    Dynamic Voltage Restorers with

    Three Level Inverter1Venkata Ravindra Reddy Putti and

    2K. Veeresham

    ABSTRACT

    This paper presents the application of dynamic voltage restorers (DVR) with three level inverter on power

    distribution systems for mitigation of voltage sags/swells at critical loads. DVR is one of the compensating types

    of custom power devices. An adequate modeling and simulation of DVR, including controls in MATLAB, show

    the flexibility and easiness of the MATLAB environment in studying and understanding such compensating

    devices. In this paper, it is demonstrated that this device can tightly regulate the voltage at the load terminal

    against imbalance or harmonic in the source side. Extensive simulation results are included to illustrate the

    operating principles of a DVR. The author presents results with balanced, unbalanced and nonlinear loads based

    on dq method.

    Keywords : DVR, Three Level Inverter, DQ-Model And Power Control.

    1. INTRODUCTIONModem power systems are complex networks, where hundreds of generating stations and thousands of loadcenters are interconnected through long power transmission and distribution networks

    [1]. The main concern of

    consumers is the quality and reliability of power supplies at various load centers where they are located at. Even

    though the power generation in most well-developed countries is fairly reliable, the quality of the supply is not

    so reliable. Power quality is obtaining increasing attention by the utilities, as well as by both industrial and

    commercial electrical consumers. For higher power sensitive loads where the energy storage capabilities of

    uninterruptible power supplies (UPS) become very costly, the dynamic voltage restorer (DVR) shows promise

    in providing a more cost effective solution[1, 8]

    . A DVR is a power-electronic controller that can protect

    sensitive loads from disturbances in the supply system. It is connected in series with a distribution feeder and is

    capable of generating or absorbing real and reactive power at its ac terminals. The basic principle of a DVR is

    simple: by inserting a voltage of required magnitude and frequency, the DVR can restore the load-side voltage

  • 7/28/2019 1 VRR Puthi 564 Research Article Mar 2012

    2/14

  • 7/28/2019 1 VRR Puthi 564 Research Article Mar 2012

    3/14

    VRR Puthi et al/ VSRD International Journal of Electrical, Electronics & Comm. Engg. Vol. 2 (3), 2012

    Page 102 of 113

    phase converter with energy storage system and control circuit[8]

    . The amplitudes of the three injected phase

    voltages are controlled such as to eliminate any detrimental effects of a bus fault to the load voltage VL(t). This

    means that any differential voltage caused by transient disturbances in the ac feeder will be compensated by an

    equivalent voltage generated by the converter and injected on the medium voltage level through the booster

    transformer.

    The DVR works independently of the type of fault or any event that happens in the system, provided that the

    whole system remains connected to the supply grid, i.e. the line breaker does not trip. For most practical cases, a

    more economical design can be achieved by only compensating the positive- and negative sequence components

    of the voltage disturbance seen at the input of the DVR. This option is reasonable because for a typical

    distribution bus configuration, the zero sequence part of a disturbance will not pass through the step down

    transformers because of infinite impedance for this component.

    For most of the time the DVR has, virtually, "nothing to do," except monitoring the bus voltage. This means it

    does not inject any voltage (Vinj = 0) independent of the load current. Therefore, it is suggested to particularly

    focus on the losses of a DVR during normal operation. Two specific features addressing this loss issue have

    been implemented in its design, which are a transformer design with low impedance and the semiconductor

    devices used for switching. An equivalent circuit diagram of the DVR and the principle of series injection for

    sag compensation are depicted in Fig. 2 and phasor diagram is shown in Fig.3.

    Fig. 2: Equivalent Circuit Diagram

    Fig. 3 : Phasor Diagram

  • 7/28/2019 1 VRR Puthi 564 Research Article Mar 2012

    4/14

    VRR Puthi et al/ VSRD International Journal of Electrical, Electronics & Comm. Engg. Vol. 2 (3), 2012

    Page 103 of 113

    2. OPERATION OF DVRIn normal conditions, the DVR operates in stand-by mode. However, during disturbances, nominal system

    voltage will be compared to the voltage variation. This is to get the differential voltage that should be injected

    by the DVR in order to maintain supply voltage to the load within limits. The amplitude and phase angle of the

    injected voltages are variable, thereby allowing control of the real and reactive power exchange between the

    DVR and the distribution system. The DC input terminal of a DVR is connected to an energy storage device of

    appropriate capacity. As mentioned, the reactive power exchange between the DVR and the distribution system

    is internally generated by the DVR without AC passive reactive components. The real power exchanged at the

    DVR output ac terminals is provided by the DVR input DC terminal by an external energy source or energy

    storage system.

    Also, there is a resemblance in the technical approach to DVRs to that of providing low voltage ride-through

    (LVRT) capability in wind turbine generators. The dynamic response characteristics, particularly for line

    supplied DVRs are similar to LVRT-mitigated turbines. Moreover, since the device is connected in series, there

    are conduction losses, which can be minimized by using Integrated Gate-Commutated Thyristor (IGCT) or GTO

    technology in the inverters.

    3. MODELLING OF DVRPower quality has a significant influence on high-technology equipments related to communication, advanced

    control, automation, precise manufacturing technique and on-line service. For example, voltage sag can have a

    bad influence on the products of semiconductor fabrication with considerable financial losses. Power quality

    problems include transients, sags, interruptions and other distortions to the sinusoidal waveform. One of the

    most important power quality issues is voltage sag that is a sudden short duration reduction in voltage

    magnitude between 10 and 90% compared to nominal voltage. Voltage sag is deemed as a momentary decrease

    in the rms voltage, with duration ranging from half a cycle up to one minute. Deep voltage sags, even of

    relatively short duration, can have significant costs because of the proliferation of voltage-sensitive computer-

    based and variable speed drive loads. The fraction of load that is sensitive to low voltage is expected to grow

    rapidly in the coming decades. Studies have shown that transmission faults, while relatively rare, can cause

    widespread sags that may constitute a major source of process interruptions for very long distances from the

    faulted point. Distribution faults are considerably more common but the resulting sags are more limited in

    geographic extent. The majority of voltage sags are within 40%of the nominal voltage. Therefore, by designing

    drives and other critical loads capable of riding through sags with magnitude of up to 40%, interruption of

    processes can be reduced significantly. The DVR can correct sags resulting from faults in either the transmission

    or the distribution system.

    This paper presents modelling and analysis of a DVR with 3-level inverter and sinusoidal pulse width

    modulation (SPWM) based controller by using the Matlab / Simulink. The proposed control scheme is simple to

    design and allows flexibility in cost or robustness constraints. In addition, the performance of the designed DVR

    is examined under different sag conditions.

    The voltage generated by power stations has a sinusoidal waveform with a constant frequency. Any disturbances

  • 7/28/2019 1 VRR Puthi 564 Research Article Mar 2012

    5/14

    VRR Puthi et al/ VSRD International Journal of Electrical, Electronics & Comm. Engg. Vol. 2 (3), 2012

    Page 104 of 113

    to voltage waveform can result in problems related with the operation of electrical and electronic devices. Users

    need constant sine wave shape, constant frequency and symmetrical voltage with a constant rms value to

    continue the production. This increasing interest to improve overall efficiency and eliminate variations in the

    industry have resulted more complex instruments that are sensitive to voltage disturbances. The typical power

    quality disturbances are voltage sags, voltage swells, interruptions, phase shifts, harmonics and transients.

    Among the disturbances, voltage sag is considered the most severe since the sensitive loads are very susceptible

    to temporary changes in the voltage.

    Voltage sag (dip) is a short duration reduction in voltage magnitude between 10% to 90% compared to nominal

    voltage from half a cycle to a few seconds[4]

    . The characterization of voltage sags is related with the magnitude

    of remaining voltage during sag and duration of sag[5]

    . The magnitude has more influence than the duration on

    the system. Voltage sags are generally within 40% of the nominal voltage in industry. They can cause damaged

    product, lost production, restarting expenses and danger of breakdown. Motor starting, transformer energizing,

    earth faults and short circuit faults will cause short duration increase in current and this will cause voltage sagson the line.

    The wide area solution is required to mitigate voltage sags and improve power quality. One new approach is

    using a DVR[1, 8]

    . The basic operation principle is detecting the voltage sag and injecting the missing voltage in

    series to the bus as shown in Fig.1. DVR has become a cost effective solution for the protection of sensitive

    loads from voltage sags. Unlike UPS, the DVR is specifically designed for large loads ranging from a few MVA

    up to 50MVA or higher[5]

    . The DVR is fast, flexible and efficient solution to voltage sag problems[4, 8]

    .

    4. MODELLING MULTILEVEL INVERTERThe variable output voltage of the inverter is achieved by voltage source inverter (VSI). Solid-state

    semiconductor devices with turn off capability are used in inverter circuits. A VSI is energized by a stiff DC

    voltage supply of low impedance at the input. The output voltage is independent of load current. In VSIs, the

    values of output voltage variations are relatively low due to capacitor[5]

    . It is difficult to limit current because of

    the capacitor. The three phase Pulse Width Modulation (PWM) VSI is most popular and common inverter type

    and it will be used in this study[4]

    .

    In general, increasing the switching frequency in voltage source inverters (VSI) leads to the better output

    voltage / current waveforms. Harmonic reduction in controlling a VSI with variable amplitude and frequency of

    the output voltage is of importance and thus the conventional inverters which are referred to as two-level

    inverters have required increased switching frequency along with various PWM switching strategies. In the case

    of high power / high voltage applications, however, the two-level inverters have some limitations to operate at

    high frequency mainly due to switching losses and constriction of device rating itself. Moreover, the

    semiconductor switching devices should be used in such a manner as problematic series / parallel combinations

    to obtain capability of handling high power. Nowadays the use of multilevel approach is believed to be

    promising alternative in such a very high power conversion processing system. Advantages of this multilevel

    approach include good power quality, good electromagnetic compatibility (EMC), low switching losses, and

    high voltage capability.

  • 7/28/2019 1 VRR Puthi 564 Research Article Mar 2012

    6/14

    VRR Puthi et al/ VSRD International Journal of Electrical, Electronics & Comm. Engg. Vol. 2 (3), 2012

    Page 105 of 113

    5. MULTILEVEL CONCEPTRecent advances in power electronics have made the multilevel concept practical. In fact, the concept is so

    advantageous that several major drives manufacturers have obtained recent patents on multilevel power

    converters and associated switching techniques. It is evident that the multilevel concept will be a prominent

    choice for power electronic systems in future years, especially for medium-voltage operation. Multi-level

    inverters arethe modification of basic bridge inverters. They arenormally connected in series to form stacks of

    level.

    The topological structure of multilevel inverter must cope with the following points.

    It should have less switching devices as far as possible. It should be capable of enduring very high input voltage such as HVDC transmission for high power

    applications.

    Each switching device should have lower switching frequency owing to multilevel approach.It is a fact that, until today, multilevel topologies are the best alternative to implement low-frequency based

    inverters with low output voltage distortion. This chapter makes a review about most common multilevel

    topologies and shows which ones are more suitable to implement inverters for SARES.

    6. THE MULTILEVEL CONCEPT AND NOTATIONA multilevel inverter can be defined as a device that is capable to produce a stepped waveform. The generalized

    stepped waveform is shown in Fig. 4.

    Fig. 4 : Multilevel Concept

    Usually, and also in this work, the follow definitions apply:

  • 7/28/2019 1 VRR Puthi 564 Research Article Mar 2012

    7/14

    VRR Puthi et al/ VSRD International Journal of Electrical, Electronics & Comm. Engg. Vol. 2 (3), 2012

    Page 106 of 113

    p:number of steps in a quarter-cycle;

    2*p + 1: number of levels of a converter;

    4*p:number of steps of a converter.

    7. QUARTER-WAVE SYMMETRIC MULTILEVEL WAVEFORMThe optimized harmonic stepped waveform is assumed to be the quarter-wave Symmetric. The first half cycle of

    the quarter-wave symmetric waveform is depicted in Fig. 5.

    Fig. 5 : First Half Cycle Of The Quarter-Wave Symmetric Waveform

    The output voltage level is zero from t = 0 to t = 1. At t = 1, the output voltage level is changed from

    zero to +V1, and from +V1 to +(V1+V2) at t = 2. The process will be repeated until t = /2, and the output

    voltage level becomes +V1 +V2++V(S-1)+VS. Then, in the second quarter, the level of output voltage will be

    decreased to +V1 +V2++V(S-1) at t = -S. The process will be repeated until t = -1 and output

    voltage becomes zero again. In the second half of the waveform, the process will be repeated all of previous

    steps except the amplitude of the dc sources change from positive to negative. The next period will then repeat

    the same cycle.

    8. FOURIER SERIES ANALYSISThe Fourier series coefficient are given by

  • 7/28/2019 1 VRR Puthi 564 Research Article Mar 2012

    8/14

    VRR Puthi et al/ VSRD International Journal of Electrical, Electronics & Comm. Engg. Vol. 2 (3), 2012

    Page 107 of 113

    For all n, the Fourier series is given as

    Hence,

    Finally, the Fourier series of the quarter-wave symmetric parallel connected multilevel waveform is written as

    follows:

    Where, ak is the switching angles, which must satisfy the following condition

    Where, s is the number of H-bridge cells.

    n is odd harmonic order.

    and E is the amplitude of dc voltages.

    9. TOTAL HARMONIC DISTORTION (THD) CALCULATIONAs introduced in the first chapter, the total harmonics distortion (THD) is mathematically given by

  • 7/28/2019 1 VRR Puthi 564 Research Article Mar 2012

    9/14

    VRR Puthi et al/ VSRD International Journal of Electrical, Electronics & Comm. Engg. Vol. 2 (3), 2012

    Page 108 of 113

    Where H1 is the amplitudes of the fundamental component, whose frequency is w0

    and Hn is the amplitudes of the nth harmonics at frequency nw0

    Therefore, output voltage THD of the presented waveform can be calculated. Theoretically, to get exact THD,

    infinite harmonics need to be calculated. However, it is not possible in practice. Therefore, certain number of

    harmonics will be given. It relies on how precise THD is needed. Usually, n = 63 is reasonably accepted.

    10.ADVANTAGES OF MULTILEVEL VOLTAGESIn general, multilevel power converters can be viewed as voltage synthesizers, in which the high output voltage

    is synthesized from many discrete smaller voltage levels. The main advantages of this approach are summarized

    as follows:

    The voltage capacity of the existing devices can be increased many times without the complications ofstatic and dynamic voltage sharing that occur in series-connected devices.

    Spectral performance of multilevel waveforms is superior to that of their two- level counterparts. Multilevel waveforms naturally limit the problems of large voltage transients that occur due to the

    reflections on cables, which can damage the motor windings and cause other problems.

    The voltage control is achieved by modulating the output voltage waveform within the inverter. Multilevel

    power converters that provide more than two levels of voltage to achieve smoother and less distorted. This paper

    presents a generalized multilevel inverter (3-level inverter) based DVR topology with self voltage balancing.

    The existing multilevel inverter such as diode-clamped multilevel inverter can be used for balancing the load

    voltage through DVR configuration. 3-level diode clamped inverter shown in Fig. 6 and phase (a) switching

    states are shown in table1.

  • 7/28/2019 1 VRR Puthi 564 Research Article Mar 2012

    10/14

  • 7/28/2019 1 VRR Puthi 564 Research Article Mar 2012

    11/14

    VRR Puthi et al/ VSRD International Journal of Electrical, Electronics & Comm. Engg. Vol. 2 (3), 2012

    Page 110 of 113

    Under the aspect of harmonic content reduction, multilevel inverters are of the highest importance. They are

    particularly suitable in high-power applications when the semiconductor devices are not able to operate at high

    switching frequencies. It is also worth noting that, when solid-state switches, which further lower the highest

    possible switching frequencies. The multilevel structures allow raising the power handled in the conversion

    processes, in a very natural and powerful way. The inverter control of three-phase six-step inverter is simple and

    switching loss is low because there are only six switching per cycle of fundamental frequency. Because an

    inverter contains electronic switches, it is possible to control the output voltage as well as optimize the

    harmonics by performing multiple switching within the inverter with the constant dc input voltage Vdc.

    12.SINUSOIDAL PULSE WIDTH MODULATION (SPWM)In sinusoidal PWM instead of maintaining the width of all pulses the same as in the case of multiple PWM, the

    width of each is varied in proportion to the amplitude of a sine wave evaluated at the same pulse. The distortion

    is reduced significantly compared to multiple PWM (Figure-7). The dq based controller of DVR with 3-level

    inverter is shown in Fig. 8.

    Fig. 7 : Sinusoidal Pulse Width Modulation

  • 7/28/2019 1 VRR Puthi 564 Research Article Mar 2012

    12/14

    VRR Puthi et al/ VSRD International Journal of Electrical, Electronics & Comm. Engg. Vol. 2 (3), 2012

    Page 111 of 113

    Fig. 8 : Control of DVR with 3-level inverter based on DQ method

    13.RESULTSThe performance of the designed DVR is evaluated by using the Matlab / Simulink program as a simulation

    example. The DVR is connected to a 50Hz distribution system with a load of 172 Vph-rms, and non linear load.

    Maximum distribution system having unbalanced load, so in this paper we are discussed about performance of

    DVR with balanced, unbalanced and nonlinear load. Fig. 9 shows the remaining voltage at PCC, injected

    voltage and load voltage at 0.4 and 0.2 voltage sags for balanced load. The sag occurs between 0.1-0.16

    seconds. The sag is mitigated quickly and almost constant load voltage is obtained. And the respective source

    voltage, injected voltage by DVR, Load voltage and load current is shown in Fig. 9. Fig. 10 shows the results for

    unbalanced load and Fig. 11 shows the results for nonlinear load. From these results, proposed control of DVR

    is shown good performance in both transient and steady state operation.

    Fig. 9: DVR Response in Balanced Load

  • 7/28/2019 1 VRR Puthi 564 Research Article Mar 2012

    13/14

    VRR Puthi et al/ VSRD International Journal of Electrical, Electronics & Comm. Engg. Vol. 2 (3), 2012

    Page 112 of 113

    Fig. 10 : DVR Response In Unbalanced Load

    Fig. 11: DVR Response In Non Linear Load

    14.CONCLUSIONThis paper presents a systematic study of a dynamic voltage restorer that can tightly regulate voltage at the load

    terminals against any variation in the supply-side voltage while consuming no real power in the steady state.

    The paper demonstrates the capability of the device through steady-state analysis. A number of options to obtain

    the time-varying DVR reference voltages are proposed. Also, a structure to realize the DVR by 3 level VSIs is

    also discussed. The proposed control of DVR is an economical approach to improve multiline power quality.

    The DVR considered in this paper consists of several algorithms of DVRs which are electrically far apart,

  • 7/28/2019 1 VRR Puthi 564 Research Article Mar 2012

    14/14

    VRR Puthi et al/ VSRD International Journal of Electrical, Electronics & Comm. Engg. Vol. 2 (3), 2012

    Page 113 of 113

    connected to a common dc link. The control scheme for the DVR includes a multi loop feedback control system,

    which is identical for both the voltage compensation and the real-power control. The only difference is the way

    the reference signal is generated, and it depends on the mode of operation. In real-power-flow control mode, the

    reference is generated according to the real-power requirement demanded by the DVR performing the voltage

    restoration. All discussions are supplemented by simulation results using MATLAB. From the studies presented

    in the paper, it can be safely concluded that a DVR is a voltage regulator, voltage restorer, and voltage

    conditionerall in one.

    15.REFERENCES[1] H.P. Tiwari, Sunil Kumar Gupta, Dynamic Voltage Restorer Based on Load Condition, International

    Journal of Innovation, Management and Technology, Vol. 1, No. 1, April 2010

    [2] Mohammed El Gamal Ahmed Lotfy G. E. M. Ali, Firing Approach for Higher Levels of Diode ClampedMulti-Level Inverters, Proceedings of the 14th International Middle East Power Systems Conference

    (MEPCON10), Cairo University, Egypt, December 19-21, 2010, Paper ID 115.

    [3] Paisan Boonchiam and Nadarajah Mithulananthan, Understanding of Dynamic Voltage Restorers ThroughMATLAB Simulation,Int. J. Sc. Tech.,Vol. 11, No. 3, July-September 2006.

    [4] Arindam Ghoshand Gerard Ledwich, Compensation of Distribution System Voltage Using DVR IEEETransactions on Power Delivery, vol. 17, NO. 4, October 2002.

    [5] Arindam Ghosh, Amit Kumar Jindal, and Avinash Joshi, Design of a Capacitor-Supported DynamicVoltage Restorer (DVR) for Unbalanced and Distorted Loads,IEEE Transactions on Power Delivery, vol.

    19, NO. 1, January 2004.

    [6] John Godsk Nielsen, Michael Newman, Hans Nielsen, and Frede Blaabjerg, Control and Testing of aDynamic Voltage Restorer (DVR) at Medium Voltage Level, IEEE Transactions on Power Electronics,

    vol. 19, NO. 3, MAY 2004.