14 - Parameter Tuning

Embed Size (px)

Citation preview

  • 8/10/2019 14 - Parameter Tuning

    1/24

  • 8/10/2019 14 - Parameter Tuning

    2/24

    section will investigate the relationship between a parameter of a mode and the model

    response process for some typical transfer function models.

    3. Tuning of Power System Dynamical Model Parameters

    A power system dynamical device usually consists of different types of elements. These

    elements can be mathematically presented by some typical dynamical components or

    transfer functions. The following describes a number of typical dynamical components inpower system dynamical models, and illustrates how the responses of these components

    are affected by varying their parameters. Also, a simplified model of a single generator

    power system is investigated in this section.

    Inertial Components: Its transfer function is shown as Figure 3.1. The inertial

    component is usually used to model the regulator amplifier, governor relay, or

    electric/hydraulic converter. Figure 3.1 and 3.2 display the responses of this component

    when applying a step input with different time constant and gain values. As can be seenfrom Figure 3.1, the raising rate of response will increase with reducing time constant

    value. But the settle down value of response would not be affected by varying timeconstant value. When increasing gain value, as shown in Figure 3.2, both the raising rate

    and settle down value of response will be increased.

    Figure 3.1 Inertial Component Responses for Changing

    Time Constant

  • 8/10/2019 14 - Parameter Tuning

    3/24

  • 8/10/2019 14 - Parameter Tuning

    4/24

    Figure 3.4, when increasing time constant value, the raising rate and overshooting

    magnitude of response will increase, but the falling rate during the decay segment will bedecreased, thus, the settle down time of response would last longer. When increasing gain

    value, as shown in Figure 3.5, the raising rate and overshooting magnitude of response

    also will increase, but the falling rate would not be changed.

    Figure 3.4 Inertial-Differential Component Responses for

    Changing Time Constant

    Figure 3.5 Inertial-Differential Component Responses for

    Changing Gain

    Single Generator Power System Model: Figure 3.6 shows a simplified model of a

    single generator power system. The block Ks and Kd are defined as system synchronizing

  • 8/10/2019 14 - Parameter Tuning

    5/24

    coefficient and system damping coefficient, respectively. These two coefficients

    represent the equivalent effects of generator, AVR, governor, loads and other systemcomponents. Figures from 3.7 to 3.12 display the power angle and speed responses of the

    power system model when a load shed is applied with different model parameters. As can

    be seen from Figure 3.7 and 3.8, when increasing damping coefficient Kd, the oscillation

    magnitudes of power angle and speed responses will be reduced, but the oscillationfrequency of them is not changed. When increasing synchronizing coefficient Ks, as

    shown in Figure 3.9 and 3.10, the oscillation magnitudes of power angle and speed

    responses will be reduced and the oscillation frequency of them will be increased. Also, itis found that the initial power angle becomes smaller with increasing Ks. When reducing

    generator inertial coefficient H, as shown in Figure 3.11 and 3.12, the raising rate,

    overshooting magnitude and oscillation frequency of speed response will be increased,but settle down time becomes shorter. For the power angle response, its falling rate, and

    oscillation frequency will be increased, but its undershooting magnitude will be

    decreased and settle down time also becomes shorter.

    Figure 3.6 Simplified Single Generator Power System Model

  • 8/10/2019 14 - Parameter Tuning

    6/24

    Figure 3.7 Generator Speed Responses for Changing

    Damping Coefficient

    Figure 3.8 Generator Power Angle Responses for Changing

    Damping Coefficient

  • 8/10/2019 14 - Parameter Tuning

    7/24

    Figure 3.9 Generator Speed Responses for Changing

    Synchronizing Coefficient

    Figure 3.10 Generator Power Angle Responses for Changing

    Synchronizing Coefficient

  • 8/10/2019 14 - Parameter Tuning

    8/24

    Figure 3.11 Generator Speed Responses for Changing

    Inertial Coefficient

    Figure 3.12 Generator Power Angle Responses for Changing

    Inertial Coefficient

    4. Examples of Tuning Power System Dynamical Model Parameters

    In this section, some examples are presented to illustrate how to tune the parameters of

    power system dynamical models utilizing the site test or system incidence recording data,so as to make the responses of dynamical model match the real recording data.

    4.1Generator Start-up Case

    This is a real test case. The test system, as shown in Figure 4.1, is a Hydro GenerationStation as the backup power system of a Nuclear Power Plant. The test process includes:

  • 8/10/2019 14 - Parameter Tuning

    9/24

    first start a generator unit, at the same time flash the generator field winding, when

    generator terminal voltage reaches approximately 70% to 90% of rated output voltage,then a voltage relay trips the appropriate circuit breakers and connect the emergency load

    from the nuclear generation plant to the generator. The generator AVR and governor

    models are shown as Figure 4.2 and 4.3. The typical parameters of the models are listed

    in Table 4.1 and 4.2. When using the typical parameters in simulation study, as can beseen from Figures 4.4, 4.6, 4.8 and 4.10, the responses of generator speed, voltage, power

    and field voltage do not match the site test results. By investigating the response curves,

    obviously, some transfer function time constants and gains of both AVR and governormodels and the generator damping and inertial coefficients need to be tuned up properly.

    A set of modified model parameters are listed in Table 4.1 and 4.2. The responses of the

    system corresponding to the parameter modifications show a very good match to the sitetest results as displayed in Figures 4.5, 4.7, 4.9 and 4.11. In this project study, it is

    discovered that the response of the motor start simulation will not correctly express the

    real situation if the formula coefficients of motor load model are not presented properly.

    The formula coefficients of motor load model usually can be obtained by using curve

    fitting technology based on the load torque curve. In most cases, the manufacturers onlyprovide the load torque curves under the speed range from 0 to 100%. It is no problem to

    simulate the motor start if the system frequency within this speed range. Otherwise, thesimulation results will not truly reflect the actual situations. In this test case, the generator

    speed ever overshoots to 120% of rated speed at a period of time. Figure 4.13 shows the

    response of a motor electrical power during start up have big discrepancy against the sitetest result when using the load model with the speed range from 0 to 100%. When

    remodeling the load torque curve covered the speed range to 120% as given in Figure

    4.12, the response of the motor electrical power corresponding to the modified loadmodel shows a very good match to site test results as shown in Figure 4.14.

  • 8/10/2019 14 - Parameter Tuning

    10/24

    KGEN 2 KGEN 1

    W/OMod#2

    4kV B1TS

    600V LC 3X4 600V LC 3X8

    4kV 3TC

    TX-3X5

    HP IP -3A600 HP

    LP IP -3A400 HP

    RBSP-3 A250 HP

    LPSWP- 3A600 HP

    TX-3X8

    MCC 3XS1

    3EPTC13

    3PTC3

    3TC/D/E-3B1T

    3TC-3B1T

    3TD/E-3B1T

    3TC-3B2T

    NO

    B1TS-3B1T

    3X5 Test 13X8 Test 1 3X8 Test 23X4 Test 23X4 Test 1

    TX-3X4

    13. 2kV Keo#113. 2kV Keo#2

    U3 4kV bus13

    CT4

    Underground

    NO

    4kV B2TS

    4kV 3TE4kV 3TD

    600V LC 3X10600V LC 3X6600V LC 3X5 600V LC 3X9

    TX-3X9 TX-3X6 TX- 3X10

    MCC 3XS2

    LP IP -3B400 HP

    RBSP-3 B250 HP

    LPSWP-3B600 HP

    HPIP-3B600 HP

    3EPTE123PTE3

    MCC 3XS3

    3PTD3 3EPTD13

    3TD-3B1T

    3TE-3 B1T3TC/D/E-3B2T

    3TD-3B2T

    3TE-3B2T

    3TD/E-3B2T

    NO

    B2TS-3B2T

    3X5 Test 23X6 Test 1 3X6 Test 23X9 Test 1 3X9 Test 2

    EFDWP- 3A600 HP

    EFDWP- 3B600 HP

    HP IP -3C600 HP

    Figure 4.1 Test System for Generator Start-up

    Figure 4.2 Exciter/AVR Model Diagram of Hydraulic Generator

  • 8/10/2019 14 - Parameter Tuning

    11/24

    Parameter Typical Tuned

    RC 0.0 0.0

    XC 0.03 0.03

    TR 0.0 0.0

    TC 0.0 0.0

    TBB 0.0 0.0

    KA 100 70

    TA 0.02 0.02KF 0.5 0.12

    TF 0.5 0.8

    KC 0.1 0.1

    VVLR 1.07 1.07

    KVL 120.0 120.0

    TVL 0.05 0.05

    KVF 1.0 1.0

    TH 0.05 0.05

    VImax 0.17 0.17

    VImin -0.17 -0.17

    VRmax 3.66 3.66

    VRmin 0.0 0.0

    Vdc 125 125

    Rf 0.15 0.06VHZ 0.74 0.74

    TD 2.5 2.5

    Vfb 87.5 87.5

    Ifb 585 585

    Vref 1.025 1.025

    Table 4.1 Typical and Tuned Parameters of Exciter Model

    Figure 4.3 Governor Model Diagram of Hydraulic Generator

    Parameter TP Q GC TG RP RT TR H D

    Typical 0.04 1 2.5 1 0.02 0.4 5.5 7 2

    Tuned 0.04 1 2.5 1.41 0.02 0.4 7.5 4.94 1.1

    Table 4.2 Typical and Tuned Parameters of Governor Model

  • 8/10/2019 14 - Parameter Tuning

    12/24

    Figure 4.4 Comparison between Simulated Generator Speed Response(Using Typical Parameters) and Site Measured Speed

    Figure 4.5 Comparison between Simulated Generator Speed Response

    (Using Tuned Parameters) and Site Measured Speed

  • 8/10/2019 14 - Parameter Tuning

    13/24

    Figure 4.6 Comparison between Simulated Generator Voltage Response

    (Using Typical Parameters) and Site Measured Voltage

    Figure 4.7 Comparison between Simulated Generator Voltage Response

    (Using Tuned Parameters) and Site Measured Voltage

  • 8/10/2019 14 - Parameter Tuning

    14/24

    Figure 4.8 Comparison between Simulated Generator Electrical Power Response

    (Using Typical Parameters) and Site Measured Electrical Power

    Figure 4.9 Comparison between Simulated Generator Electrical Power Response

    (Using Tuned Parameters) and Site Measured Electrical Power

  • 8/10/2019 14 - Parameter Tuning

    15/24

    Figure 4.10 Comparison between Simulated Generator Field Voltage Response

    (Using Typical Parameters) and Site Measured Field Voltage

    Figure 4.11 Comparison between Simulated Generator Field Voltage Response

    (Using Tuned Parameters) and Site Measured Field Voltage

  • 8/10/2019 14 - Parameter Tuning

    16/24

    Figure 4.12 Induction Motor Load Torque Curve Fitting

    Figure 4.13 Comparison between Simulated Induction Motor Electrical Power

    Response (Using Typical Parameters) and Site Measured Electrical Power

  • 8/10/2019 14 - Parameter Tuning

    17/24

  • 8/10/2019 14 - Parameter Tuning

    18/24

    Figure 4.15 Test System for Diesel Generator Load Shed

    Figure 4.16 Exciter Model Diagram of Diesel Generator

    Parameter Typical Tuned

    KA 156 240

    KC 0.001 0.001

    KE 0.08 0.08KF 0.1 0.27

    KI 9 9

    KP 0.08 0.08

    TA 0.05 0.05

    TE 1.0 4

    TF 3.0 3.0

    TR 0.005 0.005

    Vrmax 17.5 17.5

    Vrmin -15.5 -15.5

    Table 4.3 Typical and Tuned Parameters of Exciter Model

  • 8/10/2019 14 - Parameter Tuning

    19/24

    Figure 4.17 Governor Model Diagram of Diesel Generator

    Parameter Typical Tuned

    Droop 5.0 5.0

    ThetaMax 60.0 60.0

    ThetaMin 4.0 4.0Alpha 0.04 0.027

    Beta 0.02 0.0192

    Rho 0.1 0.3

    K1 128 119

    Tau 0.1 0.09

    T1 0.15 0.151

    T2 0.12 0.12

    H 1.9 1.69

    D 4.0 7.0

    Table 4.4 Typical and Tuned Parameters of Governor Model

  • 8/10/2019 14 - Parameter Tuning

    20/24

    Figure 4.18 Comparison between Simulated Generator Frequency Response

    (Using Typical Parameters) and Site Measured Frequency

    Figure 4.19 Comparison between Simulated Generator Frequency Response

    (Using Tuned Parameters) and Site Measured Frequency

  • 8/10/2019 14 - Parameter Tuning

    21/24

    Figure 4.20 Comparison between Simulated Generator Voltage Response

    (Using Typical Parameters) and Site Measured Voltage

    Figure 4.21 Comparison between Simulated Generator Voltage Response

    (Using Tuned Parameters) and Site Measured Voltage

    4.3Network Short-Circuit Fault Test Case

    This test case is to simulate a system response when a short-circuit fault occurred on a

    bus. The test system is shown in Figure 4.22. The simulation events include: short-circuitfault occurs at MCC feeder Bus3, voltage relay trips some load at Bus-A and Bus-B when

    voltage drops to 50% during the fault, in 0.38 seconds the circuit breaker 52GH is tripped

    to disconnect fault point, in 0.8 seconds the circuit breaker 52B4 is tripped to disconnectthe tie link to utility. The actual measured current and voltage of generator G4 and

    current at branch 52B4 are displayed in Figure 4.23. The simulation responses of the

    system current and voltage for using typical generator parameters listed in Table 4.5 andusing tuned parameters listed in Table 4.5 are shown as Figure 4.24 and 4.25,

  • 8/10/2019 14 - Parameter Tuning

    22/24

    respectively. As can be seen from Figure 4.25, the response of the system current and

    voltage using tuned parameters are very close to the actual measured data.

    Bus4

    Bus- BBus2

    Bus1

    T3

    12. 5 MVA

    pump273. 936 kW

    pump3937 kW

    pump483. 175 kW

    CB4

    52B4

    52GH

    LUMP15. 848 MVA

    LUMP210. 75 MVA

    pump5

    345 kW

    LUMP34. 458 MVA

    CB5

    CB6

    LUMP410. 75 MVA

    3.3 k

    3.3 k3.3 kV

    65 kV

    3.3 kV

    Bus-A

    Bus3

    3.3 kV

    Power Gr i d

    pump173. 936 kW

    G415. 111 MW

    Figure 4.22 Test System for Short-Circuit Fault

    Parameter Typical Tuned

    Xd 1.48 0.75

    Xq 1.48 0.74

    Xd 0.215 0.15

    Xq 0.45 0.16

    Xd 0.136 0.12

    Xq 0.136 0.13

    Td0 7.05 7.05

    Tq0 1.0 1.0

    Td0 0.042 0.042

    Tq0 0.18 0.18

    H 5.4 8

    D 5 1

    Table 4.5 Typical and Tuned Parameters of Generator

  • 8/10/2019 14 - Parameter Tuning

    23/24

    Figure 4.23 Site Voltage and Current Recordings DuringShort-Circuit Fault

    Figure 4.24 Simulated Generator Voltage and Current Responses

    (Using Typical Parameters)

  • 8/10/2019 14 - Parameter Tuning

    24/24

    Figure 4.25 Simulated Generator Voltage and Current Responses

    (Using Tuned Parameters)