106
MANUAL MultiMode™ MOTOR CONTROLLER © 2001 CURTIS INSTRUMENTS, INC. DESIGN OF CURTIS PMC 1200 SERIES CONTROLLERS PROTECTED BY U.S. PATENT NO. 4626750. 1244 MODEL 1244 Manual, p/n 16958 Rev. B: January 2001 CURTIS PMC 235 East Airway Boulevard Livermore, California 94568 USA Tel: 925-961-1088 Fax: 925-961-1099 www.curtisinst.com

1244

  • Upload
    milerk

  • View
    216

  • Download
    1

Embed Size (px)

DESCRIPTION

curtis

Citation preview

  • MANUAL

    MultiModeMOTOR CONTROLLER

    2001 CURTIS INSTRUMENTS, INC.

    DESIGN OF CURTIS PMC 1200 SERIESCONTROLLERS PROTECTED BY U.S.PATENT NO. 4626750.

    12 4 4MODEL

    1244 Manual, p/n 16958Rev. B: January 2001

    CURTIS PMC

    235 East Airway BoulevardLivermore, California 94568 USATel: 925-961-1088Fax: 925-961-1099www.curtisinst.com

  • 1244 Manual p/n 16958, Rev. B: January 2001

    2001 CURTIS INSTRUMENTS, INC.

    CURTIS INSTRUMENTS, INC.200 KISCO AVENUE

    MOUNT KISCO, NEW YORK 10549 USA 914-666-2971 FAX 914-666-2188

    CURTIS PMC235 EAST AIRWAY BOULEVARD

    LIVERMORE, CALIFORNIA 94550 USA 925-961-1088 FAX 925-961-1099

    ADDITIONAL OFFICES located inBulgaria, China, England, France, Germany,

    India, Italy, Japan, Netherlands, PuertoRico, Russia, Sweden, and Switzerland

    www.curtisinst.com

  • Curtis PMC 1244 Manual iii

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    CONTENTS

    1. OVERVIEW ....................................................................... 1

    2. INSTALLATION AND WIRING ..................................... 4Mounting the Controller .............................................. 4Connections: Low Current .......................................... 6Connections: High Current ........................................ 7Wiring: Controller ...................................................... 8Wiring: Throttle ........................................................ 10

    5k0, 2-wire resistive throttle (Type 1) ......... 1105V, current source, 3-wire pot, and electronic

    single-ended throttles (Type 2) ................ 1205k, 2-wire resistive throttle (Type 3) ......... 1505V and 3-wire pot wigwag-style

    throttles (Type 4) ..................................... 15CAN-Nodes throttle (Type 5) ......................... 16

    Wiring: Fault Outputs .............................................. 16Wiring: Contactor Drivers ........................................ 16Wiring: Pedal Switch ................................................. 19Wiring: Hour Meter .................................................. 19Wiring: CAN Bus Interface ....................................... 19Wiring: Emergency Reverse ....................................... 19Contactor, Switches, and Other Hardware ................. 21

    3. PROGRAMMABLE PARAMETERS ............................... 23Acceleration Parameters .............................................. 26

    Acceleration Rate, M1M4 ................................. 26Braking Rate, M1M4 ........................................ 26Deceleration Rate ................................................ 26Quick Start ......................................................... 26Taper Rate .......................................................... 27

    Speed Parameters ....................................................... 27Maximum Speed, M1M4 ................................. 27Creep Speed, M1M4......................................... 27Regen Speed ........................................................ 27

    Throttle Parameters .................................................... 28Control Mode ..................................................... 28Throttle Type ..................................................... 29

    CONTENTS

  • Curtis PMC 1244 Manual iv

    CONTENTS

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    Throttle Deadband ............................................. 30Throttle Max ...................................................... 32Throttle Map, M1M4 ....................................... 34Throttle Braking Percent, M1M4 ..................... 36

    Current Limit Parameters ........................................... 36Drive Current Limit, M1M4 ............................ 36Braking Current Limit, M1M4 ......................... 36Minimum Field Current Limit ........................... 36Maximum Field Current Limit ........................... 37Restraint .............................................................. 37Emergency Reverse Current Limit ...................... 38Current Ratio ...................................................... 38

    Field Control Parameters ........................................... 38Field Map Start ................................................... 38Field Map ........................................................... 39

    Fault Parameters ......................................................... 41High Pedal Disable (HPD) ................................. 41Static Return to Off (SRO) ................................. 41Fault Code .......................................................... 42

    Output Driver Parameters .......................................... 43Main Contactor Driver Interlock ........................ 43Main Contactor Dropout Delay ......................... 43Main Coil Open Check ...................................... 44Main Contactor Weld Check .............................. 44Auxiliary Driver Dropout Delay ......................... 44Auxiliary Coil Open Check ................................. 44Reverse Signal Open Check ................................ 45Electromagnetic Brake Delay .............................. 45Electromagnetic Brake Open Check ................... 45Contactor Holding Voltage ................................. 46Contactor Pull-in Voltage ................................... 46

    Other Parameters ....................................................... 46Battery Voltage ................................................... 46Anti-Tiedown ..................................................... 47Sequencing Delay ................................................ 47Pedal Interlock .................................................... 47Emergency Reverse Enable .................................. 48Emergency Reverse Check .................................. 48Node Address ...................................................... 48

  • Curtis PMC 1244 Manual v

    Precharge ............................................................ 49Load Compensation ............................................ 49

    4. OEM-SPECIFIED, FACTORY-SET PARAMETERS ..... 50MultiMode Enable ................................................ 50Accessory Driver Enable ............................................. 50CAN Bus Enable ........................................................ 51

    5. INSTALLATION CHECKOUT ..................................... 52

    6. VEHICLE PERFORMANCE ADJUSTMENT ............... 54Major Tuning ............................................................ 54

    Tuning the active throttle range .......................... 54Tuning the controller to the motor ..................... 57Setting the unloaded vehicle top speed ................ 59Equalizing loaded and unloaded vehicle speed .... 60

    Fine Tuning ............................................................... 62Response to increased throttle ............................. 62Response to reduced throttle ............................... 63Smoothness of direction transitions .................... 63Ramp climbing ................................................... 65Ramp restraint .................................................... 66

    7. PROGRAMMER OPERATION ..................................... 67Programmer Operating Modes ................................... 69Peace-of-Mind Programming ..................................... 71Programmer Menus .................................................... 73

    8. DIAGNOSTICS AND TROUBLESHOOTING ............ 78Programmer Diagnostics ............................................ 78LED Diagnostics ........................................................ 80Fault Output Drivers ................................................. 81

    9. MAINTENANCE ............................................................ 82Cleaning ..................................................................... 82Diagnostic History ..................................................... 82

    APPENDIX A Glossary of Features and Functions ............. A-1APPENDIX B Throttle Mounting Dimensions .................. B-1APPENDIX C Specications ............................................... C-1

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    12345678901

    CONTENTS

  • Curtis PMC 1244 Manual vi

    FIGURES

    FIG. 1: Curtis PMC 1244 electronic motor controller ....................... 1

    FIG. 2: Mounting dimensions, Curtis PMC 1244 controller .............. 4

    FIG. 3: Standard wiring conguration ................................................ 8

    FIG. 4: Wiring for 5k0 throttle (Type 1) ................................. 11

    FIG. 5: Wiring for wigwag throttle,using the 5k0 throttle input (Type 1) .......................... 11

    FIG. 6: Wiring for 05V throttle (Type 2) .................................... 12

    FIG. 7: Wiring for 3-wire potentiometer throttle (Type 2) ............ 13

    FIG. 8: Wiring for current source throttle (Type 2) ...................... 13

    FIG. 9: Wiring for Curtis ET-XXX electronic throttle (Type 2) .... 14

    FIG. 10: Wiring for 05k throttle (Type 3) ................................. 15

    FIG. 11: Wiring for fault outputs ....................................................... 16

    FIG. 12: Wiring for main and auxiliarycontactor coils when using theinterlock and dropout delay features ..................................... 18

    FIG. 13: Wiring for emergency reverse(applicable to walkie vehicles only) ....................................... 20

    FIG. 14: Effect of adjusting the neutral deadband parameter ........ 30, 31

    FIG. 15: Effect of adjusting the throttle max parameter ................ 32, 33

    FIG. 16: Throttle maps for controllerwith maximum speed set at 100%and creep speed set at 0 ........................................................ 34

    FIG. 17: Throttle maps for controllerwith maximum speed set at 80%and creep speed set at 10% ................................................... 35

    FIGURES

  • Curtis PMC 1244 Manual vii

    FIGURES / TABLES

    FIGURES, contd

    FIG. 18: Influence of various parameters oncontroller output response to throttle demand .................. 35

    FIG. 19: Field current relative to armature current,with eld map parameter set at 50% and 20% .................. 40

    FIG. B-1: Mounting dimensions, Curtis PMC standard5k, 3-wire throttle pot .................................................. B-1

    FIG. B-2: Mounting dimensions, Curtis PMC potboxes ................. B-1

    FIG. B-3: Mounting dimensions, Curtis PMC footpedal ................ B-2

    FIG. B-4: Mounting dimensions, Curtis electronic throttle ............. B-2

    TABLES

    TABLE 1: Voltages at throttle wiper input ....................................... 10

    TABLE 2: Mode selection ................................................................ 22

    TABLE 3: Programmable throttle types ............................................ 29

    TABLE 4: Fault categories ................................................................ 43

    TABLE 5: Troubleshooting chart ..................................................... 79

    TABLE 6: Status LED fault codes .................................................... 80

    TABLE 7: Fault category codes ......................................................... 81

    TABLE C-1: Specications, 1244 controller ................................... C-1

  • Curtis PMC 1244 Manual 1

    1 OVERVIEW

    OVERVIEW

    Curtis PMC 1244 MultiMode controllers are separately excited motor speedcontrollers designed for use in a variety of material handling vehicles. Theseprogrammable controllers are simple to install, efcient, and cost effective.Typical applications include low lifts, stackers, fork lifts, reach trucks, personnelcarriers, counterbalance trucks, order pickers, boom trucks, and other industrialvehicles.

    1Fig. 1 Curtis PMC1244 MultiModeelectronic motorcontroller.

    The 1244 MultiMode controller offers smooth, silent, cost effectivecontrol of motor speed and torque. A four quadrant, full-bridge eld windingcontrol stage is combined with a two quadrant, half-bridge armature power stageto provide solid state motor reversing and regenerative braking power withoutadditional relays or contactors. The 1244 controller can also be specied to becompatible with CAN Bus communication systems.

    These controllers are fully programmable by means of the optional handheld1307 programmer. Use of the programmer provides diagnostic and test capabil-ity as well as conguration flexibility.

  • Curtis PMC 1244 Manual 2

    1 OVERVIEW

    Like all Curtis PMC motor controllers, the 1244 offers superior operator controlof the vehicles motor drive speed. Features include:

    Full-bridge eld and half-bridge armature power MOSFET design,providing

    innitely variable forward, reverse, drive, and brake control silent high frequency operation high efciency

    Regenerative braking, providing longer operation on a single battery chargeand reducing motor brush wear and motor heating

    Programmability through the 1307 handheld programmer

    Complete diagnostics through the 1307 programmer and the internal StatusLED

    Two fault outputs provide diagnostics to remotely mounted displays

    Continuous armature current control, reducing arcing and brush wear

    Automatic braking when throttle is reduced from either direction; thisprovides a compression braking feel and enhances safety by automaticallyinitiating braking in an operator hands off condition

    Deceleration Rate, Load Compensation, and Restraint features preventdownhill runaway conditions; speed is controlled to within approximately20% of level surface value

    MultiMode allows four user-selectable vehicle operating personalities

    Programmable to match individual separately excited motor characteristics

    Meets or exceeds EEC fault detect requirements

    Vehicle top speed is controlled and limited in each mode

    Linear temperature and undervoltage cutback on motor currents; no suddenloss of power under any thermal conditions

    High pedal disable (HPD) and static return to off (SRO) interlocks preventvehicle runaway at startup

    Creep speed adjustable from 0% to 25% in each mode

    Continuous diagnostics during operation, with microprocessor power-onself-test

  • Curtis PMC 1244 Manual 3

    Internal and external watchdog circuits ensure proper software operation

    Programmable coil drivers provide adjustable contactor pull-in and holdingvoltages

    Hour-meter enable output is active whenever the controller is providingmotor current

    Optional Electromagnetic Brake Driver provides automatic control of anelectromagnetic brake or other similar function

    Optional Reverse Signal Driver provides a low signal any time the vehicle isdriving or braking in reverse

    Optional Auxiliary Driver provides a low signal to power an auxiliarycontactor or other similar function

    Driver outputs are short circuit protected and provide built-in coil spikeprotection

    Controller is programmable to provide throttle control of motor speed,applied motor voltage, or motor torque

    Can be congured for CAN Bus compatibility.

    Familiarity with your Curtis PMC controller will help you install and operate itproperly. We encourage you to read this manual carefully. If you have questions,please contact the Curtis ofce nearest you.

    1 OVERVIEW

  • Curtis PMC 1244 Manual 4

    INSTALLATION AND WIRING

    MOUNTING THE CONTROLLERThe outline and mounting hole dimensions for the 1244 controller are shown inFigure 2.

    The controller can be oriented in any position, and meets the IP64/IP67ratings for environmental protection against dust and water. However, thelocation should be carefully chosen to keep the controller as clean and dryas possible. When selecting the mounting position, be sure to also take into

    22 INSTALLATION & WIRING: Controller

    Fig. 2 Mountingdimensions, Curtis PMC1244 controller.

    Dimensions in millimeters (and inches)

    9.5(0.375)

    12.7(0.50)

    STATUSLED

    M8 thread, 3 plcs

    M6 thread, 2 plcs

    7.1 (0.28) dia.,4 plcs

    159(6.25)

    178(7.00)

    81(3.19)

    210 (8.25)

    229 (9.00)

  • Curtis PMC 1244 Manual 5

    2 INSTALLATION & WIRING: Controller

    consideration (1) that access is needed at the top of the controller to plug theprogrammer into its connector, and (2) that the built-in Status LED is visibleonly through the view port in the label on top of the controller.

    To ensure full rated power, the controller should be fastened to a clean, flatmetal surface with four 6 mm (1/4") diameter screws, using the holes provided.Although not usually necessary, a thermal joint compound can be used toimprove heat conduction from the controller heatsink to the mounting surface.

    C A U T I O N Working on electric vehicles is potentially dangerous. You should protectyourself against runaways, high current arcs, and outgassing from lead acidbatteries:

    RUNAWAYS Some conditions could cause the vehicle to run out of control.Disconnect the motor or jack up the vehicle and get the drive wheels off theground before attempting any work on the motor control circuitry. NOTE: Ifthe wrong throttle type is selected with the handheld programmer, thevehicle may suddenly begin to move.

    HIGH CURRENT ARCS Electric vehicle batteries can supply very highpower, and arcs can occur if they are short circuited. Always open the batterycircuit before working on the motor control circuit. Wear safety glasses, anduse properly insulated tools to prevent shorts.

    LEAD ACID BATTERIES Charging or discharging generates hydrogen gas,which can build up in and around the batteries. Follow the batterymanufacturers safety recommendations. Wear safety glasses.

  • Curtis PMC 1244 Manual 6

    CONNECTIONSLow Current ConnectionsThree low current connectors are built into the 1244 controller. They are locatedin a row on the top of the controller:

    2 INSTALLATION & WIRING: Controller

    Pin 1 keyswitch input (KSI)Pin 2 interlock inputPin 3 Mode Select 1 inputPin 4 Mode Select 2 inputPin 5 Fault 1 outputPin 6 Fault 2 outputPin 7 emergency reverse inputPin 8 pedal switch inputPin 9 coil return inputPin 10 forward inputPin 11 reverse inputPin 12 hour meter enable output

    Pin 13 throttle: 3-wire pot highPin 14 throttle: pot lowPin 15 throttle: 3-wire pot wiper or 05VPin 16 throttle: 2-wire 5k0 or 05k inputPin 17 main contactor driver outputPin 18 auxiliary contactor driver outputPin 19 reverse signal driver outputPin 20 electromagnetic brake driver outputPin 21 (not used)Pin 22 emergency reverse check outputPin 23 (not used)Pin 24 (not used)

    24 23 22 21 20 19 18 17 16 15 14 13

    12 11 10 9 8 7 6 5 4 3 2 1

    The 24-pin connector provides the logic control connections. The matingconnector is a 24-pin Molex Mini-Fit Jr. connector part number 39-01-2245using type 5556 terminals.

    24-pin 6-pin 4-pin

  • Curtis PMC 1244 Manual 7

    F1

    B- B+M-

    F2

    STATUSLED

    CABLE-FREE ZONES

    2 INSTALLATION & WIRING: Controller

    A 6-pin low power Molex connector is provided for the CAN Bus interface.However, the CAN Bus option must be specied for this interface to be active.The mating connector is a Molex Mini-Fit Jr. p/n 39-01-2065 using type 5556terminals.

    456

    123

    Pin 1 +15V supply (limited)Pin 2 ground return (B-)Pin 3 CAN H I/O line

    Pin 4 L terminationPin 5 H terminationPin 6 CAN L I/O line

    Power cables must not be routed over the indicated areas. Otherwise they mayinterfere with the proper operation of sensitive electromagnetic componentslocated underneath.

    The +15V supply should only be used with the CAN system or speed sensor andnot to power any other external systems.

    The L and H terminations provide a 120 termination impedance for theCAN H I/O and CAN L I/O inputs if necessary. Refer to the Curtis CANProtocol Document to determine the proper termination for a given application.

    A 4-pin low power connector is provided for the handheld 1307 programmer. Acomplete programmer kit with the appropriate connecting cable can be ordered:

    Curtis p/n 168961101 for the User Programmer (model 1307M-1101)Curtis p/n 168962101 for the OEM Programmer (model 1307M-2101).

    If a programmer is already available but has an incompatible cable, the 1244mating cable can be ordered as a separate part: Curtis PMC p/n 16185.

    High Current ConnectionsFive tin-plated solid aluminum bus bars are provided for the high currentconnections to the battery (B+ and B-), the motor armature (M-), and the motoreld (F1 and F2). These bus bars incorporate threaded mounting studs designedto accept mounting bolts. The B+, B-, and M- bus bars are threaded to accept M8

    bolts to a depth of 3/4". The F1 and F2 bus bars are threaded to acceptM6 bolts to a depth of 5/8". This simplies the assemblyand reduces the mounting hardware necessary for thepower connections. The tightening torque applied tothe bolts should not exceed 16.3 Nm (12 ft-lbs) for theM6 bolts or 20 Nm (15 ft-lbs) for the M8 bolts.Exceeding these specications could damage the busbars internal threads, resulting in loose connections.

    C A U T I O N

  • Curtis PMC 1244 Manual 8

    2 INSTALLATION & WIRING: Controller

    WIRING: Standard ConfigurationFigure 3 shows the typical wiring conguration for most applications. Theinterlock switch is typically a seat switch, tiller switch, or foot switch.

    Standard Power WiringMotor armature winding is straightforward, with the armatures A1 connectiongoing to the controllers B+ bus bar and the armatures A2 connection going tothe controllers M- bus bar.

    The motors eld connections (F1 and F2) to the controller are less obvious.The direction of vehicle travel with the forward direction selected will depend on

    Fig. 3 Standard wiring configuration, Curtis PMC 1244 controller.

    B- B+M- F2F1INTERLOCK

    5 k0 THROTTLE(TYPICAL)

    FORWARD

    MAINCONTACTOR

    COIL

    POLARITYPROTECTION

    DIODE

    REVERSE

    MODE SELECT 2

    MODE SELECT 1

    B+B-

    KEYSWITCH

    POWERFUSE

    AMAIN

    CONTACTORA2 A1

    F1 F2CONTROL

    FUSE

  • Curtis PMC 1244 Manual 9

    2 INSTALLATION & WIRING: Controller

    how the F1 and F2 connections are made to the controllers two eld terminalsand how the motor shaft is connected to the drive wheels through the vehiclesdrive train.

    Standard Control WiringWiring for the input switches and contactors is shown in Figure 3; the connectoris shown in more detail below.

    The main contactor coil must be wired directly to the controller as shown inFigure 3. The controller can be programmed to check for welded or missing maincontactor faults and uses the main contactor coil driver output to remove powerfrom the controller and motor in the event of various other faults. If the maincontactor coil is not wired to Pin 17, the controller will not be able to openthe main contactor in serious fault conditions and the system will thereforenot meet EEC safety requirements.

    12 11 10 9 8 7 6 5 4 3 2 1

    24 23 22 21 20 19 18 17 16 15 14 13

    INTERLOCK

    ELECTRO-MAGNETIC

    BRAKEDRIVER

    REVERSESIGNALDRIVER

    EMERGENCYREVERSE

    CHECK(factory option)

    FAULT2

    FAULT1

    HOURMETER

    REVERSE

    24-pin detail (see Fig. 3):

    EMERGENCYREVERSE

    (walkies only)

    AUXCONTACTOR

    DRIVER

    MAINCONTACTOR

    DRIVER

    POTWIPER

    POTHIGH

    POTLOW

    2-WIREPOT

    (5 k)

    PEDALSWITCH

    KEYSWITCHINPUT (KSI)

    FORWARDMODE

    SELECT2

    MODESELECT

    1COIL

    RETURN

  • Curtis PMC 1244 Manual 10

    2 INSTALLATION & WIRING: Throttle

    WIRING: ThrottleVarious throttles can be used with the 1244 controller. They are categorized asone of ve types in the programming menu of the handheld programmer.

    Type 1: two-wire 5k0 throttlesType 2: 05V throttles, current source throttles, three-wire potentiometer

    throttles, and electronic throttleswired for single-ended operationType 3: two-wire 05k throttlesType 4: 05V and three-wire potentiometer throttleswired for wigwag-

    style operationType 5: CAN-Nodes throttles

    The operating specications for these throttle types are summarized in Table 1.

    All throttle fault protection is accomplished by monitoring the wiper input. Thisprovides throttle fault protection that meets all EEC requirements. Thus, noadditional fault protection is required on any throttle type used with the 1244controller.

    Table 1 THROTTLE WIPER INPUT: THRESHOLD VALUESMINIMUM THROTTLE HPD THROTTLE MAXIMUM

    THROTTLE THROTTLE DEADBAND (25% throttle MAX THROTTLETYPE PARAMETER FAULT (0% throttle) (active range) (100% modulation) FAULT

    1 Wiper Voltage 0.1 V 3.3 V 1.0 V 0.2 V 4.4 VWiper Resistance 5.0 k 3.8 k 0 k 7.5 k

    2 Wiper Voltage (none) 0.2 V 1.4 V 5.0 V 5.5 VWiper Resistance

    3 Wiper Voltage 0.1 V 0.2 V 1.0 V 3.3 V 4.4 VWiper Resistance 0 k 1.3 k 5.0 k 7.5 k

    4 Wiper Voltage 0.5 V 2.5 V (fwd)* 3.1 V (fwd) 4.4 V (fwd) 4.5 V2.5 V (rev)* 1.9 V (rev) 0.6 V (rev)

    Wiper Resistance 0.5 k 2.5 k (fwd)* 3.1 k (fwd) 4.4 k (fwd) 4.5 k2.5 k (rev)* 1.9 k (rev) 0.6 k (rev)

    5 Wiper Voltage N/A N/A N/A N/A N/AWiper Resistance N/A N/A N/A N/A N/A

    Notes: The Upper and Lower Deadbands are valid for nominal 5k potentiometers or 5V sourceswith the default Throttle Deadband and Throttle Max parameter settings of 0% and 100%respectively. These values will change with variations in the Throttle Deadband andThrottle Max parameter settingssee Section 3, pages 30 and 32.The HPD threshold is 25% of the active throttle range and is dependent on the pro-grammed Throttle Deadband and Throttle Max settings.* With 0% Throttle Deadband, there is no neutral point on a Type 4 throttle. It isrecommended that an 8% minimum deadband be used with Type 4 throttles.

  • Curtis PMC 1244 Manual 11

    2 INSTALLATION & WIRING: Throttle

    Wiring for various throttles is described below. NOTE: In the text, throttlesare identied by their nominal range and not by their actual operating range.

    If the throttle you are planning to use is not covered, contact the Curtisofce nearest you.

    5k0 Throttle (Type 1)The 5k0 throttle (called a Type 1 throttle in the programming menu of thehandheld programmer) is a 2-wire resistive throttle that connects between the2-Wire Pot and Pot Low pins (Pins 16 and 14), as shown in Figure 4. It doesntmatter which wire goes on which pin. For Type 1 throttles, zero speed corre-sponds to a nominal 5 k measured between the two pins and full speedcorresponds to 0. (NOTE: This wiring is also shown in the standard wiringdiagram, Figure 3.)

    Fig. 4 Wiring for 5k0throttle (Type 1).

    In addition to accommodating the basic 5k0 throttle, the Type 1 throttlecan also be used to implement a wigwag-style throttle. Using a 20k pot wiredas shown in Figure 5, the pot wiper can be set such that the controller has 5 kbetween Pins 16 and 14 when the throttle is in the neutral position. The throttlemechanism can then be designed such that rotating it either forward or backdecreases the resistance between Pins 16 and 14, which increases the controlleroutput. The throttle mechanism must provide signals to the controllers forwardand reverse inputs independent of the throttle pot resistance. The controller will

    Fig. 5 Wiring for 20kpotentiometer used as partof a wigwag-style throttle(Type 1).

    14 1315161718192021222324

    12 11 10 9 8 7 6 5 4 3 2 1

    5k0

    Pin 16Pin 14

    2-Wire PotPot Low

    PIN KEY

    FASTER

    14 1315161718192021222324

    12 11 10 9 8 7 6 5 4 3 2 1

    20 kPin 16Pin 14

    2-Wire PotPot Low

    PIN KEY

    FASTERFASTER

  • Curtis PMC 1244 Manual 12

    2 INSTALLATION & WIRING: Throttle

    not sense direction from the pot resistance with Throttle Type 1. For truewigwag-style controlwithout the necessity of providing independent forwardand reverse input signalssee Throttle Type 4.

    If the total resistance between Pins 14 and 16 is greater than 7.5 k, thecontrollers 4.4 V upper fault limit will be exceeded and the controller output willbe disabled. This provides broken wire protection, and also serves as an indica-tion that the potentiometers nominal value has increased and the pot needs to bereplaced.

    05V, 3-Wire Potentiometer, Current Source,and Electronic Single-Ended Throttles (Type 2)With these throttles (Type 2 in the programming menu) the controller looksfor a voltage signal at the wiper input (Pin 15). Zero speed will correspond to 0Vand full speed to 5 V. A 3-wire pot, voltage source, voltage sensor, or currentsource can be used with this throttle type. The wiring for each is slightly different.

    05V ThrottleTwo ways of wiring the 05V throttle are shown in Figure 6. The active range forthis throttle is from 0.2V (at 0% Throttle Deadband) to 5.0 V (at 100% ThrottleMax), measured relative to B-.

    Fig. 6 Wiring for05V throttles (Type 2).

    (b) Ground-referenced05V throttle

    (a) Sensor-referenced05V throttle

    14 1315161718192021222324

    12 11 10 9 8 7 6 5 4 3 2 1

    14 1315161718192021222324

    12 11 10 9 8 7 6 5 4 3 2 1+

    -

    +

    B- Pin 15 05V InputPIN KEY

    Pin 15Pin 14

    05V InputPot Low

    PIN KEY

    SENSOR GROUND

    SEN

    SOR

    OU

    TPU

    T (0

    5V)

    SE

    NS

    OR

  • Curtis PMC 1244 Manual 13

    2 INSTALLATION & WIRING: Throttle

    3-Wire Potentiometer (1k10k) ThrottleThe 3-wire potentiometer is used in its voltage divider mode, with the voltagesource and return being provided by the 1244 controller. Pot High (Pin 13)provides a current limited 5V source to the pot, and Pot Low (Pin 14) providesthe return path. The pot wiper is then connected to the Wiper Input (Pin 15).If a 3-wire pot is used in the application, the controller will provide full throttlefault protection in accordance with EEC requirements. Potentiometers with totalresistance values between 1k and 10k can be used with Throttle Type 2.Wiring is shown in Figure 7.

    Fig. 7 Wiring for 3-wirepotentiometer throttle(Type 2).

    14 1315161718192021222324

    12 11 10 9 8 7 6 5 4 3 2 1OFFON

    1k10k

    Pin 15Pin 14Pin 13

    Pot WiperPot LowPot High

    PIN KEY

    Current Sources As ThrottlesA current source can also be used as a throttle input, as shown in Figure 8. Aresistor, Rthrottle, must be used to convert the current source value to a voltage. Theresistor should be sized to provide a 05V signal variation over the full currentrange.

    Fig. 8 Wiring for currentsource throttle (Type 2).

    14 1315161718192021222324

    12 11 10 9 8 7 6 5 4 3 2 1R throttleI source

    B-B-

    Pin 15 05V InputPIN KEY

  • Curtis PMC 1244 Manual 14

    2 INSTALLATION & WIRING: Throttle

    Fig. 9 Wiring for CurtisET-XXX electronic throttle(Type 2).

    Curtis ET-XXX Electronic ThrottleThe Curtis ET-XXX (manufactured by Hardellet) provides a 05V throttle andforward/reverse inputs for the 1244 controller. Wiring for the ET-XXX is shownin Figure 9.

    The ET-XXX can be integrated into a control head to provide wigwag-stylethrottle control. Alternatively, a complete control head assembly is available fromCurtis. This control head assemblythe CH seriescombines the ET-XXXthrottle with a variety of standard control head switch functions for use in walkieand lift truck applications.

    14 1315161718192021222324

    12 11 10 9 8 7 6 5 4 3 2 1

    GREEN

    ORANGE

    BLACK

    BLACK/WHITE

    WHITE

    WHT/BRN

    B+

    KEYSWITCH

    connector

    WHT/GRN

    Pin 15Pin 11Pin 10Pin 1

    05V InputReverseForwardKSI Input

    PIN KEY

    B-

    ET-XXX

    B-

  • Curtis PMC 1244 Manual 15

    2 INSTALLATION & WIRING: Throttle

    05k Throttle (Type 3)The 05k throttle (Type 3 in the programming menu) is a 2-wire resistivethrottle that connects between the 2-Wire Pot and Pot Low pins (Pins 16 and 14)as shown in Figure 10. Zero speed corresponds to 0 measured between the twopins and full speed corresponds to 5 k. This throttle type is not appropriate foruse in wigwag-style applications.

    Fig. 10 Wiring for05k throttle(Type 3).

    If the total resistance between Pins 14 and 16 is greater than 7.5 k, thecontrollers 4.4 V upper fault limit will be exceeded and the controller output willbe disabled. This provides broken wire protection, and also serves as an indica-tion that the potentiometers nominal value has increased and the pot needs to bereplaced.

    05V and 3-Wire Potentiometer Wigwag-Style Throttles (Type 4)With these throttles (Type 4 in the programming menu) the throttle can beused in true wigwag style. Any potentiometer value between 1 k and 10 k issupported. If a 5k potentiometer is used, the neutral point will be with the wiperat 2.5 k (measured between the Pot Wiper and Pot Low pins [Pins 15 and 14]).The controller will provide increasing speed in the forward direction as the wiperis moved toward Pot High, with maximum forward speed reached at 4.5 k. Thecontroller will provide increasing speed in the reverse direction as the wiper ismoved toward Pot Low, with maximum reverse speed reached at 0.5 k.

    A 05V voltage source can also be used as the wiper input (see Figure 6).However, the minimum and maximum wiper voltage must not exceed the 0.5Vand 4.5V fault limits.

    With a Type 4 throttle, no direction signals to the controllers forward andreverse inputs are required. Direction is determined by the wiper input value.The throttle interface to the controller is similar to that for Type 2 throttles.

    14 1315161718192021222324

    12 11 10 9 8 7 6 5 4 3 2 1

    05k

    Pin 16Pin 14

    2-Wire PotPot Low

    PIN KEY

    FASTER

  • Curtis PMC 1244 Manual 16

    2 INSTALLATION & WIRING: Fault Outputs and Contactor Drivers

    CAN-Nodes Throttle (Type 5)The Type 5 throttle option is designed for use with CAN-based controlsystems. No connections are required to the throttle input pins (Pins 1316) ordirection pins (Pins 10 and 11), because all communications are handled throughthe 6-pin CAN-Nodes interface connector. Details on how to combine a giventhrottle with the CAN-Nodes system are provided in the Curtis CAN ProtocolDocument. Fault detection for Type 5 throttles is handled by the CAN CRC(Cyclic Redundancy Check) function, which is part of each node in the CAN Busarchitecture.

    WIRING: Fault OutputsThe 1244 controller has two fault output drivers, at Pin 5 and Pin 6, which canbe used to provide diagnostic information either to a display panel on the vehicleor to a remote location. These outputs are rated at 10mA maximum current at thenominal battery pack voltage. For information on programming these outputs,see Section 3: Programmable Parameters.

    Wiring for the Fault 1 and Fault 2 outputs is shown in Figure 11.

    Fig. 11 Wiring for faultoutputs.

    Fault 1

    Pin 6Pin 5

    Fault 2 OutputFault 1 Output

    PIN KEY

    Fault 2

    14 1315161718192021222324

    12 11 10 9 8 7 6 5 4 3 2 1

    +

    B-

    -

    WIRING: Contactor DriversThe 1244 controller provides contactor coil drivers (at Pins 1720) for the maincontactor, auxiliary contactor, reverse signal, and electromagnetic brake func-tions. These four outputs are low side drivers, designed to energize contactor coils.The auxiliary, reverse signal, and electromagnetic brake drivers are optionalfunctions. They are available only if the Accessory Driver option is speciedseeSection 4, page 50.

    It is not necessary to specify the contactors coil voltage at the nominalbattery pack voltage as long as the Contactor Pull-In Voltage and ContactorHolding Voltage parameters are programmed to accommodate the coils voltage

  • Curtis PMC 1244 Manual 17

    2 INSTALLATION & WIRING: Contactor Drivers

    rating. However, all coil voltage ratings should be the same, since only one valueof pull-in and holding voltage can be specied for all four of the drivers.

    The driver outputs are rated at 2 amps and overcurrent protected at 3 amps.The controller can be programmed to check for missing coil faults. These checkscan be disabled using a 1307M-2101 programmersee Section 3, pages 44 and45. A coil suppression diode is provided internally to protect the drivers frominductive spikes generated at turn-off. To take advantage of the controllersinternal coil suppression diode, Pin 9 must be wired such that the return path tothe contactor drivers cannot be opened by any switches or contactors.

    The driver loads are not limited to contactor coils. Any load can beconnected to a Pin 1720 driver as long as it does not exceed the drivers 2 ampcurrent rating.

    For information on programming the various contactor-related parameters,see Section 3: Programmable Parameters.

    Main Contactor DriverIn the standard conguration, the main contactor driver (Pin 17) pulls low whenthe keyswitch input is enabled; this wiring is shown in the standard wiringdiagram (Figure 3, page 8).

    Alternatively, the main contactor driver can be programmed not to pull lowuntil the interlock input as well as the keyswitch input is enabled. To do this, theMain Contactor Driver Interlock parameter must be set to On. If the MainContactor Driver Interlock parameter is On, the Main Contactor DropoutDelay parameter can be set to allow the main contactor to remain engaged for upto 40 seconds after the interlock signal has been disabled. If the interlock anddelay functions are used, the main contactor and the coil return (Pin 9) mustboth be wired to KSI. This alternative wiring is shown in Figure 12.

    Auxiliary Contactor DriverLike the main contactor driver, the auxiliary contactor driver (Pin 18) pulls lowwhen the interlock input is enabled. The output will be pulse-width-modulatedat the coil holding voltage along with the main, reverse signal, and electromag-netic brake contactor drivers, if the Holding Voltage parameter is set to less than100%.

    If desired, the Auxiliary Contactor Dropout Delay parameter can be set toallow the auxiliary contactor to remain engaged for up to 40 seconds after theinterlock signal has been disabled. If the delay function is used, the auxiliarycontactor and the coil return (Pin 9) must both be wired to KSI rather than theinterlock input. This alternative wiring is shown in Figure 12.

  • Curtis PMC 1244 Manual 18

    Fig. 12 Wiring for main,auxiliary, reverse signal,and electromagnetic brakecontactor coils, using theinterlock and dropoutdelay functions.

    2 INSTALLATION & WIRING: Contactor Drivers

    Reverse Signal DriverThe reverse signal driver (Pin 19) pulls low when the vehicle is moving in thereverse direction, either in drive or in braking mode. This driver is designed todrive a reverse signal beeper or warning lamp that operates when one input ispulled low. The output will be pulse-width-modulated at the coil holding voltagealong with the main, auxiliary, and electromagnetic brake contactor drivers, if theholding voltage parameter is set to less than 100%.

    Electromagnetic Brake DriverThe electromagnetic brake driver (Pin 20) pulls low when the controller receivesa throttle request or detects that the vehicle is still in braking mode. If desired, the

    14 1315161718192021222324

    12 11 10 9 8 7 6 5 4 3 2 1

    Pin 20Pin 19Pin 18Pin 17Pin 9Pin 2Pin 1

    Electromagnetic BrakeReverse SignalAuxiliary ContactorMain ContactorCoil ReturnInterlock InputKSI Input

    PIN KEY

    MAINCONTACTOR

    COIL

    KEYSWITCH

    +

    ELECTROMAGNETIC BRAKECONTACTOR

    COIL

    INTERLOCK

    AUXILIARYCONTACTOR

    COIL

    REVERSE SIGNALCONTACTOR

    COIL

    B-

  • Curtis PMC 1244 Manual 19

    Brake Delay parameter can be set to allow the brake to remain disengaged for upto 5 seconds after braking to neutral has been completed. If the delay function isused, the brake driver and the coil return (Pin 9) must both be wired to KSI ratherthan the interlock input. This alternative wiring is shown in Figure 12.

    If the Throttle Braking parameter has been set to zero, the brake delay timebegins when the throttle is returned to neutral and the PWM output deceleratesto zero. The output will be pulse-width-modulated at the coil holding voltagealong with the main, auxiliary, and reverse signal contactor drivers, if the holdingvoltage parameter is set to less than 100%.

    WIRING: Pedal SwitchWhen the Pedal Switch option is enabled, controller output is possible only whenthe pedal input (Pin 8) is pulled to B+. This feature allows a switch connected tothe throttle mechanism to guarantee zero controller output when the operatorreleases the throttle. This adds a safety feature to protect against throttle failuresthat cause controller output when the throttle is in neutral.

    Alternatively, the pedal input can be wired into the brake pedal circuit toautomatically force zero controller output when the brake pedal is depressed,regardless of throttle request.

    WIRING: Hour MeterThe hour meter output (Pin 12) pulls to B+ to enable an hour meter whenevercurrent is flowing in the motor. This allows accurate accumulation of vehicleoperating hours. The output is current limited to 20 mA, and is compatible withCurtis 700 and 800 series hour meters. For wiring, consult the documentationsupplied with the hour meter.

    WIRING: CAN Bus InterfaceRefer to the Curtis CAN Protocol Document for information about the CANBus interface.

    WIRING: Emergency ReverseIf you are installing a 1244 controller in a walkie vehicle, the emergency reverseswitch should be wired to Pin 7, as shown in Figure 13. Emergency reverse isactivated when the keyswitch is On and the emergency reverse input is pulled to

    2 INSTALLATION & WIRING: Misc. Features

  • Curtis PMC 1244 Manual 20

    2 INSTALLATION & WIRING: Misc. Features

    B+ by closing the emergency reverse switch. After the emergency reverse switchis released, normal controller operation is not resumed until neutral (no direction)is selected or until the interlock switch is cycled. CAUTION: The polarity of theF1 and F2 connections will affect the operation of the emergency reverse feature.The forward and reverse switches and the F1 and F2 connections must becongured so that the vehicle drives away from the operator when the emergencyreverse button is pressed.

    An optional wire connected directly to the emergency reverse switch pro-vides for broken wire protection when that feature is enabled by the OEM. Theemergency reverse check feature periodically pulses the emergency reverse circuitto check for continuity in the wiring. If there is no continuity, controller outputis inhibited until the wiring fault is corrected. The emergency reverse wiringcheck wire (see dotted line in Figure 13) should be connected to the emergencyreverse switch terminals and to Pin 22.

    For information about the emergency reverse parameters, see Section 3:Programmable Parameters.

    Fig. 13 Wiring foremergency reverse(applicable to walkievehicles only).

    14 1315161718192021222324

    12 11 10 9 8 7 6 5 4 3 2 1

    Pin 22Pin 7

    Emergency Reverse CheckEmergency Reverse

    PIN KEY+EMERGENCY

    REVERSE

    emergency reverse wiring check (optional)

    B-

    C A U T I O N

  • Curtis PMC 1244 Manual 21

    CONTACTOR, SWITCHES, and OTHER HARDWARE

    Main ContactorA main contactor is recommended for use with any 1244 controller. A maincontactor allows the controller and motor to be disconnected from the battery.This provides a signicant safety feature in that the battery power can be removedfrom the drive system if a controller or wiring fault results in battery power beingapplied to the motor.

    A single-pole, single-throw (SPST) contactor with silver-alloy contacts, suchas an Albright SW180 or SW200 (available from Curtis), is recommended for useas the main contactor. It is not necessary to specify the coils at the nominalbattery pack voltage as long as the Contactor Pull-In Voltage and ContactorHolding Voltage are programmed to accommodate the coils voltage ratingseeSection 3, page 46. The contactor coil should be specied with a continuousrating if the Holding Voltage parameter is to be set at 100%. Intermittent dutycoils can be specied if they are used with appropriate Holding Voltage values.

    Keyswitch and Interlock SwitchThe vehicle should have a master on/off switch to turn the system off when notin use. The keyswitch input provides logic power for the controller. The interlockswitch provides a safety interlock to prevent operation when a mechanical brakeis engaged or to ensure operator presence before the vehicle is allowed to move.The keyswitch and interlock switch provide current to drive the various contactorcoils as well as the controllers internal logic circuitry and must be rated to carrythese currents.

    Forward, Reverse, Mode Select, and Pedal SwitchesThese input switches can be any type of single-pole, single-throw (SPST) switchcapable of switching the battery voltage at 25 mA.

    Reverse Polarity Protection DiodeFor reverse polarity protection, a diode should be added to the control circuit.This diode will prohibit main contactor operation and current flow if the batterypack is accidentally wired with the B+ and B- terminals reversed. It should be sizedappropriately for the maximum contactor coil and fault diode currents requiredfrom the control circuit. The reverse polarity protection diode should be wired asshown in the standard wiring diagram (Figure 3, page 8).

    2 INSTALLATION & WIRING: Switches, etc.

  • Curtis PMC 1244 Manual 22

    Table 2 MODE SELECTIONMODE MODE

    OPERATING MODE SELECT SELECTSWITCH 1 SWITCH 2

    MultiMode 1 OPEN OPEN

    MultiMode 2 CLOSED OPEN

    MultiMode 3 OPEN CLOSED

    MultiMode 4 CLOSED CLOSED

    2 INSTALLATION & WIRING: Switches, etc.

    Circuitry Protection DevicesTo protect the control circuitry from accidental shorts, a low current fuse(appropriate for the maximum current draw) should be connected in series withthe battery feed to the keyswitch. Additionally, a high current fuse should bewired in series with the main contactor to protect the motor, controller, andbatteries from accidental shorts in the power system. The appropriate fuse foreach application should be selected with the help of a reputable fuse manufactureror dealer. The standard wiring diagram (Figure 3, page 8) shows the recom-mended location for each fuse.

    Mode Select Switch OperationThe two mode select switches (Mode Select 1 and Mode Select 2) together denethe four operating modes. The switch combinations are shown in Table 2. Wiringfor the mode select switches is shown in the standard wiring diagram (Figure 3,page 8).

  • Curtis PMC 1244 Manual 23

    3 PROGRAMMABLE PARAMETERS

    PROGRAMMABLE PARAMETERS

    The 1244 controller has a number of parameters that can be programmed bymeans of a 1307 handheld programmer. These programmable parameters allowthe vehicles performance characteristics to be customized to t the needs ofindividual vehicles or vehicle operators.

    Each controller is shipped with the parameter settings specied by theOEM. For each programmable parameter, the specication process includesdesignating whether it is to have User or OEM-only access rights. The OEMspecies whichif anyparameters the user (dealer, distributor, etc.) will beable to adjust. Accordingly, Curtis PMC offers two versions of the 1307 pro-grammer: the 1307M-1101 is the User programmer (which can adjust only thoseparameters with User access rights) and the 1307M-2101 is the OEM program-mer (which can adjust all the programmable parameters).

    The MultiMode feature of these controllers allows operation in fourdistinct modes. These modes can be programmed to provide four different setsof operating characteristics, which can be useful for operating in differentconditionssuch as slow precise indoor maneuvering in one mode; faster, longdistance, outdoor travel in another mode; and application-specic special condi-tions in the remaining two modes.

    Eight parameters can be congured independently in the four modes:

    acceleration rate (M1M4) braking rate (M1M4) maximum speed (M1M4) creep speed (M1M4) throttle map (M1M4) throttle braking percent (M1M4) drive current limit (M1M4) braking current limit (M1M4).

    Controllers can be factory-set to allow only one mode of operation if aMultiMode system is not desirable for the applicationsee Section 4. It is notnecessary to have all eight MultiMode parameters on or off together; one orany combination of these parameters can be specied as single-mode and theothers specied as MultiMode.

    3

  • Curtis PMC 1244 Manual 24

    3 PROGRAMMABLE PARAMETERS

    The programmable parameters are described in the following order. Theyare listed in the text by the abbreviated names that appear in the programmersProgram Menu. Not all of these parameters are displayed on all controllers; thelist for any given controller depends on its specications.

    There are additional parameters that can only be congured at the factory.The manufacturer can specify how these parameters will be congured, but theyare not programmable using the 1307 programmer. See Section 4: OEM Specied,Factory Set Parameters.

    Acceleration Parameters

    Acceleration Rate, M1M4Braking Rate, M1M4Deceleration RateQuick StartTaper Rate

    Speed Parameters

    Maximum Speed, M1M4Creep Speed, M1M4Regen Speed

    Throttle Parameters

    Control ModeThrottle TypeThrottle DeadbandThrottle MaximumThrottle Map, M1M4Throttle Braking Percent, M1M4

    Current Limit Parameters

    Drive Current Limit, M1M4Braking Current Limit, M1M4Minimum Field Current LimitMaximum Field Current LimitRestraintEmergency Reverse Current LimitCurrent Ratio

  • Curtis PMC 1244 Manual 25

    Field Control Parameters

    Field Map StartField Map

    Fault Parameters

    High Pedal Disable (HPD)Static Return to Off (SRO)Fault Code

    Output Driver Parameters

    Main Contactor Driver InterlockMain Contactor Dropout DelayMain Coil Open CheckMain Contactor Weld CheckAuxiliary Driver Dropout DelayAuxiliary Coil Open CheckReverse Signal Open CheckElectromagnetic Brake DelayElectromagnetic Brake Open CheckContactor Holding VoltageContactor Pull-In Voltage

    Other Parameters

    Battery VoltageAnti-TiedownSequencing DelayPedal InterlockEmergency Reverse EnableEmergency Reverse CheckNode AddressPrechargeLoad Compensation

    3 PROGRAMMABLE PARAMETERS

  • Curtis PMC 1244 Manual 26

    3 PROGRAMMABLE PARAMETERS: Acceleration Parameters

    M1M4, ACCEL RATEThe acceleration rate denes the time it takes the controller to accelerate from0% output to 100% output. A larger value represents a longer acceleration timeand a gentler start. Fast starts can be achieved by reducing the acceleration time,i.e., by adjusting the accel rate to a smaller value. The acceleration rate isadjustable from 0.1 second to 5.0 seconds, in 0.1 second increments. It can be setindependently for each of the four operating modes.

    M1M4, BRAKE RATEThe braking rate denes the time it takes the controller to increase from 0%regen braking current to 100% regen braking current when braking is requested.A larger value represents a longer time and therefore a gentler increase in brakingstrength. Full braking strength is achieved more quickly when the braking rateparameter value is reduced. The braking rate is adjustable from 0.1 second to 5.0seconds, in 0.1 second increments, and can be set independently for each of thefour operating modes.

    DECEL RATEThe deceleration rate denes the time it takes the controller output to respondto a decrease in applied throttle. The deceleration rate denes the vehicles brakingcharacteristic for any reduction in throttle, including to neutral, that does notinclude a request for the opposite direction. It also denes the characteristic forbraking after Emergency Reverse is released. The decel rate is adjustable from 0to 10 seconds, in 0.1 second increments. The decel rate works in conjunction withthe throttle braking percent parameter, which must be set greater than zero for theprogrammed decel rate to be active. The decel rate is not a MultiModeparameter, and its value will therefore affect all four operating modes.

    QUICK STARTThe quick start function provides faster than normal acceleration in response tofast changes in throttle demand. Upon receiving a sudden high throttle demandfrom neutral, the quick start function causes the controller to exceed its normalacceleration rate. The quick start algorithm is applied each time the throttle passesthrough neutral and the controller is not in braking mode. Quick start isadjustable from 0 to 10, in increments of 1. Increasing the value livens the vehiclesacceleration response to fast throttle movements.

    Acceleration Parameters

  • Curtis PMC 1244 Manual 27

    3 PROGRAMMABLE PARAMETERS: Speed Parameters

    TAPER RATEThe taper rate parameter sets the rate at which the regenerative braking com-mand ramps down at the completion of regen braking. This controls the feel ofthe vehicle as it slows down and approaches zero speed. The taper rate should beadjusted such that during a full speed direction transition, the vehicle comes toa smooth stop before accelerating in the opposite direction. The taper rateparameter is adjustable from 0 to 64 in increments of 1, with each incrementrepresenting 1/32 of a second. This parameter is not active during plug braking.

    M1M4, MAX SPEEDThe maximum speed parameter denes the maximum controller output at fullthrottle. This parameter is adjustable from 0% to 100%, in 1% increments.

    M1M4, CREEP SPEEDThe creep speed parameter denes the initial controller output generated whena direction is rst selected. No applied throttle is necessary for the vehicle to enterthe creep mode, only a direction signal. The output maintains creep speed untilthe throttle is rotated out of the throttle deadband (typically 10% of throttle).

    Creep speed is adjustable from 0% to 25% of the controller duty cycle, in1% increments. The specied creep speed percentage is not displayed as athrottle percent in the programmers Test Menu when a direction is selected andzero throttle is applied; only the throttle command is displayed.

    REGEN SPEEDThe regen speed parameter denes the vehicle speed above which the controllerinitiates regenerative braking; below this speed, plug braking is used. Once thevehicle begins regen braking, the system will continue to regen brake all the wayto zero speed. This threshold is important as it will affect the smoothness ofdirection transitions when jockeying between forward and reverse at low speeds.Regen braking provides the most benet when the vehicle is decelerated from fastspeeds, whereas plug braking provides noticeably smoother direction changes atslow speeds. The regen speed parameter is adjustable from 0% to 100% of thevehicle speed, in 1% increments. Recommendations for adjusting the regenbraking parameter are provided in Section 6: Vehicle Performance Adjustment.

    Speed Parameters

  • Curtis PMC 1244 Manual 28

    3 PROGRAMMABLE PARAMETERS: Throttle Parameters

    CTRL MODEThe control mode parameter tailors the controllers output response to throttlecommands. The two control modes allow the throttle position to dene eitherapplied motor current or applied motor voltage.

    In current control mode (Type 0), the throttle position controls thecurrent flowing in the motor. The controller varies the percentage ofbattery voltage applied to the motor to achieve the requested motorcurrent, thus controlling the motor torque. The operator will increasethrottle demand to accelerate and reduce the throttle demand once thedesired vehicle speed is reached. Any conditions that result in anincrease in motor loading or more motor torque will require an increasein throttle demand to maintain the same vehicle speed. The throttlebraking percent, current ratio, and decel rate parameters are not activein the current control mode.

    In voltage control mode (Type 1), the throttle position controls thepercentage of battery voltage and current applied to the motor. Thecurrent that is allowed to flow in the motor can be modied using thecurrent ratio parameter; see page 38. In voltage control mode, changesin motor loading will result in only a small change in vehicle speedunless the current limit is reached.

    Acceleration and deceleration characteristics of the vehicle in response to throttlechanges in any of these modes will be determined by tuning parameters such asaccel rate, quick start, etc.

    Throttle Parameters

  • Curtis PMC 1244 Manual 29

    3 PROGRAMMABLE PARAMETERS: Throttle Parameters

    THROTTLE TYPEThe 1244 controller accepts a variety of throttle inputs, through various combi-nations of its four throttle input pins. The most commonly used throttles can behooked up directly: 5k0 and 05k 2-wire rheostats, 3-wire pots,05V throttles, Curtis ET-1XX electronic throttles, and CAN-Nodes basedthrottles.

    The standard throttle input signal type optionsTypes 1 through 5 inthe throttle type programming menuare listed in Table 3. Wiring informationand performance characteristics for each throttle type are presented in Section 2.

    Table 3 PROGRAMMABLE THROTTLE TYPESTHROTTLE

    TYPE DESCRIPTION

    1 5k0, 2-wire rheostat

    2 single-ended 3-wire potentiometer (1k to 10k range)or single-ended 05V input (from voltage throttle,Curtis ET-1XX electronic throttle, or current source)

    3 05k, 2-wire rheostat

    4 wigwag 3-wire potentiometer (1k to 10k range)or wigwag 05V input (from voltage throttle)

    5 CAN-Nodes throttle

  • Curtis PMC 1244 Manual 30

    THRTL DEADBANDThe throttle deadband parameter denes the throttle pot wiper voltage range thecontroller interprets as neutral. Increasing the throttle deadband setting increasesthe neutral range. This parameter is especially useful with throttle assemblies thatdo not reliably return to a well-dened neutral point, because it allows thedeadband to be dened wide enough to ensure that the controller goes intoneutral when the throttle mechanism is released.

    Examples of deadband settings (30%, 10%, 0%) are shown in Figure 14 forthrottle types 1 through 4, using a nominal 5k0 potentiometer. (For throttletype 5, see the Curtis CAN Protocol Document.)

    Fig. 14 Effect ofadjusting the throttledeadband parameter(Throttle Types 1 and 2).

    3 PROGRAMMABLE PARAMETERS: Throttle Parameters

    05V Single-Ended Throttle: Type 2

    5k0 Throttle: Type 1

    5V 0

    0.2V

    30% Deadband

    10% Deadband

    0% Deadband

    0.5V

    2.0V

    5V 0

    3.3V(5.0k)

    30% Deadband

    10% Deadband

    0% Deadband

    3.0V(4.5k)

    2.3V(3.2k)

    0.2V(0)

    0.2V(0)

    0.2V(0)

  • Curtis PMC 1244 Manual 31

    Fig. 14, contd Effect ofadjusting the throttledeadband parameter(Throttle Types 3 and 4).

    3 PROGRAMMABLE PARAMETERS: Throttle Parameters

    The programmer displays the throttle deadband parameter as a percentageof the nominal throttle wiper voltage range and is adjustable from 0% to 30%,in 2% increments. The default deadband setting is 10%. The nominal throttlewiper voltage range depends on the throttle type selected. See Table 1 (page 10)for the characteristics of your selected throttle type.

    05k Throttle: Type 3

    05V Wigwag Throttle: Type 4

    5V 0

    0.2V(0)

    30% Deadband

    10% Deadband

    0% Deadband

    0.6V(450)

    1.2V(1.4k)

    Notes: Voltages shown are at the pot wiper relative to B-.For throttle types 1 and 3, the deadband points aredefined in terms of the nominal 5k pot resistance.Using a pot of greater or lesser resistance will givedifferent values for the deadband points.Throttle Max parameter set at 100%.

    3.3V(5.0k)

    3.3V(5.0k)

    3.3V(5.0k)

    KEY

    100%Throttle

    DeadbandController

    Output0%

    5V 0

    0.5V(500)

    30% Deadband

    10% Deadband

    0% Deadband

    2.9V(2.9k)

    3.7V(3.7k)

    4.5V(4.5k)

    4.5V(4.5k)

    4.5V(4.5k)

    2.5V(2.5k)

    0.5V(500)

    0.5V(500)

    2.1V(2.1k)

    1.3V(1.3k)

  • Curtis PMC 1244 Manual 32

    3 PROGRAMMABLE PARAMETERS: Throttle Parameters

    THROTTLE MAXThe throttle max parameter sets the wiper voltage required to produce 100%controller output. Decreasing the throttle max setting reduces the wiper voltageand therefore the full stroke necessary to produce full controller output. Thisfeature allows reduced-range throttle assemblies to be accommodated.

    Examples are shown in Figure 15 for throttle types 1 through 4, using anominal 5k potentiometer. These examples illustrate the effect of three differ-ent throttle max settings (100%, 90%, 60%) on the full-stroke wiper voltagerequired to attain 100% controller output.

    Fig. 15 Effect ofadjusting the throttlemax parameter(Throttle Types 1 and 2).

    05V Single-Ended Throttle: Type 2

    5k0 Throttle: Type 1

    0 5V

    2.0V

    100% Throttle Max30% Deadband

    0.2V 4.5V

    0.2V 3.0V

    2.0V 4.5V

    90% Throttle Max30% Deadband

    90% Throttle Max10% Deadband

    60% Throttle Max10% Deadband

    0 5V

    2.3V(3.2k)

    0.2V(0)

    100% Throttle Max30% Deadband

    3.0V(4.5k)

    1.7V(2.2k)

    0.6V(450)

    90% Throttle Max30% Deadband

    90% Throttle Max10% Deadband

    60% Throttle Max10% Deadband

    0.6V(450)

    2.3V(3.2k)

    3.0V(4.5k)

  • Curtis PMC 1244 Manual 33

    Fig. 15, contdEffect of adjusting thethrottle max parameter(Throttle Types 3 and 4).

    3 PROGRAMMABLE PARAMETERS: Throttle Parameters

    The programmer displays the throttle max parameter as a percentage of theactive throttle voltage range. The throttle max parameter can be adjusted from100% to 60%, in 2% increments. The nominal throttle wiper voltage rangedepends on the throttle type selected. See Table 1 (page 10) for the characteristicsof your selected throttle type.

    05k Throttle: Type 3

    05V Wigwag Throttle: Type 4

    0 5V

    1.2V(1.4k)

    3.3V(5.0k)

    100% Throttle Max30% Deadband

    0.5V(400)

    2.7V(3.9k)

    3.0V(4.5k)

    90% Throttle Max30% Deadband

    90% Throttle Max10% Deadband

    60% Throttle Max10% Deadband

    Notes: Voltages shown are at the pot wiper relative to B-.For throttle types 1 and 3, the deadband points aredefined in terms of the nominal 5k pot resistance.Using a pot of greater or lesser resistance will givedifferent values for the deadband points.

    KEY

    100%Throttle

    DeadbandController

    Output0%

    1.2V(1.4k)

    0.5V(400)

    3.0V(4.5k)

    0 5V

    100% Throttle Max30% Deadband

    90% Throttle Max30% Deadband

    90% Throttle Max10% Deadband

    60% Throttle Max10% Deadband

    3.7V(3.7k)

    4.5V(4.5k)

    0.5V(500)

    1.3V(1.3k)

    3.7V(3.7k)

    4.3V(4.3k)

    0.7V(700)

    1.3V1.3k)

    2.9V(2.9k)

    4.3V(4.3k)

    0.7V(700)

    2.1V(2.1k)

    2.9V(2.9k)

    3.7V(3.7k)

    1.3V(1.3k)

    2.1V(2.1k)

  • Curtis PMC 1244 Manual 34

    3 PROGRAMMABLE PARAMETERS: Throttle Parameters

    M1M4, THRTL MAPThe throttle map parameter modies the vehicles response to the throttle input.This parameter determines the controller output, based on the selected throttlecontrol mode, for a given amount of applied throttle. Setting the throttle mapparameter at 50% provides a linear output response to throttle position. Valuesbelow 50% reduce the controller output at low throttle settings, providingenhanced slow speed control. Values above 50% give the vehicle a faster, jumpierfeel at low throttle settings.

    The throttle map can be programmed in 5% increments between 20% and80%. The number refers to the controller output at half throttle, as a percentageof the throttles full active range. The throttles active range is the voltage orresistance between the 0% output point (throttle deadband) and the 100%output point (throttle max). For example, if maximum speed is set at 100% andcreep speed is set at 0, a throttle map setting of 50% will give 50% output at halfthrottle. The 50% setting corresponds to a linear response. Six throttle mapproles (20, 30, 40, 50, 60, and 80%) are shown as examples in Figure 16, withthe maximum speed set at 100% and the creep speed set 0.

    Fig. 16 Throttle maps forcontroller with maximumspeed set at 100% andcreep speed set at 0.

    Lowering the max speed or raising the creep speed limits the controllersoutput range. Throttle map proles with the creep speed raised from zero to 10%and the max speed reduced from 100% to 80% are shown in Figure 17. Thethrottle map is always a percentage of the controllers output range. So, in theseexamples, the throttle map is a percentage of the 1080% output range; a 40%throttle map setting will give 38% output at half throttle (40% of the 70% range,which is 28%, shifted up to 38% because it starts at the 10% creep speed).Controller output will begin to increase above the set creep speed as soon as the

    THROTTLE INPUT (percent of active range)

    80%60%50%40%30%20%

    THROTTLE MAP100

    90

    80

    70

    60

    50

    40

    30

    20

    10

    0100908070605040302010 0

    SPEED PARAMETERS

    0% Creep Speed100% Max Speed

    CONT

    ROLL

    ER O

    UTPU

    T (P

    WM pe

    rcen

    t)

  • Curtis PMC 1244 Manual 35

    throttle is rotated out of its normal neutral range (deadband). Controller outputwill continue to increase, following the curve dened by the throttle map setting,as the throttle input increases and will reach maximum output when the throttleinput enters the upper deadband (crosses the throttle max threshold).

    Fig. 17 Throttle maps forcontroller with maximumspeed set at 80% and creepspeed set at 10%.

    The Throttle Map operates within the window established by the CreepSpeed, Max Speed, Throttle Deadband, and Throttle Max parameters, as shownin Figure 18. Creep Speed and Max Speed dene the controllers output range,while Throttle Deadband and Throttle Max dene the throttles active range.These four parameters, together with the Throttle Map, determine the controllersoutput response to throttle demand.

    Fig. 18 Influence ofvarious parameters oncontroller output responseto throttle demand.

    THROTTLE INPUT (percent of active range)

    CONT

    ROLL

    ER O

    UTPU

    T (P

    WM p

    erce

    nt) 80%

    60%50%40%30%20%

    THROTTLE MAP100

    90

    80

    70

    60

    50

    40

    30

    20

    10

    0100908070605040302010 0

    SPEED PARAMETERS

    10% Creep Speed80% Max Speed

    THROTTLE INPUT (percent)

    CONT

    ROLL

    ER O

    UTPU

    T (P

    WM p

    erce

    nt)

    100908070605040302010 0

    SPEED PARAMETERS

    10% Creep Speed80% Max Speed

    THROTTLEPARAMETERS

    15% Deadband90% Throttle Max40% Throttle Map

    80% Max Speed

    40% Throttle Map(38% output at half throttle)

    10% Creep Speed

    15%

    Thr

    ottle

    Dea

    dban

    d

    90%

    Thr

    ottle

    Max

    HALF

    TH

    ROTT

    LE

    100

    90

    80

    70

    60

    50

    40

    30

    20

    10

    0

    3 PROGRAMMABLE PARAMETERS: Throttle Parameters

  • Curtis PMC 1244 Manual 36

    3 PROGRAMMABLE PARAMETERS: Current Limit Parameters

    M1M4, THRT BRK %The throttle braking percent parameter establishes the braking force applied tothe vehicle when the throttle is reduced. Throttle braking is engaged when thecontroller transitions from drive to neutral. The controller recognizes neutral asthe condition where neither direction switch is closed, regardless of throttle input.This parameter is adjustable from 0% to 100% of the regen braking current limitspecied for a given mode, in 2% increments.

    M1M4, DRIVE C/LThe drive current limit parameter allows adjustment of the maximum currentthe controller will supply to the motor during drive operation. This parameter canbe used to reduce the maximum torque applied to the drive system by the motorin any of the modes. The drive current limit is adjustable from 200 amps to thecontrollers full rated current, in 5 amp increments. The full rated currentdepends on the controller model.

    M1M4, BRAKE C/LThe braking current limit parameter allows adjustment of the maximum currentthe controller will supply to the motor during regen braking operations. Duringregen braking, this parameter controls the regen current from the motorsarmature into the battery. The braking current limit is adjustable from 100 ampsup to the controllers full rated current, in 5 amp increments. The full ratedcurrent depends on the controller model.

    FIELD MINThe minimum field current limit parameter denes the minimum allowedcurrent in the motors eld winding. Its setting will determine the vehiclesmaximum speed and, to some extent, the smoothness with which the vehiclestarts and transitions from one direction to another. If the Field Min value is sethigh, the vehicles top speed will be reduced, but torque bumps may be evidentwhen the vehicle is inched or changes direction.

    One of the greatest advantages of the Field Min parameter is that it willprevent uncontrolled acceleration when the vehicle encounters a decline. Thevehicles speed is limited when it goes down ramps or when it is unloaded fromtrucks, etc.

    Current Limit Parameters

  • Curtis PMC 1244 Manual 37

    3 PROGRAMMABLE PARAMETERS: Current Limit Parameters

    The Field Min parameter is adjustable from 2 to 20 amps, in 0.5 ampincrements. Recommendations for adjusting the Field Min parameter are pro-vided in Section 6: Vehicle Performance Adjustment.

    FIELD MAXThe maximum field current limit parameter denes the maximum allowedcurrent in the motors eld winding. Its setting will determine the motorsmaximum torque during both drive and braking, and will limit the powerdissipation in the eld winding itself. The Field Max parameter is adjustable from7.5 amps to the controllers full rated eld current limit, in 0.5 amp increments.Recommendations for adjusting the Field Max parameter are provided in Section 6:Vehicle Performance Adjustment.

    RESTRAINTBecause the 1244 controller is congured to provide throttle braking, overspeed willcause the controller to create a braking current and thus limit or restrain theoverspeed condition. The restraint parameter, in combination with throttle brakingpercent parameter, determines how strongly the controller will attempt to limit thevehicle speed to the existing throttle setting. This function works at all throttlesettings, including zero throttle. It is applicable when throttle is reduced or whenthe vehicle begins to travel downhill.

    The restraint parameter is adjustable from 1 to 10. Setting the parameter toa high value will cause strong braking, in an effort to bring the vehicle speeddown to the requested speed. Setting the restraint value to 1 will result inminimal regen braking.

    At zero throttle, the restraint function will also attempt to keep the motor atzero speed. This will help hold the vehicle from running away down ramps whenbraking to neutral is completed and the mechanical or electromagnetic brake hasnot engaged. The higher the restraint parameter value, the stronger the brakingforce applied to the motor and the slower the vehicle will creep down the ramp.This creeping speed will depend on the restraint setting, the steepness of theramp, and the vehicle load. The restraint feature can never hold a vehicleperfectly stationary on a ramp and is not intended to replace a mechanical orelectromagnetic brake for this purpose. The throttle braking percent parameteris not active in this situation, and the controller will supply up to the maximumprogrammed regen current limit. Recommendations for adjusting the restraintparameter are provided in Section 6: Vehicle Performance Adjustment.

  • Curtis PMC 1244 Manual 38

    3 PROGRAMMABLE PARAMETERS: Field Control Parameters

    EMR REV C/LThe emergency reverse current limit parameter denes the maximum brakingcurrent provided through the motor when the emergency reverse function isengaged. The emergency reverse current limit is adjustable from 50 amps to thecontrollers full rated braking current limit, in 5 amp increments.

    CURRENT RATIOThe current ratio parameter denes how much of the programmed drive currentwill be available to the motor at reduced throttle requests. This will determine themaximum torque the motor can provide at partial throttle. The current ratioparameter can be set to 1, 2, 4, or 8. These settings represent a multiplicationfactor applied to the current that would otherwise be available. For example, if20% throttle is requested with the current ratio set at 1, 20% of the battery voltageand 20% of the drive current will be allowed to flow in the motor (assuming a50% throttle map setting). If the current ratio is set at 2 under these sameconditions, 40% of the current will be available; if it is set at 4, 80%. Thecontroller will never allow more than the programmed drive current to flow in themotor. If the current ratio is set at 8 with 20% throttle requested, the controllerwill allow only 100% of the drive current and not 160%.

    Because the current ratio parameter affects how much torque the motor canprovide, high current ratio settings will result in improved ramp climbing withpartial throttle, but may cause too much jumpiness at startup.

    NOTE: The current ratio parameter is valid only when the control modeparameter is set to Type 1 (Voltage Control).

    FLD MAP STARTThe field map start parameter denes the armature current at which the eldmap starts to increase from the Field Min value. This parameter is expressed inamperes, and is adjustable from 0 to one half the controllers full rated armaturecurrent value, in 5 amp increments. The Field Map Start parameter is used toequalize the vehicles maximum speed when loaded and unloaded.

    Increasing the Field Map Start value increases the maximum load the vehiclecan carry while still maintaining maximum speed on a level surface. Whether the

    Field Control Parameters

  • Curtis PMC 1244 Manual 39

    3 PROGRAMMABLE PARAMETERS: Field Control Parameters

    vehicles loaded speed will actually increase depends on the armature currentbeing drawn at that load. If the armature current is already below the Field MapStart setting, increasing the Field Map Start value will not affect the vehiclesloaded speed.

    Care should be taken to ensure that high Field Map Start values do not movethe motors operating characteristics outside its safe commutation area. Recom-mendations for adjusting the Field Map Start parameter to achieve variousperformance characteristics are provided in Section 6: Vehicle PerformanceAdjustment Guidelines.

    FIELD MAPThe field map parameter denes the variation of the eld winding current as afunction of armature current. It controls how much eld current is applied for agiven armature current, and is adjustable from 0% to 100%, in 5% increments.

    The Field Map parameter is set as a percentage of the eld current betweenthe Field Min and Field Max values. As shown in Figure 19, the Field Mapparameter increases or decreases the eld current at the armature current that ishalfway between the Field Map Start current and the controllers programmeddrive current limit. This point on the armature current curve is referred to as theField Map Midpoint.

    With the Field Map set at 50% and the Field Map Start set at zero, themotors eld current increases linearly with increasing armature currentthusemulating a series wound motor. Decreasing the eld map setting reduces theeld current at a given armature current, i.e., it weakens the eld. As the eldcurrent is reduced, the motor will be able to maintain speeds closer to themaximum speed value.

    Care should be taken to ensure that excessively low Field Map values do notmove the motors operating characteristics outside its safe commutation region.Recommendations for adjusting the Field Map parameter to achieve variousperformance characteristics are provided in Section 6: Vehicle PerformanceAdjustment Guidelines.

  • Curtis PMC 1244 Manual 40

    3 PROGRAMMABLE PARAMETERS: Field Control Parameters

    Fig. 19 Field currentrelative to armaturecurrent, with field mapparameter set at 50%and 20%.

    ARMATURE CURRENT

    FIEL

    D C

    URRE

    NT

    Field Map Start Field Map Midpoint 100%00

    Field Min

    Field Max

    Field Map(50%)

    ARMATURE CURRENT

    FIEL

    D C

    URRE

    NT

    Field Map Start Field Map Midpoint 100%00

    Field Min

    Field Max

    Field Map(20%)

  • Curtis PMC 1244 Manual 41

    HPDThe high pedal disable (HPD) feature prevents the vehicle from driving themotor if greater than 25% throttle is applied when the controller is turned on. Inaddition to providing routine smooth starts, HPD also protects against accidentalsudden starts if problems in the throttle linkage (e.g., bent parts, broken returnspring) give a throttle input signal to the controller even with the throttle released.

    If the operator attempts to start the vehicle with the throttle already applied,the controller will inhibit output to the motor until the throttle is reduced below25%. For the vehicle to run, the controller must receive a KSI inputor a KSIinput and an interlock inputbefore receiving a throttle input. Either type ofHPD (HPD on KSI input alone or HPD on KSI plus interlock inputs) can beselected via the programmer. HPD can also be disabled. To meet EEC require-ments, the HPD feature must be programmed to Type 1 or 2.

    Sequencing delay (see page 47) can be used to provide a variable delay beforethe controller is disabled, if desired.

    No HPD (Type 0)HPD function is disabled.

    Interlock-type HPD (Type 1)To start the vehicle, the controller must receive an interlock switch input inaddition to a KSI input before receiving a throttle input. Controller operation willbe disabled immediately if throttle input is greater than 25% at the time theinterlock switch is closed. Normal controller operation is regained by reducing thethrottle demand to less than 25%.

    KSI-type HPD (Type 2)To start the vehicle, the controller must receive a KSI input before receiving athrottle input. Controller operation will be disabled immediately if throttle inputis greater than 25% at the time KSI is enabled. If throttle is applied before theinterlock switch is closed but after the KSI input has been enabled, the vehicle willaccelerate to the requested speed as soon as the interlock switch is closed. Normaloperation is regained by reducing the throttle demand to less than 25%.

    SROThe static return to off (SRO) feature prevents the vehicle from being startedwhen in gear. SRO checks the sequencing of the interlock inputor the

    3 PROGRAMMABLE PARAMETERS: Fault Parameters

    Fault Parameters

  • Curtis PMC 1244 Manual 42

    interlock input and KSIrelative to a direction input. The interlock inputorthe interlock plus KSI inputsmust come on before a direction is selected. If adirection is selected before or simultaneously (within 50 msec) with the interlockinput, the controller is disabled.

    Three types of SRO are available (along with a no SRO option):

    Type 0: no SROType 1: SRO on interlock input plus a direction inputType 2: SRO on KSI plus interlock input plus a direction inputType 3: SRO on KSI plus interlock input plus forward direction input.

    If your controller is programmed so that both KSI and interlock inputs arerequired (SRO Type 2), the following sequence must be followed to enable thecontroller: STEP 1, turn on KSI; STEP 2, activate interlock (input high); and thenSTEP 3, select a direction. The interval between steps 1 and 2 is the same asbetween steps 2 and 3; that is, KSI input must precede interlock input by at least50 msec. Once the controller is operational, turning off either KSI or theinterlock causes the controller to turn off; re-enabling the controller requires the3-step sequence.

    Similarly, if your controller is programmed so that KSI, interlock, andforward inputs are all required (SRO Type 3), they must be provided in thatsequence in order to enable the controller. Note, however, that operation isallowed if a reverse input precedes the interlock input; this can be useful whenoperating a walkie on ramps.

    Sequencing delay (see page 47) can be used to provide a variable delay beforedisabling the controller, if desired.

    FAULT CODEThe 1244 controllers fault code drivers allow faults to be displayed in either oftwo different formats: Fault Code format or Fault Category format.

    With the fault code parameter specied On, the controllers fault outputswill provide information in Fault Code format. With the fault code parameterspecied Off, the controllers fault outputs will provide information in FaultCategory format.

    In Fault Code format, the two fault lines operate independently. When a faultis present, the Fault 1 driver (Pin 5) provides a pulsed signal equivalent to thefault code flashed by the controllers built-in Stat