2 Volume 3—Power Distribution and Control Assemblies CA08100004E—December 2010 www.eaton.com 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14.1 Medium Voltage Busway Medium Voltage Busway—Nonsegregated Phase Bus Nonsegregated Phase 600V, 10 kV BIL–5 kV, 60 kV BIL–15 kV, 95 kV BIL–38 kV, 170 kV BIL Typical 5/15 kV Bus Run Section End View Contents Description Page Standards and Certifications . . . . . . . . . . . . . . . . . . . . . . . . 3 Additional Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Technical Data and Specifications . . . . . . . . . . . . . . . . . . . . 3 Application Description Eaton’s nonsegregated phase bus runs are designed for use on circuits whose importance requires greater reliability than power cables provide. Typical of such applications are the connections from transformers to switchgear assemblies in unit substations, connections from switchgear assemblies to rotating apparatus, and tie connections between switchgear assemblies. Nonsegregated phase bus is an assembly of bus conductors with associated connections, joints and insulating supports confined within a metal enclosure without interphase barriers. The conductors are adequately separated and insulated from each other and ground by insulating bus supports. Each conductor for 2400V service and above is insulated with a fluidized bed epoxy coating throughout that reduces the possibility of corona and electrical tracking. Features, Benefits and Functions Ease of Installation Because of its compact dimensions, relative light weight and user-friendly design, nonsegregated phase bus is easily installed. The inherent rigidity of the design permits hanging rods to be spaced approximately every 4 ft (1.2m) for indoor bus runs, and allows supporting frames to be spaced approximately every 8 ft (2.4m) for outdoor runs. Standard length of bus run sections is 100 inches (2540 mm) or less. Short-Circuit Force Withstand Ability Nonsegregated phase bus runs in 600V, 5 kV and 15 kV are designed to withstand three-phase and phase-to-ground short- circuit current of 78 kA rms asymmetrical (132 kA peak) for 10 cycles and 50 kA rms symmetrical for 2 seconds. Momentary 4-cycle withstand ratings up to 158 kA peak (98.8 kA rms asymmetrical) are also available. For 27 kV nonsegregated phase bus runs, short-circuit withstand ratings of 64 kA rms asymmetrical (108 kA peak) for 10 cycles and 40 kA rms symmetrical for 2 seconds are standard. Construction Enclosures are fabricated from 11-gauge aluminum, and are welded for maximum rigidity. 11-gauge steel and stainless steel are options. Removable covers are secured with bolts for ease of access when making joints and subsequent and periodic inspection. Enclosures are painted with a baked-on polyester powder coat paint system resulting in a very durable finish with uniform thickness and gloss. This cosmetically pleasing finish minimizes the risk of problems in harsh environments. The standard color is ANSI-61 light gray, and special paint colors are available upon request. Stainless steel hardware option is available. Expansion joints are supplied in all straight bus runs at approximately 50 ft (15.2m) intervals to allow for the expected expansion when the conductors are energized and are carrying rated current. A variety of terminations is available to accommodate most termination requirements. Bus runs can be terminated with flexible shunts, potheads, porcelain bushings, or conductor stub ends for connection to riser bars in switchgear assemblies. Conductors All conductors are 100% conductivity copper bars. Bus joints are made by solidly bolting the bus bars together with splice plates on each side. All joint surfaces are silver-plated to ensure maximum conductivity through the joint. Tin-plating is also available. After bolting, each standard joint is covered by a preformed, flame- retardant insulating boot, providing full insulation for bus conductors. These boots are easily removable for inspection of the joints at any future time. Temperature Rise The bus will be capable of carrying rated current continuously without exceeding a conductor temperature rise of 65°C above an outside ambient temperature of 40°C, as required by ANSI Standard C37.23. For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

14.1 Medium Voltage Busway - Klockner Moeller pdf/3/3-14-1.pdf · 4000A. 27 kV and 38 kV bus ... Medium Voltage Nonsegregated Phase Bus—Standard Configurations Bus Duct Rated 49

Embed Size (px)

Citation preview

Page 1: 14.1 Medium Voltage Busway - Klockner Moeller pdf/3/3-14-1.pdf · 4000A. 27 kV and 38 kV bus ... Medium Voltage Nonsegregated Phase Bus—Standard Configurations Bus Duct Rated 49

2 Volume 3—Power Distribution and Control Assemblies

CA08100004E—December 2010 www.eaton.com

141414141414141414141414141414141414141414141414141414141414

14.1

Medium Voltage Busway

Medium Voltage Busway—Nonsegregated Phase Bus

Nonsegregated Phase 600V, 10 kV BIL–5 kV, 60 kV BIL–15 kV, 95 kV BIL–38 kV, 170 kV BIL

Typical 5/15 kV Bus Run Section End View

Contents

Description Page

Standards and Certifications . . . . . . . . . . . . . . . . . . . . . . . .

3

Additional Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

Technical Data and Specifications . . . . . . . . . . . . . . . . . . . .

3

Application Description

Eaton’s nonsegregated phase bus runs are designed for use on circuits whose importance requires greater reliability than power cables provide. Typical of such applications are the connections from transformers to switchgear assemblies in unit substations, connections from switchgear assemblies to rotating apparatus, and tie connections between switchgear assemblies. Nonsegregated phase bus is an assembly of bus conductors with associated connections, joints and insulating supports confined within a metal enclosure without interphase barriers. The conductors are adequately separated and insulated from each other and ground by insulating bus supports. Each conductor for 2400V service and above is insulated with a fluidized bed epoxy coating throughout that reduces the possibility of corona and electrical tracking.

Features, Benefits and Functions

Ease of Installation

Because of its compact dimensions, relative light weight and user-friendly design, nonsegregated phase bus is easily installed. The inherent rigidity of the design permits hanging rods to be spaced approximately every 4 ft (1.2m) for indoor bus runs, and allows supporting frames to be spaced approximately every 8 ft (2.4m) for outdoor runs. Standard length of bus run sections is 100 inches (2540 mm) or less.

Short-Circuit Force Withstand Ability

Nonsegregated phase bus runs in 600V, 5 kV and 15 kV are designed to withstand three-phase and phase-to-ground short-circuit current of 78 kA rms asymmetrical (132 kA peak) for 10 cycles and 50 kA rms symmetrical for 2 seconds. Momentary 4-cycle withstand ratings up to 158 kA peak (98.8 kA rms asymmetrical) are also available. For 27 kV nonsegregated phase bus runs, short-circuit withstand ratings of 64 kA rms asymmetrical (108 kA peak) for 10 cycles and 40 kA rms symmetrical for 2 seconds are standard.

Construction

E

nclosures are fabricated from 11-gauge

aluminum, and are welded for maximum

rigidity. 11-gauge steel and stainless steel are options. Removable covers are secured with bolts for ease of access when making joints and subsequent and periodic inspection.

Enclosures are painted with a baked-on polyester powder coat paint system resultingin a very durable finish with uniform thickness and gloss. This cosmetically pleasing finish minimizes the risk of problems in harsh environments. The standard color is ANSI-61 light gray, and special paint colors are available upon request. Stainless steel hardware option is available.

Expansion joints are supplied in all straight bus runs at approximately 50 ft (15.2m) intervals to allow for the expected expansion when the conductors are energized and are carrying rated current.

A variety of terminations is available to accommodate most termination requirements. Bus runs can be terminated with flexible shunts, potheads, porcelain bushings, or conductor stub ends for connection to riser bars in switchgear assemblies.

Conductors

All conductors are 100% conductivity copper bars. Bus joints are made by solidly bolting the bus bars together with splice plates on each side. All joint surfaces are silver-plated to ensure maximum conductivity through the joint. Tin-plating is also available. After bolting, each standard joint is covered by a preformed, flame-retardant insulating boot, providing full insulation for bus conductors. These boots are easily removable for inspection of the joints at any future time.

Temperature Rise

The bus will be capableof carrying rated current continuously without exceeding a conductor temperature rise of 65°C above an outside ambient temperature of 40°C, as required by ANSI Standard C37.23.

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Page 2: 14.1 Medium Voltage Busway - Klockner Moeller pdf/3/3-14-1.pdf · 4000A. 27 kV and 38 kV bus ... Medium Voltage Nonsegregated Phase Bus—Standard Configurations Bus Duct Rated 49

Volume 3—Power Distribution and Control Assemblies

CA08100004E—December 2010 www.eaton.com

3

141414141414141414141414141414141414141414141414141414141414

14.1

Medium Voltage Busway

Medium Voltage Busway—Nonsegregated Phase Bus

Standards and Certifications

The metal-enclosed bus runs are designed for 600V, 5 kV, 15 kV, 27 kV and 38 kV service in accordance with ANSI C37.23. 600V, 5 kV and 15 kV bus is available with continuous current ratings of 1200, 2000, 3000, 3200 or 4000A. 27 kV and 38 kV bus is available in 1200 and 2000A continuous ratings.

Tests

The design of nonsegregated bus runs has been tested per ANSI C37.23. Certification of momentary current testing, impulse testing and heat rise are available upon request.

Seismic Application

Bus run assemblies are designed to meet Uniform Building Code (UBC) and California Code Title 24 for Seismic Zones 4, 3, 2A, 2B, 1 and 0. Complete guidelines for proper supports are provided on each seismic specified order.

Additional Information

Technical Data: TD01702001E

Brochure: BR01702001E

Final Fit Program: SA01702001E

Consulting Application Guide

, CA08104001E

Technical Data and Specifications

Available Nonsegregated Bus Ratings per ANSI/IEEE Standard C37.23-1987

Notes

Refer to

Section 22

for available CSA and UL listings.

This is a value calculated from 2 second short-circuit current withstand rating based on relationship l

2

t = constant.

For 600V application, 4-cycle momentary current withstand rating up to 158 kA peak (98.8 kA rms asymmetrical) is also available.

RatedMaximumVoltage kV rms

Rated PowerFrequency Hz

Power Frequency Withstand 1 Min. Dry kV rms

Impulse Withstand (1.2 x 50 microsec)kV Peak

RatedContinuousCurrentAmperes

Rated Short-TimeShort-CircuitWithstand Current(kA rms Symmetrical)

Rated MomentaryShort-CircuitWithstand Current10 Cycle

2 Sec. 1 Sec.

kA PeakkA rms Asym.

0.635 60 2.2 10 12002000300040005000

49 69 132

78

0.635 60 2.2 10 1200200030003200

63 89 170 100.8

4.76 60 19 60 12002000300040005000

49 — 132 78

4.76 60 19 60 1200200030003200

63 — 170 100.8

8.25 60 36 95 12002000300040005000

41 — 111 66

8.25 60 36 95 1200200030003200

63 — 170 100.8

15 60 36 95 12002000300040005000

48 — 130 77

15 60 36 95 1200200030003200

63 — 170 100.8

27 60 60 125 12002000

40 — 108 64

38 60 80 170 120020003000320040005000

40 — 104 64

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Page 3: 14.1 Medium Voltage Busway - Klockner Moeller pdf/3/3-14-1.pdf · 4000A. 27 kV and 38 kV bus ... Medium Voltage Nonsegregated Phase Bus—Standard Configurations Bus Duct Rated 49

4 Volume 3—Power Distribution and Control Assemblies

CA08100004E—December 2010 www.eaton.com

141414141414141414141414141414141414141414141414141414141414

14.1

Medium Voltage Busway

Medium Voltage Busway—Nonsegregated Phase Bus

Medium Voltage Nonsegregated Phase Bus—Standard Configurations

Bus Duct Rated 49 kA rms Symmetrical 2 Seconds

Notes

All phase conductors above 635V are fully insulated with epoxy insulation for the rated maximum voltage. Epoxy insulation is available at 600V as an option.

Optional poly/porcelain or poly/epoxy bracing supports are available. Consult factory.

Add 3 lbs to the weights shown when using poly/porcelain or poly/epoxy support bracing.

For dimensions in mm, multiply inches by 25.4.

WireVoltage(kV)

AmpereRating

LayoutNumber Width Height

ConductorCenterline

ConductorSize

Phase-PhaseConductorSpacing

Bracing Supports

OptionalGround Bus

AverageWeightPer Foot Lbs (kg)

StandardsListing

Aluminum Enclosures

3 0.635/5/15 1200 1 20.00 17.38 8.13 (1) 0.5 x 3 5.38 Glass polyester 0.25 x 2 38 (17) CSA

0.635/5/15 2000 1 20.00 17.38 8.13 (1) 0.375 x 6 5.38 Glass polyester 0.25 x 2 47 (21) CSA

0.635/5/15 3000 1 20.00 17.38 8.13 (1) 0.5 x 8 5.38 Glass polyester 0.25 x 2 68 (31) CSA

0.635/5/15 3200 1 20.00 17.38 8.13 (1) 0.5 x 8 5.38 Glass polyester 0.25 x 2 68 (31) —

0.635/5/15 4000 2 35.75 17.38 8.13 (2) 0.5 x 6 5.38 Glass polyester 0.25 x 2 101 (46) CSA

0.635/5/15 5000 2 35.75 17.38 8.13 (2) 0.5 x 8 5.38 Glass polyester 0.25 x 2 118 (54) CSA

4 0.635/5/15 1200 4 26.00 17.38 8.13 (1) 0.5 x 3 5.38 Glass polyester 0.25 x 2 48 (22) CSA

0.635/5/15 2000 4 26.00 17.38 8.13 (1) 0.375 x 6 5.38 Glass polyester 0.25 x 2 60 (27) CSA

0.635/5/15 3000 4 26.00 17.38 8.13 (1) 0.5 x 8 5.38 Glass polyester 0.25 x 2 88 (40) —

0.635/5/15 3200 4 26.00 17.38 8.13 (1) 0.5 x 8 5.38 Glass polyester 0.25 x 2 88 (40) —

0.635 4000 5 35.75 17.38 8.13 (2) 0.5 x 6 4.00 Glass polyester 0.25 x 2 127 (58) —

Steel Enclosures (Steel, Stainless Steel and Galvanized Steel)

3 0.635/5/15 1200 1 20.00 17.38 8.13 (1) 0.5 x 3 5.38 Glass polyester 0.25 x 2 58 (26) CSA

0.635/5/15 2000 1 20.00 17.38 8.13 (1) 0.375 x 6 5.38 Glass polyester 0.25 x 2 67 (30) CSA

0.635/5/15 3000 1 20.00 17.38 8.13 (1) 0.5 x 8 5.38 Glass polyester 0.25 x 2 106 (48) —

0.635/5/15 3200 1 20.00 17.38 8.13 (1) 0.5 x 8 5.38 Glass polyester 0.25 x 2 106 (48) —

0.635/5/15 4000 2 35.75 17.38 8.13 (2) 0.5 x 8 5.38 Glass polyester 0.25 x 2 154 (70) —

0.635/5/15 5000 3 35.75 17.38 8.13 (2) 0.5 x 8 5.38 Glass polyester 0.25 x 2 154 (70) —

4 0.635/5/15 1200 4 26.00 17.38 8.13 (1) 0.5 x 3 5.38 Glass polyester 0.25 x 2 72 (33) CSA

0.635/5/15 2000 4 26.00 17.38 8.13 (1) 0.375 x 6 5.38 Glass polyester 0.25 x 2 84 (38) CSA

0.635/5/15 3000 4 26.00 17.38 8.13 (1) 0.5 x 8 5.38 Glass polyester 0.25 x 2 124 (56) —

0.635/5/15 3200 4 26.00 17.38 8.13 (1) 0.5 x 8 5.38 Glass polyester 0.25 x 2 124 (56) —

0.635 4000 5 35.75 17.38 8.13 (2) 0.5 x 8 4.00 Glass polyester 0.25 x 2 188 (85) —

Bus

OptionalGround Bus

Layout 1

C

W

H

1 2 3Bus

Layout 2

1 1 22 33Bus

Layout 3

1 2 13 32CL H

CL OptionalGround Bus

OptionalGround Bus

CCL

W

CL

W

H

CL

CCL

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Page 4: 14.1 Medium Voltage Busway - Klockner Moeller pdf/3/3-14-1.pdf · 4000A. 27 kV and 38 kV bus ... Medium Voltage Nonsegregated Phase Bus—Standard Configurations Bus Duct Rated 49

Volume 3—Power Distribution and Control Assemblies

CA08100004E—December 2010 www.eaton.com

5

141414141414141414141414141414141414141414141414141414141414

14.1

Medium Voltage Busway

Medium Voltage Busway—Nonsegregated Phase Bus

Medium Voltage Nonsegregated Phase Bus—Standard Configurations

Bus Duct Rated 63 kA rms Symmetrical 2 Seconds

Notes

All phase conductors above 635V are fully insulated with epoxy insulation for the rated maximum voltage. Epoxy insulation is available at 600V as an option.

Optional poly/porcelain or poly/epoxy bracing supports are available. Consult factory.

Add 3 lbs to the weights shown when using poly/porcelain or poly/epoxy support bracing.

For dimensions in mm, multiply inches by 25.4.

WireVoltage(kV)

AmpereRating

LayoutNumber Width Height

ConductorCenterline

ConductorSize

Phase-PhaseConductorSpacing

BracingSupports

GroundBus

AverageWeightPer FootLbs (kg)

StandardsListing

Aluminum Enclosures

3 0.635/5/15 1200 1 20.00 17.38 8.13 (1) 0.375 x 6 5.38 Glass polyester 0.25 x 3 48 (22) CSA

0.635/5/15 2000 1 20.00 17.38 8.13 (1) 0.375 x 6 5.38 Glass polyester 0.25 x 3 48 (22) CSA

0.635/5/15 3000 1 20.00 17.38 8.13 (1) 0.5 x 8 5.38 Glass polyester 0.25 x 3 78 (35) CSA

0.635/5/15 3200 1 20.00 17.38 8.13 (1) 0.5 x 8 5.38 Glass polyester 0.25 x 3 78 (35) —

0.635/5/15 4000 2 35.75 17.38 8.13 (2) 0.5 x 6 5.38 Glass polyester 0.25 x 3 105 (48) —

0.635/5/15 5000 2 35.75 17.38 8.13 (2) 0.5 x 8 5.38 Glass polyester 0.25 x 3 121 (55) —

4 0.635/5/15 1200 4 26.00 17.38 8.13 (1) 0.375 x 6 5.38 Glass polyester 0.25 x 3 61 (28) —

0.635/5/15 2000 4 26.00 17.38 8.13 (1) 0.375 x 6 5.38 Glass polyester 0.25 x 3 61 (28) —

0.635/5/15 3000 4 26.00 17.38 8.13 (1) 0.5 x 8 5.38 Glass polyester 0.25 x 3 101 (46) —

0.635/5/15 3200 4 26.00 17.38 8.13 (1) 0.5 x 8 5.38 Glass polyester 0.25 x 3 101 (46) —

0.635 4000 5 35.75 17.38 8.13 (2) 0.5 x 6 4.00 Glass polyester 0.25 x 3 128 (58) —

Steel Enclosures (Steel, Stainless Steel and Galvanized Steel)

3 0.635/5/15 1200 1 20.00 17.38 8.13 (1) 0.375 x 6 5.38 Glass polyester 0.25 x 3 68 (31) —

0.635/5/15 2000 1 20.00 17.38 8.13 (1) 0.375 x 6 5.38 Glass polyester 0.25 x 3 68 (31) —

0.635/5/15 3000 1 20.00 17.38 8.13 (1) 0.5 x 8 5.38 Glass polyester 0.25 x 3 89 (40) —

0.635/5/15 3200 1 20.00 17.38 8.13 (1) 0.5 x 8 5.38 Glass polyester 0.25 x 3 89 (40) —

0.635/5/15 4000 2 35.75 17.38 8.13 (2) 0.5 x 6 5.38 Glass polyester 0.25 x 3 134 (61) —

0.635/5/15 5000 3 35.75 17.38 8.13 (2) 0.5 x 8 5.38 Glass polyester 0.25 x 3 160 (73) —

4 0.635/5/15 1200 4 26.00 17.38 8.13 (1) 0.375 x 6 5.38 Glass polyester 0.25 x 3 85 (39) —

0.635/5/15 2000 4 26.00 17.38 8.13 (1) 0.375 x 6 5.38 Glass polyester 0.25 x 3 85 (39) —

0.635/5/15 3000 4 26.00 17.38 8.13 (1) 0.5 x 8 5.38 Glass polyester 0.25 x 3 115 (52) —

0.635/5/15 3200 4 26.00 17.38 8.13 (1) 0.5 x 8 5.38 Glass polyester 0.25 x 3 115 (52) —

0.635 4000 5 35.75 17.38 8.13 (2) 0.5 x 6 4.00 Glass polyester 0.25 x 3 188 (85) —

OptionalGround Bus

W

Bus

Layout 4

1 2 3 NBus

Layout 5

1 1 22 33 NNCCL

OptionalGround Bus

CL

HC

CL

W

CL

H

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Page 5: 14.1 Medium Voltage Busway - Klockner Moeller pdf/3/3-14-1.pdf · 4000A. 27 kV and 38 kV bus ... Medium Voltage Nonsegregated Phase Bus—Standard Configurations Bus Duct Rated 49

6 Volume 3—Power Distribution and Control Assemblies

CA08100004E—December 2010 www.eaton.com

141414141414141414141414141414141414141414141414141414141414

14.1

Medium Voltage Busway

Medium Voltage Busway—Nonsegregated Phase Bus

27 kV/38 kV Nonsegregated Phase Bus—–Standard Configurations

27 kV Bus Rated up to 108 kA Peak Momentary, 40 kA rms Symmetrical 2 Second

38 kV Bus Rated up to 104 kA Peak Momentary, 40 kA rms Symmetrical 2 Second

Notes

All bus bars for applications above 600V are fully insulated with fluidized epoxy coating for the rated maximum voltage.

Check with Eaton for availability.

Add 3 lbs to the weights shown when using poly/porcelain or epoxy insulating supports in place of glass polyester.

Glass polyester.

Polyester/porcelain.

Epoxy.

For dimensions in mm, multiply inches by 25.4.

WireType

RatedMaximumVoltagekV

RatedCont.CurrentAmperes

LayoutNo.

Enclosure Material

Enclosure Size (Inches)

Number of BarsPh andSize, Cu(Inches)

Ph-PhBusSpacing(Inches)

InsulatingSupports Optional

GroundBus, Cu(Inches)

Approx.AverageWeightper Foot Lbs (kg)

Listing

Std. Opt. W H C Std. Opt.

CSA UL

3 27 1200 8 Aluminum — 30.00 21.13 10.00 (1) 0.25 x 4 7.00

� � �

0.25 x 2 37 (17) Yes No

27 2000 8 Aluminum — 30.00 21.13 10.00 (1) 0.50 x 4 7.00

� � �

0.25 x 2 49 (22) Yes No

27 1200 8 — Steel 30.00 21.13 10.00 (1) 0.25 x 4 7.00

� � �

0.25 x 2 37 (17) Yes No

27 2000 8 — Steel 30.00 21.13 10.00 (1) 0.50 x 4 7.00

� � �

0.25 x 2 49 (22) Yes No

WireType

RatedMaximumVoltagekV

RatedCont.CurrentAmperes

LayoutNo.

EnclosureMaterial

EnclosureSize (Inches)

Numberof BarsPh andSize, Cu(Inches)

Ph-PhBusSpacing(Inches)

InsulatingSupports Optional

GroundBus, Cu(Inches)

Approx.AverageWeightper Foot Lbs (kg)

Listing

Std. Opt. W H C Std. Opt.

CSA UL

3 38 1200 9 Aluminum — 40.25 21.50 11.00 (1) 0.25 x 4 10.50 Epoxy — — 0.25 x 3 61 (28) Yes No

38 2000 10 Aluminum — 40.25 21.50 11.00 (1) 0.38 x 4 10.50 Epoxy — — 0.25 x 3 89 (40.4) Yes No

38 1200 9 — Steel 40.25 21.50 11.00 (1) 0.25 x 4 10.50 Epoxy — — 0.25 x 3 88 (40) No No

38 2000 10 — Steel 40.25 21.50 11.00 (1) 0.38 x 4 10.50 Epoxy — — 0.25 x 3 116 (53) No No

Ground Bus

Layout 8 Layout 9

1 2 3

Ground Bus

1 2 3

Layout 10

Ground Bus

1 2 3

W

BusC

CL HH H

CLCL

Bus CL

W W

Bus CL

CL

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Page 6: 14.1 Medium Voltage Busway - Klockner Moeller pdf/3/3-14-1.pdf · 4000A. 27 kV and 38 kV bus ... Medium Voltage Nonsegregated Phase Bus—Standard Configurations Bus Duct Rated 49

Volume 3—Power Distribution and Control Assemblies

CA08100004E—December 2010 www.eaton.com

7

141414141414141414141414141414141414141414141414141414141414

14.1

Medium Voltage Busway

Medium Voltage Busway—Nonsegregated Phase Bus

Nonsegregated Phase Bus Electrical Properties and Watt Loss Data

Note

For dimensions in mm, multiply inches by 25.4.

WireType

RatedMax.Voltage

Cont.RatedCurrent

Conductor (Copper) EnclosureElectrical PropertiesµOHM/PH/FT µµF/PH/FT

No./PhThick Width

Phase Arrang. MaterialSize DC 60 Hz Cap to Grd

kV Ampere Inch Inch W x H (Inches) R 20°C R XL Z = R+jXL Cg

3 0.635/5/15 1200 1 0.50 3.00 1-2-3 Aluminum 20.00 x 17.38 5.5 7.1 49.8 50.3 2.2

0.635/5/15 2000 1 0.38 6.00 1-2-3 Aluminum 20.00 x 17.38 3.7 4.7 37.0 37.3 4.4

0.635/5/15 3000 1 0.50 8.00 1-2-3 Aluminum 20.00 x 17.38 2.1 2. 31.1 31.3 5.9

0.635/5/15 3200 1 0.50 8.00 1-2-3 Aluminum 20.00 x 17.38 2.1 2.7 31.1 31.3 5.9

3 0.635/5/15 4000 2 0.50 6.00 1-1-2-2-3-3 Aluminum 35.75 x 17.38 1.4 1.8 35.6 35.6 5.9

0.635/5/15 5000 2 0.50 8.00 1-1-2-2-3-3 Aluminum 35.75 x 17.38 1.0 1.3 32.9 32.9 7.8

0.635/5/15 1200 1 0.50 3.00 1-2-3 Steel 20.00 x 17.38 5.5 7.1 49.8 50.3 2.2

0.635/5/15 2000 1 0.38 6.00 1-2-3 Steel 20.00 x 17.38 3.7 4.7 37.0 37.3 4.4

3 0.635/5/15 3000 1 0.50 8.00 1-2-3 Steel 20.00 x 17.38 2.1 2.7 31.1 31.3 5.9

0.635/5/15 3200 1 0.50 8.00 1-2-3 Steel 20.00 x 17.38 2.1 2.7 31. 31. 5.9

0.635/5/15 4000 2 0.50 8.00 1-1-2-2-3-3 Steel 35.75 x 17.38 1.0 1.3 32.9 32.9 7.8

0.635/5/15 5000 2 0.50 8.00 1-2-3-1-2-3 Steel 35.75 x 17.38 1.0 1.3 14.6 14.6 7.4

4 0.635/5/15 1200 1 0.50 3.00 1-2-3-N Aluminum 26.00 x 17.38 5.5 7.1 49.8 50.3 1.5

0.635/5/15 2000 1 0.38 6.00 1-2-3-N Aluminum 26.00 x 17.38 3.7 4.7 37.0 37.3 3.1

0.635/5/15 3000 1 0.50 8.00 1-2-3-N Aluminum 26.00 x 17.38 2.1 2.7 31.1 31.3 4.1

0.635/5/15 3200 1 0.50 8.00 1-2-3-N Aluminum 26.00 x 17.38 2.1 2.7 31.1 31.3 4.1

0.635 4000 2 0.50 6.00 1-1-2-2-3-3-N-N Aluminum 35.75 x 17.38 1.4 1.8 35.6 35.6 4.9

4 0.635/5/15 1200 1 0.50 3.00 1-2-3-N Steel 26.00 x 17.38 5.5 7.1 49.8 50.3 1.5

0.635/5/15 2000 1 0.38 6.00 1-2-3-N Steel 26.00 x 17.38 3.7 4.7 37.0 37.3 3.1

0.635/5/15 3000 1 0.50 8.00 1-2-3-N Steel 26.00 x 17.38 2.1 2.7 41.1 41.2 4.1

0.635 3200 1 0.50 8.00 1-2-3-N Steel 26.00 x 17.38 2.1 2.7 41.1 41.2 4.1

0.635 4000 2 0.50 8.00 1-1-2-2-3-3-N-N Steel 35.75 x 17.38 1.0 1.3 32.9 32.9 6.6

3 27 1200 1 0.25 4.00 1-2-3 Aluminum 30.00 x 21.00 8.3 10.6 51.6 52.7 1.7

27 2000 1 0.50 4.00 1-2-3 Aluminum 30.00 x 21.00 4.1 5.3 24.8 25.4 1.7

27 1200 1 0.25 4.00 1-2-3 Steel 30.00 x 21.00 8.3 10.6 51.6 52.7 1.7

27 2000 1 0.50 4.00 1-2-3 Steel 30.00 x 21.00 4.1 5.3 24.8 25.4 1.7

3 38 1200 1 0.25 4.00 1-2-3 Aluminum 40.25 x 21.50 8.3 10.6 61.3 62.3 2.0

38 2000 2 0.38 4.00 1-2-3 Aluminum 40.25 x 21.50 4.1 5.3 59.0 59.2 2.0

38 1200 1 0.25 4.00 1-2-3 Steel 40.25 x 21.50 8.3 10.6 61.3 62.3 2.0

38 2000 2 0.38 4.00 1-2-3 Steel 40.25 x 21.50 4.1 5.3 59.0 59.2 2.0

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Page 7: 14.1 Medium Voltage Busway - Klockner Moeller pdf/3/3-14-1.pdf · 4000A. 27 kV and 38 kV bus ... Medium Voltage Nonsegregated Phase Bus—Standard Configurations Bus Duct Rated 49

8 Volume 3—Power Distribution and Control Assemblies

CA08100004E—December 2010 www.eaton.com

141414141414141414141414141414141414141414141414141414141414

14.1

Medium Voltage Busway

Medium Voltage Busway—Nonsegregated Phase Bus

For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Page 8: 14.1 Medium Voltage Busway - Klockner Moeller pdf/3/3-14-1.pdf · 4000A. 27 kV and 38 kV bus ... Medium Voltage Nonsegregated Phase Bus—Standard Configurations Bus Duct Rated 49

Index

AAbility, 1above, 1, 3-5access, 1accommodate, 1accordance, 2Add, 3-5Additional, 1-2adequately, 1After, 1All, 1, 3-5all, 1allow, 1allows, 1also, 1-2Aluminum, 3-6aluminum, 1ambient, 1Ampere, 3-4, 6Amperes, 2, 5an, 1, 3-4and, 1-7ANSI, 1-2any, 1apparatus, 1Application, 1-2application, 2applications, 1, 5Approx, 5approximately, 1are, 1-5

Arrang, 6as, 1, 3-4Assemblies, 1-7assemblies, 1-2assembly, 1associated, 1Asym, 2asymmetrical, 1-2at, 1-7availability, 5Available, 2available, 1-4Average, 3-5

Bbaked, 1barriers, 1Bars, 5bars, 1, 5based, 2be, 1bed, 1been, 2Benefits, 1between, 1BIL, 1bolting, 1bolts, 1boot, 1

Page 9: 14.1 Medium Voltage Busway - Klockner Moeller pdf/3/3-14-1.pdf · 4000A. 27 kV and 38 kV bus ... Medium Voltage Nonsegregated Phase Bus—Standard Configurations Bus Duct Rated 49

Index

boots, 1BR, 2Bracing, 3-4bracing, 3-4Brochure, 2Building, 2Bus, 1-7bus, 1-2, 5bushings, 1Busway, 1-7by, 1, 3-6

CCA, 1-7cables, 1calculated, 2California, 2call, 1-7can, 1Cap, 6capable, 1carrying, 1Centerline, 3-4Certification, 2Certifications, 1-2Cg, 6Check, 5Circuit, 1-2circuit, 1-2circuits, 1CL, 3-5coat, 1coating, 1, 5Code, 2color, 1colors, 1com, 1-7compact, 1Complete, 2conductivity, 1Conductor, 3-4, 6conductor, 1conductors, 1, 3-4ConductorsBecause, 1Configurations, 3-5confined, 1connection, 1

connections, 1constant, 2Construction, 1Consult, 3-4Consulting, 2Cont, 5-6Contents, 1Continuous, 2continuous, 2continuously, 1Control, 1-7Copper, 6copper, 1corona, 1cosmetically, 1covered, 1covers, 1CSA, 2-5Cu, 5Current, 2, 5-6current, 1-2Cycle, 2cycle, 1-2cycles, 1

DData, 1-2, 6DC, 6December, 1-7Delivery, 1-7Description, 1design, 1-2designed, 1-2dimensions, 1, 3-6Distribution, 1-7Dry, 2Duct, 3-4durable, 1

EEach, 1each, 1-2

Page 10: 14.1 Medium Voltage Busway - Klockner Moeller pdf/3/3-14-1.pdf · 4000A. 27 kV and 38 kV bus ... Medium Voltage Nonsegregated Phase Bus—Standard Configurations Bus Duct Rated 49

Index

Ease, 1ease, 1easily, 1Eaton, 1, 5eaton, 1-7Electrical, 6electrical, 1enclosed, 2Enclosure, 5-6enclosure, 1Enclosures, 1, 3-4End, 1ends, 1energized, 1ensure, 1environments, 1Epoxy, 3-5epoxy, 1, 3-5every, 1exceeding, 1Expansion, 1expansion, 1expected, 1

Ffabricated, 1factory, 3-4Features, 1Final, 2finish, 1Fit, 2flame, 1flexible, 1fluidized, 1, 5Foot, 3-5For, 1-7for, 1-5Force, 1frames, 1Frequency, 2friendly, 1from, 1-2FT, 6ft, 1full, 1fully, 3-5Functions, 1

future, 1

GGalvanized, 3-4gauge, 1Glass, 3-5glass, 5gloss, 1gray, 1Grd, 6greater, 1Ground, 3-5ground, 1Guide, 2guidelines, 2

Hhanging, 1hardware, 1harsh, 1has, 2heat, 2Height, 3-4Hz, 2, 6

IIEEE, 2Immediate, 1-7importance, 1Impulse, 2impulse, 2in, 1-6Inch, 6Inches, 5-6inches, 1, 3-6indoor, 1

Page 11: 14.1 Medium Voltage Busway - Klockner Moeller pdf/3/3-14-1.pdf · 4000A. 27 kV and 38 kV bus ... Medium Voltage Nonsegregated Phase Bus—Standard Configurations Bus Duct Rated 49

Index

Information, 1-2inherent, 1inspection, 1Installation, 1installed, 1insulated, 1, 3-5Insulating, 5insulating, 1, 5insulation, 1, 3-4interphase, 1intervals, 1is, 1-4its, 1

Jjoint, 1joints, 1jXL, 6

KkA, 1-5kg, 3-5KMParts, 1-7kV, 1-6

LLayout, 3-5Lbs, 3-5lbs, 3-5length, 1less, 1light, 1Listing, 3-5listings, 2Loss, 6

Mmade, 1making, 1Material, 5-6Max, 6Maximum, 2, 5maximum, 1, 3-5Medium, 1-7meet, 2metal, 1-2microsec, 2Min, 2minimizes, 1mm, 1, 3-6Momentary, 1-2, 5momentary, 2most, 1multiply, 3-6

NNo, 5-6Nonsegregated, 1-7nonsegregated, 1-2Note, 6Notes, 2-5Number, 3-5

Oof, 1-2, 5on, 1-2Opt, 5option, 1, 3-4Optional, 3-5options, 1or, 1-7order, 2other, 1outdoor, 1

Page 12: 14.1 Medium Voltage Busway - Klockner Moeller pdf/3/3-14-1.pdf · 4000A. 27 kV and 38 kV bus ... Medium Voltage Nonsegregated Phase Bus—Standard Configurations Bus Duct Rated 49

Index

outside, 1

PPage, 1paint, 1painted, 1Peak, 2, 5peak, 1-2Per, 3-4per, 2, 5periodic, 1permits, 1PH, 6Ph, 5-6Phase, 1-7phase, 1, 3-4place, 5plated, 1plates, 1plating, 1pleasing, 1poly, 3-5Polyester, 5polyester, 1, 3-5porcelain, 1, 3-5possibility, 1potheads, 1powder, 1Power, 1-7power, 1preformed, 1problems, 1Program, 2proper, 2Properties, 6provide, 1provided, 2providing, 1

RRated, 2-6rated, 1, 3-5

Rating, 3-4rating, 2Ratings, 2ratings, 1-2reduces, 1Refer, 2relationship, 2relative, 1reliability, 1Removable, 1removable, 1request, 1-2required, 1requirements, 1requires, 1resultingNonsegregated, 1retardant, 1rigidity, 1rise, 1-2riser, 1RiseThe, 1risk, 1rms, 1-5rods, 1rotating, 1Run, 1run, 1-2runs, 1-2

SSA, 2Sec, 2Second, 5second, 2Seconds, 3-4seconds, 1Section, 1-2sections, 1secured, 1Seismic, 2seismic, 2separated, 1service, 1-2Short, 1-2short, 1-2shown, 3-5shunts, 1

Page 13: 14.1 Medium Voltage Busway - Klockner Moeller pdf/3/3-14-1.pdf · 4000A. 27 kV and 38 kV bus ... Medium Voltage Nonsegregated Phase Bus—Standard Configurations Bus Duct Rated 49

Index

side, 1silver, 1Size, 3-6solidly, 1spaced, 1Spacing, 3-5special, 1Specifications, 1-2specified, 2splice, 1Stainless, 1, 3-4stainless, 1Standard, 1-5standard, 1Standards, 1-4Std, 5Steel, 3-6steel, 1straight, 1stub, 1subsequent, 1substations, 1such, 1supplied, 1Support, 1-7support, 3-4supporting, 1Supports, 3-5supports, 1-5surfaces, 1switchgear, 1Symmetrical, 2-5symmetrical, 1system, 1

TTD, 2Tech, 1-7Technical, 1-2Temperature, 1temperature, 1terminated, 1termination, 1terminations, 1tested, 2testing, 2Tests, 2

than, 1that, 1The, 1-2the, 1, 3-5These, 1Thick, 6thickness, 1This, 1-2three, 1through, 1throughout, 1tie, 1Time, 2time, 1Tin, 1Title, 2to, 1-6together, 1tracking, 1transformers, 1Type, 5-6Typical, 1

UUBC, 2UL, 2, 5Uniform, 2uniform, 1unit, 1up, 1-2, 5upon, 1-2use, 1user, 1using, 3-5

Vvalue, 2variety, 1very, 1View, 1Voltage, 1-7voltage, 3-5

Page 14: 14.1 Medium Voltage Busway - Klockner Moeller pdf/3/3-14-1.pdf · 4000A. 27 kV and 38 kV bus ... Medium Voltage Nonsegregated Phase Bus—Standard Configurations Bus Duct Rated 49

Index

Volume, 1-7

WWatt, 6Weight, 3-5weight, 1weights, 3-5welded, 1when, 1, 3-5whose, 1Width, 3-4, 6will, 1Wire, 3-6with, 1-5within, 1without, 1Withstand, 1-2withstand, 1-2www, 1-7

XXL, 6

YYes, 5

ZZones, 2

þÿ�œµOHM, 6µµF, 6