FIRE-TIGHT SEALING FOR CABLE TRANSIT IN BULKHEAD AND DECK OF SHIPSIMO RESOLUTION MSC.307(88)-2010 FTP Code
PLASEAL NF-23 MANUAL
NITTO CHEMICAL INDUSTRY CO.,LTD.
MARCH-2014
Approved class certificate
CLASSIFICATION SOCIETY A-0 A-60 CERTIFICATE No. VALIDITY DATE
JG ○ ○ F-489F-4902017.2.122017.11.7
NK ○ ○ 12EQ375FPA(AL) 2016.10.31
ABS ○ ○ 11-YO815070-PDA 2016.12.19
MED ○ ○Module B
Module D
1
26541/A2 EC
SMS.MED.D/34/B.0 2018.2.17
2016.12.13
NITTO CHEMICAL INDUSTRY CO.,LTD.
Condition of construction (A-0 class)RECTANGULAR COAMING CIRCULAR COAMING
BULKHEAD DECK BULKHEAD DECK
Maximum size 300㎜×800㎜ Φ204.7㎜
Minimum size 50㎜×100㎜ Φ35.7㎜
The total cross-sectional area of the cables 39.2% 39.3%
Minimum length of coaming 100㎜ 100㎜
Maximum measurement of the outside diameter of a cable 73.0㎜ 56.4㎜
Contact between the cables ○ ○
Contact between a cable and coaming × ×
Insulation No need No need
NITTO CHEMICAL INDUSTRY CO.,LTD.
Condition of construction (A-15/A-30/A-60 class)RECTANGULAR COAMING CIRCULAR COAMING
BULKHEAD DECK BULKHEAD DECK
Maximum size 300㎜×800㎜ Φ204.7㎜
Minimum size 100㎜×160㎜ 100㎜×150㎜ Φ35.7㎜
The total cross-sectional area of the cables 39.2%* 39.3%
Minimum length of coaming 100㎜ 100㎜
Maximum measurement of the outside diameter of a cable 73.0㎜ 56.4㎜
Contact between the cables ○ ○
Contact between a cable and coaming × ×
Insulation Partially insulation Fully insulation
* Less than 175mm×225mm (BULKHEAD) : The total cross-sectional area of the cables is 31.2%2
NITTO CHEMICAL INDUSTRY CO.,LTD.
Construction drawing of cable transit(A-0 class, Rectangular coaming)
BULKHEAD(50㎜×100㎜〜300㎜×800㎜)
DECK(50㎜×100㎜〜300㎜×800㎜)
NITTO CHEMICAL INDUSTRY CO.,LTD.
BULKHEAD(Φ35.7㎜〜Φ204.7㎜)
DECK(Φ35.7㎜〜Φ204.7㎜)
3
Construction drawing of cable transit(A-0 class, Circular coaming)
NITTO CHEMICAL INDUSTRY CO.,LTD.
BULKHEAD(100㎜×160㎜〜300㎜×800㎜)
Construction drawing of cable transit(A-15/A-30/A-60 class, Rectangular coaming)
NITTO CHEMICAL INDUSTRY CO.,LTD.
DECK(100㎜×150㎜〜300㎜×800㎜)
BULKHEAD(Φ35.7㎜〜Φ204.7㎜)
DECK(Φ35.7㎜〜Φ204.7㎜)
Construction drawing of cable transit(A-15/A-30/A-60 class, Circular coaming)
NITTO CHEMICAL INDUSTRY CO.,LTD.
4
Please clean the surface where PLASEAL NF-23 will be constructed, and be free of water and dust.
NITTO CHEMICAL INDUSTRY CO.,LTD.
Application Procedure①
Please construct NF-23 so that any cables do not touch rectangular / circular coaming.
If a cable needs to be spaced from any other cables or rectangular /circular coaming, spacer can be used to make space.
Metal parts can be used at the deck division for ease in construction.
5
NITTO CHEMICAL INDUSTRY CO.,LTD.
Application Procedure②
Please construct NF-23 without any space, especially at the surrounding of any cables.( For example, a stick or suitable instrument can be used in order not to make any space. )
Fill with PLASEAL NF-23 up to the edge of rectangular / circular coaming and cover the surface of edge with it.
Total area of several bundled cables should be as follows or less.For rectangular coaming approx.105㎜×365㎜ ( height×width )For circular coaming approx.105㎜×110㎜ ( height×width )
NITTO CHEMICAL INDUSTRY CO.,LTD.
Application Procedure③
Notes・Since PLASEAL NF-23 is a dry-hardening type putty (fire-resistant putty),
it should start hardening from the applied surface. Please make sure that it might take several months for fully hardening based on applied thickness, temperature and humidity.It should still have high fire-resistant performance even though the applied putty hasn’t fully hardened yet.(When you apply 100㎜ of PLASEAL NF-23 to φ130 at an ambient temperature of 20 degrees C / humidity of 65%, it takes about a month for hardening of 10㎜ from the applied surface, and about 4 months for fully hardening.)
・The warranty period for PLASEAL NF-23 is 6 months after production, and is valid if products remain sealed and are stored at room temperature avoiding direct sunlight.
・Avoid using PLASEAL NF-23 outdoors and in a place where water splashes directly.
・It is recommended to use some waterproof sealing materials or coating materials like NAICOAT SB-61(waterproof type ; Nitto chemical Industry co.,ltd. ) at high humidity area in order to cover the surface of PLASEAL NF-23 from moisture. (If it is exposed under high humidity for a long time, this might cause dripping and seeping from the surface.)
NITTO CHEMICAL INDUSTRY CO.,LTD.