PRIMARY SUBSTATIONS
Use: company
2
Main content
• HV network scheme
• Standardised primary substation
• HV section: AIS and Hybrid module
• MV section: Standard and Container section
• Neutral earthing system
Use: company
3
Transmission
Substation
Primary Substation
TRANSMISSION NETWORK
Transmission
Substation
Enel Distribuzione – Endesa LATAM Workshop
The HV network
Use: company
4
HV SECTION SCHEME
• Simple busbar system with
disconnector
• Two line poles (other lines
can be added)
• Two transformer poles
16 - 25 - 40 or 63 MVA
(other transformers can be
added)
MV SECTION SCHEME
• Simple busbar system with bus-tie CB
• Two transformer poles• Emergency supply from
the other transformer• Up to 20 line poles
(including auxiliary services)
HV Busbar
HV/MV Transformers
HV Line
Neutral Earthing System
MV Busbar Bus-tie CB
MV Lines
Disconnector
Primary Substations
Enel Distribuzione standard (H) scheme
Use: company
5
MV section
HV lineHV line
Neutral earthing system
HV/MV transformers
HV section
System
connected online
to the Network
Operating
Centers
By means of the remote control system:• switches position can be known;
• main electrical parameters can be measured;• closing and opening commands can be sent.
2000 Primary Substations:
all remotely controlled
Primary Substations
Remote Control System
Use: company
6
HV line
HV busbar
CVT
CT
HV busbar
Disconnector
Disconnector
Circuit Breaker
Earthing Switch
Disconnector
CT
Circuit Breaker
Surge Arrester
Transformer
Primary Substations
HV line bay and transformer bay
Use: company
7
• Traditional AIS Substation (Air Insulated Switchgear)
• MTS Substation with Hybrid Modules (Mixed Technology Switchgear)
DTB Circuit Breaker Current
Transformer
Hybrid Modules Circuit Breaker Current Transformer Voltage Transformer Disconnector Earthing Switch
GISCircuit BreakerCurrent TransformerVoltage TransformerDisconnectorEarthing SwitchBusbar / Busducts
LTB Circuit Breaker
Primary Substations
HV section – Two main solutionsEnel standard
since 2000
Use: company
8
HV section - layout TRANSFORMER BAY
HV LINE BAY
BUSBAR SYSTEM
CB
DIS
C.
CVT
CT
DIS
C.
DIS
C.
CB
CT
AR
RESTER
32,5 m
21 m
700 m2
Primary Substations
“Traditional” Standardised Primary Substation
Use: company
9
HV switchboard – HV busbar system
Primary Substations
“Traditional” Standardised Primary Substation
Use: company
10
One bay with 1 circuit breaker and motor driven disconnector and earthing
disconnector.
Three bays with 2 (or 1) circuit breakers (Y2 o Y1), motor driven disconnectors and earthing
disconnectors.
HV compact switchgear, integrated and pre-assembled, SF6 insulated, equipped with bushings for the connection to the HV lines (bare conductors or cables), the HV busbars and the transformers.
Primary Substations
MTS Substation – Hybrid Modules
Use: company
11
Y2
Simplified configuration Traditional HV/MV (H) Scheme
Y2+Y2CB
CB CB
CB
CB
CB
Primary Substations
Standard Schemes with Hybrid Modules
Use: company
12
12 m
21 m
250 m2
Primary Substations
Standard Schemes with Hybrid Modules
Use: company
13
Rated Characteristics, Enel Specs DY105
(Y1). DY106B (Y2) and DY107B (single bay)
• Rated voltage 170 kV
• Rated impulse withstand voltage 650 kV
• Rated power frequency withstand voltage 275 kV
• Rated current 1250 A
• Rated short circuit current 31,5 kA
Primary Substations
Hybrid Main Characteristics
Use: company
14
Primary Substations
Y2 type
Use: company
15
BUSHING
CURRENT
TRANSFORMER
DISCONNECTOR +
EARTHING SWITCH
DRY-TYPE
CABLE TERMINALS
CIRCUIT BREAKER
TraditionalPlug-in/plug-out
Primary Substations
Hybrid Module – Basic Components
Use: company
16
Primary Substations
Hybrid Module – Basic Architecture
Use: company
17
BUSHINGS
CURRENT TRANSFORMERS
DISCONNECTORS
AND EARTHING
SWITCHES
CIRCUIT BREAKERSSPRING
MECHANISM
Primary Substations
Hybrid Module in operation
Use: company
18
Y1 Hybrid Module
Single Bay cable connected
Hybrid Module
Y2 Hybrid Module with
SF6 cable bushings
Y2 Hybrid Module with
SF6 air and cable bushings
Primary Substations
Hybrid Modules solutions
Use: company
19
• reduction of environmental impact and permission easier to obtain (construction under the HV line)
• reduction of necessary space for installation (compact HV switchboard)
• limited civil works
• easily transportable (three pieces per road width)
• fast installation
• reduction of mountings and on-site tests (extended prefabrication with tests on manufacturing site)
• fewer maintenance needs (reduction in component numbers)
• easy maintenance (reduced times for substitution of integrated components)
• higher reliability (active HV parts hermetically protected from the environment)
• total cost reduction
ADVANTAGES
Primary Substations
Standardized Primary Substations with Hybrid Modules
Use: company
20
“Compact” H Primary Substation with Two Y2 Modules
Traditional HV section of a Primary Substation
Primary Substations
Comparison between AIS and MTS HV section
Use: company
21
Single floor
air insulated switchgear
Primary Substations
MV section – Three main solutions
Double floor
air insulated switchgear
Compact
air insulated switchgear
Enel standardsince 2000
Use: company
22
30 m
10 m
Primary Substations
MV section – Traditional solutions (single and double floor)
Use: company
23
Main characteristics:
- Air insulated busbars
- Vacuum circuit breakers
- Withdrawable circuit breakers
- Protections installed on the panels
- Compact size:
Height 1820 mm; Width 750 or 850 mm; Depth 1200 mm
Primary Substations
MV section – Compact switchgear
Rated values: - Rated voltage: 24 kV - Rated Current: 1600 A - Short circuit current: 16 kA- Rated duty cycle: O-0,3s-CO-30s-CO
Use: company
24
MV Container Section
Primary Substations
Extreme modularity and flexibility
• MV Busbar system with bus-tie circuit breakers
• Up to 12 MV lines
• Auxiliary services included
• Protection and control systems integrated “all in one”
• No civil works need, just “plug and play”
Use: company
25
MV Container Section
Primary Substations
Use: company
26
14 m
9 m
MV Container Section
Primary Substations
Use: company
27
MV Container Section in operation
Primary Substations
Use: company
28
• Permission easier to be obtained
• No buildings needed
• Easily transportable
• Fast installation
• MV switchgear preassembled (no mountings on site)
• Simplified maintenance operations
• Enhanced reliability (vacuum CB)
• Reduction of environmental impact (no SF6)
• Cost reduction
MV Container Section – Main advantages
Primary Substations
Use: company
29
Direct connection Connection by means of Earthing
Transformer
The Neutral Earthing System
Primary Substations