22
APPENDIX B—RECOMMENDATIONS FOR DESIGN AND CONSTRUCTION OF FOUNDATIONS FOR ABOVEGROUND OIL STORAGE TANKS B.1 Scope This appendix provides important considerations for the design and construction of foundations for aboveground steel oil storage tanks with flat bottoms. Recommendations are offered to outline good practice and to point out some precautions that should be considered in the design and construction of storage tank foundations. Since there is a wide variety of surface, subsurface, and climatic conditions, it is not practical to establish design data to cover all situations. The allowable soil loading and the exact type of subsurface construction to be used must be decided for each individual case after careful consideration. The same rules and precautions shall be used in selecting foundation sites as would be applicable in designing and constructing foundations for other structures of comparable magnitude. B.2 Subsurface Investigation and Construction B.2.1 At any tank site, the subsurface conditions must be known to estimate the soil bearing capacity and settlement that will be experienced. This information is generally obtained from soil borings, load tests, sampling, laboratory testing, and analysis by an experienced geotechnical engineer familiar with the history of similar structures in the vicinity. The subgrade must be capable of supporting the load of the tank and its contents. The total settlement must not strain connecting piping or produce gauging inaccuracies, and the settlement should not continue to a point at which the tank bottom is below the surrounding ground surface. The estimated settlement shall be within the acceptable tolerances for the tank shell and bottom.

118637409 Traduccion Apendice B API 650

Embed Size (px)

Citation preview

Page 1: 118637409 Traduccion Apendice B API 650

APPENDIX B—RECOMMENDATIONS FOR DESIGN AND CONSTRUCTION OF FOUNDATIONS FOR ABOVEGROUND OIL STORAGE TANKS

B.1 Scope

This appendix provides important considerations for the design and construction of foundations for aboveground steel oil storage tanks with flat bottoms. Recommendations are offered to outline good practice and to point out some precautions that should be considered in the design and construction of storage tank foundations.Since there is a wide variety of surface, subsurface, and climatic conditions, it is not practical to establish design data to cover all situations. The allowable soil loading and the exact type of subsurface construction to be used must be decided for eachindividual case after careful consideration. Thesame rules and precautions shall be used in selecting foundation sites as would be applicable in designing and constructing foundations for other structures of comparable magnitude.

B.2 Subsurface Investigation andConstruction

B.2.1 At any tank site, the subsurface conditions must be known to estimate the soil bearing capacity and settlement that will be experienced. This information is generally obtained from soil borings, load tests, sampling, laboratory testing, and analysis by an experienced geotechnical engineer familiar with the history of similar structures in the vicinity. The subgrade must be capable of supporting the load of the tank and its contents. The total settlement must not strain connecting piping or produce gauging inaccuracies, and the settlement should not continue to a point at which the tank bottom is below the surrounding ground surface. The estimated settlement shall be within the acceptable tolerances for the tank shell and bottom.

APENDICE B – RECOMENDACIONES PARA EL DISEÑO Y CONSTRUCCIÓN DE CIMENTACIONES SOBRE EL SUELO PARA TANQUES DE ALMACENAMIENTO DE ACEITE

B.1 Alcance

En este apéndice se ofrece consideraciones importantes para el diseño y construcción de bases para tanques de almacenamiento de aceite sobre el suelo de acero de fondo plano. Las recomendaciones se ofrecen para delinear las buenas prácticas y señalar algunasprecauciones que deben tenerse en cuenta en el diseño y construcción de cimentaciones de tanques de almacenamiento.Puesto que existe una amplia variedad desuperficie, subsuelo, y las condicionesclimáticas, que no es práctico para establecer los datos de diseño para cubrir todas lassituaciones. La carga admisible del suelo y el tipo exacto de la construcción subterránea que se utiliza debe decidirse en cada caso individual después de una cuidadosa consideración. Las mismas reglas y precauciones se utilizarán en la selección de los sitios de cimentación como sería aplicable en el diseño y la construcción de cimientos para otras estructuras de magnitud comparable.

B.2 Investigación del subsuelo yConstrucción

B.2.1 En cualquier sitio del tanque, las condiciones de la superficie debe ser conocido para estimar la capacidad de soporte del suelo y la solución que será experimentado. Esta información se obtiene generalmente a partir de perforaciones del suelo, pruebas de carga, muestreo, pruebas de laboratorio y análisis deun ingeniero geotécnico experimentadofamiliarizado con la historia de estructuras similares en las cercanías. El subsuelo debe ser capaz de soportar la carga del tanque y su contenido. El asentamiento total no debe forzar la conexión de tuberías o producir imprecisiones de aforo, y la solución no debe seguir un punto en el que el fondo del tanque está por debajo de la superficie del terreno circundante. El asentamiento estimado será igual dentro de las

Page 2: 118637409 Traduccion Apendice B API 650

B.2.2 When actual experience with similar tanks and foundations at a particular site is not available, the following ranges for factors of safety should be considered for use in the foundation design criteria for determining the allowable soil bearing pressures.(The owner or geotechnical engineer responsible for the project may use factors of safety outside these ranges.)

a. From 2.0 to 3.0 against ultimate bearing failure for normal operating conditions.b. From 1.5 to 2.25 against ultimate bearing failure during hydrostatic testing.c. From 1.5 to 2.25 against ultimate bearing failure for operating conditions plus the maximum effect of wind or seismic loads.

B.2.3 Some of the many conditions that require special engineering consideration are as follows:a. Sites on hillsides, where part of a tank may be on undisturbed ground or rock and part may be on fill or another construction or where the depth of required fill is variable.b. Sites on swampy or filled ground, wherelayers of muck or compressible vegetation are at or below the surface or where unstable or corrosive materials may have been deposited as fill.c. Sites underlain by soils, such as layers of plastic clay or organic clays, that may support heavy loads temporarily but settle excessively over long periods of time.d. Sites adjacent to water courses or deepexcavations, where the lateral stability of the ground is questionable.e. Sites immediately adjacent to heavy structures that distribute some of their load to the subsoil under the tank sites, thereby reducing the subsoil’s capacity to carry additional loads without excessive settlement. f. Sites where tanks may be exposed to floodwaters, possibly resulting in uplift, displacement, or scour.g. Sites in regions of high seismicity that may be susceptible to liquefaction.h. Sites with thin layers of soft clay soils that are

tolerancias aceptables para la coraza del tanque y la parte inferior.B.2.2 Cuando la experiencia actual en tanques y fundaciones similares en un sitio particular no está disponible, los siguientes rangos para los factores de seguridad deben ser considerados para su uso en los criterios de diseño de la cimentación para la determinación de las presiones del suelo permisibles de rodamientos. (El propietario o un ingeniero geotécnico responsable del proyecto pueden utilizar los factores de seguridad fuera de estos rangos.)

a. De 2,0 a 3,0 contra el fallo carga última para condiciones normales de funcionamiento.b. De 1,5 a 2,25 contra el fallo de carga última durante la prueba hidrostática.c. De 1,5 a 2,25 contra el fallo carga última para las condiciones de operación más el máximo efecto del viento o de las cargas sísmicas.

B.2.3 Algunas de las muchas condiciones que requieren una consideración especial de la ingeniería son los siguientes:a. Sitios en laderas, donde parte de un tanque puede estar en una superficie no perturbado o roca y en parte puede ser llenado o construcción otro o donde la profundidad de llenado requerido es variable.b. Sitios en un terreno pantanoso o lleno, donde las capas de lodo o vegetación compresibleestán en o por debajo de la superficie o donde los materiales inestables o corrosivos pueden haber sido depositadas como relleno.c. Sitios sustentada por los suelos, tales como capas de arcilla plástica o arcillas orgánicas, que pueden soportar cargas pesadas temporalmente pero resolver excesivamente durante largos períodos de tiempo.d. Sitios adyacentes a cursos de agua o excavaciones profundas, donde la estabilidad lateral de la tierra es cuestionable.e. Sitios inmediatamente adyacentes a estructuras pesadas que distribuyen una parte de su carga en el subsuelo de los sitios de depósito, reduciendo así la capacidad del subsuelo para llevar cargas adicionales sin asentamiento excesivo.f. Sitios en los que los tanques pueden estar expuestos a las inundaciones, posiblemente resultando en elevación, desplazamiento o

Page 3: 118637409 Traduccion Apendice B API 650

directly beneath the tank bottom and that can cause lateral ground stability problems.

B.2.4 If the subgrade is inadequate to carry the load of the filled tank without excessive settlement, shallow or superficial construction under the tank bottom will not improve the support conditions. One or more of thefollowing general methods should be considered to improve the support conditions:

a. Removing the objectionable material and replacing it with suitable, compacted material.b. Compacting the soft material with short piles. c. Compacting the soft material by preloading the area with an overburden of soil. Strip orsand drains may be used in conjunction with thismethod.d. Stabilizing the soft material by chemical methods or injection of cement grout.e. Transferring the load to a more stable material underneath the subgrade by driving piles or constructing foundation piers. This involves constructing a reinforced concrete slab on the piles to distribute the load of the tank bottom.f. Constructing a slab foundation that willdistribute the load over a sufficiently large area of the soft material so that the load intensity will be within allowable limits and excessive settlement will not occur.g. Improving soil properties by vibro- compaction, vibro-replacement, or deep dynamic-compaction.h. Slow and controlled filling of the tank during hydrostatic testing. When this method is used, the integrity of the tank may be compromised by excessive settlements of the shell or bottom.For this reason, the settlements of the tank shall be closely monitored.In the event of settlements beyond established ranges, the test may have to be stopped and the tank releveled.

erosión.g. Sitios en regiones de alta sismicidad que pueden ser susceptibles a la licuefacción.h. Los sitios con capas delgadas de suelos arcillosos blandos que son directamente debajo de la parte inferior del tanque y que puede causar problemas de estabilidad lateral de tierra.

B.2.4 Si la subrasante es insuficiente para soportar la carga del tanque lleno sin asentamiento excesivo y poco profundo o superficial construcción bajo el fondo del tanque no va a mejorar las condiciones de apoyo. Uno o más de los siguientes métodos generalesdebería serconsiderarse para mejorar las condiciones de apoyo:a. Extracción del material objetable y reemplazarlo con material adecuado, compactado.b. Compactar el material blando con pilotes cortos.c. Compactar el material blando mediante la precarga de la zona con una sobrecarga de suelo. Franja o drenes de arena puede ser utilizado en conjunción con este método.d. La estabilización de la material blando por métodos químicos o de inyección de lechada de cemento.e. La transferencia de la carga a un material másestable por debajo de la rasante de hincar pilotes o pilares de la construcción de la fundación. Esto implica la construcción de una losa de hormigón armado sobre los pilotes para distribuir la carga de la parte inferior del tanque. f. La construcción de una losa de cimentación que se va a distribuir la carga sobre un área suficientemente grande de material blando, de manera que la intensidad de carga dentro de los límites permisibles y asentamiento excesivo no se producirán.g. Mejora de las propiedades del suelo por vibro-compactación, vibro-sustitución, o profundidad de compactación dinámica.h. Lenta y controlada de llenado del depósitodurante la prueba hidrostática. Cuando se utiliza este método, la integridad de la cisterna puede verse comprometida por asentamientos excesivos de la cáscara o inferior. Por esta razón, los asentamientos del tanque debe ser

Page 4: 118637409 Traduccion Apendice B API 650

estrechamente monitorizados.En el caso de los asentamientos más allá de los rangos establecidos, la prueba puede tener que ser detenido y releveled el tanque.

B.2.5 The fill material used to replace muck or other objectionable material or to build up the grade to a suitable height shall be adequate for the support of the tank and product after the material has been compacted. The fill material shall be free of vegetation,organic matter, cinders, and any material that will cause corrosion of the tank bottom. The grade and type of fill material shall be capable of being compacted with standard industry compaction techniques to a density sufficient to provide appropriate bearing capacity and acceptable settlements. The placement of thefill material shall be in accordance with the project specifications prepared by a qualified geotechnical engineer.

B.3 Tank Grades

B.3.1 The grade or surface on which a tank bottom will rest should be constructed at least0.3 m (1 ft) above the surrounding ground surface. This will provide suitable drainage, help keep the tank bottom dry, and compensate for some small settlement that is likely to occur. If a large settlement is expected, the tank bottom elevation shall be raised so that the final elevation above grade will be a minimum of 150 mm (6 in.) after settlement.B.3.2 There are several different materials that can be used for the grade or surface on which the tank bottom will rest. To minimize future corrosion problems and maximize the effect of corrosion prevention systems such as cathodic protection, the material in contact with the tank bottom should be fine and uniform. Gravel or large particles shall be avoided. Clean washed sand 75 mm – 100 mm (3 in. – 4 in.) deep is recommended as a final layer because it can be readily shaped to the bottom contour of thetank to provide maximum contact area and will protect the tank bottom from coming into contact with large particles and debris.Large foreign objects or point contact by gravel

B.2.5 El material de relleno que se utiliza para reemplazar lodo o material objetable distinto o para construir el grado a una altura adecuada debe ser adecuada para el soporte del depósitoy el producto después de que el material ha sido compactado. El material de relleno debe estar libre de vegetación,materia orgánica, cenizas, y cualquier materialque va a provocar la corrosión de la parteinferior del tanque. El grado y el tipo de material de relleno debe ser capaz de ser compactadocon técnicas estándar de la industria decompactación a una densidad suficiente para proporcionar capacidad de soporte adecuada y asentamientos aceptables. La colocación del material de relleno debe estar de acuerdo conlas especificaciones del proyecto preparados por un ingeniero geotécnico cualificado.

B.3 Grados de Tanque

B.3.1 El grado o superficie en la que un fondo del tanque descansará debe construir por lo menos 0,3 m (1 pie) por encima de los alrededoressuperficie del suelo. Esto proporcionará drenaje adecuado, ayudan a mantener la parte inferior del depósito seco, y compensar alguna pequeña población quees probable que se produzca. Si un gran asentamiento que se espera, la elevación del fondo del tanque se elevará de manera que la elevación final por encima del nivelserá de un mínimo de 150 mm (6 pulgadas)después de la liquidación.B.3.2 Existen varios materiales diferentes que se pueden utilizar para el grado o la superficie sobre la que el fondo del tanque descansará. Para minimizarfuturos problemas de corrosión y de maximizar el efecto de los sistemas de prevención de la corrosión tales como la protección catódica, el materialen contacto con el fondo del tanque debe ser fino y uniforme. Partículas de grava o grande debe evitarse. Limpie arena lavada

Page 5: 118637409 Traduccion Apendice B API 650

or rocks could cause corrosion cells that will cause pitting and premature tank bottom failure.During construction, the movement ofequipment and materials across the grade will mar the graded surface. These irregularities should be corrected before bottom plates are placed for welding.Adequate provisions, such as making size gradients in sublayers progressively smaller from bottom to top, should be made to prevent the fine material from leaching down into the larger material, thus negating the effect of using the fine material as a final layer. This is particularly important for the top of a crushed rock ringwall. Note: For more information on tank bottom corrosion and corrosion prevention that relates to the foundation of a tank, see API RP 651.B.3.3 Unless otherwise specified by the Purchaser, the finished tank grade shall be crowned from its outer periphery to its center at a slope of 1 in. in 10 ft. The crown will partly compensate for slight settlement, which is likely to be greater at the center. Itwill also facilitate cleaning and the removal of water and sludge through openings in the shell or from sumps situated near the shell. Because crowning will affect the lengths of roof- supporting columns, it is essential that the tank Manufacturer be fullyinformed of this feature sufficiently in advance. (For an alternative to this paragraph, see B.3.4.) B.3.4 As an alternative to B.3.3, the tank bottom may be sloped toward a sump. The tank Manufacturer must be advised as required in B.3.3.

75 mm - 100 mm (3 pulgadas - 4 pulgadas) de profundidad se recomienda como una capa final porque puede ser fácilmente adaptado al contorno inferior de latanque para proporcionar un área de contacto máxima y proteger el fondo del tanque entre en contacto con las partículas grandes y los desechos.Grandes objetos extraños o puntos de contacto de grava o rocas puede causar que las células de corrosión que causan picaduras y depósito prematurofondo fracaso.Durante la construcción, el movimiento de equipos y materiales a través de la calificación se estropee la superficie graduada. Estas irregularidadesdebe ser corregida antes de placas de fondo secolocan para la soldadura.Las medidas adecuadas, como hacer que los gradientes de tamaño en subcapas cada vez más pequeños de abajo hacia arriba, deben tomar medidas para impedirel material fino de la lixiviación hacia abajo en el material de mayor tamaño, lo que anula el efecto de usar el material fino como una final capa. Esto es particularmente importante parala parte superior de un Ringwall roca triturada.Nota: Para obtener más información sobre la corrosión del fondo del tanque y prevención de la corrosión que se refiere a la fundación de un tanque, vea API RP 651.B.3.3 A menos que se especifique lo contrario por parte del comprador, el grado de acabado del tanque serán coronados desde su periferia exterior de su centrocon una inclinación de 1 cm en 10 pies La coronaparcialmente compensará la solución ligera, que es probable que sea mayor en el centro. Lo también facilitar la limpieza y la eliminación de agua y lodo a través de los orificios del depósito o de sumideros situados cerca de lashell. Debido coronación afectará las longitudes de columnas de soporte de techo, es esencial que el fabricante del tanque ser completamente informado de esta función con la suficiente antelación. (Para una alternativa a este párrafo, véase B.3.4).B.3.4 Como alternativa a B.3.3, el fondo del tanque puede estar inclinada hacia un sumidero. El fabricante del tanque debe ser informado

Page 6: 118637409 Traduccion Apendice B API 650

requerida en B.3.3.

B.4 Typical Foundation TypesB.4.1 EARTH FOUNDATIONS WITHOUT A RINGWALL

B.4.1.1 When an engineering evaluation of subsurface conditions that is based on experience and/or exploratory work has shown that the subgrade has adequate bearing capacity and that settlements will be acceptable, satisfactory foundations may beconstructed from earth materials. The performance requirements for earth foundations are identical to those for more extensive foundations. Specifically, an earth foundation should accomplish the following:

a. Provide a stable plane for the support of the tank.b. Limit overall settlement of the tank grade to values compatible with the allowances used in the design of the connecting piping.c. Provide adequate drainage.d. Not settle excessively at the perimeter due to the weight of the shell wall.B.4.1.2 Many satisfactory designs are possible when sound engineering judgment is used in their development. Three designs are referred to in this appendix on the basis of their satisfactory long-term performance. For smaller tanks, foundations can consistof compacted crushed stone, screenings, fine gravel, clean sand, or similar material placed directly on virgin soil. Any unstable material must be removed, and any replacement material must be thoroughly compacted. Tworecommended designs that include ringwalls are illustrated in Figures B-1 and B-2 and described in B.4.2 and B.4.3.

EARTH FOUNDATIONS WITH A CONCRETE RINGWALL

B.4.2.1 Large tanks and tanks with heavy or tall shells and/or self-supported roofs impose a substantial load on the foundation under the shell. This is particularly important with regard

B.4 Tipos típicos de Cimentación B.4.1 Cimentaciones de tierra sin anillo de concreto

B.4.1.1 Cuando una evaluación técnica de las condiciones del subsuelo, que se basa en la experiencia y / o trabajo exploratorio ha demostrado que la sub-base tiene capacidad de carga adecuada y que los asentamientos sean aceptables, las fundaciones pueden ser satisfactoriosconstruido a partir de materiales de la tierra. Los requisitos de rendimiento para las fundaciones de tierra son idénticas a las de bases más amplias. En concreto, una fundación tierra debe cumplir con lo siguiente:

a. Proporcionar un plano estable para el soporte del depósito.b. Limitar solución global del grado tanque a valores compatibles con las dietas usadas en el diseño de la tubería de conexión.c. Proveer drenaje adecuado.d. No se conforme excesivamente en el perímetro debido al peso de la pared del depósito.B.4.1.2 diseños satisfactorios Muchos son posibles cuando el juicio de ingeniería de sonido se utiliza en su desarrollo. Tres diseños se refiere el presente anexo sobre la base de su satisfactoria a largo plazo. Para tanques más pequeños, las fundaciones pueden consistirde material compactado de piedra triturada, proyecciones, grava fina, arena limpia, o similar colocado directamente sobre suelo virgen. Cualquier material inestable debe ser eliminado, y cualquier material de sustitución debe ser compactado a fondo. Dos diseñosrecomendados que incluyen ringwalls se ilustran en las Figuras B-1 y B-2 y se describe en B.4.2 y B.4.3.

B.4.2 Cimentaciones de tierra con anillo de concreto

B.4.2.1 grandes tanques y tanques con cáscaras pesadas o altos techos y / o auto-apoyados por imponer una carga sustancial sobre la fundación de la cáscara. Esto es particularmente

Page 7: 118637409 Traduccion Apendice B API 650

to shell distortion in floating-roof tanks. When there is some doubt whether a foundation will be able to carry the shell load directly, a concrete ringwall foundation should be used. As an alternative to the concrete ringwall noted in this section, a crushed stone ringwall (see B.4.3) may be used. A foundation with a concrete ringwall has the following advantages:a. It provides better distribution of the concentrated load of the shell to produce amore nearly uniform soil loading under the tank. b. It provides a level, solid starting plane for construction of the shell.c. It provides a better means of leveling the tank grade, and it is capable of preserving its contour during construction.d. It retains the fill under the tank bottom and prevents loss of material as a result of erosion. e. It minimizes moisture under the tank.A disadvantage of concrete ringwalls is that they may not smoothly conform to differential settlements. This disadvantage may lead to high bending stresses in the bottom plates adjacent to the ringwall.

B.4.2.2 When a concrete ringwall is designed, it shall be proportioned so that the allowable soil bearing is not exceeded. The ringwall shall not be less than 300 mm (12 in.) thick. The centerline diameter of the ringwall should equal the nominal diameter ofthe tank; however, the ringwall centerline mayvary if required to facilitate the placement of anchor bolts or to satisfy soil bearing limits for seismic loads or excessive uplift forces. The depth of the wall will depend on local conditions, but the depth must be sufficient to place the bottom of the ringwall below the anticipated frost penetration and within the specified bearing strata. As a minimum, the bottom of the ringwall, if founded on soil, shall be located 0.6 m (2 ft) below the lowestadjacent finish grade. Tank foundations must be constructed within the tolerances specified in7.5.5. Recesses shall be provided in the wall for flush-type cleanouts, drawoff sumps, and any other appurtenances that require recesses.

importante con respecto a la distorsión de la carcasa en los tanques de flotación con techo corredizo. Cuando hay alguna duda sobre si una base será capaz de soportar la carga de shell directamente, a fundación de hormigón Ringwall se debe utilizar. Como una alternativa a la Ringwall hormigón se indica en esta sección, una piedra triturada Ringwall (ver B.4.3) se puede utilizar. Una fundación con a Ringwall concreto tiene las siguientes ventajas:a. Se proporciona una mejor distribución de la carga concentrada de la cáscara para producir una carga de suelo más casi uniforme bajo el depósito.b. Se proporciona un nivel, plano sólido de partida para la construcción del depósito.c. Se proporciona un medio mejor de nivelar el grado tanque, y es capaz de preservar su contorno durante la construcción.d. Se mantiene el relleno bajo la parte inferior del depósito y evita la pérdida de material como resultado de la erosión.e. Se minimiza la humedad por debajo del depósito.Una desventaja de ringwalls concreto es que no puede ajustarse sin problemas a los asentamientos diferenciales. Este inconveniente puede dar lugar a altos esfuerzos de flexión en las placas de fondo adyacentes a la Ringwall.

B.4.2.2 Cuando un Ringwall concreto está diseñado, deberá estar dimensionada de modo que la resistencia del suelo permitida no se excede. LaRingwall no deberá ser inferior a 300 mm (12 pulg) de espesor. El diámetro central de la Ringwall debe ser igual al diámetro nominal de el tanque, sin embargo, la línea central Ringwall puede variar si es necesario para facilitar la colocación de pernos de anclaje o para satisfacer cojinete suelolímites para las cargas sísmicas o fuerzas excesivas levantamiento. La profundidad de la pared dependerá de las condiciones locales, pero la profundidad debe sersuficiente para colocar la parte inferior de la Ringwall debajo de la penetración esperada helada y dentro de los estratos que contienen especificados. Comomínimo, la parte inferior de la Ringwall, si es basada en el suelo, se encuentra 0,6 m (2 pies)

Page 8: 118637409 Traduccion Apendice B API 650

B.4.2.3 A ringwall should be reinforced against temperature changes and shrinkage and reinforced to resist the lateral pressure of the confined fill with its surcharge from product loads. ACI 318 is recommended for design stress values, material specifications, and rebar development and cover. The following items concerning a ringwall shall be considered:a. The ringwall shall be reinforced to resist the direct hoop tension resulting from the lateral earth pressure on the ringwall’s inside face. Unless substantiated by proper geotechnical analysis, the lateral earth pressure shall be assumed to be at least 50% of the vertical pressure due to fluid and soil weight. If a granular backfill is used, a lateral earth pressure coefficient of 30% may be used.b. The ringwall shall be reinforced to resist thebending moment resulting from the uniform moment load. The uniform moment load shall account for the eccentricities of the applied shell and pressure loads relative to the centroid ofthe resulting soil pressure.The pressure load is due to the fluid pressure on the horizontal projection of the ringwall inside the shell.c. The ringwall shall be reinforced to resist the bending and torsion moments resulting from lateral, wind, or seismic loads applied eccentrically to it. A rational analysis, which includes the effect of the foundation stiffness, shall be used to determine these moments and soil pressure distributions.

d. The total hoop steel area required to resist the loads noted above shall not be less than the area required for temperature changes and shrinkage. The hoop steel area required for temperature changes and shrinkage is 0.0025 times the vertical cross-sectional area of the

por debajo del grado más bajo de acabado adyacente. Tanquecimientos deben ser construidos dentro de lastolerancias especificadas en 7.5.5. Los huecos se facilitará en la pared para montaje incorporado limpiezas, sumideros drawoff, y cualquier otros accesorios que requieran recesos.B.4.2.3 Una Ringwall debería reforzarse contralos cambios de temperatura y la contracción y reforzado para resistir la presión lateraldel relleno confinado con su pago de las cargas de productos. ACI 318 se recomienda para los valores de tensión de diseño, especificaciones de materiales,barras de refuerzo y el desarrollo y la cubierta. Los siguientes artículos relativos a una Ringwall se considerará:una. El Ringwall estará reforzado para resistir latensión del aro directo resultante de la presión lateral de tierra en el interior de la Ringwall de cara. A menos que se fundamenta en el análisis geotécnico adecuado, la presión lateral de tierra se supone que al menos 50% de la vertical debido a la presión del fluido y el peso del suelo. Si un relleno granular se utiliza, un coeficientede empuje lateral de 30% puede ser utilizado. b. El Ringwall estará reforzado para resistir el momento de flexión resultante de la carga de momento uniforme. El momento uniformecarga deberá representar las excentricidades de la cáscara aplicado y cargas de presión en relación con el centroide de la presión del suelo resultante.La carga de presión es debido a la presión del fluido en la proyección horizontal de la Ringwall dentro de la cáscara.c. El Ringwall estará reforzado para resistir losmomentos de flexión y torsión que resultan de viento lateral, o cargas sísmicasaplicada excéntricamente a la misma. Un análisis racional, que incluye el efecto de la rigidez de la fundación, se utiliza para determinarestos momentos y distribuciones de suelos presión.

d. El área de aro de acero total requerida para resistir las cargas mencionadas anteriormente no será menor que el área necesaria para los cambios de temperatura y la contracción. Elárea de acero aro requerido para los cambios de temperatura y la contracción es 0,0025 veces la

Page 9: 118637409 Traduccion Apendice B API 650

ringwall or the minimum reinforcement for walls called for in ACI 318, Chapter 14.e. For ringwalls, the vertical steel area requiredfor temperature changes and shrinkage is0.0015 times the horizontal cross-sectional area of the ringwall or the minimum reinforcement for walls called for in ACI 318, Chapter 14. Additional vertical steel may be required for uplift or torsional resistance. If the ring foundation is wider than its depth, the design shall consider its behavior as an annular slab with flexure in the radial direction. Temperature and shrinkage reinforcement shall meet the ACI318provisions for slabs. (See ACI 318, Chapter 7.)f. When the ringwall width exceeds 460 mm (18 in.), using a footing beneath the wall should be considered. Footings may also be useful for resistance to uplift forces.g. Structural backfill within and adjacent to concrete ringwalls and around items such as vaults, undertank piping, and sumps requires close field control to maintain settlement tolerances. Backfill should be granular material compacted to the density and compacting as specified in the foundation construction specifications. For other backfill materials, sufficient tests shall be conducted to verify that the material has adequate strength and will undergo minimal settlement.h. If the tank is designed and constructed for elevated temperature service, see B.6.

B.4.3 EARTH FOUNDATIONS WITH A CRUSHED STONE AND GRAVEL RINGWALL

B.4.3.1 A crushed stone or gravel ringwall will provide adequate support for high loads imposed by a shell. A foundation with a crushed stone or gravel ringwall has the following advantages:a. It provides better distribution of the concentrated load of the shell to produce amore nearly uniform soil loading under the tank.

sección transversal vertical de la zona Ringwall o el refuerzo mínimo para las paredes que se solicitan en ACI 318, Capítulo 14.e. Para ringwalls, el área vertical de acerorequerido para los cambios de temperatura y contracción es 0,0015 veces la sección transversal horizontal de la zona Ringwall o el refuerzo mínimo para las paredes que se solicitan en ACI 318, Capítulo 14. Vertical de acero adicional puede ser necesaria para la elevación o la resistencia torsional. Si la base del anillo es más ancho que su profundidad, el diseño deberá tener en cuenta su comportamiento como una losa anular con la flexión en la dirección radial. Temperatura y refuerzo para la contracción se reunirá el ACI318disposiciones para losas. (Véase el ACI 318,capítulo 7.)f. Cuando la anchura Ringwall excede 460 mm (18 pulgadas), utilizando una base debajo de la pared debe ser considerado. Zapatas también puede ser útil para elevar la resistencia a las fuerzas.g. Relleno estructural dentro y los elementos adyacentes a ringwalls concretas y en todo, como bóvedas, tuberías y sumideros undertank, requiere un control de campo cercano para mantener las tolerancias de liquidación. El relleno deberá ser material granularcompactada a la densidad de compactación y como se especifica en las especificaciones de construcción de cimentación. Para otros materiales de relleno, las suficientes pruebas se llevó a cabo para verificar que el material tenga la resistencia adecuada y será objeto de liquidación mínima.h. Si el tanque está diseñado y construido para el servicio de elevada temperatura, ver B.6.

B.4.3 CIMENTACIONES DE TIERRA CON PIEDRA TRITURADA Y MURO ANULAR DE GRAVA

B.4.3.1 Una piedra triturada o grava Ringwall proporcionará un apoyo adecuado a las altas cargas impuestas por una concha. Una base con una piedra machacada o grava Ringwall tiene las siguientes ventajas:una. Se proporciona una mejor distribución de la carga concentrada de la cáscara para producir una carga de suelo más casi uniforme bajo el

Page 10: 118637409 Traduccion Apendice B API 650

b. It provides a means of leveling the tank grade, and it is capable of preserving its contour during construction.c. It retains the fill under the tank bottom andprevents loss of material as a result of erosion. d. It can more smoothly accommodate differential settlement because of its flexibility. A disadvantage of the crushed stone or gravel ringwall is that it is more difficult to construct it to close tolerances and achieve a flat, level plane for construction of the tank shell.B.4.3.2 For crushed stone or gravel ringwalls, careful selection of design details is necessary to ensure satisfactory performance.The type of foundation suggested is shown in Figure B-2. Significant details include the following:a. The 0.9 m (3 ft) shoulder and berm shall beprotected from erosion by being constructed of crushed stone or covered with a permanent paving material.b. Care shall be taken during construction to prepare and maintain a smooth, level surface for the tank bottom plates.c. The tank grade shall be constructed to provide adequate drainage away from the tank foundation.d. The tank foundation must be true to thespecified plane within the tolerances specified in7.5.5.

B.4.4 SLAB FOUNDATIONSB.4.4.1 When the soil bearing loads must be distributed over an area larger than the tank area or when it is specified by the owner, a reinforced concrete slab shall be used. Piles beneath the slab may be required for proper tank support.B.4.4.2 The structural design of the slab, whether on grade or on piles, shall properly account for all loads imposed upon the slab by the tank. The reinforcement requirements and the design details of construction shall be in accordance with ACI 318.

B.5 Tank Foundations for Leak Detection B.5Appendix I provides recommendations on the

depósito.b. Se proporciona un medio de nivelación del grado tanque, y es capaz de preservar su contorno durante la construcción.c. Se mantiene el relleno bajo la parte inferior del depósito y evita la pérdida de material como resultado de la erosión.d. Se puede acomodar sin problemasasentamiento diferencial debido a su flexibilidad.Una desventaja de la piedra machacada o grava Ringwall es que es más difícil de construir para cerrar las tolerancias y lograr una superficie plana y nivelada para la construcción de la estructura del tanque.B.4.3.2 Para piedras machacadas o grava ringwalls, la selección cuidadosa de los detalles del diseño es necesaria para asegurar un rendimiento satisfactorio.El tipo de cimentación sugerida se muestra en la Figura B-2. Los detalles significativos son los siguientes:una. El 0,9 m (3 pies) de hombro y berma deberá estar protegido contra la erosión por estar construido de piedra machacada o cubierto con un material de pavimentación permanente.b. Se debe tener cuidado durante la construcción para preparar y mantener una superficie lisa y plana para las placas del fondo del tanque.c. El grado tanque será construido para permitir la evacuación de los cimientos del tanque.d. La base del tanque debe ser fiel al plano indicado dentro de las tolerancias especificadas en 7.5.5.

B.4.4 losas de cimentaciónB.4.4.1 Cuando las cargas de apoyo del suelo debe ser distribuido sobre un área más grande que el área de depósito o cuando se especifica por el propietario, una losa de hormigón armado se utilizará. Piles debajo de la losa puede ser necesario para el soporte del tanque apropiado. B.4.4.2 El diseño estructural de la losa, si elgrado o sobre pilotes, adecuadamente deberá representar todas las cargas impuestas sobre la losa de la cisterna. Los requisitos de refuerzo y los detalles de diseño de construcción deben estar de acuerdo con ACI 318.

B.5 Fundamentos del tanque para la detección de fugas.

Page 11: 118637409 Traduccion Apendice B API 650

construction of tank and foundation systems for the detection of leaks through the bottoms of storage tanks.

B.6 Tank Foundations for ElevatedTemperature ServiceThe design and construction of foundations for tanks operating at elevated temperatures [>93°C (200°F)] should address the following considerations.a. When subjected to elevated operating temperatures, an unanchored tank may tend to move in one or more directions over time.This movement must be accommodated in the design of the tank fittings and attachments.b. Elevated temperature service may evaporate moisture in the soil supporting the tank and lead to increased, and possibly nonuniform, settlement. Such settlement may include differential settlement between the ringwall and soil under the tank bottom immediatelyadjacent to the ringwall resulting from non- uniform shrinkage of the soil with respect to the stone or concrete ringwall.c. In cases where there is high groundwatertable, elevated temperatures may vaporize groundwater and generate undesirable steam. d. Attachments between the tank and the foundation must accommodate the thermal expansion and contraction of the tank without resulting in unacceptable stress levels.e. The elevated temperature must be accounted for in the design of concrete ringwall foundations. The ringwall is subject to a moment due to the higher temperature at the top of the ringwall with respect to the temperature at the bottom of the ringwall. If not adequately accounted for in the design of the ringwall, this moment can lead to cracking of the concrete foundation and loss of tank support.

El Apéndice I proporciona recomendaciones sobre la construcción de sistemas de tanques y bases para la detección de fugas a través de los fondos de los tanques de almacenamiento.

B.6 Fundamentos del tanque para el servicio de temperatura elevadaEl diseño y la construcción de cimientos para lostanques que operan a temperaturas elevadas [>93 ° C (200 ° F)] debe atender a las siguientes consideraciones.una. Cuando se somete a temperaturas de funcionamiento elevadas, un tanque sin anclar puede tender a moverse en una o más direcciones en el tiempo.Este movimiento debe ser acomodado en eldiseño de los accesorios de tanque y accesorios. b. Servicio de temperatura elevada puede evaporar la humedad en el suelo de soporte del depósito y provocar un aumento, y no uniforme, posiblemente, de liquidación. Solución de este tipo puede incluir un asentamiento diferencial entre el Ringwall y el suelo bajo el fondo del tanque inmediatamente adyacente a la Ringwall resultante de la contracción no uniforme de la tierra con respecto a la piedra o de hormigón Ringwall.c. En caso de que exista freático alto, las temperaturas elevadas pueden vaporizar el agua subterránea y generar vapor de aguaindeseable.d. Adjuntos entre el tanque y la base debe adaptarse a la expansión y contracción térmica del tanque sin resultar en niveles de estrés inaceptables.e. La temperatura elevada debe tenerse encuenta en el diseño de los cimientos de hormigón Ringwall. El Ringwall está sujeto a un momento debido a la temperatura más alta enla parte superior de la Ringwall con respecto a la temperatura en la parte inferior de la Ringwall.Si no adecuadamente en cuenta en el diseño de la Ringwall, este momento puede conducir a la rotura de los cimientos de hormigón y la pérdida de soporte del depósito.