Upload
wado11
View
5
Download
1
Embed Size (px)
DESCRIPTION
cable cal
Citation preview
CABLE SIZE CALCULATIONDOCUMENT NO. E-CAL-001
COMPANY NAME TITLE CABLE SIZE CALCULATION
PROJECT No: Your Project Number
REV A PROJECT: Your Project
BY CLIENT: Your Client
CHKD ENGINEERED BY: Your Name here
APPRV'D
DATE PAGE 1 OF 1 REV A
Cable Number Load
Load Data
Motor Rating 370 kW No. of Parallel Conductor 4
Rated voltage 400 V No. of Adjacent Circuits <5
FL power factor 0.8 Full load current 667.6 A
Power Frequency 50 Current / Conductor (Io) 166.9 A
Allowable Voltage Drop 2 % Allowable Voltage Drop (Starting) 15 %
Cable Data
Conductor size 50 Tmax operating 90
Number of Cores 3 Ambient Air Temperature 40
Total Cable length (L) 50 m Temp. Cable Derating (DF) 1.05
Conductor rating 196 A Grouping Factor (GF) 1
Operating Temperature:
Conductor derating = = 205.8 A
Operating temperature =
= 72.88 deg Celcius
Operating temperature is Acceptable!
Voltage Drop (Normal Operating):
= 0.3910 Ohm/km = 0.000391 Ohm/m
= 0.4217 Ohm/km = 0.000422 Ohm/m
Conductor reactance = 0.1040 Ohm/km = 0.0001 Ohm/m
MCC busbar Voltage = 400 V
Cable volt drop = = 5.778 V 1.44 %
Voltage at the load = 400 - 5.8 = 394.2 V
Min. load volts (Vmin) = 392 V @ 2% Voltage Drop
Voltage Drop is Acceptable!
Starting Current = 6 X 166.9 = 1,001.3 A
Cable volt dip = = 34.67 V 8.67 %
Voltage at the load = 400 - 34.7 = 365.3 V
Min. load volts (Vmin) = 340 V @ 15% Voltage Dip (Motor Starting)
Voltage Dip is Acceptable!
I"k = 18 kA (From Short Circuit Calculations result)
t = 0.5 s
K = 143 (143 for Copper conductors PVC Insulated)
S = = 89.01 (Minimum cable size to withstand short circuit)
Short Circuit Withstand OK
Notes:
The methods used in this calculation are based on the recommendations of IEC 60228, IEC 60364-5-54Copyright 2008 - Ver Pangonilo - http://www.filipinoengineer.org - its free to use and modify but leave this copyright note.
COMPANYLOGO
(cosq)
mm2 Copper (ÆR) oC
(ÆA) oC
(IR1)
(IR2) IR1 x DF x GF
(ÆO) [Io/IR2]2 x [(ÆR - ÆA)+ÆA]
Conductor resistance, 20OC (R20C)
Conductor resistance, 40OC (R40C)
(XC)
(VL)
Vd3Æ Io L [Ö3 (RC cosq + XC sinq)]
Vd3Æ Io L [Ö3 (RC cosq + XC sinq)]
Short Circuit Withstand (3Æ Fault):
(Fault clearing time £ 5s)
Ö[(I"k x 1000)2t]/K mm2
Note: These data are based on a cable manufacturer's datasheet. Refer to your cable manufacturer for more information.
Cable Data (PVC Insulated Cables Only)
Item
1 16 2.5 1.16 1.48 0.116 0.14 96 2240
2 25 4 0.734 0.936 0.11 0.132 127 3500
3 35 6 0.529 0.675 0.106 0.128 157 4900
4 50 6 0.391 0.499 0.104 0.125 196 7000
5 70 6 0.27 0.344 0.099 0.119 242 9800
6 95 10 0.195 0.249 0.097 0.116 293 13300
7 120 10 0.154 0.196 0.094 0.113 339 16800
8 150 10 0.126 0.161 0.092 0.111 389 21000
9 185 10 0.1 0.128 0.091 0.109 444 25900
10 240 16 0.0762 0.0972 0.089 0.107 522 33600
11 300 16 0.0607 0.0774 0.087 0.105 601 42000
Temperature Correction Factor Frequency Parallell Conductors50 1
Item Temp, Deg C Factor 60 2
1 35 1.1 3
2 40 1.05 4
3 45 1 5
4 50 0.94
5 55 0.88
6 60 0.82
7 65 0.74
8 70 0.67
9 75 0.58
10 80 0.47
Below this line are References OnlyIEC 60364-5-54Table 54B Values for K for insulated protective conductors not incorporated in cables
PVC XLPE EPR Butyl Rubber
Final Temperature, degC 160 250 250 220 1
1 Copper 143 176 176 166 2
2 Aluminium 95 116 116 110 3
3 Steel 52 64 64 60 4
Cross section core, mm²
Cross section
screen, mm²
Max. conductor
resistance at 20°C,
Ohm/km
Max. conductor
resistance at 90°C,
Ohm/km
Reactance at 50Hz, Ohm/km
Reactance at 60Hz, Ohm/km
Current rating IEC,
Ampere
Short circuit rating
1second, Ampere
Note: These data are based on a cable manufacturer's datasheet. Refer to your cable manufacturer for more information.
Below this line are References Only
Final Temp
PVC 160
XLPE 250
EPR 250
Butyl Rubber 220
Notes to Cable Calculations1. Cable data provided in here are based on a manufacturer's datasheet. Refer to your cable manufacturer for project specific values.2. Cable calculation is based on IEC standards.3. Load data is based on motor load and 3 phase4. This calculation is just a sample. It is always a good practice to verify the results.5. I"k should be based on the short circuit calculation result. It is not part of this worksheet.6. Please read the Disclaimer Statement before using this calculation worksheet.
1. Cable data provided in here are based on a manufacturer's datasheet. Refer to your cable manufacturer for project specific values.