LAHMEYER INTERNATIONAL
GOVERNMENT OF THE REPUBLIC OF THE SUDANMINISTRY OF IRRIGATION AND WATER RESOURCES
MEROWE DAM PROJECT IMPLEMENTATION UNIT
MEROWE DAM PROJECT 10 x 140MVA
CONTRACTS 3A, 3B, 3C, 3E
ENGINEER:CONTRACTOR:
OPERATING & MAINTENANCE MANUAL
SANITARY WASTE WATER TREATMENT SYSTEMCONTROLLER CABINET, TECHNICAL LEAFLETS, UPS & UNIT DISPLAY -SEO-
(92SEOW01DL, 92SEO001AR)
SCALE1/1
Subcontractor:
INTERNAL USE
Power EnvironmentHydro
REV
ASH/SH END
1/
N of SH AHS MRW00SEO.OM.109.06
Ce document propriété de ALSTOM ne doit pas être utilisé, copié ou communiqué à des tiers sans son autorisation
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 1 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
2/415
CHAPTER
B) List of Illustrations 4
C) Introduction: 5
C1) General Description of Equipment ………… 6
C2) Brief Description of Equipment Use ………… 7
C3) Definitions and Technical Terms Used ………… 9
C4) List of items used ………… 10
D) Detailed Description of Equipment
E) Operating Principles and Characteristics
● UNINTERRUPTABLE POWER SUPPLY (UPS) ………… 12
‐ SAFETY STANDARDS ………… 15
‐GENERAL DESCRIPTION / OPERATION ………… 16
‐UNPACKING & INSTALLATION ………… 18
‐ CONFIGURATION & START UP ………… 21
‐ DISPLAYS & CONTROLS ………… 22
‐USE OF SIGNAL RELAY ………… 26
‐ TECHNICAL DATA ………… 27
‐ TROUBLESHOOTING ………… 28
● CONTROL CUBICLE EQUIPMENT DRAWING ‐ SANITARY WASTE WATER TREATMENT SYS. ………… 29
● ELECTRICAL DIAGRAM ‐ SANITARY WASTE WATER TREATMENT SYS. ………… 39
● TECHNICAL LEAFLETS ………… 65
‐ CIRCUIT BREAKERS ………… 66
‐ CONTROL & SIGNALLING UNITS ………… 88
‐ POWER DISTRIBUTION ………… 138
‐ CURRENT TRANSFORMER ………… 140
‐MOTOR STARTERS ………… 153
‐ CONTACTOR CONTROL UNITS ………… 169
‐ BEACONS ………… 176
‐ RELAYS ………… 183
‐MISCELLANEOUS COMPONENTS ………… 194
F) Operating Instructions
G) Testing and Adjustment ● UNIT DISPLAY OPERATOR'S MANUAL ‐ MEGALIS XBT R410 ………… 209
● UNIT DISPLAY USER MANUAL ………… 216
PAGE
……………
……………
……… 11
……… 208
OPERATION & MAINTENANCE MANUAL
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 2 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
3/415
CHAPTER
H) Maintenance Instructions: 407
H1) Preventive Maintenance ………… 408
H2) Repair and Adjustment ………… 409
● MAINTENANCE INSTRUCTIONS: UPS SYSTEM ………… 410
H3) Spare Parts Lists ………… 412
H4) Special Tools Lists ………… 414
H5) List of Suppliers ………… 415
J) As Built Drawings ………… 416
……………
OPERATION & MAINTENANCE MANUAL
PAGE
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 3 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
4/415
B) LIST OF ILLUSTRATIONS
SITE TEST REPORTSSEO – DOMESTIC SEWAGE – SANITARY
WASTEWATER TREATMENT SYSTEM
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 4 of 416
http://seo_site%20test%20reports/00_00SEO_TABLE%20OF%20CONTENTS.xlshttp://seo_site%20test%20reports/00_00SEO_TABLE%20OF%20CONTENTS.xls
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
5/415
C) INTRODUCTION
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 5 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
6/415
C1) BRIEF DESCRIPTION OF EQUIPMENT
CONTROLLER CABINET ,UNINTERRUPTED POWER SUPPLY,DISPLAY UNIT
LIST OF MAIN EQUIPMENT:
REFERENCE DESCRIPTION MODEL SUPPLIER
92SEOW01DLUINTERREUPTED POWER SUPPLY
(UPS)ENT-TW15
(800-2000VA)MANUF: SOCOMECSICONSUPPLIER: HYTEC
--- UNIT DISPLAY XBTR410 MANUF: MAGELIS(SCHNEIDER)SUPPLIER: HYTEC
92SEO001AR CABINET CONTROLLER --- SUPPLIER: HYTEC
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 6 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
7/415
C2) DESCRIPTION OF USE OF EQUIPMENT
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 7 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
8/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 8 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
9/415
C3) DEFINITION OF TECHNICAL TERMS
UPS: The main purpose of the UPS is to protect sensitive and critical equipment items fromthe electrical disturbances that can compromise operation. Black-outs, brown-outs,variations of voltage and frequency, lightening, electrostatic discharges and rapidovervoltages are phenomena found in all office and industrial environments and which causehardware damage and data losses.
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 9 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
10/415
C4) List of Items Used
UNIT SYS. NUM TYPE DESIGNATION SUPP. ROOM
92 SEO 001 AR CABINET CONTROLER AHS STP
92 SEO 001 DL UNINTERRUPTIBLE POWER SUPPLY AHS STP
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 10 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
11/415
D) DETAILED DESCRIPTION&
E) OPERATING PRINCIPLES ANDCHARACTERISTICS
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 11 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
12/415
UNINTERRUPTIBLE POWERSUPPLY
UPS - 92SEO001DL
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 12 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
13/415
992-11803.11. 180/201 /A
5. MISCELLANEOUS
5.1. Uninterruptible power supply 92SEOW01DL
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 13 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
14/415
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
15/415
992-11803.11. 182/201 /A AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 15 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
16/415
992-11803.11. 183/201 /A AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 16 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
17/415
992-11803.11. 184/201 /A AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 17 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
18/415
992-11803.11. 185/201 /A AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 18 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
19/415
992-11803.11. 186/201 /A AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 19 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
20/415
992-11803.11. 187/201 /A AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 20 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
21/415
992-11803.11. 188/201 /A AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 21 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
22/415
992-11803.11. 189/201 /A AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 22 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
23/415
992-11803.11. 190/201 /A AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 23 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
24/415
992-11803.11. 191/201 /A AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 24 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
25/415
992-11803.11. 192/201 /A AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 25 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
26/415
992-11803.11. 193/201 /A AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 26 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
27/415
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
28/415
992-11803.11. 195/201 /A AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 28 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
29/415
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
30/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
31/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
32/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
33/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
34/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
35/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
36/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
37/415
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
38/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
39/415
SANITARY WASTE WATER TREATMENT SYSTEM
ELECTRICAL DIAGRAM
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 39 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
40/415
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
41/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
42/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
43/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
44/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
45/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
46/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
47/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
48/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
49/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
50/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
51/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
52/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
53/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
54/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
55/415
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
56/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
57/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
58/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
59/415
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
60/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
61/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
62/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
63/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
64/415
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
65/415
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
66/415
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
67/415
T h e
i n f o r m a
t i o n p r o v
i d e
d i n
t h i s d o c u m e n
t a t i o n c o n
t a i n s g e n e r a
l d e s c r i p
t i o n s a n
d / o r
t e c
h n
i c a
l c
h a r a c
t e r i s
t i c s o
f t h e p e r f o r m a n c e o
f t h e p r o
d
u c
t s c o n
t a i n e
d h e r e
i n .
T h i s d o c u m e n
t a t i o n
i s n o
t i n
t e n
d e
d a s a s u
b s
t i t u t e f o r a n
d i s n o
t t o b e u s e
d f o r
d e
t e r m
i n i n g s u
i t a
b i l i t y o r r e
l i a
b i l i t y o
f t h e s e p r o
d u c
t s f o r s p e c
i f i c u s e r a p p
l i c a
t i o n s .
I t i s t h e
d u
t y o
f a n y s u c
h u s e r o r
i n t e g r a
t o r
t o p e r f o r m
t h e a p p r o p r i a
t e a n
d c o m p
l e t e
r i s
k a n a
l y s
i s ,
e v a
l u a
t i o n a n
d t e s
t i n g o
f t h e p r o
d u c
t s w
i t h
r e s p e c
t t o t h e r e
l e v a n
t s p e c
i f i c a p p
l i c a
t i o n o r u s e
t h e r e o
f .
N e
i t h e r
S c
h n e
i d e r
E l e c
t r i c I n
d u s
t r i e s
S A S n o r a n y o
f i t s a
f f i l i a t e s o r s u
b s
i d i a r i e s s
h a
l l b e r e s p o n s
i b l e o r
l i a
b l e f o r m
i s u s e o
f t h e
i n f o r m a
t i o n c o n
t a i n e
d h e r e
i n .
Mon Oct 11 10:03:43 EDT 2010
1
Product data sheetCharacteristics
24186miniature circuit breaker Multi 9 - C60N - 1 pole
+ N - 4 A - C curve
Certifications and standards
Standards EN 60898
IEC 60947-2
Compatibility
Comb busbar distribution block compatibility NO
Earth-leakage protection Separate block
Product compatibility C60 accessories
C60 auxiliary
Connections
Connections - terminals Tunnel type terminals 25 mm² rigid
Tunnel type terminals 16 mm² flexible
Electrical
[In] rated current 4 A 30 °C
[Ue] rated operational voltage 12...440 V AC 50/60 Hz
[Ui] rated insulation voltage 500 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV IEC 60947-2
Breaking capacity 20 kA Icu IEC 60947-2 130 V AC 50/60 Hz
10 kA Icu IEC 60947-2 230...240 V AC 50/60 Hz
3 kA Icu IEC 60947-2 400...415 V AC 50/60 Hz
15 kA Icu IEC 60947-2 60 V DC 1P
6 kA Icn EN 60898 230/400 V AC 50/60 Hz
Magnetic tripping limit 5...10 x In
Network frequency 50/60 Hz
Environment
Ambient air temperature for operation -25...60 °C
Ambient air temperature for storage -40...70 °C
Operating altitude 2000 m
Relative humidity 95 % 55 °C
Tropicalisation 2 IEC 60068-1
RoHS EUR conformity date 0643
RoHS EUR status Compliant
Functional
Contact position indicator Yes
Control type Toggle
Limitation class 3 IEC 60947-2
Local signalling ON/OFF indication
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 67 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
68/415
2
Installation
Mounting mode Fixed
Mounting support 35 mm symmetrical DIN rail
Performance
[Ics] rated service breaking capacity 2,25 kA IEC 60947-2 400...415 V AC 50/60 Hz
6 kA EN 60898 230/400 V AC 50/60 Hz
7,5 kA IEC 60947-2 230...240 V AC 50/60 Hz15 kA IEC 60947-2 130 V AC 50/60 Hz
Mechanical durability 20000 cycles
Physical characteristics
9 mm pitches 4
Depth 73 mm
Height 81 mm
Product weight 0,12 kg
Tightening torque 2 N.m upside power circuit
2 N.m downside
Width 36 mm
Poles descriptions
Neutral position Left
Number of protected poles 1
Poles description 1P + N
Product identification
Device short name C60N
Range of product C60
Usage / Application
Circuit breaker application Distribution
Curve code C
Network type AC
DC
Suitability for isolation Yes IEC 60947-2
Trip unit technology Thermal-magnetic
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 68 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
69/415
T h e
i n f o r m a
t i o n p r o v
i d e
d i n
t h i s d o c u m e n
t a t i o n c o n
t a i n s g e n e r a
l d e s c r i p
t i o n s a n
d / o r
t e c
h n
i c a
l c
h a r a c
t e r i s
t i c s o
f t h e p e r f o r m a n c e o
f t h e p r o
d
u c
t s c o n
t a i n e
d h e r e
i n .
T h i s d o c u m e n
t a t i o n
i s n o
t i n
t e n
d e
d a s a s u
b s
t i t u t e f o r a n
d i s n o
t t o b e u s e
d f o r
d e
t e r m
i n i n g s u
i t a
b i l i t y o r r e
l i a
b i l i t y o
f t h e s e p r o
d u c
t s f o r s p e c
i f i c u s e r a p p
l i c a
t i o n s .
I t i s t h e
d u
t y o
f a n y s u c
h u s e r o r
i n t e g r a
t o r
t o p e r f o r m
t h e a p p r o p r i a
t e a n
d c o m p
l e t e
r i s
k a n a
l y s
i s ,
e v a
l u a
t i o n a n
d t e s
t i n g o
f t h e p r o
d u c
t s w
i t h
r e s p e c
t t o t h e r e
l e v a n
t s p e c
i f i c a p p
l i c a
t i o n o r u s e
t h e r e o
f .
N e
i t h e r
S c
h n e
i d e r
E l e c
t r i c I n
d u s
t r i e s
S A S n o r a n y o
f i t s a
f f i l i a t e s o r s u
b s
i d i a r i e s s
h a
l l b e r e s p o n s
i b l e o r
l i a
b l e f o r m
i s u s e o
f t h e
i n f o r m a
t i o n c o n
t a i n e
d h e r e
i n .
Mon Oct 11 10:09:27 EDT 2010
1
Product data sheetCharacteristics
24187miniature circuit breaker Multi 9 - C60N - 1 pole
+ N - 6 A - C curve
Certifications and standards
Standards EN 60898
IEC 60947-2
Compatibility
Comb busbar distribution block compatibility NO
Earth-leakage protection Separate block
Product compatibility C60 accessories
C60 auxiliary
Connections
Connections - terminals Tunnel type terminals 16 mm² flexible
Tunnel type terminals 25 mm² rigid
Electrical
[In] rated current 6 A 30 °C
[Ue] rated operational voltage 12...440 V AC 50/60 Hz
[Ui] rated insulation voltage 500 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV IEC 60947-2
Breaking capacity 20 kA Icu IEC 60947-2 130 V AC 50/60 Hz
10 kA Icu IEC 60947-2 230...240 V AC 50/60 Hz
3 kA Icu IEC 60947-2 400...415 V AC 50/60 Hz
15 kA Icu IEC 60947-2 60 V DC 1P
6 kA Icn EN 60898 230/400 V AC 50/60 Hz
Magnetic tripping limit 5...10 x In
Network frequency 50/60 Hz
Environment
Ambient air temperature for operation -25...60 °C
Ambient air temperature for storage -40...70 °C
Operating altitude 2000 m
Relative humidity 95 % 55 °C
Tropicalisation 2 IEC 60068-1
RoHS EUR conformity date 0643
RoHS EUR status Compliant
Functional
Contact position indicator Yes
Control type Toggle
Limitation class 3 IEC 60947-2
Local signalling ON/OFF indication
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 69 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
70/415
2
Installation
Mounting mode Fixed
Mounting support 35 mm symmetrical DIN rail
Performance
[Ics] rated service breaking capacity 15 kA IEC 60947-2 130 V AC 50/60 Hz
7,5 kA IEC 60947-2 230...240 V AC 50/60 Hz
2,25 kA IEC 60947-2 400...415 V AC 50/60 Hz6 kA EN 60898 230/400 V AC 50/60 Hz
Mechanical durability 20000 cycles
Physical characteristics
9 mm pitches 4
Depth 73 mm
Height 81 mm
Product weight 0,12 kg
Tightening torque 2 N.m upside power circuit
2 N.m downside
Width 36 mm
Poles descriptions
Neutral position Left
Number of protected poles 1
Poles description 1P + N
Product identification
Device short name C60N
Range of product C60
Usage / Application
Circuit breaker application Distribution
Curve code C
Network type AC
DC
Suitability for isolation Yes IEC 60947-2
Trip unit technology Thermal-magnetic
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 70 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
71/415
T h e
i n f o r m a
t i o n p r o v
i d e
d i n
t h i s d o c u m e n
t a t i o n c o n
t a i n s g e n e r a
l d e s c r i p
t i o n s a n
d / o r
t e c
h n
i c a
l c
h a r a c
t e r i s
t i c s o
f t h e p e r f o r m a n c e o
f t h e p r o
d
u c
t s c o n
t a i n e
d h e r e
i n .
T h i s d o c u m e n
t a t i o n
i s n o
t i n
t e n
d e
d a s a s u
b s
t i t u t e f o r a n
d i s n o
t t o b e u s e
d f o r
d e
t e r m
i n i n g s u
i t a
b i l i t y o r r e
l i a
b i l i t y o
f t h e s e p r o
d u c
t s f o r s p e c
i f i c u s e r a p p
l i c a
t i o n s .
I t i s t h e
d u
t y o
f a n y s u c
h u s e r o r
i n t e g r a
t o r
t o p e r f o r m
t h e a p p r o p r i a
t e a n
d c o m p
l e t e
r i s
k a n a
l y s
i s ,
e v a
l u a
t i o n a n
d t e s
t i n g o
f t h e p r o
d u c
t s w
i t h
r e s p e c
t t o t h e r e
l e v a n
t s p e c
i f i c a p p
l i c a
t i o n o r u s e
t h e r e o
f .
N e
i t h e r
S c
h n e
i d e r
E l e c
t r i c I n
d u s
t r i e s
S A S n o r a n y o
f i t s a
f f i l i a t e s o r s u
b s
i d i a r i e s s
h a
l l b e r e s p o n s
i b l e o r
l i a
b l e f o r m
i s u s e o
f t h e
i n f o r m a
t i o n c o n
t a i n e
d h e r e
i n .
Mon Oct 11 10:00:25 EDT 2010
1
Product data sheetCharacteristics
24188miniature circuit breaker Multi 9 - C60N - 1 pole
+ N - 10 A - C curve
Certifications and standards
Standards EN 60898
IEC 60947-2
Compatibility
Comb busbar distribution block compatibility NO
Earth-leakage protection Separate block
Product compatibility C60 accessories
C60 auxiliary
Connections
Connections - terminals Tunnel type terminals 16 mm² flexible
Tunnel type terminals 25 mm² rigid
Electrical
[In] rated current 10 A 30 °C
[Ue] rated operational voltage 12...440 V AC 50/60 Hz
[Ui] rated insulation voltage 500 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV IEC 60947-2
Breaking capacity 15 kA Icu IEC 60947-2 60 V DC 1P
20 kA Icu IEC 60947-2 130 V AC 50/60 Hz
6 kA Icn EN 60898 230/400 V AC 50/60 Hz
10 kA Icu IEC 60947-2 230...240 V AC 50/60 Hz
3 kA Icu IEC 60947-2 400...415 V AC 50/60 Hz
Magnetic tripping limit 5...10 x In
Network frequency 50/60 Hz
Environment
Ambient air temperature for operation -25...60 °C
Ambient air temperature for storage -40...70 °C
Operating altitude 2000 m
Relative humidity 95 % 55 °C
Tropicalisation 2 IEC 60068-1
RoHS EUR conformity date 0651
RoHS EUR status Compliant
Functional
Contact position indicator Yes
Control type Toggle
Limitation class 3 IEC 60947-2
Local signalling ON/OFF indication
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 71 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
72/415
2
Installation
Mounting mode Fixed
Mounting support 35 mm symmetrical DIN rail
Performance
[Ics] rated service breaking capacity 15 kA IEC 60947-2 130 V AC 50/60 Hz
7,5 kA IEC 60947-2 230...240 V AC 50/60 Hz
2,25 kA IEC 60947-2 400...415 V AC 50/60 Hz6 kA EN 60898 230/400 V AC 50/60 Hz
Mechanical durability 20000 cycles
Physical characteristics
9 mm pitches 4
Depth 73 mm
Height 81 mm
Product weight 0,12 kg
Tightening torque 2 N.m upside power circuit
2 N.m downside
Width 36 mm
Poles descriptions
Neutral position Left
Number of protected poles 1
Poles description 1P + N
Product identification
Device short name C60N
Range of product C60
Usage / Application
Circuit breaker application Distribution
Curve code C
Network type AC
DC
Suitability for isolation Yes IEC 60947-2
Trip unit technology Thermal-magnetic
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 72 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
73/415
T h e
i n f o r m a
t i o n p r o v
i d e
d i n
t h i s d o c u m e n
t a t i o n c o n
t a i n s g e n e r a
l d e s c r i p
t i o n s a n
d / o r
t e c
h n
i c a
l c
h a r a c
t e r i s
t i c s o
f t h e p e r f o r m a n c e o
f t h e p r o
d
u c
t s c o n
t a i n e
d h e r e
i n .
T h i s d o c u m e n
t a t i o n
i s n o
t i n
t e n
d e
d a s a s u
b s
t i t u t e f o r a n
d i s n o
t t o b e u s e
d f o r
d e
t e r m
i n i n g s u
i t a
b i l i t y o r r e
l i a
b i l i t y o
f t h e s e p r o
d u c
t s f o r s p e c
i f i c u s e r a p p
l i c a
t i o n s .
I t i s t h e
d u
t y o
f a n y s u c
h u s e r o r
i n t e g r a
t o r
t o p e r f o r m
t h e a p p r o p r i a
t e a n
d c o m p
l e t e
r i s
k a n a
l y s
i s ,
e v a
l u a
t i o n a n
d t e s
t i n g o
f t h e p r o
d u c
t s w
i t h
r e s p e c
t t o t h e r e
l e v a n
t s p e c
i f i c a p p
l i c a
t i o n o r u s e
t h e r e o
f .
N e
i t h e r
S c
h n e
i d e r
E l e c
t r i c I n
d u s
t r i e s
S A S n o r a n y o
f i t s a
f f i l i a t e s o r s u
b s
i d i a r i e s s
h a
l l b e r e s p o n s
i b l e o r
l i a
b l e f o r m
i s u s e o
f t h e
i n f o r m a
t i o n c o n
t a i n e
d h e r e
i n .
Mon Oct 11 10:02:23 EDT 2010
1
Product data sheetCharacteristics
24189miniature circuit breaker Multi 9 - C60N - 1 pole
+ N - 16 A - C curve
Certifications and standards
Standards EN 60898
IEC 60947-2
Compatibility
Comb busbar distribution block compatibility NO
Earth-leakage protection Separate block
Product compatibility C60 accessories
C60 auxiliary
Connections
Connections - terminals Tunnel type terminals 16 mm² flexible
Tunnel type terminals 25 mm² rigid
Electrical
[In] rated current 16 A 30 °C
[Ue] rated operational voltage 12...440 V AC 50/60 Hz
[Ui] rated insulation voltage 500 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV IEC 60947-2
Breaking capacity 20 kA Icu IEC 60947-2 130 V AC 50/60 Hz
10 kA Icu IEC 60947-2 230...240 V AC 50/60 Hz
3 kA Icu IEC 60947-2 400...415 V AC 50/60 Hz
15 kA Icu IEC 60947-2 60 V DC 1P
6 kA Icn EN 60898 230/400 V AC 50/60 Hz
Magnetic tripping limit 5...10 x In
Network frequency 50/60 Hz
Environment
Ambient air temperature for operation -25...60 °C
Ambient air temperature for storage -40...70 °C
Operating altitude 2000 m
Relative humidity 95 % 55 °C
Tropicalisation 2 IEC 60068-1
RoHS EUR conformity date 0651
RoHS EUR status Compliant
Functional
Contact position indicator Yes
Control type Toggle
Limitation class 3 IEC 60947-2
Local signalling ON/OFF indication
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 73 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
74/415
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
75/415
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
76/415
2
Installation
Mounting mode Fixed
Mounting support 35 mm symmetrical DIN rail
Performance
[Ics] rated service breaking capacity 15 kA IEC 60947-2 130 V AC 50/60 Hz
7,5 kA IEC 60947-2 230...240 V AC 50/60 Hz
2,25 kA IEC 60947-2 400...415 V AC 50/60 Hz6 kA EN 60898 230/400 V AC 50/60 Hz
Mechanical durability 20000 cycles
Physical characteristics
9 mm pitches 4
Depth 73 mm
Height 81 mm
Product weight 0,12 kg
Tightening torque 3,5 N.m upside power circuit
3,5 N.m downside
Width 36 mm
Poles descriptions
Neutral position Left
Number of protected poles 1
Poles description 1P + N
Product identification
Device short name C60N
Range of product C60
Usage / Application
Circuit breaker application Distribution
Curve code C
Network type AC
DC
Suitability for isolation Yes IEC 60947-2
Trip unit technology Thermal-magnetic
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 76 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
77/415
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
78/415
2
Functional
Contact position indicator Yes
Control type Toggle
Limitation class 3 IEC 60947-2
Local signalling ON/OFF indication
Installation
Mounting mode Fixed
Mounting support 35 mm symmetrical DIN rail
Performance
[Ics] rated service breaking capacity 7,5 kA IEC 60947-2 230...240 V AC 50/60 Hz
3,75 kA IEC 60947-2 400...415 V AC 50/60 Hz
2,25 kA IEC 60947-2 440 V AC 50/60 Hz
6 kA EN 60898 230/400 V AC 50/60 Hz
Mechanical durability 20000 cycles
Physical characteristics
9 mm pitches 6
Depth 73 mm
Height 81 mm
Product weight 0,36 kg
Tightening torque 2 N.m upside power circuit
2 N.m downside
Width 54 mm
Poles descriptions
Number of protected poles 3
Poles description 3P
Product identification
Device short name C60N
Range of product C60
Usage / Application
Circuit breaker application Distribution
Curve code C
Network type AC
DC
Suitability for isolation Yes IEC 60947-2
Trip unit technology Thermal-magnetic
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 78 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
79/415
T h e
i n f o r m a
t i o n p r o v
i d e
d i n
t h i s d o c u m e n
t a t i o n c o n
t a i n s g e n e r a
l d e s c r i p
t i o n s a n
d / o r
t e c
h n
i c a
l c
h a r a c
t e r i s
t i c s o
f t h e p e r f o r m a n c e o
f t h e p r o
d
u c
t s c o n
t a i n e
d h e r e
i n .
T h i s d o c u m e n
t a t i o n
i s n o
t i n
t e n
d e
d a s a s u
b s
t i t u t e f o r a n
d i s n o
t t o b e u s e
d f o r
d e
t e r m
i n i n g s u
i t a
b i l i t y o r r e
l i a
b i l i t y o
f t h e s e p r o
d u c
t s f o r s p e c
i f i c u s e r a p p
l i c a
t i o n s .
I t i s t h e
d u
t y o
f a n y s u c
h u s e r o r
i n t e g r a
t o r
t o p e r f o r m
t h e a p p r o p r i a
t e a n
d c o m p
l e t e
r i s
k a n a
l y s
i s ,
e v a
l u a
t i o n a n
d t e s
t i n g o
f t h e p r o
d u c
t s w
i t h
r e s p e c
t t o t h e r e
l e v a n
t s p e c
i f i c a p p
l i c a
t i o n o r u s e
t h e r e o
f .
N e
i t h e r
S c
h n e
i d e r
E l e c
t r i c I n
d u s
t r i e s
S A S n o r a n y o
f i t s a
f f i l i a t e s o r s u
b s
i d i a r i e s s
h a
l l b e r e s p o n s
i b l e o r
l i a
b l e f o r m
i s u s e o
f t h e
i n f o r m a
t i o n c o n
t a i n e
d h e r e
i n .
Mon Oct 11 10:08:04 EDT 2010
1
Product data sheetCharacteristics
24214miniature circuit breaker Multi 9 - C60N - 3
poles - 10 A - C curve
Certifications and standards
Standards EN 60898
IEC 60947-2
Compatibility
Comb busbar distribution block compatibility NO
Earth-leakage protection Separate block
Product compatibility C60 accessories
C60 auxiliary
Connections
Connections - terminals Tunnel type terminals 16 mm² flexible
Tunnel type terminals 25 mm² rigid
Electrical
[In] rated current 10 A 30 °C
[Ue] rated operational voltage 12...440 V AC 50/60 Hz
[Ui] rated insulation voltage 500 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV IEC 60947-2
Breaking capacity 10 kA Icu IEC 60947-2 400...415 V AC 50/60 Hz
30 kA Icu IEC 60947-2 125 V DC 3P
20 kA Icu IEC 60947-2 230...240 V AC 50/60 Hz
40 kA Icu IEC 60947-2 250 V DC 4P
6 kA Icn EN 60898 230/400 V AC 50/60 Hz
20 kA Icu IEC 60947-2 125 V DC 2P
6 kA Icu IEC 60947-2 440 V AC 50/60 Hz
Magnetic tripping limit 5...10 x In
Network frequency 50/60 Hz
Environment
Ambient air temperature for operation -25...60 °C
Ambient air temperature for storage -40...70 °C
Operating altitude 2000 m
Relative humidity 95 % 55 °C
Tropicalisation 2 IEC 60068-1
RoHS EUR conformity date 0651
RoHS EUR status Compliant
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 79 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
80/415
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
81/415
Page 11
trippingVisualisation of tripping by means of the redindicator on front face.
MX + OF shunt tripRemote tripping of a circuit-breaker:c equipped with an OF changeover switch:- to indicate the circuit-breaker’s position- to carry out self-breaking allowing thecontrol circuit to remain energized.Undervoltage releases(MN, MN sssss)Controls the tripping of a circuit-breaker when its supply voltage drops(threshold between 70 and 35 % of Un)It allows for manual closing of thecircuit-breaker if its voltage exceeds 85 % of the rated voltagedelayed MN sssss release0.2 second time-delay: prevents tripping dueto brownouts or momentary voltage
decreases.MNx release for opening pushbuttonCompletely unaffected by power supplycircuit cuts, it is recommended for fail-safeemergency stopping. Replaces the MX“voluntary“ release equipped with its NO/NCindicator lights.MSU overvoltageMSU voltage threshold releaseSpecially designed to monitor voltagebetween the neutral and phase(s)conductors, it cuts power supply by openingthe circuit-breaker in event of an overvoltage.For overvoltages lasting for more than a fewseconds.
technical dataComplance with standard: AS 3947-2
v release consumption type voltage power
(V AC or DC) (W or VA)
MX+OF 415 V AC inrush 120
220...240 V AC inrush 50
110...130 V AC inrush 200
DC inrush 10
48 V AC inrush 22
DC inrush 12
24 V AC inrush 120
DC inrush 120
12 V AC inrush 20
DC inrush 20
MN 220...240 V AC holding 4.1
48 V AC holding 4.3
DC holding 2.0
MNs 220...240 V AC holding 4.1MNx 230 AC inrush 50
400 AC inrush 120
MSU 230 AC inrush 50
400 AC inrush 120
remote indication
OF auxiliary switchv changeover switch that indicates the
“open” or “closed” position of thecircuit-breaker.v test button on the front face that allows for the indication circuit to be verified withoutoperating the circuit-breaker SD fault indicating switchv changeover switch that indicates the ”faulttrip” position of the circuit-breaker v visualisation of the fault (SD) by means of a mechanical indicator on front face.OF+SD/OF selector switchv double changeover switch that indicates:v the “open” or “closed” position of thecircuit-breaker (OF)v the “fault trip” position of the circuit-breaker (SD).v 2 circuits:
- upper: OF- lower: SD or OF.v function is selected using rotary selector switch on the right-hand sidev the selected function is indicated on thefront facev visualisation of the fault (SD) by means of a red mechanical indicator on front face.
technical dataComplies with standard: AS 3947-2
v rated current of auxiliary contacts voltage rated current
(V AC or DC) (A)
415 V AC 3
≤ 240 V AC 6
130 V DC 1
≤ 48 V DC 2≤ 24 V DC 6
connectionc using screw clamp terminals for 1 or 2cables (max. 2.5 mm2)c visible markers near terminals.
protection
electrical auxiliariesfor C60 and C120 circuit-breakers
AHSMRW00LAA-OM100.159/A
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 81 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
82/415
Page 12 Schneider Electric Help Centre: 1300 369 233
type control voltage catalogue width
(V AC) (V DC) number in mod.
of 9 mm
MX + OF shunt release
220...415 110...130 26946 2
48...130 48 26947 2
24 24 26948 2
12 12 26949 2
MSU overvoltage release
1P + N 220...240 26979 4
3P + N 380...415 26980 4
MN undervoltage release
instantaneous 220...240 26960 2
48 26961 2
48 26962 2
delayed s 220...240 26963 4
MNx release for opening pushbutton
Ph + N 220...240 26969 4
Ph to Ph 380...415 26971 4
references
26946
26963
26979
26969
C1C21214
U >
E2 NE1 L
U <
N L
U >>
D2D1
U <
E2 L1E1 L2
U <
L3L2N L1
U >>
protection
electrical auxiliariesfor C60 and C120 circuit-breakers
AHSMRW00LAA-OM100.160/A
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 82 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
83/415
Page 13
type control voltage catalogue width
(V AC) (V DC) number in mod.
of 9 mm
SD fault indicating switch
26927 1
OF auxiliary contact
26924 1
OF+SD/OF selector switch
26929 1
26927
26924
26929
14 12 11
2191
2294
2492
919294
111214
protection
electrical auxiliariesfor C60 and C120 circuit-breakers
AHSMRW00LAA-OM100.161/A
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 83 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
84/415
2
PresentationGB2 thermal-magnetic circuit-breakers protect and isolate the control circuits of
industrial equipment with contactor coils, transformers.…
They protect and isolate single-phase auxiliary circuits such as solenoid valves,
electro-brakes, battery chargers, supplied from the control circuit voltage.
GB2 CB, GB2 CD, GB2 DB12 ratings are available, from 0.5 to 20 A, in single-pole (GB2 CB), single-pole +
neutral (GB2 CD) and 2-pole (GB2 DB) versions.
They have a magnetic tripping threshold set at between 12 and 16 In to withstand the
current peaks generated by many industrial components.
GB2 CS2 ratings are available, 0.5 and 1 A, in single-pole version.
The magnetic tripping threshold is set between 5 and 7 In.
Functions, installationClip-on fixing onto all types of 35 mm 5 rails, on 4 rails and on Telequick
mounting plates.Upstream and downstream marking by means of AB1 clip-in markers.
Clear indication of “I” and “O” positions on the operator.
Tamper-proof device which requires no special maintenance (fixed magnetic and
thermal tripping thresholds).
Selection for the protection of circuits supplied by transformersSingle-phase transformers.
Magnetising peak: 20 In.
Operation of magnetic trips: 13 In.
Power Primary (1) Secondary
VA 220/240 V 380/415 V 24 V 48 V 110 V 220 V
40 GB2 DB05 GB2 DB05 GB2 CD07 GB2 CD06 GB2 CD05 GB2 CD05
63 GB2 DB05 GB2 DB05 GB2 CD08 GB2 CD07 GB2 CD06 GB2 CD05
100 GB2 DB06 GB2 DB05 GB2 CD10 GB2 CD07 GB2 CD06 GB2 CD05
160 GB2 DB07 GB2 DB06 GB2 CD14 GB2 CD09 GB2 CD07 GB2 CD06
250 GB2 DB07 GB2 DB06 GB2 CD16 GB2 CD12 GB2 CD08 GB2 CD07
400 GB2 DB08 GB2 DB07 GB2 CD22 GB2 CD14 GB2 CD09 GB2 CD07
630 GB2 DB10 GB2 DB08 – GB2 CD21 GB2 CD12 GB2 CD08
1000 GB2 DB14 GB2 DB09 – – GB2 CD16 GB2 CD10
1600 GB2 DB20 GB2 DB14 – – – GB2 CD14
2000 GB2 DB21 GB2 DB14 – – GB2 CD22 GB2 CD16
2500 GB2 DB22 GB2 DB20 – – – GB2 CD20
3000 GB2 DB22 GB2 DB20 – – – GB2 CD21
4000 – GB2 DB21 – – – GB2 CD22
5000 – GB2 DB22 – – – –
(1) If the breaking capacity of the GB2 is insuf ficient, use a GV2 RT with 2 poles connected inseries, see page 24508/7.
Characteristics :pages 21092/3 to 21092/5
References :pages 21093/2 and 21093/3
Dimensions :page 21093/3
Schemes :page 21093/3
Characteristics :pages 21092/3 to 21092/5
References :pages 21093/2 and 21093/3
Dimensions :page 21093/3
Schemes :page 21093/3
Characteristics :pages 21092/3 to 21092/5
References :pages 21093/2 and 21093/3
Dimensions :page 21093/3
Schemes :page 21093/3
Characteristics :pages 21092/3 to 21092/5
References :pages 21093/2 and 21093/3
Dimensions :page 21093/3
Schemes :page 21093/3
Protection componentsThermal-magnetic circuit-breakers TeSys GB2for the protection of industrial equipment controlcircuits
Presentation, selection
21092-EN_Ver5.0
1
2
3
4
5
6
7
8
9
10
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 84 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
85/415
3
Circuit-breaker type GB2 CB GB2 CD GB2 DB GB2 CS
EnvironmentConforming to standards IEC 60947-1, 947-2, EN 60947-1, 60947-2
Product certifications CSA, NEMKO, UL NEMKO, UL – –
Protective treatment “TC”
Degree of protection Conforming to IEC 60529 IP 20
Shock resistance Conforming to IEC 60068-2-27 22 gn for 20 ms
Vibration resistance Conforming to IEC 60068-2-6 5 gn (5…110 Hz)
Ambien t air temperaturearound the device
Storage °C - 40…+ 80
Operation °C - 20…+ 60
Flame resistance Conforming to IEC 60695-2-1 °C 960
Maximum operating altitude m 3000
Operating positi on In relation to normalvertical mounting plane
GB2 CB,CD, CS GB2 DB
Cabling Minimum c.s.a. Maximum c.s.a.
Solid cable mm 2 1 x 0.75 1 x 6 or 2 x 4
Flexible cable with cable end mm 2 1 x 0.75 1 x 4 or 2 x 2.5
Tightening torque N.m 1.2
Technical characteristicsUtilisation category Conforming to IEC 60947-2 A A A A
Rated operational voltage(Ue)
Conforming to IEC 60947-2 V 415 (1) 250 415 415 (1)
Conforming to CSA C22-2 Nr 14and UL 1077
V 277 – 277 –
Rated operational frequency Conforming to IEC 60947-2 Hz 50/60 50/60 50/60 50/60
Rated impulse wi thstandvoltage (U imp)
Conforming to IEC 60947-2 kV 4 4 4 4
Total power dissipated per pole W 2 2 2 1.9
Mechanical andelectrical durability
C.O.: Closing - Opening C.O. 8000 8000 8000 8000
Operational cu rrentcorrection coef ficient(a orc)
According to the permissibleambient temperature
°C - 20 - 10 0 + 10 + 20 + 30 + 40 + 50 + 60
Correction coef ficient 1.2 1.15 1.1 1.05 1 0.95 0.90 0.85 0.80
Tripping threshold Of the magnetic trips 12…16 In 12…16 In 12…16 In 5…7 In
(1) One GB2 circuit-breaker on each live conductor.
Tripping curves
Average operat ing t ime at 20 °C withou t pri or cu rren t flow (cold state)
GB2 CB, GB2 CD, GB2 DB GB2 CS
1,05
1,5
2 3 4 5 6 8
10
1
5
2
2010
100
50
1
5
2
2010
1
5
2
20
10
60
120
500
200
100 x In1,05
1,5
2 3 4 5 6 8
10
1
5
2
2010
100
50
1
5
2
2010
1
5
2
20
10
60
120
500
200
100 x In
M i l l i s e c o n d s
S e c o n d s
M i n u t e s
1,05
1,5
2 3 4 5 6 8
10
1
5
2
2010
100
50
1
5
2
2010
1
5
2
20
10
60
120
500
200
100 x In1,05
1,5
2 3 4 5 6 8
10
1
5
2
2010
100
50
1
5
2
2010
1
5
2
20
10
60
120
500
200
100 x In
M i l l i s e c o n d s
S e c o n d s
M i n u t e s
1,05
1,5
2 3 4 56 8
10
1
5
2
20
10
100
50
1
5
2
20
10
1
5
2
20
10
60
120
500
200
100 x In
M i l l i s e c o n d s
S e c o n d s
M i n u t e s
1,05
1,5
2 3 4 56 8
10
1
5
2
20
10
100
50
1
5
2
20
10
1
5
2
20
10
60
120
500
200
100 x In
M i l l i s e c o n d s
S e c o n d s
M i n u t e s
Presentation, selection :page 21092/2
References :pages 21093/2 and 21093/3
Dimensions :page 21093/3
Schemes :page 21093/3
Presentation, selection :page 21092/2
References :pages 21093/2 and 21093/3
Dimensions :page 21093/3
Schemes :page 21093/3
Presentation, selection :page 21092/2
References :pages 21093/2 and 21093/3
Dimensions :page 21093/3
Schemes :page 21093/3
Presentation, selection :page 21092/2
References :pages 21093/2 and 21093/3
Dimensions :page 21093/3
Schemes :page 21093/3
Protection componentsThermal-magnetic circuit-breakers TeSys GB2for the protection of industrial equipment controlcircuits
Characteristics
21092-EN_Ver5.0
1
2
3
4
5
6
7
8
9
10
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 85 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
86/415
4
Circuit-breaker type GB2
CB 05 CB06 CB 07 CB08 CB09 CB10 CB12 CB 14 CB16 CB20 CB 21 CB 22
Rating A 0.5 1 2 3 4 5 6 8 10 12 16 20
Breaking capacityconforming to IEC 60947-2a 50/60 Hz
110 V Icu kA 50 50 15 10 6 3 3 3 2 2 2 2
Ics % (1) 100 50 50 50 50 75 75 75 75 75 75 75
230/240 V Icu kA 50 50 15 3 3 2 1.5 1.5 1.5 1.5 1.5 1.5
Ics % (1) 25 25 25 50 50 75 75 75 75 75 75 75
400/415 V Icu kA 50 50 15 3 3 2 1.5 1.5 1.5 1.5 1.5 1.5
Ics % (1) 25 25 25 50 50 75 75 75 75 75 75 75
Assoc iated f uses , if requi redif Isc > breaking capacity Icuconforming to IEC 60947-2
110 V aM A g g 20 25 25 40 40 50 50 63 63 63
gG A g g 25 32 32 50 50 63 63 80 80 80
230/240 V aM A g g 16 20 20 32 32 40 40 50 50 50
gG A g g 25 32 32 40 40 50 50 63 63 63
400/415 V aM A g g 16 20 20 32 32 40 40 50 50 50
gG A g g 25 32 32 40 40 50 50 63 63 63
Circuit-breaker type GB2
CD05 CD06 CD07 CD08 CD09 CD10 CD12 CD14 CD16 CD20 CD21 CD22
Rating A 0.5 1 2 3 4 5 6 8 10 12 16 20
Breaking capacityconforming to IEC 60947-2a 50/60 Hz
110 V Icu kA 50 50 15 10 6 3 3 3 2 2 2 2
Ics % (1) 100 50 50 50 50 75 75 75 75 75 75 75
230/ 240 V Icu kA 50 50 15 3 3 2 1.5 1.5 1.5 1.5 1.5 1.5
Ics % (1) 25 25 25 50 50 75 75 75 75 75 75 75
Assoc iated fuses , if requi redif lsc > breaking capacity Icuconforming to IEC 60947-2
110 V aM A g g 20 25 25 40 40 50 50 63 63 63
gG A g g 25 32 32 50 50 63 63 80 80 80
230/240 V aM A g g 16 20 20 32 32 40 40 50 50 50
gG A g g 25 32 32 40 40 50 50 63 63 63
Circuit-breaker type GB2
DB05 DB06 DB 07 DB08 DB 09 DB10 DB12 DB14 DB16 DB20 DB21 DB 22
Rating A 0.5 1 2 3 4 5 6 8 10 12 16 20
Breaking capacityconforming to IEC 60947-2a 50/60 Hz
110 V lcu kA 50 50 15 10 6 3 3 3 2 2 2 2
Ics % (1) 100 50 50 50 50 75 75 75 75 75 75 75
230/240 V lcu kA 50 50 15 3 3 2 1.5 1.5 1.5 1.5 1.5 1.5
Ics % (1) 25 25 25 50 50 75 75 75 75 75 75 75
400/415 V lcu kA 50 50 15 3 3 2 1.5 1.5 1.5 1.5 1.5 75
Ics % (1) 25 25 25 50 50 75 75 75 75 75 1.5 75
Assoc iated fuses , if requi redif lsc > breaking capacity Icuconforming to IEC 60947-2
110 V aM A g g 20 25 25 40 40 50 50 63 63 63
gG A g g 25 32 32 50 50 63 63 80 80 80
230/240 V aM A g g 16 20 20 32 32 40 40 50 50 50
gG A g g 25 32 32 40 40 50 50 63 63 63
400/415 V aM A g g 16 20 20 32 32 40 40 50 50 50
gG A g g 25 32 32 40 40 50 50 63 63 63
(1) As % of Icu.g Fuse not required. Breaking capacity Icu > lsc.
Presentation, selection :page 21092/2
References :page 21093/2
Dimensions :page 21093/3
Schemes :page 21093/3
Presentation, selection :page 21092/2
References :page 21093/2
Dimensions :page 21093/3
Schemes :page 21093/3
Presentation, selection :page 21092/2
References :page 21093/2
Dimensions :page 21093/3
Schemes :page 21093/3
Presentation, selection :page 21092/2
References :page 21093/2
Dimensions :page 21093/3
Schemes :page 21093/3
Protection componentsThermal-magnetic circuit-breakers TeSys GB2for the protection of industrial equipment controlcircuits
Characteristics (continued)
21092-EN_Ver5.0
1
2
3
4
5
6
7
8
9
10
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 86 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
87/415
5
Circuit-breaker type GB2
pp05 pp06 pp07 pp08 pp09 pp10 pp12 pp14 pp16 pp20 pp21 pp22
Breaking capacity (lcu)
conforming to IEC 60947-2c
24 V kA 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
48 V kA 1 1 1 1 1 1 1 1 – – – –
Operational currentconforming to IEC 60947-5-1c
DC-12 24 V A 0.5 1 2 3 4 5 6 8 10 12 16 20
48 V A 0.5 1 2 3 4 5 6 8 10 12 16 20
DC-13 24 V A 0.5 1 2 3 4 5 6 8 10 12 16 20
48 V A 0.5 1 2 3 4 5 6 8 – – – –
Circuit-breaker type GB2
CS05 CS06
Rating A 0.5 1
Breaking capacityconforming to IEC 60947-2a 50/60 Hz
110 V lcu kA 50 50
lcs % (1) 100 100
230/240 V lcu kA 50 50
lcs % (1) 25 25
400/415 V(2)
lcu kA 50 50
lcs % (1) 25 25
Breaking capacity (lcu) conforming to IEC 60947-2c
24 V kA 1.5 1.5
48 V kA 1 1
Operational currentconforming to IEC 60947-5-1c
DC-12 24 V A 0.5 1
48 V A 0.5 1
DC-13 24 V A 0.5 1
48 V A 0.5 1
Maximumpermissible
line length forstar-delta starting(length of cablecontaining 2 ormore conductors)
With contactorsLCp D09 …D18
Operational voltage V 48 110 230 48 110 230
C.s.a. 060 mm2 m (3) 31 365 6 85 230
0.75 mm2 m (3) 39 460 8 110 290
1 mm2 m (3) 52 610 10 145 380
1.5 mm2 m (3) 78 910 15 220 570
2.5 mm2 m (3) 130 1520 26 360 950
4 mm2 m (3) 200 2400 41 580 1500
With contactorsLCp D25…D32
Operational voltage V 48 110 230 48 110 230
C.s.a. 0.60 mm2 m (3) (3) 230 (3) 56 230
0.75 mm2 m (3) (3) 290 (3) 70 290
1 mm2 m (3) (3) 390 (3) 95 380
1.5 mm2 m (3) (3) 580 (3) 140 570
2.5 mm2 m (3) (3) 970 (3) 230 950
4 mm2 m (3) (3) 1500 (3) 375 1500
With contactorsLCp D40…D80
Operational voltage V 48 110 230 48 110 230
C.s.a. 0.60 mm2 m (3) (3) 46 (3) 13 100
0.75 mm2 m (3) (3) 60 (3) 17 130
1 mm2 m (3) (3) 80 (3) 22 170
1.5 mm2 m (3) (3) 120 (3) 34 250
2.5 mm2 m (3) (3) 190 (3) 56 420
4 mm2 m (3) (3) 310 (3) 90 680
(1) As % of Icu.(2) One GB2 CS circuit-breaker on each live conductor.(3) Use relays.
Presentation, selection :page 21092/2
References :pages 21093/2 and 21093/3
Dimensions :page 21093/3
Schemes :page 21093/3
Presentation, selection :page 21092/2
References :pages 21093/2 and 21093/3
Dimensions :page 21093/3
Schemes :page 21093/3
Presentation, selection :page 21092/2
References :pages 21093/2 and 21093/3
Dimensions :page 21093/3
Schemes :page 21093/3
Presentation, selection :page 21092/2
References :pages 21093/2 and 21093/3
Dimensions :page 21093/3
Schemes :page 21093/3
Protection componentsThermal-magnetic circuit-breakers TeSys GB2for the protection of industrial equipment controlcircuits
Characteristics (continued)
21092-EN_Ver5.0
1
2
3
4
5
6
7
8
9
10
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 87 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
88/415
CONTROL & SIGNALLING UNITS
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 88 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
89/415
Control and signalling unitsThe essential guide
AHSMRW00LAA-OM100.223/A
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 89 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
90/415
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
91/415
2/1Schneider Electric
2
2121 0 21 021
21
IN 230 V
6 V
IN
21
230 V6 V
IN
1 3
1 4
2 4
2 3
IN250 V max
BA 0 BA 0BA
D
C
0 BA
D
C
0 BA
D
C
0
Pushbuttons and Emergency stop pushbuttons
Selector switches
Selector switch - 2 position,spring return from right to left,key withdrawal LH positionN/O contact
Pilot lights
Illuminated pushbuttons and selector switches
Pushbutton Pushbutton Mushroom head, Emergency stop latchingN/O contact N/C contact spring return mushroom head. Push-pull
N/O contact N/C contact
Emergency stop trigger Emergency stop trigger Emergency stop trigger Emergency stop triggeraction mushroom head action mushroom head action mushroom head action mushroom headPush-pullN/O + N/C contact
Turn to release - N/C contact Key release - N/C contact Turn to releaseN/O + N/C contact
Emergency stop triggeraction mushroom headKey release Double-headed pushbuttonN/O + N/C contact N/O + N/C contact
Selector switch - 2 position, Selector switch - 3 position, Selector switch - 3 position, Selector switch - 2 position,stay put stay put 2 spring return to centre stay put, key withdrawal LHN/O contact N/O + N/O contact N/O + N/O contact position - N/O contact
Pilot light with BA 9s Pilot light with integral transformer, 230 V aa a a primary,incandescent bulb LED pilot light 6 V secondary. BA 9s incandescent bulb or LED
Illuminated pushbutton Illuminated pushbutton Illuminated pushbutton Double-headed pushbuttonBA 9s incandescent bulb with LED with integral transformer, with LED pilot lightN/O + N/C contact N/O + N/C contact 230 V aa a a 50/60 Hz primary, N/O + N/C contact
6 V secondary.BA 9s incandescent bulb or LEDN/O + N/C contact
Illuminated selector switchwith LED - 2 position stay putN/O + N/C contact
Joystick controllers 4 direction
2 direction
Without With Without With springspring return spring return spring return return
Control and signalling units Ø 22Harmony ® style 5Pushbuttons, switches and pilot lights, with doubleinsulated bezel
General
Schematic library
Characteristics:pages 2/6 to 2/9
References:pages 2/10 to 2/47
Dimensions:pages 2/48 to 2/55
LED LED
LED
LED
LEDLED
AHSMRW00LAA-OM100.225/A
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 91 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
92/415
2/2 Schneider Electric
2
Non illuminated unitsfor user assembly
Contact functions
Body Headsub-assemblies sub-assemblies
Pushbuttons, spring return,without marking
Screw clamp terminalsZB5-AZ10pppp /AZ141see page 2/10 Flush push Flush push for Flush push
insertion of legend
ZB5-AA0/AA9 ZB5-AApppp ZB5-AApppp8 ZB5-CApppp
see page 2/11 see page 2/11 see page 2/11 see page 2/11
Plug-in connectorZB5-AZ10p4/AZ1414see page 2/10 Projecting push Recessed push Booted flush push Projecting push
ZB5-ALpppp ZB5-AApppp4 ZB5-APpppp / APpppp8 ZB5-CLppppsee page 2/11 see page 2/11 see page 2/11 see page 2/11
Pushbuttons, spring return,with marking
Flush push Projecting push Flush pushZB5-AApppp3pppp/AApppp4pppp ZB5-AL ZB5-CApppp3/CApppp9see page 2/12 see page 2/12 see page 2/12
“Push-turn” pushbuttons (1) Knob positions
Lockable Knurled knob (1)ZB5-AFD ZB5-AFsee page 2/12 see page 2/12
Double-headed pushbuttons,
spring return
Flush pushes (IP 40/IP 66) Flush push + Projecting push (IP 40/IP 66)Without/with markings Without/with markingsZB5-AA81/AA82 ZB5-AA91/AA92 ZB5-AL83/AL84 ZB5-AL93/AL94see page 2/13 see page 2/13 see page 2/13 see page 2/13
“Push-push to release”pushbuttons
Flush push Projecting push Flush pushZB5-AH0/CH0 ZB5-AHp ZB5-CH0psee page 2/13 see page 2/13 see page 2/13
Control and signalling units Ø 22Harmony ® style 5Pushbuttons, switches and pilot lights, with double insulated bezelSub-assemblies, ZB5-A
General (continued)
Characteristics:pages 2/6 to 2/9
References:pages 2/10 to 2/47
Dimensions:pages 2/48 to 2/55
AHSMRW00LAA-OM100.226/A
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 92 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
93/415
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
94/415
2/4 Schneider Electric
2
Pilot lightsfor user assembly
Signalling functions
Body sub-assemblies Head sub-assembliesIntegral LED
With lens mountedZB5-AV0p3 ZB5-CV0p3see page 2/21 see page 2/21
Screw clamp terminalsZB5-AVB/AVG/AVMsee page 2/20
With 5 separate lensesZB5-AV003 ZB5-CV003see page 2/21 see page 2/21
Plug-in connectorZB5-AVBp4/AVGp4/AVMp4see page 2/20
Body sub-assemblies Head sub-assembliesfor BA 9s bulb
With lens mountedZB5-AV0psee page 2/21
Direct supplyScrew clamp terminalsZB5-AV6see page 2/21
Via integral transformerScrew clamp terminalsZB5-AVp /AV3Dp(1) /AV5Dp(1)see page 2/21
Control and signalling units Ø 22Harmony ® style 5Pushbuttons, switches and pilot lights, with double insulated bezelSub-assemblies, ZB5-A
General (continued)
Characteristics:pages 2/6 to 2/9
References:pages 2/10 to 2/47
Dimensions:pages 2/48 to 2/55
AHSMRW00LAA-OM100.228/A
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 94 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
95/415
2/5Schneider Electric
2
Control and signalling units Ø 22Harmony ® style 5Pushbuttons, switches and pilot lights, with double insulated bezelSub-assemblies, ZB5-A
General
Characteristics:pages 2/6 to 2/9
References:pages 2/10 to 2/47
Dimensions:pages 2/48 to 2/55
Illuminatedpushbuttonsand selector switches
for user assembly
Combined contact and signalling functions
Body sub-assemblies Head sub-assembliesIntegral LED
Illuminated pushbuttons,spring return
Flush push with cap Flush push for Booted Flush pushmounted or not insertion of legend
ZB5-AW3pppp3/AW9pppp3 ZB5-AApppp8 ZB5-AW5pppp3see page 2/29 see page 2/29 see page 2/29
Screw clamp terminalsZB5-AW0B/AW0G/ AW0Msee page 2/24
Projecting push Flush or projecting push
ZB5-AW1pppp3/ALpppp8 ZB5-CW3pppp3/CW1pppp3see page 2/29 see page 2/29
Double headed pushbuttons,spring return, with pilot light
Plug-in connectorZB5-AW0Bpppppppp4/ AW0Gpppppppp4/AW0Mpppppppp4 Flush pushes Flush push + projecting pushsee page 2/26 Without/with markings Without/with markings
ZB5-AW81pppppppppppp3, ZB5-AW82pppppppppppp3 ZB5-AW83pppppppppppp3, ZB5-AW84pppppppppppp3see page 2/30 see page 2/30 see page 2/30 see page 2/30
Illuminated “push-push torelease” pushbuttons andilluminated selector switcheswith standard handle
Flush or projecting Selector switches with“push-push to release” standard handleZB5-AH0i3/AHpppp3 ZB5-AK1ppppi3see page 2/30 see page 2/31
Body sub-assemblies Head sub-assembliesFor BA 9s bulb
Illuminated pushbuttons,spring return
Flush pushZB5-AW3pppp
Direct supply see page 2/29Screw clamp terminalsZB5-AW06ppppsee page 2/28
Projecting pushZB5-AW1ppppsee page 2/29
Via integral transformerScrew clamp terminalsZB5-AW03/4/5/3D/5Dsee page 2/28
AHSMRW00LAA-OM100.229/A
AHS-MRW00SEO.OM.109.06
REVISION: A Rev. Date: 18.04.2011
page: 95 of 416
8/18/2019 109.06_seo_ups, Contol Cubile, Controller, Technical Leaflets
96/415
2/6 Schneider Electric
2
Control and signalling units Ø 22Harmony ® style 5Pushbuttons, switches and pilot lights, with doubleinsulated bezel
Environment
Protective treatment “TH”standard version
Ambient air temperature Storage ˚C - 40…+ 70around the device
Operation ˚C - 25…+ 70 unless otherwise stated
Electric shock protection Conforming to IEC 536 Class II
Degree of protection Conforming to IEC 529 IP 65, unless otherwise statedIP 66, for booted pushbutton heads
Conforming to NEMA NEMA type 4X and 13, unless otherwise stated
High pressure cleaning resistance Pa 70 x 105 (70 bar); distance: 0.1 m
Temperature: 55˚C
Mechanical shock protection Conforming to EN 50102 Non illuminated heads: IK 03
Illuminated heads: IK 05
Conforming to standards IEC/EN 60947-1, IEC/EN 60947-5-1, IEC/EN 60947-5-4,JIS C 4520,UL 508, CSA C22-2 n˚ 14
Product certifications UL Listed, CSA Standard single contacts with screw clamp terminals: A600; Q600Double contacts with screw clamp terminals: A600; Q600Light blocks with screw clamp terminalsJoystick controllers XD5-PA/ZD5-PA: A600; R300
UL Recognized, CSA Standard single contacts for plug-in connector: A300; R300Standard single contacts for printed circuit board: B300; R300
BV, RINA, LROS, DNV, GL (pending) Standard single contacts and double contacts with screw clampterminals
Terminal identification Conforming to EN 50005 & EN 50013
Characteristics of contact blocks
Mechanical characteristics
Contact operation N/C or N/O Slow break
Positive operation Conforming to IEC/EN 60947-5-1 All functions incorporating a N/C contact are positive openingAppendix K operation
Operating travel Pushbutton mm Changing N/C state: 1.5(to change electrical state) mm Changing N/O state: 2.6
mm Total travel: 4.3
Operating force Pushbutton N Changing N/C state: 3.5N Changing N/O state: 3.8
Additional contact N Single N/C contact: 2(extra to change state) N Single N/O contact: 2.3
N Double contact N/C: 3.4N Double contact N/O: 5N Double contact N/C + N/O: 4.6
Emergency stop with N/C + N/O N Standard push-pull: 45
N Trigger action push-pull: 50
N Standard turn to release and key release: 40N Trigger action turn to release and key release: 44
Characteristics�