115/12/10 FV
Common DCS hardware
VF 2
General ideas• Centralized system:
o Common computers. Detector dedicated computers (with detector participation) only in case of un-proportionally heavy load
o Common infrastructureo The boundary of responsibility between a detector and
the DCS teams is an “intelligent unit”: a power supply, ELMB, etc..
• Use “off the shelf” solutions:o ELMBs for analogues measurement o PLCs for digital I/Oo CAEN and ISEG HV power supplieso WIENER electronics crates and LV power supplies
• High availability and reliabilityo Industrial equipment, redundancy and spare parts easy
accesso UPS for PCs and analog measurements (lifetime at least
½ hour)
10/09/10
VF 3
Layout
15/12/10
VF 4
Computers - 1• Two levels computer structure
o High computer power supervision stationo Many slots front-end computers
• Supervision PCo Location: PC farm room was chosen because of
availability of the network in case of a power cut (alternative place was the CCC farm area)
o Model: we will try to follow the PC farm team choice• Common maintenance contract• Spare parts • Eventual reinforcement with a redundant power supply and
hard disk
15/12/10
VF 5
Computers - 2• Front-end PCs: KISS 4U PCI-760
o The model is extensively used by BE/CO in the accelerator control
o The PCs are covered by BE/CO maintenance and support contact with KONTRON
o Main PC parameters:• Processor: Core 2 Duo E6400• Backplane
1 PCI_e x16 4 PCI_e x 1 7 PCI 32 Bit
• Memory: 4GB DDR2• Redundant HD: STOR-1 2x500GB • PSU: Redundant 2x 300W
o Two units are purchased and under evaluation
15/12/10
VF 6
Front-end PCs : KISS 4U PCI-760
15/12/10
Redundant STOR-1 2x500GB HDD
Redundant power supply 2x 300W AC
VF 7
Infrastructure: CAN buses• ELMBs
o PC interface: Kvaser PCIcan 4xHS card (4 procured)o CERN CAN power supply (procured):
• 2 crates (8 modules per crate) • 10 modules + 8 rear panels (2 channels per module)• this cover up to 16 lines
• WIENER crates and power supplieso PC interface: Kvaser PCIcan card
• ISEG HV power supplieso PC interface: Peak PCAN-PCI Two Channel card
• Cables: o thick cables down to the areao thin cables dispatched to the sub-detectors
15/12/10
VF 815/12/10
Infrastructure: Ethernet (Alberto)
Alberto: “slow control Ethernet devices can be connected to the same switches as the other devices: my plan is to isolate them in a dedicated vlan”.