How can I...

Increase the Availability of a

Collaborative Control System

System Technical Note

Page 2: Document1

2

Page 3: Document1

3

Table of Contents

Introduction to High Availability .............................................5

High Availability Theoretical Basics.......................................9

High Availability with Collaborative Control System..........31

Conclusion..............................................................................73

Appendix .................................................................................76

Reliability & Availability Calculation Examples...................83

Page 4: Document1

Introduction to High Availability

4

Page 5: Document1

Introduction to High Availability

5

Introduction to High Availability

Purpose

The intent of this System Technical Note (STN) is to describe the capabilities of the

different Schneider Electric solutions that answer most critical applications

requirements, and consequently increase the availability of a Collaborative Control

System. It provides a description of a common, readily understandable reference

point for end users, system integrators, OEMs, sales people, business support and

other parties.

Introduction

Increasingly, process applications require a high availability automation system.

Before deciding to install a high availability automation system in your installation, you

need to consider the following key questions:

• What is the security level needed? This regards security concerning of both

persons and hardware. For instance, the complete start/stop sequences that

manage the kiln in a cement plant includes a key condition: the most powerful

equipment must be the last to start and stop.

• What is the criticality of the process? This point concerns all the processes that

involve a reaction (mechanical, chemical, etc.). Consider the example of the kiln

again. To avoid its destruction, the complete stop sequence needs a slow cooling

of the constituent material. Another typical example is the biological treatment in

a wastewater plant, which cannot be stopped every day.

• What is the environmental criticality?. Consider the example of an automation

system in a tunnel. If a fire starts on a side, thereof the PLCs (the default and the

redundant one) will be installed on each side of the tunnel. More, does the

system will face to harsh environment; in terms of vibration, temperature, shock…?

• Which other particular circumstances does the system have to address? This last

topic includes additional questions, for example: does the system really need

redundancy if the electrical network becomes inoperative in the concerned layer

of the installation, what is the criticality of the data in the event of a loss of

communication, etc.

Page 6: Document1

Introduction to High Availability

6

Availability is a term that increasingly used to qualify a process asset or system. In

addition, Reliability and Maintainability are terms now often used for analyses

considered of major usefulness in design improvement, and in production diagnostic

issues. Accordingly, the design of automation system architectures must consider

these types of questions.

The Collaborative Control System provided by Schneider Electric offers different

levels of redundancy, allowing you to design an effective high availability system.

Document Overview

This document contains the following chapters:

• The High Availability Theoretical Basics chapter describes the fundamentals in

High Availability. In one hand it presents theory and basics, in another hand

explains a method to conceptualize series/parallel architectures. Calculation

examples illustrate this approach.

• The Collaborative Control System Availability chapter provides different solutions

in High Availability, especially for Collaborative Control System; from the

information management to the I/O modules level.

• The final Conclusion chapter summarizes customer benefits provided by

Schneider Electric High Availability solutions, as well as additional information

and references.

Page 7: Document1

Introduction to High Availability

7

The following drawing represents various levels of an automation system architecture:

As shown in the following chapters, redundancy is a convenient means of elevating

global system reliability, and so far its availability. The Collaborative Control System

Hi-Availability, that is redundancy, can be addressed at the different levels of the

architecture:

� Single or redundant I/O Modules (depending on sensors/actuators redundancy).

� Depending on the I/O handling philosophy (for example conventional Remote I/O

stations, or I/Os Islands distributed on Ethernet) different scenarios can be

applied: dual communication medium I/O Bus or Self healing Ring, single or dual.

� Programmable Controller CPU redundancy (HotStandby PAC Station).

� Communication network and ports redundancy.

� SCADA System dedicated approaches with multiple operator station location

scenarios and resource redundancy capabilities.

Page 8: Document1

High Availability Theoretical Basics

8

Guide Scope

The realization of an automation project includes five main phases: Selection, Design,

Configuration, Implementation and Operation. To help you develop a whole project

based on these previous phases, Schneider Electric created the System Technical

book concept: Guide (STG) and Notes (STN).

A System Technical Guide provides you technical guidelines and recommendations

to implement technologies regarding to your needs and requirements. This guide

covers the entire project life cycle scope, from the selection to the operation phase

providing design methodology and even source code examples of all components

part of a sub-system.

A System Technical Notes gives a more theoretical approach by focusing specially on

a system technology. This book describes what is our complete solution offer

regarding a system and therefore supports you in the selection phase of a project.

STG and STN are obviously linked and complementary. To sum up, you will figure out

the technologies fundamentals in a STN, and their corresponding tested and

validated applications in one or several STGs.

Automation Project

Life Cycle

STN Scope STG Scope

Page 9: Document1

High Availability Theoretical Basics

9

High Availability Theoretical Basics

This section describes basic high availability terms, concepts and formulas, and

includes examples for typical applications.

Fault Tolerant System

A Fault Tolerant System usually refers to a system that can operate even though a

hardware component becomes inoperative. The Redundancy principle is often used

to implement a Fault Tolerant Systems, because an alternate component takes over

the task transparently.

Lifetime and Failure Rate

Considering a given system or device, its Lifetime corresponds to the number of

hours it can function under normal operating conditions. This number is the result of

the individual life expectancy of the components used in its assembly.

Lifetime is generally seen as a sequence of three subsequent phases: the “early life”

(or “infant mortality”), the "useful life,” and the "wear out period.”

Failure Rate (λ) is defined as the average (mean) rate probability at which a system

will become inoperative.

When considering events occurring on a series of systems, for example a group of

light bulbs, the units to be used should normally be “failures-per-unit-of- system-time.”

Examples include failures per machine-hour or failures per system-year. Because the

scope of this document is limited to single repairable entities, we will usually discuss

failures-per-unit-of-time.

Failure Rate Example: For a human being, Failure Rate (λ) measures the

probability of death occurring in the next hour. Stating λ (20 years) = 10-6 per

hour would mean that the probability for someone age 20 to die in the next

hour is 10-6.

Page 10: Document1

High Availability Theoretical Basics

10

Bathtub Curve

The following figure shows the Bathtub Curve, which represents the Failure Rate (λ)

according to the Lifetime (t):

Consider the

relation between

Failure Rate and

Lifetime for a

device consisting of

assembled

electronic parts.

This relationship is

represented by the

"bathtub curve". As

shown in the previous diagram. In "early life," this system, exhibits a high Failure

Rate, which gradually reduces until it approaches a constant value, maintained during

its "useful life.” The system finally enters the “wear-out” stage of its life, where Failure

Rate increases exponentially.

Note: Useful Life normally starts at the beginning of system use and ends at the

beginning of its wear-out phase. Assuming that "early life" corresponds to the ”burn-

in” period indicated by the manufacturer, we generally consider that Useful Life starts

with the beginning of system use by the end user.

RAMS (Reliability Availability Maintainability Safety)

The following text, from the MIL-HDBK-338B standard, defines the RAM criteria and

their probability aspect:

"For the engineering specialties of reliability, availability and maintainability (RAM),

the theories are stated in the mathematics of probability and statistics. The underlying

reason for the use of these concepts is the inherent uncertainty in predicting a failure.

Even given a failure model based on physical or chemical reactions, the results will

not be the time a part will fail, but rather the time a given percentage of the parts will

fail or the probability that a given part will fail in a specified time."

Along with Reliability, Availability and Maintainability, Safety is the fourth metric of a

meta-domain that specialists have named RAMS (also sometimes referred to as

dependability).

The Bathtub Curve

Page 11: Document1

High Availability Theoretical Basics

11

Metrics

RAMS metrics relate to time allocation and depend on the operational state of a given

system.

The following curve defines the state linked to each term:

• MUT: Mean Up Time

MUT qualifies the average duration of the system being in operational state.

• MDT: Mean Down Time

MDT qualifies the average duration of the system not being in operational state. It

comprises the different portions of time required to subsequently detect the error, fix it,

and restore the system to its operational state.

• MTBF: Mean Time between Failure

MTBF is defined by the MIL-HDBK-338 standard as follows: "A basic measure of

reliability for repairable items. The mean number of life units during which all parts of

the item perform within their specified limits, during a particular measurement interval

under stated conditions."

Thus for repairable systems, MTBF is a metric commonly used to appraise Reliability,

and corresponds to the average time interval (normally specified in hours) between

two consecutive occurrences of inoperative states.

Put simply: MTBF = MUT + MDT

MTBF can be calculated (provisional reliability) based on data books such as UTE

C80-810 (RDF2000), MIL HDBK-217F, FIDES, RDF 93, and BELLCORE. Other

inputs include field feedback, laboratory testing, or demonstrated MTBF (Operational

Reliability), or a combination of these. Remember that MTBF only applies for

repairable systems

Page 12: Document1

High Availability Theoretical Basics

12

• MTTF (or MTTFF): Mean Time to First Failure

MTTF is the mean time before the occurrence of the first failure.

Considering a repairable system with an exponential distribution Reliability and a

constant Failure Rate (λ), MTTF = 1 / λ.

Mean Down Time is usually very low compared to Mean Up Time. This equivalence

is extended to MTBF, and assimilated to MTTF, resulting in the following relationship:

MTBF = 1 / λ.

This relationship is widely used in additional calculations.

• FIT: Failures in Time

Typically used as the Failure Rate measurement for non- repairable electronic

components, FIT is the number of failures in one billion hours.

FIT= 109 / MTBF or MTBF= 109 / FIT

Example:

Given the MTBF of a communication adapter, 618,191 hours, what is the

probability for that module to operate without failure for 5 years?

Calculate the module Reliability over a 5-year time period:

R(t) = e -λt = e -t / MTBF

a) Divide by 5 years, that is 8,760 * 5 = 43,800 hours, by the given MTBF:

43,800 / 618,191 = 0.07085

b) Then raise e to the power of the negative value of that number:

e -.07085 = .9316

Thus there is a 93.16% probability that the communication module will not fail

on a 5-year period.

MTTF (and MTBF by extension) is often confused with Useful Life, even though

these two concepts are not related in any way. For example, a battery may have

a Useful Life of 4 hours and have a MTTF of 100,000 hours. These figures

indicate that for a population of 100,000 batteries, there will be approximately

one battery failure every hour (defective batteries being replaced).

Page 13: Document1

High Availability Theoretical Basics

13

Safety

Definition

Safety refers to the protection of people, assets and the environment. For example, if

an installation has a tank with an internal pressure that exceeds a given threshold,

there is a high chance of explosion, and eventual destruction of the installation (with

injury or death of people and damage to the environment). In this example, the Safety

System put in place is to open a valve to the atmosphere, to prevent the pressure

threshold from being crossed.

Maintainability

Definition

Maintainability refers to the ability of a system to be maintained in an operational

state. This once again relates to probability. Maintainability corresponds to the

probability for an inoperative system to be repaired in a given time interval.

If design considerations may at a certain level impact the maintainability of a system,

then the maintenance organization will also have a major impact on its maintainability.

Having the right number of people trained to observe and react with the proper

methods, tools, and spare parts are considerations that usually depend more on the

customer organization than on the automation system architecture.

Mathematics Basics

Equipment shall be maintainable on-site by trained personnel according to the

maintenance strategy. A common metric named Maintainability, M(t), gives the

probability that a required given active maintenance operation can be accomplished

in a given time interval.

The relationship between Maintainability and repair is similar to the relationship

between reliability and failure, with the repair rate µ(t) defined in a way analogous to

the Failure Rate. When this repair rate is considered as a constant, it implies an

exponential distribution for Maintainability: M(t) = e -µt.

The maintainability of equipment is reflected in MTTR, which is usually considered as

the sum of the individual times required for administrative, transport, and repair times.

Page 14: Document1

High Availability Theoretical Basics

14

Availability

Definition

The term High Availability is often used when discussing Fault Tolerant Systems. For

example, your telephone line is supposed to offer you a high level of availability: the

service you are paying for has to be effectively accessible and dependable. Your line

availability is compared related to the continuity of the service which you are

provided. As an example, assume you are living in a remote area with occasional

violent storms. Because of your loacation and the damage these storms can cause,

long delays are required to fix your line once it is out of order. In these conditions, if

on average your line appears to be usable only 50% of the time, you have poor

availability. By contrast, if on average each of your attempts is 100% satisfied, then

your line has high availability.

This example demonstrates that Availability is the key metric to measuring a system’s

tolerance level, that it is typically expressed in percent (for example 99.999%), and

that it belongs to the domain of probability.

Mathematics Basics

The Instantaneous Availability of a device is the probability that this device will be in

the functional state for which it was designed, under given conditions and at a given

time (t), with the assumption that the required external conditions are met.

Besides Instantaneous Availability, different variants have been specified, each

corresponding to a specific definition, including Asymptotic Availability, Intrinsic

Availability and Operational Availability.

Page 15: Document1

High Availability Theoretical Basics

15

Asymptotic (or Steady State) Availability: ∞A

Asymptotic Availability is the limit of the instantaneous availability function as time

approaches infinity,

MTBF

MUT

MDTMUT

MUT

MDTMUT

MDT1A =

+=

+−=

where Downtime includes all repair time (corrective and preventive maintenance

time), administrative time and logistic time.

The following curve shows an example of asymptotic behavior:

Intrinsic (or Inherent) Availability: Ai

Intrinsic Availability does not include administrative time and logistic time, and usually

does not include preventive maintenance time. This is primarily a function of the basic

equipment/system design.

MTTR MTBF

MTBF

iA

+=

We will consider Intrinsic Availability in our Availability calculations.

Operational Availability

Operational Availability corresponds to the probability that an item will operate

satisfactorily at a given point in time when used in an actual or realistic operating and

support environment.

CycleOperating

Uptime

0A⋅

=

Operational Availability includes logistics time, ready time, and waiting or

administrative downtime, and both preventive and corrective maintenance downtime.

Page 16: Document1

High Availability Theoretical Basics

16

This is the availability that the customer actually experiences. It is essentially the a

posteriori availability based on actual events that happened to the system.

Classification

A quite common way used to classify a system in terms of Availability consists of

listing the number of 9s of its availability figure.

The following table defines types of availability:

Class Type of

Availability

Availability

(%)

Downtime

per Year

Number of

Nines

1 Unmanaged 90 36.5 days 1-nine

2 Managed 99 3.65 days 2-nines

3 Well Managed 99.9 8.76 hours 3-nines

4 Tolerant 99.99 52.6 minutes 4-nines

5 High Availability 99.999 5.26 minutes 4-nines

6 Very High 99.9999 30.00 seconds 6-nines

7 Ultra High 99.99999 3 seconds 7-nines

For example, a system that has a five-nine availability rating means that the system is

99.999 % available; with a system downtime of approximately 5.26 minutes per year.

Reliability

Definition

A fundamental associated metric is Reliability. Return to the example of your

telephone line. If the wired network is a very old one, having suffered from many

years of lack of maintenance, it may frequently be out of order. Even if the current

maintenance personnel are doing their best to repair it in a minimum time, it can be

said to have poor reliability if, for example, it has experienced ten losses of

communication during the last year. Notice that Reliability necessarily refers to a

given time interval, typically one year. Therefore, Reliability will account for the

absence of shutdown of a considered system in operation, on a given time interval.

As with Availability, we consider Reliability in terms of perspective (a prediction), and

within the domain of probability.

Page 17: Document1

High Availability Theoretical Basics

17

Mathematics Basics

In many situations a detected disruption fortunately does not mean the end of a

device’s life. This is usually the case for the automation and control systems being

discussed, which are repairable entities. As a result, the ability to predict the number

of shutdowns, due to a detected disruption over a specified period of time, is useful to

estimate the budget required for the replacement of inoperative parts.

In addition, knowing this figure can help you maintain an adequate inventory of spare

parts. Put simply, the question "Will a device work for a particular period" can only be

answered as a probability; hence the concept of Reliability.

According to the MIL-STD-721C standard, the definition of reliability R(t) of a given

system is the probability of that system to perform its intended function under stated

conditions for a stated period of time. As an example, a system featured by 0.9999

reliability over a year has a 99.99% probability of functioning properly throughout an

entire year.

Note: The reliability is systematically indicated for a given period of time, for example

one year.

Referring to the system model we considered with the "bathtub curve,” one

characteristic is its constant Failure Rate, during the useful life. In that portion of its

lifetime, the Reliability of the considered system will follow an exponential law, given

by the following formula: R(t) = e -λt, where λ stands for the Failure Rate.

The following figure illustrates the exponential law, R(t) = e -λt, where λ stands for the

Failure Rate:

As shown in the diagram,

Reliability starts with a value of

1 at time zero, which

represents the moment the

system is put into operation.

Reliability then falls graduallly

down to zero, following the

exponential law. Therefore,

Reliability is about 37% at

t=1/λ. As an example, assume the given system experiences an average number of

0.5 inoperative states per a 1-year time unit. The exponential law indicates that such

a system would have about a 37% chance of remaining in operation, reaching 1 / 0.5

= 2 years of service.

Page 18: Document1

High Availability Theoretical Basics

18

Note: Considering the flat portion of the bathtub curve model, where the Failure Rate

is constant over time and remains the same for a unit regardless of this unit’s age, the

system is said to be "memoryless.”

Reliability versus Availability

Reliability one of the factors influencing Availability, but must not be confused with

Availabilty: 99.99% Reliability does not mean 99.99% Availability. Reliability

measures the ability of a system to function without interruptions, while Availability

measures the ability of this system to provide a specified application service level.

Higher reliability reduces the frequency of inoperative states, while increasing overall

Availability.

There is a difference between Hardware MTBF and System MTBF. The mean time

between hardware component failures occurring on an I/O Module, for example, is

referred to as the Hardware MTBF. Mean time between failures occurring on a

system considered as a whole, a PLC configuration for example, is referred to as the

System MTBF.

As will be demonstrated, hardware component redundancy will provide an increase in

the overall system MTBF, even though the individual component’s MTBF remains the

same.

Although Availability is a function of Reliability, it is possible for a system with

poor Reliability to achieve high Availability. For example, consider that a system

averages 4 failures a year, and for each failure, this system can be restored with

an average outage time of 1 minute. Over the specified period of time, MTBF is

131,400 minutes (4 minutes of downtime out of 525,600 minutes per year).

In that one year period:

� Reliability R(t) = e -λt = e - 4 = 1.83%, very poor Reliability

� (Inherent) Availability 99,99924%1 400131

400131

MTTR MTBF

MTBF

iA =

+

⋅=

+= ,

very good Availability

Page 19: Document1

High Availability Theoretical Basics

19

Reliability Block Diagrams (RBD)

Based on basic probability computation rules, RBD are simple, convenient tools to

represent a system and its components, to determine the Reliability of the system.

Series-Parallel Systems

The target system, for example a PLC rack, must first be interpreted in terms of series

and parallel arrangements of elementary parts.

The following figure shows a representation of a serial architecture:

As an example, assume that one of the 5

modules (1 power supply and 4 other

modules) that populate the PLC rack

becomes inoperative. As a consequence,

the entire rack is affected, as it is no longer

100% capable of performing its assigned

mission, regardless of which module is

inoperative. Thus each of the 5 modules

are considered as a participant member of a 5-part series.

Note: When considering Reliability, two components are described as in series if both

are necessary to perform a given function.

The following figure shows a representation of a parallel architecture:

As an example, assume that the PLC rack

now contains redundant Power Supply

modules, in addition to the 4 other

modules. If one Power Supply becomes

inoperative, then the other supplies power

for the entire rack. These 2 power supplies

would be considered as a parallel sub-

system, in turn coupled in series with the

sequence of the 4 other modules.

Note: Two components are in parallel, from a reliability standpoint, when the system

works if at least one of the two components works. In this example, Power Supply 1

and 2 are said to be in active redundancy. The redundancy would be described as

passive if one of the parallel components is turned on only if the other is inoperative

only, for example in the case of auxiliary power generators.

Page 20: Document1

High Availability Theoretical Basics

20

Serial RBD

Reliability

Serial system Reliability is equal to the product of the individual elements’ reliabilities.

(t)n

1i iR(t)nR...(t)3R(t)2R(t)1R(t)SR ∏

==∗∗∗∗=

where: Rs(t) = System Reliability

Ri(t) = Individual Element Reliability

n = Total number of elements on the serial system

Assuming constant individual Failure Rate:

t)n

...321

(

e

tne...

t31e

t2e

t1e(t)

nR...(t)

3R(t)

2R(t)

1R(t)

SR

λλλλλλλλ ++++−=

−∗∗

−∗

−∗

−=∗∗∗∗=

That is ∑

==

n

1iiSλλ : Equivalent Failure Rate for n serial elements is equal to the sum

of the individual Failure Rate of these elements, with tSe(t)SR

λ−=

Example 1:

Consider a system with 10 elements, each of them required for the proper operation

of the system, for example a 10-module rack. To determine RS(t), the Reliability of

that system over a given time interval t, if each of the considered elements shows an

individual Reliability Ri(t) of 0.99:

(t)10

1i iR(t)SR ∏

== = (0.99) x (0.99) x (0.99) . . . (0.99) = (0.99)

10 = 0.9044

Thus the targeted system Reliability is 90.44%

Example 2:

Consider two elements with the following failure rates:

λ1 = 120 x 10-6 h-1 and λ2 = 180 x 10-6 h-1

Element 1

λ1 = 120 x 10-6 h-1

Element 2

λ2 = 180 x 10-6 h-1

Page 21: Document1

High Availability Theoretical Basics

21

The System Reliability, over a 1,000- hour mission, is:

21

n

1i iS λλλλ +=∑=

= = 120 x 10-6

+ 180 x 10-6 = 300 x 10

-6 = 0.3 x 10

-3 h-1

0.74080.3

e310x310x0.3

etSeh) (1000SR =−=

−−=−

Thus the targeted system Reliability is 74.08%

Availability

Serial system Availability is equal to the product of the individual elements’

Availabilities.

∏=

==n

1iiAn.A....3A.2A.1ASA

where: As= system (asymptotic) availability

Ai = Individual element (asymptotic) availability

n = Total number of elements on the serial system

Page 22: Document1

High Availability Theoretical Basics

22

Calculation Example

In this example, we calculate the availability of a PAC Station using shared distributed

I/O Islands. The following illustration shows the final configuration:

This calculation applies the equations given by basic probability analysis. To do this

calculation, a spreadsheet was developed. These are the figures applied in the

spreadsheet:

Failure rate: λ = 1/MTBF

Reliability: R(t) = e -λt

Total serial Systems Failure Rate ∑

==

n

1iiSλλ

Total MTBF serial Systems = 1 / λs

Availability = MTBF/ MTBF+ MTTR

Unavailability = 1 – Availability

Unavailability over years: Unavailability × hours (one year = 8460 hours)

The following table shows the method to perform the calculation:

Step Action

1 Perform the calculation of the Standalone CPU.

2 Perform the calculation of a distributed island.

3 Based on the serial structure, add up the results from Steps 1 and 2.

Note: A common variant of in-rack I/O Module stations are I/O Islands, distributed on

an Ethernet communication network. Schneider Electric offers a versatile family

named Advantys STB, which can be used to define such architectures.

Step 1: Calculation linked to the Standalone CPU Rack.

The following figures represent the Standalone CPU Rack:

Page 23: Document1

High Availability Theoretical Basics

23

The following screenshot is the spreadsheet corresponding to this analysis.

Step 2: Calculation linked to the STB Island.

The following figures represent the Distributed I/O on STB Island:

The following screenshot is the spreadsheet corresponding to this analysis:

Page 24: Document1

High Availability Theoretical Basics

24

Step 3: Calculation of the entire installation. Assume that the communication network

used to link I/O Islands to CPU has no examples of Reliability metrics (these are

explored further in a subsequent chapter).

The following figures represent the final Distributed architecture:

The following screenshot is the spreadsheet corresponding to the entire analysis:

Note: The highlighted values were calculated in the two previous steps

Considering the results of this Serial System (Rack # 1+ Islands # 1 ... #4), Reliability over

one year is approximately 82 % (the probability that this system will encounter one failure

during one year is approximately 18%).

System MTBF itself is approximately 44,000 hours (about 5 years)

Considering the Availability, with a 2-hour Mean Time To Repair (typical of a very good

logistics and maintenance organization), the system would achieve a 4-nines Availability,

an average probability of approximately 24 minutes downtime per year;

Page 25: Document1

High Availability Theoretical Basics

25

Parallel RBD

Reliability

Theory of Probability provides expression of the Reliability of a Parallel System (for

example, a Redundant System), with Qi(t) (unreliability) being the reverse of Ri(t).

(t) Ri - 1 (t) Ri (t) Qi == :

∏=

−−=∏=

−=−=n

1i)t(iR11)t(

n

1iiQ1])t(nQx....x)t(3Qx)t(2Qx)t(1Q[1)t(dReR

with: R Red = Reliability of the Simple Redundancy System

∏=

n

1iiQ = Probability of Failure of the System

Rj = Probability of Non-Failure of an Individual Parallelized Element

Qj = Probability of Failure of an Individual Parallelized Element

n = Total number of Parallelized Elements

Example:

Considering two elements with the following failure rates:

λ1 = 120 x 10-6 h-1 and λ2 = 180 x 10-6 h-1

The System Reliability, over a 1,000-hour mission, is:

Reliability of elements 1 and 2 over the 1,000-hour period:

8869,0ee)h000,1(R36

1 10x10x120t1 ===

−−λ−

8353.0ee)h000,1(R36

2 10x10x180t2 ===

−−λ−

Unreliability of elements 1 and 2 over the 1,000 hour-period:

1130.08869.01)h000,1(R1)h000,1(Q 11 =−=−=1647.08353.01)h000,1(R1)h000,1(Q 22 =−=−=

Element 1

λ1 = 120 x 10-6 h-1

Element 2

λ2 = 180 x 10-6 h-1

Page 26: Document1

High Availability Theoretical Basics

26

Redundant System Reliability, over the 1,000-hour period:

9814.0)1647.0x1130.0(1])h000,1(Q.)h1000t(Q[1)h1000t(R 2112 =−==−==

Thus with Individual Elements’ Reliability of 88.69% and 83.53% respectively, the

targeted Redundant System Reliability is 98.14%

Availability

Parallel system Unavailability is equal to the product of the individual elements’

Unavailabilities. Thus the Parallel system Availability, given the individual parallelized

elements’ Availabilities, is:

)A1(1])A1(.....)A1(.)A1([1An

1i

in21S ∏=

−−=−−−−=

where: As= system (asymptotic) availability

Ai = Individual element (asymptotic) availability

n = Total number of elements on the serial system

Page 27: Document1

High Availability Theoretical Basics

27

Calculation Example

To illustrate a Parallel system, we perform the calculation of the Availability of a

redundant PLC System using shared distributed I/O Islands.

The following illustration shows the final configuration:

The formulas are the same as used in the previous calculation example, except for

the calculation of the reliability for a parallel system, which is as follows:

∏=

−−=∏=

−=−=n

1i)t(iR11)t(

n

1iiQ1])t(nQx....x)t(3Qx)t(2Qx)t(1Q[1)t(dReR

The following table shows the method to perform the calculation:

Step Action

1 Perform the calculation of a standalone CPU

2 Perform the calculation for the redundant structure, here the two CPUs

3 Perform the calculation of a distributed island

4 Concatenate the results from Steps 1,2 and 3

Note: the previous results from the serial analysis, regarding the calculation linked to

the standalone elements, are reused.

Page 28: Document1

High Availability Theoretical Basics

28

Step 1: Calculation linked to the Standalone CPU Rack.

Because the analysis is identical to that for the serial case, the following screenshot

shows the spreadsheet corresponding only to the final results:

Step 2: Calculation of the redundant CPU group.

The following figures show represent the Redundant CPUs:

The following screenshot is the spreadsheet corresponding to this analysis:

Step 3: Calculation linked to the STB Island.

Because the analysis is identical to that for the serial case, the following screenshot

shows the spreadsheet corresponding to the final results only:

Page 29: Document1

High Availability Theoretical Basics

29

Step 4: Calculation of the entire installation.

The following screenshot is the spreadsheet corresponding to the entire analysis:

Note: The only difference between this architecture and the previous one relates to

the CPU Rack: this one is a redundant one (Premium Hot Standby), while the former

one was a standalone one.

Note: Other calculations examples are available in the Calculation Examples chapter.

Note: The previous examples cover the PAC station only. To extend the calculation

to a whole system, the MTBF of the network components and the SCADA systems

(PC, servers) must be taken in account.

Looking at the results of this Parallel System (Premium CPU Rack Redundancy), Reliability

over one year would be approximately 99.9%, compared to 97.4% available with a

Standalone Premium CPU Rack (i.e. the probability for a Premium Rack System to

encounter one failure during one year would have been reduced from 2.6% to 0.1%).

System MTBF itself would increas from 335,000 hours (approximately 38 years) to 503,000

hours (approximately 57 years).

For System Availability, a 2-hour Mean Time To Repair we provide approximately a 9-nines

resulting Availability (almost 100%).

Page 30: Document1

High Availability Theoretical Basics

30

Conclusion

Serial System

The above computations demonstrate that the combined availability of two

components in series is always lower than the availability of its individual components.

The following table gives an example of combined availability in serial system:

Component Availability Downtime

X 99% (2-nines) 3.65 days/year

Y 99.99% (4-nines) 52 minutes/year

X and Y Combined 98.99% 3.69 days/year

This table indicates that even though a very high availability Part Y was used, the

overall availability of the system was reduced by the low availability of Part X. A

common saying indicates that "a chain is as strong as the weakest link", however, in

this instance a chain is actually “weaker than the weakest link.”

Parallel System

The above computations indicate that the combined availability of two components in

parallel is always higher than the availability of its individual components.

The following table gives an example of combined availability in a parallel system:

Component Availability Downtime

X 99% (2-nines) 3.65 days/year

Two X components

operating in parallel

99.99% (4-nines)

52 minutes/year

Three X components

operating in parallel

99.9999% (6-nines) 31 seconds /year !

This indicates that even though a very low availability Part X was used, the overall

availability of the system is much higher. Thus redundancy provides a very powerful

mechanism for making a highly reliable system from low reliability components.

Page 31: Document1

High Availability with Collaborative Control System

31

High Availability with Collaborative Control System

In an automation system, how can you reach the level of availability required to keep

the plant in operation? By what means should you enforce the system architecture,

providing and maintaining access to the information required to monitor and control

the process?

This chapter provides answers to these questions, and reviews the system

architecture from top to bottom, that is, from operator stations and data servers

(Information Management) to Controllers and Devices (Control System Level), via

communication networks (Communication Infrastructure Level).

The following figure illustrates the Collaborative Control System:

This previous system architecture drawing above shows various redundancy

capabilities that can be proposed:

• Dual SCADA Vijeo Citect server

• Dual Ethernet control network managed by ConneXium switches

• Premium Hot Standby with Ethernet device bus

• Quantum Hot Standby with Remote I/O, Profibus and Ethernet.

• Quantum safety controller HotStandby with remote I/O

Ethernet

Ethernet Ethernet

Profibus

Page 32: Document1

High Availability with Collaborative Control System

32

Information Management Level

This section explains how to implement various technological means to address

architecture challenges, with examples using a current client/server paradigm. The

section describes:

• A method to define a redundancy level

• The most appropriate system architecture for the defined level

Redundancy Level

Key Features

The key features a Vijeo Citect SCADA software has to handle relate to:

• Data acquisition

• Events and Alarms (including time stamping)

• Measurements and trends

• Recipes

• Report

• Graphics ( displays and user interfaces)

In addition, any current SCADA package provides access to a treatment/calculation

module (openness module), allowing users to edit program code (IML/CML, Cicode,

Script VB, etc.).

Note: This model is applicable for a single station (PC), including for small

applications. The synthesis between the stakes and the key features will help to

determine the most appropriate redundant solution.

Page 33: Document1

High Availability with Collaborative Control System

33

Stakes

Considering the previously defined key features, stakes when designing a SCADA

system include:

• Is a changeover possible?

• Does a time limit exist?

• What are the critical data?

• Has cost reduction been considered?

Risk analysis

Linked to the previous stakes, the risk analysis is essential to defining the redundancy

level. Consider the events the SCADA system will face, i.e. the risk, in terms of the

following:

• Inoperative hardware

• Inoperative power supply

• Environmental events (natural disaster, fire, etc.)

That can imply loss of data, operator screen, connection with devices and so on.

Level Definition

Finally, the redundancy level is defined as the compilation of the key features, the

stakes, and the risk analysis with the customer expectations related to the data

criticality level. The following table illustrates the flow from the process analysis to the

redundancy level:

Page 34: Document1

High Availability with Collaborative Control System

34

The following table explains the redundancy levels:

Redundancy Level State of the standby system Switchover performance

No redundancy No standby system Not applicable

Cold Standby The Standby system is only powered on

if the default system becomes

inoperative.

Several minutes

Large amount of lost data

Warm Standby The Standby system switches from

normal to backup mode.

Several seconds

Small amount of lost data

Hot Standby The Standby system runs together with

the default system one.

Transparent

No lost data

Architecture Redundancy Solutions Overview

This section examines various redundancy solutions. A Vijeo Citect SCADA system

can be redundant at the following levels:

• Clients, i.e. operator stations

• Data servers

• Control and information network

• Targets, i.e. PAC station, controller, devices

Page 35: Document1

High Availability with Collaborative Control System

35

The Vijeo Citect functional organization corresponds directly

to a Client/Server philosophy. An example of a Client/Server

topology is shown in the diagram to the left: a single Display

Client Operator Station with a single I/O Server, in charge of

device data (PLC) communication.

Vijeo Citect architecture is a combination of several operational entities that handles

A

l

a

r

m

s

,

T

r

e

n

d

s

a

Alarms, Trends and Reports, respectively. In addition, this functional architecture

includes at least one I/O Server. The I/O Server acts as a Client to the peripheral

devices (PAC) and as a Server to Alarms, Trends and Reports (ATR) entities.

As shown in the figure above, ATR and I/O Server(s) act either as a Client or as a

Server, depending on the designated relationship. The default mechanism linking

these Clients and Servers is based on a Publisher / Subscriber relation.

As shown in the following screenshot, because of its client server model, Vijeo Citect

can create a dedicated server, depending on the application requirements: for

example for ATR, or for I/O server:

Page 36: Document1

High Availability with Collaborative Control System

36

.

Clients: Operator Workstations

Vijeo Citect is able to manage the redundancy at the operator station level with

several client workstations. These stations can be located in the control room or

distributed in the plant close to the critical part of the process. A web client interface

can also be used to monitor and control the plant using a standard web browser.

If an operator station becomes inoperative, the plant can still be monitored and

controlled using additional operator screen.

Servers: Resource Duplication Solution

This example assumes a Field Devices Communication Server, providing Services to

several types of Clients, such as Alarm Handling, Graphic Display, etc.

A first example of Redundancy is a complete duplication of the first Server. Basically,

if a system becomes inoperative, for example Server A, Server B would retain the job

and respond to the service requests presented by the Clients.

Page 37: Document1

High Availability with Collaborative Control System

37

Vijeo Citect can define Primary and Standby servers within a project, with each

element of a pair being held by different hardware.

The first level of redundancy duplicates the I/O

server or the ATR server, as shown in the

illustration. In this case, a Standby server is

maintained in parallel to the Primary server. In the

event of a detected interruption on the hardware,

the Standby server will assume control of the

communication with the devices.

Based on data criticality, the second level

duplicates all the servers, ATR and I/O. Identical data is maintained on both servers.

In the diagram to the left,

Primary and Standby I/O

servers are deployed

independently, while Alarms,

Trends and Reports servers

are run as separate

processes on common

Primary and Standby

computers.

Network: Data Path Redundancy

Data path redundancy involves not alternative

device(s), but alternative data paths between

the I/O Server and connected I/O Devices.

Thus if one data path becomes inoperative,

the other is used.

Note: Vijeo Citect reconnects through the primary data path when it is returned into

service.

On a larger Vijeo Citect system, you can

also use data path redundancy to

maintain device communications through

multiple I/O Server redundancy, as shown

in the following diagram.

Page 38: Document1

High Availability with Collaborative Control System

38

Redundant LAN

As previously indicated, redundancy of Alarms, Reports, Trends, and I/O Servers is

achieved by adding standby servers. Vijeo Citect can also use the dual end point (or

multiple network interfaces) potentially available on each server, enabling the

specification of a complete and unique network connection between a Client and a

Server.

Target: I/O Device

A given I/O Server is able to

handle designated pairs of

Devices, Primary and Standby.

This Device Redundancy does

not rely on a PLC Hot Standby

mechanism: Primary and

Standby devices are assumed

to be concurrently acting on the

same process, but no

assumption is made

concerning the relationship

between the two devices. Seen from I/O Server, this redundancy offers access only to

an alternate device, in case the first device becomes inoperative.

The I/O device is an extension of I/O Device Redundancy, providing for more than

one Standby I/O Device. Depending on the user configuration, a given order of

priority applies when an I/O Server (potentially a redundant one) needs to switch to a

Standby I/O Device. For example, in the figure above I/O Device 3 would be allotted

the highest priority, then I/O Device 2, then finally I/O Device 4.

Page 39: Document1

High Availability with Collaborative Control System

39

In those conditions, in case of a detected interruption occurring on Primary I/O Device

1, a switchover would take place, with I/O Server 2 handling communications, and

with Standby I/O Device 3. If an interruption is now detected on I/O Device 3, a new

switchover would take place, with I/O Server 1 handling communications, with

Standby I/O Device 2. Finally, if there is an interruption on I/O Device 2, another

switchover would take place, with I/O Server 2 handling communications, with

Standby I/O Device 4

Clustering

Refer again to the

diagram on the left,

explaining

Redundancy basics,

and examine the

functional

representation as a

cluster.

A cluster may

contain several

possibly

redundant I/O

Servers

(maximum of

one per

machine), and

standalone or

redundant

ATR servers; these latter servers being implemented either on a common or on

separate machines.

Page 40: Document1

High Availability with Collaborative Control System

40

The cluster concept

offers a response to a

typical scenario of a

system separated into

several sites, with

each of these sites

being controlled by

local operators, and

supported by local

redundant servers.

The clustering model

can concurrently address an additional level of management that requires all sites

across the system to be monitored simultaneously from a central control room.

With this scenario, each site is represented with a separate cluster, grouping its

primary and standby servers. Clients on each site are interested only in the local

cluster, whereas clients at the central control room are able to view all clusters.

B

a

s

e

d

o

n

c

l

u

s

t

e

Based on cluster design, each site can then be addressed independently within its

own cluster. As a result, deployment of a control room scenario is fairly

straightforward, with the control room itself only needing display clients.

The cluster concept does not actually provide an additional level of redundancy.

Regarding data criticality, clustering organizes servers, and consequently provides

additional flexibility.

Page 41: Document1

High Availability with Collaborative Control System

41

Each cluster contains only one pair each of ATR servers. Those pairs of servers,

redundant to each other, must be on different machines.

Each cluster can contain an unlimited number of I/O servers; those servers must also

be on different machines that increase the level of system availability.

Conclusion

The following illustration shows a complete installation. Redundant solutions

previously discussed can be identified:

Communication Infrastructure Level

The previous section reviewed various aspects of enhanced availability at the

Information Management level, focusing on SCADA architecture, represented by

Vijeo Citect. This section covers High Availability concerns between the Information

level and the Control Level.

A proper design at the communication infrastructure level must include:

• Analysis of the plant topology

• Localization of the critical process steps

• The definition of network topologies

• The appropriate use of communication protocols

Scada Clients

Data Servers

Control Network

Targeted Devices

Page 42: Document1

High Availability with Collaborative Control System

42

Plant Topology

The first step of the communication infrastructure level definition is the plant topology

analysis. From this survey, the goal is to gather information to develop a networking

system diagram, prior to defining the network topologies.

This plant topology analysis must be done as a top-down process:

• Break-down of the plant in selected areas

• Localization of the areas to be connected

• Localization of the hazardous areas

• Localization of the station and the nodes included in these areas to be connected

• Localization of the existing networks & cabling paths, in the event of expansion or

redesign

Before defining the network topologies, the following project requirements must be

considered:

• Availability expectation, according to the criticality of the process or data.

• Cost constraints

• Operator skill level

From the project and the plant analyses, identify the most critical areas:

<- Valves

<- Pumps

<- Motors (Conveyor)

<- Measure-ments

ProcessProject

Criticality analysis Criticality analysis Criticality analysis Criticality analysis

Identification of the most critical areas Identification of the most critical areas Identification of the most critical areas Identification of the most critical areas

Page 43: Document1

High Availability with Collaborative Control System

43

Network Topology

Topologies

Following the criticality analysis, the networking diagram can be defined by selecting

the relevant Network topology.

The following table describes the four main topologies from which to choose:

Architecture Limitations Advantages Disadvantages

Bus

The traffic must flow serially,

therefore the bandwidth is not

used efficiently

Cost-effective solution If a switch becomes

inoperative, the

communication is lost.

Star

Cable ways and distances Efficient use of the

bandwidth, as the

traffic is spread across

the star

Preferred topology

when there is no need

of redundancy

If the main switch

becomes inoperative,

the communication is

lost

Ring

Behavior quite similar to Bus Auto-configuration if

used with self-healing

protocol

Possible to couple

others rings for

increasing redundancy

The Auto-configuration

depends on the

protocol used

Note: These different topologies can be mixed to define the plant network diagram.

Page 44: Document1

High Availability with Collaborative Control System

44

The following diagram shows the level of availability based on topology:

In automation architecture, Ring (and Dual ring) topologies are the most commonly

used to increase the availability of a system.

Mesh architecture is not used in process applications; therefore we will not discuss it

in detail. All these topologies are allowed using Schneider Electric ConneXium

switches.

Ring Topology

In a ring topology four events can occur, leading to a loss of communication:

1)Broken ring line

2)Inoperative ring switch

3)Inoperative ended-line devices

4)Inoperative ended-line devices switch

Page 45: Document1

High Availability with Collaborative Control System

45

The following diagram illustrates these four occurrences:

To protect the network architecture from these events, several communication

protocols are proposed and described in the following section.

A solution able to enhance networking availability while preserving budget

considerations consists of reducing both limitations of an Ethernet network:

distributed as a bus, but built as a ring. At least one specific active component is

necessary: this is a network switch usually named Redundancy Manager (RM).

Consider an Ethernet loop designed with such a RM switch. In normal conditions, this

RM switch will open the loop: which prevents Ethernet frames from circulating

endlessly in a loop.

If a break occurs, the

Redundancy Manager

switch reacts immediately,

and closes the Ethernet

loop, bringing the network

back to full operating

condition.

Note that the term Self

Healing Ring concerns the

ring management only;

once cut, the cable is not

able to repair itself.

1

4 3 2

Page 46: Document1

High Availability with Collaborative Control System

46

A mix of Dual Networking and Network Redundancy is possible. Note that in such a

design, a SCADA I/O Server has to be equipped with two communication boards, and

reciprocally, each device (PLC) has to be allotted two Ethernet ports.

Redundant Coupling of a Ring Network or a Network Segment

Topological considerations may lead to consideration of a network layout aggregating

satellite rings or segments around a backbone network (itself designed as a ring or as

a segment).

This may be an effective design, considering the junction between trunk and satellites,

especially if backbone and satellite networks have been designed as ring networks to

provide for High Availability.

With the Connexium product line, Schneider Electric offers switches that may afford a

redundant coupling. Several variations allow connection to the network. Each of these

variations is featured by two “departure” switches on the backbone network. Each

departure switch is crossing through a separate link to access the satellite network.

These variations include:

1. A single pivot ”arrival' switch on the connected network

2. Two different arrival switches on the connected network; this links

synchronization, making good use of backbone and satellite networks

3. Two different switches to access the connected network; this links

synchronization being carried via an additional specific link established

between the two arrival switches on the connected network.

Page 47: Document1

High Availability with Collaborative Control System

47

The following drawing illustrates this architecture:

Ring coupling capabilities increase the level of networking availability by allowing

different paths to access to targeted devices.

New generation of Schneider ConneXium switches authorize many architectures

based on dual ring. A unique switch is able now to couple two Ethernet rings

extending the capabilities of Ethernet architecture.

Dual Ring in One Switch

The following illustration shows the architecture, which allows the combination of two

rings managed by a unique switch.

RMRMRMRM

RMRMRMRM

MRP / RSTP

ETY SYNC LINKETY SYNC LINKETY SYNC LINKETY SYNC LINKETY SYNC LINKETY SYNC LINKETY SYNC LINKETY SYNC LINK

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

CPU SYNC LINKCPU SYNC LINKCPU SYNC LINKCPU SYNC LINK

PremiumPremiumPremiumPremium

ETY SYNC LINKETY SYNC LINKETY SYNC LINKETY SYNC LINKETY SYNC LINKETY SYNC LINKETY SYNC LINKETY SYNC LINK

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

CPU SYNC LINKCPU SYNC LINKCPU SYNC LINKCPU SYNC LINK

PremiumPremiumPremiumPremium

Ring CouplingRing CouplingRedundant lineRedundant line

Page 48: Document1

High Availability with Collaborative Control System

48

Dual Ring in Two Switches

The following architecture bypasses the single detected interruption.

Dual Ring Extension in Two Switches

The following architecture allows extension of the main network to other segments :

This concept of sub-ring enables to couple segments to existing redundancy rings.

The devices in the main ring (1) are seen as Sub-Ring Managers (SRM) for the new

connected sub-ring (2).

Daisy Chain Loop Topology

Ethernet "daisy chain" refers to the

integration of a switch function inside a

communicating device; as a result, this

“daisy-chainable” device offers two

Ethernet ports, for example one "in" port

Page 49: Document1

High Availability with Collaborative Control System

49

and one "out" port. The advantage of such a daisy-chainable device is that its

installation inside an Ethernet network requires only two cables.

In addition, a daisy-chain layout can

correspond to either a network segment

or a network loop; a managed Connexium

switch4, featuring an RM capability, is

able to handle such a daisy-chained loop.

The First daisy-chainable devices

Schneider Electric plans to offer are:

� Advantys STB dual port Ethernet communication adapter (STB NIP 2311)

� Advantys ETB IP67 dual port Ethernet

� Motor controller TeSys T

� Variable speed drive ATV 61/71 (VW3A3310D)

� PROFIBUS DP V1 Remote Master

� ETG 30xx Factorycast gateway

Note: Assuming no specific redundancy protocol is selected to handle the daisy

chain loop, expected loop reconfiguration time on failover is approximately one

second.

PrimaryPrimaryPrimaryPrimary StandbyStandbyStandbyStandby

SCADASCADASCADASCADA

SCADASCADASCADASCADA

RMRMRMRM

RMRMRMRM

MRP / RSTP

MRP / RSTP

ETY SYNC LINKETY SYNC LINKETY SYNC LINKETY SYNC LINKETY SYNC LINKETY SYNC LINKETY SYNC LINKETY SYNC LINK

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

CPU SYNC LINKCPU SYNC LINKCPU SYNC LINKCPU SYNC LINK

PremiumPremiumPremiumPremium

ETY SYNC LINKETY SYNC LINKETY SYNC LINKETY SYNC LINKETY SYNC LINKETY SYNC LINKETY SYNC LINKETY SYNC LINK

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

ETY

CPU SYNC LINKCPU SYNC LINKCPU SYNC LINKCPU SYNC LINK

PremiumPremiumPremiumPremium

RMRM

Ring CouplingRing CouplingRedundant lineRedundant line

Page 50: Document1

High Availability with Collaborative Control System

50

Daisy chaining topologies can be coupled to dual Ethernet rings using TCSESM

ConneXium switches.

Redundancy Communication Protocols

The management of Ethernet ring requires dedicated communication protocols as

described in the following table:

Each protocol is characterized by different performance criteria in terms of fault

detection and global system recovery time.

Rapid Spanning Tree Protocol (RSTP)

RSTP stands for Rapid Spanning Tree Protocol (IEEE 802.1w standard)1. Based on

STP, RSTP has introduced some additional parameters that must be entered during

the switch configuration. These parameters are used by the RSTP protocol during the

path selection process; because of these, the reconfiguration time is much faster than

with STP (typically less than one second).

1 The new edition of the 802.1D standard, IEEE 802.1D-2004, incorporates IEEE 802.1t-2001 and IEEE

802.1w standards

MRP Rapid Spanning Tree (RSTP)

HIPER-Ring Fast HIPER-Ring

Mix Switches In Network (Cisco/3Com/Hirschmann)

Part of IEC 62439 FDIS

Yes No No( New features

available only on Extended

Connexium switches)

Recovery Time Less than 200 ms

50 switches max

depending on number

of switches up to 1 sec

300 or 500ms

50 switches max

10 ms for 5 switches

160 microseconds for

each additional switch

Page 51: Document1

High Availability with Collaborative Control System

51

The new release of TCSESM ConneXium switches allows better performance of

RSTP management with a detection time of 15 ms and a propagation time of 15 ms

for each switch. Considering a 6 switches configuration, the recovery time is about

105 ms.

HIPER-Ring (Version 1)

Version 1 of the HIPER-Ring networking strategy has been available for

approximately 10 years. It applies to a Self Healing Ring networking layout.

Such a ring structure may include up to 50 switches. It typically features a

reconfiguration delay of 150 milliseconds2 and a maximum time of 500 ms. As a result,

in case of an issue occurring on a link cable or on one of the switches populating the

ring, the network will take about 150 ms to detect this event, and cause the

Redundancy Manager switch to close the loop.

Note: The Redundancy Manager switch is said to be active when it opens the

network.

Note: If recovery time of 500 ms is acceptable, then no switch redundancy

configuration is needed only dip switches have to be set up.

HIPER-Ring Version 2 (MRP)

2When configuring a Connexium TCS ESM switch for HIPER-Ring V1, the user is asked to choose

between a maximum Standard Recovery Time, which is 500 ms, and a maximum Accelerated Recovery

Time, which is 300 ms.

Page 52: Document1

High Availability with Collaborative Control System

52

MRP is an IEC 62439 industry standard protocol based on HIPER-ring. Therefore all

switch manufactures can implement MRP if they choose too. This allows a mix of

different manufactures in an MRP configuration. Schneider’s’ switches support a

selectable maximum recovery time of 200ms or 500ms and 50 switch maximum ring

configuration.

TCESM switches also support redundant coupling of MRP rings. MRP rings could

easily be used instead of HIPER-ring. MRP would require that all switches be

configured via Web pages and allow for recovery time of 200ms or 500ms.

Additionally the I/O network could be a MRP redundant network and the control

network HIPER-ring or vice versa.

Fast HIPER-Ring

A new family of Connexium switches is coming named TCS ESM Extended. This will

offer a third version of HIPER-Ring strategy, named Fast HIPER-RING.

Featuring a guaranteed recovery time of less than 10 milliseconds, the fast HIPER

ring structure allows both a cost optimized implementation of a redundant network as

well as maintenance and network extension during operation. This makes fast HIPER

ring especially suitable for complex applications such as a combined transmission of

video, audio and data information

Page 53: Document1

High Availability with Collaborative Control System

53

Selection

To end the communication level section, the following table presents all the

communication protocols, and thus helps you selecting the most appropriate

installation for your high availability solution:

Selection Criteria Solution Comments

Ease of configuration or

installed base

HIPER-Ring If recovery time of 500 ms is acceptable, then no switch

redundancy configuration is needed. Dip switches have

to be set up only.

New installation MRP All switches are configured via web pages

Installation with one MRM (Media Ring Manager) and

X MRCs (Media Ring Client)

Open architecture with

multiple vendors switch

RSTP Reconfiguration time: 15 ms (detected fault) + 15 ms

per switch.

Complex Architecture MRP, RSTP or

FAST HIPER-

Ring

We recommend MRP or RSTP for High Availability with

dual ring, and FAST HIPER-Ring for high performance.

Page 54: Document1

High Availability with Collaborative Control System

54

Control System Level

Having detailed High Availability aspects at the Information Management level and at

the Communication Infrastructure level, we will now concentrate on High Availability

concerns at the Control Level. Specific discussion will focus on PAC redundancy.

Redundancy Principles

Modicon Quantum and Premium PAC provide Hot Standby capabilities, and have

several shared principles:

1. The type of architecture is

shared. A Primary unit executes

the program, with a Standby unit

ready, but not executing the

program (apart from the first

section of it). By default, these two units contain an identical application program.

2. The units are synchronized. The standby unit is aligned with the Primary unit.

Also, on each scan, the Primary unit transfers to the Standby unit its "database,”

that is, the application variables (located or not located) and internal data. The

entire database is transferred, except the "Non-Transfer Table", which is a

sequence of Memory Words (%MW). The benefit of this transfer is that, in case of

a switchover, the new Primary unit will continue to handle the process, starting

with updated variables and data values. This is referred to as a "bumpless"

switchover.

3. The Hot Standby redundancy mechanism is controlled via the "Command

Register" (accessed thru %SW60 system word); reciprocally, this Hot Standby

redundancy mechanism is monitored via the "Status Register" (accessed thru

%SW61 system word). As a result, as long as the application creates links

between these system words and located memory words, any HMI can receive

feedback regarding Hot Standby system operating conditions, and, if necessary,

address these operating conditions.

4. For any Ethernet port acting as a server (Modbus/TCP or HTTP protocol) on the

Primary unit, its IP address is implicitly incremented by one on the Standby unit.

Page 55: Document1

High Availability with Collaborative Control System

55

In case a switchover occurs, homothetic addresses will automatically be

exchanged. The benefit of this feature is that seen from a SCADA/HMI, the

"active" unit is still accessed at the same IP address. No specific adaptation is

required at the development stage of the SCADA / HMI application.

5. The common programming environment that is used with both solutions is Unity

Pro. No particular restrictions apply when using the standardized (IEC 1131-3)

instruction set. In addition, the portion of code specific to the Hot Standby system

is optional, and is used primarily for monitoring purpose. This means that with any

given application, the difference between its implementation on standalone

architecture and its implementation on a Hot Standby architecture is largely

cosmetic.

Consequently, a user familiar with one type of Hot Standby system does not have to

start from scratch if he has to use a second type; initial investment is preserved and

re-usable, and only a few differences must be learned to differentiate the two

technologies.

Premium and Quantum Hot Standby Architectures

Depending on projects constraints or customers requirements (performance, installed

base or project specifications), a specific Hot Standby PAC station topology can be

selected:

- Hot Standby PAC with in-rack I/O or remote I/O

- Hot Standby PAC with distributed I/O, connected on Standard Ethernet or

connected to another device bus, such as Profibus DP.

- Hot Standby PAC mixing different topologies

The following table presents the available configurations with either a Quantum or

Premium PLC:

PLC I/O Bus Ethernet Profibus

Quantum Configuration 1 Configuration 3 Configuration 5

Premium Configuration 2 Configuration 4 Not applicable

Note: A sixth configuration may be considered, which combines all other

configurations listed above

Layer

Page 56: Document1

High Availability with Collaborative Control System

56

In-Rack and Remote I/O Architectures

Quantum Hot Standby: Configuration 1

With Quantum Hot Standby, in-rack I/O

modules are located in the remote I/O

racks. They are "shared" by both Primary

and Standby CPUs, but only the Primary

unit actually handles the I/O

communications at any given time. In

case of a switchover, the control

takeover executed by the new Primary

unit occurs in a bumpless way (provided

that the holdup time parameter allotted to

the racks is greater than the lack of

communication gap that takes place at the

switchover). The module population of a

Quantum CPU rack in a Hot Standby

configuration is very similar to that of a

standalone PLC3. The only specific requirement

is that the CPU module must be a 140 CPU 671 60.

For redundant PAC architecture, both units require two interlinks to execute different

types of diagnostic - to orient the election of the Primary unit, and to achieve

synchronization between both machines. The first of these "Sync Links,” the CPU

Sync Link, is a dedicated optic fiber link anchored on the Ethernet port local to the

CPU module. This port is dedicated exclusively for this use on Quantum Hot Standby

architecture. The second of these Sync Links, Remote I/O Sync Link, is not an

additional one: the Hot Standby system uses the existing Remote I/O medium,

hosting both machines, thus providing them with an opportunity to communicate.

One benefit of the CPU optic fiber port is its inherent capability to have the two units

installed up to 2 km apart, using 62.5/125 multimode optic fiber. The Remote I/O Sync

Link can also run through optic fiber, provided that Remote I/O Communication

Processor modules are coupled on the optic fiber.

3All I/O modules are accepted on remote I/O racks, except 140 HLI 340 00 (Interrupt module).

Looking at Ethernet adapters currently available, 140 NWM 100 00 communication module is not

compatible with a Hot Standby system. Also EtherNet/IP adapter (140 NOC 771 00) is not compatible with

Quantum Hot Standby in Step 1.

Page 57: Document1

High Availability with Collaborative Control System

57

Up to 6 communication modules4, such as NOE Ethernet TCP/IP adapters, can be

handled by a Quantum unit; whether it is a standalone unit or part of a Hot Standby

architecture.

Up to 31 Remote I/O stations can be handled from a Quantum CPU rack, whether

standalone or Hot Standby. Note that the Remote I/O service payload on scan time is

approximately 3 to 4 ms per station.

Redundant Device Implementation

Using redundant in-rack I/O modules on

Quantum Hot Standby, and having to

interface redundant sensors/actuators, will

require redundant input / output channels.

Preferably, homothetic channels should be

installed on different modules and different

I/O Stations. For even a simple transfer of

information to both sides of the outputs, the

application must define and implement rules

for selecting and treating the proper input

signals. In addition to information transfer,

the application will have to address

diagnostic requirements.

4Acceptable communication modules are Modbus Plus adapters, Ethernet TCP/IP adapters, Ethernet/IP

adapters and PROFIBUS DP V1 adapters.

Page 58: Document1

High Availability with Collaborative Control System

58

Single Device Implementation

Assuming a Quantum Hot Standby

application is required to handle redundant

in-rack I/O channels, but without redundant

sensors and actuators, special devices are

used to handle the associated wiring

requirements. Any given sensor signal,

either digital or analog, passes through

such a dedicated device, which replicates it

and passes it on to homothetic input

channels. Reciprocally, any given pair of

homothetic output signals, either digital or

analog, are provided to a dedicated device

that selects and transfers the proper signal

(i.e. the one taken on Primary output) to the target actuator.

Depending on the selected I/O Bus technology, a specific layout may result in

enhanced availability.

Dual Coaxial Cable

Coaxial cable can be installed with

either as a single or redundant

design. With a redundant design,

communications are duplicated on

both channels, providing a "massive

communication redundancy.” Either

the Remote I/O Processor or Remote

I/O adapters are equipped with a pair

of connectors, with each connector

attached to a separate coaxial

distribution.

Page 59: Document1

High Availability with Collaborative Control System

59

Self Healing Optical Fiber Ring

Remote I/O Stations can be installed

as terminal nodes of a fiber optic

segment or (self-healing) ring. The

Schneider catalog offers one model

of transceiver (490 NRP 954)

applicable for 62.5/125 multimode

optic fiber: 5 transceivers maximum,

10 km maximum ring circumference.

When the number of transceivers is

greater than 5, precise optic fiber

ring diagnostics are required, or single mode fiber is required.

Configuration Change on the Fly

High-level level feature is currently being added to Quantum Hot Standby applications

design. This is CCTF, or Configuration Change on the Fly. This new feature will allow

you to modify the configuration of the existing and running PLC application program,

without having to stop the PLC. As an example, consider the addition of a new

discrete or analog module on a remote Quantum I/O Station. For the CPU Firmware

version upgrade, executed on a Quantum Hot Standby architecture, this CCTF will be

sequentially executed, one unit at a time.This is an obvious for applications that

cannot afford any stop, which will now become available for architecture modification

or extensions.

Premium Hot Standby: Configuration 2

Premium Hot Standby is able to

handle in-rack I/O modules, installed

on Bus-X racks5. The Primary unit

acquires its inputs, executes the logic,

and updates its outputs. As a result of

cyclical Primary to Standby data

transfer, the Standby unit provides

local outputs that are the image of the outputs decided on the Primary unit. In case of

a switchover, the control takeover executed by the new Primary unit occurs in a

bumpless fashion.

5Initial version of Premium Hot Standby only authorizes a single Bus-X rack on both units.

Page 60: Document1

High Availability with Collaborative Control System

60

The module population of a Premium

CPU rack, in a Hot Standby

configuration, is very similar to that of

a standalone PLC (some restrictions

apply on compatible modules6). Two

types of CPU modules are available:

TSX H57 24M and TSX H57 44M,

which differ mainly in regard to memory and communication resources.

The first of the two Sync Links, the

CPU Sync Link is a dedicated copper

link anchored on the Ethernet port

local to the CPU module. With

Premium Hot Standby architecture, the

second Sync Link, Ethernet Sync Link is established using a standard Ethernet

TCP/IP module7. It corresponds to the communication adapter elected as the

"monitored" adapter

6Counting, motion, weighing and safety modules are not accepted. On the communication side, apart from

Modbus modules TSX SCY 11 601/21 601, only currently available Ethernet TCP/IP modules are accepted.

Also EtherNet/IP adapter (TSX ETC 100) is not compatible with Premium Hot Standby in Step 1.

7TSX ETY 4103 or TSX ETY 5103 communication module

Page 61: Document1

High Availability with Collaborative Control System

61

The following picture illustrates the Premium Ethernet configuration, with the CPU

and the ETY Sync links:

This Ethernet configuration is detailed in the following section.

Redundant Device Implementation

In-rack I/O module implementation on Premium

Hot Standby corresponds by default to a

massive redundancy layout: each input and

each output has a physical connection on both

units. Redundant sensors and actuators do not

require additional hardware. For even a simple

transfer of information to both sides of the outputs, the application must define and

implement rules for selecting and treating the proper input signals. In addition to

information transfer, the application will have to address diagnostic requirements.

Single Device Implementation

Assuming a Premium Hot Standby application

is required to handle redundant in-rack I/O

channels, but without redundant sensors and

actuators, special devices are used to handle

the associated wiring requirements. Any given

sensor signal, either digital or analog, passes

through such a dedicated device, which

replicates it and passes it on to homothetic input channels. Reciprocally, any given

pair of homothetic output signals, either digital or analog, are provided to a dedicated

device that selects and transfers the proper signal (i.e. the one taken on Primary

output) to the target actuator.

Page 62: Document1

High Availability with Collaborative Control System

62

Distributed I/O Architectures

Ethernet TCP/IP: Configurations 3&4

Schneider Electric has supported Transparent Ready strategy for several years. In

addition to SCADA and HMI, Variables Speed Drives, Power Meters, and a wide

ranges of gateways, Distributed I/Os with Ethernet connectivity, such as Advantys

STB, are also being proposed,. In addition many manufacturers are offering devices

capable of communicating on Ethernet using Modbus TCP8 protocol. These different

contributions using the Modbus protocol design legacy have helped make Ethernet a

general purpose preferred communication support for automation architectures.

In addition to Ethernet messaging services solicited through application program

function blocks, a communication service is available on Schneider Electric PLCs: the

I/O Scanner. The I/O Scanner makes a PLC Ethernet adapter/Copro act as a

Modbus/TCP client, periodically launching a sequence of requests on the network.

These requests correspond to standard Modbus function codes, asking for Registers

(Data Words), Read, Write or Read/Write operations. This sequence is determined by

a list of individual contracts specified in a table defined during the PLC configuration.

The typical target of such a communication contract is an I/O block, hence the name

"I/O Scanner". Also, the I/O Scanner service may be used to implement data

exchanges with any type of equipment, including another PLC, provided that

equipment can behave as a Modbus/TCP server, and respond to multiple words

access requests.

Ethernet I/O scanner service is

compatible with a Hot Standby

implementation, whether Premium

or Quantum. The I/O scanner is

active only on the Primary unit. In

case of a controlled switchover,

Ethernet TCP/IP connections

handled by the former Primary unit

are properly closed, and new ones

are reopen once the new Primary

gains control. In case of a sudden

switchover, resulting, for example,

8In step 1, support of Ethernet/IP Quantum/Premium adapters is not available with Hot Stand-By.

Page 63: Document1

High Availability with Collaborative Control System

63

from a power cut-off, the former Primary may not able to close the connections it had

opened. These connections will be closed after expiration of a Keep Alive timeout.

In case of a switchover, proper communications will typically recover after one initial

cycle of I/O scanning. However, the worst case gap for address swap, with I/O

scanner, is 500 ms, plus one initial cycle of I/O scanning. As a result, this mode of

communication, and hence architectures with Distributed I/Os on Ethernet, is not

preferred with a control system that regards time criticality as an essential criteria.

Note: The automatic IP address swap capability is a property inherited by every

Ethernet TCP/IP adapter installed in the CPU rack.

Self Healing Ring

As demonstrated in the previous chapter, Ethernet TCP/IP used with products like

Connexium offers real opportunities to design enhanced availability architectures,

handling communication between the Information Management Level and the Control

Level. Such architectures, based on a Self Healing Ring topology, are also applicable

when using Ethernet TCP/IP as a fieldbus.

Note that Connexium accepts Copper or Optic Fiber rings. In addition, dual

networking is also applicable at the fieldbus level.

Page 64: Document1

High Availability with Collaborative Control System

64

Profibus Architecture

I/O Devices Distributed on PROFIBUS DP/PA: Configuration 5

A PROFIBUS DP V1 Master Class 1

Quantum form communication module is

available. It handles cyclic and acyclic data

exchanges, and accepts FDT/DTM Asset

Management System data flow, through its

local Ethernet port.

The PROFIBUS network is configured with

a Configuration Builder software, which

supplies the Unity Pro application program

with data structures corresponding to cyclic

data exchanges and to diagnostic

information.

The Configuration Builder can also be configured to pass Unity Pro a set of DFBs,

allowing easy implementation of Acyclic operations.

Each Quantum PLC can accept up to 6 of these DP Master modules (each of them

handling its own PROFIBUS network). Also, the PTQ PDPM V1 Master Module is

compatible with a Quantum Hot Standby implementation. Only the Master Module in

the Primary unit is active on the PROFIBUS network; the Master Module on the

Standby unit stays in a dormant state unless awakened by a switchover.

Page 65: Document1

High Availability with Collaborative Control System

65

PROFIBUS DP V1 Remote Master and Hot Standby PLC

With a smart device such as

PROFIBUS Remote Master9,

an I/O Scanner stream is

handled by the PLC

application10 and forwarded

to the Remote Master via

Ethernet TCP/IP. In turn,

Remote Master handles the

corresponding cyclic

exchanges with the devices populating the PROFIBUS network. Remote Master can

also handle acyclic data exchanges.

The PROFIBUS network is configured with Unity Pro11, which also acts as an FDT

container, able to host manufacturer device DTMs. In addition, Remote Master offers

a comDTM to work with third party FDT/DTM Asset Management Systems.

Automatic symbol generation provides Unity Pro with data structures corresponding

to data exchanges and diagnostic information. A set of DFBs is delivered that allows

an easy implementation of acyclic operations.

Remote Master is compatible with a Quantum, Premium or Modicon M340 Hot

Standby implementation.

9Planned First Customer Shipment: Q4 2009

10M340, Premium or Quantum

11version 5.0

Page 66: Document1

High Availability with Collaborative Control System

66

Redundancy and Safety

Requirements for Availability and Safety are often considered

to be working against each other. Safety can be the

response to the maxim "stop if any potential danger arises,’

whereas Availability can follow the slogan "Produce in spite of

everything.”

Two models of CPU are available to design a Quantum

Safety configuration: the first model (140 CPU 651 60S) is

dedicated to standalone architectures, whereas the second

model ( 140 CPU 671 60S) is dedicated to redundant

architectures.

The Quantum Safety PLC has some exclusive features: a

specific hardware design for safety modules (CPU and I/O

modules) and a dedicated instruction set.

Otherwise, a Safety Quantum Hot Standby configuration has

much in common with a regular Quantum Hot Standby configuration. The

configuration windows, for example, are almost the same, and the Ethernet

communication adapters inherit the IP Address automatic swap capability. Thus the

Safety Quantum Hot Standby helps to reconcile and integrate the concepts of Safety

and Availability.

Page 67: Document1

High Availability with Collaborative Control System

67

Mixed Configuration: Configuration 6

Whether Premium or Quantum,

application requirements such as

topology, environment, periphery,

time criticality, etc. may influence

the final architecture design to

adopt both types of design

strategies concurrently, i.e. in-

rack and distributed I/Os,

depending on individual

subsystems constraints.

Premium / Quantum Hot Standby Switchover Conditions

System Health Diagnostics

Systematic checks are executed cyclically by any running CPU, in order to detect a

potential hardware corruption, such as a change affecting the integrity of the Copro,

the sub-part of the CPU module that hosts the integrated Ethernet port. Another

example of a systematic check is the continuous check of the voltage levels provided

by the power supply module(s). In case of a negative result during these hardware

health diagnostics, the tested CPU will usually switch to a Stop State.

When the unit in question is part of a Hot Standby System, in addition to these

standard hardware tests separately executed on both machines, more specific tests

are conducted between the units. These additional tests involve both Sync Links. The

basic objective is to confirm that the Primary unit is effectively operational, executing

the application program, and controlling the I/O exchanges. In addition, the system

must verify that the current Standby unit is able to assume control after a switchover.

Page 68: Document1

High Availability with Collaborative Control System

68

If an abnormal situation occurs on the current Primary unit, it gives up control and

switches either to Off-Line state (the CPU is not a part of the Hot Standby system

coupling) or to Stop State, depending on the event. The former Standby unit takes

control as the new Primary unit.

Controlled Switchover

As previously indicated, the Hot Standby system is controlled through the %SW61

system register. Each unit owns an individual bit on the system Command Register

that decides whether or not that particular unit has to make its possible to "hook" to

the other unit. An operational hooked redundant Hot Standby system requires both

units to indicate this intent. Consequently, executing a switchover controlled by the

application on a hooked system is straightforward; it requires briefly toggling the

decision bit that controls the current Primary unit’s "hooking" intent. The first toggle

transition switches the current Primary unit to Off-Line Sate, and makes the former

Standby unit take control. The next toggle transition makes the former Primary unit

return and hook as the new Standby Unit.

An example of this possibility is a controlled switchover resulting from diagnostics

conducted at the application level. A Quantum Hot Standby, Premium Hot Standby or

Monitored Ethernet Adapter system does not handle a Modbus Plus or Ethernet

communication adapter malfunction as a condition implicitly forcing a switchover. As a

result, these communication modules must be cyclically tested by the application,

both on Standby and on Primary. Diagnostic results elaborated on Standby are

usually transferred to the Primary unit because of the Reverse Transfer Registers.

Finally, the application being reported a non fugitive inconsistency affecting Primary

unit, and at the same time a fully operational Standby unit, forces a switchover based

on the playing on Control Register.

Hence, the application program can decide on a Hot Standby switchover, having

registered a steady state negative diagnostic on the Ethernet adapter linking the

Primary unit to the "Process Network", and being at the same time informed that the

Standby unit is fully operational.

Note: There are two ways to implement a Controlled Switchover: automatically

through configuration of a default DFB, or customized with the creation of a DFB with

its own switchover conditions.

Page 69: Document1

High Availability with Collaborative Control System

69

The following illustration represents an example of a DFB handling a Hot Standby

Controlled Switchover:

This in turn makes use of an embedded DFB: HSBY_WR:

Fragment of HSBY_Switch_Decision DFB

Fragment of HSBY_WR DFB

Note: HSBY_WR DFB executes a write access on HSBY Control Register (%SW60).

Page 70: Document1

High Availability with Collaborative Control System

70

Switchover Latencies

The following table details the typical and maximum swap time delay encountered

when reestablishing Ethernet services during a Switchover event. (Premium and

Quantum configurations)

Service Typical Swap Time Maximum Swap Time

Swap IP Address 6 ms 500 ms

I/O Scanning 1 initial cycle of I/O scanning 500 ms + 1 initial cycle of I/O scanning

Client Messaging 1 MAST task cycle 500 ms + 1 MAST task cycle

Server

Messaging

1 MAST task cycle + the time required

by the client to reestablish its

connection with the server (1)

500 ms + the time required by the

client to reestablish its connection with

the server (1)

FTP/TFTP Server the time required by the client to

reestablish its connection with the

server (1)

500 ms + the time required by the

client to reestablish its connection with

the server (1)

SNMP 1 MAST task cycle 500 ms + 1 MAST task cycle

HTTP Server the time required by the client to

reestablish its connection with the

server (1)

500 ms + the time required by the

client to reestablish its connection with

the server (1)

(1) The time the client requires to reconnect with the server depends on the client communication loss

timeout settings.

Selection

To end the control level section, the following table presents the four main criteria that

help you selecting the most appropriate configuration for your high availability solution:

Criteria Cost High Criticality

Switchover Performance Premium

In Rack Architecture

Quantum

In Rack Architecture

Openness Premium

Distributed Architecture

Quantum

Distributed Architecture

Page 71: Document1

Conclusion

71

Premium/ Quantum Hot Standby Solution Reminder

The following tables provide a brief reminder of essential characteristics for Premium

and Quantum Hot Standby solutions, respectively:

Premium Hot Standby Essential Characteristics

Up to 128 per network / ETY I/O Scanner handles up to 64 transactions

Page 72: Document1

Conclusion

72

Quantum Hot Standby Essential Characteristics

Conclusion

This chapter has covered functional and architectural redundancy aspects, from the

Information Management level to the Control level, and up through the

Communication Infrastructure level.

Page 73: Document1

Conclusion

73

Conclusion

This section summarizes the main characteristics and properties of Availability for

Collaborative Control automation architectures.

Chapter 1 demonstrated that Availability is dependent not only on Reliability, but also

on Maintenance as it is provided to a given system. The first level of contribution,

Reliability, is primarily a function of the system design and components. Component

and device manufacturers thus have a direct but not exclusive influence on system

Availability. The second level of contribution, Maintenance and Logistics, is totally

dependent on end customer behavior.

Chapter 2 presented some simple Reliability and Availability calculation examples,

and demonstrated that beyond basic use cases, dedicated skills and tools are

required to extract figures from real cases.

Chapter 3 explored a central focus of this document, Redundancy, and its application

at the Information Management Level, Communication Infrastructure Level and

Control System Level.

This final chapter summarizes customer benefits provided by Schneider Electric High

Availability solutions, as well as additional information and references.

Page 74: Document1

Conclusion

74

Benefits

Schneider-Electric currently offers a wide range of solutions, providing the best

design to respond to specific customer needs for Redundancy and Availability in

Automation and Control Systems.

Standard Offer

One key concept of High Availability is that redundancy is not a default design

characteristic at any system level. Also, Redundancy can be added locally, using in

most cases standard components.

Simplicity of Implementation

At any level, intrusion of Redundancy into system design and implementation is

minimum, compared to a non-redundant system. For SCADA implementation,

network active components selection, or PLC programming, most of the software

contributions to redundancy are dependent on selections executed during the

configuration phase. Also, Redundancy can be applied selectively.

System Transparency

The transparency of a redundant system, compared to a standalone one, is a

customer requirement. With the Schneider Electric automation offer, this transparency

is present at each level of the system.

Information Management Level

For Client Display Stations, Dual Path Supervisory Networks, Redundant I/O servers,

or Dual Access to Process Networks, each redundant contribution is handled

separately by the system. For example, concurrent Display Clients communication

flow will be transparently re-routed to the I/O sever by the Supervisory Network in

case of a cable disruption. This flow will also be transparently routed to the alternative

I/O Server, in case of a sudden malfunction of the first server. Finally, the I/O Server

may transparently leave the communication channel it is using per default, if that

channel ceases to operate properly, or if the target PLC will not respond through this

channel.

Page 75: Document1

Conclusion

75

Communication Infrastructure Level

Whether utilized as a Process Network or as a Fieldbus Network, currently available

active network components can easily participate in an automatically reconfigured

network. With continuous enhancements, HIPER-Ring strategy not only offers

simplicity, but also a level of performance compatible with a high-reactivity demand.

Control System Level

The “IP Address automatic switch" for a SCADA application communicating through

Ethernet is an important feature of Schneider Electric PLCs. Apart from simplifying

the design of the SCADA application implementation, what may cause delays and

increased cost, this feature also contributes to reducing the payload of a

communication context exchange on a PLC switchover.

Ease of Use

As previously stated, increased effort has been made to make the implementation of

a redundant feature simple and straightforward.

The Vijeo Citect, ConneXium Web Pages and Unity Pro software environments offer

clear and accessible configuration windows, along with a dedicated selective help, in

order to execute the required parameterization.

More Detailed RAMS Investigation

In case of a specific need for detailed dependability (RAMS) studies, for any type of

architecture, contact the Schneider Electric Safety Competency Center. This center

has skilled and experienced individuals ready to help you with all your needs.

Page 76: Document1

Appendix

76

Appendix

Glossary

Note: the references in bracket refer to standard, which are specified at the end of

this glossary.

1) Active Redundancy

Redundancy where the different means required to accomplish a given function are

present simultaneously [5]

2) Availability

Ability of an item to be in a state to perform a required function under given conditions,

at a given instant of time or over a given time interval, assuming that the required

external resources are provided [IEV 191-02-05] (performance) [2]

3) Common Mode Failure

Failure that affects all redundant elements for a given function at the same time [2]

4) Complete failure

Failure which results in the complete inability of an item to perform all required

functions [IEV 191-04-20] [2]

5) Dependability

Collective term used to describe availability performance and its influencing factors:

reliability performance, maintainability performance and maintenance support

performance [IEV 191-02-03] [2]

Note: Dependability is used only for general descriptions in non-quantitative terms.

6) Dormant

A state in which an item is able to function but is not required functioning. Not to be

confused with downtime [4]

7) Downtime

Time during which an item is in an operational inventory but is not in condition to

perform its required function [4]

8) Failure

Termination of the ability of an item to perform a required function [IEV 191-04-01] [2]

Note 1: After failure the item detects a fault.

Note 2: "Failure" is an event, as distinguished from "fault", which is a state.

Page 77: Document1

Appendix

77

9) Failure Analysis

The act of determining the physical failure mechanism resulting in the functional

failure of a component or piece of equipment [1]

10) Failure Mode and Effects Analysis (FMEA)

Procedure for analyzing each potential failure mode in a product, to determine the

results or effects on the product. When the analysis is extended to classify each

potential failure mode according to its severity and probability of occurrence, it is

called a Failure Mode, Effects, and Criticality Analysis (FMECA).[6]

11) Failure Rate

Total number of failures within an item population, divided by the total number of life

units expended by that population, during a particular measurement period under

stated conditions [4]

12) Fault

State of an item characterized by its inability to perform a required function, excluding

this inability during preventive maintenance or other planned actions, or due to lack of

external resources [IEV 191-05-01] [2]

Note: a fault is often the result of a failure of the item itself, but may exist without prior

failure.

13) Fault- tolerance

Ability to tolerate and accommodate for a fault with or without performance

degradation

14) Fault Tree Analysis (FTA)

Method used to evaluate reliability of engineering systems. FTA is concerned with

fault events. A fault tree may be described as a logical representation of the

relationship of primary or basic fault events that lead to the occurrence of a specified

undesirable fault event known as the “top event.” A fault tree is depicted using a tree

structure with logic gates such as AND and OR [7]

Page 78: Document1

Appendix

78

FTA illustration [7]

15) Hidden Failure

Failure occurring that is not detectable by or evident to the operating crew [1]

16) Inherent Availability (Intrinsic Availability) : Ai

A measure of Availability that includes only the effects of an item design and its

application, and does not account for effects of the operational and support

environment. Sometimes referred to as "intrinsic" availability [4]

17) Integrity

Reliability of data which is being processed or stored.

18) Maintainability

Probability that an item can be retained in, or restored to, a specified condition when

maintenance is performed by personnel having specified skill levels, using prescribed

procedures and resources, at each prescribed level of maintenance and repair. [4]

19) Markov Method

A Markov process is a mathematical model that is useful in the study of the

availability of complex systems. The basic concepts of the Markov process are those

of the “state” of the system (for example operating, non-operating) and state

“transition” (from operating to non-operating due to failure, or from non-operating to

operating due to repair). [4]

Page 79: Document1

Appendix

79

Markov Graph illustration [2]

20) MDT: Mean Downtime

Average time a system is unavailable for use due to a failure.

Time includes the actual repair time plus all delay time associated with a repair

person arriving with the appropriate replacement parts [4]

21) MOBF: Mean Operating Time Between Failures

Expectation of the operating time between failures [IEV 191-12-09] [2]

22) MTBF

A basic measure of reliability for repairable items. The mean number of life units

during which all parts of the item perform within their specified limits, during a

particular measurement interval under stated conditions. [4]

23) MTTF : Mean Time To Failure

A basic measure of reliability for non-repairable items. The total number of life units of

an item population divided by the number of failures within that population, during a

particular measurement interval under stated conditions. [4]

Note: Used with repairable items, MTTF stands for Mean Time To First Failure

24) MTTR : Mean Time To Repair

A basic measure of maintainability. The sum of corrective maintenance times at any

specific level of repair, divided by the total number of failures within an item repaired

at that level, during a particular interval under stated conditions. [4]

25) MTTR : Mean Time To Recovery

Expectation of the time to recovery [IEV 191-13-08] [2]

Page 80: Document1

Appendix

80

26) Non-Detectable Failure

Failure at the component, equipment, subsystem, or system (product) level that is

identifiable by analysis but cannot be identified through periodic testing or revealed by

an alarm or an indication of an anomaly. [4]

27) Redundancy

Existence in an item of two or more means of performing a required function [IEV

191-15-01] [2]

Note: in this standard, the existence of more than one path (consisting of links and

switches) between end nodes.

Existence of more than one means for accomplishing a given function. Each means

of accomplishing the function need not necessarily be identical. The two basic types

of redundancy are active and standby. [4]

28) Reliability

Ability of an item to perform a required function under given conditions for a given

time interval [IEV 191-02-06] [2]

Note 1: It is generally assumed that an item is in a state to perform this required

function at the beginning of the time interval

Note 2: the term “reliability” is also used as a measure of reliability performance (see

IEV 191-12-01)

29) Repairability

Probability that a failed item will be restored to operable condition within a specified

time of active repair [4]

30) Serviceability

Relative ease with which an item can be serviced (i.e. kept in operating condition). [4]

31) Standby Redundancy

Redundancy wherein a part of the means for performing a required function is

intended to operate, while the remaining part(s) of the means are inoperative until

needed [IEV 19-5-03] [2]

Note: this is also known as dynamic redundancy.

Redundancy in which some or all of the redundant items are not operating

continuously but are activated only upon failure of the primary item performing the

function(s). [4]

Page 81: Document1

Appendix

81

32) System Downtime

Time interval between the commencement of work on a system (product) malfunction

and the time when the system has been repaired and/or checked by the maintenance

person, and no further maintenance activity is executed. [4]

33) Total System Downtime

Time interval between the reporting of a system (product) malfunction and the time

when the system has been repaired and/or checked by the maintenance person, and

no further maintenance activity is executed. [4]

34) Unavailability

State of an item of being unable to perform its required function [IEV 603-05-05] [2]

Note: Unavailability is expressed as the fraction of expected operating life that an

item is not available, for example given in minutes per year

Ratio: downtime/(uptime + downtime) [3]

Often expressed as a maximum period of time during which the variable is

unavailable, for example 4 hours per month

35) Uptime

That element of Active Time during which an item is in condition to perform its

required functions. (Increases availability and dependability). [4]

[1] Maintenance & reliability terms - Life Cycle Engineering

[2] IEC 62439: High Availability automation networks

[3] IEEE Std C37.1™-2007: Standard for SCADA and Automation System

[4] MIL-HDBK-338B - Military Handbook - Electronic Reliability Design Handbook

[5] IEC-271-194

[6] The Certified Quality Engineer Handbook - Connie M. Borror, Editor

[7] Reliability, Quality, and Safety for Engineers - B.S. Dhillon - CRC Press

Page 82: Document1

Appendix

82

Standards

This section contains a selected, non-exhaustive list of reference documents and

standards related to Reliability and Availability:

General purpose

� IEC 60050 (191):1990 - International Electrotechnical Vocabulary (IEV)

FMEA/FMECA

� IEC 60812 (1985) - Analysis techniques for system reliability - Procedures for failure mode and

effect analysis (FMEA)

� MIL-STD 1629A (1980) Procedures for performing a failure mode, effects and criticality analysis

Reliability Block Diagrams

� IEC 61078 (1991) Analysis techniques for dependability - Reliability block diagram method

Fault Tree Analysis

� NUREG-0492 - Fault Tree Handbook - US Nuclear Regulatory Commission

Markov Analysis

� IEC 61165 (2006) Application of Markov techniques

RAMS

� IEC 60300-1 (2003) - Dependability management - Part 1: Dependability management systems

� IEC 62278 (2002) - Railway applications - Specification and demonstration of reliability, availability, maintainability and safety (RAMS)

Functional Safety

� IEC 61508 - Functional safety of electrical/electronic/programmable electronic safety related

systems (7 parts)

� IEC 61511 (2003) Functional safety - Safety instrumented systems for the process industry sector.

Page 83: Document1

Calculation Examples

83

Reliability & Availability Calculation Examples

The previous chapter provided necessary knowledge and theory basics to understand

simple examples of Reliability and Availability calculations. This section examines

concrete, simple but realistic examples, related to current, plausible solutions.

The root piece of information required for all of these calculations, for all major

components we will implement in our architectures, is the MTBF figure. MTBFs are

normally provided by the manufacturer, either on request and/or on dedicated

documents. For Schneider Electric PLCs, MTBF information can be found on the

intranet site Pl@net, under Product offer>Quality Info.

Note: The MTBF information is usually not accessible via the Schneider Electric

public website.

Redundant PLC System, Using Massive I/O Modules Redundancy

Standalone Architecture

Consider a simple, single-rack Premium PLC configuration.

First, calculate the individual modules’ MTBFs, using a spreadsheet that will do the

calculations (examples include Excel and Open Office).

Page 84: Document1

Calculation Examples

84

The calculation guidelines are derived from the main conclusion given by Serial RBD

analysis, that is:. ∑

==

n

1iiSλλ : Equivalent Failure Rate for n serial elements is equal

to the sum of the individual Failure Rate of these elements, with tSe(t)SR

λ−= .

The first operation will identify individual MTBF figures of the part references

populating the target system. Using these figures, a second sheet will then

subsequently consider the item, group and system levels.

� For each of the identified items part references:

- Individual item Failure Rate λ, calculated just by inverting individual item

MTBF : λ = 1 / MTBF

- individual item Reliability, over 1 year, applying R(t) = e -λt, where t = 8760

that is the number of hours in one year (365 * 24)

Page 85: Document1

Calculation Examples

85

� For each of the identified items references groups:

- Group Failure Rate: Individual item Failure Rate times the number of items in

the considered group

- Group Reliability: Individual item Reliability powered by the number of items

� For the considered System:

- System Failure Rate: sum of Groups Failure Rates

- System MTBF in hours: reverse of System Failure Rate

- System Reliability over one year: exp(- System Failure Rate * 8760)]

(where 8760 = 365 *24 : number of hours in one year)

- System Availability (with MTTR = 2 h): System MTBF / (System MTBF + 2)]

Note:

� As previously explained, System figures produced by our basic calculations only

apply the equations given by basic probability analysis. In addition to these

calculations, a commercial software tool has been used, permitting us to confirm

our figures.

Looking at the example results, Reliability over one year is approximately 83%

(This means that the probability for this system to encounter one failure during

one year is approximately 17%).

System MTBF itself is approximately 45,500 hours (approximately 5 years)

Regarding Availability, with a 2 hour Mean Time To Repair (which corresponds to

a very good logistic and maintenance organization), we would have a 4-nines

resulting Availability, an average probability of approximately 23 minutes

downtime per year

Page 86: Document1

Calculation Examples

86

Redundant Architecture

Assuming we would like to increase this system’s

Availability by implementing a redundant architecture,

we need to calculate the potential gain for System

Reliability and Availability.

We will assume that we have no additional hardware,

apart from the two redundant racks. The required calculation guidelines are derived

from the main conclusion given by Parallel RBD analysis, that is:

∏=

−−=n

1i)t(iR11)t(dReR

This means if we consider RS as the Standalone System Reliability and RRed as the

Redundant System Reliability: 2))t(SR1(1)t(dReR −−=

Note: Formal calculations should also take into account undetected errors on

redundant architecture, what would provide somewhat less optimistic figures.

A complete analysis should also take in account the additional wiring devices typically

used on a massive I/O redundancy strategy, feeding homothetic input points with the

same input signal, and bringing homothetic output points onto the same output signal.

Also, with this software, a parallel structure has been retained, with the Failure Rate

the same on the Standby rack as on the Primary rack.

As a result of the redundant architecture, System Reliability over one year is

now approximately 97% (i.e. the probability for the system to encounter one

failure during one year has been reduced to approximately 3%).

System MTBF has increased from 45,500 hours (approximately 5 years) to

68,000 hours (approximately 7.8 years).

Regarding System Availability, with a 2 hour Mean Time To Repair we would

receive an 8-nines resulting Availability, which is close to 100%.

Page 87: Document1

Calculation Examples

87

Reminder of Standby Definitions:

Cold Standby: The Standby unit starts only

if the default unit becomes inoperative.

Warm Standby: The Failure Rate of the

Standby unit during the inactive mode is

less the Failure Rate when it becomes

active.

Hot Standby: The Failure Rate of the

Standby unit during the inactive mode is the same as the Failure Rate when it

becomes active. This is a simple parallel configuration.

Page 88: Document1

Calculation Examples

88

Redundant PLC System, Using Shared Remote I/O Racks

Simple Architecture with a Standalone CPU Rack

Consider a standalone CPU rack equipped

with power supply, CPU, remote I/O

processor and Ethernet communication

modules.

As in the previous section, calculate the

potential gain a redundant architecture would

allow, in terms of Reliability and Availability.

First calculate the individual modules MTBFs,

then establish, for each subsequent rack, a

worksheet that provides the Reliability and

Availability metrics figures.

Standalone CPU Rack

Page 89: Document1

Calculation Examples

89

Remote I/O Rack

Simple Architecture : Standalone CPU Rack + Remote I/O Rack

Page 90: Document1

Calculation Examples

90

Note: As expected, Reliability and Availability figures resulting from this Serial

implementation are determined by the weakest link of the chain.

For this Serial System (Rack # 1+ Rack # 2), Reliability over one year is approximately 82.8% (the

probability for this system to encounter one failure during one year is approximately 17%).

System MTBF is approximately 46,260 hours (approximately 5.3 years)

Regarding Availability, with a 2 hour Mean Time To Repair (which corresponds to a very good logistic

and maintenance organization), we receive a 4-nines resulting Availability, which is an average

probability of approximately 23 minutes downtime per year

Page 91: Document1

Calculation Examples

91

Simple Architecture with a Redundant CPU Rack

One solution to enforce Rack #1 Availability (i.e.the

rack hosting the CPU, and at present the process

control core) is to implement a Hot Standby

configuration.

Note: As expected, Reliability and Availability figures resulting from this Parallel

implementation are better than the best of the individual figures for different links of

the chain.

As a result of Rack #1 Redundancy, Reliability over one year would be approximately

99.7%, compared to 94.6% availability with a Standalone Rack #1 (i.e. the probability for

Redundant Rack #1 System to encounter one failure during one year would have been

reduced from 5.4% to 0.3%).

System MTBF would increase from approximately 157,000 hours (approximately 18 years)

to 235,000 hours (approximately 27 years).

Regarding System Availability, with a 2 hour Mean Time To Repair we would receive a 9-

nines resulting Availability, close to 100%

Page 92: Document1

Calculation Examples

92

Consider a common misuse of reliability figures:

� Last architecture examination (Distributed Architecture with a Redundant CPU

Rack) has proven a real benefit in implementing a CPU Rack redundancy, with

this architecture a sub-sytem would be elevated to a 99.9 % Reliability, and

almost a 100% Availability.

� The common misuse of this Reliability figure would be to make arguments for the

potential benefit on Reliability and Availability for the whole resulting system.

Note: This example has considered the Sub-System Failure Rate provided by the

reliability Software.

Regarding the Serial System built by the Redundant CPU Racks and the STB Islands,

the worksheet above shows a resulting Reliability (over one year) of 84,06%, the

Standalone System Reliability during the same period of time being 81.95%.

In addition, the worksheet shows a resulting Availability (for a 2 hour MTTR) of

99.96%, the Standalone System Availability (for a 2 hour MTTR) being 99.9957%.

As a result, this data suggests that implementing a CPU Rack Redundancy would

have almost no benefit.

Of course, this is an incorrect conclusion, and the example should suggest a simple

rule: always compare comparable items. If we implement a redundancy on the CPU

Control Rack in order to increase process control core Reliability, and to an extent

Availability, we need to then examine and compare the figures only at this level, as

the entire system has not received an increase in redundancy.

Page 93: Document1

Calculation Examples

93

Recommendations for Utilizing Figures

Previous case studies provide several important items concerning Reliability metrics

evaluation:

• Provided elementary MTBF figures are available, a "serial" system is quite easy

to evaluate, thanks to the "magic bullet" formula: λ = 1 / MTBF

• If you consider a "parallel sub-system", System Reliability can be easily derived

from the Sub-System Reliability. Thus System Availability can be almost as easily

calculated, starting from the Sub-System Reliability. But the "magic bullet"

formula no longer applies, as in those conditions, exponential law does not

directly link Reliability to Failure Rate. However, System MTBF can be

approximated from the Sub-System MTBF :

"System MTBF (in hours) # 1.5 Sub-System MTBF"

But no direct relationship will provide the System Failure Rate.

Because these calculations must be precisely executed, the acquisition of

commercial reliability software could be one solution. Another consideration

would be the solicitation of an external service.