Installation Instructions FLEX I/O Digital Input and Output Modules with Diagnostics Catalog numbers 1794-IB16D, 1794-OB16D Table of Contents Topic Page Important User Information 2 Environment and Enclosure 3 Preventing Electrostatic Discharge 3 North American Hazardous Location Approval 6 Install the Isolated Analog Output Module 7 Diagnostics 11 Configuration 14 Specifications 16

1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

Installation Instructions

FLEX I/O Digital Input and Output Modules with DiagnosticsCatalog numbers 1794-IB16D, 1794-OB16D

Table of Contents

Topic Page

Important User Information 2

Environment and Enclosure 3

Preventing Electrostatic Discharge 3

North American Hazardous Location Approval 6

Install the Isolated Analog Output Module 7

Diagnostics 11

Configuration 14

Specifications 16

Page 2: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

2 FLEX I/O Digital Input and Output Modules with Diagnostics

Important User Information

Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation, and Maintenance of Solid-State Controls (Publication SGI-1.1 available from your local Rockwell Automation Sales Office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequences.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

Publication 1794-IN096D-EN-P - June 2018

Page 3: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

FLEX I/O Digital Input and Output Modules with Diagnostics 3

Environment and Enclosure

Preventing Electrostatic Discharge

ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in EN/IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.

This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments.

This equipment is supplied as open-type equipment for indoor use. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain more information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.

In addition to this publication, see the following:

• Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1, for more installation requirements.

• NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.

ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:

• Touch a grounded object to discharge potential static.• Wear an approved grounding wriststrap.• Do not touch connectors or pins on component boards.• Do not touch circuit components inside the equipment.• Use a static-safe workstation, if available.• Store the equipment in appropriate static-safe packaging when not in use.

Publication 1794-IN096D-EN-P - June 2018

Page 4: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

4 FLEX I/O Digital Input and Output Modules with Diagnostics

ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc plated chromate-passivated steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately. Be sure to ground the DIN rail properly. Refer to Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1, for more information

ATTENTION: If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

ATTENTION: If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

ATTENTION: Read this document and the documents listed in the Additional Resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.

ATTENTION: Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.

ATTENTION: In case of malfunction or damage, no attempts at repair should be made. The module should be returned to the manufacturer for repair. Do not dismantle the module.

ATTENTION: Use only a soft dry anti-static cloth to wipe down equipment. Do not use any cleaning agents.

Publication 1794-IN096D-EN-P - June 2018

Page 5: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

FLEX I/O Digital Input and Output Modules with Diagnostics 5

WARNING: When you insert or remove the module while backplane power is on, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electric arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.

WARNING: If you insert or remove the module while backplane power is on, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

Publication 1794-IN096D-EN-P - June 2018

Page 6: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

6 FLEX I/O Digital Input and Output Modules with Diagnostics

North American Hazardous Location ApprovalThe following modules are North American Hazardous Location approved: 1794-IB16D, 1794-OB16D.

The following information applies when operating this equipment in hazardous locations:

Informations sur l’utilisation de cet équipement en environnements dangereux:

Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation

WARNING: Explosion Hazard• Do not disconnect equipment unless power

has been removed or the area is known to be nonhazardous.

• Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.

• Substitution of components may impair suitability for Class I, Division 2.

AVERTISSEMENT: Risque d’Explosion• Couper le courant ou s'assurer que

l'environnement est classé non dangereux avant de débrancher l'équipement.

• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.

• LLa substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.

Publication 1794-IN096D-EN-P - June 2018

Page 7: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

FLEX I/O Digital Input and Output Modules with Diagnostics 7

Install the Isolated Analog Output Module

The input module mounts on a 1794-TB32 or 1794-TB32S terminal base. The output module mounts on a 1794-TB2, 1794-TB3, or 1794-TB3S terminal base.

1. Rotate the keyswitch (3) on the terminal base (4) clockwise to position 4 as required for this type of module.

2. Make sure the Flexbus connector (1) is pushed all the way to the left to connect with the neighboring terminal base/adapter. You cannot install the module unless the connector is fully extended.

3. Make sure the pins on the bottom of the module are straight so they will align properly with the connector in the terminal base.

4. Position the module (7) with its alignment bar (6) aligned with the groove (5) on the terminal base.

5. Press firmly and evenly to seat the module in the terminal base unit. The module is seated when the latching mechanism (2) is locked into the module.

Component Identification

Description Description

1 Flexbus connectors 5 Groove

2 Latching mechanism 6 Alignment bar

3 Keyswitch 7 Module

4 Terminal base

6

1

7

5

4

3

2

45284

Publication 1794-IN096D-EN-P - June 2018

Page 8: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

8 FLEX I/O Digital Input and Output Modules with Diagnostics

1794-TB32 and 1794-TB32S Terminal Base Wiring for 1794-IB16D

Wiring Connections for the 1794-IB16 Module(use with 1794-TB32 or 1794-TB32S terminal base units)

Input Input Terminal Sensor Power Terminal

Common Supply(1)

(1) 3-wire devices only. 2-wire devices use input and sensor power terminals; 3-wire devices use input, sensor power and common terminals.

IN 00 A-0 B-17 -V common connected to terminals 36, 38, 40, 42, 44, 46, 48, and 50

+V2 connected to terminals 43, 45, 47, and 49IN 01 A-1 B-18

IN 02 A-2 B-19IN 03 A-3 B-20IN 04 A-4 B-21IN 05 A-5 B-22IN 06 A-6 B-23IN 07 A-7 B-24IN 08 A-8 B-25IN 09 A-9 B-26IN 10 A-10 B-27IN 11 A-11 B-28IN 12 A-12 B-29IN 13 A-13 B-30IN 14 A-14 B-31IN 15 A-15 B-32+V2 DC power Power terminals 43, 45, 47 and 49 (power terminals are internally connected

together in the module)COM DC return Common terminals 36, 38, 40, 42, 44, 46, 48 and 50 (common terminals are

internally connected together in the module)

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16

35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 5134

NC

+V2 = Terminals 43, 45, 47 and 49 -

Input Terminals 0…15

Sensor Power Terminals 0…15

+V1 COM1 +V1 COM1 +V1 COM1 +V1 COM1 +V2 COM2 +V2 COM2 +V2 COM2 +V2 COM2 NC

+V1 = Terminals 35, 37, 39 and 41 (not used)

COM1, COM2 = Terminals 36, 38, 40, 42, 44, 46, 48 and 50 -

NC = No connections (terminals 16, 33, 34 and 51)

NC NC

1794-TB32 shown Voltage applied to Inputs 0…15 and Sensor power 0…15

Common for inputs 0…15 and sensor power 0…15

A

B

C

Publication 1794-IN096D-EN-P - June 2018

Page 9: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

FLEX I/O Digital Input and Output Modules with Diagnostics 9

Connecting Wiring for the 1794-OB16D Module use with 1794-TB2, 1794-TB3, or 1794-TB3S Terminal Base

1. Connect individual output wiring to numbered terminals on the 0-15 row (A) as indicated in the Wiring Connections for 1794-OB16D table.

2. Connect the associated common for each output to the corresponding terminal on the 16-33 row (B) as indicated in the Wiring Connections for 1794-OB16D table. The common terminals of row (B) are internally connected together.

3. Connect +V DC power to terminal 34 on the 34-51 row (C). The power terminals of row (C) are internally connected together.

4. Connect DC common (COM) to terminal 16 on the 16-33 row (B).

5. If daisychaining power to the next terminal base, connect a jumper from terminal 51 (+V DC) on this base unit to terminal 34 on the next base unit.

6. If continuing DC common to the next base unit, connect a jumper from terminal 33 (common) on this base unit to terminal 16 on the next base unit.

1794-TB32 and 1794-TB32S Terminal Base Wiring for 1794-OB16D

ATTENTION: Do not remove or replace a Terminal Base unit while power is applied. Interruption of the backplane can result in unintentional operation or machine motion.

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16

35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 5134

Outputs

Commons

1794-TB3 shown-V (Supply common) = Terminals B-16…B-33+V (Supply +voltage in) = Terminals C-34…C-51

-V

VoltageIn +V

VoltageOut +V

Voltage

A

B

C

Use B-33 and C-51 for daisychaining to next terminal base unit

Common-V

Common

Terminals 35…50 not available on 1794-TB2

Publication 1794-IN096D-EN-P - June 2018

Page 10: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

10 FLEX I/O Digital Input and Output Modules with Diagnostics

Wiring Connections for the 1794-OB16D Output Moduleuse with 1794-TB2, 1794-TB3, or 1794-TB3S terminal base

Output Output Terminal Common TerminalOutput 00 A-0 B-17Output 01 A-1 B-18Output 02 A-2 B-19Output 03 A-3 B-20Output 04 A-4 B-21Output 05 A-5 B-22Output 06 A-6 B-23Output 07 A-7 B-24Output 08 A-8 B-25Output 09 A-9 B-26Output 10 A-10 B-27Output 11 A-11 B-28Output 12 A-12 B-29Output 13 A-13 B-30Output 14 A-14 B-31Output 15 A-15 B-32-V DC C-34 and C-51 (1794-TB2). Power Terminals are internally connected in the terminal

base unit.C-34...C-51 (1794-TB3, 1794-TB3S). Power terminals are internally connected in the terminal base unit.

Common B-16...B-33. Common terminals are internally connected in the terminal base unit.

Publication 1794-IN096D-EN-P - June 2018

Page 11: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

FLEX I/O Digital Input and Output Modules with Diagnostics 11

DiagnosticsSee configuration information below for location of diagnostic bits.

Note: Each unused sensor port requires a dummy resistor to mask the channel diagnostic function. Diagnostic Functions for the 1794-IB16D

Ext. Power

Wiring Input Status

Channel LED Status

Open Wire Error Bit

Short Error Bit

Rev. Error Bit

Module Error Bit/LED

OFF Open Off Off 0 0 0 0/OFFOn Off 0 0 0 0/OFF

Short Off Off 0 0 0 0/OFFOn Off 0 0 0 0/OFF

Normal Off Off 0 0 0 0/OFFOn Off 0 0 0 0/OFF

ON Open Off RED 1 0 0 1/REDOn RED/YEL 1 0 0 1/RED

Short Off RED 0 1 0 1/REDOn RED/YEL 0 1 0 1/RED

Normal Off Off 0 0 0 0/OFFOn YEL 0 0 0 0/OFF

REV Open Off Off 0 0 1 1/REDOn Off 0 0 1 1/RED

Short Off Off 0 0 1 1/REDOn Off 0 0 1 1/RED

Normal Off Off 0 0 1 1/REDOn Off 0 0 1 1/RED

The module monitors each sensor-power port for current and voltage. It turns on the channel red LED and sets (1) the error bit when 1) the module detects a short circuit (no voltage at the sensor-port), and 2) the module detects an open wire ( no current at the sensor-port).

Publication 1794-IN096D-EN-P - June 2018

Page 12: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

12 FLEX I/O Digital Input and Output Modules with Diagnostics

Diagnostic Functions for the 1794-OB16D

Ext. Power

Wiring Input Status

Channel LED Status

Open Wire Error Bit

Short Error Bit

Rev. Error Bit

Module Error Bit/LED

OFF Open Off Off 0 0 0 0/OFFOn Off 0 0 0 0/OFF

Short Off Off 0 0 0 0/OFFOn Off 0 0 0 0/OFF

Normal Off Off 0 0 0 0/OFFOn Off 0 0 0 0/OFF

ON Open Off RED 1 0 0 1/REDOn YEL 0 0 0 0/OFF

Short Off Off 0 0 0 0/OFFOn RED 0 1 0 1/RED

Normal Off Off 0 0 0 0/OFFOn YEL 0 0 0 0/OFF

REV Open Off Off 0 0 1 1/REDOn Off 0 0 1 1/RED

Short Off Off 0 0 1 1/REDOn Off 0 0 1 1/RED

Normal Off Off 0 0 1 1/REDOn Off 0 0 1 1/RED

The module monitors each output channel. It turns on the channel red LED and sets (1) the error bit when 1) the module detects a short circuit (the output signal is active at a channel and the corresponding output voltage is low), and 2) the module detects an open wire (the output signal is inactive at a channel and the corresponding output voltage is high).

Publication 1794-IN096D-EN-P - June 2018

Page 13: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

FLEX I/O Digital Input and Output Modules with Diagnostics 13

Sensor Diagram for the 1794-IB16D Module

Sensor Diagram for the 1794-OB16D Module

3-Wire Sensor

ExternalPowerSupply

1794-IB16D

3-Wire Sensor

2-Wire Sensor

ExternalPowerSupply

1794-IB16D

2-Wire Sensor

3-Wire Sensor

ExternalPowerSupply

1794-IB16D

DummyResistor

ExternalPowerSupply

1794-IB16D

ShuntResistor

ShuntResistor

Sensor-power lines -Detect open wireDetect short circuit

Sensor-power lines -Detect open wire

3-Wire Sensor

ExternalPowerSupply

1794-IB16D

3-Wire Sensor

2-Wire Sensor

ExternalPowerSupply

1794-IB16D

2-Wire Sensor

3-Wire Sensor

ExternalPowerSupply

1794-IB16D

DummyResistor

ExternalPowerSupply

1794-IB16D

ShuntResistor

ShuntResistor

Sensor-power lines -Detect open wireDetect short circuit

Sensor-power lines -Detect open wire

Unused input port -Dummy resistor needed orFault LED remains lighted.

20kΩ, ≥1/8W

20kΩ, ≥1/8W

+_+

_

+_

+_

20kΩ, ≥1/8W

Load

ExternalPowerSupply

1794-OB16D

DummyResistor

Unused output port -Dummy resistor needed orFault LED remains lighted. 10kΩ, ≥1/8W

+_

Publication 1794-IN096D-EN-P - June 2018

Page 14: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

14 FLEX I/O Digital Input and Output Modules with Diagnostics

Configuration

Configuring Your 1794-IB16D Input ModuleConfigure your input module by setting bits in the configuration word (word 3). This module is compatible with the Remote I/O network with 1794-ASB series E or later, DeviceNet network, and the ControlNet network. Note: You must use the Module Connection when used in a ControlNet system

Image Table Memory Map for the 1794-IB16D Module

Dec 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Oct 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0

Read 1 I15 I14 I13 I12 I11 I10 I9 I8 I7 I6 I5 I4 I3 I2 I1 I0

Read 2 Read Diagnostic Status

Write 3 Not Used Input Filter FT 0...15

Not Used

Where

Diagnostic Status

I = Input status FT = Filter Time

Bit 00 = Module error; Bit 01 = External power reverse polarity error; Bit 02 = Sensor power short error; Bit 03 = Sensor power open wire error

At the end of its life, this equipment should be collected separately from any unsorted municipal waste.

Publication 1794-IN096D-EN-P - June 2018

Page 15: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

FLEX I/O Digital Input and Output Modules with Diagnostics 15

Setting the Input Filter Time

To set the input filter time, set the associated bits in the output image (complementary word) for the module.

Configuring Your 1794-OB16D Output ModuleConfigure your output module by setting bits in the configuration word (word 3). This module is compatibility with the Remote I/O network, with 1794-ASB series D or later,

Input Filter Time

Bits Description Filter Time

10 09 08 Filter Time for inputs 0...15 Off to On / On to Off

0 0 0 Filter Time 0 (Default) 0.25 ms

0 0 1 Filter Time 1 0.5 ms

0 1 0 Filter Time 2 1 ms

0 1 1 Filter Time 3 2 ms

1 0 1 Filter Time 4 4 ms

1 0 1 Filter Time 5 8 ms

1 1 0 Filter Time 6 16 ms

1 1 1 Filter Time 7 32 ms

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1794-IB16DFT = 0-15

FLL

I:000

00

Fill FileSourceDestinationLength

#O:0101

Write FT to complementof input module.

Write filter time on system startup.

O:010

Dec.

12 11 10 9 8 7 6 5

1= 5 Octal or 5 Decimal

0 11794-IB16D

Publication 1794-IN096D-EN-P - June 2018

Page 16: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

16 FLEX I/O Digital Input and Output Modules with Diagnostics

DeviceNet network, and the ControlNet network. Note: You can use the Module Connection or Rack Connection when used in a ControlNet system.

Specifications

Image Table Memory Map for the 1794-OB16D Module

Dec 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Oct 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0

Read 1 Not used Read Diagnostic Status

Write 2 O15 O14 O13 O12 O11 O10 O9 O8 O7 O6 O5 O4 O3 O2 O1 O0

Where

Diagnostic Status

O = Output

Bit 00 = Module error; Bit 01 = External power reverse polarity error; Bit 02 = Output short error; Bit 03 = Output open wire error

Specifications – 16 Input Module w/ Diagnostics, 1794-IB16DMeets IEC 3 24V DC input specifications

Attribute Value

Number of inputs 16, current, sinking

Recommended terminal base unit 1794-TB32, 1794-TB32S, 1794-TB62DS, 1794-TB62EXD4X15

On-state voltage, min 10V DC

On-state voltage, nom 24V DC

On-state voltage, max 31.2V DC

On-state current, min 2.0 mA

On-state current, max 1.5 mA

Off-state voltage, max 5.0V DC

Off-state current, max 1.5 mA

Nominal input impedance 3.1 kΩ

Isolation voltage 50V (continuous), Basic Insulation Type Type tested @ 2121V DC for 2 s, between field side and system No isolation between individual channels

Input filter time(1) Off to On On to Off

Refer to Setting the Input Filter Time table.

Publication 1794-IN096D-EN-P - June 2018

Page 17: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

FLEX I/O Digital Input and Output Modules with Diagnostics 17

Flexbus current 30 mA @ 5V DC

Power dissipation, max 8.5 W @ 31.2V DC

Thermal dissipation, max 29 BTU/hr @ 31.2V DC

Sensor power, voltage drop, max 2.2V DC

Sensor power, current, max 50 mA

Sensor power line, short detect circuit, min

1.0 A (in 10 s)

Sensor power line, open wire detect, max

50 μA

Detect reverse polarity voltage Minimum 10V: Module must detect if the reverse polarity external power supply voltage is greater than the value.

(1) Input off-to-on filter time is the time from a valid input signal to recognition by the module. Input on-to-off filter time is time from the input signal dropping below the valid level to recognition by the module.

Specifications – 16 Output Module w/ Diagnostics, 1794-OB16D

Attribute Value

Number of outputs 16, current, sourcing

Recommended terminal base unit 1794-TB2, 1794-TB3, 1794-TB3S

Output voltage, min 10V DC

Output voltage, nom 24V DC

Output voltage, max 31.2V DC

Output current rating 8.0 A (16 outputs @ 0.5 A)

On-state current, min 1.0 mA per channel

On-state current, max 500 mA per channel

Surge current 2 A for 50 ms each, repeatable every 2 seconds

Off-state leakage, max 0.5 mA

Isolation voltage 50V (continuous), Basic Insulation Type Type tested at 850V DC for 60 s, between field side and system No isolation between individual channels

Output signal delay(1) Off to On On to Off

0.5 ms 0.5 ms

Specifications – 16 Input Module w/ Diagnostics, 1794-IB16DMeets IEC 3 24V DC input specifications

Attribute Value

Publication 1794-IN096D-EN-P - June 2018

Page 18: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

18 FLEX I/O Digital Input and Output Modules with Diagnostics

FlexBus current 60 mA @ 5V DC

Power dissipation, max 4.8 W @ 31.2V DC

Thermal dissipation, max 16.4 BTU/hr @ 31.2V DC

Short circuit protect and detection Thermal shutdown (auto reset) Detection condition: when external power active, output signal active, and output port voltage less than 2V.

Open wire detect off-state leakage current

0.1 mA – When external power active and output signal inactive.

Detect reverse polarity voltage Minimum 10V: Module must detect if the reverse polarity external power supply voltage is greater than the value.

(1) Delay time is the time from the receipt of an output on or off command to the output actually turning on or off.

General Specifications

Attribute Value

Terminal base screw torque Determined by installed terminal base

Dimensions, approx. (H x W x D) 45.7 x 94 x 53.3 mm (1.8 x 3.7 x 2.1 in.) – 1794-IB16D 94 x 94 x 91 mm (3.7 x 3.7 x 3.6 in.) – 1794-OB16D

Weight, approx. 90 g (3.17 oz.) – 1794-IB16D95 g (3.35 oz.) – 1794-OB16D

Indicators (field side) 16 yellow ON/OFF status indicators 16 red diagnostic status indicators 1 red module fault indicator

External DC power supply voltage, nom 24V DC

External DC power voltage range 10...31.2V DC (includes 5% AC ripple)

North American temp code T3C

Keyswitch position 2

Enclosure type rating None (open-style)

Wire size Determined by installed terminal base

Wiring category(1) 2 - on signal ports

(1) Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Specifications – 16 Output Module w/ Diagnostics, 1794-OB16D

Attribute Value

Publication 1794-IN096D-EN-P - June 2018

Page 19: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

FLEX I/O Digital Input and Output Modules with Diagnostics 19

Environmental Specifications

Attribute Value

Operating temperature IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock):0 °C < Ta < +55 °C (+32 °F < Ta < +131 °F)

Temperature, surrounding air, max.

55 °C (131 °F)

Storage temperature IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):-40…85 °C (-40…185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):5…95% non-condensing

Vibration IEC60068-2-6 (Test Fc, Operating):5 g @ 10...500 Hz

Shock, operating IEC60068-2-27 (Test Ea, Unpackaged shock):30 g

Shock, nonoperating IEC60068-2-27 (Test Ea, Unpackaged shock):50 g

Emissions CISPR 11:Group 1, Class A (with appropriate enclosure)

ESD immunity IEC 61000-4-2:6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3:10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz1V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz

EFT/B immunity IEC 61000-4-4:±2 kV @ 5 kHz on power ports ±2 kV @ 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5:±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports

Conducted RF immunity IEC 61000-4-6:10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Publication 1794-IN096D-EN-P - June 2018

Page 20: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

20 FLEX I/O Digital Input and Output Modules with Diagnostics

Certifications

Certifications (when product is marked)(1)

Value

c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E334470.

CE European Union 2014/30/EU EMC Directive, compliant with: EN 61131-2; Programmable Controllers (Clause 11) EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

European Union 2011/65/EU RoHS, compliant with: EN 50581; Technical documentation

KC Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

EAC Russian Customs Union TR CU 020/2011 EMC Technical Regulation

RCM Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

(1) See the Product Certification link at http://www.rockwellautomation.com/global/certification/overview.page for Declarations of Conformity, Certificates, and other certification details.

Publication 1794-IN096D-EN-P - June 2018

Page 21: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

FLEX I/O Digital Input and Output Modules with Diagnostics 21

Derating Curves

1794-IB16D Input Voltage

Sensor Power

WARNING: When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes.

0

5

10

15

25

20

30

10 20 30 40 50 55

31 .2

26 .4

Ambient Temperature (˚C)

InputVoltage(V)

10 20 30 40 50 55 0

10

20

30

40

50

45

Sensor Power

(m A )

Current

Ambient Temperature (˚C)

Publication 1794-IN096D-EN-P - June 2018

Page 22: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

22 FLEX I/O Digital Input and Output Modules with Diagnostics

Notes:

Publication 1794-IN096D-EN-P - June 2018

Page 23: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

FLEX I/O Digital Input and Output Modules with Diagnostics 23

Notes:

Publication 1794-IN096D-EN-P - June 2018

Page 24: 1794-IN096D-EN-P FLEX I/O Digital Input and Output Modules with ... · l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes

Rockwell Automation SupportRockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.

For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/.

Installation AssistanceIf you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.

New Product Satisfaction ReturnRockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.

Documentation FeedbackYour comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.

United States or Canada 1.440.646.3434

Outside United States or Canada

Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell Automation representative.

United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.

Outside United States Please contact your local Rockwell Automation representative for the return procedure.

Publication 1794-IN096D-EN-P - June 2018

Allen-Bradley, Rockwell Automation, FLEX I/O, Rockwell Software, and TechConnect are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

Supersedes Publication 1794-IN096C-EN-P - August 2015 Copyright © 2018 Rockwell Automation, Inc. All rights reserved.