    HD2-DM-A

    Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

    Pepperl+Fuchs Group Tel.: Germany +49-621-776-0 USA +1-330-4253555 Singapore +65-67-799091 Internet www.pepperl-fuchs.com 1

    Fieldbus Power Hub, Advanced Diagnostic Module

    +

    +

    +

    Seg 4

    Seg 3

    Seg 2

    +

    -

    -

    -

    -

    FieldbusSeg 1

    Alarm

    screen/shield

    screen/shield

    screen/shield

    screen/shield

    -

    -

    +

    Diagnosis/ Alarm

    Diagnostic busRS-485

    +

    U

    U

    Connection

    Assembly

    Comprehensive diagnostics for fieldbus physical layer andpower supply

    Plug-in Module for the FieldConnex Power Hub Precise measurements through passive circuits For commissioning, online monitoring and troubleshooting For FOUNDATION fieldbus and PROFIBUS PA Installation in Zone 2/Class I, Div. 2 System state and fault indication via LEDs Display of data in the safety of the control room Automatic setup of diagnostic system Full software integration into DCS and PAM possible

    Function

    Designed as a plug-in module for the FieldConnex PowerHub, this Advanced Diagnostic Module (ADM) is acomprehensive measurement tool for the physical layer of upto four fieldbus segments. It's passive input circuits leave thephysical layer untouched for exact data. The ADM detectsgradual or sudden changes and helps trace even intermittentmalfunctions.The ADM supports commissioning, online monitoring andtroubleshooting. It can be integrated tightly into the DCS andPAM via a separate diagnostic bus, making the fieldbusphysical layer itself a managable asset. Configuration toolsautomate setup of the ADM and of selected DCS.The Diagnostic Manager is the software for display andoperation from the safety of the control room. TheProfessional Edition provides powerful functions and wizardssimplifying and automating work procedures: Embeddedexpert system data historian and a built-in oscilloscope areincluded. (see datasheet DTM-FC.AD*).

    Features

    R

  • 7/31/2019 131000_eng

    2/4

    R e

    l e a s e

    d a

    t e 2 0 1 0 - 1

    0 - 2 5 1 6 : 1

    3

    D a

    t e o

    f i s s u e

    2 0 1 0 - 1

    1 - 1

    2

    1 3 1 0 0 0

    _ E N G

    . x m l

    Technical data HD2-DM-A

    S ub ject to reasona b le modifications d u e to technical advances. Copyright Pepperl+F u chs, Printed in Germany

    Pepperl+F u chs Gro u p Tel.: Germany +49-621-776-0 USA +1-330-4253555 Singapore +65-67-799091 Internet www.pepperl-f u chs.com 2

    SupplyRated voltage 19.2 ... 35 VRated current 110 ... 30 mAPower loss max. 2 WFieldbus interfaceNumber of segments 4Fieldbus type FOUNDATION Fieldbus/PROFIBUS PA

    Rated voltage 9 ... 32 VIndicators/operating meansLED PRI PWR green: on, primary bulk power supply connectedLED SEC PWR green: on, secondary bulk power supply connectedLED Seg 1...4 yellow: bus activity; red 2 Hz flashing: alarm; red: hardware errorFault signal VFC alarm 1 A, 50 V DC, normally closedDIP-switch diagnostic address 1...247, binary codedInterfaceInterface type diagnostic bus: RS 485Electrical isolationFieldbus segment/Fieldbus segment functional insulation acc. to IEC 62103, rated insulation voltage 50 VeffFieldbus segment/Supply functional insulation acc. to IEC 62103, rated insulation voltage 50 VeffDirective conformity

    Electromagnetic compatibilityDirective 2004/108/EC EN 61326-1:2006Standard conformityElectromagnetic compatibility NE 21:2006Protection degree IEC 60529Shock resistance EN 60068-2-27Vibration resistance EN 60068-2-6Ambient conditionsAmbient temperature -40 ... 60 C (-40 ... 140 F)Storage temperature -40 ... 85 C (-40 ... 185 F)Relative humidity < 95 % non-condensingShock resistance 15 g 11 msVibration resistance 1 g , 10 ... 150 Hz

    Corrosion resistance acc. to ISA-S71.04-1985, severity level G3Mechanical specificationsConnection type motherboard specificCore cross-section motherboard specificHousing material PolycarbonateHousing width 18 mmHousing height 106 mmHousing depth 128 mmProtection degree IP20Mass approx. 100 gMounting motherboard mountingMating cycles 100Data for application in connection

    with Ex-areasStatement of conformity TV 04 ATEX 2500 XGroup, category, type of protection,temperature classification

    II 3G EEx nA IIC T4

    Directive conformityDirective 94/9/EC EN 60079-15:2003

    International approvalsFM approval CoC 3024816, CoC 3024816C

    Approved for Class I, Division 2, Groups A, B, C, D, T4 / Class I, Zone 2, AEx/Ex nA IIC T4Certificates and approvalsMarine approval DNV A-10798

    Statement of Conformity, Declaration of Conformity and instructions have to be observed. For information seewww.pepperl-fuchs.com.

    Supplementary information

  • 7/31/2019 131000_eng

    3/4

    R e

    l e a s e

    d a

    t e 2 0 1 0 - 1

    0 - 2 5 1 6 : 1

    3

    D a

    t e o

    f i s s u e

    2 0 1 0 - 1

    1 - 1

    2

    1 3 1 0 0 0

    _ E N G

    . x m l

    Technical data HD2-DM-A

    S ub ject to reasona b le modifications d u e to technical advances. Copyright Pepperl+F u chs, Printed in Germany

    Pepperl+F u chs Gro u p Tel.: Germany +49-621-776-0 USA +1-330-4253555 Singapore +65-67-799091 Internet www.pepperl-f u chs.com 3

    System topology

    Installation notes see manual.

    Dimensions

    1 8

    m m

    ( 0

    . 7 " )

    106 mm (4.2")

    1 2 8

    m m

    ( 5 " )

    10

    131211

    14

    15 Moduladresse1

    Bit

    ADRESSAUSWAHL/ ADDRESSSELECTION

    0

    moduleaddressModuladresse

    Bit 7 6 5 4 3 2 1 0

    10

    moduleaddress

    2

    3

    246

    247

    7 6 5 4 3 2 1 0

    Note:Themoduleaddressesareonlyvalid intherangefrom 1to 247(binarycoded).

    0

    0 0

    0

    0

    0

    0

    0 0

    0

    0 0

    0

    0

    0

    0

    0 0

    0

    1

    1

    1 1

    1

    1 1

    1 1

    1 1

    1 0

    0 1

    1 1

    1 1

    0

    Hinweis:DieModuladressensind nurim Bereichvon1 bis247g ltig (binrkodiert).

    2 2 1 m m

    ( 8

    . 7 " )

    36 mm(1.4")

    1 6 2 m m

    ( 6 . 4 " )

    110 mm (4.3")

    220 mm ( 8 .7")

    246 mm (9.7")6

    5

    7

    8

    9

    1

    2

    3

    4

    +

    - S

    S E

    G1

    +

    - S

    S E

    G2

    +

    - S

    S E

    G 3

    +

    - S

    S E

    G4

    - +

    - +

    S -+

    S E

    G 3

    O F F

    O N

    H o s t A

    H o s t B

    S -+

    S -+

    S E

    G1

    O

    F F

    O N

    H o s t A

    H o s t B

    S -+

    S -+

    S E

    G2

    O F F

    O N

    H o s t A

    H o s t B

    S -+

    S -+

    S E

    G4

    O F F

    O N

    H o s t A

    H o s t B

    S -+

    P R I

    P WR

    S E

    C P WR

    Dimensions complete red u ndant system*

    *all dimensions without toleranceindication

    Dimensions Advanced Diagnostic Mod u le*

    Description:1 Power S u pply Mod u les, see separate data sheets2 Advanced Diagnostic Mod u le3 Connections for field bu s tr u nk, terminator switch4 Screening/earthing kit for tr u nk ca b les shield, optional

    accessory5 Mo u nting slot for DIN rail6 Mother b oard, see separate data sheets7 Connections for alarm, voltage free contact and diagnostics

    bu s8 Connections for red u ndant host9 Connections for red u ndant bu lk power s u pply

    10 Pl u g connections to Mother b oard11 LED Seg 1 ... Seg 412 LED green SEC Power13 LED green PRI Power14 Dip-Switch-Array for diagnostic address or address on the

    diagnostics bu s15 Address selection overview

    Installation note

    Work-station

    ConverterEthernet -> RS 4 8 5 HD2-DM-A

    1

    S e g m e n

    t 2

    S e g m e n

    t 3

    S e g m e n

    t 4

    S e g m e n

    t 1

    HD2-DM-A

    31. . .

    . . .

    S e g m e n

    t 1 2 4

    S e g m e n

    t 1 2 3

    S e g m e n

    t 1 2 2

    S e g m e n

    t 1 2 1

  • 7/31/2019 131000_eng

    4/4

    R e

    l e a s e

    d a

    t e 2 0 1 0 - 1

    0 - 2 5 1 6 : 1

    3

    D a

    t e o

    f i s s u e

    2 0 1 0 - 1

    1 - 1

    2

    1 3 1 0 0 0

    _ E N G

    . x m l

    Technical data HD2-DM-A

    S ub ject to reasona b le modifications d u e to technical advances. Copyright Pepperl+F u chs, Printed in Germany

    Pepperl+F u chs Gro u p Tel.: Germany +49-621-776-0 USA +1-330-4253555 Singapore +65-67-799091 Internet www.pepperl-f u chs.com 4

    Software User Interface for monitoring up to or including 100 fieldbus segments: Diagnostic Manager, Professional EditionDTM-FC.AD

    Software User Interface for monitoring more than 100 fieldbus segments: Diagnostic Manager, Professional EditionDTM-FC.AD.1

    KT-MB-GT2AD Diagnostic Gateway

    Expert system Built-in expert system interprets behavior of each segment based on rules and givespointed information in clear text. Precisely diagnosis causes and suggests remedies,which are easy to understand.

    Supply input voltage The supply voltage of the primary and secondary input is measured in a range of0 V ... 40 V.

    Segment power redundancyintegrity

    The health of the primary and backup fieldbus power supply is monitored. Mismatch ofredundancy pairs is detected and causes an alarm.

    Fieldbus voltage The segment voltage is measured in a range of 0 V ... 35 V.Fieldbus current The current feed into a fieldbus segment is measured in a range of 0 A ... 1 A depending

    on the used power supply.Unbalance detection A capacitive or resistive short between any fieldbus wire and shield is measured and

    given in a range between -100% ... +100%.(-100% = short against - wire, +100% = short against +wire)

    Termination Over- and Undertermination are detected and reported.Signal level Node specific signal levels are measured in a range of 0 V ... 2.5 V.Jitter Jitter is a measurement for the timing of each bit. Each component connected (power

    supply, field instrument, cable, ...) to the segment influences jitter. It is an excellentindicator for segment health. The jitter is either segment- or device-specifically measuredin a range of 0 sec ... 8 sec.

    Signal polarity For each node the polarity of the signal modulation is given.Noise measurement Noise is measured in a frequency range between 100 Hz ... 140 kHz. Noise measurement

    is node-address-specific in order to detect device-specific noise.Communication errors statistics Segment-specific error counters, e. g. for CRC errors, framing errors.Oscilloscope function The built-in oscilloscope is a powerful tool for signal voltage behavior analysis. It allows

    for analysis of specific frames and occurring communication errors. Trigger conditions, ase. g. different frame types, CRC errors, framing errors are either node-address-specific orunspecific. The frame contents detected in the sampled period are analyzed and shown.

    Live list generation A list of all connected devices and additional status information is generated. The ADMdetects initial connection of a device to a segment in operation. A message reminds theuser to re-run the commissioning wizard.

    Alarm management For all measured values, either segment- or node-specific, alarm limits exist. In addition,warning limits can be defined. When these limits are violated, alarms are generated.

    History/trending function For up to 2 years, segment- and node-specific physical layer values can be stored andtime stamped in the Diagnostic Module, so trending analyses are possible over longerperiods of time.

    Accessories

    Functional overview