ABB Data schedule: SF 6 Circuit Breaker Tender: 13Q1925303-1 , Item: 70 General data Type LTB 245E1 Type of operation 1 Pole Operation Number of poles 3 Min temperature °C -25 Max temperature °C 40 Max altitude m 1000 Ratings and guaranteed performance in accordance with IEC 62271-100 Rated voltage kV 245 Rated insulation levels Rated lightning impulse withstand voltage to earth kV peak 1050 across the open circuit breaker kV peak 1050 Rated switching impulse withstand voltage to earth kV peak - across the open circuit breaker kV peak - Rated power frequency withstand voltage to earth kV 460 across the open circuit breaker kV 460 Rated frequency Hz 60 Rated normal current A 2000 Rated short-circuit breaking current kA 40 DC component % 60 First pole-to-clear factor 1.5 Rated transient recovery voltage for terminal faults kV peak 420 Rated characteristics for short line fault Peak factor 1.6 RRRV factor kV/μs/kA 0.24 Surge impedance Ohm 450 Rated peak making current kA peak 104 Rated duration of short-circuit current s 3 Rated out of phase characteristics Out of phase making and breaking current kA 10.0 Voltage factor 2 Rated line charging breaking current A 125 Rated cable charging breaking current A 250 Rated operating sequence O-0.3s-CO-3min-CO Mechanical endurance class M2 Operating times Opening time ms 17 ±2 Break time ms 40 Closing time ms <28 Constructional features Number of breaks per pole 1 Gas mixture 0.8 MPa SF6 Total mass of gas kg 26 Volume of gas liter 3 x 158 Max. working pressure MPa (gauge) 0.80 Filling pressure at +20°C MPa (abs) 0.80 Alarm pressure MPa (abs) 0.72 Blocking pressure MPa (abs) 0.70 Bursting disc No HV terminal IEC(40) 9-hole + NEMA(44.5) 4-hole 06/28/2013 03:32:06 PM 1/2

1.2 Data Schedule LTB245E1

Embed Size (px)

Citation preview

Page 1: 1.2 Data Schedule LTB245E1

ABBData schedule: SF 6 Circuit Breaker

Tender: 13Q1925303−1 , Item: 70

General dataType LTB 245E1Type of operation 1 Pole OperationNumber of poles 3Min temperature °C −25Max temperature °C 40Max altitude m 1000

Ratings and guaranteed performance in accordance with IEC 62271−100

Rated voltage kV 245

Rated insulation levelsRated lightning impulse withstand voltage to earth kVpeak 1050 across the open circuit breaker kVpeak 1050Rated switching impulse withstand voltage to earth kVpeak − across the open circuit breaker kVpeak −Rated power frequency withstand voltage to earth kV 460 across the open circuit breaker kV 460

Rated frequency Hz 60Rated normal current A 2000Rated short−circuit breaking current kA 40DC component % 60First pole−to−clear factor 1.5Rated transient recovery voltage for terminal faults kVpeak 420

Rated characteristics for short line faultPeak factor 1.6RRRV factor kV/µs/kA 0.24Surge impedance Ohm 450

Rated peak making current kApeak 104Rated duration of short−circuit current s 3

Rated out of phase characteristicsOut of phase making and breaking current kA 10.0Voltage factor 2

Rated line charging breaking current A 125Rated cable charging breaking current A 250

Rated operating sequence O−0.3s−CO−3min−COMechanical endurance class M2

Operating timesOpening time ms 17 ±2Break time ms 40Closing time ms <28

Constructional featuresNumber of breaks per pole 1Gas mixture 0.8 MPa SF6Total mass of gas kg 26Volume of gas liter 3 x 158Max. working pressure MPa (gauge) 0.80Filling pressure at +20°C MPa (abs) 0.80Alarm pressure MPa (abs) 0.72Blocking pressure MPa (abs) 0.70

Bursting disc No

HV terminal IEC(40) 9−hole +NEMA(44.5) 4−hole

06/28/2013 03:32:06 PM 1/2

Page 2: 1.2 Data Schedule LTB245E1

Heater in packing boxes Yes

Breaker position indication (O−I) ABIERTO−CERRADOYellow−Yellow

Dimension print 1HSB435452M202Seismic/Reinforced 0.5g IEC 62271−300

InsulatorsType of insulators and colour Brown porcelainMin nominal creepage distance phase−to−earth mm 6523Min nominal creepage distance across open breaker mm 6370

Operating mechanismNumber of drives 3Motor charged spring operating mechanism BLK 222Whether fixed trip or trip−free (IEC Publ.60050(441)) Trip−freeOperating voltage VDC 220Heater voltage VAC 220Motor voltage VDC 220

Power required at rated supply voltage byClosing coil W 200Opening coil W 200Motor kW 0.9Heating element, continuously W 70Heating elements, connected by thermostat W 140

Number of auxiliary contacts making and breaking 12NO+12NCManual trip Yes, internal

Type of terminals supply Entrelec M6/8 STA(disconnectable)

Type of terminals signals Entrelec M4/6TCS resistor YES without resistorCircuit diagram 1HSB543212−GKFTCS resistor 'ICC' YES without resistorCircuit diagram 'ICC' 1HSB543212−GKE