ABB Switzerland Ltd 1KHW001757-EN Archive No.: Rev. Date: Upgrade Options for P4LT and P4LU - _
Responsible Department: Prepared: Approved: Distribution: Lang.: Page:
PSND 2006-11-15 M. Dick 2007-02-14 Ch.Leeb - EN 1/5 Valid for: Derived from: Replaces: Classification-No.: File:
- - - 1KHW001757_e Upgrade Options for P4LT and P4LU.doc
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. © ABB Switzerland Ltd
Power Line Carrier Equipment: Series ETL600
Upgrade Options for P4LT and P4LU
Contents
1 Purpose of document 2 2 Safety instructions 2 3 Upgrade P4LU with R1LA 2
List of equipment:
PC with Windows 2000 or XP
HMI600 software PC P4LT/P4LU cable 1:1 serial RS-232 Torx screwdriver Size: 8
Note:
• Please refer 1KHW001490 for compatibility between software HMI600, firmware and hardware of ETL600.
Revision: Language: Page:
_ EN 2/5 1KHW001757-EN
1 Purpose of document
This document describes mounting of upgrade options for P4LT and P4LU.
2 Safety instructions
ESD protection
Caution The modules in this equipment contain devices, which can be damaged by electrostatic discharges. Appropriate measures must be taken before unpacking modules or withdrawing them from equipment racks. Essential precautions to prevent ESD damage when handling or working on modules are grounding straps for technical personnel and the provision of anti-static workbenches. Modules may only be shipped either in their original packing or installed in equipment racks.
ESD
3 Upgrade P4LU with R1LA
For new projects and systems the module “P4LU with R1LA” has to be ordered if LAN600 functions are required, i.e. R1LA is already assembled on P4LU ex works. In the exceptional case when a P4LU shall be upgraded with R1LA (using the optional R1LA upgrade kit), the following - rather unusual - procedure may be applied to avoid completely disassembling of the module P4LU.
Note:
The module R1LA is only compatible with P4LUa, not with P4LU and P4LT/P4LTa.
Note:
1. Switch off power to ETL600. 2. Unplug the P4LU board from ETL600 channel rack P7LC. 3. Remove the two torx screws ( Fig. 1). 4. Insert a 25 mm spacer between corner of P1LX and P4LT ( Fig. 2).
Fig. 35. Remove torx screw and washers from spacer at connector side of R1LA ( ) and put them aside.
6. Insert R1LA board ( Fig. 4) and place it such that the connector pins marked in Fig. 3 are inserted into the corresponding sockets on P1LX.
7. Fix R1LA to P1LX with washer, spring washer and torx screw from step 5 ( Fig. 5, Fig. 6).
8. Remove the spacer inserted in step 4. 9. Remount the two torx screws removed in step 3 ( Fig. 7). 10. Plug P4LU back into ETL600 channel rack P7LC. 11. Switch on power to ETL600.
Revision: Language: Page:
_ EN 3/5 1KHW001757-EN
Fig. 1 Remove the two indicated torx screws
Max 25mm!
Fig. 2 Insert a spacer with a maximum height of 25mm.
Fig. 3 Bottom side of R1LA
Torx screw and washers to be removed
Connector pins to be inserted into corresponding sockets on P1LX
Revision: Language: Page:
_ EN 4/5 1KHW001757-EN
Fig. 4 Inserting R1LA between P1LX and P4LT
Fig. 5 Tightening screw to fix R1LA in place
Revision: Language: Page:
_ EN 5/5 1KHW001757-EN
Fig. 6 R1LA installed and fixed in place with screw
Fig. 7 Remount the two torx screws