBINERBOXCB1
GN
AUXILIARYGUTTER
M1
LOADS
G NEU
GG
3/4"C-1#4
(e)GROUND RODS 6'-0"
(2) 3/4" x 10'APART TYPICAL
CONDUIT
2" EMT
AC.3
(e)SWITCHBOARD 11000/440V 3PH
2500A BUSBAR
POINTOF CONNECTIONPER 690.64; 705.12(D)
SPLICES& TAPS PER 366.56
(3) POLARISSTACKEDCONNECTORS IPLDS
LOCKABLE &
AC.2
120A, 11kV FUSED AC CIRCUIT BREAKER
7/26/2019 1MW_ROOFTOP_SOLAR_PV_POWER_PLANT_PERMIT (1).pdf
6/9
PROJECTTITLE:
INNOVATIVETYRES
1M
WG
RIDCONNECTED
SOL
ARPVPOWERSYSTEM
SHEETTITLE:
SITELAYOUT
SUGGESTEDPVARRAYLAYOUT
Engineer:
I hereby certify that this drawing
by me or under my supe
Date
Date Marks
DESIGNED BY
DRAWN BY:
CHECKED BY:
SUPERVISED BY:
Drawing Number
S101
SITE LAYOUT
WITH SUGGESTED PV ARRAY LAYOUT
OMSAISOLAR
CONSULTING
7/26/2019 1MW_ROOFTOP_SOLAR_PV_POWER_PLANT_PERMIT (1).pdf
7/9
PROJECTTITLE:
INNOVATIVETYRES
1M
WG
RIDCONNECTED
S O L
A R P V P O W E R S Y S T E M
SHEETTITLE:
DATASHEET
SOLAR
PHOTOVOLTAIC
M O D U L E
Engineer:I hereby certify that this drawin
by me or under my supe
Date
Date Marks
DESIGNED BY
DRAWN BY:
CHECKED BY:
SUPERVISED BY:
Drawing Number
D101
BURDWAN,WB,INDIA
l i @ i l
OMSAISOLAR
CONSULTING
SOLAR PHOTOVOLTAIC MODULEDATA SHEET
7/26/2019 1MW_ROOFTOP_SOLAR_PV_POWER_PLANT_PERMIT (1).pdf
8/9
B U R D W A N
W B I N D I A
PROJECTTITLE:
INNOVATIVETYRES
1M
WG
RIDCONNECTED
S O L
A R P V P O W E R S Y S T E M
SHEETTITLE:
DATA
SHEET
SOLARINVERTER
Engineer:I hereby certify that this drawing
by me or under my supe
Date
Date Marks
DESIGNED BY
DRAWN BY:
CHECKED BY:
SUPERVISED BY:
Drawing Number
D102
SOLAR INVERTERDATA SHEET
OMSAISOLAR
CONSULTING
7/26/2019 1MW_ROOFTOP_SOLAR_PV_POWER_PLANT_PERMIT (1).pdf
9/9
BURDWAN,WB,INDIA
+918116401052
PROJECTTITLE:
INNOVATIVETYRES,HALOL,GUJARAT
GRID-CONNECTEDSOLARPVSYSTEM
SYSTEMS
IZE:
1000kWdc
SITEADDRESS:
MIDC,HALOL,GUJARAT,INDIA
SHEETTITLE:
LABELS
Engineer:I hereby certify that this drawing was
prepared by me or under my supervision
Date Issue
Date Marks Revisions
DESIGNED BY
DRAWN BY:
CHECKED BY:
SUPERVISED BY:
Drawing Number
L100
Scale:
AS SHOWN
Sheet No.
09 OF 09
Date:
02/06/2016
LABEL AND MARKINGS LEGEND:
PROVIDES THE LOCATIONOF THE SERVICEDISCONNECTING MEANS ANDTHEPHOTOVOLTAICDISCONNECTING MEANS. THISPLAQUE SHALLBE APPLIEDTO THE MAIN
SERVICE DISCONNECTING MEANS ANDTHE
PHOTOVOLTAICDISCONNECTING MEANS; (2TOTAL)
LABELFORUTILITY ACDISCONNECT; 1 PERAC
DISCONNECT.
UTILITY ACDISCONNECT WARNING LABEL. 1PERACDISCONNECT ANDALL3 ACLOADCENTERS.
UTILITY ACDISCONNECT OPERATINGSPECIFICATIONS. 1PER ACDISCONNECT SITUATED
BETWEENSUB-PANELAND COMBINERBOX
LABELFORSYSTEMOWNER'S KWHGENERATIONMETER; 1PER OWNERMETER.
LABELFOR FACILITY NET GENERATIONMETER; 1
PERFACILITY GENERATIONMETER.
LABELFORARCFLASHWARNING. 1PER
ENERGIZEDENCLOSURE WITHACCESS TO LIVEPARTS.
ONE PERINVERTER. NUMBERSEQUENTIALLY
CONDUIT RUNFROMSOURCE CIRCUT TOINVERTER. (AS NEEDED)
CONDUIT RUNFROMINVERTER TO POCC. (ASNEEDED)
GENERAL NOTES FOR LABELS ANDMARKINGS:
1. LABELS ANDMARKINGS SHALLBE APPLIEDTOTHE APPROPRIATE COMPONENTS IN
ACCORDANCE WITHTHE NEC.
2. SOLARMODULES ARE SUPPLIEDFROMTHEMANUFACTURERWITHMARKINGS PRE-APPLIEDTOMEET THE REQUIREMENTS OF THE NEC.
3. NEXTRONEX ANDSOLAR EDGE INVERTERS ARESUPPLIEDFROM THE MANUFACTURERWITHTHEAPPROPRIATE LABELS ANDMARKINGS TO MEETTHE REQUIREMENTS OF THE NEC.
4. TEXT LABELS WILLBE ETCHEDWITHWHITEGRAPHICS ONTO 1/16" REDPLASTICPLACARDS.
THE LABELWILLBE MECHANICALLY ATTACHEDTOTHE APPROPRIATE COMPONENT ENCLOSURES INCONSPICUOUS PLACES.
5. LABEL"A" WILLBE ETCHEDWITH WHITE
GRAPHICS ONTO 1/16" REDPLASTICPLACARD.THE LABELWILLBE EFFECTIVELY BONDEDTO THEEXISTING FACILITY SWITCHBOARDAND THE NEW
PHOTOVOLTAICSYSTEMDISCONNECT.
CAUTION
UTILITY AC DISCONNECT
,
PHOTOVOLTAICAC DISCONNECT
PHOTOVOLTAICAC DISCONNECT
S Y S T E M O W N E R
G E N E R A T I O N M E T E R
F A C I L I T Y N E T
G E N E R A T I O N M E T E R
Arc flash andshock hazard.Appropriate PPErequired.
! DANGER
INV.XX
1000 VOLTS DC
208 VOLTS AC
CAUTIONLABEL
UV RESISTANT, REFLECTIVE MARKINGS
REQUIREDONALLINTERIORANDEXTERIORDCCONDUIT, RACEWAYS, ENCLOSURES, CABLE
ASSEMBLIES ANDJUNCTIONBOXES TO ALERTFIRE SERVICE. MARKINGS SHALLBE PLACEDEVERY 10FEET, AT TURNS, ADJACENT TOPENETRATIONS, AT ALLDC COMBINERBOXES,
ANDAT ALL DCJUNCTION BOXES. MARKINGCONTENT SHALLREAD, "CAUTION: SOLAR
CIRCUIT" INNON-BOLDARIALORSIMILARFONT
WITH3/8" ALL CAPS WHITE LETTERING ONREDBACKGROUND
POWER TO THIS SERVICE IS ALSO
SUPPLIED FROM THE FOLLOWINGSOURCES WITH DISCONNECTS
LOCATED AS SHOWN
W A R N I N G :E L E C T R I C S H O C K H A Z A R D , D O N O T
T O U C H T E R M I N A L S . T E R M I N A L S O N
B O T H T H E L I N E A N D L O A D S I D E S M A Y
B E E N E R G I Z E D I N T H O P E N P O S I T I O N
AC DIS CO NN ECT RA TIN GS :
O P E R A T I N G C U R R E N T : 2 0 0 A M P S
O P E R A T I N G V O L T A G E : 4 8 0 V O L T S A C
M A X I M U M C U R R E N T : 1 0 0 0 A M P S / P O L E
M A X I M U M V O L T A G E : 4 8 0 V O L T S A C
S O L A R P H O T O V O L T A IC
ARRA YLOC ATIO N
PHOTOVOLTAICAC DISCONNECT
AC DIS CO NN ECT RA TIN GS :O P E R A T I N G C U R R E N T : 1 6 0 0 A M P S
O P E R A T I N G V O L T A G E : 4 8 0 V O L T S A C
M A X I M U M C U R R E N T : 1 0 0 0 A M P S / P O L E
M A X I M U M V O L T A G E : 4 8 0 V O L T S A C
L O C AT IO N O F T H IS L ABEL IS O N T H E AC D ISC O N N EC T PL AC ED
BET W EEN C O MBIN ER BO X AN D T R AN SF O MER