Report No: 1501-02-IRTS
Inspected by Pyae Phyo Hein Page 10 / 28
INFRARED THERMAL SCAN REPORT
Reference Image No.
01
Circuit Information Circuit No: Overview Type of component: Cable Termination
Current Loading R / L1 Y / L2 B / L3 N
- - - 3.3
Reference Temperature Fault Temperature Temperature Difference
47.3oC 57.3oC 10oC
Ambient Temperature 30oC Temperature
Category 3
ANALYSIS OF THERMOGRAM
Possible Thermal Anomaly on the neutral cable termination of BI connector. Possible cause is caused by poor contact on this termination.
RECOMMENDATIONS
Forward this thermal graphic report to LEW in-charge for necessary corrective measure. Recommend to carry out infrared thermal scan upon the completion of corrective action.
General Information Customer : Facebook Date of Inspection : 13 Jan 2015
Location : Corridor level 14 Name of Switchboard / Equipment
: DB - 2
Thermogram 13.01.2015 Photo
Sp2
Sp1
26.9
80.7 °C
40
60
80
Sp1 Temperature 57.3 °C
Sp2 Temperature 47.3 °C
Report No: 1501-02-IRTS
Inspected by Pyae Phyo Hein Page 11 / 28
INFRARED THERMAL SCAN REPORT
Reference Image No.
02
Circuit Information Circuit No: - Type of component: 125A Fuses
Current Loading R / L1 Y / L2 B / L3 N
- - - -
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : Facebook Date of Inspection : 13 Jan 2015
Location : Store Room level 14 Name of Switchboard / Equipment
: SB-14
Thermogram 13.01.2015 Photo
Sp2 Sp3Sp1
25.4
53.2 °C
30
40
50
Sp1 Temperature 30.5 °C
Sp2 Temperature 29.1 °C
Sp3 Temperature 28.3 °C
Report No: 1501-02-IRTS
Inspected by Pyae Phyo Hein Page 12 / 28
INFRARED THERMAL SCAN REPORT
Reference Image No.
03
Circuit Information Circuit No: Main Switch Type of component: 125A TPN MCCB
Current Loading R / L1 Y / L2 B / L3 N
31.4A 22.4A 21.8A 14.3A
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : Facebook Date of Inspection : 13 Jan 2015
Location : Store Room level 14 Name of Switchboard / Equipment
: SB-14
Thermogram 13.01.2015 Photo
Sp2Sp4
Sp3Sp1
24.2
56.1 °C
30
40
50
Sp1 Temperature 33.3 °C
Sp2 Temperature 33.0 °C
Sp3 Temperature 31.3 °C
Sp4 Temperature 28.7 °C
Report No: 1501-02-IRTS
Inspected by Pyae Phyo Hein Page 13 / 28
INFRARED THERMAL SCAN REPORT
Reference Image No.
04
Circuit Information Circuit No: Overview Type of component: OUTPUT MCB
Current Loading R / L1 Y / L2 B / L3 N
- - - -
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : Facebook Date of Inspection : 13 Jan 2015
Location : Store Room level 14 Name of Switchboard / Equipment
: SB-14
Thermogram 18.06.2014 Photo
Sp2
Sp3Sp1
26.0
38.4 °C
30
35
Sp1 Temperature 29.2 °C
Sp2 Temperature 30.1 °C
Sp3 Temperature 27.6 °C
Report No: 1501-02-IRTS
Inspected by Pyae Phyo Hein Page 14 / 28
INFRARED THERMAL SCAN REPORT
Reference Image No.
05
Circuit Information Circuit No: Overview Type of component: OUTPUT MCB
Current Loading R / L1 Y / L2 B / L3 N
1.4A 3.2A 1.1A 2.6A
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : Facebook Date of Inspection : 13 Jan 2015
Location : Store Room level 14 Name of Switchboard / Equipment
: EDB-14
Thermogram 13.01.2015 Photo
Sp2
Sp1
23.7
45.1 °C
30
40
Sp1 Temperature 26.1 °C
Sp2 Temperature 25.6 °C
Report No: 1501-02-IRTS
Inspected by Pyae Phyo Hein Page 15 / 28
INFRARED THERMAL SCAN REPORT
Reference Image No.
06
Circuit Information Circuit No: Main Incoming MCCB Type of component: 63A TPN MCCB
Current Loading R / L1 Y / L2 B / L3 N
7.3A 8.8A 2.0A 8.7A
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : Facebook Date of Inspection : 13 Jan 2015
Location : Corridor level 14 Name of Switchboard / Equipment
: DB-1
Thermogram 13.01.2015 Photo
Sp2
Sp1
25.4
52.5 °C
30
40
50
Sp1 Temperature 27.6 °C
Sp2 Temperature 28.0 °C
Report No: 1501-02-IRTS
Inspected by Pyae Phyo Hein Page 16 / 28
INFRARED THERMAL SCAN REPORT
Reference Image No.
07
Circuit Information Circuit No: Main Incoming MCCB Type of component: 63A TPN MCCB
Current Loading R / L1 Y / L2 B / L3 N
5.6A 12.3A 7.1A 8.8A
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : Facebook Date of Inspection : 13 Jan 2015
Location : Corridor level 14 Name of Switchboard / Equipment
: DB - 2
Thermogram 13.01.2015 Photo
Sp2
Sp1
27.1
57.0 °C
30
40
50
Sp1 Temperature 29.9 °C
Sp2 Temperature 29.3 °C
Report No: 1501-02-IRTS
Inspected by Pyae Phyo Hein Page 17 / 28
INFRARED THERMAL SCAN REPORT
Reference Image No.
08
Circuit Information Circuit No: Main Incoming MCB Type of component: 63A TPN MCB
Current Loading R / L1 Y / L2 B / L3 N
8.6A 5.5A 5.4A 5.7A
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : Facebook Date of Inspection : 13 Jan 2015
Location : Server Room level 14 Name of Switchboard / Equipment
: DB - 3
Thermogram 13.01.2015 Photo
Sp2
Sp1
23.7
42.3 °C
25
30
35
40
Sp1 Temperature 25.1 °C
Sp2 Temperature 25.2 °C
Report No: 1501-02-IRTS
Inspected by Pyae Phyo Hein Page 18 / 28
INFRARED THERMAL SCAN REPORT
Reference Image No.
09
Circuit Information Circuit No: Main Breaker Type of component: 40A TPN MCB
Current Loading R / L1 Y / L2 B / L3 N
6.7A 10.8A 4.4A 6.2A
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : Facebook Date of Inspection : 13 Jan 2015
Location : Office Area level 13 Name of Switchboard / Equipment
: DB-L
Thermogram 13.01.2015 Photo
Sp2
Sp1
28.0
47.5 °C
30
35
40
45
Sp1 Temperature 31.3 °C
Sp2 Temperature 33.0 °C
Report No: 1501-02-IRTS
Inspected by Pyae Phyo Hein Page 19 / 28
INFRARED THERMAL SCAN REPORT
Reference Image No.
10
Circuit Information Circuit No: Outgoing Breakers Type of component: OUTPUT MCB
Current Loading R / L1 Y / L2 B / L3 N
- - - -
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : Facebook Date of Inspection : 13 Jan 2015
Location : Office Area level 13 Name of Switchboard / Equipment
: DB-L
Thermogram 13.01.2015 Photo
Sp2
Sp1
27.6
45.7 °C
30
35
40
45
Sp1 Temperature 30.5 °C
Sp2 Temperature 29.7 °C
Report No: 1501-02-IRTS
Inspected by Pyae Phyo Hein Page 20 / 28
INFRARED THERMAL SCAN REPORT
Reference Image No.
11
Circuit Information Circuit No: Main Breaker Type of component: 40A TPN MCB
Current Loading R / L1 Y / L2 B / L3 N
11.8A 9.3A 7.8A 11.5A
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : Facebook Date of Inspection : 13 Jan 2015
Location : Office Area level 13 Name of Switchboard / Equipment
: DB-P
Thermogram 13.01.2015 Photo
Sp2
Sp1
28.1
49.5 °C
30
40
Sp1 Temperature 32.1 °C
Sp2 Temperature 32.7 °C
Report No: 1501-02-IRTS
Inspected by Pyae Phyo Hein Page 21 / 28
INFRARED THERMAL SCAN REPORT
Reference Image No.
12
Circuit Information Circuit No: Outgoing Breakers Type of component: OUTPUT MCB
Current Loading R / L1 Y / L2 B / L3 N
- - - -
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : Facebook Date of Inspection : 13 Jan 2015
Location : Office Area level 13 Name of Switchboard / Equipment
: DB-P
Thermogram 13.01.2015 Photo
Sp2
Sp1
27.7
52.2 °C
30
40
50
Sp1 Temperature 29.5 °C
Sp2 Temperature 28.8 °C
Report No: 1501-02-IRTS
Inspected by Pyae Phyo Hein Page 22 / 28
INFRARED THERMAL SCAN REPORT
Reference Image No.
13
Circuit Information Circuit No: Main Incoming Breaker Type of component: 100A TPN MCCB
Current Loading R / L1 Y / L2 B / L3 N
- - - -
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : Facebook Date of Inspection : 13 Jan 2015
Location : Store Room level 13 Name of Switchboard / Equipment
: MSB
Thermogram 18.06.2014 Photo
Sp2
Sp1 22.2
36.5 °C
25
30
35
Sp1 Temperature 28.1 °C
Sp2 Temperature 27.9 °C
Report No: 1501-02-IRTS
Inspected by Pyae Phyo Hein Page 23 / 28
INFRARED THERMAL SCAN REPORT
Reference Image No.
14
Circuit Information Circuit No: Main Outgoing Breaker Type of component: 100A TPN MCCB
Current Loading R / L1 Y / L2 B / L3 N
19.2A 19.1A 14.8A 14.9A
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : Facebook Date of Inspection : 13 Jan 2015
Location : Store Room level 13 Name of Switchboard / Equipment
: MSB
Thermogram 13.01.2015 Photo
Sp2
Sp1
23.8
46.1 °C
30
40
Sp1 Temperature 28.3 °C
Sp2 Temperature 28.1 °C
Report No: 1501-02-IRTS
Inspected by Pyae Phyo Hein Page 24 / 28
INFRARED THERMAL SCAN REPORT
Reference Image No.
15
Circuit Information Circuit No: Outgoing Breakers Type of component: OUTPUT MCBs
Current Loading R / L1 Y / L2 B / L3 N
- - - -
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : Facebook Date of Inspection : 13 Jan 2015
Location : Store Room level 13 Name of Switchboard / Equipment
: MSB
Thermogram 13.01.2015 Photo
Sp2Sp4
Sp3 Sp1
24.7
50.2 °C
30
40
50
Sp1 Temperature 29.2 °C
Sp2 Temperature 27.7 °C
Sp3 Temperature 28.6 °C
Sp4 Temperature 27.1 °C
Report No: 1501-02-IRTS
Inspected by Pyae Phyo Hein Page 25 / 28
INFRARED THERMAL SCAN REPORT
Reference Image No.
16
Circuit Information Circuit No: Main Breaker Type of component: 63A TPN MCCB
Current Loading R / L1 Y / L2 B / L3 N
0.6A 5.6A 0A 5.3A
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : Facebook Date of Inspection : 13 Jan 2015
Location : Store Room level 13 Name of Switchboard / Equipment
: DB A/C
Thermogram 13.01.2015 Photo
Sp2
Sp1
23.8
28.4 °C
24
26
28
Sp1 Temperature 25.5 °C
Sp2 Temperature 25.6 °C
Report No: 1501-02-IRTS
Inspected by Pyae Phyo Hein Page 26 / 28
INFRARED THERMAL SCAN REPORT
Reference Image No.
17
Circuit Information Circuit No: Outgoing Breakers Type of component: OUTPUT MCBs
Current Loading R / L1 Y / L2 B / L3 N
- - - -
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : Facebook Date of Inspection : 13 Jan 2015
Location : Store Room level 13 Name of Switchboard / Equipment
: 13 Jan 2015
Thermogram 13.01.2015 Photo
Sp2
Sp1
22.5
43.1 °C
30
40
Sp1 Temperature 25.7 °C
Sp2 Temperature 25.1 °C
Report No: 1501-02-IRTS
Inspected by Pyae Phyo Hein Page 27 / 28
INFRARED THERMAL SCAN REPORT
Reference Image No.
18
Circuit Information Circuit No: Overview Type of component: 32A TPN MCB
Current Loading R / L1 Y / L2 B / L3 N
0.9A 3.1A 0.3A 2.1A
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : Facebook Date of Inspection : 13 Jan 2015
Location : Store Room level 13 Name of Switchboard / Equipment
: EDB - 13
Thermogram 13.01.2015 Photo
Sp2
Sp1
22.5
40.8 °C
25
30
35
40
Sp1 Temperature 24.9 °C
Sp2 Temperature 25.1 °C
Report No: 1501-02-IRTS
Inspected by Pyae Phyo Hein Page 28 / 28
INFRARED THERMAL SCAN REPORT
Reference Image No.
19
Circuit Information Circuit No: Main Incoming MCB Type of component: 63A DP MCB
Current Loading R / L1 Y / L2 B / L3 N
15A - - 10.3A
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : Facebook Date of Inspection : 13 Jan 2015
Location : Store Room level 13 Name of Switchboard / Equipment
: DB-13
Thermogram 13.01.2015 Photo
Sp2
Sp1
23.8
51.3 °C
30
40
50
Sp1 Temperature 27.7 °C
Sp2 Temperature 28.5 °C