40
EUROVENT CERTITA CERTIFICATION OM-5-2015 Issued January 2015 OPERATIONAL MANUAL for the CERTIFICATION of AIR HANDLING UNITS

1422285511_2014-10_OM-5-2015_AHU

Embed Size (px)

DESCRIPTION

1422285511_2014-10_OM-5-2015_AHU

Citation preview

Page 1: 1422285511_2014-10_OM-5-2015_AHU

EUROVENT CERTITA CERTIFICATION

OM-5-2015 Issued January 2015

OPERATIONAL MANUAL for the

CERTIFICATION of

AIR HANDLING UNITS

Page 2: 1422285511_2014-10_OM-5-2015_AHU

This document is strictly reserved for use in the Eurovent Certification Programmes.

Reproduction or translation of any part of the document is forbidden without written permission from Eurovent Certita Certification.

Published by Eurovent Certita Certification 48-50 rue de la Victoire 75009 Paris, FRANCE

Tel: + 33 1 75 44 71 71

E-mail: [email protected]

OM-5-2015 Issued January 2015

Page 2 of 40

OM-5-2015 Issued January 2015

Supersedes OM-5-2014 Editing (date): Anthony BAILLAU (September 2014) Checking (date): Jean FOURCROY (December 2014) Approval (date): Compliance Committee for AHU (10 October 2014) Approval (date) CPPC (6 January 2015) Comes into effect from: 16 January 2015

Modifications as against last version: No. Modifications Section Page

1 Pre-application procedure is removed. The process is now included in the qualifying procedure III.1 - IV.2 5 - 6

2

Any major non-conformity identified during an on-site checking shall be solved within 30 days after the factory audit (or within the deadline defined by the auditor during the audit). Non resolution of a major non-conformity after this deadline can lead to an immediate temporary suspension until the non-compliance is solved

IV.16 14

3 For brandname participants, the city (ies) and country (ies) of the production site(s) of the OEM(s) shall be displayed on ECC website next to the units of the brand name participant and on its certificate.

IV.15 13

4 This check only occurs if there is no RU selection during the audit. IV.5a 8

5 Delete “failure” for Model Box tests IV.13d 13

6 Addition of a paragraph “Naming of non-certified range”, stating that the range name of non certified range has to be significantly different from the certified range.

IV.11 11

7 Procedure for Brand Name companies IV.2b 7

8 Real Units shall be delivered between 4 weeks and 6 weeks before the scheduled test date IV.9 10

9

Software shall be able to store and restore the selection details from the same software version without any alterations of the calculation. Should the certified performances change due to the software revision, it shall not be possible to get the printout of the project without a new calculation taking into account the performances revision

APPENDIX A 16

10 Mandatory Model Box specifications on the printouts APPENDIX A 16

11 Inlet, outlet and airborn power: octave bands in dB and total sound power in dB(A). APPENDIX A 16

12 “Class <E” has been replaced by “class E” as the class <E doesn’t exist anymore. V.2b 15

13 Mandatory information to be found on printouts: Unique identification No or reference of the selection, Fan system effect,

APPENDIX A 16

14 Update of the forms APPENDIX D 24

Page 3: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 3 of 40

TABLE OF CONTENTS

I. PURPOSE___________________________________________________________ 5

II. SCOPE _____________________________________________________________ 5

III. BASIC OUTLINE OF THE PROGRAMME __________________________________ 5 III.1 Qualifying procedure ................................................................................................................. 5 III.2 Repetition procedure ................................................................................................................. 5 III.3 Failure treatment ....................................................................................................................... 6

IV. OPERATION OF THE PROGRAMME _____________________________________ 6 IV.1 Declaration of data .................................................................................................................... 6

a. Rated performance data ........................................................................................................................ 6 b. Certification forms .................................................................................................................................. 6 c. Modifications to the range ..................................................................................................................... 6

IV.2 Application procedure ............................................................................................................... 6 a. General procedure ................................................................................................................................. 6 b. Procedure for Brand Name companies ................................................................................................. 7

IV.3 Software .................................................................................................................................... 7 IV.4 Factory visits ............................................................................................................................. 7 IV.5 Consistency check of heat recovery ......................................................................................... 8

a. Manufacturer uses Eurovent certified heat recovery systems (HRS) .................................................... 8 b. Manufacturer does not use Eurovent certified HRS............................................................................... 9 c. For certified and non-certified rotors ...................................................................................................... 9

IV.6 Qualifying campaign .................................................................................................................. 9 IV.7 Repetition campaign ...............................................................................................................10 IV.8 Ranges to be taken out of production .....................................................................................10 IV.9 Selection of units for tests .......................................................................................................10 IV.10 Ranges produced in several production places ......................................................................11 IV.11 Naming non-certified ranges ...................................................................................................11 IV.12 Procedures at the laboratory ...................................................................................................11

a. General ................................................................................................................................................ 11 b. Test conditions .................................................................................................................................... 11 c. Test report and tests results ................................................................................................................ 12

IV.13 Failure treatment .....................................................................................................................12 a. Component failure ............................................................................................................................... 12 b. Unit failure on a real unit ...................................................................................................................... 12 c. No class reached during RU tests ....................................................................................................... 12 d. Test results on a Model Box ................................................................................................................ 13 e. Failure in case of multiple production places ....................................................................................... 13 f. Irregularities in production places ........................................................................................................ 13

IV.14 Special complaint procedure ...................................................................................................13 IV.15 Brand Name ............................................................................................................................13 IV.16 Non-respect of procedures .....................................................................................................14

V. PROMOTION OF THE PROGRAMME ____________________________________ 14 V.1 By Eurovent Certita Certification .............................................................................................14 V.2 By the Participant ....................................................................................................................14

a. On printouts ......................................................................................................................................... 14 b. On units ............................................................................................................................................... 15

APPENDIX A. SELECTION SOFTWARE MANDATORY REQUIREMENTS _________ 16

APPENDIX B. EUROVENT CERTIFIED PERFORMANCE MARK AND ENERGY EFFICIENCY LABEL ______________________________________________________ 19

B.I. Eurovent Certified Performance mark .....................................................................................19 B.II. Eurovent Certified Performance energy efficiency label .........................................................20

Page 4: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 4 of 40

B.II.1. For units (eventually on printouts) ....................................................................................................... 20 B.II.2. For printouts ........................................................................................................................................ 20

APPENDIX C. CERTIFICATION SCHEDULE _________________________________ 21 C.I. Application and test schedule .................................................................................................21 C.II. Checking of software schedule ...............................................................................................23

APPENDIX D. FORMS ___________________________________________________ 24 D.I. Submittal for certification by Manufacturer..............................................................................24

D.I.1. Form AHU-1A: Data list of certified models & sizes............................................................................. 24 D.I.2. Form AHU-1B: Data list of certified model boxes, or casing constructions .......................................... 24

D.II. Submittal for certification by Brand Name...............................................................................24 D.II.1. Form AHU-2A: Data list of certified models & sizes (BN) ............................................................... 24 D.II.2. Form AHU-2B: Data list of certified model boxes, or casing constructions (BN) ............................. 24

D.III. Technical forms .......................................................................................................................25 D.III.1. Form AHU-3A: Technical specification related to tested real unit .............................................. 25 D.III.2. Form AHU-3B: Technical specifications related to tested model box ......................................... 29

D.IV. Test result forms .....................................................................................................................30 D.IV.1. Form AHU-4A: Recalculation after Real Unit Test ..................................................................... 30 D.IV.2. Form AHU-4C: Software Update Record Sheet ......................................................................... 32

APPENDIX E. MAJOR / MINOR NON COMPLIANCES _________________________ 33 E.I. Handling of several ranges .....................................................................................................33 E.II. Major Non-Compliances (2 Points) .........................................................................................35 E.III. Minor Non-Compliances (0 Points) .........................................................................................38

APPENDIX F. CONSTRUCTION VARIATIONS OF AHU MODEL BOXES __________ 39 F.I. Corner post (corner and frame) ..............................................................................................39 F.II. Mullion .....................................................................................................................................39 F.III. Filter construction ....................................................................................................................40 F.IV. Panel shape ............................................................................................................................40

Page 5: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 5 of 40

I. PURPOSE

The purpose of this manual is to prescribe procedures for the operation of the Eurovent Certified Performance Programme for Air Handling Units, in accordance with the Eurovent Certified Performance Certification Manual.

II. SCOPE

This programme applies to selected ranges of Air Handling Units. Each range shall at least present one size with a rated air volume flow below 7 m3/s. All Real Unit sizes in the range up to the maximum stated air flow shall be declared. All Model Box configurations shall be declared.

Ranges without at least one size with a rated air volume flow below 7 m3/s (25 000 m3/h) are excluded.

III. BASIC OUTLINE OF THE PROGRAMME

III.1 Qualifying procedure

After the licence agreement is signed between the company and Eurovent Certita Certification, the qualifying procedure shall be completed.

The company shall first submit to Eurovent Certita Certification name of the range and complete list of names and versions of the corresponding selection tools (selection softwares) for verification by an auditor appointed by Eurovent Certita Certification. If the software fulfils all preliminary requirements, the company shall submit to Eurovent Certita Certification the complete list of factories where the range is produced for verification by an auditor appointed by Eurovent Certita Certification. If the software and the factory fulfil all the preliminary requirements, the applicant shall submit to Eurovent Certita Certification the declaration list with all Real Unit (RU) sizes and Model Box (MB) configurations with all the required characteristics and performance data as required by the Rating Standard, RS 6/C/005.

The following number of units per factory producing the range (except the case of “sister factories”, see IV.10) are then required for test in an independent laboratory selected by Eurovent Certita Certification:

The minimum number of Model Boxes to cover all worst configurations of the mechanical, thermal and acoustical performance. If several ranges use the same construction, the corresponding unit will be tested only once.

One complete Air Handing Unit, being one size from the range, for all performance. The Real Unit is selected during the factory visit by the auditor appointed by Eurovent Certita Certification.

For units above the stated air flow rate of 7 m3/s, the software shall be checked for consistency. If the tests show conformity with the relevant Rating Standard and consistency is verified, certification is granted until next annual on-site checking of software.

III.2 Repetition procedure

For mechanical, thermal and acoustical testing, Model Boxes shall be tested every six years for ISO-certified factories, every three years otherwise. For performance testing, a Real Unit from recent regular production shall be tested, every three years for ISO 9001 certified factories, every year otherwise. If several factories produce exactly the same range with the same components, suppliers and methods, one unit is sufficient instead of one per factory. In addition, annual onsite checking of software shall be carried out every year. When the repetition procedure is passed certification is renewed for another campaign.

Page 6: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 6 of 40

III.3 Failure treatment

When a unit fails to comply with the requirements of the relevant Rating Standard, failure treatment shall be applied.

IV. OPERATION OF THE PROGRAMME

IV.1 Declaration of data

Each manufacturer shall nominate one contact person who will deal with all certification matters, plus eventually one by factory.

a. Rated performance data

All characteristics shall be expressed in SI Units.

b. Certification forms

Submittal of certification of models shall be completed and sent to Eurovent Certita Certification as .xlsx files. Copies of these forms are part of this manual (see APPENDIX D).

Original Equipment Manufacturer (OEM): Form AHU-1A for Real Units and Form AHU-1B for Model Boxes will be used.

Brand Name: For models submitted by a company presenting on the market units, under its own brand, manufactured by a certified company, forms AHU-2A and AHU-2B will be used to identify the corresponding model number of the OEM.

Technical forms: For models selected for test, Forms AHU-3A and AHU-3B have to be completed with technical description of all components along with characteristics and performance data.

Evaluation of test result: For models tested, Forms AHU-4A is added to the test report and AHU-4B is sent by Eurovent Certita Certification, showing the deviations between claimed and measured data.

c. Modifications to the range

The Participant shall inform Eurovent Certita Certification and the auditor of any modification to the range and/or software, using Form AHU-4C. A new software version without impact on performance does not have to be sent. If new components (fans, coils etc) are implemented in standard production, manufacturer shall inform Eurovent Certita Certification and provide new software to the auditor. For next test new components shall be selected.

Non compliance is considered as a non-respect of procedures (see IV.16).

Anytime, Eurovent Certita Certification has the right to perform extra checking of software. Eurovent Certita Certification decides whether the modification is significant for the certified performance data or not. In the case of significant modifications Eurovent Certita Certification is entitled to demand adequate tests to verify the influence on performance data. This test shall not be considered as a repetition one.

IV.2 Application procedure

a. General procedure

During the application procedure, the auditor appointed by Eurovent Certita Certification shall first verify that the software fulfils minimum requirements (no certification shall be accepted without appropriate selection software). If yes, he shall visit the factory, verify that AHUs are really manufactured there and selected with the software, and send a report of his visit to

Page 7: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 7 of 40

Eurovent Certita Certification. If the report shows that rules are not followed the Licence Agreement shall not be signed.

b. Procedure for Brand Name companies

When a company applies as a Brand Name of an already certified company, the application procedure shall consist in a pre-check of the selection software.

The software shall be a version not already used by the Brand Name manufacturer, but already including the Eurovent Certified Performance mark. The pre-check shall include at least two comparisons between selections made with the OEM’s software and the Brand Name company’s software.

If the technical requirements are fulfilled and the comparisons shows no differences between the calculation results, the applicant can be certified.

Once the certification is granted, a visit of the applicant’s office shall be carried out no later than 3 months after the delivery of the certificate.

IV.3 Software

An English version of the software selection is necessary. Each quotation of a certified AHU shall include the date/code/number of the software version used for the selection of the unit. From the version code-key it shall be possible to check what the latest technical software version is by splitting up the code in more characters. An example of a suitable code is given below:

Version: XY / Z

characters indicating a version serial number, not affecting the selection results characters to indicate the technical version serial number

The participant is obliged to send the most recent technical software version to Eurovent Certita Certification.

The selection software shall be operative as an entity with all unit components integrated in one software. Components in an AHU that are selected with different software or any other means of selection cannot be certified. The units of the applied range shall be built with components specified in the selection software. If some components not present in the certified software performing a certified performance item (see VI.2 of RS 6/C/005) are included in the technical specification of a particular order, the following statement shall be provided in the quotation: “This component is not included in the software Eurovent certified”. This statement is not required for components serving for non-certified performance items (see list on VI.2 of RS 6/C/005).

At least four sections must be included: fan, filter, heating and cooling. When a heat recovery section is available, it shall be declared and included in the selected unit for test for certification.

Consistency of the software shall be verified by the auditor appointed by Eurovent Certita Certification. In case inconsistency of the software is observed, failure treatment shall be applied.

Anytime, Eurovent Certita Certification has the right to collect data directly from customer and perform extra checking of software.

IV.4 Factory visits

Before each visit the auditor appointed by Eurovent Certita Certification shall collect and study the construction details and claimed performance of the relevant AHU range in order to make a proper selection of suitable unit(s) for testing.

Page 8: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 8 of 40

Anytime, Eurovent Certita Certification has the right to ask an auditor to conduct a surprise visit to participants’ factory as well as to collect data directly from customer and perform extra checking of software.

During selection visits, a factory tour shall be made by the auditor, accompanied by manufacturer’s technical expert. A random selection of at least one unit under construction or just built, shall be made. The selected unit shall be suitable for testing. If no unit suitable for testing is under construction or just built, a random selection from files of recently delivered units shall be made.

The entire composition and technical specifications of the selected units shall then be checked onsite. Manufacturer’s technical expert shall fully inform the auditor by submitting all relevant assembly drawings, specifications and technical data sheets of the selected units. Agreement shall be reached between manufacturer and the auditor on final selection of Real Unit for testing.

During annual on-site checking of software, the same procedure shall be applied, without selection of unit for testing so without the restrictions for measuring facilities. This implies that any size may be selected.

The expected performance shall be recalculated based on components reselected with the software provided to Eurovent Certita Certification. The composition and technical specifications and performance from recalculation shall be the same as the one specified and announced to the customer. If in the meantime the Participant has officially launched a new software version and recalculation is made with this version, deviations should be traceable in the software update record sheet (see D.IV.1). Deviations on performance above tolerances can lead to additional test (see IV.1c). If it appears that different software had been used, this shall be considered as a non-respect of procedures (see relevant chapter in Certification Manual).

In addition, mechanical construction (all the parameters) of one production unit shall be verified by the auditor, to compare certified characteristics of production with the tested Model Box(es). If it appears that different construction had been used, additional Model Box test shall be required by the auditor.

Finally, consistency of heat recovery shall be verified by the auditor. At least one unit shall be verified with the methodology detailed in the following paragraph.

In case of force majeure (e.g. accidents, labour disputes, natural events, acts of war) which would not allow Eurovent Certita Certification to perform a factory visit Eurovent Certita Certification can decide to replace it by another mean of verification, to postpone it within a reasonable deadline or to cancel it. The Compliance Committee will be made informed regarding these cases.

IV.5 Consistency check of heat recovery

a. Manufacturer uses Eurovent certified heat recovery systems (HRS)

Compare the efficiency and pressure drop data in the AHU quotation or software with results obtained from the current stand-alone certified software from the HRS supplier. AHU manufacturer can never claim higher efficiencies and/or lower pressure drops than the values received from the stand-alone software.

If possible one quotation with a rotor and one quotation with a plate heat exchangers have to be checked.

This check only occurs if there is no RU selection during the audit.

Page 9: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 9 of 40

b. Manufacturer does not use Eurovent certified HRS

Additional testing of non-certified HRS are requested in the laboratory of the regular certification campaign, of the different models, one every year. Repetition would only be necessary in case of change of the structure of the HRS. When a HRS is tested in the RU one year, this additional testing is not necessary for that year.

Compare the efficiency and pressure drop data in the AHU quotation or software with results obtained from the test result. Deviation shall be equal or lower than the acceptable tolerance defined in the certification programme for the HRS. In case a RU is tested every year, this additional testing is not necessary.

c. For certified and non-certified rotors

Observations of rotor arrangements in the AHUs shall be made during the annual factory inspection. If it appears that (sometimes) parts of the actual heat exchanger surface of the rotor are blanked/obstructed it shall be verified in manufacturer’s software if this unfavourable assembly has been considered. The software shall predict (small) reduction in efficiency and (substantial) pressure drop increase, compared to a selection with completely open rotor surface.

IV.6 Qualifying campaign

For a company (“Brand name”) presenting on the market units, under its own brand, manufactured by a certified company, only on-site checking of software shall be conducted at the place (“office”) where the orders to the customers can be accessed. This place is often the factory of the certified manufacturer.

For manufacturers, Real Units taken from the production line shall be selected by the auditor appointed by Eurovent Certita Certification during a factory visit, using the selection software. Models Boxes will be directly selected by Eurovent Certita Certification from the declaration list, to cover all worst configurations of the mechanical, thermal and acoustical performance (see VI.1 of RS 6/C/005).

Selected units shall be sent to the independent laboratory within maximum 6 months. If this deadline is not fulfilled another on-site checking with selection shall be scheduled within maximum one year from the previous on-site checking.

Units are then tested and the obtained performances compared with the values calculated using the software. The test on the Real Unit of a range can be carried out after the test results on the Model Box(es) is/are available.

Assembly places of flat-package units shall be considered exactly the same way as manufacturing places. When a manufacturer presents several manufacturing places, each place shall be considered independently.

If all the test results are within the tolerances and calculation model appears consistent, Eurovent Certita Certification shall grant the certification. If not, failure treatment shall be applied.

When certified, the range is published on the Eurovent Certified Performance website with a certificate number, associated characteristics and performance, name and version of the last software verified by Eurovent Certita Certification, and production places. The participant is then entitled to use the certification mark for this range in literature and on products (see V.2). It shall be obvious for which products the certification is granted (see also 0 and Certification Manual).

Page 10: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 10 of 40

IV.7 Repetition campaign

For a company (“Brand name”) presenting on the market units, under its own brand, manufactured by a certified company, only on-site checking of software shall be conducted annually at the place (“office”) where the orders to the customers can be accessed.

For manufacturers, Participant’s quality control shall be appropriate to maintain the performance within the tolerances. A quality system according to ISO 9001 (covering the production quality systems) is acknowledged by a reduction in the frequency of repetition tests. The manufacturer shall then annually provide a valid ISO 9001 certificate to Eurovent Certita Certification. In addition, annual on-site checking shall be performed in each Participant’s factory(ies). Assembly places of flat-package units shall be considered exactly the same way as manufacturing places.

For each certified range and factory, repetition tests in the independent laboratory selected by

Eurovent Certita Certification shall be required:

Every six years for mechanical, thermal and acoustical performance on Model Boxes for participants holding valid ISO 9001 (every three years otherwise)

Every three years for performance on Real Unit for participants holding valid ISO 9001 (every year otherwise)

Eurovent Certita Certification shall select the units for repetition using the same procedure as for selection of units for the qualification test. If possible, a RU size or MB configuration different from those previously tested shall be selected.

If all the test results are within the tolerances and calculation model appears consistent, Eurovent Certita Certification shall maintain the certification for another period. If not, failure treatment shall be applied.

IV.8 Ranges to be taken out of production

Running a test on a unit from a range which is going to disappear from the market can represent a useless cost for the Participants. If a test is necessary on a unit from a range which is going to disappear from the market, the Participant may send an official letter to Eurovent Certita Certification stating that the range will disappear between the date of the scheduled test and the date + one year. The range remains then certified for maximum one year. If the Participant changes his mind or if it appears that the range is still available after that time, it is considered as a major breach of the rules, and the Participant will have to pay a penalty fee of 15 000 €. In addition, the unit will have to be tested and the following test will have to follow normal schedule.

IV.9 Selection of units for tests

Regarding Model Boxes, Eurovent Certita Certification shall select the minimum number of units to cover the construction variations available on the software and catalogue under the declared range names (see VI.1 of RS 6/C/005). All variations (marked by a X) and worst cases are mandatory to be tested according to Table 1 in RS 6/C/005, and worst case performances can be transferred from the tested MB to other constructions. To claim better class on one performance data, another MB with the construction parameter variation has to be tested too.

If a model box is partly tested (not on all mechanical characteristics); it shall have the same dimensions as the already tested model box (on other characteristics) from which not tested characteristics will be adapted to declare all claimed model box values.

Selection of one Real Unit suitable for testing shall be made during selection visits as described above (see IV.4). Size of the units, air volume performance, heating and cooling capacity, shall be within the limits of the measuring facilities of the laboratory. An up-scaled or down-scaled unit can be selected if no suitable size is available. In case no unit with heat recovery or

Page 11: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 11 of 40

cooling/heating coils can be provided by the factory, these components and the associated performance shall be non-certified. Because it is a significant parameter for the energy efficiency classification, in case the software proposes heat recovery, then the selected unit shall include heat recovery.

Model Box(es) for test shall be supplied to the laboratory within six weeks for factories in Europe and within eight weeks for factories outside Europe (see APPENDIX C).

Real Unit(s) for test shall reach the laboratory no earlier than six weeks and no later than four weeks before the scheduled test date.

When the manufacturer does not meet the corresponding time limits for the supply of units this will be considered as a non-respect of procedures. The manufacturer shall inform the laboratory (preferably before the test) if he wants the unit to be scrapped after the test results are available.

IV.10 Ranges produced in several production places

When a manufacturer presents several production places, each place will be considered independently so each factory has to be visited every year by the auditor appointed by Eurovent Certita Certification (selection or annual on-site checking). Assembly places of flat-package units shall be considered exactly the same way as manufacturing places.

Regarding the selection of units to be tested, the production places for an identical product – identical software, identical components (designation) and suppliers, same casing (same drawings and materials), same assembly procedures and ISO 9001 – have to be considered as one collective production place. In that case each time a different production location will be randomly chosen for the selection of the unit to be tested. The different production places are thus called “sister production places”.

During the annual on-site checking (see IV.4), if there is any suspicion that the production place cannot ensure the same performances as its sister production places, then the auditor may ask that a Real Unit and/or Model Box be tested.

IV.11 Naming non-certified ranges

When a manufacturer also produces units he doesn’t want to submit for certification or out of the software scope, they shall have a significantly different range name from the certified range. If the non-certified range can be selected in the same selection tool, it shall be clear that this range is not certified.

IV.12 Procedures at the laboratory

a. General

Only the independent laboratory personnel shall be permitted to handle test units. The manufacturer's installation and handling instructions shall be followed. The laboratory shall be responsible for uncrating, handling, testing and recrating the unit for shipment. The laboratory personnel shall make repairs to the test unit only in agreement with the manufacturer. No manufacturer's personnel shall be present in the test facility during the test.

b. Test conditions

The units shall be tested at the conditions as stated in the relevant Rating Standard.

Thermal tests will be performed at 2 conditions in the heating mode and 2 conditions in the cooling mode (one condition at manufacturer’s rated design and one condition selected by Eurovent Certita Certification within the scope of the selection software). Independent laboratory shall test units at the conditions as close as possible to the selected rating conditions.

Page 12: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 12 of 40

Aerodynamic tests (air flow - pressure - power input) shall be performed in accordance with the test standard ISO 5801:2007, in an operating range of +/-5% around the selected rating point.

Testing for heat recovery shall be carried out with at least 20 K difference, under dry conditions (supply air temperature should not be below +5°C).

c. Test report and tests results

For each unit, upon completion of all the measurements, the laboratory will render a test report (pdf) to Eurovent Certita Certification with tested data compared to original selection data. If at least one performance measurement is out of the tolerances, the auditor shall conduct a “test check”, i.e. the selection software will be used to recalculate the performance at conditions used for test: test data will be compared to recalculation data. Eurovent Certita Certification will transmit a copy of the report together with results of test check (Forms AHU-4, see APPENDIX D).

Manufacturer has to collect its products one month after receiving the test report. After this delay, the laboratory will destroy the units if not collected and the manufacturer will be invoiced through Eurovent Certita Certification.

If the results are out of the allowable tolerance, or the calculation model appears inconsistent, failure treatment shall be applied.

IV.13 Failure treatment

For each test, a performance item fails when the difference between the declared value and the measurement differs by more than the allowable tolerance (see relevant Rating Standard). A test fails when one or more performance(s) fail. In case of failure, Eurovent Certita Certification shall promptly notify the Participant.

a. Component failure

The manufacturer shall be authorised to examine the reasons of the failure. In case of a component failure the unit may be repaired or replaced by a new one of the same model within 4 weeks, which shall be tested then, according to normal schedule of the laboratory.

b. Unit failure on a real unit

If the failure is established after the recalculation, the manufacturer shall rerate his data by adapting the software to the test results within 6 weeks (see APPENDIX C). If the software is then in accordance with all measurements, certification is granted or maintained with the re-rated data.

After reverification (“test recheck”), if the software is still not in accordance with the test results, manufacturer will have two additional weeks for final adjustment of the software (see APPENDIX C). In case of new failure, no adjustment of software will be accepted and manufacturer has to restart the test procedure.

c. No class reached during RU tests

In case of failure on RU tests not reaching any Filter By-pass Leakage (FBL) class, it is considered as Component failure (immediate stop of the test) and complete retest is mandatory. In case retest is failed, manufacturer is excluded from the programme for 1 year.

In case of failure on RU tests not reaching any Casing Air Leakage (CAL) class, it is considered as Component failure (immediate stop of the test) and complete retest is mandatory. In case retest is failed, manufacturer is excluded from the programme for 1 year.

Page 13: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 13 of 40

d. Test results on a Model Box

Manufacturer has four weeks after reception of result to select one of the following alternatives:

Accept measured values. (Uprate is allowed.)

Ask for a second test on the same unit. In this case, the Manufacturer can choose to re-test only the performances which are not accepted

Ask for a second test on another unit of the same model selected by Eurovent Certita Certification. The delivery shall be done within 8 weeks from the date of the test report. In this case, all measurements are to be re-tested.

e. Failure in case of multiple production places

When a range is tested for different production places, if one repetition test fails, all production places will have to re-rate their data and the software shall be re-rated according to the worst test results for each performance item.

f. Irregularities in production places

Irregularities found in a factory can be a reason for retesting or suspension of certification of the factory or the complete range. In case several factories produce the same range, if one factory is suspended, the Participant has one year to align it. After this delay, if the factory is still not in accordance with the requirements, the complete range is suspended from certification for one year.

IV.14 Special complaint procedure

The general complaint procedure is described in Certification Manual.

In addition, if a Participant obtains doubtful data from a competitor quotation he may present a complaint request. The Participant who complains will pay 1000 € as fee. Eurovent Certita Certification auditor will examine complaint within 6 weeks and complaint data will be also used during annual on-site checking.

If checking results show that the obtained data are different – meaning that other software had been used or quotation data manipulated – this is considered as a non-respect of procedures (see Certification Manual). The 1000 € fee will then be sent back to the plaintiff and it will be invoiced to the Participant who failed.

IV.15 Brand Name

This covers the case of models submitted by a company presenting on the market units, under its own brand, manufactured by a certified company. When Company A doesn’t produce his own range but distributes under its own brand ranges already certified by Participant B, no additional test is required for A. Nevertheless, A has to declare to Eurovent Certita Certification a place (“office”) where the orders to the customers can be accessed to and the software can be annually verified by an Eurovent Certita Certification auditor, during the same quarter as the verification of software hold by B. A’s office is often B’s factory. If a range or a production place of B doesn’t fulfil the requirements and B’s certificate is suspended and/or expelled from the programme, A is also automatically suspended. If B quits certification, A is offered the possibility to cover test expenses for B’s products.

The Brand of the A company must be shown on the output.

A is fully responsible of his software and any non compliance may have a consequence on A certification, even if B is the software provider.

The city(ies) and country(ies) of the production site(s) of company B shall be displayed on Eurovent Certified Performance website next to company A units and on company A certificate.

Page 14: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 14 of 40

IV.16 Non-respect of procedures

The general consequences of non-respect of procedures are described in Certification Manual. In complement applied penalties can be:

A certified range and/or production place is withdrawn from the Eurovent Certified Performance website for one year.

Any minor non-conformity identified during an on-site checking will be escalated to major if not solved prior or during the next follow-up audit.

Any major non-conformity identified during an on-site checking shall be solved within 30 days after the factory audit (or within the deadline defined by the auditor during the audit). Non resolution of a major non-conformity after this deadline can lead to an immediate suspension until the non-compliance is solved.

At the end of the first penalty year and after a second checking, if failure occurs again, the certified range and/or production place is withdrawn from the Eurovent Certified Performance website for three years.

The level of penalties and the list of major and minor non-conformities are listed in APPENDIX E.

V. PROMOTION OF THE PROGRAMME

V.1 By Eurovent Certita Certification

The following information shall be published for each certified range on the Eurovent Certified Performance website www.eurovent-certification.com:

Name of Company

Trade or brand name

Agreement number (format: YY.MM.NNN)

Designation(s) of the range

Software name and version

List of certified characteristics and performance items

Designation of certified sizes of the real units

Heights and widths of the real units

Designation of certified model boxes

The certified mechanical, thermal and acoustical performance data of the model boxes: casing strength (deflection) identified with a “(M)”, casing air leakage at -400 Pa and +700 Pa identified with a “(M)”, filter bypass leakage identified with a “(M)”, thermal transmittance, thermal bridging factor and sound level at different frequencies

Production sites (city, country)

V.2 By the Participant

The design of the Eurovent Certified Performance mark for Air Handling Units, letter size and style are presented in 0. Display of Eurovent Certied Performance mark on literature is detailed in Eurovent Certified Performance Certification Manual, paragraph VI.2.

The design and specifications of the energy efficiency label are given in 0.

a. On printouts

Participants are obliged to display the Eurovent energy efficiency class on the printouts of certified ranges by the means of class on first page (statement, small or large label). If possible the graphical energy efficiency label shall be displayed. Otherwise statement shall be: “Eurovent energy efficiency class X”. The following shall be applied:

Page 15: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 15 of 40

Heat recovery systems: Plate and Rotary Heat Exchangers

Component in Eurovent

certified software AHU

Component not in Eurovent certified software AHU but

Eurovent certified component

Component not in Eurovent certified software AHU and no Eurovent certified component

AHU energy efficiency label mandatory

Specify at least dry efficiency at equal mass flow and design pressure drops for

extract and supply air

AHU energy efficiency label mandatory

Component identification shall be enabled

Specify brand and type (product key) of component

Specify at least dry efficiency at equal mass flow and design pressure drops

AHU energy efficiency label not allowed

Specify at least dry efficiency at equal mass flow and design pressure drops for

extract and supply air

……………………………………………………………………………………………………………………

Fan and electric motor

Component in Eurovent

certified software AHU

Component not in Eurovent

certified software AHU

AHU energy efficiency label mandatory

Specify at least all data, required to check the energy efficiency class (as described in “Requirements for quotations / technical

specifications”)

AHU energy efficiency label not allowed if fan out

AHU energy efficiency label mandatory if motor out only Fan and motor identification shall be enabled

Specify brand and type (product key) of components (fan and/or motor) that are not in the certified software

Specify at least fan and motor date, required to check energy label:

-for the fan: volume flow, fan speed and useful static pressure -for the motor: rated shaft power, synchronic speed, absorbed

power

Standard plate and rotary heat exchangers, as well as standard fans and motors shall be obvious in the software and label is mandatory (first column).

In case of a special project and a heat recovery component is not included in the AHU software but Eurovent certified or covered by IV.5a or IV.5b (second column), or if the motor is out only (third column), label is mandatory.

In case of special projects and if displaying the energy label is not allowed (third column), the following statement shall be written instead: “Heat recovery component and/or fan selection beyond certified software does not comply with the Eurovent Certified Performance rules for label designation.”

b. On units

Each Participant is entitled to display the Eurovent Certified Performance mark on units of ranges which have been certified:

By using the relevant Eurovent Certified Performance mark

By application of the relevant Eurovent Certified Performance mark directly on the nameplate

By using the relevant Eurovent Certified Performance energy efficiency label if applicable. In case the Participant has chosen to display the Eurovent Certified Performance Energy Efficiency label on units, each unit shall be marked, even the one with class E.

Page 16: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 16 of 40

APPENDIX A. SELECTION SOFTWARE MANDATORY REQUIREMENTS

The auditor assigned by Eurovent Certita Certification shall receive a software program, on a CD-Rom or a website with remote access. Other access facilities are only possible in consultation with Eurovent Certita Certification and the auditor. The primary language of the software including outputs must be in English.

The software must be able to calculate operating points between the upper and lower operating condition without changing any components (for example):

The operating point of fan (nominal air flow = 100 %) have to calculate by +5 %, +2.5 %, -2.5 % and -5 % of nominal air flow. The fan speed must be constant. The external pressure will be variable. The software has to calculate the power input (in kW) at the electric terminal of the motor / FU-controller.

The software must have the possibility to calculate the heating capacity with the selected heating coil between the upper and lower operating condition. It must be possible to change the air flow rate, the water flow rate, the air inlet temperature. The software must show and print out the results. The software must give a warning, in case that the result data run out of limits.

The software must have the possibility to calculate the cooling capacity with the selected cooling coil between the upper and lower operating condition. It must be possible to change the air flow rate, the water flow rate, the air inlet temperature, the air inlet humidity. The software must show and print out the results. The software must give a warning, in case the result data run out of limits.

The software must have the possibility to calculate the heat recovery capacity with the selected heat recovery system between the upper and lower operating condition. It must be possible to change the air flow rate, the supply air inlet temperature and humidity, the exhaust air inlet temperature and humidity. The software must show and print out the results. The software must give a warning, in case the result data run out of limits.

The selection software must have the following Mandatory requirements including Input data & Output data.

General Requirements:

Printouts should be provided as a minimum pdf file.

There must be only one Eurovent certified software version.

All components must be described by product key or relevant information (manufacturer name and reference).

Calculations must all be at a minimum in SI units.

The software must show a sketch of the AHU

Software shall be able to store and restore the selection details from the same software version without any alterations of the calculation.

Should the certified performances change due to the software revision, it shall not be possible to get the printout of the project without a new calculation taking into account the performances revision.

General: all data which are asked for in D.IV.1 “Form AHU-4A: Recalculation after Real Unit Test” must be given from the selection software.

Mandatory Input Data:

Reference nomenclature of unit i.e ABC 40.

Upper & lower Summer & Winter operating conditions (outdoor air temp & humidity).

Air flow rate & external pressure.

Heating coil water inlet temp, water flow rate or water outlet temp & supply air temp behind the heater coil.

Cooling coil water inlet temp, water flow rate or water outlet temp & outlet air temp & relative humidity and supply air temp and humidity behind the cooler.

Selected filter section (filter class).

Selected fan section (fan type, motor type).

Selected inlet & outlet sections.

Selected heat recovery system with all necessary inputs (Rotary, Plate HX & Run around coils.)

Page 17: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 17 of 40

Mandatory information to be found on printouts:

General information:

On the first page: o Unique identification No or reference of the selection o Unit range o Unit designation o Eurovent Energy efficiency class. Preferably the graphical energy efficiency label shall be

displayed. Otherwise the statement: “Eurovent energy efficiency class X”, must be announced.

o If the graphical energy efficiency label is not used the Eurovent Certified Performance mark shall be displayed

o If it is not allowed to display the Eurovent Certified Performance mark or energy class/label, a statement shall be written instead, e.g. “Heat recovery component- and/or fan selection beyond certified software do not comply with Eurovent Certified performance rules for label designation”.

On each page (including the first page): o Software name, version code and version date o printout date o page numbering with total number of pages of the printout (e.g. page x of y)

Statement “This component is not included in the software Eurovent certified”, if a component, serving a certified performance (e.g. fan, coil, HRS, etc.), cannot be selected within the certified software. This statement is not required for non certified components that are not included in the software (e.g. filters, attenuators, humidifiers, etc.).

Unit sketches with overall dimensions, unique identification No of the selection and software version must be available on selection printouts.

Technical data:

The technical specification of a quoted AHU shall include all technical data required to verify the claimed energy efficiency class:

General

Velocity in the cross section of the filter section (or of the fan cross section if no filter)

Inlet, outlet and airborn sound power: octave bands in dB and total sound power in dB(A).

Air Density if set at 1.2kg/m3 then no need to be on printout, otherwise actual density must be provided on selection output.

Design winter outdoor temperature for the selected unit, specified as a separate item or mentioned as design inlet temperature for the first thermal component (heat recovery component or heating coil)

Mixing ratio (RCA/SUP) at design winter outdoor temperature (maximum value 85%)

External static pressure for the supply and extract unit (where applicable)

Basic unit construction (same as model box), it is not necessary to include leakage class & deflection on the selection / quotation output.

Internal static pressure drop across the components in the AHU. The two requirements below shall be fulfilled:

o the air side pressure drop across each component is specified in the technical specification o the external static pressure and static fan pressure for the design duty point is specified. o Fan system effect shall be considered:

Either by displaying an additional pressure drop or Within the fan performances. In this case a statement shall be provided (e.g.:“The

fan system effect is taken into account in the fan performances.”) The useful fan static pressure increase to calculate the fan reference power can be derived from all data sets.

Fans

Fan speed in rpm

Page 18: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 18 of 40

Absorbed electrical power from the mains for each fan in the AHU, including the power losses in any motor speed controller. If no fan speed controller is quoted, but the fan needs such a device to operate on the design fan speed, the power loss of such device shall be included in the specified absorbed power.

Filters

Filter type and class

Pressure drops: clean, design and final conditions

Heat recovery system (HRS)

Dry temperature efficiency (no condensation on extract side) of the HRS for design winter operation at equal mass flows (extract flow equal to design supply flow)

Air side pressure drop across the heat recovery system on the extract side and supply side for the design air flows at winter condition and standard density 1.2 kg/m3.

Brine concentration in fluid of run around coil system (where applicable)

Coils

Statement if air side pressure drop cooling coil is for dry (“dry pressure drop”) or wet (“wet pressure drop”) condition or statement if fan has been designed for dry or wet condition.

Heating coil: air side Inlet/Outlet temperatures, airside pressure drop, water flow, & waterside Inlet/Outlet temperatures & pressure drop.

Cooling coil: air side Inlet/Outlet temperatures, inlet/Outlet relative humidity, air side pressure drops (designed: wet or dry, both can be provided, however dry shall be always visible in the software), waterside flow rate and Inlet/Outlet temperatures and pressure drop.

Casing

Casing name

Profile

Thickness of the panel

Insulation material

Internal and external sheet metal thickness

Frame

Single or double skin

Page 19: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 19 of 40

APPENDIX B. EUROVENT CERTIFIED PERFORMANCE MARK AND ENERGY EFFICIENCY LABEL

B.I. Eurovent Certified Performance mark See relevant specifications in Certification Manual.

In addition, the mark shall also include the name of the certified range and the certificate number provided by Eurovent Certita Certification when certification is granted.

Figure 1: Eurovent Certified Performance mark specifications and Eurovent Certified Performance mark for Air Handling Units

Page 20: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 20 of 40

B.II. Eurovent Certified Performance energy efficiency label

Rules for the use of Eurovent Certified Performance energy label are given in the Certification Manual.

It is not mandatory to use Eurovent Certified Performance energy labels however it is highly recommended to do so. If an energy label is used by the participant it is mandatory to use the layout described on our website.

High resolution files of these labels, as well as specifications for the layout are available on the website in the manufacturer’s restricted area.

http://www.eurovent-certification.com/en/Documentation/_ECC_mark_and_Energy_efficiency_labels.php?rub=09&srub=07&ssrub=&lg=en

B.II.1. For units (eventually on printouts)

Figure 2: Examples for Eurovent Certified Performance Energy Efficiency Label – for units

B.II.2. For printouts

The label shall be at least 40 mm wide and 40 mm high. The diploma number shall be displayed on the label.

Conditions of use: can only be used in printed/web document:

if the product shown is certified

if no other product is shown

if all certified performance of the product are displayed next to the label (in the same technical specification).

Files can be found on the restricted part of the Eurovent Certified Performance website http://www.eurovent-certification.com/en/Documentation/_ECC_mark_and_Energy_efficiency_labels.php?rub=09&srub=07&ssrub=&lg=en

Figure 3: Eurovent Certified Performance Energy Efficiency Label – for printouts

Page 21: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 21 of 40

APPENDIX C. CERTIFICATION SCHEDULE

C.I. Application and test schedule

The process lasts an average of about 8½ months, including the preliminary steps (see Table 1 and Figure 4). About 7 months are necessary for repetition tests (pre-checking is not included).

Table 1: Minimum, maximum and average time needed for certification of a range

Certification Step

How many weeks does it take? min max

Average week number The auditor appointed by Eurovent Certita Certification contacts the manufacturer. 1 1 1

Manufacturer sends software to auditor. 1 4 3.5 The auditor pre-checks the software. When software does not meet the certification requirements, the manufacturer has to correct it and send a new version. When the software meets the certification requirements, the manufacturer makes an appointment with the auditor to visit the factory.

1 2 5

Waiting for the visit date. 1 4 7.5 The auditor visits manufacturer’s factory, checks sale data and selects one unit for testing. The auditor sends the visit report and technical form completed for the selected unit to Eurovent Certita Certification. The manufacturer must up-date his list of products and then to send it to Eurovent Certita Certification (Forms AHU-1A and 1B).

1 2 9

Eurovent Certita Certification has to send the manufacturer the visit report and the quotation according to the technical form of the selected real unit(s). When necessary, Eurovent Certita Certification has also to send the quotation for the model box(es).

1 3 11

The manufacturer has to send the order/payment(s) to Eurovent Certita Certification. The unit(s) has(have) then to be delivered to the independent laboratory(ies) (2 to 6 weeks for Europe, 4 to 8 weeks for outside of Europe).

2 8 16

Waiting for the availability of the test rig. 0 5 18.5

The unit(s) is/are tested at the laboratory(ies). 1 2 20 The auditor checks that the software is in accordance with the test results. The laboratory has to send the test report and the checking report to Eurovent Certita Certification.

1 2 21.5

Eurovent Certita Certification has to send the report (comments included) to the manufacturer. If the software is in accordance with the test results, the certification is granted for the next period.

0 2 22.5

In case the software is not in accordance with the test results, the manufacturer has to send the software revised according to the test results to the auditor.

2 6 26.5

The auditor has to check the revised software and send Eurovent Certita Certification a new, revised report.

1 2 28

Eurovent Certita Certification has to check this report and send it to the manufacturer. If the software is in accordance with the test results, the certification is granted for the next period.

0 2 29

In case the software is still not in accordance with the test results, the manufacturer may correct again and send back to the auditor for rechecking.

2 4 32

The auditor has to check the software and send a new report to Eurovent Certita Certification. 1 2 33.5 If the software is in accordance with the test results, the certification is granted for the next period. In case the software is still not in accordance with the test results the selection process has to start again from the beginning and the manufacturer’s data are withdrawn from Eurovent Certified Performance Website until the certification is granted (min. one year after the first certification step).

0 1 34

TOTAL number of weeks necessary 16 52 34

Page 22: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 22 of 40

Figure 4: Planning for application procedure and testing of units

1st contact

Checking of software

Softwar

e ok ?

Factory visit

Factory ok?

Sign licence

agreement

Visit report

Report of selection of

real unit

Up-date of lists

Quotation for real unit

Quotation for model box

Appointment

Delivery Delivery

Testing and test report

Testing and test report

Checking

Software

ok?

EUROVENT C. certificate

Purchase order

Purchase order

Send software

ISO 9001?

1 week

2 weeks

5 weeks

4 weeks

1.5 weeks

3.5 weeks

Send revised software

Send revised software

0.5 weeks

6 weeks

4 weeks 3 weeks

Software failure

Failure treatment:

Checking report

4 weeks

Licence agreement

1.5 weeks AP

LLIC

AT

ION

PR

OC

ED

UR

E:

PR

E-C

HE

CK

ING

Q

UA

LIF

YIN

G O

R R

EP

ET

ITIO

N P

RO

CE

DU

RE

: T

ES

TIN

G O

F U

NIT

S

1.5 weeks

YES

YES

YES

NO

NO

YES: every 3 years

NO: every year

1 week 1.5 weeks

0.5 week

Page 23: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 23 of 40

C.II. Checking of software schedule

The process lasts an average of about 3½ months (see Table 2 and Figure 5).

Table 2: Schedule for annual onsite checking – Minimum, maximum and average time needed for certification of a new AHU range

Certification Step

How many weeks does it take? min max

Average week number

Eurovent Certita Certification informs the manufacturer about the need for a visit of the factory. 1 1 1

The manufacturer has to give to the auditor an appointment for visit of the factory. 1 2 2.5

Waiting for the visit date. 1 4 5 The auditor has to visit manufacturer’s factory and check sale data. The auditor sends the visit report to Eurovent Certita Certification.

1 2 6.5

Eurovent Certita Certification has to send the report including its comments to the manufacturer. If the onsite software version is in accordance with the certified software version kept by the technical auditor and the last test results, the certification is granted for the next period.

0 2 7.5

In case the software is not in accordance with the test results, the manufacturer has to send the revised software according to the test results to the auditor.

2 4 10.5

The auditor has to finalize the recheck of the software and send back to Eurovent Certita Certification a new report.

1 2 13

If the software is in accordance with the test results, the certification is granted for the next period. In case the software is still not in accordance with the test results it is considered as violation of rules.

0 1 13.5

TOTAL number of weeks necessary 7 18 13.5

Figure 5: Planning for on-site checking of software

Factory visit

Appointment

Checking

Sofware

ok?

EUROVENT C. certificate

4 weeks

1.5 weeks

1.5 weeks

Send revised software

2 weeks

3 weeks

Failure treatment:

Checking report

RE

PE

TIT

ION

PR

OC

ED

UR

E: C

HE

CK

ING

YES

NO

1 week

0.5 weeks

Page 24: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 24 of 40

APPENDIX D. FORMS

D.I. Submittal for certification by Manufacturer

Information to be provided by Manufacturer (except gray cells)

D.I.1. Form AHU-1A: Data list of certified models & sizes

id n° PA

Trade name

Range Agreement

Sub Range

Model name

Height Width Catalo

gue Software

Perf Lib

Certified

The “Perf Lib” column should be filled in with: “heating only”/”reversible”/”cooling only” and “with heat recovery”/”without heat recovery”.

D.I.2. Form AHU-1B: Data list of certified model boxes, or casing constructions

id n° PA

Trade name

Range Agreement Casing name

Model box tests (followed by “(M)”) Real Unit tests (followed by “(R)”

Casing Strength

Casing Air Leakage

400 Pa

Casing Air Leakage

700 Pa

Filter Bypass

Leakage

Casing Strength

Casing Air Leakage

400 Pa

Casing Air Leakage

700 Pa

Filter Bypass

Leakage

Thermal Transmittance

Thermal Bridge

Insertion 125

Insertion 250

Insertion 500

Insertion 1000

Insertion 2000

Insertion 4000

Insertion 8000

Corner post Mullion Filter

construction

Panel shape

Panel thickness

Sheet metal

thickness

Insulation material

Insulation material density

Insulation material

conductivity

Way of insulation mounting

Metal sheet of panel Certified

D.II. Submittal for certification by Brand Name

Information to be provided by the Brand Name (except gray cells)

D.II.1. Form AHU-2A: Data list of certified models & sizes (BN)

OEM Brand name

id n° PA

Trade Name

Range Sub

Range Model Height Width id

n° PA

Trade Name

Range Sub

Range Model Software Catalogue

D.II.2. Form AHU-2B: Data list of certified model boxes, or casing constructions (BN)

OEM Brand name

id n° PA

Trade Name

Range Casing Name

id n° PA

Trade Name

Range Casing Name

Page 25: 1422285511_2014-10_OM-5-2015_AHU

AHU, OM-5-2015 Issued January 2015

Page 25 of 40

D.III. Technical forms

D.III.1. Form AHU-3A: Technical specification related to tested real unit

APPLICANT:

DESIGNATION:

Software version:

Manufacturing Place:

Participant Contact:

(Name / Email Address / Telephone No.)

Nominal

applied value

Meas. 1

- 5,0%

Meas. 2

- 2,5%

Meas. 3

± 0,0%

Meas. 4

+ 2,5%

Meas. 5

+ 5%

a - Air flow 0 0 0 0 0 0 m3/h

Total fan pressure 0 Pa

External pressure 0 Pa

Filter pressure drop 1) 0 Pa

Fan speed 0 rpm Values transposed to

Power input 2) 0 kW 20°C ; 101325 Pa ; 1,2 kg/m3

1) of the clean filters 2) at the terminal of the motor / frequency converter

b - Octave band OUTLET in-duct sound power, supply air only

Conditions: Fan speed: 0 rpm - Ext. pressure: 0 Pa - Air flow: 0 m³/h at 20 °C

dBA 125 250 500 1000 2000 4000 8000 Hz

Total dB

c - Octave band INLET in-duct sound power, supply air only

Conditions: Fan speed: 0 rpm - Ext. pressure: 0 Pa - Air flow: 0 m³/h at 20 °C

dBA 125 250 500 1000 2000 4000 8000 Hz

Total dB

d - Airborne sound power, supply air only

Conditions: Fan speed: 0 rpm - Ext. pressure: 0 Pa - Air flow: 0 m³/h at 20 °C

dBA 125 250 500 1000 2000 4000 8000 Hz

Total dB

e - Capacity of cooling coil

(at 1,2 kg/m³) Supply air flow rate : 0 m3/h Supply air flow rate : m3/h

Mass air flow rate : 0 kg/h Mass air flow rate : kg/h

Air in/out : 27 / °C Air in/out : / °C

Cold water in/out : 7 / 12 °C Cold water in/out : / °C

Water flow rate : dm3/h Water flow rate : dm3/h

Humidity in/out : 47 / % Humidity in/out : / %

kW kW

f - Capacity of heating coil Supply air flow rate : 0 m3/h Supply air flow rate : m3/h

(at 1,2 kg/m³) Mass air flow rate : 0 kg/h Mass air flow rate : kg/h

Air in/out : 10 / °C Air in/out : / °C

Hot water in/out : 60 / °C Hot water in/out : / °C

Water flow rate : dm3/h Water flow rate : dm3/h

kW kW

The test w ill be performed at the specified water flow rate and the specified air flow rate. The air flow rate w ill be adjusted

before the test if the claimed available pressure for this flow is not achieved during the aerodynamic test.

g - Pressure drop on water side

Cooling coil kPa kPa

Heating coil kPa kPa

h - Heat recovery : category I (in accordance with EN 308)

Temp.

supply-air inlet (21) °C 0,0 m3/h 0,0 kg/h

supply-air outlet (22) °C

exhaust-air inlet (11) °C 0,0 m3/h 0,0 kg/h

exhaust-air outlet (12) °C

ratio % winter conditions, no condensation on the exhaust air side

INFORMATION RELATING TO TESTED UNIT and CERTIFIED VALUES

PERFORMANCE

xxx

xxx

xxx

(air flow measurements

have to be +/-5% around

nominal point)

1st point 2nd point

xxx

xxx

Page 26: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 26 of 40

APPLICANT

DESIGNATION

Software version

Manufacturing Place

Participant Contact

FAN Supply air circuit Exhaust air circuit

Type

Model

Diameter / Number

Manufacturer

Speed rpm

belt pulley diameter mm

belt pulley type

Belt type

Efficiency of belt drive %

Motor Supply air circuit Exhaust air circuit

Type

Model

Diameter / Number

Manufacturer

Nominal current A A

Efficiency of motor % %

belt pulley diameter mm mm

Start current A A

Speed rpm rpm

Nominal voltage V V

Frequency converter

Frequency (in / out) Hz Hz

Efficiency of converter % %

FILTER Supply air circuit Exhaust air circuit

Brand and type

Filter class

Initial pressure drop (clean filter) Pa Pa

Final pressure drop (dirty filter) Pa Pa

Design pressure drop Pa Pa

Type of filterframe

Number and size of filters

Type

Manufacturer

Fin spacing / number per m mm Nb/m mm Nb/m

Fin thickness and type mm type mm type

Length(L) x height(H) x width(W) mm mm

Number of rows deep

Number of circuits

Tube nominal OD mm mm

Tube pattern mm mm

Tube innergrooved/smooth

Inlet connection

Outlet connection

Internal volume dm3 dm3

Air pressure drop (dry) qv1 & qv2 Pa Pa

Air pressure drop (wet) qv1 & qv2 Pa --- Pa

Type code of manufacturer

Drop eliminator of cooling coil yes / no q v1 ; q v2 : air volume flow 1; 2

Air pressure drop at qv1 & qv2 Pa

xxx

xxx

COOLING COIL HEATING COIL

xxx

xxx

xxx

Page 27: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 27 of 40

APPLICANT

DESIGNATION

Software version

Manufacturing Place

Participant Contact

PLATE

Manufacturer

Reference

Material

Fin spacing

Fin thickness

Dimensions

Pressure drop on air side sup./ ex.

Drop eliminator of HR

Air pressure drop at nominal point

Net weight kg

Dimensions (overall) mm

Dimensional drawing of unit and the coil circuiting shall be provided

1 Physical checks shall made on the additional informations and result shown before performance test.

Fin spacing - the number of fins shall be counted over three separate 100 mm sections of the coil face, the

average figure shall then be divided by 100 and the reciprocal shown to 2 decimal places.

Dimensional drawing and circuit diagram - this shall be checked against test unit.

2 Fan type : Axial - Centrifugal - Tangential - 3 Fin type : Flat - Corrugated - Louvered - Wavy

action or reaction

Date :

xxx

xxx

xxx

Notes for the Test House

mm

HEAT RECOVERY SYSTEM

Pa

TOTAL UNIT

yes / no

Pa

mm

mm

xxx

xxx

APPLICANT

DESIGNATION

Software version

Manufacturing Place

Participant Contact

Type

Manufacturer

Designation

Diameter / depth mm mm

Fin Spacing / number per m mm Nb/m mm Nb/m

Fin Thickness and type mm type mm type

length(l)xheight(H)xwidth(L) mm mm

Number of Rows deep

Number of circuits

Tube Nominal OD mm mm

Tube Pattern mm mm

Tube innergrooved/smooth

Inlet Connection mm mm

Outlet Connection mm mm

Internal Volume dm3 dm3

Air pressure drop at nominal point Pa Pa

Drop eliminator of cooling coil yes / no

Air pressure drop at nominal point Pa

TOTAL UNIT

Net weight kg

Dimensions (overall) mm

Dimensional drawing of unit and the coil circuiting shall be provided

Notes for the Test House

1 Physical checks shall made on the additional informations and result shown before performance test.

Fin spacing - the number of fins shall be counted over three separate 100 mm sections of the coil face, the

average figure shall then be divided by 100 and the reciprocal shown to 2 decimal places.

Dimensional drawing and circuit diagram - this shall be checked against test unit.

2 Fan type : Axial - Centrifugal - Tangential - 3 Fin type : Flat - Corrugated - Louvered - Wavy

action or reaction

Date :

HEAT RECOVERY COILS

COOLING COIL HEATING COIL

xxxxxxxxx

xxx

xxx

Page 28: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 28 of 40

APPLICANT

DESIGNATION

Software version

Manufacturing Place

Participant Contact

ROTARY

Type

Manufacturer

Reference of the wheel

Material

Fin Spacing or Density mm

Fin Thickness and type mm type

Pressure drop on air side sup. / ext. / Pa

Diameter mm

Depth mm

Speed rpm

Power input W

Nominal voltage V

Frequency Hz

TOTAL UNIT

Net weight kg

Dimensions (overall) mm

Dimensional drawing of unit and the coil circuiting shall be provided

Notes for the Test House

1 Physical checks shall made on the additional informations and result shown before performance test.

Fin spacing - the number of fins shall be counted over three separate 100 mm sections of the coil face, the

average figure shall then be divided by 100 and the reciprocal shown to 2 decimal places.

Dimensional drawing and circuit diagram - this shall be checked against test unit.

2 Fan type : Axial - Centrifugal - Tangential - 3 Fin type : Flat - Corrugated - Louvered - Wavy

action or reaction

Date :

xxx

HEAT RECOVERY SYSTEM

xxx

xxx

xxx

xxx

APPLICANT

DESIGNATION

Software version

Manufacturing Place

Participant Contact

Drop eliminator of cooling coil yes / no

Air pressure drop at nominal point Pa

Software version yes / no

Manufacturing Place Pa

Participant Contact

TOTAL UNIT

Net weight kg

Dimensions (overall) mm

Dimensional drawing of unit and the coil circuiting shall be provided

Notes for the Test House

1 Physical checks shall made on the additional informations and result shown before performance test.

Fin spacing - the number of fins shall be counted over three separate 100 mm sections of the coil face, the

average figure shall then be divided by 100 and the reciprocal shown to 2 decimal places.

Dimensional drawing and circuit diagram - this shall be checked against test unit.

2 Fan type : Axial - Centrifugal - Tangential - 3 Fin type : Flat - Corrugated - Louvered - Wavy

action or reaction

Date :

xxx

xxx

xxx

xxx

xxx

Page 29: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 29 of 40

D.III.2. Form AHU-3B: Technical specifications related to tested model box

INFORMATION RELATED TO TESTED UNIT and CERTIFIED VALUES

MECHANICAL CARACTERISTICS

MANUFACTURER:

UP DATE:

Eurovent test code/ Product number

Serial Number

Manufacturing place

name email adress

Contact for technical questions:

Contact for pickup of model box:

1

Range names using this casing:

Type name:

Designation of the panel:

Max.admissible pressure: Pa

Cover (Painted, corrosive treatment,....) :

Option (Special joint, hygienic.....) :

Length of model box: mm

Width of model box: mm Number of access doors:

Heigth of model box: mm Number of door locks on a door:

Number of hinges on a door:

thickness of side panel: mm Additional fixing brackets

thickness of bottom panel: mm Number fixing brackets

thickness of roof panel: mm Design of door gaskets:

thickness of access doors: mm Design of filter gaskets:

Insulation type ( Rock wool, PU, mineral

wool.....) :

specific volume of insulation: kg/m³

coefficient of heat conductivity

of insulation:W/mK

Thermal breaks …

on access doors:

Sheet metal material (inside): on the panels:

Sheet metal material (outside): on the frame:

Thickness of sheet metal (inside): mm on the mullion:

Thickness of sheet metal (outside): mm on the connection of the section:

Profile dimentions: x mm

Applied classes (specified in EN1886)

a - Casing strength Maximum relative deflection: mm/m

- 400 Pa + 700 Pa - 400 Pa + 700 Pa

b - Casing air leakage Maximum leakage rate: l.s-1m-2

c - Filter bypass leakage Maximum filter bypass leakage rate: %

d - Thermal transmittance Thermal transmittance range: W.m-2.K-1

e - Thermal bridging factor

125 250 500 1000 2000 4000 8000

f - Acoustical insulation

material corners: plastic (coated)

material corner post: aluminium

MODEL BOX

Additional stiffener inside the panel ?

Page 30: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 30 of 40

D.IV. Test result forms

D.IV.1. Form AHU-4A: Recalculation after Real Unit Test

RE-CALCULATION AFTER REAL UNIT TESTDate of recalculation

Participant

Participant contact Name: Email:

Auditor Name: Email:

Real unit designation

Software Designation

Version number

Laboratory

CAPACITY 1st point 2nd point

Applied Measured Deviation Applied Measured Deviation Result

Cooling kW ########## ########## #VALEUR!

Heating kW ########## ########## #VALEUR!

Tolerance -2%

Applied Measured

Water flow Press. loss Water flow Press. loss

dm3/h kPa dm3/h kPa

1st point ########## #VALEUR! #VALEUR!

2nd point ########## #VALEUR! #VALEUR!

1st point ########## #VALEUR! #VALEUR!

2nd point ########## #VALEUR! #VALEUR!

The pressure losses are compared with the following formulas #1 and #2:

Deviation#1 {[(Dp / q m1,8) Measured / (Dp / q m

1,8) Applied] - 1} Tolerance: 10%

Deviation#2 {(Dp)Measured - (Dp / qm1,8)Applied * (qm1,8)Measured} Tolerance: 2.0kPa

HEAT RECOVERY Temperatures in °C Air-side pressure loss in Pa

Applied Measured Applied MeasuredDeviation

#1

Deviation

#2Result

In

Out

In

Out

#VALEUR! #VALEUR! Deviation#1 Tolerance : 10%

Deviation#2 Tolerance: 15Pa

Tolerance-3%-points

SOUND POWER

Fan speed: 2305 rpm

Air flow: 5000 m³/h

ESP: 250 Pa

Octave Band In-duct OUTLET in dB

125 250 500 1000 2000 4000 8000 Hz

Applied dB

Measured dB

Deviation #VALEUR! #VALEUR! #VALEUR! #VALEUR! #VALEUR! #VALEUR! #VALEUR! dB

Result #VALEUR! #VALEUR! #VALEUR! #VALEUR! #VALEUR! #VALEUR! #VALEUR!

Octave Band In-duct INTLET in dB

125 250 500 1000 2000 4000 8000 Hz

Applied dB

Measured dB

Deviation #VALEUR! #VALEUR! #VALEUR! #VALEUR! #VALEUR! #VALEUR! #VALEUR! dB

Result #VALEUR! #VALEUR! #VALEUR! #VALEUR! #VALEUR! #VALEUR! #VALEUR!

AIRBORNE Sound Power - Total in dB(A)

Applied Measured Deviation Tolerance Result

#VALEUR! 3 #VALEUR! dB(A)

#VALEUR!

XX/XX/XXXX

XXX

XXX

#VALEUR!

XXX XXX

XXX

TUV NORD OR DTI OR TUV SUD

XXX XXX

XXX

Heating

Cooling

Water-side pressure loss in kPa

Deviation

#1

Deviation

#2Result

#VALEUR!

#VALEUR!

Conditions during acoustic test

##########

Result #VALEUR!

#VALEUR!

##########Supply air

Exhaust air

Ratio

Deviation

Page 31: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 31 of 40

RECALCULATION AFTER REAL UNIT TESTDate of recalculation XX/XX/XXXX

Participant XXX

Real unit designation XXX

Software Designation XXX

Version number XXX

Laboratory TUV NORD OR DTI OR TUV SUD

External pressure in Pa (1) Power input in kW (2) Fan speed in rpm

Applied Measured Applied Measured Available (3) Deviation Results Applied Measured Deviation Results Applied Measured

#VALEUR! #VALEUR! #VALEUR! #VALEUR! #VALEUR!

#VALEUR! #VALEUR! #VALEUR! #VALEUR! #VALEUR!

#VALEUR! #VALEUR! #VALEUR! #VALEUR! #VALEUR!

#VALEUR! #VALEUR! #VALEUR! #VALEUR! #VALEUR!

#VALEUR! #VALEUR! #VALEUR! #VALEUR! #VALEUR!

Values listed above are related to nominal condition r =1,2 kg/m 3

(1) Allowable deviation : -4 % or -15 Pa

(2) Allowable deviation : +3 %

(3) To get the available external pressure, the measured one must be lowered by the unconsidered part of the design filter pressure drop

for the nominal conditions and dry cooler during the air flow test.

Correction for the ESP measured during air flow test

All pressure drops in Pa

#VALEUR!

#VALEUR!

X limit Y limit X limit Y limit

(1) Allowable deviation : -4 % or -15 Pa0 (1) Allowable deviation : -4 % or -15 Pa

(1) Allowable deviation : -4 % or -15 Pa0 (1) Allowable deviation : -4 % or -15 Pa#VALEUR!

#VALEUR! 0 #VALEUR! #VALEUR!

#VALEUR! 0 #VALEUR!

(1) Allowable deviation : -4 % or -15 Pa0 (1) Allowable deviation : -4 % or -15 Pa

Difference to be taken in consideration @ nominal point 100%

Air flow in m3/h

Corrected design pressure drop of filter

Measured pressure drop of clean filter

100

110

120

130

140

150

160

170

180

190

200

0 1 2 3 4 5 6

Ex

tern

al p

ress

ure

in

Pa

Air flow in m³/h

Air flow / Pressure Applied Available (cooler dry) Measured

1,40

1,60

1,80

2,00

2,20

2,40

2,60

2,80

0 1 2 3 4 5 6

Po

we

r in

pu

t in

kW

Air flow in m³/h

Air flow / Power input Applied Measured

RECALCULATION AFTER REAL UNIT TESTDate of recalculation XX/XX/XXXX

Participant XXX

Real unit designation XXX

Software Designation XXX

Version number XXX

Laboratory TUV NORD OR DTI OR TUV SUD

Air Flow Points Air Flow Rate

m³/h measured applied Δpclean, mea-app applied corrected Δpcorr. design - clean measured available

95,0% #VALEUR! ######## #VALEUR! #VALEUR!

97,5% #VALEUR! ######## #VALEUR! #VALEUR!

100,0% #VALEUR! ######## #VALEUR! #VALEUR!

102,5% #VALEUR! ######## #VALEUR! #VALEUR!

105,0% #VALEUR! ######## #VALEUR! #VALEUR!

Δpclean filter in Pa Δpdesign filter in Pa ESP in Pa

Page 32: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 32 of 40

D.IV.2. Form AHU-4C: Software Update Record Sheet

Company Logo

XXXXX Software Name Software Update Record Sheet

Prepared By: _____________________________

Software Revision Date Brief Description of update

Page 33: 1422285511_2014-10_OM-5-2015_AHU

AHU, OM-5-2015 Issued January 2015

Page 33 of 40

APPENDIX E. MAJOR / MINOR NON COMPLIANCES

Each certified range shall be allocated of 15 audit points (after first delivery of certificate). Each major non-compliance related to the range (independently of the manufacturing place), shall remove 2 points to the account of the range.

If a range reaches 0 point, Participant shall be notified for immediate suspension of the range for one year. A 24-months period without major non-conformity resets the account to the initial level.

E.I. Handling of several ranges

CASE ARE ENERGY COMPONENTS

THE SAME?

IS MECHANICAL CONSTRUCTION

THE SAME? MANDATORY AUTHORIZED FORBIDDEN COMMENTS

2 ranges with different names, Range A is certified, Range B is not certified

YES NO Energy efficiency

label1 for A

ECP mark and Eurovent Energy

Efficiency label for B

Range A and B shall have

significantly different names.

2 ranges with different names, Range A is certified, Range B is not certified

NO YES Energy efficiency

label1for A

ECP mark and Eurovent Energy

Efficiency label for B

Range A and B shall have

significantly different names. MB shall have

different names

2 ranges with different names, Range A is certified, Range B is not certified

YES YES Energy efficiency

label1 for A

ECP mark and Eurovent Energy

Efficiency label for B

Range A and B shall have

significantly different names.

2 products A and B from the same Eurovent certified range: they include

only components available in the certified software except product B

includes a Eurovent certified HRS not included in the certified software.

YES except Eurovent certified

HRS YES

Energy efficiency

label1 for A and B

2 products A and B from the same Eurovent certified range: they include

only components available in the certified software except product B

includes a non-Eurovent certified HRS not included in the certified software.

YES except non-Eurovent certified

HRS YES

Energy efficiency

label1 for A and

ECP mark for B

Energy efficiency class and label for

B

Page 34: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 34 of 40

CASE ARE ENERGY COMPONENTS

THE SAME?

IS MECHANICAL CONSTRUCTION

THE SAME? MANDATORY AUTHORIZED FORBIDDEN COMMENTS

2 products A and B from the same Eurovent certified range: they include

only components available in the certified software except product B

includes a fan (or fans) not included in the software

YES except fan(s) YES Energy efficiency label1 for A and ECP mark for B

Energy efficiency class and label for

B

2 products A and B from the same Eurovent certified range: they include

only components available in the certified software except product B

includes a motor (or motors) not included in the software

YES except motor(s)

YES Energy efficiency

label1 for A and B

2 products A and B from the same Eurovent certified range: they include

only components available in the certified software except product B has a mechanical construction not included in

the software

YES NO

This case is not allowed as all mechanical constructions for a certified range shall be certified and available in the certified software.

Product with non certified mechanical construction shall carry a significantly different range name from the certified range name

Note: Use of components not in the certified software shall remain exceptional. Energy class shall be consistent with the unit delivered to the customer. Eurovent Certita Certification is entitled to ask a manufacturer to include a component in the software if it is observed that it this component is used very often.

1 Preferably the graphical energy efficiency label shall be displayed. Otherwise the statement: “Eurovent energy efficiency class X”, must be announced. If the graphical energy efficiency label is not used the Eurovent Certified Performance mark shall be displayed

Page 35: 1422285511_2014-10_OM-5-2015_AHU

AHU, OM-5-2015 Issued January 2015

Page 35 of 40

E.II. Major Non-Compliances (2 Points)

Item No.

OM-5, Page No.

Major Non Compliance = Non-compliance which involves direct impact on the units finished product performance, and may mis-lead the end user from the software output / product and marketing advertisment, or impacts on the completion of the 3A

Technical Form for ECC Real Unit test selection.

1 P14 Any minor non-conformity identified during an on-site checking will be escalated to major if not resolved prior or during the next follow-up audit (IV.16 OM-5)

2 P9/P14/P17 Mis-use of ECC mark in portraying products / ranges to be certified when they are not, this also applies to branded products that have not been declared to ECC or tracability of the original ECC manufacturer has been removed, either software or unit.

3 P9/P18 Use of ECC mark: The participant is entitled to use the certification mark for the certified range in literature and on products, however it must be obvious for which products the certification is granted. See also guidance in Certification Manual.

4 P6/P13 Declaration of Certified Brand without prior knowledge / approval from ECC HQ.

5 P6/P16 Model Size in Certified range not already declared to ECC

6 P11 Declaration of Certified MB values without prior knowledge / approval from ECC HQ

7 P8 If it appears that different MB construction has been used during the factory audit to that supplied for the MB certification charateristics, then this is deemed a failure and additional MB test shall be required.

8 P11

Several production places: During the annual on-site checking (see IV.4), if there is any suspicion that the production place cannot ensure the same performances as its 'sister' production places, then the auditor can issue a major non-compliances and ask for that a Real Unit and/or Model Box be tested.

9 P7 Software update record sheet not available for updated perfomance to existing components i.e DLL updates

10 P8 Software update record sheet must provide enough traceable information should differences exist during factory software checking

11 P5/P10/P11 Manufacturer not providng proof of ISO 9001 continuation after existing certification has lapsed.

12 P8/P9 Consistancy checks of Heat Recovery stand-alone ECC software or Real Unit component test to unit selection: NO unit selection software performance can be higher than that of the stand-alone ECC software or outside the tolerance of the independent Heat Recovery test report.

13 P8 Able to re-calculate the last Real Unit before removing the compoment from selection software, otherwise re-calculation can not be completed.

14 P8 If moving to new software platform between the period when the Real Unit was selected & re-calculation, the same unit (all components) must be selectable.

15 P7/P9 During the factory audit if it appears that different software has been used, then this shall be considered as a non-respect of procedures (see certification manual)

16 P20 Calculated Eurovent Certified Performance energy class is lower than the claimed energy class

17 P15/P17

If it is not allowed to display the energy class classification a statement shall be written e.g "Heat Recovery component -and/or fan selection beyond certified software do not comply with Eurovent Certita Certification rules for Energy Class classification.," Refer to Table V.2 in OM-5 for heat recovery systems & fan / electrical motors for when the energy classification can be used.

General Software Requirements

18 P16 Printouts must be provided as a minimium pdf file.

Page 36: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 36 of 40

Item No.

OM-5, Page No.

Major Non Compliance = Non-compliance which involves direct impact on the units finished product performance, and may mis-lead the end user from the software output / product and marketing advertisment, or impacts on the completion of the 3A

Technical Form for ECC Real Unit test selection.

19 P16 There must be only one active Eurovent Certified AHU software version

20 P16 If the software is able to export to other formats, then the key output selection requirements must exist eg. Software version, Project name etc…

21 P16 All components must be described inside the software by a product key or relevant tracable information.

22 P16 Software data charateristics shall be expressed in SI Units as a minimuim.

23 P7/P16 The primary language of the software including outputs must be in English.

24 P17 ECC energy efficiency Class i.e. 'A' must be on the first page (at least on one page)

25 P16 Unit Sketches and overal dimensions must be available from software.

26 P16 Software must be able to calculate between the upper & lower operating conditions without changing components, software should provide user warning if selection not possible.

27 P16 Software able to store & restore the selection details without alterations of the calculation.

Input / Selection Print Output Data

28 P16 Unit reference nomenclature to be present on selection output i.e. ABC 40 The product name must be same as that of the certified product listed on the ECC website.

29 P16 Upper & Lower Summer & Winter operating conditions (outdoor air temperature & humidity)

30 P16 Air flow rate & external pressure

31 P16 Heating & Cooling coil water inlet temperatures, water flow rate or water outlet temperatures. Supply air temp behind heating coil & outlet air temp & relative humidity for cooling coil and supply air temp and humidity behind the cooler

32 P7/P17 On the First Page: Project name / Customer / Quote No./ Unit designation & Project selection date must be at a minimium on the first page.

33 P18

On the first page: Eurovent Energy efficiency class. Preferably the graphical energy efficiency label shall be displayed. Otherwise the statement: “Eurovent energy efficiency class X”, must be announced. If the graphical energy efficiency label is not used the Eurovent Certified Performance mark shall be displayed.

34 P18 On Each Page: Software name, version code, printout date, page numbering with total no. of pages (e.g. x of y)

35 P7/P17

Statement: "This component is not included in the software certified by Eurovent Certification", if a component, serving a certified performance, cannot be selected within the certified software. This statement is not required for non-certified components that are not included in the software (e.g Filters, Attenuators, Humidifiers, etc)

Technical Selection Print Output Data

36 P17 All data to calculate the Energy efficiency Class must be available from the data selection sheet.

37 P17 Velocity in cross-section of the filter section (or of the fan cros-section if no filter)

38 P17 Octave bands to be in (dB) and Outlet/Inlet & Airbourne Sound Power (dBA) of the unit

39 P17 If software not using standard 1.2kg/m3 air density, then actual air density must be provided on selection output

Page 37: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 37 of 40

Item No.

OM-5, Page No.

Major Non Compliance = Non-compliance which involves direct impact on the units finished product performance, and may mis-lead the end user from the software output / product and marketing advertisment, or impacts on the completion of the 3A

Technical Form for ECC Real Unit test selection.

40 P17 Design Winter outdoor air temperature and % factor of recirculation air (if applicable) must be declared on the selection printout or mentioned as design inlet temperature for the first thermal component (heat recovery or heating component)

41 P17 External static pressure for the supply and extract unit (where applicable)

42 P17 Basic unit construction(same as Model Box), it is not necessary to include leakage class & deflection on the selection /quotation output

43 P18 Selected filter sections with filter type & class, pressure drops for Clean, Design & Dirty conditions (Energy class based on Design)

44 P18 Heat recovery system (HRS): Dry temperature efficiency (no condensation on extract side) of the HRS for the design winter operation @ equal mass flows (extract flow equsl to design supply flow)

45 P18 Brine concentration in fluif of run around coil system (where applicable)

46 P18 Coils: statement if airside pressure drop cooling coil is dry (dry pressure drop) or wet (wet pressure drop) condition or statement if fan has been designed for dry or wet condition

47 P18 Cooling Coil: Designed wet or dry, both can be provided, however dry shall be always visible in the software

48 P18 Fan & motor type including fan and motor data i.e. RPM, Input Power Absorbed Power, must be declared on selection output.

49 P18 Inverter power absorption not included in total active power absorbed of the unit when inverter is not fitted in factory but required to run unit

50 P18 Total static pressure values of actual unit configuration different to that declared on printout “Total internal static pressure + external static pressure (+possible system effect) but not including Dynamic pressure”.

51 P17/P18 All data to calculate the Energy efficiency Class must be available from the data selection sheet.

52 P33 If unit called same for certified & non-certified with different components (unit must have different range name!)

Note: The above list is not absolute and at the auditors discretion based on the definition of "major" non-compliance this will be included in the audit assessment

Notes: Some of these items may have also been listed on the 'minor' non-compliance list, however they will be considered as a 'major' non-compliance should they not be resolved during the n+1 audit

Page 38: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 38 of 40

E.III. Minor Non-Compliances (0 Points)

Item No.

OM-5, Page No.

Minor Non Compliance = which does not involve a direct impact on the units finished product performance, and does not mislead the end user from the Software output / product and marketing advertisment, or does not impact on the audit completion.

1 P7 Software update record sheet not provided to ECC HQ for additional component additions or other updates within Software excluding performance changes to certified scope

2 P19 Incorrect design of ECC Mark used on any documentation as detailed in the certification manual (VI.2), this also includes color of mark

3 P15 If the participant has chosen to fit the energy efficiency class to the units even the one with class <E must be fitted.

4 P17 Filter pressure drop is missing on software print out, however tracable in software audit check

5 P18 If selection design is based on WET fan condition and the energy class is calculated correctly based on the WET pressure drop of the internal static pressure, but NO note can be found on Fan selection output designed for WET conditions.

6 P18 The middle-life filter pressure drop is not the average between clean and final filter pressure drop. EN13053 §6.9.2

7 P17 No Page numbering on selection outputs

8 P17 Software name / Version and printout date displayed on each page of the selection output with page numbering.

9 P17 Project name / Customer / Quote No./ Unit designation & Project selection date must be at a minimium on the first page.

10 P17 If Energy Efficiency class is provided on selection output but not on the first page

11 P17 Software version number required on DWG (not created by Software) to customer that includes selection output data.

Note: The above list is not absolute and at the auditors discretion based on the definition of "minor" non-compliance this will be included in the audit assessment

Notes: Some of these items may have also been listed on the 'major' non-compliance list, however they will be considered on the first occasion as a 'minor' non-compliance

Page 39: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 39 of 40

APPENDIX F. CONSTRUCTION VARIATIONS OF AHU MODEL BOXES

F.I. Corner post (corner and frame)

material: steal/aluminium/plastic

shape (see pictures):

thickness of the material

with/without thermal break

F.II. Mullion

material: steal/aluminium/plastic

shape (see pictures):

thickness of the material

with/without thermal break

Page 40: 1422285511_2014-10_OM-5-2015_AHU

OM-5-2015 Issued January 2015

Page 40 of 40

F.III. Filter construction

fixed or laterally extractable

position in the unit (fixed on mullion or on panel)

kind of filter gasket ( flat/profiled)

material/thickness of gasket

fixing of gasket (glued/clamped/foamed)

fixing of filter cell (with springs/screws/...)

used sealing material (gasket/silicone/...)

F.IV. Panel shape

with/without thermal break

design (see sketch)