1MW_ROOFTOP_SOLAR_PV_POWER_PLANT_PERMIT (1).pdf

Embed Size (px)

Citation preview

  • 7/26/2019 1MW_ROOFTOP_SOLAR_PV_POWER_PLANT_PERMIT (1).pdf

    1/9

    PROJECTTITLE:

    IN

    NOVATIVETYRES

    1M

    WC

    APTIVESOLARPV

    POWERPLANT

    SHEETTITLE:

    TITLESHEET

    Engineer:I hereby certify that this drawing

    by me or under my supe

    Date

    Date Marks

    DESIGNED BY

    DRAWN BY:

    CHECKED BY:

    SUPERVISED BY:

    Drawing Number

    T100

    INNOVATIVE TYRES, HALOL, GUJARATUTILITY SCALE SOLAR PV POWER PLANT

    1. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY

    PERMITS AND APPROVALS PRIOR TO STARTING ANY WORK.

    2. EXISTING UTILITIES SHALL REMAIN IN SERVICE AND IN

    PLACE UNLESS NOTED OTHERWISE. INTERRUPTION OF

    SERVICE SHALL BE KEPT TO A MINIMUM ANDONLY WITH

    THE APPROVAL OF THE ENGINEER AND CONTRACTING

    OFFICER.

    3. WORK SHALL BE PERFORMED IN ACCORDANCE WITH

    APPLICABLE OSHA REGULATIONS.

    4. CONTRACTOR TO VERIFY AND CHECK THE DIMENSIONS

    AND DETAIL PRIOR TO THE START OF CONSTRUCTION. ANY

    DISCREPANCY SHALL BE IMMEDIATELY REPORTED TO THE

    ENGINEER FOR CLARIFICATIONANBD RESOLUTION.

    5. CONTRACTOR SHALL EXERCISE DUE CARE AND DILIGENCE

    TO AVOID DAMAGE TO EXISTING UTILITIES, STRUCTURES OR

    OTHER SITE IMPROVEMENTS NOT DESIGNATED TO BE

    REMOVED OR MODIFIED. ANY DAMAGE TO EXISTING

    IMPROVEMENTS NOT DESIGNATED TO BE REMOVED OR

    MODIFIED SHALL BE RESTORED TO THEIR ORIGINAL

    CONDITION OR BETTER.

    SHEET NO. DWG NO. DESCRIPTION

    1 OF 09

    2 OF 09

    3 OF 09

    4 OF 09

    5 OF 09

    6 OF 09

    7 OF 09

    8 OF 09

    T100

    G101

    S101

    E101

    E102

    E103

    D101

    D102

    TITLE SHEET

    GENERAL NOTES

    SITE LAYOUT

    POWER ONE-LINE DIAGRAM (1)

    POWER ONE-LINE DIAGRAM (2)

    POWER ONE-LINE DIAGRAM (3)

    SPV MODULE DATASHEET

    SOLAR INVERTER DATASHEET

    ABBREVIATIONDRAWING INDEX

    LOCATION MAP VICINITY MAP GENERAL NOTES

    NORMALIZED PRODUCTION PER INSTALLED kWp

    (1000kWdc NOMINAL POWER)

    kWh/kWp/day

    OMSAISOLAR

    CONSULTING

    BURDWANWBINDIA

  • 7/26/2019 1MW_ROOFTOP_SOLAR_PV_POWER_PLANT_PERMIT (1).pdf

    2/9

    PROJECTTITLE:

    INNOVATIVETYRES

    1M

    WG

    RIDCONNECTED

    SOLARPVPOWERSYSTEM

    SHEETTITLE:

    GENERALNOTES

    ELECTRICAL

    Engineer:I hereby certify that this drawin

    by me or under my supe

    Date

    Date Marks

    DESIGNED BY

    DRAWN BY:

    CHECKED BY:

    SUPERVISED BY:

    Drawing Number

    G101

    GENERAL NOTES:

    1.DO NOTSCALE DRAWINGS, IF UNABLETO LOCATEDIMENSIONSFOR ANY ITEMOF WORK, CONSULTARCHITECT/ENGINEERFORDIRECTIONSBEFOREPROCEEDING.

    2.IN THEABSENCE OF THEEXACT ROOFDIMENSIONS,THE DRAWING WILLBASED ONGOOGLEMAP, THEREFORETHESEMAYNOTBE ACCURATE.CONTRACTOR ON SITE TO VERIFYALL OBSTACLESON THE ROOF ANDENSUREALL REQUIREDCLEARENCES WITH AUTHORITY HAVING JURISDICTION(S) PRIOR TO INSTALLATION, ORDERING MATERIAL OR

    FABRICATION

    3.CONTRACTOR SHALL OBTAINELECTRICALAND OTHERPERMITSPRIOR TOINSTALLATIONANDSHALL COORDINATEALLINSPECTIONS BY THECITY INSPECTORS,TESTING/ COMMISSIONING BY THEUTILITYCO. ANDACCEPTANCEBY THECLIENT, AS NEEDED.

    4.ROUTINGOR RACEWAYSMATERIAL SHALLBE AT THE OPTIONOF THECONTRACTOR, WITHIN THE CODE,UNLESSOTHERWISENOTED ANDSHALLBE COORDINATED WITH OTHERTRADES.

    5. IF THEROOF MATERIALOR ROOF STRUCTUREIS NOT ADEQUATE FOR PVI NSTALLATION, CALL ENGINEER PRIOR TOINSATLL.THECONTRACTORISRESPONSIBLETOVERIFY THAT ROOF IS CAPABLE OF WITHSTANDINGTHE EXTRAWEIGHT.

    6.WHENEVER A DISCREPANCY IN QUANTITY OF EQUIPMENT ARISES ON THE DRAWING OR SPECIFICATIONS, THECONTRACTOR SHALL BERESPONSIBLE FOR PROVIDINGAND INSTALLING ALL MATERIAL AND SERVICES REQUIREDBYSTRICTEST CONDITIONSNOTED ON THE DRAWING OR IN THE SPECIFICATIONS TO ENSURE COMPLETE COMPLIANCEAND

    LONGEVITY OF THEOPERABLESYSTEMREQUIRED BYTHE ARCHITECT/ENGINEER

    7.THIS DESIGNI SFULLY BASEDON THE INFORMATION PROVIDED BYTHE DEVELOPER,ANY MODIFICATIONSOR REMOVALOF THE LOGO OFTHE EPC;"VARIETAS PROJECTMANAGERS &ENGINEERS" IS NOT ALLOWED AND WILL RENDER THISDESIGN VOID.

    8.THE WORKING CLEARANCE AROUNDTHE EXISTING ELECTRICAL EQUIPMENTS AS WELL AS THE NEW ELECTRICALEQUIPMENTWILL BE MAINTAINEDIN ACCORDANCE WITH.

    9.ADEQUATE SPACING MUSTBE MAINTAINEDBETWEEN ANY PLUMBING/SEWERVENTS EXTENDINGTHROUGH THEROOFANDUNDERSIDE OF THEPHOTOVOLTAIC PANELS(6''MINIMUM RECOMMENDED).

    ELECTRICAL NOTES AND STANDARDS TO FOLLOW:

    GENERAL NOTES

    IEC 60050V(826)

    IEC 60068

    IEC 60364-7-712

    IEC 60439-1

    IEC 60755

    IEC 61215

    IEC 61683

    IEC 61701

    IEC 61724

    IEC 61730

    IEC 62305

    IEC 62446

    IEC 62548

    IEC 62109-1:2010

    IEC 62116

    ELECTRICAL INSTALLATIONS OF BUILDINGS

    ENVIRONMENTAL TESTING

    REQUIREMENTSFOR SPECIAL INSTALLATIONS OR LOCATIONS SOLAR PHOTOVOLTAIC(PV) POWER SUPPLYSYSTEMS

    LOWVOLTAGESWITCHGEAR &CONTROLGEAR ASSEMBLIES

    GENERAL REQUIREMENTS FOR RESIDUAL CURRENT OPERATEDPROTECTIVE DEVICES(OCPD)

    CRYSTALLINE SILICONTERRESTIAL PHOTOVOLTAIC(PV) MODULES DESIGNQUALIFICATION ANDTYPE APPROVAL

    EFFICIENCY MEASUREMENTSANDENVIRONMENTAL TESTS OFPOWER CONDITIONINGUNITS(PCUs)

    PVMODULESTOBE USED IN A HIGHLYCORROSIVE ATMOSPHERE

    PHOTOVOLTAIC SYSTEMPERFORMANCE MONITORING GUIDELINES FOR MEASUREMENT,DATAEXCHANGEANDANALYSIS

    PART-2:REQUIREMENTSFOR CONSTRUCTION&PART-2:REQUIREMENTSFOR TESTING, FOR SAFETYQUALIFICATION

    LIGHTINGPROTECTION

    GRIDCONNECTED PHOTOVOLTAIC SYSTEMSMINIMUM REQUIREMENTSFOR SYSYTEM DOCUMENTATION,COMMISSIONING TESTSANDINSPECTION

    PHOTOVOLTAIC ARRAYSDESIGNREQUIREMENTS

    SAFETY OFPOWER CONVERTERS FOR USE INPHOTOVOLTAIC POWER SYSTEMS

    UTILITY-INTERCONNECTEDPHOTOVOLTAICINVERTERSTEST PROCEDURE OF ISLANDINGPREVENTIONMEASURES

    IEC 61727

    IEC 61000

    IEC 62305

    IEC 61643-11

    TUV 2PfG1169

    AS1319

    APPLICABLEJUNCTIONBOX

    STANDARDS

    IEC 60664

    IEC 50548

    IEC 60529

    IEC 60269

    IEC 62208

    EN60715

    APPLICABLESWITCHBOARD

    STANDARDS

    ICE 60947

    PHOTOVOLTAIC SYSTEMS -CHARACTERISTICSOFTHEUTILITYINTERFACES

    ELECTROMAGNETICCOMPATIBILITY(EMC)

    LIGHTNINGPROTECTIONSTANDARD

    LOWVOLTAGESURGE PROTECTIVE DEVICES REQUIREMNETS&TESTS FOR SPDs IN PHOTOVOLTAICAPPLICATIONS

    TUV INTERNAL CABLESTANDARD

    SAFETY SIGNSFOR THE OCCUPATIONAL ENVIRONMENT

    CREEPAGE DISTANCES ANDCLEARANCES

    JUNTION BOXES

    DEGREESOFPROTECTION PROVIDEDBYTHE ENCLOSURES

    LOWVOLTAGEFUSES

    COPPER BUS BARS /TERMINAL BLOCKS HOUSEDIN THE JUNCTIONBOX WITHSUITABLE TERMINATIONTHREADS

    CHROMATEDDINRAIL

    LOWVOLTAGEACSWITCHGEAR ANDCONTROL GEARS SPECIFICATIONS

    IEC 60439

    IEC 60947

    IEC 60529

    IEC 60404

    IEC 62056

    IEC 60364

    IEC 60947.2

    IEC 60439

    IEC EN 60269-1

    IEC 60529

    APPLICABLESTANDARDSFOR LOW

    VOLTAGE ACCABLES

    IEC 60840

    IEC 60502

    IEC 60227,60228

    APPLICABLELOCAL STANDARDS

    LOWVOLTAGEACSWITCHGEAR ANDCONTROL GEARSASSEMBLIES

    GENERAL REQUIREMENTS FOR ACSWITCHGEAR &CONTROLGEAR VOLTAGE

  • 7/26/2019 1MW_ROOFTOP_SOLAR_PV_POWER_PLANT_PERMIT (1).pdf

    3/9

    PROJECTTITLE:

    INNOVATIVETYRES

    1M

    WG

    RIDCONNECTED

    SOLARPVPOWERSYSTEM

    SHEETTITLE:

    POWERONE-LINE

    DIAGRAM

    PVtoSTRINGS

    Engineer:

    I hereby certify that this drawing

    by me or under my supe

    Date

    Date Marks

    DESIGNED BY

    DRAWN BY:

    CHECKED BY:

    SUPERVISED BY:

    Drawing Number

    E101

    POWER ONE-LINE DIAGRAM

    PV TO STRINGS

    6 sq.mm

    BARE COPPER

    GROUNDING WIRE

    +

    -

    +

    -

    +

    -

    +

    -

    RAIL

    GROUNDING LUG

    1

    STRING #G1, 20 MODULES

    -

    ....

    -

    +

    +

    ----

    RAIL

    GROUNDING LUG

    6

    -

    ....

    -

    +

    +

    -

    +

    -

    +

    -

    +

    -

    RAIL

    GROUNDING LUG

    11

    -

    ....

    -

    +

    +

    ----

    RAIL

    GROUNDING LUG

    16

    -

    ....

    -

    +

    6 sq.mm PV WIRE

    6 sq.mm PV WIRE

    20

    MODULE MFR: JINKO SOLARMODEL: JKM250P

    VOC

    = 37.7V

    VMP

    = 30.5V

    ISC

    = 8.85A

    IMP = 8.20A

    PV MODULE RATINGS @ STC

    OMSAISOLAR

    CONSULTING

  • 7/26/2019 1MW_ROOFTOP_SOLAR_PV_POWER_PLANT_PERMIT (1).pdf

    4/9

    PROJECTTITLE:

    INNOVATIVETYRES

    1M

    WG

    RIDCONNECTED

    SOL

    ARPVPOWERSYSTEM

    SHEETTITLE:

    POWERONE-LINE

    DIAGRAM

    STRINGSTOINVERTERTOSUB-PANEL

    Engineer:I hereby certify that this drawin

    by me or under my sup

    Date

    Date Marks

    DESIGNED BY

    DRAWN BY:

    CHECKED BY:

    SUPERVISED BY:

    Drawing Number

    E102

    #10 AWG THWNMODULE/RACKING

    EGC

    +-

    +-

    +-

    +-

    DC.1

    RAILGROUNDING LUG

    1 .... .... 20

    #10 AWG THWNMODULE/RACKING

    EGC

    +-

    +-

    +-

    +-

    DC.1

    RAILGROUNDING LUG

    1 .... ....

    STRING#A1, 2MODULES

    STRING #B1, 20 MODULES

    #10 AWG THWNMODULE/RACKING

    EGC

    +-

    +-

    +-

    +-

    DC.1

    RAILGROUNDING LUG

    1 .... ....

    STRING #C1, 20 MODULES

    CONDUIT

    114" EMT

    DC.2

    +- +- +- +- +- +- +- +-GMPPT

    1MPPT

    2

    "INV#1"INGETEAM 24TL-U-M480WITH BOTHDC & ACDISCONNECT

    &ARC-FUALT INTEREPTER

    L3L2

    NG

    L1

    DC DISC.

    AC DISC. (n)

    40A/3P

    GNEU

    (n)200A 3P

    NEW PV SUB-PANEL, "SP1"200A BUSMINUMUM,277/480V 4W

    CONDUIT

    1- "

    EMT

    AC.1

    CONDUIT

    1-" E

    MT

    AC.2

    #10 AWG THWNMODULE/RACKING

    EGC

    --

    DC.1

    RAILGROUNDING LUG

    ....

    #10 AWG THWNMODULE/RACKING

    EGC

    +-

    +-

    +-

    +-

    DC.1

    RAILGROUNDING LUG

    1 .... ....

    STRING#E1,20 MODULES

    CONDUIT

    114" EMT

    DC.2

    +-

    +-

    +-

    +-

    RAILGROUNDING LUG

    1 .... ....

    STRING #D1, 20 MODULES

    --

    STRING #A2, 20 MODULES

    STRING #B2, 20 MODULES

    STRING #C2, 20 MODULES

    "INV#2"

    & ARC-FUALT INTEREPTER

    STRING #E2, 20 MODULES

    STRING #D2, 20 MODULES

    STRING #E3, 20 MODULES

    STRING #D3, 20 MODULES

    STRING #A3, 20 MODULES

    STRING #B3, 20 MODULES

    STRING #C3, 20 MODULES

    "INV#3"

    & ARC-FUALT INTEREPTER

    INVERTER MFR: INGETEAM

    INVERTER MODEL: 24TL U M480DC VOLT RATING = 1000V

    OPERATING VOLTAGE =580-950V

    DC MAX USABLE INPUT CURRENT:

    PER MPPT = 27APER INVERTER = 54A

    AC MAX RATED OUTPUT POWER = 24000W

    AC MAX OUTPUT CURRENT

    MIN WIRE SIZE = 29A * 125% = 36.25AMIN (OCPD) = 40A, AVAILABLE (OCPD) =40A

    MODULE MFR: ZINKO SOLARMODEL: 250Wp

    VOC

    = 37.7V

    VMP

    = 30.5V

    ISC

    = 8.85A

    IMP = 8.20A

    21

    21

    21

    21

    = 29A

    C IR CU IT DE SC RI PT IO N C ON DU CT OR S IZ E/ TY PE C ON DU IT S I ZE */ QT Y

    (DC) SOLARSTRING

    WIRING2-CORE 6 sq.mm FA

    (DC) STRINGTO INVERTER (5

    STRINGS) (5)2-CORE 6 sq.mm (2) 1- in

    (AC) INVERTER TOCOMBINER BOX (5INVERTERS) (5)4-CORE 16 sq.mm (1) 1- in

    (AC) GECGROUNDING (1)BARECOPPER10mm (1) 1 in

    (DC) GECGROUNDING (1)BARECOPPER6mm (1) in

    1-WAY WIRETRAVELVOLTAGE

    @MAXPOWER

    - 622 Vdc

    350 ft 622 Vdc

    140 ft 480VAC

    65 ft 480VAC

    450 ft 622 Vdc

    CURRENT

    @MAXPOWERVOLTAGEDROP(%)

    8.53A 0.5%

    2*8.53A 0.5%

    29A 0.80%

    - -

    - -

    (A)

    (B)

    (C)

    (D)

    (E)

    POWER ONE-LINE DIAGRAM

    STRINGS TO INVERTER TO SUB-PANEL

    40A/3P

    40A/3P

    PV MODULE RATINGS @ STC

    PV INVERTER RATINGS

    STRING #E4, 20 MODULES

    STRING #D4, 20 MODULES

    STRING #A4, 20 MODULESSTRING #B4, 20 MODULES

    STRING #C4, 20 MODULES

    "INV#4"

    & ARC-FUALT INTEREPTER

    40A/3P40A/3P

    STRING #E5, 20 MODULES

    STRING #D5, 20 MODULES

    STRING #A5, 20 MODULES

    STRING #B5, 20 MODULES

    STRING #C5, 20 MODULES

    "INV#5"

    & ARC-FUALT INTEREPTER

    INGETEAM 24TL-U-M480WITH BOTH DC & AC DISCONNECT

    INGETEAM 24TL-U-M480WITH BOTHDC & ACDISCONNECT

    INGETEAM 24TL-U-M480WITH BOTHDC & ACDISCONNECT

    INGETEAM 24TL-U-M480WITH BOTH DC & AC DISCONNECT

    OMSAISOLAR

    CONSULTING

    BURDWAN,WB,INDIA

  • 7/26/2019 1MW_ROOFTOP_SOLAR_PV_POWER_PLANT_PERMIT (1).pdf

    5/9

    PROJECTTITLE:

    INNOVATIVETYRES

    1M

    WG

    RIDCONNECTED

    SOL

    ARPVPOWERSYSTEM

    SHEETTITLE:

    POWERLINE

    DIAGRAM

    Engineer:

    I hereby certify that this drawing

    by me or under my supeDate I

    Date Marks

    DESIGNED BY

    DRAWN BY:

    CHECKED BY:

    SUPERVISED BY:

    Drawing Number

    E103

    (n)

    AC.2

    G

    H1

    H2 H3

    NEW 1250kVATRANSFORMER#1

    SECONDARY

    14kV Delta

    PRIMARY

    480 Wye

    G

    X1

    X2 X3

    H0

    ARRAY CONFIGURATIONNo. of Inverters:40

    Strings Per Inverter: 5

    (n)

    40A/3P

    GNEU

    (n)

    200A 3P

    NEW PV SUB-PANEL, "SP1"200A BUSMINUMUM, 277/480V 4W

    CONDUIT

    1-"EMT

    AC.2

    40A/3P

    40A/3P

    40A/3P

    40A/3P

    INV#1

    A#1, 20SPVMODULES

    B#1, 20SPVMODULES

    C#1, 20SPVMODULES

    D#1, 20SPVMODULES

    E#1, 20SPVMODULES

    INV#2

    A#2, 20SPVMODULES

    B#2, 20SPVMODULES

    C#2, 20SPVMODULES

    D#2, 20SPVMODULES

    E#2, 20SPVMODULES

    INV#3

    A#3, 20SPVMODULES

    B#3, 20SPVMODULES

    C#3, 20SPVMODULES

    D#3, 20SPVMODULES

    E#3, 20SPVMODULES

    INV#4

    A#4,20SPVMODULES

    B#4, 20SPVMODULES

    C#4, 20SPVMODULES

    D#4,20SPVMODULES

    E#4, 20SPVMODULES

    INV#5

    A#5, 20SPVMODULES

    B#5,20SPVMODULES

    C#5, 20SPVMODULES

    D#5, 20SPVMODULES

    E#5, 20SPVMODULES

    TOTALSTRINGSIZE = 25kWp,

    5x20SPV

    INV#6

    TOTALSTRINGSIZE = 25kWp,5x20SPV

    INV#7

    TOTALSTRINGSIZE = 25kWp,5x20SPV

    TOTALSTRINGSIZE = 25kWp,

    5x20SPV

    TOTALSTRINGSIZE = 25kWp,5x20SPV

    INV#8

    INV#9

    INV#10

    NEW PV SUB-PANEL, "SP2"200A BUSMINUMUM,277/480V 4W

    40A/3P

    40A/3P

    40A/3P

    40A/3P

    40A/3P

    INPUT SIDE

    OUTPUT SIDE

    200A3P

    TOTALSTRINGSIZE = 25kWp,5x20SPV

    INV#11

    TOTALSTRINGSIZE = 25kWp,

    5x20SPV

    INV#12

    TOTALSTRINGSIZE = 25kWp,

    5x20SPV

    TOTALSTRINGSIZE = 25kWp,5x20SPV

    TOTALSTRINGSIZE = 25kWp,5x20SPV

    INV#13

    INV#14

    INV#15

    NEW PV SUB-PANEL, "SP3"200A BUSMINUMUM, 277/480V 4W

    40A/3P

    40A/3P

    40A/3P

    40A/3P

    40A/3P

    INPUT SIDE

    OUTPUT SIDE

    200A3P

    TOTALSTRINGSIZE = 25kWp,5x20SPV

    INV#16

    TOTALSTRINGSIZE = 25kWp,5x20SPV

    INV#17

    TOTALSTRINGSIZE = 25kWp,

    5x20SPV

    TOTALSTRINGSIZE = 25kWp,5x20SPV

    TOTALSTRINGSIZE = 25kWp,

    5x20SPV

    INV#18

    INV#19

    INV#20

    NEW PV SUB-PANEL, "SP4"200A BUSMINUMUM, 277/480V 4W

    40A/3P

    40A/3P

    40A/3P

    40A/3P

    40A/3P

    INPUT SIDE

    OUTPUT SIDE

    200A3P

    TOTALSTRINGSIZE = 25kWp,

    5x20SPV

    INV#21

    TOTALSTRINGSIZE = 25kWp,5x20SPV

    INV#22

    TOTALSTRINGSIZE = 25kWp,5x20SPV

    TOTALSTRINGSIZE = 25kWp,

    5x20SPV

    TOTALSTRINGSIZE = 25kWp,5x20SPV

    INV#23

    INV#24

    INV#25

    NEW PV SUB-PANEL, "SP5"200A BUSMINUMUM, 277/480V 4W

    40A/3P

    40A/3P

    40A/3P

    40A/3P

    40A/3P

    INPUT SIDE

    OUTPUT SIDE

    200A3P

    TOTALSTRINGSIZE = 25kWp,

    5x20SPV

    INV#26

    TOTALSTRINGSIZE = 25kWp,

    5x20SPV

    INV#27

    INV#28

    NEW PV SUB-PANEL, "SP6"200A BUSMINUMUM, 277/480V 4W

    40A/3P

    40A/3P

    40A/3P

    INPUT SIDE

    TOTALSTRINGSIZE = 25kWp,5x20SPV

    INV#31

    TOTALSTRINGSIZE = 25kWp,

    5x20SPV

    INV#32

    TOTALSTRINGSIZE = 25kWp,

    5x20SPV

    TOTALSTRINGSIZE = 25kWp,5x20SPV

    TOTALSTRINGSIZE = 25kWp,5x20SPV

    INV#33

    INV#34

    INV#35

    NEW PV SUB-PANEL,"SP7"200A BUSMINUMUM, 277/480V 4W

    40A/3P

    40A/3P

    40A/3P

    40A/3P

    40A/3P

    INPUT SIDE

    OUTPUT SIDE

    200A3P

    TOTALSTRINGSIZE = 25kWp,5x20SPV

    INV#36NEW PV SUB-PANEL, "SP8"

    200A BUSMINUMUM, 277/480V 4W

    INPUT SIDE

    200A 3P

    POWER ONE-LINE DIAGRAM

    COMPLETE SOLAR PV SYSTEM

    OMSAISOLAR

    CONSULTING

    BURDWAN,WB,INDIA

    o m s s c o n s u l t i n g @ g m a i l c o m

    AC SIDECOMBINERBOXCB1

    GN

    AUXILIARYGUTTER

    M1

    LOADS

    G NEU

    GG

    3/4"C-1#4

    (e)GROUND RODS 6'-0"

    (2) 3/4" x 10'APART TYPICAL

    CONDUIT

    2" EMT

    AC.3

    (e)SWITCHBOARD 11000/440V 3PH

    2500A BUSBAR

    POINTOF CONNECTIONPER 690.64; 705.12(D)

    SPLICES& TAPS PER 366.56

    (3) POLARISSTACKEDCONNECTORS IPLDS

    LOCKABLE &

    AC.2

    120A, 11kV FUSED AC CIRCUIT BREAKER

  • 7/26/2019 1MW_ROOFTOP_SOLAR_PV_POWER_PLANT_PERMIT (1).pdf

    6/9

    PROJECTTITLE:

    INNOVATIVETYRES

    1M

    WG

    RIDCONNECTED

    SOL

    ARPVPOWERSYSTEM

    SHEETTITLE:

    SITELAYOUT

    SUGGESTEDPVARRAYLAYOUT

    Engineer:

    I hereby certify that this drawing

    by me or under my supe

    Date

    Date Marks

    DESIGNED BY

    DRAWN BY:

    CHECKED BY:

    SUPERVISED BY:

    Drawing Number

    S101

    SITE LAYOUT

    WITH SUGGESTED PV ARRAY LAYOUT

    OMSAISOLAR

    CONSULTING

  • 7/26/2019 1MW_ROOFTOP_SOLAR_PV_POWER_PLANT_PERMIT (1).pdf

    7/9

    PROJECTTITLE:

    INNOVATIVETYRES

    1M

    WG

    RIDCONNECTED

    S O L

    A R P V P O W E R S Y S T E M

    SHEETTITLE:

    DATASHEET

    SOLAR

    PHOTOVOLTAIC

    M O D U L E

    Engineer:I hereby certify that this drawin

    by me or under my supe

    Date

    Date Marks

    DESIGNED BY

    DRAWN BY:

    CHECKED BY:

    SUPERVISED BY:

    Drawing Number

    D101

    BURDWAN,WB,INDIA

    l i @ i l

    OMSAISOLAR

    CONSULTING

    SOLAR PHOTOVOLTAIC MODULEDATA SHEET

  • 7/26/2019 1MW_ROOFTOP_SOLAR_PV_POWER_PLANT_PERMIT (1).pdf

    8/9

    B U R D W A N

    W B I N D I A

    PROJECTTITLE:

    INNOVATIVETYRES

    1M

    WG

    RIDCONNECTED

    S O L

    A R P V P O W E R S Y S T E M

    SHEETTITLE:

    DATA

    SHEET

    SOLARINVERTER

    Engineer:I hereby certify that this drawing

    by me or under my supe

    Date

    Date Marks

    DESIGNED BY

    DRAWN BY:

    CHECKED BY:

    SUPERVISED BY:

    Drawing Number

    D102

    SOLAR INVERTERDATA SHEET

    OMSAISOLAR

    CONSULTING

  • 7/26/2019 1MW_ROOFTOP_SOLAR_PV_POWER_PLANT_PERMIT (1).pdf

    9/9

    BURDWAN,WB,INDIA

    [email protected]

    +918116401052

    PROJECTTITLE:

    INNOVATIVETYRES,HALOL,GUJARAT

    GRID-CONNECTEDSOLARPVSYSTEM

    SYSTEMS

    IZE:

    1000kWdc

    SITEADDRESS:

    MIDC,HALOL,GUJARAT,INDIA

    SHEETTITLE:

    LABELS

    Engineer:I hereby certify that this drawing was

    prepared by me or under my supervision

    Date Issue

    Date Marks Revisions

    DESIGNED BY

    DRAWN BY:

    CHECKED BY:

    SUPERVISED BY:

    Drawing Number

    L100

    Scale:

    AS SHOWN

    Sheet No.

    09 OF 09

    Date:

    02/06/2016

    LABEL AND MARKINGS LEGEND:

    PROVIDES THE LOCATIONOF THE SERVICEDISCONNECTING MEANS ANDTHEPHOTOVOLTAICDISCONNECTING MEANS. THISPLAQUE SHALLBE APPLIEDTO THE MAIN

    SERVICE DISCONNECTING MEANS ANDTHE

    PHOTOVOLTAICDISCONNECTING MEANS; (2TOTAL)

    LABELFORUTILITY ACDISCONNECT; 1 PERAC

    DISCONNECT.

    UTILITY ACDISCONNECT WARNING LABEL. 1PERACDISCONNECT ANDALL3 ACLOADCENTERS.

    UTILITY ACDISCONNECT OPERATINGSPECIFICATIONS. 1PER ACDISCONNECT SITUATED

    BETWEENSUB-PANELAND COMBINERBOX

    LABELFORSYSTEMOWNER'S KWHGENERATIONMETER; 1PER OWNERMETER.

    LABELFOR FACILITY NET GENERATIONMETER; 1

    PERFACILITY GENERATIONMETER.

    LABELFORARCFLASHWARNING. 1PER

    ENERGIZEDENCLOSURE WITHACCESS TO LIVEPARTS.

    ONE PERINVERTER. NUMBERSEQUENTIALLY

    CONDUIT RUNFROMSOURCE CIRCUT TOINVERTER. (AS NEEDED)

    CONDUIT RUNFROMINVERTER TO POCC. (ASNEEDED)

    GENERAL NOTES FOR LABELS ANDMARKINGS:

    1. LABELS ANDMARKINGS SHALLBE APPLIEDTOTHE APPROPRIATE COMPONENTS IN

    ACCORDANCE WITHTHE NEC.

    2. SOLARMODULES ARE SUPPLIEDFROMTHEMANUFACTURERWITHMARKINGS PRE-APPLIEDTOMEET THE REQUIREMENTS OF THE NEC.

    3. NEXTRONEX ANDSOLAR EDGE INVERTERS ARESUPPLIEDFROM THE MANUFACTURERWITHTHEAPPROPRIATE LABELS ANDMARKINGS TO MEETTHE REQUIREMENTS OF THE NEC.

    4. TEXT LABELS WILLBE ETCHEDWITHWHITEGRAPHICS ONTO 1/16" REDPLASTICPLACARDS.

    THE LABELWILLBE MECHANICALLY ATTACHEDTOTHE APPROPRIATE COMPONENT ENCLOSURES INCONSPICUOUS PLACES.

    5. LABEL"A" WILLBE ETCHEDWITH WHITE

    GRAPHICS ONTO 1/16" REDPLASTICPLACARD.THE LABELWILLBE EFFECTIVELY BONDEDTO THEEXISTING FACILITY SWITCHBOARDAND THE NEW

    PHOTOVOLTAICSYSTEMDISCONNECT.

    CAUTION

    UTILITY AC DISCONNECT

    ,

    PHOTOVOLTAICAC DISCONNECT

    PHOTOVOLTAICAC DISCONNECT

    S Y S T E M O W N E R

    G E N E R A T I O N M E T E R

    F A C I L I T Y N E T

    G E N E R A T I O N M E T E R

    Arc flash andshock hazard.Appropriate PPErequired.

    ! DANGER

    INV.XX

    1000 VOLTS DC

    208 VOLTS AC

    CAUTIONLABEL

    UV RESISTANT, REFLECTIVE MARKINGS

    REQUIREDONALLINTERIORANDEXTERIORDCCONDUIT, RACEWAYS, ENCLOSURES, CABLE

    ASSEMBLIES ANDJUNCTIONBOXES TO ALERTFIRE SERVICE. MARKINGS SHALLBE PLACEDEVERY 10FEET, AT TURNS, ADJACENT TOPENETRATIONS, AT ALLDC COMBINERBOXES,

    ANDAT ALL DCJUNCTION BOXES. MARKINGCONTENT SHALLREAD, "CAUTION: SOLAR

    CIRCUIT" INNON-BOLDARIALORSIMILARFONT

    WITH3/8" ALL CAPS WHITE LETTERING ONREDBACKGROUND

    POWER TO THIS SERVICE IS ALSO

    SUPPLIED FROM THE FOLLOWINGSOURCES WITH DISCONNECTS

    LOCATED AS SHOWN

    W A R N I N G :E L E C T R I C S H O C K H A Z A R D , D O N O T

    T O U C H T E R M I N A L S . T E R M I N A L S O N

    B O T H T H E L I N E A N D L O A D S I D E S M A Y

    B E E N E R G I Z E D I N T H O P E N P O S I T I O N

    AC DIS CO NN ECT RA TIN GS :

    O P E R A T I N G C U R R E N T : 2 0 0 A M P S

    O P E R A T I N G V O L T A G E : 4 8 0 V O L T S A C

    M A X I M U M C U R R E N T : 1 0 0 0 A M P S / P O L E

    M A X I M U M V O L T A G E : 4 8 0 V O L T S A C

    S O L A R P H O T O V O L T A IC

    ARRA YLOC ATIO N

    PHOTOVOLTAICAC DISCONNECT

    AC DIS CO NN ECT RA TIN GS :O P E R A T I N G C U R R E N T : 1 6 0 0 A M P S

    O P E R A T I N G V O L T A G E : 4 8 0 V O L T S A C

    M A X I M U M C U R R E N T : 1 0 0 0 A M P S / P O L E

    M A X I M U M V O L T A G E : 4 8 0 V O L T S A C

    L O C AT IO N O F T H IS L ABEL IS O N T H E AC D ISC O N N EC T PL AC ED

    BET W EEN C O MBIN ER BO X AN D T R AN SF O MER