Upload
trinhliem
View
266
Download
19
Embed Size (px)
Citation preview
10- Step Design ofPost-Tensioned Floors
Dr Bijan O AalamiProfessor Emeritus,
San Francisco State UniversityPrincipal, ADAPT Corporation; [email protected]
www.adaptsoft.comwww.adaptsoft.comPTPT--Structures copyright 2015Structures copyright 2015
301 Mission StreetSan Francisco, California
High Seismic Force Region
Four Seasons Hotel; Florida
High Wind Force Region Residential/Office Post-Tensioned Building in Dubai
Column supported multistory building
Two-way flat slab construction
Multi-level parking structures
One-way beam and slab design
Example of a Floor System using the Unbonded Post-tensioning System
An example of a grouted
system hardware with flat duct
Post-Tensioning SystemsGrouted System
Example of a Floor System Reinforcedwith Grouted Post-Tensioning System
Preliminary ConsiderationsDesign of Post-Tensioned Floors
Dimensions (sizing)Optimum spans; optimum thickness
Structural system One-way/two-way; slab band
Boundary conditions; connections Service performance; strength condition
Design strips
Design sections; design values
Preliminary ConsiderationsDesign of Post-Tensioned Floors
Dimensions (sizing)Optimum spans; optimum thickness
An optimum design is one in which thereinforcement determined for “servicecondition” is used in its entirety for “strength condition.”
PT amount in service condition is governed mostly by:
Hypothetical tensile stressesTendon spacing
Spans: between 7 m – 9 m ft
Span/thickness ratios 40 for interior35 for exterior with no overhang
One-way and two-way systemsSkeletal Systems share loadSlab systems may not share load, depending on reinforcement layout
Preliminary ConsiderationsDesign of Post-Tensioned Floors
F
F
(a) ONE-WAY BEAM SYSTEM
(b) TWO-WAY BEAM SYSTEM
C
A D
B
B
F
Skeletal System
One-way and two-way systemsSkeletal Systems share loadSlab systems may not share loaddepending on reinforcement layout
Preliminary ConsiderationsDesign of Post-Tensioned Floors
PL/4
(1-a)P
BEAM
(b) BEAMS ON FOUR COLUMNS
L
(iii)
(ii)
A,C
aP
PB,D
B C
(i)A
L
C
A LOAD
P
B
D
(PL/4)
2
D
COLUMN
Capacity required for 100% of load in each direction, if reinforcement is placed along AD,
and AC
Structural system One-way/two-way; slab band
Preliminary ConsiderationsDesign of Post-Tensioned Floors
h < 2t b > 3h
b
h
SLAB BAND
Slab band is treated as part ofa two-way system. One-way sheardesign provisions meant for beams
do not apply to slab bands
Selection of load path for two-waysystems – Design Strips
Preliminary ConsiderationsDesign of Post-Tensioned Floors
Subdivide the structure into design strips in two orthogonal directions
(Nahid slab)
XY
G
F
E
D
C
B
A
31 2 4 5
Subdivide the floor along supportlines in design strips
Preliminary ConsiderationsDesign of Post-Tensioned Floors
XY
1 2 3 4 5
F
E
D
C
B
A
Subdivide slab along support lines in design strips in the orthogonal direction
An important aspect of load path selection in a two-way system is that every point of the slab should be assigned to a specific design strip. No portion of the slab should be left unassigned.
Preliminary ConsiderationsDesign of Post-Tensioned Floors
Design sectionsDesign sections extend over the entire
design strip and are considered at critical locations, such as face of support andmid-span
Preliminary ConsiderationsDesign of Post-Tensioned Floors
Design valuesActions, such as moments at each design
section are reduced to a “single”representative value to be used for design
559 k-ft is the area (total) of bendingmoment at face of support
10- StepsDesign of Post Tensioned Floors
1. Geometry and Structural System2. Material Properties3. Loads4. Design Parameters5. Actions due to Dead and Live Loads6. Post-Tensioning7. Code Check for Serviceability8. Code Check for Strength9. Check for Transfer of Prestressing10. Detailing
Select design strip and IdealizeExtract; straighten the support line;square the boundary
Step 1 Geometry and Structural System
Select design strip and IdealizeExtract; straighten the support line;square the boundaryModel the slab frame with a row of
supports above and below. This represents an upper level of multi-story concrete frame.
Assume rotational fixity at the far ends;Assume roller support at the far
ends
Step 1 Geometry and Structural System
View of idealized slab-frame
Step 2Material Properties
ConcreteWeight 24 kN/m328 day cylinder 40 MPaElastic modulus 29,725 MPaLong-term deflection factor 2
Non-Prestressed reinforcementfy 460 MPaElastic modulus 200,000 MPa
PrestressingStrand diameter 13 mmStrand area 99 mm2Ultimate strength 1,860 MPaEffective stress 1,200 MPaElastic modulus 200,000 MPa
Step 3Dead and Live Loads
SelfweightBased on member volume
Superimposed dead loadMin (partitions) 2.00 kN/m2
Live loadResidential 3.00 kN/m2
Step 4Design Parameters
Applicable codeACI 318-14IBC 2012 ?Local codes, such as California Building
Code (CBC 2011) ?
Cover for protection against corrosion
Cover to rebarNot exposed to weather 20 mmExposed to weather 50 mm
Cover to tendonNot exposed to weather 20 mmExposed to weather 25 mm
Step 4Design Parameters
Cover for fire resistivity
Identify “restrained” and “unrestrainedpanels.”
Restrained orUnrestrained
Aggregate Type Cover Thickness, mmfor Fire Endurance
1 hr 1.5 hr 2 hr 3 hr 4 hr
Unrestrained CarbonateSiliceous
Lightweight
---
---
383838
515151
-
Restrained CarbonateSiliceous
Lightweight
---
---
191919
252525
323232
--
For 2-hour fire resistivityRestrained 20 mmUnrestrained 38 mm
Step 4Design Parameters
Cover for fire resistivityIdentify “restrained” and “unrestrainedpanels.”
Step 4Design Parameters
Select post-tensioning system For corrosive environment use “encapsulated system.”
For non-corrosive environment, regular hardware may be used
Step 4Design Parameters
Allowable stresses for two-waysystems
Service conditionTotal (frequent) load case
Tension ---------------------------
Compression --------------------
Sustained (quasi permanent) load case
Tension --------------------------
Compression ------------------
Initial conditionTension ------------------------
Compression ---------------
'0.5 cf
'0.5 cf
'0.25 cf
'0.6 cf
'0.45 cf
'0.6 cf
Step 4Design Parameters
Allowable deflections (ACI 318 .5)
For visual impact use total deflectionSpan/240Use camber, if necessary
Total deflection subsequent to installation of members that are likely to be damaged
Span/360
Immediate deflection due to live loadSpan/480
Long-term deflection magnifier 2. This brings the total long-term deflection to 3,
Step 5Actions due to Dead and Live Loads
Analyze the design strip as a singlelevel frame structure with one row ofsupports above and below, usingIn-house simple frame program(Simple Frame Method; SFM); orin-house Equivalent Frame Program (EFM); Specialty commercial software
All the three options yield safe designs.But, each will give a different amount of reinforcement. The EFM is suggested by ACI-318. To some extent, it accounts for biaxial action of the prototype structure in the frame model.3D FEM software can improve optimization
Step 5Actions due to Dead and Live Loads
Analyze the design strip as a single levelframe structure with one row of supports above and below.
Moments due to DL (k-ft)
Moments due to LL (k-ft)
Step 6 Post-Tensioning
Selection of design parameters
Selection of PT force and profile
Effective force vs tendon selection optionForce selection option
Calculation of balanced loads;adjustments for percentage of loadbalanced
Calculation of actions due to balanced loads
Step 6 Post-Tensioning
Selection of PT force and profileTwo entry value selections must be made to initiate the computations. Select precompression and % of DL to balance
Step 6Post-Tensioning
Selection of design parametersSelect average precompression 1 MPaTarget to balance 60% of DL
Selection of PT force and profileAssume simple parabola mapped within
the bounds of top and bottom covers
Force diagram of simple parabola
Step 6Post-Tensioning
Assume simple parabola forhand calculation
Calculation of balanced loads;adjustment of % of DL balanced
STEP 6Post-Tensioning
Select critical span
Select max drape
Calculate %of DL balanced (%DL)
%DL < 50%?
Reduce P/AReduce drape
Yes
Increase P/A
NoYes
No
No Yes
Yes No
Assume P/A =150psi[1MPa]
P /A<300ps i [2MP a]? %DL > 80%?
P/A>125psi [0.8MPa]?
Go to next span
1
2
F121_ACI_PT_2_way_082012
Member with widely different spans
Calculation of balanced loads;adjustment for % of DL balanced
STEP 6Post-Tensioning
Select max drape using tendons from critical span
Calculate %of DL balanced (%DL)
Move to next span
Reduce P/A or tendons to%DL balanced ~ 60% ;
P/A >= 125 psi [0.8 MPa]
YesNo
No Yes
Is it practical to reduce P/A or tendons?
%DL > 80%?
Rais e tendon to reach%DL ~ 60%
Exit after last span
F121_ACI_2-way_PT_force_082012
Calculation of balanced loadsLateral forced from continuous tendonsLateral force from terminated tendonsMoments from change in centroid of
member
Example of force from continuous tendon
STEP 6Post-Tensioning
P = 500 ka = 93 mm; b = 186 mm ; L = 9.0 m ; c = {[93/186]0.5/[1 + (93/186)0.5]} * 9.00
= 3.73 m wb = 2 P*a/c2 = (2*193*93/1000)/3.732
= 1.59 kN/m per tendon
Calculation of balanced loadsLateral forced from continuous tendonsLateral force from terminated tendonsMoments from change in centroid of member
Example of force from terminated tendon
STEP 6Post-Tensioning
L = 10 m ; a = 93 mm; P = 119 kN/tendon c = 0.20*10 = 2.00 m Wb = (2*119*93/1000) / 22 = 5.53 kN/tendon ↓Concentrated force at dead end= 2*119*93/2000
= 11.06 k/tendon ↑
Calculation of balanced loadsLateral forced from continuous tendonsLateral force from terminated tendonsMoments from change in centroid of member
Example of force from shift in membercentroidal axis
STEP 6Post-Tensioning
Moment at face of drop = MM = P * shift in centroid = P * (Yt-Left – Yt-Right)P = 119 k; Yt-Left = 120 mm; Yt-Right = 146 mmM = 119 (120 – 146)/1000 = - 3.09 kNm
Calculation of actions due to balanced loadsCheck balanced loads for static equilibriumDetermine moments/shears from balanced loads
applied to the frame model that was used for deadand live loads
Note down reactions from balanced loads
Example of Balanced Load Assembly
STEP 6Post-Tensioning
Calculation of actions due to balanced loadsObtain moments at face-of-supports and mid-spansNote the reactions. The reactions are hyperstatic forces..
Comments:Moments will be used for serviceability check. Reactions will be used for
Strength check.
STEP 6Post-Tensioning
ACI 318-14 requirements for serviceabilityLoad combinationsStress checkMinimum reinforcementDeflection check.
Load combinationTotal load condition1.00DL + 1.00LL + 1.00PT
Sustained load condition1.00DL + 0.30LL + 1.00PT
Stress check
STEP 7Code Check for Serviceability
Using engineering judgment, select the locations thatare likely to be critical. Typically, these are at the faceof support and for hand calculation at mid-spanAt each section selected for check, use the design actionsapplicable to the entire design section and apply those to the entire cross-section of the design section to arrive at the hypothetical stresses used in code check.
σ = (MD + ML + MPT)/S + P/AS = I/Yc ; I = second moment of area;Yc = distance to farthest tension fiber
ACI 318-14 Minimum Reinforcement
STEP 6Post-Tensioning
Yes
6
8
ACI Minimum Rebarfor two-way systems
F114_041112
BondedUnbonded
At supportsAs = 0.0075Acf
Add rebar to resistforce in tensile zone
No added rebarrequired
EXIT
Add rebar to increaseMoment capacity to
1.2 Mcr
7
5
4
3
2
1
11
10
9
PT system?
`
`
No
ft ?tension stress
In span calculatehypothetical tension
stress ft
ft > 2 root 'c[ft > 0.17 root f'c ]
ft =< 2 root 'c[ ft =< 0.17 root f'c ]
Does Mcr exceeed1.2xmoment capacity?
No added rebarrequired
Calculate the cracking moment Mcr at
supports and spans
12
ACI 318-14 Minimum ReinforcementRebar over support is function of geometry of the
design strip and the strip in the orthogonal directionRebar in span is a function of the magnitude of
the hypothetical tensile stress
STEP 6Post-Tensioning
As = 0.00075*Acf
As = Area of steel requiredAcf = Larger of cross-sectional area of the strip in direction of analysis and orthogonal to it.
ACI 318-14 Minimum ReinforcementRebar over support is function of geometry of the
design strip and the strip in the orthogonal directionRebar in span is a function of the magnitude of
the hypothetical tensile stress
In span, provide rebar if the hypothetical tensile stress exceeds 0.16√f’c
The amount of reinforcement As is given by:As = N / (0.5fy)
where N is the tensile force in tension zone
STEP 6Post-Tensioning
h = member thickness; b = design section width
Read deflections from the frame analysis of the design strip for dead, live and PT; (ΔDL , ΔLL , and ΔPT ).
. Make the following load combinations and check against the allowable values for each case
Total Deflection(1 + 2)(ΔDL + ΔPT + 0.3 ΔLL ) + 0.7 ΔLL < span/240This is on the premise of sustained load being 0.3 time the design live load. It is for visual effects; Provide camber to reduce value, where needed and practical
Immediate deflection from live loadΔimmediate = 1.00ΔL < span/480This check is applicable, where non-structural members are likely to be damaged. Otherwise, span/240 applies
Presence of members likely to be damaged from sustained deflection (1+ 2)(0.3 ΔLL ) + 0.7 ΔLL < span/360
STEP 7Deflection Check
Steps in strength checkLoad combinations
Determination of hyperstatic actionsCalculation of design moments (Mu)Calculate capacity/rebar for design moment MuCheck for punching shearCheck/detail for unbalanced moment at support
Load combinationsU1 = 1.2DL + 1.6LL + 1.0HYPU2 = 1.4DL + 1.0HYPwhere, HYP is moment due to hyperstatic actions from prestressing
Determination of Hyperstatic actionsDirect Method – based on reactions from balanced loadsIndirect Method – Using primary and post-tensioningmoments
STEP 8Strength Check
Determination of Hyperstatic actionsDirect Method – based on reactions from balanced loads
STEP 8Strength Check
A comment on capacity versus demandPost-tensioned members possess both a positive
and negative moment capacity along the member length
Rebar needs to be added, where capacity falls short of demand
First, find the capacity and compare it with demand
STEP 8Strength Check
The figure below shows the forces on a PT member.In calculating the force from PT tendons, use eitherthe ACI 318 or the following simplified procedure, based on parametric study of common building structures can be used for slabs
STEP 8Strength Check
f’c ≥ 28 MPa; P/A ≤ 1.7 MPac/dt ≤ 0.375 ; dt is distance from compressionfiber to farthest tension rebar Tendon Length ≤ 38 m for single end stressing;if length ≤ 76 m double end stressingfps is conservatively 1480 MPa if span is less than 10 m fps is conservatively 1340 MPa if span is greaterthan 10 m
Check for adequate ductilityDuctility is deemed adequate, if c/dt <= 0.345 dtThis condition guarantees that steel will yield, before concrete in compression crushes.
STEP 8Strength Check
Verify adequacy (detail) of the design fortransfer of unbalanced moment at supports
Unbalanced moment (Mc)is defined as the difference between the design moments on the opposite sides of a column support. This is the moment that is resisted by the support.The reinforcement associated with the transfer of unbalanced moment must be placed over anarrow band at the support (next slide) In most cases, this provision leads to a “detailing”requirement, as opposed to added rebar, sincethe reinforcement for slab design is in excess of that needed for transfer of unbalanced moment.
STEP 8Strength Check
LINECENTER-
SLAB/BEAM LINECOLUMN
M
MOMENTS
c
STEP 8Strength Check
Transfer of unbalanced moment
Place the reinforcement within the narrow band identified as rebar strip
FOR THE EVALUATION OF PUNCHING SHEAR STRESSESILLUSTRATION OF CRITICAL SURFACE
D108/SLID
ES/060591 Vu
COLUMN REGIONPUNCHED OUT
TWO-WAY SLAB
CRITICAL SURFACE
SHEAR STRESSDUE TO Vu
M uDUE TOSHEAR STRESS
kMu
Punching Shear Design
Definition based on ACI 318
STEP 9Check for Transfer of Prestressing
At stressing: Tendon has its maximum force;
Concrete is at its weakest strength; and
Live load to counteract prestressing is absent
Hence the member is likely to experience stresses more severe than when in service
STEP 9Check for Transfer of Prestressing
At stressing check extreme fiber stresses
Add rebar when “representative”(hypothetical) tension stresses exceeda thresholdDo not exceed “representative”hypothetical compressive stresses. Waituntil concrete gains adequate strength
Local failure at stressingLocal failure at stressing
STEP 9Check for Transfer of Prestressing
Load combination
U = 1.00*Selfweight + 1.15*PT
Allowable stresses
Tension 0.25√f’ci
Compression 0.60f’ci
If tension exceeds, provide rebar in tensile zone to resist N
As = N / (0.5 fy)
If compression exceeds, wait until concrete gains adequate strength
Position of rebar
STEP 10Detailing
STAGGER
SEE PLANEQ.
MID-SPAN
STA
GG
ER
DROP CAP
COLUMN
SUPPORT
EQ. EQ.EQ.
SUPPORT TYP.TOP REBAR AT
SUPPORT
EQ.
WALL
EQ.
SUPPORT LINE
POST-TENSIONED
COLUMN
DROP
Lc/6
L
Lc/3Lc
SLAB
Lc/6
*
d
BOTTOM
PLAN
ELEVATION
Thank you for listening.