USER MANUAL FOR 1 PHASE DIN RAIL METER Doc.No.4D060283 Rev.0 1 Phase DIN Rail Meter L&T Electrical & Automation

1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

  • Upload
    others

  • View
    10

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

USER MANUAL FOR 1 PHASE DIN RAIL METER

Doc.No.4D060283 Rev.0

1 Phase DIN Rail Meter

L&T Electrical & Automation

Page 2: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

LCD display

Push-to-Push consumption, Daily, Weekly, Monthly consumption.

Terminal covers to avoid direct contact of the supply terminals along with sealing provision.

Data transfer through optical communication*.

Easy mounting on DIN rail with locking.

Energy recording at current as low as 0.02A.

* Note:

1) Additional “Wi-Fi Module” is available to get data over Wi-Fi (to be purchased separately).

2) Mobile Application is also available for Energy Monitoring for iOS, Android, Windows & Symbian

Operating systems.

3) RS485 Module is available.

Meter Type 1P2W Direct Whole current Operated, Direct Connected, Unidirectional

Voltage Rating 240 V (Phase to Neutral) Current Rating 5A (Ibasic), 40A (Imax) Starting Current 0.4% Ibasic

Accuracy Class 1.0 (5% to 800% Ibasic) Operating Voltage 168V to 288V Current Display Range 0.05A onwards

Operating Frequency 50Hz ±5%

Meter Constant 3200 Imp/kWh

Measurement Category Category III

Standard Compliance IEC 62052-11, IEC 62053-21, IP20

Enclosure Polycarbonate

Dimension 36mm x 83mm x 66.5mm (Tolerances Apply)

Weight 132 grams(Approximate)

Communication Compatible with Wi-Fi & RS485 communication

Page 2 of 8

FEATURES

TECHNICAL SPECIFICATIONS

Terminal sealing provision

Terminal cover Display

Pulse LED

Push button

Optical

communication

Terminal sealing provision

FEATURES & TECHNICAL SPECIFICATIONS

Page 3: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

1 Phase Load

3

Phase

Neutral

M0 M1

L1

Parameter scrolling: The default display mode is Auto Scroll Mode in which the parameters scroll

automatically. On pressing key, the meter display goes to manual mode. If key press doesn’t happen

for approximately 30 seconds, meter display returns to default mode i.e. Auto Scroll mode.

Push-to-push consumption: The push button is also used for measuring Push-to-Push kWh

consumption. Follow the below steps to measure the Push-to-Push kWh consumption:

a) Scroll through the parameters until Display No.11 (Refer Display Parameters Table 2) is displayed.

b) When Display No.11 is displayed; press and hold the push button, it resets to zero.

c) Energy recording starts in Display No.11.

d) Check Display No.12 to get the energy consumed value between the previous start-&-stop

operations.

Page 3 of 8

2

1

WIRING DIAGRAM

DISPLAY

WIRING DIAGRAM, OPERATING INSTRUCTIONS & DISPLAY

OPERATING INSTRUCTIONS

Page 4: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

DISPLAY PARAMETERS

Table 1.

DISPLAY EXPLANATION

Sl. No. Parameter Display Legend

1 Quantities measured

2 Energy, Voltage, Amps, Power kWh, V, A, kW

3

Different consumptions

Present day D (Flashing)

Present week W (Flashing)

Present month M (Flashing)

Previous day D

Previous week W

Previous month M

Push-to-Push kWh consumption(present) T (Flashing)

Push-to-Push kWh consumption(previous) T

Table 2.

No.

Parameter LCD Pattern

No. Parameter LCD Pattern

1 Cumulative Forward

kWh

2 Present kW

3 Current

4 Voltage

5

Current Month consumption

'M' will be flashing at the rate of 0.5sec

6 Last month

consumption

7

Current Week consumption

'W' will be flashing at the rate of 0.5sec

8 Last Week

consumption

9

Current DAY consumption

'D' will be flashing at the rate of 0.5sec

10 Last DAY consumption

11

Current Push-to-Push consumption

'T' will be flashing at the rate of 0.5sec

12 Last Push-to-Push

consumption

Page 4 of 8

DISPLAY PARAMETERS

Page 5: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

DISPLAY PARAMETERS & METER SETTING

No. Parameter LCD Pattern

No. Parameter LCD Pattern

13

Meter Mode of communication Configuration

display

14 1st Byte of IP Address of

Wi-Fi Module *

15 2nd Byte of IP

Address of Wi-Fi Module *

16 3rd Byte of IP Address of

Wi-Fi Module *

17 4th Byte of IP

Address of Wi-Fi Module *

18 Meter Modbus

Communication Slave ID **

19 Meter Modbus

Communication Baud rate **

20

Meter Modbus Communication Parity **

Note:

* Parameters available only in WiFi mode of Communication.

** Parameters available only in MODBUS mode of Communication.

Following settings need to be done to configure the DIN meter to WiFi or MODBUS mode: • Connect the meter to the power supply and manually scroll till parameter "Config" is displayed. • Press and hold the push button for approximately 5 sec, meter will display “Yi-Fi”, “ndbus”,”IEC”and “ESC”on each scroll. • Press and hold the push button for approximately 5 sec after the required mode of communication. Select “Yi-Fi” for Wi-Fi mode to use with Wi-Fi module and “ndbus” for MODBUS mode to use with RS-485 module. • Meter will restart in selected mode of communication. • Escape is to exit from the configuration mode. • 30 Second timeout is given from configuration mode to the Auto scroll mode.

Page 5 of 8

CONFIGURING COMMUNICATION:

Page 6: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

METER SETTING & MEMORY MAP

Table 3.

Address Parameters Words MF

Read only Parameters ( Function Code 4)

Instantaneous Parameters

30001 R Phase Voltage 2 0.01

30007 R Phase Current 2 0.001

30013 Average Voltage 2 0.01

30015 Average Current 2 0.001

30017 Total Active Power 2 0.0001

30023 Total Power Factor 2 0.001

NOTE: Format for above addresses 7 to 11, 15 to 23

1st word – (MSW) 0x0000 if value positive 0xFFFF if value negative

2nd word – value itself, if positive as indicated by 1st word

2’s complement of value, if negative as indicated by 1st word

30025 Line Frequency 2 0.01

30027 Cumulative energy – forward kWh 2 0.01

30029 Previous Day Consumption-kWh 2 0.01

30031 PresentDay Consumption-kWh 2 0.01

30033 Previous Week Consumption-kWh 2 0.01

30035 Present Week Consumption-kWh 2 0.01

30037 Previous Month Consumption-kWh 2 0.01

30039 Present Month Consumption-kWh 2 0.01

30041 Current Push-to-Push Consumption-kWh 2 0.01

30043 Backup Push-to-Push Consumption-kWh 2 0.01

LS DATA -Last 4 IP kWh

30049 IMPKWH Previous Integration 2 0.01

30051 IMPKWH Previous to Previous Integration 2 0.01

30053 IMPKWH Previous to Previous to Previous Integration 2 0.01

30055 IMPKWH Previous to Previous to Previous to Previous

Integration 2 0.01

30057 Meter Serial Number

Format For Above :ASCII Value 6 1

Read Write Parameters(Read supported by function

code 3)(Supported by function code 6 and 16)

Communication Parameters

42385 Meter Address 1 1

42386

Baud Rate

Format : 3 -> 1200 4 -> 2400 5 -> 4800 6 -> 9600

baud rate

1 1

42387

Parity

Format of Address 2387:

0 -> None Parity 1 -> Odd Parity 2 -> Even Parity

1 1

42388 Push-to-Push Consumption Reset Command 1 1

Page 6 of 8

Memory Map

g

Page 7: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

All dimensions are in mm

* For terminal cover sealing, wire used should be of maximum 0.8mm diameter.

Page 7 of 8

DIMENSIONS

INSTALLATION PROCEDURE

PULL** PRESS

STEP 1 STEP 2 STEP 3 STEP 4

UN-INSTALLATION PROCEDURE

PULL **

Note:

1) Before installing & uninstalling the meter make sure that the

Power supply to meter is switched off.

2) Remove all the connections to the meter before uninstalling.

3) ** PULL the locking clips with the help of a screwdriver by

inserting it in slot provided in the clip.

Page 8: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

WARRANTY & DISCLAIMER

Larsen & Toubro warrants that 1 PHASE DIN RAIL ENERGY METER is free from defects in workmanship and

material. Larsen & Toubro’s obligation under this warranty shall be for a period of 18 months from the date of

sale subject to the following terms and conditions provided the notice of defects and satisfactory proof thereof

is given to Larsen & Toubro by its Customer within the warranty period.

1. Larsen & Toubro shall provide only repairs for the sold item. 2. Defective parts shall be serviced or replaced by Larsen & Toubro. This warranty does not cover any defect in the product caused by accident, misuse, mishandling (includes improper electrical, mechanical installation), tamper, neglect, alteration/modification or substitution of any of the components or parts, or any attempt of internal adjustment by unauthorized service personnel. For applicability of warranty Larsen & Toubro shall be the sole judge. Under no circumstance shall Larsen & Toubro be liable for any consequential or resulting injury or for loss, damage or expense directly or indirectly from the use of this product. The foregoing warranty is in lieu of all other warranties, expressed or implied, and is the sole and exclusive

remedy for any claim arising from any defect in the product.

Sufficient care is taken to provide all information regarding the product but Larsen & Toubro Electrical and

Automation does not claim any responsibility for the damage caused by using the product directly or indirectly.

In case of customer complaint please contact

Customer Interaction Centre (CIC)

Toll Free: 1800 233 5858, 1800 200 5858

Telephone: 022 6774 5858

Email: [email protected]

Electrical Standard Products

L&T Business Park, Tower ‘B’ / 3rd Floor

Saki Vihar Road, Powai, Mumbai 400 072

Website: www.Lntebg.com

WD4000DR06A – 1P

Page 8 of 8

DISCLAIMER

WARRANTY

L&T Electrical & Automation

Page 9: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

USER MANUAL 3 PHASE DIN RAIL ENERGY METER

L&T Electrical & Automation Doc.No.4D060284 Rev.0

3 Phase DIN Rail Meter

Page 10: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Page 2 of 8

Bright LCD display

Push to Push consumption

Terminal covers to avoid direct contact of the supply terminals along with sealing provision.

* Data transfer through “Wi-Fi” and “MODBUS”.

Easy mounting on DIN rail with locking.

Energy recording at current as low as 0.04A.

Reverse current indication.

* Wi-Fi and RS485 modules are available as an add–on and should be purchased separately to Communicate with meter.

Meter Type 3 Phase 4 Wire Whole current Operated, unidirectional

Accuracy Class 1.0

Voltage Rating 3 x 240V (Phase to Neutral)

Current Rating 10A (Ibasic), 60A (Imax)

Operating Voltage 168V to 288V

Starting Current 0.4% Ibasic

Operating Frequency 50Hz± 5%

Meter Constant 450 impulses/kWh

Measurement Category Category III

Standards Applicable IEC 62052-11, IEC 62053-21, IP50

Enclosure Polycarbonate

Dimension 125mm x 83mm x 66mm

Weight 460g

Communication Compatible with Wi-Fi and RS485 communication

Sealing

provision Terminal

cover Display

Pulse rate

LED

Push button

Optical

communication

FEATURES

TECHNICAL SPECIFICATIONS

Page 11: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Page 3 of 8

L1 L2 L3

Y-Phase 3 Phase

supply

Parameter scrolling:

Manual Scroll: Press and release the push button to view the next parameter. Meter will continue to be

in Manual scroll mode once push button is pressed and will change over to Auto scroll

mode if the Push button is left inactive for 5 minutes.

Auto Scroll : In Auto scroll mode, each parameter will be displayed for 6 seconds.

Push to push consumption: The push button is also used for measuring Push to Push kWh consumption.

Follow the below steps to measure the Push to Push consumption:

a) Scroll through the parameters until the push to push consumption (P0) is displayed.

b) When P0 is displayed press and hold the push button, it resets to zero.

c) Energy recording starts in P0 display.

d) To stop the Push to Push consumption press and hold the push button in P0 display.

e) Check the display parameter P1 to get the energy consumed value between the start and stop

operations.

CONNECTION DIAGRAM

OPERATING INSTRUCTIONS

DISPLAY

B-Phase

Neutral

M1 M2 M3 M0

LOAD

R-Phase

Page 12: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Page 4 of 8

DISPLAY EXPLANATION

Sl # Parameter Display Legend

1 Value of quantity measure

2 Units of Energy, Voltage, Current and Power

kWh, V, A, kW

3 Maximum demand

4 Presence of R, Y and B phase voltages and blinks when current flows to the load.

5

Different consumptions

Present day energy Pd

Present week energy P7

Present month energy Pb

Previous day energy Ld

Previous week energy L7

Previous month energy Lb

Cumulative energy C

Instantaneous power Pr

6 Reverse current indication (Rev.) Rev. is displayed when connections to M1 and L1 or M2 and L2 or M3 and L3 are interchanged

No. Parameter LCD Pattern

1 Voltage reading R phase

2 Voltage reading Y phase

3 Voltage reading B phase

DISPLAY PARAMETERS

6

3

2 1

4

5

DISPLAY

Page 13: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Page 5 of 8

4 Current reading R phase

5 Current reading Y phase

6 Current reading B phase

7 Frequency

8 Power factor

9 Instantaneous Active Power

10 Instantaneous Reactive Power

11 Instantaneous Apparent Power

12 Present month Demand

13 Previous month Demand

14 Cumulative energy (kWh)

15 Present Push to push consumption

16 Push to Push consumption

17 Present day consumption (kWh)

18 Previous day consumption (kWh)

19 Present week consumption (kWh)

20 Previous week consumption (kWh)

21 Present month consumption (kWh)

Page 14: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Page 6 of 8

22 Previous month consumption (kWh)

23 First byte of IP address *

24 Second byte of IP address *

25 Third byte of IP address *

26 Fourth byte of IP address *

27 Slave ID **

28 Baud rate **

29

Parity **

30

Config

31 Indicates change over from manual scroll mode to auto scroll mode

32 Indicates data collection

* Parameters available only in WiFi mode of Communication. ** Parameters available only in MODBUS mode of Communication

Following settings need to be done to configure the DIN meter to WiFi or MODBUS mode:

Connect the meter to the power supply and manually scroll till parameter "Config" is displayed.

Press and hold the push button for 6 sec, meter will display “Yi-Fi”, “ndbus”,”IEC”and “ESC”on

each scroll.

Press and hold the push button for 6 sec after the required mode of communication. Select “Yi-Fi”

for Wi-Fi mode to use with Wi-Fi module and “ndbus” for MODBUS mode to use with RS-485

module.

Meter will restart in selected mode of communication.

After entering into Config menu, if the key is not pressed for 1 min then meter will resume to

Config display mode.

After entering into Config Menu, if key is not pressed for 5 min then meter will resume to auto

scroll mode.

CONFIGURING COMMUNICATION

Page 15: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Page 7 of 8

PULL PULL

PULL*** PULL***

All dimensions are in mm

* For terminal cover sealing, wire used should be of maximum 0.8mm diameter

Warning: Terminal cover has to be used for operator protection. As soon as the connections are

made the terminals has to be covered by terminal cover.

*** Note:

1) Before installing and uninstalling the meter make sure that the Power supply to the meter is switched

off.

2) Remove all the connections to the meter.

3) PULL the locking clips with the help of a screwdriver by inserting it in slot provided in the clip.

DIMENSION

S

INSTALLATION PROCEDURE

PRESS PRESS

STEP 1. STEP 2. STEP 3. STEP 4.

UN-INSTALLATION PROCEDURE

Page 16: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Page 8 of 8

Larsen & Toubro warrants that 3 PHASE DIN RAIL ENERGY METER is free from defects in workmanship and material. Larsen & Toubro obligation under this warranty shall be for a period of 18 months from the date of sale subject to the following terms and conditions provided the notice of defects and satisfactory proof thereof is given to Larsen & Toubro Limited by its Customer within the warranty period. 1. Larsen & Toubro shall provide only repairs for the sold item. 2. Defective parts shall be serviced or replaced by Larsen & Toubro. This warranty does not cover any defect in the product caused by accident, misuse, mishandling (Includes improper electrical, mechanical installation), tamper, neglect, alteration/modification or substitution of any of the components or parts, or any attempt of internal adjustment by unauthorized service personnel. For applicability of warranty Larsen & Toubro shall be the sole judge. Under no circumstance shall Larsen & Toubro be liable for any consequential or resulting injury or for loss, damage or expense directly or indirectly from the use of this product. The foregoing warranty is in lieu of all other warranties, expressed or implied, and is the sole and exclusive remedy for any claim arising from any defect in the product.

Sufficient care is taken to provide all information regarding the product but Larsen & Toubro does not

claim any responsibility for the damage caused by using the product directly or indirectly.

In case of customer complaint please contact

Customer Interaction Centre (CIC)

Toll Free: 1800 233 5858, 1800 200 5858

Telephone: 022 6774 5858

Email: [email protected]

Electrical Standard Products

L&T Business Park, Tower ‘B’ / 3rd Floor

Saki Vihar Road, Powai, Mumbai 400 072

Website: www.Lntebg.com

WD4005DB00A – 3P

WARRANTY

DISCLAIMER

L&T Electrical & Automation

Page 17: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Doc.No.4D060285 Rev.0

USER MANUAL DIN RS485 MODULE

L&T Electrical & Automation

RS485 Module DIN Energy Meter

Module DIN Energy Meter

Module DIN Energy Meter

WiFi Module DIN Energy Meter

MO

Page 18: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Page 2 of 8

DIN RS485 module is used to collect data from L&T make DIN meters through optical interface and

to make it available for the user through RS485 port and modbus protocol. This RS485 module is

compatible with 1 Phase as well as 3 Phase meters.

RS485 port enables a master to communicate with many DIN meters connected in daisy

chain.

Data transfer through modbus protocol.

Terminal cover to avoid direct contact of the supply terminals along with sealing

provision.

Easy mounting on DIN rail with locking.

Voltage rating : 240 V (-30% to +20% AC)

Operating Temperature : -20°C to 70°C

Storage Temperature : -40°C to 85°C

Enclosure : Poly carbonate

Dimension : 36mm x 83mm x 66.5mm

Weight :115 g

Terminal

cover

Power on

LED

Optical

communication

FEATURES

SPECIFICATIONS

Terminal sealing

provision

RS485 connector

Page 19: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Page 3 of 8

Neutral

Phase

Radiated RF field immunity : IEC 61000-4-3

Conducted RF immunity : IEC 61000-4-6

Conducted RF emissions : CISPR 22

Radiated RF Emission : CISPR-22-A

Fast transient burst (2kV) : IEC 61000-4-4

Electrostatic Discharge (±15kV) : IEC 61000-4-2

Surge Immunity Test ( ±4kV) : IEC 61000-4-5

The configuration details to communicate with the module are given below.

Standard RS485 (half duplex)

Baud Rate Selectable (19200, 9600,4800, 2400, 1200)

Parity Selectable ( None,Odd,Even)

Protocol

RS485 interface uses MODBUS Protocol in RTU mode. Communicating with the meter involves sending commands to the meter for reading and writing the particular register. The meter can be addressed with specific user defined meter address (Slave ID) from 1 to 247

CONNECTION DIAGRAM

STANDARDS APPLICABLE

INTERFACE DETAILS

Modbus interface

Page 20: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Page 4 of 8

Address Parameters Words MF

(if no specific format is mentioned, format is HEX)

Read only Parameters ( Supported by Function Code 4) Instantaneous Parameters

30001 R Phase Voltage 2 0.01

30003 Y Phase Voltage 2 0.01

30005 B Phase Voltage 2 0.01

30007 R Phase Current 2 0.001

30009 Y Phase Current 2 0.001

30011 B Phase Current 2 0.001

30013 Average Voltage 2 0.01

30015 Average Current 2 0.001

30017 Total Active Power 2 0.0001

30019 Total Reactive Power 2 0.0001

30021 Total Apparent Power 2 0.0001

30023 Total Power Factor 2 0.001

Format: for above addresses 7 to 11, 15 to 23 1st word – (MSW) 0x0000 if value positive 0xFFFF if value negative 2nd word – value itself, if positive as indicated by 1st word 2’s complement of value, if negative as indicated by 1st word

30025 Line Frequency 2 0.01

30027 Cumulative energy – kWh 2 0.01

30029 Previous Day Consumption-kWh 2 0.01

30031 Present Day Consumption-kWh 2 0.01

30033 Previous Week Consumption-kWh 2 0.01

30035 Present Week Consumption-kWh 2 0.01

30037 Previous Month Consumption-kWh 2 0.01

30039 Present Month Consumption-kWh 2 0.01

30041 Current Push to Push Consumption-kWh 2 0.01

30043 Backup Push to Push Consumption-kWh 2 0.01

30045 Present Month MD-kW 2 0.0001

30047 Previous Month MD-kW 2 0.0001

MEMORY MAP

Page 21: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Page 5 of 8

LS DATA -Last 4 IP kWh

30049 1st Integration period -kWh 2 0.01

30051 2nd Integration period (Previous of 1st integration period )-kWh 2 0.01

30053 3rd Integration period (Previous of 2nd integration period )-kWh 2 0.01

30055 4th Integration period (Previous of 3rd integration period)_kWh 2 0.01

30057 Meter Serial Number Format For Above :ASCII Value

6 1

Settings Parameters (Supported by function code 3,6 and 16)

Communication Parameters

42385 Meter Address 1 1

42386 Baud Rate Format : 3 -> 1200 4 -> 2400 5 -> 4800 6 -> 9600 baud rate

1 1

42387 Parity Format of Address 2387: 0 -> None Parity 1 -> Odd Parity 2 -> Even Parity

1 1

Real time clock

42390 Current Time: Year, Month (Format:YYMM (BCD)) 1

42391 Current Time: Date, Day (Format:DTDY (BCD)) 1

42392 Current Time: Hour, Minute (Format: HHMM (BCD)) 1

42393 Current Time: Second, not used (Format:SSOO (BCD)) 1

RTC Day Indication: 0-Sunday 1-Monday 2-Tuesday 3-Wednesday 4-Thursday 5-Friday 6-Saturday Programming shall be done from 0 to 6

Energy Reset (Supported by function code 6)

42388 Push to Push Consumption Reset Command 1 1

Page 22: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Page 6 of 8

All dimensions are in mm

DIMENSION

S

Page 23: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Page 7 of 8

PULL PULL PULL

PULL

RS485 module should be connected to the left side of the DIN meter (as per the picture shown in un-installation procedure) as it communicates with meter through optical port.

CAUTION!!!: 1) Before installing, uninstalling, connecting the RS485 connector to the module and

disconnecting the RS485 connector from the module make sure that the Power supply to the

module is switched off.

2) Remove all the connections to the module before uninstalling.

3) PULL the locking clips with the help of a screwdriver by inserting it in slot provided in the clip.

`

INSTALLATION PROCEDURE

UN-INSTALLATION PROCEDURE

PRESS

Page 24: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Page 8 of 8

Larsen & Toubro warrants that the RS485s module is free from defects in workmanship and material. Larsen & Toubro obligation under this warranty shall be for a period of 18 months from the date of sale subject to the following terms and conditions provided the notice of defects and satisfactory proof thereof is given to Larsen & Toubro Limited by its Customer within the warranty period. 1. Larsen & Toubro shall provide only repairs for the sold item. 2. Defective parts shall be serviced or replaced by Larsen & Toubro. This warranty does not cover any defect in the product caused by accident, misuse, mishandling (Includes improper electrical, mechanical installation), tamper, neglect, alteration/modification or substitution of any of the components or parts, or any attempt of internal adjustment by unauthorized service personnel. For applicability of warranty Larsen & Toubro shall be the sole judge. Under no circumstance shall Larsen & Toubro be liable for any consequential or resulting injury or for loss, damage or expense directly or indirectly from the use of this product. The foregoing warranty is in lieu of all other warranties, expressed or implied, and is the sole and exclusive remedy for any claim arising from any defect in the product.

Sufficient care is taken to provide all information regarding the product but Larsen & Toubro does

not claim any responsibility for the damage caused by using the product directly or indirectly.

In case of customer complaint please contact

Customer Interaction Centre (CIC)

Toll Free: 1800 233 5858, 1800 200 5858

Telephone: 022 6774 5858

Email: [email protected]

Electrical Standard Products

L&T Business Park, Tower ‘B’ / 3rd Floor

Saki Vihar Road, Powai, Mumbai 400 072

Website: www.Lntebg.com

WD40000000A – RS

WARRANTY

DISCLAIMER

L&T Electrical & Automation

Page 25: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Doc.No.4D060286 Rev.0

USER MANUAL WiFi MODULE

L&T Electrical & Automation

WiFi Module DIN Energy Meter

Page 26: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Page 2 of 8

Wi-Fi is one of the most popular wireless communication standards on the market. WiFi

module is used to collect data from L&T make DIN meters through optical interface and to make it

available for the user through WiFi network. The module operates within the ISM 2.400 – 2.484 GHz

frequency band with IEEE802.11b baseband. This WiFi module is compatible with 1 Phase as well

3 Phase meters. The data can be viewed by the user through home page of the module using a web

browser as well as in the user application.

The modes for Wi-Fi connectivity are as follow:

- Infrastructure mode

- Ad hoc Mode

WiFi module is configured in Infrastructure mode as factory default.

Terminal cover to avoid direct contact of the supply terminals along with sealing

provision.

Easy mounting on DIN rail with locking.

Supported network topologies: Ad-hoc and Infrastructure modes

IEEE 802.11b-compliant RF transceiver

Integrated antenna

Range: up to 100m

Supported connections: Open, WEP64, WEP128, WPA, and WPA2.

FEATURES

Terminal

cover

Power on

LED

Optical

communication

Terminal sealing

provision

Reset Key

Mode Key

Page 27: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Page 3 of 8

Phase

Neutral

Mode key helps to configure the WiFi module to infrastructure or ad-hoc mode by pressing it for

1 second .If the same key is pressed for more than 10sec then the module will be configured to

factory defaults. Reset Key resets the module. Power ON LED gives the indication of the selected

mode. Ad-hoc mode will be indicated by the high pulse rate (i.e. 4 pulse/sec). Infrastructure mode

will be indicated by slow pulse rate (i.e. 3 pulses for 5 sec).

Voltage rating : 240 V (-30% to +20% AC)

Operating Temperature : -10°C to 55°C

Storage Temperature : -20°C to 70°C

Power consumption : < 1W, 1VA in voltage circuits

Frequency : ISM 2.400 – 2.484 GHz

Receiver sensitivity : 85dBm

Number of channels : 13

Enclosure : Poly carbonate

Dimension : 36mm x 83mm x 66.5mm

Weight :115 g

SPECIFICATIONS

CONNECTION DIAGRAM

Page 28: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Page 4 of 8

Radiated RF field immunity : IEC 61000-4-3

Conducted RF immunity : IEC 61000-4-6

Conducted RF emissions : CISPR 22

Radiated RF Emission : CISPR-22-A

Fast transient burst (2kV) : IEC 61000-4-4

Electrostatic Discharge (±15kV): IEC 61000-4-2

Surge Immunity Test ( ±4kV) : IEC 61000-4-5

Infrastructure mode:

Infrastructure mode is one of the two methods of connecting the module to existing WiFi network

present at home or office with Wi-Fi enabled devices such as laptops, Smart phones etc. These

devices are connected to wireless network with the help of Access point (AP).

Setting Up Infrastructure Mode:

Power ON the meter and module. Configure WiFi router (or any smart device that support WiFi

hotspot) with SSID as “MiEnergyWiFi” and security as “Open”. WiFi module joins with the

configured router and can be accessed for installation.

Note the IP address (For eg: ‘192.168.0.103’) that will be displayed on DIN meter. Navigate to the

home page of the module using web browser by using the IP address as URL. Enter into

configuration page by clicking the link available in the home page using username “admin” and

password “lnt”. Select mode of communication as “Infrastructure” in configuration page and also

assign desired SSID to the module. Various types of security such as Open, WEP64, WEP128, WPA,

and WPA2 are supported. Select the desired security settings. Save these details and module will

restart with new settings.

STANDARDS APPLICABLE

FIRST TIME INSTALLATION

Page 29: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Page 5 of 8

Ad-hoc:

Ad-hoc is another mode of connectivity available in Wi-Fi. By using this mode, devices are capable

for communicating directly each other. All devices are connected in peer to peer communication

mode without using any Access point (router/switch) between devices. Note that android OS does

not support ad-hoc mode communication.

Setting up Ad hoc Mode:

Power ON the meter and module. Configure the module in Ad-Hoc mode by pressing the mode key

for more than 1 second. Connect device that supports Ad-hoc communication to the network SSID

“MiEnergyWiFi” broadcasted by the WiFi module. Enter the default IP address “192.168.0.15” in

the device’s web browser to open the WiFi module’s home page.

The default IP address can be changed to desired value in configuration page. User can go to

configuration page as explained in “Infrastructure mode” section.

Page 30: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Page 6 of 8

All dimensions are in mm

DIMENSIONS

Page 31: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Page 7 of 8

PULL

PULL PULL PULL

Wi-Fi module should be connected to the left side of the DIN meter (As per the picture shown in un-installation procedure) as it communicates with meter through optical port.

Note:

1) Before installing & uninstalling the meter make sure that the Power supply to the meter is

switched off.

2) Remove all the connections to the meter before uninstalling.

3) PULL the locking clips with the help of a screwdriver by inserting it in slot provided in the clip.

UN-INSTALLATION PROCEDURE

INSTALLATION PROCEDURE

PRESS

Page 32: 1 Phase DIN Rail Meter. WD4000 1P, 3P DIN Meter...1 Phase Load 3 Phase Neutral M1 M0 L1 OPERATING INSTRUCTIONS Parameter scrolling: The default display mode is Auto Scroll Mode in

Page 8 of 8

Larsen & Toubro warrants that the Wi-Fi module is free from defects in workmanship and material. Larsen & Toubro obligation under this warranty shall be for a period of 1 year from the date of sale subject to the following terms and conditions provided the notice of defects and satisfactory proof thereof is given to Larsen & Toubro Limited by its Customer within the warranty period. 1. Larsen & Toubro shall provide only repairs for the sold item. 2. Defective parts shall be serviced or replaced by Larsen & Toubro. This warranty does not cover any defect in the product caused by accident, misuse, mishandling (Includes improper electrical, mechanical installation), tamper, neglect, alteration/modification or substitution of any of the components or parts, or any attempt of internal adjustment by unauthorized service personnel. For applicability of warranty Larsen & Toubro shall be the sole judge. Under no circumstance shall Larsen & Toubro be liable for any consequential or resulting injury or for loss, damage or expense directly or indirectly from the use of this product. The foregoing warranty is in lieu of all other warranties, expressed or implied, and is the sole and exclusive remedy for any claim arising from any defect in the product.

Sufficient care is taken to provide all information regarding the product but Larsen & Toubro does

not claim any responsibility for the damage caused by using the product directly or indirectly.

In case of customer complaint please contact

Customer Interaction Centre (CIC)

Toll Free: 1800 233 5858, 1800 200 5858

Telephone: 022 6774 5858

Email: [email protected]

Electrical Standard Products

L&T Business Park, Tower ‘B’ / 3rd Floor

Saki Vihar Road, Powai, Mumbai 400 072

Website: www.Lntebg.com

WD40000002A – WF

DISCLAIMER

WARRANTY

L&T Electrical & Automation